You are on page 1of 3

24 & 48 VDC direct current alternators

for lighting towers


and telecom applications

24 & 48 VDC low voltage alternators

Designed for applications requiring 24 & 48 VDC low voltage


supply, Omega DC power solutions are suitable both as battery
chargers and emergency power supplies of auxiliary circuits, in the
telecommunication, transports and industrial field.

Typical application
LED
lamps

Applications
Battery chargers
Low voltage LED light towers
Power supply of auxiliary circuits, high/medium voltage
disconnectors coils, signalling devices
Power supply of monitoring and alarm systems

Battery charger

G
Low voltage LED light towers

G
G

General features
AVR electronic voltage regulation
Based on three-phase synchronous alternators
1500 rpm or 3000 rpm with large speed tollerance
Constant DC output voltage
Adjustable output voltage
Current overload protection
Fan cooled
Complying with EN 60034-1, IEC 60034-1, ISO 8528-3

Emergency power back-up for BTS power systems

Capacity table

Sectors of use
es

Telecommunications
Industry
Transports
Military

Advantages
High voltage stability in a large speed range
High efficiency
Low voltage ripple
High reliability
Available with the most common couplings
Fast recovery time during transient by step load variation

kW
3,6
4,8
7,2
9,6
12
14,4
16,8
19.2
21,6

24 V
current
150A
200A
300A
400A
500A
600A
700A
800A
900A

4 poles
model
Om-B4-24/150
Om-B4-24/200
Om-B4-24/300
Om-B4-24/400
Om-B4-24/500
Om-B4-24/600
Om-B4-24/700
Om-B4-24/800
Om-B4-24/900

kW
7,2
9,6
14,4
19.2
24
28.8
33,6
38,4
43,2

48 V
current
150A
200A
300A
400A
500A
600A
700A
800A
900A

model
OM-B4-48/150
OM-B4-48/200
OM-B4-48/300
OM-B4-48/400
OM-B4-48/500
OM-B4-48/600
OM-B4-48/700
OM-B4-48/800
OM-B4-48/900

Electrical data
Type
Technology
Fixed speed
Over speed
Underspeed protection
Nominal voltage
Adjustable output voltage
Output current
Max output power (Watt)
Efficiency (3/4 load)
Current limit protection
Ripple (2)
Insulation class
Temperature rise class
IP protection
Operating temperature range
Electromagnetic compatibility

OM - IB
three-phase synchronous with AVR
brushes
brushless
1500 or 3000 rpm (1)
+ 20%
included
24 VDC or 48 VDC (1)
from 23 VDC to 31 VDC
or from 48 VDC to 58 VDC (1)
see selection table @ 24 VDC or 48 VDC
Current (A) x 24 (VDC) or 48 (VDC)
> 0,80
included
without load < 8%
with full resistive load < 6%
with batteries < 3%
H
H
IP23
- 20 C to + 40 C (until + 55 C with derating)
EN 61000-6-2 , EN 61000-6-4

(1) see capacity table (2) on request reinforced filter for ripple reduction

Operating derating factors


amb. temp.
factor

25 C
1,05

40 C
1

45 C
0,96

50 C
0,92

55 C
0,88

altitude
factor

1000m
1

1500m
0,96

2000m
0,93

2500m
0,9

3000m
0,86

Overall dimensions

model @ 24V
OM-B4-24/150
OM-B4-24/200
OM-B4-24/300

D
mm
329
329
329

B
mm
437
437
437

mass
Kg
63,2
59,2
70,6

OM-B4-24/400
OM-B4-24/500
OM-B4-24/600
OM-B4-24/700
OM-B4-24/800
OM-B4-24/900

506
506
506
506
576
576

570
570
570
570
640
640

150
160
170
180
195
205

model @ 48V
OM-B4-48/150
OM-B4-48/200
OM-B4-48/300

D
mm
329
329
329

B
mm
437
437
437

mass
Kg
63,2
59,2
70,6

OM-B4-48/400
OM-B4-48/500
OM-B4-48/600
OM-B4-48/700
OM-B4-48/800
OM-B4-48/900

506
506
506
506
576
576

570
570
570
570
640
640

150
160
170
180
195
205

150A-300A: J609B coupling. 400A: SAE 4 6 coupling. 500A: SAE 4 7 coupling.


600A: SAE 3 or 4 8 coupling. 700A: SAE 3 or 4 10 coupling.
800A-900A: SAE 3 11 coupling.

You might also like