You are on page 1of 21

Split Air Conditioners

ACUM-L + CADX-L Series


Range 4 TR to 21 TR
( 15 kW to 74 kW )

Bulletin # 077/2012

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Contents
Introduction................................02
Legend........................................02
Nomenclature.............................02
Component Features.......................03
Optional Features............................04
Specifications..................................06
Capacity Ratings..............................08

Fan Performance............................... 10
F
E
Electrical Data .....................................11
T
Typical Wiring Diagram .....................12
D
Dimensional Data ...............................13
R
Recommended Line Sizes ..................16
R
Recommended Clearances ................17
IInstallation and commissioning .........18
G
Guide Specifications..........................20

Introduction

Legend
The following legends are used throughout this manual:
cfm ........ Cubic feet per minute
Hz ......... Hertz
kW ........ Kilowatts
kg .......... Kilogram
lbs ......... Pounds
l/s ......... Liters per second
MBh ...... BTUH x 1000

Ph ......... Phase
PI .......... Power Input of Compressor
TR ......... Tons of Refrigeration
V ........... Volts
kPa ....... Kilopascal
EWB...... Evaporator Wet Bulb air
entering temperature.
BPF....... By Pass Factor

SKM air cooled split air conditioners available


in 14 variations to cover the range from 4 to
21 TR (15 to 74 kW) in 50Hz at nominal AHRI
conditions. It is suitable to operate in a wide
range of ambient temperatures from 50 F
(10C) to 125F (52C).

Nomenclature

ACU M - 060 L Y
Power Suppy Code

Air Cooled Condensing Units

Y: 380-415V/3Ph/50Hz
P: 440V/3Ph/50Hz
M-series

The new series of SKM air cooled split


system air conditioner has been developed to
satisfy the needs in air conditioning practices,
meet high quality of job requirements every
time and to deliver the best in split system
performance.
SKM air cooled split air conditioners consist
of ceiling suspended indoor air handler
(CADX-L) matched with floor mounted
outdoor air cooled condensing unit (ACUM-L)
series.

Model Designation
Nominal Capacity (MBh)

SKM split units are internally wired and


all that is required to be done on site is
ducting, refrigerant piping, power wiring for
CADX-L motor from ACUM-L, thermostat
wiring and power supply connection which
reduces installation work and consequently
keeps costs to a minimum. Two independent
refrigeration circuits are provided when two
compressors are used.

SKM split air conditioner are simply,

CA DX -

060 L Y
Power Suppy
Y: 380-415V/3Ph/50Hz
P: 440V/3Ph/50Hz

Comfort Air Conditioner

Model Designation
Nominal Capacity (MBh)

You name it.....We cool it

Direct Expansion Cooling Coil

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
GENERAL FEATURES

Condenser Coils

SKM split system air conditioners incorporate many features


and benefits in both the air handler and condensing units, which
together provides a heavy duty, robust and long lasting commercial
units application.
SKM split air conditioners combined high efficiency components
to provide an extremely rugged and energy efficient split system
that will provide cooling with higher efficiency for a long and
extended period of time.

Condenser coils are manufactured from cross fin Waffle Louvre


and Hi-X seamless copper tubes mechanically bonded to
aluminium fins to ensure optimum heat transfer. All coils are
tested against leakage by air pressure 450psig (3100 kPa)
under water. An integral subcooling circuit is incorporated in the
lower section of the condenser to increase system capacity. The
additional condenser surface provides more cooling using less
energy at no additional cost.

SKM split system is ACUM-L+ CADX-L is yet another model in


the top class range of SKM products which uses the following
basic components:

Condenser Fans

High efficiency totally sealed hermetic scroll compressors


utilizing the most current state of the art technology and provides
smooth, efficient and quiet operation.
Totally enclosed, class F insulated, IP55 protected condenser
and evaporator fan motors.
Heavy duty condenser and evaporator coils optimized and
designed for a long life maintenance free operation.
Cabinet construction specifically for gulf climate condition.
Electrical panel with many features as standard.
Factory matched performance and reliable output to minimize
field decisions.

Condenser fans are propeller type with aluminium alloy blades


and are directly driven by electric motors. Motors are internally
protected for overloads and Totally Enclosed Air Over (TEAO),
six pole with Class F insulation and minimum IP55 protection.
The TEAO and Class F insulation features ensure long life and
are unique to SKM. The condenser fans are individually statically
and dynamically balanced at the factory. Complete fan assembly
is mounted downward on the strong and acrylic coated fan guard
for the smaller units. For larger units fan, assembly is separate
and provided with suitable acrylic
coated fan guard.
Motors are wired to the control panel
to control the operation of these
motors along with the compressors.

Many standard features which are not included in residential


domestic type split systems.

Figure 1: Condenser fan motor arrangement


for models ACUM-050L, 110L, 120L,
130L, 145L

Typically, much heavier gauge tubing and thicker fins for


ruggedness and long life.

COMPONENT FEATURES
ACUM-L CONDENSING UNIT
Compressor
Compressors used in the ACUM-L series condensing units are
hermetically sealed, hi-efficiency, low noise, and compact scroll
with the following features:
High efficiency.
Quite operation, low sound levels.
Better debris handling.
Self compensating of wear (wear-in vs. wear-out).
70% fewer moving parts than comparably sized reciprocating
compressors.
Internal motor protection / Advanced scroll temperature
protection.
Suction gas motor cooling.
Suction screen.
Disc type check valve.
Centrifugal force for oil lubrication.
Brazed fittings as standard, rotalock as an option.

Figure 2 : Condenser fan motor arrangement


for models ACUM-060L,070L,085L,
100L,160L,180L,205L,240L,260L

Control Panel
Outdoor condensing units are provided with IP-54 control panel
enclosure comprising all starting, operating and safety controls.
Following are the standard components used in the ACUM-L
control panel:
All compressors are with DOL starting.
Individual compressor and condenser fan motor contactors.
Overload relays for condenser fan motors.
Control Relays and control circuit fuses.
Control disconnect for each refrigerant circuit.

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Anti-short cycle timer for compressors.

CADX-240L model is with Penta-Post construction from


extruded aluminum profiles and nylon glass fiber reinforced
corners joints.

24V Control Transformer.


Starter (contactor & overload relay) for CADX-L evaporator
fan motor. (Power wiring from ACUM-L control panel to CADX-L
motor to be done at site by others)
Power and control terminal blocks.

The cross section of the profile is specially designed for


maximum rigidity and strength Profiles for panels with 1 (25
mm) nominal thickness have got built-in PVC inserts to prevent
thermal bridge. Access doors & fixed panels are insulated with
1thick fiber glass thermal and acoustic insulation, as standard.

Unit Casing
The unit casing used in the ACUM-L condensing unit is made
of zinc coated galvanised steel sheets conforming to JIS-G
3302 and ASTM A525 which is phosphatized and baked after
an electrostatic powder coating in RAL7032 color scheme of
approximately 60 microns. This finish and coating can pass
a 1000 hour in 5% salt spray testing at 95F (35C) and 95%
relative humidity as per ASTM B117.

OPTIONAL FEATURES
As with all SKM air conditioning units, a wide range of options
are available with SKM Split Units on request.

Copper Fins

CADX AIR HANDLING UNIT

Pre Coated Aluminum Fins

Evaporator Coils

Aeris Coating for Aluminium Fins


/Copper Fins.

All evaporator coils are made of inner grooved copper tubes


mechanically bonded into cross wave aluminum fins to ensure
optimum heat transfer. Coils conform to AHRI-410. All evaporator
coils are tested against leakage by air pressure of 300 psig
(2068 kPa) under water. Each evaporator coil is supplied with a
factory sized and matched thermostatic expansion valves and
4 mounting holes for ceiling suspension.

(FC)
(FAP)
(FAA)/(FCA)

2 (50mm) Flat Filter Section

(FFS)

For heavy filtration need a section can be provided without or


with aluminium cleanable filter (2AF).

Voltage Monitoring Module

(VMM)

To prevent ACUM-L unit operation in the event of Phase loss


Phase reversal, and Under / Over voltage on the incoming line
voltage.

Evaporator Fan & Drive


Evaporator fans are forward curved centrifugal double inlet, double
width, statically and dynamically balanced. Bearings used in the
fans are self aligning and lubricated for life. Evaporator fans are
belt driven and use V belts with an adjustable variable pitch
motor pulley resulting in an accurate fan air flow adjustment.
Fans are driven by Totally Enclosed, IP55 Protected, 4 Pole
Class F insulated electric motors which conform to relevant
IEC standards.

Voltage Monitoring Module as per DEWA

(DVM)

Under voltage relay as per DEWA regulations. This option is


available for Dubai, UAE only.

External Overload Protection

(EOP)

For those electrical specification requires additional overload


protection for the compressors.

Filter
All CADX-L units are supplied as standard with 1 (25mm) thick
permanent washable expanded aluminum flat filter having
average dust arrestance 54% according to ASHRAE standard
52-76.

High & Low Pressure Gauges

Liquid Line Controls

Casing \ Structure (CADX-L):


The unit casing for CADX-L is made of zinc coated galvanized
steel sheets conforming to JIS-G3302 and ASTM A525 which
is phosphatized and baked after an electrostatic powder
coating in RAL7032 color scheme of approximately 60 microns.
This finish and coating can pass a 1000 hour in 5% salt spray
testing at 95F (35C) and 95% relative humidity as per ASTM
B117. Panels and casing are insulated with 1 (25mm) thick
fiberglass (with BGT coating) thermal and acoustic insulation
having density of 2 lb/ft. (32 kg/m) and thermal conductivity
of 0.23 BTU.in/ftFh (0.033 W/mK). Insulation meets the
requirements of NFPA 90A and 90B for fire resistance.

(SDG)

Factory installed for each compressor to monitor the high side


and low side operating pressure.

(CRSP)

Refrigeration specialties comprising solenoid valve, filter drier,


sight glass and shut-off valve. Factory sizing and selection
ensures correctly sized and selected components to complete
the field installation.

Low voltage thermostats

(CHTS)

Wall mounted 24 volts cooling/heating thermostats, supplied


loose for field installation. (Not required with MCP option)

Rotalock Valves on compressors

You name it.....We cool it

(RVC)

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Electric Heating

(HC@)

Eectric heating batteries are made up of finned heating


elements, constructed from high quality 80/20 nickel chrome
resistance wire centred in metal tube by compressed
magnesium oxide. Helical fins are tightly wound around the
tubular heating element.
Heater batteries when ordered comes with CADX-L mounted
control panel consisting of stage contactors, primary auto reset
thermal safety cut-out, secondary manual reset thermal safety
cut-out and air flow switch. Control of the heater stages will be
from ACUM-L control panel through heating/cooling thermostat
(either supplied by SKM or by customer).

Factory Installed Option


Microprocessor Based Control

(MCP)

A compact and user friendly electronic controller is available as an


option for the control of the split units. The controller comes with
a built in display, loose supplied room terminal and duct sensor.
The main features of the controller are as follows:
Built-in display with keypad.
Room terminal for mounting in the conditioned space.
Control of the indoor Fan & compressors.
Control of the compressors is based on return duct temperature.

Following are the optional kW ratings for electric heater.

Alarm management.
Built-in anti recycle time for the compressors.

ACUM-

CADX-

050L
060L
070L
085L
100L
110L
120L
130L
145L
160L
180L
205L
240L
260L

050L
060L
070L
085L
100L
120L
120L
150L
150L
150L
180L
180L
240L
240L

Automatic lead-lag for the compressors based on run time (for


units with two compressors)

Heater (kW) Stages

Volt free contact for common fault.

Remote start/stop provision.

7.5
9
1
12
15
18
2

Figure 3

24
Table 1

Condenser Coil Guard

(CGP)

Wire mesh guard, in painted finish, for condenser coils.


Recommended on ground level installation where coil needs to
be protected against vandalism

The controller displays status of the indoor fan, compressors,


duct temperature and active alarms. Alarms can be automatic
or manual reset (factory default is auto reset). Set points are
configurable from the controller display as well. The loose
supplied room terminal also shows the same information as
the built-in display.

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
CONDENSING UNIT SPECIFICATIONS
Condensing Unit

ACUM-

050L

060L

070L

085L

100L

110L

Matched Air Handling Unit

CADX-

050L

060L

070L

085L

100L

120L

120L

MBh

50.7

63.8

72.1

84.8

96.5

116.0

125.8

Cooling Capacity (1)


Cooling Capacity (2)
Capacity Steps
Compressor

kW

14.9

18.7

21.1

24.9

28.3

34.0

36.9

MBh

47.0

58.8

66.5

78.4

89.6

107.6

116.2

kW

13.8

17.2

19.5

23.0

26.3

31.5

34.1

100-0

100-0

100-0

100-0

100-0

100-50-0

100-50-0

Type

Hermetic - Scroll

Qty.
Type

Outdoor Coil

ft

20.0

26.7

26.7

26.7

26.7

40.0

40.0

1.86

2.48

2.48

2.48

2.48

3.72

3.72

1/2

1/2

1/2 (x2)

1/2 (x2)

1 1/8

1 1/8

7/8 (x2)

7/8 (x2)
628 / 2

No. Refrigerant Circuits


Connections (3)

1
Waffle louver fins and Hi-X tubes 3/8'' OD

Qty.
Face Area

Liquid

in

1/2

1/2

1/2

Suction

in

7/8

7/8

7/8

Type
Outdoor Fan

Motor

Propeller Direct Drive

Code/Qty
Air Flow

560 / 1

723 / 1

723 / 1

723 / 1

723 / 1

560 / 2

cfm

4430

7090

7090

7030

7030

8760

9560

l/s

2091

3346

3346

3318

3318

4134

4512

kW / #

0.25 / 1

0.75 / 1

0.75 / 1

0.75 / 1

0.75 / 1

0.25 / 2

0.37 / 2

lbs

6.9

8.6

8.6

13.9

14.3

22.1

22.1

kg

3.1

3.9

3.9

6.3

6.5

10.0

10.0

Type
Size / Qty.

Refrigerant Operating Charge


R-22 (4)
Operating Weight Approximate

120L

Totally enclosed, Class-F insulation, 6-pole, IP55 Protected

lbs

321

354

363

446

453

688

697

kg

146

161

165

202

206

312

316
260L

Condensing Unit

ACUM-

130L

145L

160L

180L

205L

240L

Matched Air Handling Unit

CADX-

150L

150L

150L

180L

180L

240L

240L

MBh

133.1

145.5

151.0

173.4

189.8

234.0

252.4

Cooling Capacity (1)


Cooling Capacity (2)
Capacity Steps
Compressor

kW

39.0

42.7

44.2

50.8

55.6

68.6

74.0

MBh

123.2

134.5

140.2

160.0

176.4

216.5

232.2

kW

36.1

39.4

41.1

46.9

51.7

63.5

68.0

100-50-0

100-50-0

100-50-0

100-50-0
Hermetic - Scroll

100-50-0

100-50-0

100-50-0

Type
Qty.
Type

Outdoor Coil

Qty.
Face Area

Outdoor Fan

40.0

40.0

40.0

40.0

48.0

54.7

54.7

3.72

3.72

3.72

3.72

4.46

5.08

5.08

Liquid

in

1/2 (x2)

1/2 (x2)

1/2 (x2)

1/2 (x2)

1/2 (x2)

5/8 (x2)

5/8 (x2)

Suction
Type

in

7/8 (x2)

7/8 (x2)

7/8 (x2)

1 1/8 (x2)
Propeller Direct Drive

1 1/8 (x2)

1 1/8 (x2)

1 1/8 (x2)

Code/Qty
Air Flow

Motor

ft

No. Refrigerant Circuits


Connections (3)

2
Waffle louver fins and Hi-X tubes 3/8'' OD

628 / 2

628 / 2

723 / 2

723 / 2

729 / 2

823 / 2

823 / 2

cfm

9560

9560

13900

13900

15540

19640

19640

l/s

4512

4512

9269

9269

kW / #

0.37 / 2

0.37 / 2

0.75 / 2

0.75 / 2

1.1 / 2

1.1 / 2

1.1 / 2

lbs

22.1

22.3

22.9

23.1

25.5

31.7

31.7

kg

10.0

10.1

10.4

10.5

11.5

14.4

14.4

Type
Size / Qty.

Refrigerant Operating Charge


R-22 (4)
Operating Weight Approximate

6560
6560
7334
Totally enclosed, Class-F insulation, 6-pole, IP55 Protected

lbs

707

713

860

860

946

909

913

kg

321

324

390

390

429

413

414

Table 2

Notes:
(1) The capacity ratings are based on AHRI standard 210/240 & 340/360. Evaporator entering air conditions of 80F/67F (27C/19.5C)
dry bulb / wet bulb and condenser entering air temperature of 95F (35C) dry bulb.
(2) Evaporator entering air conditions of 80F/67F (27C/19.5C) dry bulb / wet bulb and condenser entering air temperature of
115F(46C) dry bulb.
(3) Connections are based on 25 ft maximum linear distance between the outdoor & indoor unit and 66 ft maximum lift.
(4) Refrigerant operating charge is for combined condensing unit with the matching air handling unit and 25 ft (7.6m) of interconnecting
refrigerant lines.
Capacity for condition (1) & (2) are gross which doesnt include the effect of evaporator fan motor heat.

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
AIR HANDLING UNIT SPECIFICATIONS
Air Handling Unit

CADX-

050L

060L

070L

085L

100L

120L

120L

Matched Condensing Unit

ACUM-

050L

060L

070L

085L

100L

110L

120L

MBh

50.7

63.8

72.1

84.8

96.5

116.0

125.8

kW

14.9

18.7

21.1

24.9

28.3

34.0

36.9

MBh

47.0

58.8

66.5

78.4

89.6

107.6

116.2

kW

13.8

17.2

19.5

23.0

26.3

31.5

34.1

Cooling Capacity (1)


Cooling Capacity (2)
Type
Indoor Coil

Face Area

Hi-X tubes 3/8'' OD


ft

4.17

5.81

5.81

6.25

7.99

7.99

7.99

0.39

0.54

0.54

0.58

0.74

0.74

0.74

Refrigerant Control

Expansion Valve(s)

Connections (3)

Liquid

in

1/2

1/2

1/2

1/2

1/2

1/2 (x2)

1/2 (x2)

Suction

in

7/8

7/8

7/8

1 1/8

1 1/8

7/8 (x2)

7/8 (x2)

AT-10/10

AT-10/10

AT-10/10

AT-12/12

AT-12/12

AT-12/12

AT-12/12

cfm

1700

2000

2400

2800

3000

3600

3600

l/s

802

944

1133

1321

1416

1699

1699

Type
Indoor Fan

Air Flow
Motor

Centrifugal DIDW Belt Drive

Code

Type
Size / Qty.

Totally Enclosed, Class F insulated, IP55 Protected


kW / #

0.55 / 1

0.55 / 1

0.75 / 1

1.1 / 1

1.1 / 1

1.5 / 1

1.5 / 1

lbs

204

225

225

265

310

334

334

kg

93

102

102

120

141

151

151

Matched Air Handling Unit

CADX-

150L

150L

150L

180L

180L

240L

240L

Matched Condensing Unit

ACUM-

130L

145L

160L

180L

205L

240L

260L

MBh

133.1

145.5

151.0

173.4

189.8

234.0

252.4

kW

39.0

42.7

44.2

50.8

55.6

68.6

74.0

MBh

123.2

134.5

140.2

160.0

176.4

216.5

232.2

kW

36.1

39.4

41.1

46.9

51.7

63.5

68.0

Operating Weight Approximate

Cooling Capacity (1)


Cooling Capacity (2)
Type
Indoor Coil

Face Area

Hi-X tubes 3/8'' OD


ft

11.67

11.67

11.67

14.17

14.17

19.36

19.36

1.08

1.08

1.08

1.32

1.32

1.80

1.80

Refrigerant Control
Connections (3)

Expansion Valve(s)
Liquid

in

1/2 (x2)

1/2 (x2)

1/2 (x2)

1/2 (x2)

1/2 (x2)

5/8 (x2)

5/8 (x2)

Suction

in

7/8 (x2)

7/8 (x2)

7/8 (x2)

1 1/8 (x2)

1 1/8 (x2)

1 1/8 (x2)

1 1/8 (x2)

AT-15/15

AT-15/15

AT-15/15

AT-12/12 SC2

AT-12/12 SC2

AT-15/15 SC2

AT-15/15 SC2

cfm

4200

4800

4800

5800

6200

8000

8000

l/s

1982

2265

2265

2737

2926

3775

3775

Type
Indoor Fan

Air Flow
Motor

Centrifugal DIDW Belt Drive

Code

Type
Size / Qty.

Operating Weight Approximate

Totally Enclosed, Class F insulated, IP55 Protected


kW / #

1.5 / 1

1.5 / 1

1.5 / 1

2.2 / 1

2.2 / 1

2.2 / 1

2.2 / 1

lbs

442

442

442

469

469

678

678

kg

200

200

200

213

213

308

308
Table 3

Notes:

(1) The capacity ratings are based on AHRI standard 210/240 & 340/360. Evaporator entering air conditions of 80F/67F (27C/19.5C)
dry bulb / wet bulb and condenser entering air temperature of 95F (35C) dry bulb.
(2) Evaporator entering air conditions of 80F/67F (27C/19.5C) dry bulb / wet bulb and condenser entering air temperature of
115F(46C) dry bulb.
(3) Connections are based on 25 ft maximum linear distance between the outdoor & indoor unit and 66 ft maximum lift.
(4) Refrigerant operating charge is for combined condensing unit with the matching air handling unit and 25 ft (7.6m) of interconnecting
refrigerant lines.
Capacity for condition (1) & (2) are gross which doesnt include the effect of evaporator fan motor heat.

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
CAPACITY RATINGS
Model
ACUM+
CADX-

050L
+
050L

060L
+
060L

070L
+
070L

085L
+
085L

100L
+
100L

110L
+
120L

120L
+
120L

AFR
cfm
l/s
(BPF)
1146
541
0.17
1700
802
0.22
2292
1082
0.26
1597
754
0.17
2000
944
0.19
3193
1507
0.26
1597
754
0.17
2400
1133
0.22
3193
1507
0.26
1719
811
0.17
2800
1321
0.23
3438
1622
0.26
2196
1036
0.17
3000
1416
0.21
4392
2073
0.26
2196
1036
0.09
3600
1699
0.13
4392
2073
0.14
2196
1036
0.09
3600
1699
0.13
4392
2073
0.14

Condenser Entering Air Temperature


EWB
F
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72

C
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2

Total Capacity
MBh kW
43.4 12.7
47.2 13.8
50.8 14.9
46.5 13.6
50.7 14.9
54.7
16
48.5 14.2
53
15.5
57.1 16.8
56
16.4
61.2 17.9
66
19.3
58.4 17.1
63.8 18.7
68.7 20.1
62.5 18.3
68.2
20
73.2 21.5
61.5
18
66.9 19.6
71.9 21.1
66.2 19.4
72.1 21.1
77.5 22.7
68.9 20.2
75.1
22
80.8 23.7
70.9 20.8
77.1 22.6
83
24.3
77.8 22.8
84.8 24.9
91.5 26.8
80.2 23.5
87.5 25.6
94.5 27.7
83.7 24.5
91
26.7
97.9 28.7
88.6
26
96.5 28.3
103.9 30.5
93.7 27.5
102.2 29.9
110 32.3
95.6
28
104 30.5
111.9 32.8
106.5 31.2
116
34
124.4 36.5
110 32.2
119.7 35.1
128.2 37.6
102 29.9
111.3 32.6
120.1 35.2
115.1 33.7
125.8 36.9
135.5 39.7
119.3 35
130.4 38.2
140.4 41.1

95F (35C)
Sensible Capacity
MBh kW
36.1 10.6
30.3
8.9
24.3
7.1
44.1 12.9
36.3 10.6
28.2
8.3
48.5 14.2
41.9 12.3
31.8
9.3
48.3 14.2
40.5 11.9
32.2
9.4
54.4 15.9
44.9 13.2
35
10.3
62.5 18.3
56.4 16.5
42.3 12.4
50.8 14.9
42.7 12.5
34.3 10.1
62.4 18.3
51.3
15
39.9 11.7
68.9 20.2
58.8 17.2
44.7 13.1
56.8 16.6
48.1 14.1
39
11.4
72.4 21.2
59.7 17.5
46.6 13.7
80.2 23.5
65.7 19.3
50.5 14.8
69.4 20.3
58.4 17.1
46.8 13.7
81.3 23.8
67.2 19.7
52.5 15.4
93.7 27.5
80.5 23.6
61.1 17.9
77.8 22.8
65.9 19.3
53.3 15.6
101.8 29.8
83.7 24.5
64.8
19
110 32.2
92.4 27.1
70.4 20.6
80.8 23.7
69
20.2
56.4 16.5
105.4 30.9
87.4 25.6
68.6 20.1
117.6 34.5
96.4 28.2
74.3 21.8

105F (41C)
PI*
kW
3.6
3.6
3.7
3.6
3.7
3.8
3.7
3.8
3.9
4.1
4.2
4.3
4.1
4.2
4.3
4.2
4.3
4.4
4.9
5.1
5.2
5.1
5.2
5.3
5.1
5.3
5.3
5.3
5.4
5.5
5.4
5.5
5.6
5.4
5.6
5.7
6.1
6.3
6.4
6.2
6.4
6.5
6.3
6.5
6.7
6.8
7
7.2
7
7.3
7.7
7.1
7.5
8
7.8
7.9
8.1
8
8.2
8.3
8.1
8.2
8.4

MBh
41.8
45.5
49.1
44.8
48.9
52.7
46.7
51
55
53.9
59
63.6
56.1
61.4
66.1
59.9
65.5
59.1
64.4
69.3
63.5
69.3
74.7
66.1
72.1
77.7
68.3
74.4
80.2
74.8
81.7
88.3
77.1
84.3
91.2
80.8
87.9
94.7
85.4
93.1
100.3
90.2
98.4
105.9
92.3
100.6
108.2
102.6
111.8
120.1
105.9
115.3
123.7
98.5
107.6
116.2
110.8
121.2
130.7
114.7
125.5
135.2

kW
12.2
13.3
14.4
13.1
14.3
15.4
13.7
14.9
16.1
15.8
17.3
18.6
16.4
18
19.4
17.6
19.2
17.3
18.9
20.3
18.6
20.3
21.9
19.4
21.1
22.8
20
21.8
23.5
21.9
23.9
25.9
22.6
24.7
26.7
23.7
25.8
27.8
25
27.3
29.4
26.4
28.8
31
27.1
29.5
31.7
30.1
32.8
35.2
31
33.8
36.2
28.9
31.5
34
32.5
35.5
38.3
33.6
36.8
39.6

MBh
35.4
29.7
23.7
43.4
35.6
27.6
46.7
41.2
31.1
47.4
39.6
31.4
53.4
44
34.2
59.9
55.5
49.7
41.7
33.4
61.3
50.3
38.9
66.1
57.8
43.7
55.6
47
37.9
71.2
58.5
45.5
77.1
64.6
49.4
68.1
57.1
45.7
79.9
65.9
51.3
90.2
79.2
59.8
76.3
64.4
51.9
100.1
82.1
63.4
105.9
90.8
68.9
79.2
67.4
54.9
103.6
85.6
66.9
114.7
94.6
72.7

kW
10.4
8.7
7
12.7
10.4
8.1
13.7
12.1
9.1
13.9
11.6
9.2
15.7
12.9
10
17.6
16.3
14.6
12.2
9.8
18
14.7
11.4
19.4
16.9
12.8
16.3
13.8
11.1
20.9
17.2
13.3
22.6
18.9
14.5
20
16.7
13.4
23.4
19.3
15
26.4
23.2
17.5
22.4
18.9
15.2
29.4
24.1
18.6
31
26.6
20.2
23.2
19.8
16.1
30.4
25.1
19.6
33.6
27.7
21.3

PI*
kW
4
4.1
4.2
4.1
4.2
4.3
4.1
4.3
4.4
4.7
4.7
4.8
4.7
4.8
4.9
4.8
4.9
5.6
5.7
5.9
5.7
5.9
6
5.8
5.9
6.1
6
6.1
6.2
6.1
6.3
6.4
6.2
6.3
6.5
7
7.1
7.3
7.1
7.2
7.4
7.2
7.4
7.6
7.8
7.9
8.2
8
8.3
8.8
8.1
8.5
9.1
8.9
9.1
9.2
9.1
9.3
9.5
9.2
9.4
9.6

MBh
40.2
43.9
47.3
43
47
50.6
44.8
48.9
52.7
51.5
56.5
61.1
53.6
58.8
63.6
57.2
62.8
56.6
61.8
66.7
60.8
66.5
71.7
63.2
69.2
74.6
65.3
71.4
77.2
71.5
78.4
84.9
73.7
80.9
87.6
77.6
84.7
91.3
82
89.6
96.4
86.5
94.4
101.3
89
97
104.4
98.6
107.6
115.8
101.6
110.9
94.5
103.4
111.8
106
116.2
125.7
109.7
120.3
130.1

kW
11.8
12.9
13.9
12.6
13.8
14.8
13.1
14.3
15.5
15.1
16.6
17.9
15.7
17.2
18.6
16.8
18.4
16.6
18.1
19.6
17.8
19.5
21
18.5
20.3
21.9
19.1
20.9
22.6
21
23
24.9
21.6
23.7
25.7
22.7
24.8
26.7
24
26.3
28.2
25.4
27.7
29.7
26.1
28.4
30.6
28.9
31.5
34
29.8
32.5
27.7
30.3
32.8
31.1
34.1
36.8
32.1
35.3
38.1

115F (46C)
Sensible Capacity
MBh kW
34.7 10.2
29
8.5
23.1
6.8
42.7 12.5
34.9 10.2
26.9
7.9
44.8 13.1
40.5 11.9
30.4
8.9
46.4 13.6
38.6 11.3
30.5
8.9
52.4 15.3
43
12.6
33.4
9.8
57.2 16.8
54.5
16
48.6 14.2
40.7 11.9
32.5
9.5
60.2 17.6
49.3 14.4
38
11.1
63.2 18.5
56.8 16.6
42.7 12.5
54.2 15.9
45.8 13.4
36.9 10.8
69.8 20.5
57.3 16.8
44.4
13
73.7 21.6
63.4 18.6
48.3 14.2
66.7 19.6
55.9 16.4
44.5
13
78.5
23
64.5 18.9
50
14.7
86.5 25.4
77.8 22.8
58.4 17.1
74.7 21.9
62.9 18.4
50.5 14.8
98.5 28.9
80.5 23.6
62
18.2
101.6 29.8
89.3 26.2
77.3 22.6
65.6 19.2
53.2 15.6
101.5 29.8
83.8 24.6
65.2 19.1
109.7 32.1
92.7 27.2
71
20.8

PI*
kW
4.5
4.6
4.7
4.6
4.7
4.8
4.6
4.7
4.9
5.3
5.3
5.4
5.3
5.4
5.5
5.4
5.5
6.3
6.4
6.5
6.4
6.5
6.8
6.4
6.6
6.9
6.9
7
7.1
7
7.1
7.2
7
7.1
7.3
7.9
8
8.2
8
8.1
8.3
8.1
8.3
8.6
8.9
9.1
9.3
9.1
9.4
9.9
9.2
9.6
10.2
10.3
10.4
10.3
10.5
10.7
10.4
10.6
10.8

118.4F (48C)
Total Capacity Sensible Capacity
MBh kW MBh kW
39.6 11.6 34.4 10.1
43.3 12.7 28.8
8.4
46.7 13.7 22.9
6.7
42.4 12.4 42.4 12.4
46.3 13.6 34.7 10.2
50
14.6 26.7
7.8
44.1 12.9 44.1 12.9
48.2 14.1 40.2 11.8
50.7 14.9
46
13.5
55.7 16.3 38.3 11.2
60.3 17.7 30.2
8.9
52.8 15.5
52
15.2
58
17
42.7 12.5
62.8 18.4 33.1
9.7
56.3 16.5 56.3 16.5
61.9 18.1 54.2 15.9
55.8 16.3 48.2 14.1
61
17.9 40.4 11.8
65.8 19.3 32.2
9.4
59.9 17.6 59.8 17.5
65.6 19.2 48.9 14.3
70.8 20.7 37.7
11
62.3 18.2 62.3 18.2
68.2
20
56.4 16.5
73.6 21.6 42.4 12.4
64.3 18.8 53.8 15.8
70.4 20.6 45.3 13.3
76.2 22.3 36.5 10.7
70.4 20.6 69.4 20.3
77.3 22.7 56.9 16.7
83.8 24.6 44.1 12.9
72.5 21.3 72.5 21.3
79.7 23.4 62.9 18.4
86.4 25.3 47.9
14
76.5 22.4 66.2 19.4
83.6 24.5 55.4 16.2
90.1 26.4 44.1 12.9
80.9 23.7 78.1 22.9
88.4 25.9 64.1 18.8
95
27.8 49.6 14.5
85.3
25
85.3
25
93
27.3 77.3 22.7
87.8 25.7 74.2 21.7
95.7 28.1 62.4 18.3
103.1 30.2
50
14.7
97.2 28.5 97.2 28.5
106.1 31.1
80
23.4
114.4 33.5 61.5
18
100.1 29.3 100.1 29.3
109.4 32.1 88.7
26
93
27.3 76.6 22.4
101.9 29.9
65
19
110.3 32.3 52.7 15.4
104.3 30.6 100.8 29.6
114.5 33.6 83.1 24.4
124 36.3 64.7
19
107.9 31.6 107.9 31.6
118.6 34.8
92
27
128.4 37.6 70.4 20.6

PI*
kW
4.7
4.8
4.8
4.7
4.8
4.9
4.8
4.9
5.5
5.5
5.6
5.5
5.6
5.7
5.5
5.7
6.5
6.6
6.8
6.6
6.8
7
6.7
6.9
7.2
7.2
7.3
7.3
7.3
7.4
7.5
7.3
7.4
7.6
8.2
8.3
8.5
8.3
8.4
8.7
8.4
8.6
9.3
9.5
9.7
9.5
9.8
10.2
9.6
10
10.6
10.7
10.8
10.7
10.9
11.1
10.8
11
11.3

125F (52C)
Total Capacity Sensible Capacity
MBh kW MBh kW
38.5 11.3
34
10
42.2 12.4 28.3
8.3
46.4 13.6 22.8
6.7
41.2 12.1 41.2 12.1
46
13.5 34.6 10.1
49.6 14.5 26.6
7.8
42.9 12.6 42.9 12.6
47.9
14
40.1 11.8
49.2 14.4 45.4 13.3
54.2 15.9 37.7 11.1
58.7 17.2 29.7
8.7
51.2
15
51.2
15
56.4 16.5 42.1 12.3
61.1 17.9 32.5
9.5
54.6
16
54.6
16
60.1 17.6 53.6 15.7
54.2 15.9 47.5 13.9
59.4 17.4 39.8 11.7
65.4 19.2
32
9.4
58.2 17.1 58.2 17.1
65.1 19.1 48.8 14.3
70.3 20.6 37.5
11
60.5 17.7 60.5 17.7
67.7 19.9 56.3 16.5
73.1 21.4 42.3 12.4
62.3 18.3 52.9 15.5
68.4 20.1 44.6 13.1
74.2 21.7 35.8 10.5
68.2
20
68.2
20
75.1
22
56.1 16.5
81.5 23.9 43.3 12.7
70.3 20.6 70.3 20.6
77.5 22.7 62.2 18.2
84
24.6 47.2 13.8
74.5 21.8 65.3 19.2
81.5 23.9 54.6
16
87.8 25.7 43.3 12.7
78.7 23.1 77.1 22.6
86
25.2 63.2 18.5
92.4 27.1 48.7 14.3
82.9 24.3 82.9 24.3
90.4 26.5 76.4 22.4
85.5 25.1 73.1 21.4
93.3 27.3 61.4
18
100.6 29.5 49.1 14.4
94.4 27.7 94.4 27.7
103.3 30.3 78.9 23.1
111.6 32.7 60.6 17.8
97.3 28.5 97.3 28.5
106.4 31.2 87.7 25.7
90.3 26.5 75.3 22.1
99.1
29
63.8 18.7
107.4 31.5 51.6 15.1
101.2 29.6 99.5 29.2
111.4 32.6 81.9
24
120.8 35.4 63.6 18.6
104.7 30.7 104.7 30.7
115.3 33.8 90.8 26.6
125 36.6 69.3 20.3

PI*
kW
5
5
4.9
5
4.9
5
5.1
5
5.8
5.9
6
5.9
5.9
6.1
5.9
6.1
6.9
7
6.9
7
6.9
7.1
7
7
7.2
7.7
7.8
7.9
7.8
7.9
8
7.8
7.9
8.1
8.8
8.9
9
8.8
9
9.2
8.9
9.1
10
10.2
10.4
10.2
10.5
10.9
10.3
10.6
11.4
11.5
11.5
11.5
11.6
11.9
11.5
11.7
12.1

Table 4

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
CAPACITY RATINGS
Model
ACUM+
CADX-

130L
+
150L

145L
+
150L

160L
+
150L

180L
+
180L

205L
+
180L

240L
+
240L

260L
+
240L

AFR
cfm
l/s
(BPF)
3208
1514
0.17
4200
1982
0.2
6417
3028
0.26
3208
1514
0.17
4800
2265
0.22
6417
3028
0.26
3208
1514
0.17
4800
2265
0.22
6417
3028
0.26
4604
2173
0.19
5800
2737
0.22
7792
3677
0.26
4604
2173
0.19
6200
2926
0.22
7792
3677
0.26
6292
2969
0.19
8000
3775
0.22
10649
5025
0.26
6292
2969
0.19
8000
3775
0.22
10649
5025
0.26

Condenser Entering Air Temperature


EWB
F
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72
62
67
72

C
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2
16.7
19.4
22.2

Total Capacity
MBh
kW
116
34
126.5 37.1
136.5
40
121.8 35.7
133.1
39
143.7 42.1
129.6
38
141.9 41.6
153.6
45
124.2 36.4
135.1 39.6
145.3 42.6
133.6 39.2
145.5 42.7
156.6 45.9
139.3 40.8
151.8 44.5
163.4 47.9
128.3 37.6
139.6 40.9
150.3 44.1
138.4 40.6
151
44.2
162.8 47.7
144.5 42.4
157.9 46.3
170.5
50
152.8 44.8
166.4 48.8
179.4 52.6
159
46.6
173.4 50.8
187.3 54.9
165.8 48.6
181.2 53.1
196
57.4
165.4 48.5
179.8 52.7
193.4 56.7
174.4 51.1
189.8 55.6
204.4 59.9
180.3 52.8
196.4 57.6
211.5
62
206.5 60.5
224.6 65.8
241.5 70.8
214.9
63
234
68.6
251.8 73.8
223.5 65.5
243.5 71.4
262.2 76.9
222.4 65.2
241.7 70.8
259.5 76.1
232.1
68
252.4
74
270.7 79.3
242
70.9
263
77.1
281.8 82.6

95F (35C)
Sensible Capacity
MBh
kW
98.6
28.9
82.7
24.2
66.1
19.4
113.3 33.2
93.6
27.4
73.2
21.5
129.6
38
115.1 33.7
87
25.5
102.3
30
86.1
25.2
69.2
20.3
125.4 36.8
103.2 30.3
80.3
23.5
139.3 40.8
118.6 34.7
90.1
26.4
104.1 30.5
88
25.8
71.1
20.8
127.4 37.3
105.3 30.9
82.4
24.1
144.5 42.4
120.7 35.4
92.3
27.1
133.6 39.2
111.3 32.6
88.2
25.9
150.6 44.1
123.9 36.3
96.4
28.3
165.8 48.6
142.9 41.9
108.6 31.8
139.1 40.8
116.6 34.2
93.1
27.3
161.7 47.4
133.3 39.1
103.9 30.5
180.3 52.8
148.3 43.5
113.6 33.3
181.6 53.2
151
44.3
119.3
35
205.7 60.3
168.8 49.5
130.8 38.3
223.5 65.5
193.8 56.8
146.7
43
188.5 55.2
157.7 46.2
125.6 36.8
212.8 62.4
175.7 51.5
137
40.2
242
70.9
200.7 58.8
152.9 44.8

PI*
kW
8.3
8.5
8.7
8.4
8.7
8.9
8.6
8.8
9.1
9.6
9.9
10.1
9.8
10.1
10.3
10
10.2
10.3
9.4
9.6
9.7
9.6
9.7
9.9
9.7
9.8
10.1
11.1
11.3
11.6
11.2
11.5
11.8
11.3
11.7
12
12.1
12.4
12.7
12.3
12.6
12.9
12.4
12.8
13.1
14.4
14.8
15.1
14.6
15
15.4
14.7
15.2
15.6
16.7
17.1
17.5
16.9
17.4
17.8
17.1
17.6
18.1

Total Capacity
MBh
kW
111.7 32.7
122.1 35.8
131.8 38.6
117.2 34.4
128.3 37.6
138.7 40.6
124.6 36.5
136.6
40
147.8 43.3
119.5
35
130.2 38.2
140.2 41.1
128.4 37.6
140.1 41.1
151
44.2
133.7 39.2
146
42.8
157.3 46.1
123.6 36.2
134.9 39.5
145.5 42.7
133.4 39.1
145.8 42.7
157.5 46.2
139.2 40.8
152.4 44.7
164.8 48.3
146.7
43
160.2
47
173
50.7
152.6 44.7
166.9 48.9
180.5 52.9
159
46.6
174.2 51.1
188.7 55.3
159.6 46.8
173.8 50.9
187.1 54.8
168.2 49.3
183.3 53.7
197.4 57.9
173.8 50.9
189.5 55.5
204
59.8
198.9 58.3
216.6 63.5
233.2 68.4
206.8 60.6
225.5 66.1
243
71.2
214.9
63
234.5 68.7
252.9 74.1
213.6 62.6
232.5 68.1
249.9 73.2
222.8 65.3
242.5 71.1
260.4 76.3
68
232
252.5
74
270.8 79.4

105F (41C)
Sensible Capacity
MBh
kW
96.7
28.4
80.9
23.7
64.5
18.9
111.4 32.7
91.8
26.9
71.5
21
124.6 36.5
113.2 33.2
85.2
25
100.2 29.4
84.2
24.7
67.4
19.8
123.3 36.1
101.2 29.7
78.5
23
133.7 39.2
116.5 34.2
88.2
25.8
102
29.9
86.1
25.2
69.3
20.3
125.3 36.7
103.3 30.3
80.6
23.6
139.2 40.8
118.8 34.8
90.5
26.5
131
38.4
108.9 31.9
86
25.2
148
43.4
121.5 35.6
94.2
27.6
159
46.6
140.4 41.2
106.3 31.2
136.6
40
114.2 33.5
90.9
26.6
159.1 46.6
130.8 38.3
101.6 29.8
173.8 50.9
145.8 42.7
111.2 32.6
178.3 52.3
148
43.4
116.5 34.1
202.4 59.3
165.7 48.6
127.9 37.5
214.9
63
190.6 55.9
143.8 42.1
184.7 54.1
154.1 45.2
122.2 35.8
209
61.2
172
50.4
133.6 39.2
232
68
197
57.7
149.4 43.8

PI*
kW
9.5
9.7
9.9
9.7
9.9
10.1
9.8
10.1
10.3
10.9
11.2
11.4
11.1
11.4
11.6
11.3
11.5
11.8
10.8
11
11.1
10.9
11.1
11.3
11
11.2
11.5
12.6
12.9
13.2
12.7
13
13.4
12.9
13.2
13.6
13.9
14.1
14.4
14
14.3
14.7
14.1
14.5
14.8
16.5
16.9
17.3
16.7
17.1
17.6
16.9
17.4
17.8
19
19.5
19.9
19.3
19.7
20.2
19.5
20
20.4

Total Capacity
MBh
kW
107.1 31.4
117.4 34.4
126.9 37.2
112.4 32.9
123.2 36.1
133.2 39.1
119.3
35
130.9 38.4
114.5 33.6
125.1 36.7
134.9 39.5
122.9
36
134.5 39.4
145.1 42.5
127.9 37.5
140
41
151
44.3
118.4 34.7
129.7
38
140.3 41.1
127.8 37.5
140.2 41.1
151.9 44.5
133.4 39.1
146.6
43
158.9 46.6
140.1 41.1
153.7
45
166.4 48.8
145.8 42.7
160
46.9
173.4 50.8
151.9 44.5
167
49
181
53
153.4
45
167.4 49.1
180.4 52.9
161.6 47.4
176.4 51.7
189.9 55.7
166.9 48.9
182.2 53.4
195.9 57.4
190.6 55.9
208.1
61
224.5 65.8
198.1 58.1
216.5 63.5
233.7 68.5
205.7 60.3
225
66
204.2 59.8
222.7 65.3
239.8 70.3
212.7 62.4
232.2
68
249.9 73.2
221.4 64.9
241.7 70.8
259.8 76.2

115F (46C)
Sensible Capacity
MBh
kW
94.7
27.8
79.1
23.2
62.7
18.4
109.4 32.1
89.9
26.3
69.7
20.4
119.3
35
111.2 32.6
97.9
28.7
82.1
24.1
65.5
19.2
121
35.5
99.1
29.1
76.5
22.4
127.9 37.5
114.4 33.5
86.2
25.3
99.7
29.2
84
24.6
67.5
19.8
123
36.1
101.2 29.7
78.8
23.1
133.4 39.1
116.7 34.2
88.7
26
128.2 37.6
106.4 31.2
83.7
24.5
145.2 42.6
119
34.9
91.9
26.9
151.9 44.5
137.9 40.4
103.9 30.5
133.9 39.2
111.7 32.7
88.6
26
156.4 45.8
128.3 37.6
99.2
29.1
166.9 48.9
143.2
42
108.6 31.8
174.8 51.2
144.7 42.4
113.5 33.3
198.1 58.1
162.4 47.6
124.9 36.6
205.7 60.3
187.3 54.9
180.6 52.9
150.3
44
118.7 34.8
204.8
60
168.1 49.3
130.2 38.2
221.4 64.9
193.1 56.6
146
42.8

PI*
kW
10.9
11.1
11.3
11
11.2
11.4
11.1
11.4
12.3
12.5
12.8
12.5
12.8
13.1
12.6
12.9
13.4
12.4
12.5
12.7
12.5
12.6
12.8
12.6
12.7
12.9
14.3
14.5
14.8
14.4
14.7
15
14.5
14.8
15.2
15.8
16
16.2
15.9
16.1
16.5
16
16.3
16.7
18.9
19.3
19.7
19
19.5
19.9
19.2
19.7
21.6
22
22.3
21.8
22.1
22.5
21.9
22.3
22.7

Total Capacity
MBh
kW
105.6 30.9
115.8 33.9
125.2 36.7
110.7 32.5
121.5 35.6
131.4 38.5
117.5 34.4
128.9 37.8
112.8 33.1
123.3 36.1
133.2
39
121.1 35.5
132.6 38.9
143.1 41.9
126
36.9
138
40.5
148.9 43.6
116.6 34.2
127.9 37.5
138.6 40.6
125.9 36.9
138.3 40.5
150
44
131.4 38.5
144.6 42.4
156.8
46
137.9 40.4
151.5 44.4
164.1 48.1
143.5 42.1
157.7 46.2
170.9 50.1
149.6 43.8
164.5 48.2
178.3 52.3
151.3 44.3
165.3 48.4
178.1 52.2
159.3 46.7
174
51
187.3 54.9
164.5 48.2
179.7 52.7
193.1 56.6
187.7
55
205.1 60.1
221.5 64.9
195.1 57.2
213.4 62.6
230.6 67.6
202.6 59.4
221.8
65
201
58.9
219.4 64.3
236.5 69.3
209.4 61.4
228.7
67
246.4 72.2
217.9 63.9
238
69.8
256.2 75.1

118.4F (48C)
Sensible Capacity
MBh
kW
94.1
27.6
78.5
23
62.2
18.2
108.7 31.9
89.3
26.2
69.1
20.3
117.5 34.4
110.5 32.4
97.2
28.5
81.4
23.9
64.9
19
120.3 35.3
98.4
28.9
75.9
22.2
126
36.9
113.7 33.3
85.6
25.1
98.9
29
83.3
24.4
66.8
19.6
122.2 35.8
100.6 29.5
78.1
22.9
131.4 38.5
116
34
88
25.8
127.3 37.3
105.6
31
83
24.3
143.5 42.1
118.1 34.6
91.1
26.7
149.6 43.8
137
40.2
103.1 30.2
133
39
110.9 32.5
87.8
25.7
155.5 45.6
127.4 37.3
98.4
28.8
164.5 48.2
142.3 41.7
107.7 31.6
173.6 50.9
143.6 42.1
112.5
33
195.1 57.2
161.3 47.3
123.9 36.3
202.6 59.4
186.2 54.6
179.2 52.5
149
43.7
117.6 34.5
203.4 59.6
166.8 48.9
129
37.8
217.9 63.9
191.9 56.2
144.8 42.4

PI*
kW
11.4
11.5
11.7
11.4
11.6
11.9
11.5
11.8
12.7
13
13.2
12.9
13.2
13.6
13
13.4
14
12.9
13
13.2
13
13.2
13.3
13.1
13.2
13.4
14.9
15.1
15.3
14.9
15.2
15.5
15
15.3
15.8
16.4
16.6
16.8
16.5
16.7
17.1
16.6
16.9
17.4
19.7
20.1
20.5
19.9
20.3
20.7
20
20.5
22.4
22.8
23.1
22.6
22.9
23.2
22.7
23.1
23.4

Total Capacity
MBh
kW
102.6 30.1
112.7
33
122
35.7
107.5 31.5
118.2 34.6
127.8 37.4
114.1 33.4
125.2 36.7
109.5 32.1
120.1 35.2
129.9 38.1
117.6 34.5
129
37.8
139.5 40.9
122.4 35.9
134.3 39.4
148
43.4
113.3 33.2
124.6 36.5
135.3 39.6
122.3 35.8
134.8 39.5
146.4 42.9
127.7 37.4
140.9 41.3
153
44.8
133.8 39.2
147.3 43.2
159.7 46.8
139.1 40.8
153.3 44.9
166.2 48.7
145
42.5
159.8 46.8
147.3 43.2
161
47.2
173.6 50.9
155
45.4
169.4 49.7
182.3 53.4
159.9 46.9
174.8 51.2
187.6
55
182.3 53.4
199.7 58.5
216
63.3
189.5 55.5
207.7 60.9
224.8 65.9
196.7 57.6
215.8 63.3
194.9 57.1
213.3 62.5
230.2 67.5
203.1 59.5
222.3 65.2
239.7 70.3
211.3 61.9
231.3 67.8
249.1
73

125F (52C)
Sensible Capacity
MBh
kW
92.8
27.2
77.3
22.6
61
17.9
107.4 31.5
88
25.8
67.9
19.9
114.1 33.4
109.3
32
95.8
28.1
80.1
23.5
63.8
18.7
117.6 34.5
97.2
28.5
74.7
21.9
122.4 35.9
112.4
33
85.3
25
97.4
28.6
81.9
24
65.7
19.2
120.8 35.4
99.3
29.1
77
22.6
127.7 37.4
114.7 33.6
86.8
25.4
125.5 36.8
104
30.5
81.5
23.9
139.1 40.8
116.5 34.1
89.6
26.3
145
42.5
135.4 39.7
131.2 38.5
109.2
32
86.2
25.3
153.7
45
125.7 36.9
96.7
28.4
159.9 46.9
140.6 41.2
106
31.1
171.4 50.2
141.6 41.5
110.6 32.4
189.5 55.5
159.2 46.7
122
35.8
196.7 57.6
184.1
54
176.7 51.8
146.7
43
115.4 33.8
200.9 58.9
164.5 48.2
126.9 37.2
211.3 61.9
189.5 55.5
142.6 41.8

PI*
kW
12.2
12.3
12.5
12.2
12.4
12.7
12.3
12.6
13.6
13.8
14
13.7
14
14.4
13.8
14.2
14.2
13.9
14
14.1
14
14.1
14.2
14
14.2
14.3
15.9
16.1
16.3
15.9
16.2
16.5
16
16.3
17.6
17.7
17.9
17.6
17.8
18.2
17.7
17.9
18.5
21.1
21.5
21.9
21.3
21.7
22
21.5
21.9
23.9
24.2
24.4
24
24.3
24.5
24.2
24.4
24.7

Table 5

Notes:
1. See Page 2 for legend
2. Ratings are based on 80F (27C) return air dry bulb temperature.
3. Direct interpolation is permissible. Do not extrapolate.
4. SKM Computer Selection Software are available for quick and accurate selections..
5. Shaded area in gray are at 120F condenser entering air temperature.

* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data page 11 should be referred for the same.

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Fan Performance
ACUM+
CADX050L + 050L

060L + 060L

070L + 070L

085L + 085L

100L + 100L

110L + 120L

120L + 120L

130L + 150L

145L + 150L

160L + 150L

180L + 180L

205L + 180L

240L + 240L

260L + 240L

External Static Pressure in.wg (Pa)

Air Flow Rate

Internal Static
Pressure

cfm

l/s

in.wg

Pa

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1146

541

0.24

59.7

615

0.11

747

0.15

808

0.17

865

0.19

972

0.24

1069

0.29

1181

0.36

0.2 (50)

0.4 (100)

0.5 (125)

0.6 (150)

0.8 (200)

1.0 (250)

1.25 (312)

1700

802

0.51

127.8

787

0.27

886

0.33

933

0.35

979

0.38

1068

0.44

1152

0.51

1251

0.59

2292

1082

0.96

239.3

1010

0.61

1085

0.68

1122

0.72

1158

0.76

1230

0.83

1299

0.91

1383

1.01

1597

754

0.24

59.8

635

0.18

745

0.23

798

0.25

849

0.28

948

0.34

1040

0.39

1148

0.47

2000

944

0.36

90.2

737

0.32

827

0.37

871

0.40

915

0.43

1000

0.50

1082

0.56

1180

0.65

3193

1507

0.96

239.2

1098

1.17

1156

1.25

1184

1.29

1213

1.33

1270

1.42

1326

1.51

1395

1.63

1597

754

0.24

59.8

635

0.18

745

0.23

798

0.25

849

0.28

948

0.34

1040

0.39

1148

0.47

2400

1133

0.53

131.4

853

0.52

929

0.58

967

0.62

1004

0.65

1077

0.72

1149

0.80

1236

0.89

3193

1507

0.96

239.2

1098

1.17

1156

1.25

1184

1.29

1213

1.33

1270

1.42

1326

1.51

1395

1.63

1719

811

0.24

59.7

524

0.17

639

0.23

692

0.26

743

0.30

836

0.37

921

0.45

1017

0.55

2800

1321

0.62

155.7

724

0.55

801

0.63

838

0.68

875

0.72

947

0.82

1017

0.92

1100

1.06

3438

1622

0.96

239.3

863

0.96

926

1.06

957

1.12

988

1.17

1049

1.29

1108

1.40

1181

1.55

2196

1036

0.24

59.7

535

0.24

632

0.31

680

0.35

726

0.39

815

0.47

898

0.55

994

0.66

3000

1416

0.43

107.5

661

0.53

734

0.62

770

0.66

806

0.71

877

0.80

946

0.90

1030

1.03

4392

2073

0.96

239.2

920

1.55

970

1.67

995

1.73

1020

1.79

1069

1.91

1119

2.04

1180

2.20

2196

1036

0.28

69.7

554

0.26

652

0.33

699

0.36

744

0.40

832

0.48

913

0.57

1008

0.68

3600

1699

0.74

185.5

804

0.94

865

1.04

895

1.09

925

1.14

985

1.25

1044

1.36

1117

1.51

4392

2073

1.13

282.7

963

1.65

1013

1.77

1038

1.83

1063

1.90

1113

2.02

1162

2.15

1223

2.32

2196

1036

0.28

69.7

554

0.26

652

0.33

699

0.36

744

0.40

832

0.48

913

0.57

1008

0.68

3600

1699

0.74

185.5

804

0.94

865

1.04

895

1.09

925

1.14

985

1.25

1044

1.36

1117

1.51

4392

2073

1.13

282.7

963

1.65

1013

1.77

1038

1.83

1063

1.90

1113

2.02

1162

2.15

1223

2.32

3208

1514

0.24

59.7

458

0.35

534

0.44

571

0.49

608

0.54

678

0.65

745

0.77

823

0.93

4200

1982

0.40

98.6

552

0.70

612

0.81

641

0.87

670

0.93

728

1.05

784

1.19

852

1.36

6417

3028

0.96

239.2

797

2.31

837

2.47

857

2.55

877

2.63

916

2.80

954

2.97

1002

3.19

3208

1514

0.24

59.7

458

0.35

534

0.44

571

0.49

608

0.54

678

0.65

745

0.77

823

0.93

4800

2265

0.52

130.0

616

1.01

669

1.13

695

1.20

720

1.26

771

1.40

822

1.54

883

1.73

6417

3028

0.96

239.2

797

2.31

837

2.47

857

2.55

877

2.63

916

2.80

954

2.97

1002

3.19

3208

1514

0.24

59.7

458

0.35

534

0.44

571

0.49

608

0.54

678

0.65

745

0.77

823

0.93

4800

2265

0.52

130.0

616

1.01

669

1.13

695

1.20

720

1.26

771

1.40

822

1.54

883

1.73

6417

3028

0.96

239.2

797

2.31

837

2.47

857

2.55

877

2.63

916

2.80

954

2.97

1002

3.19

4604

2173

0.29

71.1

688

0.75

735

0.83

782

0.92

872

1.09

957

1.28

1056

1.53

5800

2737

0.46

114.7

699

1.09

778

1.27

817

1.37

856

1.46

932

1.67

1006

1.88

1094

2.16

7792

3677

0.87

215.7

902

2.50

961

2.73

990

2.84

1020

2.96

1078

3.21

1136

3.47

1207

3.81

4604

2173

0.29

71.1

688

0.75

735

0.83

782

0.92

872

1.09

957

1.28

1056

1.53

6200

2926

0.53

132.4

739

1.31

813

1.50

849

1.60

886

1.70

958

1.91

1028

2.14

1113

2.43

7792

3677

0.87

215.7

902

2.50

961

2.73

990

2.84

1020

2.96

1078

3.21

1136

3.47

1207

3.81

6292

2969

0.29

71.1

578

0.97

617

1.08

655

1.19

729

1.43

799

1.68

880

2.01

8000

3775

0.47

117.0

595

1.45

660

1.68

691

1.80

723

1.93

785

2.20

845

2.49

917

2.87

10649

5025

0.87

215.7

762

3.22

811

3.52

835

3.67

860

3.83

908

4.15

955

4.49

1014

4.94

6292

2969

0.29

71.1

578

0.97

617

1.08

655

1.19

729

1.43

799

1.68

880

2.01

8000

3775

0.47

117.0

595

1.45

660

1.68

691

1.80

723

1.93

785

2.20

845

2.49

917

2.87

10649

5025

0.87

215.7

762

3.22

811

3.52

835

3.67

860

3.83

908

4.15

955

4.49

1014

4.94

RPM RANGE

778
to
1004

812
to
1047
747
to
931
702
to
875

798
to
995

564
to
704

625
to
780

705
to
879

629
to
784

Table 6

Notes:
Areas shaded in blue indicate factory setting of rpm.
Areas shaded in gray indicate operating range outside the standard motor. Shift one step larger motor size in this area.
Internal static pressure is based on pressure drops through evaporator coil, fan casing & 1 washable flate filter.
The shown rpm range is with standard pulleys combination.

10

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
ELECTRICAL DATA
POWER SUPPLY 380-415V/3Ph/50Hz
Unit Characteristic

Compressor

Condenser Fan motor

Model
ACUM-

MFA

MCA

ICF

QTY

RLA

LRA

QTY

FLA

LRA

Model
CADX-L

050L
060L
070L
085L
100L
110L
120L
130L
145L
160L
180L
205L
240L
260L

25
32
32
50
50
40
40
40
50
63
63
80
80
100

15
18
21
27
28
30
30
30
35
41
48
51
56
62

66
82
109
103
119
83
93
93
122
126
124
147
156
159

1
1
1
1
1
2
2
2
2
2
2
2
2
2

8
10
12
16
17
10
10
10
12
14
16
17
19
22

62
74
101
95
111
66
74
74
101
100
95
111
118
118

1
1
1
1
1
2
2
2
2
2
2
2
2
2

0.7
1.7
1.7
1.7
1.7
0.7
0.9
0.9
0.9
1.7
1.7
2.8
2.8
2.8

2.5
5.8
5.8
5.8
5.8
2.5
4.0
4.0
4.0
5.8
5.8
11.0
11.0
11.0

050L
060L
070L
085L
090L
120L
120L
150L
150L
150L
180L
180L
240L
240L

Evaporator Fan Motor


FLA
1.7
1.7
2.0
2.6
2.6
3.7
3.7
3.7
3.7
3.7
5.2
5.2
5.2
5.2

LRA
6.7
6.7
8.6
11.6
11.6
17.1
17.1
17.1
17.1
17.1
25.6
25.6
25.6
25.6
Table 7

POWER SUPPLY 440V/3Ph/50Hz


Compressor

Unit Characteristic

Condenser Fan motor

Model
ACUM-

MFA

MCA

ICF

QTY

RLA

LRA

QTY

FLA

LRA

Model
CADX-L

050L
060L
070L
085L
100L
110L
120L
130L
145L
160L
180L
205L
240L
260L

25
32
32
50
50
40
40
40
50
63
63
80
80
100

15
18
21
27
27
29
30
30
34
41
47
50
55
62

66
81
109
103
119
82
92
92
121
125
123
146
155
158

1
1
1
1
1
2
2
2
2
2
2
2
2
2

8
10
12
16
17
10
10
10
12
14
16
17
19
22

62
74
101
95
111
66
74
74
101
100
95
111
118
118

1
1
1
1
1
2
2
2
2
2
2
2
2
2

0.7
1.7
1.7
1.7
1.7
0.7
0.9
0.9
0.9
1.7
1.7
2.8
2.8
2.8

2.5
5.8
5.8
5.8
5.8
2.5
4.0
4.0
4.0
5.8
5.8
11.0
11.0
11.0

050L
060L
070L
085L
090L
120L
120L
150L
150L
150L
180L
180L
240L
240L

Evaporator Fan Motor


FLA

LRA

1.5
1.5
1.8
2.3
2.3
3.2
3.2
3.2
3.2
3.2
4.5
4.5
4.5
4.5

6.0
6.0
8.2
11.2
11.2
16.0
16.0
16.0
16.0
16.0
25.0
25.0
25.0
25.0
Table 8

Legend
MFA Maximum Fuse Amps (for fuse sizing), complies with
NEC Article 440-22 & 430-52.
MCA Minimum Circuit Amps.(for wire sizing), complies with
NEC article 440-33.
ICF

RLA
LRA
FLA

Rated Load Amps. (at worst operating condition)


Locked Rotor Amps
Full Load Amps

Maximum Instantaneous Current Flow

Note :
Voltage imbalance not to exceed 2 % of the rated voltage

You name it.....We cool it

11

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Typical Wiring Diagram
ACUM- Models: 050L - 100L
PTB

** L1
L2
L3
N

C1

C2

PROVIDE OVERCURRENT, EARTH FAULT PROTECTION,


**SHORT
CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY

C3

LOCAL & NATIONAL ELECTRIC CODE.

T3

T1

OL2

T2

CM

FIELD WIRING
BY OTHERS

O L3
Y

LEGEND

CFM

CF1

CF2

2A

4A

C1

TH (BY O THERS)

CS

EFM

C1

CADX-L

C3

CR1

HPS

MODEL: ACUL-51050,51060,51070,
51085 & 51095

OL2
M

WIRING DIAGRAM SHOWN IN


*TYPICAL
SUITABLE FOR 380~415V/3Ph/50Hz ONLY.

LPS

OL3

FOR 440V/3Ph/50Hz PLEASE CONSULT SKM.

TDR

CR1

CR2

CONTACTOR
CRANK CASEHEATER
CONTROL FUSE
CONDENSER FAN MOTOR
COMPRESSOR MOTOR
CONTROL SWITCH
EVAPORATOR FAN MOTOR
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
OVERLOAD RELAY
POWER TERMINAL BLOCK
TRANSFORMER
THERMOSTAT
TIME DELAY RELAY
FIELD WIRING AND
FIELD SUPPLIED DEVICES

CR2

24V

CCH

220V-240V

TFR

C
CCH
CF
CFM
CM
CS
EFM
HPS
LPS
OL
PTB
TFR
TH
TDR
------

C3

TDR

C1

C2

N
E

CONTROL CIRCUIT

ACUM- Models: 110L - 260L

**L1

POWER SUPPLY (V/Ph/Hz)

PTB

PROVIDE OVERCURRENT, EARTH FAULT PROTECTION,


** SHORT
CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY

L2
L3
N

LOCAL & NATIONAL ELECTRIC CODE.

C1

C2

C3

C4

C5

L EGE ND
T1

T3

T1

T2

T3
T2

OL3

OL4

FIELD WIRING
BY OTHERS

OL5
R Y B

CM1

CFM2

CFM1

CM2
CF2

CF1

10A

2A
C1

C2

Y1

CS2

CS1

TH (BY OTHERS)

C1

C2

EFM

Y2

CADX-L
C5

C5

CR2

CR3

HPS1

HPS2

CR1
24V

220V-240V

CCH2

CCH1

TFR
FCS1

C
CCH
CF
CFM
CM
CS
EFM
FCS
HPS
LPS
OL
PTB
TFR
TH
TDR
------

CONTACTOR
CRANK CASE HEATER
CONTROL FUSE
CONDENSER FAN MOTOR
COMPRESSOR MOTOR
CONTROL SWITCH
EVAPORATOR FAN MOTOR
FAN CYCLING SWITCH
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
OVERLOAD RELAY
POWER TERMINAL BLOCK
TRANSFORMER
THERMOSTAT
TIME DELAY RELAY
FIELD WIRING AND
FIELD SUPPLIED DEVICES

FCS2

WIRING DIAGRAM SHOWN IN


*TYPICAL
SUITABLE FOR 380~415V/3Ph/50Hz ONLY.

FOR 440V/3Ph/50Hz PLEASE CONSULT SKM.

LPS2

LPS1

OL5

OL3
TDR1

CR1

CR2

CR3

C5

TDR1

C1

TDR2

C2

C3

N
E

12

OL4

TDR2

CONTROL CIRCUIT

You name it.....We cool it

C4

MODELS: ACUL- 52110, 52120,


52145, 52160,
52180, 52205,
52225, 52240, 52260

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Condensing Unit Dimensional Data
6
[152]

Models: ACUM- 050L


1

4-0.79[20]HOLES
FOR ANCHOR BOLTS

L E GE ND

A1
A3

1- CONDENSER COIL
2- CONDENSER FAN
3- CONTROL PANEL
4- COMPRESSOR

A4

A2
6
[152]

ALL DIMENSIONS ARE IN INCHES [mm]


A1-A4 ARE LOADING POINTS
28
[711]

30
[762]

3
42.28
[1074]
40.31
[1024]

ACCESS FOR
COMPRESSOR
SUC.

POWER SOURCE
HOLE 1 [25]
CONTROL CIRCUIT
HOLE 0.75 [19]

LIQ.

1.6
[40]

1.97
[50]

4
28
[711]

8
[203]

2
[50]

6
[152]

Models: ACUM- 060L, 070L, 085L & 100L


2
[51]
A1

LEGEND

A3

1- CONDENSER COIL
2- CONDENSER FAN
3- CONTROL PANEL

4- COMPRESSOR
ALL DIMENSIONS ARE IN INCHES [mm]
A1-A4 ARE LOADING POINTS

A4

6
[152]

A2

38
[965]

38
[965]

1.97
[50]

47.99
[1219]
40.31
[1024]

POWER SOURCE
HOLE 1 [25]

SUC.
LIQ.

1.6
[40]

4
38
[965]

1.6
[40]

CONTROL CIRCUIT
HOLE 0.75 [19]

11
[279]

You name it.....We cool it

2
[50]

ACCESS FOR
COMPRESSOR

13

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Condensing Unit Dimensional Data
Models: ACUM- 110L, 120L, 130L, 145L, 160 & 180L
MODEL: ACUM- 110L, 120L, 130L, 145L, 160 & 180L
10
[254]

LEGEN D
A1

A3

1- CONDENSER COIL
2- CONDENSER FAN
4-0.79[20] HOLES
FOR ANCHOR BOLTS

3- CONTROL PANEL
4- COMPRESSOR
ALL DIMENSIONS ARE IN INCHES [mm]
A1-A4 ARE LOADING POINTS

ACCESS
145mm FOR MODELS 160L & 180L
*ADD
FOR UPWARD CONDENSER FAN
1

M O DE LS A CUM L

DIMENSION

A4

10
[254]

A2

110L

120L

130L

145L

160L

180L

16.4
[416]

16.4
[416]

16.4
[416]

16.4
[416]

8.4
[213]

8.4
[213]

44.25
[1124]
40.31
[1024]

43
[1092]
AIR OUT

AIR IN

RIGGING HOLES
0.79 [20] x 4Nos.

SUC. #1
LIQ. #1

6
[152]

3.94
[100]

74
[1880]

SUC. #2
LIQ. #2
CONTROL CIRCUIT
HOLE 0.75[19]

ACCESS
POWER SOURCE
HOLE 1 [25]

Models: ACUM- 205L, 240L & 260L


10
[254]

4-0.79[20] HOLES
FOR ANCHOR BOLTS
A1

A2

ACCESS

10
[254]

A4

A3

43
[1092]

80
[2032]

AIR IN

9.72
[247]

57.96
[1472]
48.31
[1227]

14

6
[152]

3.94
[100]

4
RIGGING HOLES
0.79[20] x 4Nos.

SUC. #1
LIQ. #1

CONTROL CIRCUIT
HOLES 1 [25]
POWER SOURCE
HOLES 1 1/2 [38]

You name it.....We cool it

SUC. #2
LIQ. #2

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Air Handling Unit Dimensional Data
Models: CADX-050L to 180L
DIMENSIONS
B

050L

45
48
[1143] [1219]

21.2
[538]

37.5
[952]

16
[406]

11.38
[289]

13.03
[331]

45
48
[1143] [1219]

25.2
[640]

38
[965]

20
[508]

17.48
[444]

11.38
[289]

13.03
[331]

070L

45
[1143]
45
[1143]
50
[1270]
50
[1270]

25.2
[640]
25.2
[640]
27.2
[690]
27.2
[690]

24
[610]
24
[610]
26
[660]

38
[965]
45
[1143]
46
[1168]

20
[508]

17.48
[444]
17.48
[444]
17.48
[444]
19.72
[501]

17.48
[444]

060L

20
[508]
24
[610]

17.48
[444]
19.72
[501]

11.38
[289]

13.03
[331]

46
[1168]

20
[508]

20.2
[514]
20.2
[514]

15.55
[395]
15.55
[395]

26
[660]

20.2
[514]
20.2
[514]

13.43
[341]
13.43
[341]
13.43
[341]

15.55
[395]

30.2
[767]

29
[737]

25
[635]
25
[635]

25.73
[653]

15.91
[404]

18.54
[653]

32
[813]

60
[1524]
60
[1524]

25.73
[653]

33.2
[843]

13.17
[344]

13.17
[344]

13.43
[341]

43.66
[1109]

100L

*120L
*150L
*180L

48
[1219]
55
[1397]
56
[1422]
56
[1422]

58
70
[1474] [1778]
70
60
[1524] [1778]

LEGEND

16
[406]
20
[508]

0.75
[19]
ACCESS

A1

A3

FILTER
REMOVAL

MODEL CADX-180L W ITH DOUBLE BLOWER FAN.


A2

1- EVAPORATOR FAN

*MODELS WITH DOUBLE CIRCUITS

2- EVAPORATOR FAN MOTOR


3- EVAPORATOR COIL

A4
4-0.5 [13]
MOUNTING HOLES

6.5
[165]

085L

1.5
[38]

3.5
[89]

1.97
[50]

MODEL
CADX

ALL DIMESIONS ARE IN INCHES [mm]


A1-A4 ARE LOADING POINTS

4- 1"THK. FLAT FILTER

W
[1219]
1.5
[38]

USE DRAIN SIZE 1[25] FOR MODELS 150 to 240

L
E
1

LIQ.

S/A
C

SUC.

CABLE
ENTRY

3.3
[83]

1.2
[30]

R/A

ACCESS
DRAIN 3/4 [19]

2.5
[63]

Models: CADX-240L

2
[50]

4-0.5 [13]
MOUN TIN G
HOLES
A3

ACCESS
A1

1.6
[40]

1.5
[38]

MODEL: CADX-240L

40mm ALUMINIUM

89.85
[2282]

CON STRUCTION
USE 40mm ALUMINIUMPENTAPOST
PENTAPOST
CONSTRUCTION
25mm THICK PANELS
25mm THICK PANELS

L EARE
G E NINDINCHES [mm]
ALL DIMENSIONS
1- EVAPORATOR
FAN
A1-A4 ARE LOADING
POINTS
2- EVAPORATOR FAN MOTOR

L E G E N D3- EVAPORATOR COIL


4- 1"THK. FLAT FILTER

1- EVAPORATOR FAN
ALL DIMEN
SIONS
ARE IN INCHES [mm]
2- EVAPORATOR
FAN
MOTOR
A1-A 4 ARE LOADING POINTS

3- EVAPORATOR COIL

4- 1"THK. FLAT FILTER

A4
1.6
[40]

A2

52.3
[1328]

2
[51]

20.4
[517]
7.4
[189]

20.4
[517]

28
[711]
1

36
[914]
2

4
[102]
3

1.57
[40]

64
[1626]

93
[2362]

ACCESS

R/A

DRAIN 1 [25]

ACCESS

30.85
[784]

S/A

1.57
[40]

6
[152]

CABLE ENTRY
1 [25]
6

15.91
[404]

LIQ.#2
SUC.#2

34
[864]
1.2
[30]

35.18
[894]

LIQ.#1
SUC.#1

[152]

You name it.....We cool it

15

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Condensing Unit Dimensional Data
Weights:
LOADING POINTS
CONDENSING
UNIT ACUM-

050L
060L
070L
085L
100L
110L
120L
130L
145L
160L
180L
205L
240L
260L

A1

A2

A3

A4

TOTAL
WEIGHT

lbs

lbs

lbs

lbs

lbs

kg
79
36
87
39
89
40
110
50
112
51
171
78
173
79
176
80
177
80
214
97
214
97
235
107
226
103
227
103

kg
82
37
91
41
93
42
114
52
116
53
171
78
173
79
176
80
177
80
214
97
214
97
235
107
226
103
227
103

kg
79
36
87
39
89
40
110
50
112
51
173
78
175
80
178
81
179
81
216
98
216
98
238
108
229
104
230
104

kg
81
37
89
40
91
41
112
51
114
52
173
78
175
80
178
81
179
81
216
98
216
98
238
108
229
104
230
104

kg
321
146
354
161
363
165
446
202
453
206
688
312
697
316
707
321
713
324
860
390
860
390
946
429
909
413
913
414

LOADING POINTS
AIR HANDLING
UNIT CADX-

050L
060L
070L
085L
100L
120L
120L
150L
150L
150L
180L
180L
240L
240L

A1

A2

A3

A4

TOTAL
WEIGHT

lbs

lbs

lbs

lbs

lbs

kg
59
27
65
29
65
29
76
34
81
37
87
39
87
39
115
52
115
52
115
52
119
54
119
54
171
78
171
78

kg
55
25
61
28
61
28
71
32
84
38
90
41
90
41
120
54
120
54
120
54
133
60
133
60
192
87
192
87

kg
48
22
53
24
53
24
62
28
73
33
78
36
78
36
104
47
104
47
104
47
105
48
105
48
152
69
152
69

kg
43
19
47
21
47
21
55
25
72
33
78
35
78
35
103
47
103
47
103
47
113
51
113
51
162
74
162
74

kg
204
93
225
102
225
102
265
120
310
141
334
151
334
151
442
200
442
200
442
200
469
213
469
213
678
308
678
308

Table 9

Recommended Suction and Liquid Line Sizes:


PIPE LENGTH - FEET (m)
Models
25 (7.6)
Circuit A

050L
060L
070L
085L
100L
110L
120L
130L
145L
160L
180L
205L
240L
260L

050L
060L
070L
085L
100L
120L
120L
150L
150L
150L
180L
180L
240L
240L

50 (15.2)
Circuit B

Circuit A

75 (22.9)
Circuit B

Circuit A

100 (30.5)
Circuit B

Circuit A

Circuit B

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
5/8
5/8

7/8
7/8
7/8
1 1/8
1 1/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 1/8
1 1/8

1/2
1/2
1/2
1/2
1/2
1/2
1/2
5/8
5/8

7/8
7/8
7/8
7/8
7/8
1 1/8
1 1/8
1 1/8
1 1/8

1/2
1/2
1/2
1/2
5/8
1/2
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8

7/8
1 1/8
1 1/8
1 1/8
1 1/8
7/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8

1/2
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8

7/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8

1/2
1/2
1/2
5/8
5/8
1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8

7/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8

1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8

1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8

1/2
1/2
5/8
5/8
5/8
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
3/4

1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8

1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
3/4

1 1/8
1 1/8
1 1/8
1 1/8
1 1/8
1 3/8
1 3/8
1 3/8
1 3/8
Table 10

Notes :
1. Pipe diameters are based on equivalent length of copper tubing sizes.

2. Pipe sizes are based on 2F (1.1C) or less temperature losses for liquid and suction line in equivalent pipe length.
3. If the condensing unit is below the evaporating unit, the maximum lift should not exceed to 66 feet.
4. Do not exceed 100 feet piping length without checking with SKM.
5. These sizes are for guidance only. For detailed proper piping, refer to recognized piping references like ASHRAE
Guide and Data Book.
The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant
connections available on the outdoor or indoor unit. Necessary transformation may be required and its field performed.

16

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Recommended Clearances
UNIT CLEARENCE

SPACING FOR AIR FLOW

SPACING FOR SERVICE

30
[762]

30
[762]

30
[762]

30
[762]

30
[762]

45
[1143]

30
[762]

30
[762]

ALL DIMENSIONS ARE IN INCHES[mm]

30
[762]

30
[762]

30
[762]

ACUM- 050L to 100L

SINGLE UNIT

ACUM- 050L to 100L

MULTIPLE UNIT
UNIT CLEARENCE
SPACING FOR SERVICE

SPACING FOR AIR FLOW

ACUM- 110L to 260L

30
[762]

52
[1322]

52
[1321]

52
[1322]

30
[762]

52
[1322]

52
[1322]

52
[1321]

SINGLE UNIT

30
[762]

52
[1322]

30
[762]

30
[762]

52
[1321]

52
[1322]

88
[2235]

30
[762]

52
[1322]

52
[1322]

52
[1321]

MULTIPLE UNIT

You name it.....We cool it

17

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Installation and Commissioning

Install the unit in such a location which is flat and strong enough to support its weight.

All field wiring must comply with applicable local and national codes.

Service spacing should be provided as shown in the figure. If any obstacles are around the unit, distributed air is short-circuited
so that the unit stops frequently and access to the unit is difficult for inspection and aftersales services.

INSTALLATION & COMMISSIONING

SPACING FOR SERVICE

SPACING FOR AIRFLOW

AIR OUT

AIR OUT

3000mm

No obstacle

AIR OUT

L
RO
NT EL
CO PAN

AI R
R
AI

3000mm

No obstacle

L
RO
NT E L
CO PAN
IN

A IR

IN

IN

A IR
UI D
LI QLI NE

ION
CT
SU LI NE

N
UI D
LIQLINE UCTINOE
S LI
A IR

OL
NTR IT
COCIRCU

AIR

IN

IN

IN

OL
TR IT
IT
CU R ON CU
CIROWE C CIR
P

R
WE IT
POIRCU
C

UID
LIQLINE

ACUM- 050L

A IR

AIR

IN

IN

ION
CT
SU LINE

ACUM- 110L to 145L

3000mm

No obstacle

AIR OUT

L
RO
NT EL
CO PAN

A IR

A IR

UID
LI QLINE

IN

3000mm

No obstacle

AIR OUT

IN

ON
CTI
SU LINE

L
RO
NT E L
CO PAN
L
RO
NT IT
C OCIRCU

AI R

IN

A IR

IN
A IR

R
WE IT
POI RCU
C

ACUM- 060L to 100L

UI D
LIQLINE

I ON
CT E
SU LIN

AIR

IN

OL
TR IT
IT
CU R ON CU
CIROWE C CIR
P
UID
LIQLINE
N
TIO
SUCLINE

18

You name it.....We cool it

AIR

IN

ACUM- 160L to 260L

AIR

IN

IN

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
Typical Refrigeration Piping
LEGEND
1 SIGHT GLASS
2 SOLENOID VALVE
3 FILTER DRIER
NOTE:-

2
5

EXPANSION VALVE
INSIDE CADX L

CADX L

ACUM L

4 SHUT OFF VALVE


5 LIQUID LINE
6 SUCTION LINE

A
R/

3
4

CADX L

LEGEND

R/

1 SIGHT GLASS
2 SOLENOID VALVE
3 FILTER DRIER

NOTE:-

4 SHUT OFF VALVE


5 LIQUID LINE
6 SUCTION LINE

EXPANSION VALVE
INSIDE CADX L

ACUM L

* INVERTED TRAP WITHOUT PUMP DOWN CONTROL.


DOTTED WITH PUMP DOWN CONTROL.

Refrigerant Piping:
Correct design and size of refrigerant piping is necessary to proper operation. The refrigerant piping generally should be
designed to accomplish the following:
a) To ensure proper refrigerant feed to the evaporator.
b) To provide practical refrigerant line sizes without excessive pressure drop.
c) To maintain uniform return of lubricating oil to the compressor.
d) To prevent refrigerant from entering the compressor and causing compressor damage due to slugging.

You name it.....We cool it

19

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
GUIDE SPECIFICATIONS
GENERAL

CONDENSING UNIT CASING

Spilt air conditioner shall be composed of a ceiling suspended air


handling unit & floor mounted air cooled condensing unit, rated
in accordance with AHRI standards 210 / 240 and 340 / 360.
The indoor and outdoor units shall be factory assembled, internally
wired, charged with R-22 and fully tested. Unit should be capable
to operate in a wide range of ambient temperatures from 50F
(10C) to 125F (52C) and shall be selected in accordance with
project requirements and installed as per Instruction, Operation
& Maintenance Manual.

Units casing shall be made of hot dip galvanized steel sheets


(zinc coated) conforming to JIS-G3302 and ASTMA525 that
shall be phosphatized and then elctrostatically dry powder
coated of approx 60 microns to provide an extremely tough,
scratch resistance, excellent anti corrosive protection that
can pass 1000 hours in 5% salt spray testing at 95F relative
humidity as per ASTM B117.

CONDENSING UNIT
The condensing unit shall be composed of compressor(s), coil(s)
and condenser fan(s) and motor(s).

COMPRESSOR
Compressor shall be hermetically sealed, compact high efficiency
and low noise scroll type. These compressors are refrigerant gas
cooled, furnished with advanced scroll temperature protection
or internal motor protection.

AIR HANDLING UNIT CASING


The unit casing for CADX-L is made of zinc coated galvanized
steel sheets conforming to JIS-G3302 and ASTM A525 which
is phosphatized and baked after an electrostatic powder coat
of approximately 60 microns. This finish and coating can pass
a 1000 hour in 5% salt spray testing at 95F (35C) and 95%
relative humidity as per ASTM B117. Panels and casing are
insulated with 1 (25mm) thick fiberglass (with BGT coating)
thermal and acoustic insulation having density of 2 lb/ft. (32
kg/m) and thermal conductivity of 0.23 BTU.in/ftFh (0.033
W/mK). Insulation meets the requirements of NFPA 90A and
90B for fire resistance.

CONDENSER COIL(S)

CADX-240L model is with Penta-Post construction from


extruded aluminum profiles and nylon glass fiber reinforced
corners joints.

Condenser coils shall be air cooled with integral sub cooler,


constructed of special inner grooved seamless copper tubes
3/8 OD mechanically expanded into waffle louver aluminum p
fins . These coils shall be tested against leakage by air pressure
of 450 psig (3100 kPa) under water, cleaned & dehydrated at
the factory.

The cross section of the profile is specially designed for


maximum rigidity and strength Profiles for panels with 1 (25
mm) nominal thickness have got built-in PVC inserts to prevent
thermal bridge. Access doors & fixed panels are insulated with
1thick fiber glass thermal and acoustic insulation, as standard.

EVAPORATOR COIL

CONDENSER FAN(S) & MOTOR(S)


Condenser Fans shall be direct driven propeller type discharging
air vertically upward, equipped with statically & dynamically
balanced aluminum alloy blades, inherent corrosion resistant
shaft & PVC coated steel wire fan guard. Condenser fan
motor(s) shall be Totally Enclosed Air Over (TEAO), 6 poles
with class-F insulation, minimum IP55 protection & wired to
unit control panel.

Evaporator coil shall be constructed of inner grooved copper


tubes 3/8 OD mechanically bonded to aluminum cross wave fins.
Coil consists of headers of seamless copper tubing, thermostatic
expansion valve(s) & multi-circuited distributor(s). These coils
shall be tested against leakage by air pressure of 300 psig (2068
Kpa) under water, cleaned & dehydrated at the factory. Coil shall
conform to AHRI-410.

EVAPORATOR FAN AND MOTOR


CONTROLS
Outdoor condensing units shall be provided with IP-54 control
panel enclosure comprising all starting, operating and safety
controls. Following shall be the standard components used in
the condensing unit control panel:

All compressors shall be with DOL starting.


Individual compressor and condenser fan motor contactors.
Overload relays for condenser fan motors.
Control Relays and control circuit fuses.
Control disconnect for each refrigerant circuit.
Anti-short cycle timer for compressors.
24V Control Transformer.
Starter (contactor & overload relay) for indoor unit evaporator
fan motor.
Power and control terminal blocks.

20

Fans of evaporators shall be forward curved, double inlet


double width (DIDW), centrifugal type, Statically & dynamically
balanced, mounted on a single heavy duty statically & shaft
with permanently lubricated bearings & driven by V belt with
an adjustable variable pitch motor pulley. Motor shall be Totally
Enclosed Fan Cooled (TEFC), 4 poles, class-F insulated,
minimum IP55 protection & wired to unit control panel.

FILTERS
Air handling units shall be provided with air filter. Filter should
be 1 (25mm) standard or 2 (50mm) thick optional washable
aluminum media with average dust arrestance 54% based on
ASHRAE standards 52.1.

You name it.....We cool it

SKM Split Air Conditioners


ACUM-L + CADX-L Series - R22
NOTES:

You name it.....We cool it

21