You are on page 1of 3

Telecom Battery

UPS Battery

Renewable Energy Battery

Tubular GEL Battery-OPzV Series

10 OPzV1000 (2V1000AH)
Applications
Telecom application (indoor or outdoor BTS)
Solar System
Wind system
Hybrid solution

Design
Positive plate: Tubular plate, adopts multi-component alloy frame
negative plate: special radiated structure
Electrolyte: sulphuric acid fixed as GEL by fumed silica
Separator: special microporous PVC-SiO2 separator
Safety valve: valve with flame arrestor

Terminal

Features

Terminal Model:

9.7

15.7

Unit: mm

Long life: 20 years design life


Good deep discharge resilience performance
Special plate design, long cycle lifetime
High thermal capacity, reduce the risk of
thermal out of control and drying hard,
can be used in bad enviroment
Flame retardant container UL94-V0

Layout

6462
663.72
6812

Unit: mm

ANHUI UPLUS ENERGY TECHNOLOGY CO., LTD.

www. uplus-battery.com

Publication No.: UB-OPzV-09-2015

Telecom Battery
UPS Battery

Renewable Energy Battery

Tubular GEL Battery-OPzV Series

Specification
2V
1000.0 AH/100.0A
762.0 AH/254.0A
568.0 AH/568.0A
Length
Width
Container Height
Total Height

Nominal Voltage
Rated Capacity

(Ah)

Dimension

(10hr,1.80V/cell,250C)
(3hr,1.75V/cell,250C)
(1hr,1.60V/cell,250C)

2332mm
2102mm
6462mm
6812mm

Approx Weight

Approx 78.5 kg

Terminal

Material: Copper

Container Material

ABS

Max. Discharge Current

8000A (5s)

Internal Resistance

Approx 0.45m

Operating Temp. Range

Discharge: -20550C Charge: 0400C Storage: -20500C

Tubular
GEL Bat
tery
10 OPzV70

0 (2V,1000

AH)

Maintenc
e-free Sea
led Lead-ac
SEA LED
id GEL Batt
LEA D BAT
TER Y MUS
ery
DISP OSE
T

D OF PRO
BE REC
YCL ED
PER LY
OR
ANH UI UPL
US ENE
RGY TEC
MAD E IN
HNO LOG
CHIN A
Y CO., LTD.

40o C
103%
100%
25o C
86%
0o C
Initial Charging Current less than 250.0A.

Capacity Affected by
Temperature
Cycle Use

Voltage: 2.4V at 250 C

Temp. coefficient -5mV/0C

Standby Use

Equalization voltage: 2.35V at 250C Temp. coefficient -3mV/0C


Temp. coefficient -3mV/0C
Float voltage: 2.25V at 250C

Self Discharge

2% per month @ 25 0C.

ISO9001

ISO14001

Performance
Constant Current Discharge (Amperes) at 25 0C (77 0F )
F.V/Time

10min

15min

30min

1h

2h

3h

5h

8h

10h

1.85V/cell

682

648

558

445

295

228

157

110

93.7

1.80V/cell

839

784

650

502

324

249

169

118

100

1.75V/cell

992

877

693

522

333

254

173

119

102

1.70V/cell

1113

957

733

542

342

259

175

121

103

1.65V/cell

1196

1011

763

558

349

264

178

122

104

1.60V/cell

1251

1047

782

568

354

267

180

123

105

Constant Power Discharge (Watts/cell) at 25 0C (77 0F )


F.V/Time

10min

15min

30min

1h

2h

3h

5h

8h

10h

1.85V/cell

1268

1217

1066

862

574

446

309

217

186

1.80V/cell

1532

1452

1230

964

627

483

332

232

199

1.75V/cell

1782

1603

1298

997

641

492

337

236

201

1.70V/cell

1964

1724

1360

1029

654

500

341

238

203

1.65V/cell

2071

1793

1400

1051

665

507

345

241

205

1.60V/cell

2126

1830

1421

1062

670

511

347

242

206

ANHUI UPLUS ENERGY TECHNOLOGY CO., LTD.

www. uplus-battery.com

Publication No.: UB-OPzV-09-2015

Telecom Battery
UPS Battery

Renewable Energy Battery

Tubular GEL Battery-OPzV Series

Characteristic Curve
Discharge Characteristics

Charging Characteristics

2.50

25

Charging time in hours

Charge voltage (V/cell)

2.45
Equaling charge voltage
for max. 16 hours

2.40

2.35
2.30
2.25

Float voltage +/- 1%


2.20
2.15

0.1C 10

20
A

0.2C 10

10

2.10
-20

-10

30

20

10

50

40

50

100

Depth of discharge in % of C10

Temperature ( C)
Charge voltage:

For continuous charging we recommend a voltage of 2.25 V.


The charging voltage must be compensated to the curve for
acontinuously different battery ambient temperature.

A2.25 V/cell

B 2.40 V/cell

State of charge 100 %

Temperature Effects in Relation to Battery Capacity

State of charge 90 %

Effect of Temperature on Long Term Float Life

110
100

22

95

20

Life expectancy (year)

Available capacity( % )

105

90
85
80
75
70

C 10
C5
C3
C1

65
60
55
50
45

18

Charging voltage
2.25V/cell

16
14
12
10
5

40
35
30
-20

-15

-10

-5

10

15

20

25

20

30

30

Cycle Life in Relation to Depth of Discharge

50

General Relation of Capacity VS. Storage Time

Acc.to IEC 896-2 (25 0 C)

Residual average capacity in % of C 10

120

Remaining capacity / %

100

Extracted capacity in %

40

Battery temperature

Ambient temperature()

90
80
70
60
50
40
30

100
80
10

60
30

40

25

40
20

20
10
1500

2000

2500

3000

3500

4000

4500

5000

5500

6000

6500

Number of Cycles

ANHUI UPLUS ENERGY TECHNOLOGY CO., LTD.

10

15

20

25

Storage time (months)

www. uplus-battery.com

Publication No.: UB-OPzV-09-2015