You are on page 1of 2

CAT. NO.

D -F-8507

FIRE ALARM BELL

FEATURES
Motor driven type alarm bell
High sound output with low current consumption
High durability
Low RFI noise
Rainproof type available
Lead wire connection

DESCRIPTION
The NOHMI's re alarm bell provides a higher level of
sound with a high eciency and a lower level of RFI
noise.
FBM023 and FBW013-EA re alarm bells are not
compatible with the Automatic Testing FunctionATF
of the NOHMI analog addressable re alarm system,
since these alarm bells are not polarized.

FBM023-D and FBM023Z-D bells are compatible with


both NOHMI ATF analog addressable and conventional
re alarm systems.
It is recommended that re alarm bells are installed so
that the sound level at any place is higher than 65 dB
or higher than 6 dB plus the ambient sound level.

SPECIFICATIONS
Model No.
TYPE

FBM023

FBM023-D

Standard

FBM023Z-D
With diode

RATED VOLTAGE

24V DC

RATED CURRENT

10mA

POLARITY
AMBIENT TEMPERATURE

Polarized

Non-polarized
10 to 40

FBW013-EA
Rainproof

Non-polarized
10 to 50

NOMINAL SOUND LEVEL

More than 90dBat 1m

SOUNDING MECHANISM

Motor driven

MATERIALS

Gong
: Aluminum Alloy
Fixing plate : Steel plate t=1.2mm

Gong :Aliminium Alloy


Housing:ABS resin

FINISH

Gong
: Baked meramine
Fixing plate : Galvanized

Gong :
Baked meramine

WEIGHT
OTHERS

Approx. 420g
Marked in Japanese

Approx. 540g
Marked in English

Marked in Japanese

HEAD OFFICE7-3, Kudan-Minami 4-chome, Chiyoda-ku, Tokyo 102-8277, Japan PHONE


813-3265-0231 FAX
813-3265-5348

FIRE ALARM BELL FBM023/FBM023-D/FBM023Z-D/FBW013-EA


TYPICAL WIRING DIAGRAM

R-21N or FRR026-BL
PANEL
Transmitter
BC

Red wire

Fire alarm bell

Red wire

B1to B3

B
BF

Black wire

BF

D -F-8507

WIRING DIAGRAM WITH LINE MONITOR FUNCTION

FBM023/FBW013-EA FBM023-D/FBM023Z-D

BC

CAT. NO.

ER:10k 1/2W

B1to B3
Black wire

Fire alarm bell

CIRCUIT

Conventional
re alarm panel

Red wire

B : FBM023-D, FBM023Z-D

Black wire

DIMENSIONS
STANDARD TYPE
FBM023/FBM023-D/FBM023Z-D

RAINPROOF TYPE
FBW013-EA

Gong

Gong

45.5

150

150

71.5

INSTALLATION

STANDARD TYPE

RAINPROOF TYPE

Outlet box with cover


JIS C 8336 or

JIS C 8336

46

83.5

6094

83.5

66.7

150

75

65

87
75
Fixing plate
Supplied with FBM023

Fixing holes on FBW013-EA


Front view
JIS C 8340
Compatible Box:Switch Box for 2 units with cover
JIS C 8340

These

instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in
connection with installation, operation and maintenance.
Specications are subject to change without notice. Contact Nohmi before relying on above specications.
Actual performance is based on proper application of the product by a qualied professional.
Should further information be desired or should particular problems arise, which are not covered suciently for the purchaser's purposes, the matter should
be referred to Nohmi or a distributer in your region.

OFFICE 7-3, Kudan Minami 4-chome,


Chiyoda-ku, Tokyo 102-8277, Japan
PHONE
81
3-3265-0231
F A X
81
3-3265-5348
U R L http://www.nohmi.co.jp/english/
HEAD

100401D -F-8507YO3

You might also like