Professional Documents
Culture Documents
Eduardo Rodrigues
Universidade do Vale do Rio dos Sinos
So Leopoldo - RS - Brasil
Recebido em 15/11/14
Aceito em 30/06/15
Abstract
Buildings performance building is in evidence in Brazil, especially after the
adoption of the Performance Standard ABNT NBR 15575: 2013. This
standard is concerned with the need of building systems to meet minimal fire
safety requirements, among others. The aim of this paper is to investigate the
potential application vertical sealing of reinforced concrete for fire resistance
purposes by the construction industry. Through prototypes tested at full scale
(3.15 x 3.00 m) in a standardized vertical furnace, two wall thicknesses (10
and 14 cm), with the same concrete mix were analysed by observing their
behaviour in terms of thermal insulation, sealing and stability. The tests
demonstrated that the samples met the applicable conditions for up to 120
minutes of testing, with the 14 cm thickness showing better rates of thermal
insulation and sealing.
Keywords: Fire safety. Performance. Sealing systems.
BOLINA, F. L.; PRAGER, G. L.; RODRIGUES, E.; TUTIKIAN, B. F. Avaliao da resistncia ao fogo de paredes macias
de concreto armado. Ambiente Construdo, Porto Alegre,v. 15, n. 4, p. 291-305, out./dez. 2015.
ISSN 1678-8621 Associao Nacional de Tecnologia do Ambiente Construdo.
http://dx.doi.org/10.1590/s1678-86212015000400051
291
Introduo
O desempenho das edificaes um tema em
evidncia no cenrio brasileiro, principalmente
aps a aprovao da norma de desempenho das
edificaes, a NBR 15575 (ABNT, 2013).
Composta de seis partes, que analisam os
requisitos gerais, estruturais, de pisos, de
vedaes, de coberturas e hidrossanitrios, essa
regulamentao
objetiva
a
validao
e
aplicabilidade em termos de segurana, conforto,
resistncia e durabilidade dos materiais e sistemas
construtivos frequentemente utilizados no setor.
Entre tais requisitos de segurana est a resistncia
ao fogo dos sistemas constituintes das edificaes
habitacionais (BOLINA; ESTEVAM; TUTIKIAN,
2014), tais como o de vedao vertical. Segundo
Buchanan e Munukutla (1991), quando ocorre um
incndio em um edifcio, paredes so necessrias
para limitar a propagao do fogo aos cmodos
vizinhos, mantendo a integridade e a segurana da
edificao durante algum tempo.
No que tange resistncia ao fogo, destaca Silva
(2013) que esta a propriedade de um elemento
resistir ao do fogo, mantendo sua integridade,
segurana estrutural, estanqueidade e isolamento
quando submetido a esse fenmeno. Geralmente
essa resistncia medida segundo o tempo que o
elemento suporta a ao do fogo produzido durante
um incndio. No Brasil, em termos de
regulamentao tcnica, esse tempo definido pela
NBR 14432 (ABNT, 2001a) Exigncias de
resistncia ao fogo de elementos construtivos de
edificaes. Para cada elemento construtivo a
norma estabelece uma resistncia requerida
mnima ao fogo, o tempo requerido de resistncia
ao fogo (TRRF), em funo da altura, da ocupao
e do uso de uma edificao.
A Instruo Tcnica n. 8 do Corpo de Bombeiros
da Polcia Militar do Estado de So Paulo
(CBPMESP), a IT08:2011 (SO PAULO, 2011),
utilizada em 16 estados do Brasil at 13 de
fevereiro de 2015, especifica que o TRRF, em
essncia, visa prevenir o colapso de uma
edificao em situao de incndio por
determinado perodo, propiciando a sada segura
dos ocupantes, limitando a propagao do fogo
para compartimentos adjacentes e preservando
condies mnimas para o trabalho do Corpo de
Bombeiros. A perda patrimonial e a proteo ao
meio ambiente surgem tambm como objetivos
almejados de carter secundrio quando se
estabelece uma resistncia ao fogo para as
edificaes (WANG et al., 2013). Assim, entre os
sistemas que se necessita garantir tais requisitos de
resistncia ao fogo est, alm do estrutural, o de
vedao vertical, necessrio para possibilitar a
Materiais e mtodos
Materiais
O concreto empregado foi usinado, e para as
formas foi utilizada madeira. A Tabela 1 mostra as
propriedades do concreto que foi empregado para a
confeco das amostras.
Parede n
1
2
Propriedades do concreto
fck (MPa) Rel. a/c Cimento
25
0,60
CPIV
25
0,60
CPIV
293
Eq. 1
Onde:
T: temperatura do forno no tempo T, em C;
To : temperatura inicial do forno, em C, sendo 10
C To < 40 C; e
t: tempo do ensaio, em minutos.
incndio-padro, estabelecida a partir do fenmeno
que causa a elevao abrupta das temperaturas em
um compartimento incendiado, a ignio sbita
generalizada (flashover). Essa curva, com elevao
constante de temperatura, tambm uma
simplificao bem aceita no meio tcnico para a
realizao de dimensionamento, ensaios e anlises,
j que a curva real de incndio influenciada por
Figura 1 - Detalhe do forno com os queimadores acesos
Parmetros avaliados
Os parmetros avaliados neste estudo foram o
isolamento trmico, a estanqueidade e a
estabilidade das paredes, o que compe a
resistncia ao fogo. O acompanhamento do
isolamento trmico feito por termopares,
correlacionando as temperaturas internas e
externas com o tempo transcorrido de ensaio.
Segundo os preceitos da NBR 10636 (ABNT,
1989), as variaes de temperaturas mximas
registradas no podem superar 180 C em cada
termopar ou 140 C sobre a mdia aritmtica
destes. J a E 119 (AMERICAN..., 2014)
estabelece como 250 F (139 C) a variao
mxima da temperatura mdia dos termopares em
relao temperatura mdia inicial destes. A
norma australiana AS 1530 (AUSTRALIAN...,
2005) limita a temperatura mdia dos termopares
em 140 K (133 C). Todo o procedimento de
coleta das temperaturas foi filmado com cmara
termogrfica, acompanhando o desenvolvimento
do calor externo da amostra no tempo.
A estanqueidade das amostras deve ser observada
por intermdio de um chumao de algodo, que,
posicionado por 10 s sobre as eventuais fissuras,
com 1 cm a 3 cm de distncia, no inflame,
obedecendo s prescries da NBR 5628 (ABNT,
2001b). As fissuras deflagradas, caso no
provoquem a inflamao do chumao de algodo,
no sero registradas e locadas, uma vez que elas
no comprometem a estanqueidade. A NBR 10636
(ABNT, 1989) explica que, para analisar a
estanqueidade do elemento estrutural submetido ao
fogo, devem ser avaliadas as fissuras ou outras
aberturas que surjam no ato do ensaio. Tal como a
E 119 (AMERICAN..., 2014) e a AS 1530
(AUSTRALIAN..., 2005), a norma brasileira
classifica como estanques todas as paredes que, ao
295
Instrumentao do ensaio
Resultados e discusso
Aspectos gerais
Descrio
Modelo
Forno vertical
GFT 03276 FG
Cmera termogrfica
Trena a laser
A325
GLM 80 Professional
Calibrao
Resoluo 0,01 C
Capacidade trmica 1.200 C
FLIR
Bosch
Figura 3 - Numerao dos termopares dispostos junto face externa das paredes
Tempo
0:00
14 min
17 min
PAREDE 1 10 cm
Descrio
Incio do ensaio
Amostra comea a liberar gua da
composio
Inicia-se um acrscimo de calor no
ponto onde aconteceu a liberao
de gua
Tempo
0:00
13 min
PAREDE 2 14 cm
Descrio
Incio do ensaio
Foco de calor na parte central da
amostra
14 min
20 min
26 min
35 min
28 min
46 min
32 min
66 min
56 min
81 min
117 min
120 min
Trmino do ensaio
117 min
120 min
297
140
120
Temperatura (C)
100
80
60
40
MDIA
Termopar 06
20
Termopar 07
Termopar 08
Termopar 09
Termopar 10
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
0
Tempo (min)
120
Temperatura (C)
100
80
60
40
20
MDIA
Termopar 6
Termopar 7
Termporar 8
Termopar 9
Termopar 10
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
0
Tempo (min)
Com base na Tabela 4 e nas Figuras 6 a 9, observase que em todas as situaes a parede de concreto
de 14 cm de espessura apresentou temperatura da
face externa sempre inferior temperatura da face
externa da parede de concreto de 10 cm de
Tempo
(min)
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
PAREDE 1 10 cm
CurvaTemperatura mdia da
padro T' face no exposta ao
To (C)
fogo (C)
556
25,6
659
25,5
718
26,3
821
28,2
865
32,8
898
40,5
925
49,1
948
57,9
968
66,3
986
73,6
1002
80,2
1016
86,0
1029
92,2
1041
96,7
1052
100,0
1062
102,1
1077
104,5
1081
106,7
1090
108,6
1098
110,3
1106
112,1
1113
113,8
1120
115,6
1126
117,2
PAREDE 2 14 cm
CurvaTemperatura mdia
padro T' - da face no exposta
To (C)
ao fogo (C)
556
20,7
659
20,8
718
20,9
821
21,2
865
22,4
898
24,5
925
28,6
948
33,4
968
38,9
986
44,8
1002
49,8
1016
54,8
1029
60,1
1041
65,9
1052
71,3
1062
76,1
1077
80,1
1081
83,4
1090
86,2
1098
88,7
1106
90,9
1113
93,0
1120
94,7
1126
96,2
Diferena de
temperatura entre as
paredes 1 e 2 (C)
4,9
4,7
5,4
7,0
10,4
16,0
20,5
24,5
27,4
28,8
30,4
31,2
32,1
30,8
28,7
26,0
24,4
23,3
22,4
21,6
21,2
20,8
20,9
21,0
299
Avaliao da estanqueidade
Na Figura 10 mostrada a anlise de uma fissura
formada durante o perodo de ensaio da parede 1.
A Figura 11 mostra o operador do ensaio
aproximando o chumao de algodo na fissura
formada durante o ensaio da parede 2. Observa-se
que em ambos os casos no h inflamao do
chumao de algodo.
Portanto, no se observou nas duas paredes a
inflamao generalizada do chumao de algodo.
Ambas as paredes apresentaram microfissuras no
desenvolver do ensaio, porm estas no foram
suficientes para proporcionar a passagem de gases
inflamveis para a face oposta face de aplicao
Avaliao da estabilidade
Na Tabela 5 se evidencia o deslocamento lateral
sofrido pela parede 1 durante o ensaio; j na
Tabela 6 se evidencia o deslocamento lateral
sofrido pela parede 2, ambos medidos
externamente ao forno.
301
Tempo (min)
0
5
10
15
20
25
30
40
50
60
70
80
90
100
110
120
Deslocamento (mm)
0
11
22
28
33
36
38
39
39
39
4
4
42
43
43
44
Distncia (mm)
7.001
7.012
7.023
7.029
7.034
7.037
7.039
7.040
7.040
7.040
7.041
7.041
7.043
7.044
7.044
7.045
Tempo (min)
0
5
10
20
30
40
50
60
70
80
90
100
110
120
Deslocamento (mm)
0
6
15
27
40
45
49
52
56
59
62
64
67
69
Distncia (mm)
7.424
7.430
7.439
7.451
7.464
7.469
7.473
7.476
7.480
7.483
7.486
7.488
7.491
7.493
Avaliao final
Os resultados obtidos contribuem para as opes
de espessuras do sistema de vedao desse tipo
apresentado pela IT08 (SO PAULO, 2011). No
entanto, destaca-se que esses resultados divergem
dos apresentados pela prpria IT08:2011, a qual
no permite o uso de espessuras de paredes de
concreto macio de 11,5 cm para tempos maiores
que 60 min, bem como da EN 1992-1-2
EUROPEAN..., 2004), a qual no permite o uso de
espessuras de parede de concreto macio de 10 cm
para tempos maiores que 90 min.
Figura 12 - Aspecto final da parede 1 (10 cm) aps o teste do choque mecnico
Figura 13 - Aspecto final da parede 2 (14 cm) aps o teste do choque mecnico
Concluso
Neste trabalho foi efetuado o teste de duas paredes
macias em concreto armado nas dimenses de
3,153,000,10 m (parede 1) e 3,153,000,14 m
(parede 2) segundo a curva de aquecimento dos
gases especificados pela NBR 10636 (ABNT,
1989). Foram analisados os critrios de isolamento
trmico, estanqueidade e estabilidade estrutural.
Conclui-se que as paredes 1 e 2 apresentaram
resistncia contra o fogo para o tempo de 120 min,
atendendo s exigncias de estanqueidade,
isolamento trmico e estabilidade segundo a
classificao da NBR 10636 (ABNT, 1989). Com
isso possvel afirmar que as paredes de vedao
vertical executadas em concreto de fck 25 MPa,
com o trao e as armaduras utilizados neste artigo,
Referncias
AMERICAN SOCIETY FOR TESTING AND
MATERIALS. E 119: standard test methods for
fire tests of building construction and materials.
West Conshohocken, 2014.
ASSOCIAO BRASILEIRA DE NORMAS
TCNICAS. NBR 10636: paredes divisrias sem
funo estrutural: determinao da resistncia ao
fogo: mtodo de ensaio. Rio de Janeiro, 1989.
303
FDRATION INTERNATIONALE DU
BTON. Fire Design of concrete Structures:
structural behavior and assessment. Lausanne:
CEB-FIP, 2008. Bulletin no 46.
Eduardo Rodrigues
ITT Performance | Universidade do Vale do Rio dos Sinos | E-mail: eduardoec@unisinos.br