Ducted Mini Split System

Range 1.5 TR to 6 TR
( 5 kW to 21 kW )

Bulletin # 068/2010

SKM Ducted Mini Split Systems


Contents
Introduction .........................................2
Legend................................................2
Nomenclature .....................................3
Features & Specification............... 4-10
Combination Ratings ........................11
Electrical Data ..................................13
Options .............................................15
Fan Performance ..............................16

Recommended Line Sizes................18


Typical Refrigeration Piping ..............19
Typical Wiring Diagram.....................21
Dimensional Data .............................25
Outdoor Unit Clearance
and Spacing...............................28
Guide Specification...........................30

Legend
The following legends are used throughout
this manual:
AFR ...... Air Flow Rate
cfm ....... Cubic feet per minute
dB ........ Decibels
EADB .... Entering Air Dry Bulb
EAWB .... Entering Air Wet Bulb
ET ......... Evaporating Temperature
Hz ........ Hertz
kW ........ Kilowatts
kg ......... Kilograms
kPa ...... Kilo Pascals

LADB ....
LAWB ...
lbs .........
l/s ..........
Mbh ......
OD ........
Ph .........
Pa .........
SC ........
TC .........
TR ........
V ...........

Leaving Air Dry Bulb


Leaving Air Wet Bulb
Pounds weight (British units)
Liters per second
1000 Btuh
Outside Diameter
Phase
Pascals
Sensible Capacity
Total Capacity
Tons of refrigeration = 12 MBH
Volts

Introduction
The Ducted Mini Split system from SKM consists of RXV (a high efficiency- TOP discharge Air Cooled
Condensing Unit); and RXH-DC (a high efficiency-SIDE Discharge Air cooled Condensing Unit) matching with
DCYP (a low noise, ceiling suspended indoor fan coil unit). This split systems are ideally suited for apartments,
houses, offices, shops, small residences, and in small commercial establishments.
SKM ducted mini split system are available in different models covering 1.5 TR to 6 TR (5 kW to 21 kW) at
nominal AHRI condition, which make them ideally suited for a very small foot print for space saving and a
pleasant exterior appearance.
SKM ducted mini split units are suitable to operate in a wide range of ambient temperature.
SKM ducted mini split units are internally wired and all that required to be done on site is ducting, refrigerant
piping, power supply and suitable room thermostat installation and field wiring, which reduces the installation
work and consequently keeps to a minimum cost.
SKM Ducted Mini Split Air Conditioning Units are:

Built in the Gulf... For the World.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


NOMENCLATURE
OUTDOOR ( TOP DISCHARGE AIR COOLED CONDENSING UNIT )
R X V - 020- Y

Direct Expansion

S1: 220-240V/1Ph/50Hz
S2: 220V/1Ph/60Hz
Y: 380-415V/3Ph/50Hz
R: 380V/3Ph/60Hz
T: 220-230V/3Ph/60Hz

Vertical Discharge

Nominal Capacity in Mbh

Remote Air Cooled Condenser

OUTDOOR ( SIDE DISCHARGE AIR COOLED CONDENSING UNIT )


R X H - 020 - 5 D C
Remote Air Cooled Condenser
Direct Expansion
Horizontal Discharge

C = Cooling only

Matching to Ducted Indoor Units

Power Supply
Frequency

Nominal Capacity in MBh

5 : 50 Hz
6 : 60 Hz

INDOOR UNIT
FCU - DCY P - 12 / 4 / X G
G=Galvanised Finish
F=Painted FInish

Fan Coil Unit

Type of cooling coil: X = DX coil,


Direct Drive
No. of rows for cooling coil
(3 or 4 rows)

P : Ceiling suspended with plenum

Unit size nom. x 100 cfm


(06,08,10,12,15,18, & 21)

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


VERTICAL DISCHARGE AIR COOLED CONDENSING UNIT - RXV
Design Features: (Air Cooled units up to 6.0 Tons of Refrigeration)

Design - Outdoor condensing units are ideal for rooftop or ground installation. Units have a pleasant exterior appearance
and have a very small footprint for space saving installation.

High efficiency Coils - 3/8 OD Hi-x tubes; mechanically bonded to hi-efficiency aluminium fins to match for a maximum
efficiency.

Hermetic Compressor - High efficiency hermetically sealed compressor located on engineered mounts for safe, quiet and
vibration free operation.Compresssors are selected for reliability and power efficiency.

Cabinet Construction - Heavy gauge zinc clad steel, latest technology electrostatic powder baked finish to ensure a long
lasting, durable cabinet.

High Efficiency Fan Motor Permanently lubricated fan motor and is precisely matched to a metal propeller type Fan
blades which provides a maximum efficiency.

Brass Service Valves Factory installed service valve with sweat connections to provide quick and accurate installation
for start-up and servicing.

Ease of Service and Installation Designed to make servicing easier for the contractor, access panels are provided
for all controls and the compressor from the side of the unit.

Compressor Short Cycling Protection To protect the compressor against rapid short cycling.

High and Low Pressure Protection - To protect the compressor against high discharge pressure and low suction
pressure, and to guarantee safe operation of compressor.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


SPECIFICATION (RXV - VERTICAL DISCHARGE CONDENSING UNITS) - 50HZ
Model
Cooling Capacity (1)
Cooling Capacity (2)
Power Supply
Compressor

RXV

020

025

030

040

045

050

060

070

Mbh

19.1

24.6

29.7

33.5

42.3

52.4

61.4

62.9

kW

5.6

7.2

8.7

9.8

12.4

15.4

18.0

18.4

Mbh

17.0

22.2

27.1

30.2

38.9

48.6

56.5

58.1

kW

5.0

6.5

7.9

8.9

11.4

14.2

16.6

17.0

V / Ph / Hz

220-240/1/50

380-415/3/50

Type

Reciprocating

Scroll

Qty.

Coil

Face Area

ft

12

16

16

16

16

16

16

0.74

1.11

1.49

1.49

1.49

1.49

1.49

1.49

460/1

460/1

460/1

460/1

560/1

560/1

560/1

560/1

cfm

1750

1850

1850

1850

3750

3600

3600

3600

l/s

826

873

873

1699

1699

1699

Propeller,Direct Drive

Condenser

Blade Dia. / Qty


Air Flow

Motor

873
1770
TEAO (Totally Enclosed Air Over) Motor

Type
Size

Type
Fan

Waffle Louver Fins and Inner Grooved tubes 3/8"OD

Type

kW

0.10

0.10

0.10

0.10

0.25

0.25

0.25

0.25

Refrigerant Operating Charge (R-22)

lbs / kg

2.43 / 1.10

3.11 / 1.41

3.87 / 1.76

4.11 / 1.86

4.25/ 1.93

6.93 / 3.14

7.09 / 3.21

7.54 / 3.42

Operating Weight Approximate

lbs / kg

202 / 92

202 / 92

221 / 100

228 / 103

242 / 110

277 / 125

277 / 125

284 / 129

Length

23

23

26

26

29

29

29

29

Height

25

33

37

37

33

33

33

33

Width

23

23

26

26

29

29

29

29

Liquid

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

1/2"

Suction

5/8"

5/8"

5/8"

3/4"

3/4"

3/4"

3/4"

7/8"

Dimensions (inches)

Pack valves Connections

SPECIFICATION (RXV - VERTICAL DISCHARGE CONDENSING UNITS) - 60HZ


Model
Cooling Capacity (1)
Cooling Capacity (2)
Power Supply
Compressor

RXV

021

026

031

041

046

051

061

071

Mbh

21.1

24.3

30.7

36.6

49.8

58.2

68.6

70.5

kW

6.2

7.1

9.0

10.7

14.6

17.1

20.1

20.7

Mbh

19.1

21.7

28.0

33.0

45.9

54.1

63.7

65.6

kW

5.6

6.4

8.2

9.7

13.5

15.9

18.7

19.2

220/1/60Hz

380/3/60Hz

220/3/60Hz

Reciprocating

Scroll

V / Ph / Hz
Type

Qty.

Type
Coil

Waffle Louver Fins and Inner Grooved tubes 3/8"OD


8

12

16

16

16

16

16

16

0.74

1.11

1.49

1.49

1.49

1.49

1.49

1.49

460/1

460/1

460/1

460/1

560/1

560/1

560/1

560/1

cfm

2100

2220

2220

2220

4500

4320

4320

4320

l/s

991

1048

1048

1048

2124

2039

2039

2039

kW

0.10

0.10

0.10

0.10

0.37

0.37

0.37

0.37

Refrigerant Operating Charge (R-22)

lbs / kg

2.43 / 1.10

3.11 / 1.41

3.87 / 1.76

4.11 / 1.86

4.25/ 1.93

6.93 / 3.14

7.09 / 3.21

7.54 / 3.42

Operating Weight Approximate

lbs / kg

202 / 92

202 / 92

221 / 100

228 / 103

242 / 110

277 / 125

277 / 125

284 / 129

Length

23

23

26

26

29

29

29

29

Height

25

33

37

37

33

33

33

33

Width

23

23

26

26

29

29

29

29

Condenser

ft
m

Face Area
Type

Fan

Air Flow
Motor

Propeller,Direct Drive

Blade Dia. / Qty

Type
Size

Dimensions (inches)

Pack valves Connections

TEAO (Totally Enclosed Air Over) Motor

Liquid

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

1/2"

Suction

5/8"

5/8"

5/8"

3/4"

3/4"

3/4"

3/4"

7/8"

Notes: 1. Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67F (27/19.5C) dry
bulb/wet bulb and condenser entering air temperature of 95F (35C) dry bulb.
2. Evaporator entering air conditions of 80/67F (27/19.5C) dry bulb/wet bulb and condenser entering air temperature of
115F (46C) dry bulb..
Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


SIDE DISCHARGE AIR COOLED CONDENSING UNIT - RXH-DC
Design Features: (Air cooled units up to 5.5 Tons of Refrigeration)

Design - Outdoor condensing units with side discharge air delivery are ideal for rooftop or ground installation and ledge
installation. This unit has a pleasant exterior aesthetic design and has a very small footprint for space saving installation.

High Efficiency Coils 3/8 O.D. inner grooved copper tubes with mechanically bonded to aluminium corrugated fins to
attain maximum efficiency.

Compressor Uses high efficiency rotary or scroll hermetic compressor located on engineered mounts for safe, quite and
vibration free operation.

Cabinet Construction- Heavy gauge zinc clad steel, latest technology electrostatic powder baked finish to ensure a long
lasting, durable cabinet.

Brass Service Valves Factory installed service valve with sweat connections to provide quick and accurate installation
for start-up and servicing.

High efficiency fan motor permanently lubricated fan motor and it is precisely matched to plastic propeller type blades
which provides a maximum efficiency.

Ease of service and installation designed to make servicing easier for the contractor; access panel are also provided
for all controls from the side of the unit.

Electronic control board for all models.

Compressor Short Cycling Protection To protect the compressor against rapid short cycling.

High and Low Pressure Protection To protect the compressor against high discharge pressure and low suction
pressure, and to guarantee safe operation of compressor.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


SPECIFICATION (RXH - SIDE DISCHARGE CONDENSING UNIT) - 50HZ
Model
Cooling Capacity
Power Supply

RXH

020 - 5DC

025 - 5DC

030 - 5DC

040 - 5DC

045 - 5DC

050 - 5DC

060 - 5DC

Mbh

19.1

24.6

29.7

33.5

42.3

52.1

59.3

kW

5.6

7.2

8.7

9.8

12.4

15.3

17.4

220-240/1/50

V / Ph / Hz
Rotary

Type

Compressor

Qty.

Scroll
1

Type

Condenser

Coil

Face Area

380-415/3/50

1
1
1
1
Hydrophilic aluminium Corrugated Fin and Innergroved Copper Tube - 3/8" OD

ft

5.92

5.92

9.26

9.26

12.53

12.53

12.53

0.55

0.55

0.86

0.86
Propeller Direct Drive

1.164

1.164

1.164

550/1

550/1

460/2

460/2

460/2

Type
Fan

Blade Dia. / Qty


Air Flow

Motor

460/1

460/1

cfm

1700

2100

3590

3590

4000

4000

4000

l/s

802

991

1694

1694

1888

1888

1888

Type

TEAO (Totally Enclosed Air Over) Motor

Size
Refrigerant Operating Charge (R-22)

kW

0.053

0.100

0.250

0.250

0.080x2

0.080x2

0.080x2

lbs / kg

2.54 / 1.15

3.97 / 1.8

5.73 / 2.6

6.06 / 2.75

7.056 / 3.2

6.84 / 3.1

6.84 / 3.1

Operating Weight Approximate

lbs / kg

110.25 / 50

132.3 / 60

218.3 / 99

195.14 / 88.5

225 / 102

240 / 109

260.19 / 118

Length

33.3

33.3

38.98

38.9

37

37

37

Height

27.4

27.4

37.8

37.8

49.02

49

49

Dimensions (inches)

Pack valves Connections

Width

13.2

13.2

14.2

14.2

13.39

13.9

13.9

Liquid

1/4"

3/8"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction

1/2"

5/8"

3/4"

3/4"

3/4"

3/4"

3/4"

045 - 6DC

050 - 6DC

060 - 6DC

SPECIFICATION (RXH - SIDE DISCHARGE CONDENSING UNIT) - 60HZ


Model
Cooling Capacity
Power Supply

RXH

020 - 6DC

025 - 6DC

030 - 6DC

Mbh

21.1

24.3

30.7

36.6

46.3

57.4

64.7

kW

6.2

7.1

9.0

10.7

13.6

16.8

18.9

V / Ph / Hz

220/1/60
Rotary

Type

Compressor

Qty.

Type

Condenser

Coil

Face Area

Scroll
1

1
1
1
1
Hydrophilic aluminium Corrugate Fin and Innergroved Copper Tube - 3/8" OD

ft

5.92

5.92

9.26

9.26

12.53

12.53

12.53

0.55

0.55

0.86

0.86
Propeller Direct Drive

1.164

1.164

1.164

460/1

460/1

550/1

550/1

460/2

460/2

460/2

cfm

2030

2030

3325

3305

3502

3508

3455

l/s

958

958

1569

1560

1653

1656

1631

Blade Dia. / Qty


Air Flow

Motor

Type
Fan

040 - 6DC

Type

TEAO (Totally Enclosed Air Over) Motor

Size
Refrigerant Operating Charge (R-22)

kW

0.053

0.053

0.250

0.250

0.065X2

0.065X2

0.065X2

lbs / kg

2.65(1.2)

3.53 / 1.6

5.73 / 2.6

5.95 / 2.7

7.056 / 3.2

8.16 / 3.7

10.1 / 4.6

Operating Weight Approximate

lbs / kg

110.25 / 50

132.3 / 60

201 / 91

217 / 98.5

251.4 / 114

275 / 125

275 / 125

Dimensions (inches)

Pack valves Connections

Length

33.3

33.3

38.98

38.98

37

37

37

Height

27.4

27.4

37.8

37.8

49.02

49

49

Width

13.2

13.2

14.7

14.7

13.39

13.9

13.9

Liquid

1/4"

3/8"

1/2"

1/2"

1/2"

1/2"

1/2"

Suction

1/2"

5/8"

3/4"

3/4"

3/4"

3/4"

3/4"

Notes: Nominal cooling capacities are based on the following conditions: Evaporator entering air of 80/67F (27/19.5C) dry
bulb/wet bulb and condenser entering air temperature of 95F (35C).

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


INDOOR UNIT - DCYP
Design and Features

High efficiency coil with high efficiency wavy corrugated fins.

High efficiency, low power consumption PSC electric motor.

High efficiency forward curved fan for quiet operation.

Heavy gauge galvanized casing and fan housing. Hot dip is standard.

Insulated heavy gauge drain pan.

Isolating grommet for an additional vibration isolation.

Easy wiring / electrical and piping connections.

Evaporator coils equipped with plain tubes and aluminium fins which give high capacity sensible and latent cooling capabilities.

Equipped with refrigerant flow control orifice or expansion valve.

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXV) - 50HZ
Indoor Unit Size
Matched Outdoor Units
Cooling Capacity

(1)

Cooling Capacity

(2)

Nominal Air Flow Rate


Type
No. Of Row / FPI
Fin Height
Coil
Fin Length
Face Area
Metering Device
Fan

Motor

Type
Code
Quantity
Type
Size
Quantity

DCYP
RXV

06
020

08
025

21
060

21
070

Mbh
kW
Mbh
kW
cfm
l/s
#
inch
mm
inch
mm
2
ft
2
m
Type
#
Watts
#

19.1
5.60
17.0
4.98
686
324

24.6
29.7
33.5
42.3
52.4
61.4
7.21
8.70
9.82
12.40
15.36
17.99
22.2
27.1
30.2
38.9
48.6
56.5
6.51
7.94
8.85
11.40
14.24
16.56
785
1061
1331
1536
1914
2200
370
501
628
725
903
1038
Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
3 / 12
3 / 12
3 / 12
3 / 12
3 / 12
3 / 12
12
16
12
12
16
16
305
406
305
305
406
406
24
24
36
42
42
48
610
610
914
1067
1067
1219
2.0
2.7
3.0
3.5
4.7
5.3
0.19
0.25
0.28
0.33
0.43
0.50
orifice
expansion valve
Double Inlet Double Width Centrifugal Forward Curve Direct Drive
7-7
9-7
7-7
7-7
9-7
9-7
1
1
2
2
2
2
220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
150
1
1
2
2
2
2
3/8
3/8
3/8
1/2
1/2
1/2
10
10
10
13
13
13
5/8
5/8
5/8
7/8
1 1/8
1 1/8

62.9
18.43
58.1
17.03
2200
1038

7-7
1

inch
mm
inch

Liquid
Connection Sizes
Suction
Machine Weight

3 / 12
12
305
20
508
1.7
0.15

mm

150
1
3/8
10
5/8

10
030

12
040

15
045

18
050

3 / 12
16
406
48
1219
5.3
0.50

9-7
2
150
2
1/2
13
1 1/8

16

16

16

16

22

29

29

29

lbs.

60

67

82

87

109

134

141

141

kg.

27.3

30.5

37.3

39.5

49.5

60.9

64.1

64.1

15
046

18
051

SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXV) - 60HZ


Indoor Unit Size
Matched Outdoor Units
Cooling Capacity

(1)

Cooling Capacity

(2)

Nominal Air Flow Rate


Type
No. Of Row / FPI
Fin Height
Coil
Fin Length

DCYP
RXV

06
021

08
026

21
061

21
071

Mbh
kW
Mbh
kW
cfm
l/s
#
inch
mm
inch
mm

21.1
6.18
19.1
5.60
583
274

24.3
30.7
36.6
49.8
58.2
68.6
7.12
9.00
10.73
14.59
17.06
20.10
21.7
28.0
33.0
45.9
54.1
63.7
6.36
8.21
9.67
13.45
15.86
18.67
735
984
1147
1450
1813
2190
347
464
541
684
856
1034
Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
3 / 12
3 / 12
3 / 12
4 / 12
3 / 12
3 / 12
12
16
12
12
16
16
305
406
305
305
406
406
24
24
36
42
42
48
610
610
914
1067
1067
1219
2.0
2.7
3.0
3.5
4.7
5.3
0.19
0.25
0.28
0.33
0.43
0.50
orifice
expansion valve
Double Inlet Double Width Centrifugal Forward Curve Direct Drive
7-7
9-7
7-7
7-7
9-7
9-7
1
1
2
2
2
2
220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
150
1
1
2
2
2
2
3/8
3/8
3/8
1/2
1/2
1/2
10
10
10
13
13
13
5/8
5/8
5/8
7/8
1 1/8
1 1/8
16
16
16
22
29
29
67
82
87
114
134
141
30.5
37.3
39.5
51.8
60.9
64.1

70.5
20.66
65.6
19.23
2190
1034

4 / 12
12
305
20
508
1.7
0.15

Face Area
Metering Device
Fan

Motor

Type
Code
Quantity
Type
Size
Quantity

ft
2
m
Type
#
Watts
#
Liquid

Connection Sizes
Suction
Machine Weight

lbs.
kg.

7-7
1

inch
mm
inch
mm

150
1
3/8
10
5/8
16
63
28.6

10
031

12
041

3 / 12
16
406
48
1219
5.3
0.50

9-7
2
150
2
1/2
13
1 1/8
29
141
64.1

Notes: (1). Capacity ratings are based on AHRI Standard 210/240. Evaporator entering air conditions of 80/67F (27/19.5C)
dry bulb/wet bulb and condenser entering air temperature of 95F (35C) dry bulb.
(2). Evaporator entering air conditions of 80/67F (27/19.5C) dry bulb/wet bulb and condenser entering air temperature
of 115F (46C) dry bulb.
Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXH-DC) - 50H
HZ
Indoor Unit Size
Matched Outdoor Units
Cooling Capacity
Nominal Air Flow Rate
Type
No. Of Row / FPI
Fin Height
Coil
Fin Length
Face Area
Metering Device
Fan

Motor

Type
Code
Quantity
Type
Size
Quantity

DCYP
RXH

06
020-5DC

Mbh
kW
cfm
m3/h

19.1
5.6
686
1166

#
inch
mm
inch
mm
ft2
m2
Type

3 / 12
12
305
20
508
1.7
0.15

7-7
1

#
Watts
#
inch
mm
inch
mm

Liquid
Connection Sizes
Suction
lbs.
Kg.

Machine Weight

150
1
3/8
10
5/8
16
60
27.3

08
025-5DC

10
030-5DC

12
040-5DC

15
045-5DC

18
050-5DC

24.6
29.7
33.5
42.3
52.1
7.2
8.7
9.8
12.4
15.3
785
1061
1331
1536
1914
1334
1803
2261
2610
3252
Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
3 / 12
3 / 12
3 / 12
3 / 12
3 / 12
12
16
12
12
16
305
406
305
305
406
24
24
36
42
42
610
610
914
1067
1067
2.0
2.7
3.0
3.5
4.7
0.19
0.25
0.28
0.33
0.43
orifice
Double Inlet Double Width Centrifugal Forward Curve Direct Drive
7-7
9-7
7-7
7-7
9-7
1
1
2
2
2
220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
1
1
2
2
2
3/8
3/8
3/8
1/2
1/2
10
10
10
13
13
5/8
5/8
5/8
7/8
1 1/8
16
16
16
22
29
67
82
87
109
134
30.5
37.3
39.5
49.5
60.9

21
060-5DC
59.3
17.4
2200
3738
3 / 12
16
406
48
1219
5.3
0.50

9-7
2
150
2
1/2
13
1 1/8
29
141
64.1

SPECIFICATION (INDOOR UNIT DCYP MATCHED WITH RXH-DC) - 60HZ


Indoor Unit Size
Matched Outdoor Units
Cooling Capacity
Nominal Air Flow Rate
Type
No. Of Row / FPI
Fin Height
Coil
Fin Length
Face Area
Metering Device
Fan

Motor

Type
Code
Quantity
Type
Size
Quantity

DCYP
RXH

06
020-6DC

Btuh
kW
cfm
m3/h
#
inch
mm
inch
mm
ft2
m2
Type
#
Watts
#

21.1
6.2
583
991

Liquid
Connection Sizes
Suction
Machine Weight

lbs.
kg.

4 / 12
12
305
20
508
1.7
0.15

7-7
1

inch
mm
inch
mm

150
1
3/8
10
5/8
16
63
28.6

08
025-6DC

10
030-6DC

12
040-6DC

15
045-6DC

18
050-6DC

24.3
30.7
36.6
46.3
57.4
7.1
9.1
10.5
14.1
16.8
735
984
1147
1150
1813
1249
1672
1949
1954
3080
Copper Tubes mechanically bonded to Hi-effeciency wavy corrugated Aluminium Fins
3 / 12
3 / 12
3 / 12
4 / 12
3 / 12
12
16
12
12
16
305
406
305
305
406
24
24
36
42
42
610
610
914
1067
1067
2.0
2.7
3.0
3.5
4.7
0.19
0.25
0.28
0.33
0.43
orifice
Double Inlet Double Width Centrifugal Forward Curve Direct Drive
7-7
9-7
7-7
7-7
9-7
1
1
2
2
2
220-240V/1Ph/50-60Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
1
1
2
2
2
3/8
3/8
3/8
1/2
1/2
10
10
10
13
13
5/8
5/8
5/8
7/8
1 1/8
16
16
16
22
29
67
82
87
114
134
30.5
37.3
39.5
49.5
60.9

21
060-6DC
64.7
18.9
2190
3721
3 / 12
16
406
48
1219
5.3
0.5

9-7
2
150
2
1/2
13
1 1/8
29
141
64.1

Notes: Nominal cooling capacities are based on the following conditions: Evaporator entering air of 80/67F (27/19.5C) dry
bulb/wet bulb and condenser entering air temperature of 95F (35C).

10

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


Combination Ratings - RXV and DCYP Units
Capacity Ratings 50 Hz
Outdoor
Unit

Indoor
Unit

Indoor Unit
Air Flow
Rate

RXV

DCYP

CFM

020
025
025
030
030
040
040
045
045
050
050
060
060
070
070

06/30
06/40
08/30
08/40
10/30
10/40
12/30
12/40
15/30
15/40
18/30
18/40
21/30
21/30
21/40

686
680
785
777
1061
1046
1331
1317
1536
1519
1914
1882
2200
2200
2150

Air on coil Temperature DB/WB-80/67F (26.6/19.4C)

Air on coil Temperature DB/WB-76/63F (24.4/17.2C)

Ambient(Condenser Entering Air)Temperature

Ambient(Condenser Entering Air)Temperature

95F (35C)
TC
Mbh
19.1
24.7
24.6
28.3
29.7
33.5
33.5
42.8
42.3
51.0
52.4
62.1
61.4
62.9
66.6

SC
Mbh
14.1
17.0
17.3
19.5
22.0
24.5
25.9
30.8
31.3
36.2
39.1
44.6
45.4
45.9
49.3

105F (41C)
PI
kW
1.9
2.6
2.5
2.7
2.8
2.6
2.6
3.4
3.4
3.4
3.6
4.5
4.5
4.8
4.9

TC
Mbh
18.1
23.5
23.4
27.0
28.4
31.8
31.9
41.1
40.6
49.2
50.5
59.6
59.0
60.5
63.9

SC
Mbh
13.8
16.5
16.8
19.0
21.5
23.8
25.3
30.1
30.7
35.5
38.4
43.7
44.4
45.0
48.3

PI
kW
2.0
2.7
2.7
2.9
3.0
2.8
2.8
3.8
3.8
4.1
4.1
5.1
5.1
5.4
5.5

115F (46C)
TC
Mbh
17.0
22.3
22.2
25.7
27.1
30.1
30.2
39.3
38.9
47.3
48.6
57.1
56.5
58.1
61.3

SC
Mbh
13.4
16.1
16.4
18.5
21.0
23.2
24.7
29.5
30.0
34.8
37.7
42.7
43.6
44.1
47.4

PI
kW
2.1
2.9
2.9
3.1
3.2
3.0
3.0
4.2
4.2
4.5
4.6
5.7
5.7
6.1
6.1

95F (35C)
TC
Mbh
17.7
23.1
23.0
26.3
27.6
31.1
31.2
40.0
39.6
47.6
48.9
58.0
57.4
58.8
62.1

SC
Mbh
14.2
17.1
17.4
19.6
22.1
24.6
26.1
31.1
31.6
36.5
39.5
45.0
45.8
46.3
49.8

105F (41C)
PI
kW
1.8
2.4
2.4
2.6
2.7
2.5
2.5
3.3
3.3
3.5
3.6
4.4
4.4
4.7
4.8

TC
Mbh
16.8
21.9
21.8
25.0
26.2
29.6
29.6
38.4
38.0
45.9
47.1
55.5
55.0
56.4
59.6

SC
Mbh
13.8
16.6
16.9
19.1
21.6
24.0
25.5
30.4
31.0
35.8
38.7
44.0
44.8
45.4
48.7

PI
kW
1.9
2.6
2.6
2.8
2.9
2.7
2.7
3.7
3.7
4.0
4.0
5.0
5.0
5.3
5.4

115F (46C)
TC
Mbh
15.8
20.6
20.5
23.7
24.9
27.9
28.0
36.7
36.4
44.1
45.3
53.1
52.5
54.1
57.0

SC
Mbh
13.5
16.1
16.4
18.5
21.0
23.3
24.9
29.8
30.3
35.1
38.0
43.0
43.9
44.5
47.7

PI
kW
2.0
2.8
2.8
3.0
3.1
2.9
2.9
4.1
4.1
4.5
4.5
5.6
5.6
6.0
6.0

Capacity Ratings 60 Hz
Outdoor
Unit

Indoor
Unit

Indoor Unit
Air Flow
Rate

RXV

DCYP

CFM

021
021
026
026
031
031
041
041
046
046
051
051
061
061
071
071

06/30
06/40
06/40
08/30
08/40
10/30
10/40
12/30
12/40
15/40
15/40
18/30
18/40
21/30
18/40
21/30

581
583
583
735
732
984
986
1147
1150
1450
1450
1813
1814
2190
1814
2190

Air on coil Temperature DB/WB-80/67F (26.6/19.4C)

Air on coil Temperature DB/WB-76/63F (24.4/17.2C)

Ambient(Condenser Entering Air)Temperature

Ambient(Condenser Entering Air)Temperature

95F (35C)
TC
Mbh
19.7
21.1
23.8
24.3
29.2
30.7
37.1
36.6
46.3
49.8
56.3
58.2
68.8
68.6
70.8
70.5

SC
Mbh
13.5
14.7
15.7
16.7
19.4
21.7
25.3
25.5
30.6
35.0
37.6
40.4
46.6
47.9
47.4
48.7

105F (41C)
PI
kW
2.0
2.0
2.3
2.3
3.1
3.1
3.3
3.3
4.0
4.1
4.3
4.4
5.5
5.5
5.8
5.8

TC
Mbh
18.7
20.1
22.5
23.0
27.9
29.3
35.2
34.8
44.5
47.8
54.5
56.2
66.4
66.2
68.3
68.1

SC
Mbh
13.1
14.3
15.2
16.2
18.9
21.2
24.5
24.9
29.9
34.3
36.9
39.7
45.6
47.0
46.4
47.7

PI
kW
2.1
2.2
2.4
2.4
3.2
3.3
3.5
3.5
4.5
4.6
4.9
4.9
6.2
6.2
6.5
6.5

115F (46C)
TC
Mbh
17.7
19.1
21.2
21.7
26.6
28.0
33.4
33.0
42.7
45.9
52.5
54.1
64.0
63.7
65.8
65.6

SC
Mbh
12.7
13.9
14.7
15.7
18.4
20.7
23.8
24.2
29.2
33.6
36.1
38.9
44.7
46.1
45.4
46.8

PI
kW
2.2
2.3
2.5
2.6
3.3
3.4
3.7
3.7
5.0
5.1
5.4
5.5
6.9
6.9
7.2
7.2

95F (35C)
TC
Mbh
18.3
19.5
22.2
22.7
27.2
28.6
34.5
34.1
43.4
46.6
52.6
54.2
64.4
64.2
66.4
66.1

SC
Mbh
13.6
14.7
15.9
16.9
19.6
21.9
25.4
25.7
31.0
35.4
38.0
40.8
47.1
48.4
48.0
49.3

105F (41C)
PI
kW
1.9
2.0
2.2
2.2
2.9
3.0
3.2
3.1
3.9
4.0
4.3
4.3
5.3
5.3
5.7
5.6

TC
Mbh
17.2
18.4
21.0
21.4
25.9
27.2
32.7
32.3
41.6
44.7
50.8
52.4
62.1
61.8
64.0
63.7

SC
Mbh
13.1
14.3
15.3
16.4
19.0
21.3
24.7
25.0
30.2
34.7
37.2
40.0
46.1
47.5
46.9
48.3

PI
kW
2.0
2.1
2.3
2.3
3.1
3.2
3.3
3.3
4.4
4.5
4.8
4.8
6.1
6.1
6.4
6.4

115F (46C)
TC
Mbh
16.2
17.3
19.6
20.0
24.7
25.9
30.9
30.6
39.9
42.8
48.9
50.4
59.7
59.4
61.5
61.2

SC
Mbh
12.7
13.8
14.8
15.8
18.5
20.8
24.0
24.3
29.5
33.9
36.4
39.2
45.1
46.5
45.9
47.3

PI
kW
2.1
2.2
2.4
2.4
3.2
3.3
3.5
3.5
4.9
5.0
5.3
5.4
6.8
6.8
7.1
7.1

*See notes in page 12

Air Conditioning Equipment . Built in the Gulf... for the World

11

SKM Ducted Mini Split Systems


Combination Ratings - RXH-D and DCYP Units
Capacity Ratings 50 Hz
Outdoor
Unit

Indoor
Unit

Indoor Unit
Air Flow
Rate

RXH-5DC

DCYP

CFM

020
025
025
030
030
040
040
045
045
050
050
060
060

06/30
06/40
08/30
08/40
10/30
10/40
12/30
12/40
15/30
15/40
18/30
18/40
21/30

686
680
785
777
1061
1046
1331
1317
1536
1519
1914
1882
2200

Air on coil Temperature DB/WB-80/67F (26.6/19.4C)

Air on coil Temperature DB/WB-76/63F (24.4/17.2C)

Ambient(Condenser Entering Air)Temperature

Ambient(Condenser Entering Air)Temperature

95F (35C)
TC
Mbh
19.1
24.7
24.6
28.3
29.7
33.5
33.5
42.8
42.3
50.8
52.1
59.9
59.3

SC
Mbh
14.1
17.0
17.3
19.5
22.0
24.5
25.9
30.8
31.3
36.1
39.0
43.8
44.6

105F (41C)
PI
kW
1.9
2.6
2.5
2.7
2.8
2.6
2.6
3.4
3.4
3.2
3.2
3.7
3.7

TC
Mbh
18.1
23.5
23.4
27.0
28.4
31.8
31.9
41.1
40.6
48.9
50.1
57.5
57.0

SC
Mbh
13.8
16.5
16.8
19.0
21.5
23.8
25.3
30.1
30.7
35.4
38.2
42.9
43.7

PI
kW
2.0
2.7
2.7
2.9
3.0
2.8
2.8
3.8
3.8
3.6
3.6
4.3
4.3

115F (46C)
TC
Mbh
17.0
22.3
22.2
25.7
27.1
30.1
30.2
39.3
38.9
46.9
48.0
55.1
54.6

SC
Mbh
13.4
16.1
16.4
18.5
21.0
23.2
24.7
29.5
30.0
34.6
37.5
42.0
42.9

PI
kW
2.1
2.9
2.9
3.1
3.2
3.0
3.0
4.2
4.2
4.0
4.0
4.9
4.9

95F (35C)
TC
Mbh
17.7
23.1
23.0
26.3
27.6
31.1
31.2
40.0
39.6
47.5
48.7
55.9
55.4

SC
Mbh
14.2
17.1
17.4
19.6
22.1
24.6
26.1
31.1
31.6
36.5
39.4
44.2
45.0

105F (41C)
PI
kW
1.8
2.4
2.4
2.6
2.7
2.5
2.5
3.3
3.3
3.1
3.1
3.7
3.7

TC
Mbh
16.8
21.9
21.8
25.0
26.2
29.6
29.6
38.4
38.0
45.6
46.7
53.7
53.2

SC
Mbh
13.8
16.6
16.9
19.1
21.6
24.0
25.5
30.4
31.0
35.7
38.6
43.3
44.1

PI
kW
1.9
2.6
2.6
2.8
2.9
2.7
2.7
3.7
3.7
3.5
3.1
3.7
3.7

115F (46C)
TC
Mbh
15.8
20.6
20.5
23.7
24.9
27.9
28.0
36.7
36.4
43.7
44.7
51.4
50.9

SC
Mbh
13.5
16.1
16.4
18.5
21.0
23.3
24.9
29.8
30.3
34.9
37.8
42.3
43.2

PI
kW
2.0
2.8
2.8
3.0
3.1
2.9
2.9
4.1
4.1
3.9
3.9
4.8
4.8

Capacity Ratings 60 Hz
Outdoor
Unit

Indoor
Unit

Indoor Unit
Air Flow
Rate

RXH-6DC

DCYP

CFM

020
020
025
025
030
030
040
040
045
045
050
050
060
060

06/30
06/40
06/40
08/30
08/40
10/30
10/40
12/30
12/40
15/40
15/40
18/30
18/40
21/30

581
583
583
735
732
984
986
1147
1150
1450
1450
1813
1814
2190

Air on coil Temperature DB/WB-80/67F (26.6/19.4C)

Air on coil Temperature DB/WB-76/63F (24.4/17.2C)

Ambient(Condenser Entering Air)Temperature

Ambient(Condenser Entering Air)Temperature

95F (35C)
TC
Mbh
19.7
21.1
23.8
24.3
29.2
30.7
37.1
36.6
46.3
49.8
55.9
57.4
64.9
64.7

SC
Mbh
13.5
14.7
15.7
16.7
19.4
21.7
25.3
25.5
30.6
35.0
37.4
40.1
45.0
46.5

105F (41C)
PI
kW
2
2.0
2.3
2.3
3.1
3.1
3.3
3.3
4.0
4.1
4.0
4.1
4.8
4.8

TC
Mbh
18.7
20.1
22.5
23.0
27.9
29.3
35.2
34.8
44.5
47.8
53.8
55.2
62.3
62.1

SC
Mbh
13.1
14.3
15.2
16.2
18.9
21.2
24.5
24.9
29.9
34.3
36.6
39.3
44.0
45.5

PI
kW
2.1
2.2
2.4
2.4
3.2
3.3
3.5
3.5
4.5
4.6
4.5
4.6
4.8
5.5

115F (46C)
TC
Mbh
17.7
19.1
21.2
21.7
26.6
28.0
33.4
33.0
42.7
45.9
51.6
53.0
59.7
59.5

SC
Mbh
12.7
13.9
14.7
15.7
18.4
20.7
23.8
24.2
29.2
33.6
35.8
38.5
43.1
44.6

PI
kW
2.2
2.3
2.5
2.6
3.3
3.4
3.7
3.7
5.0
5.1
5.0
5.1
6.1
6.1

95F (35C)
TC
Mbh
18.3
19.5
22.2
22.7
27.2
28.6
34.5
34.1
43.4
46.6
52.3
53.7
60.7
60.5

SC
Mbh
13.6
14.7
15.9
16.9
19.6
21.9
25.4
25.7
31.0
35.4
37.9
40.6
45.5
47.0

105F (41C)
PI
kW
1.9
2.0
2.2
2.2
2.9
3.0
3.2
3.1
3.9
4.0
4.0
4.0
4.7
4.7

TC
Mbh
17.2
18.4
21.0
21.4
25.9
27.2
32.7
32.3
41.6
44.7
50.2
51.6
58.2
58.0

SC
Mbh
13.1
14.3
15.3
16.4
19.0
21.3
24.7
25.0
30.2
34.7
37.0
39.7
44.5
45.9

PI
kW
2
2.1
2.3
2.3
3.1
3.2
3.3
3.3
4.4
4.5
4.4
4.5
5.4
5.4

115F (46C)
TC
Mbh
16.2
17.3
19.6
20.0
24.7
25.9
30.9
30.6
39.9
42.8
48.2
49.5
55.6
55.5

SC
Mbh
12.7
13.8
14.8
15.8
18.5
20.8
24.0
24.3
29.5
33.9
36.1
38.8
43.4
44.9

PI
kW
2.1
2.2
2.4
2.4
3.2
3.3
3.5
3.5
4.9
5.0
4.9
5.0
6.0
6.0

Notes : 1. Shaded areas represent matched cooling capacities based as per AHRI Standards 210/240, 80/67F (26.6/19.4C) DB/WB temperature
of air entering the indoor coil and 95F outside air dry bulb. Capacities at other ambient temperature as shown.
2. For matched conditions, at entering condition other than shown, consult SKM.
3. Direct interpolation is permissible but extrapolation is prohibited.
4. Combination ratings are based on indoor and outdoor units at the same elevation and connected by 25 ft. (7.6 m) of refrigerant tubing.
For tubing in excess of 25 feet, slight capacity reduction will occur (approximately 0.5% per 50 feet length). Do not exceed 120 feet
tubing length without checking with SKM.
5. Matching systems will operate satisfactorily at desert conditions of 125F (51.7C) air entering outdoor unit and 80/67F (26.6/19.4C)
DB/WB air entering the indoor coil.
6. TC - Total cooling capacity in Mbh (1000 Btuh)
SC - Sensible cooling capacity in Mbh (1000 Btuh)
PI - Power input in kW (compressor only)
To convert Mbh to kW, divide by 3.413
To convert cfm to l/s, divide by 2.12

12

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


Electrical Data - RXV & DCYP
Vertical Discharge Outdoor Unit: RXV-50Hz
Model

R XV

020

MFA
MCA

11.4
51
0.9
32
15

Electrical

Power Supply
Comp. RLA
LRA
Condenser motor FLA

Unit Characteristics

025
030
220-240V/1Ph/50Hz
15
16.5
58
58
0.9
0.9
40
40
20
22

040

045

15.3
85
0.9
40
20

7.3
50
0.7
20
10

050
060
380-415V/3Ph/50Hz
9.6
10.5
61.8
74
0.7
0.7
25
25
13
14

070
10.9
74
0.7
32
15

Indoor Unit: DCYP-50Hz


Unit Size
Motor

Type
Size
Quantity

Maximum
Amps

Speed

DCYP
Watts
#
High
Medium
Low

06

08

150
1
1.3
0.9
0.8

150
1
1.4
1.1
0.8

10
12
15
18
21
220-240V/1Ph/50Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
1
2
2
2
2
1.3
2.6
2.8
2.6
2.8
1.1
1.8
2.2
2.2
2.2
0.8
1.6
1.6
1.6
1.8

21
150
2
2.8
2.2
1.8

Vertical Discharge Outdoor Unit: RXV-60Hz


Model

021

RXV

Electrical

Power Supply

031

041

046

051

061

071

15.6
9.4
91
54
2.5
0.8
40
25
22
13

(i) 220V/3Ph/60Hz
(ii) 380V/3Ph/60Hz
18.2
21.4
11
12
124
156
75
70
2.5
2.5
0.8
0.8
50
63
32
32
25
29
15
16

22.0
13.2
156
70
2.5
0.8
63
32
30
17

RLA
COMPRESSOR
LRA

FLA

(i)
(ii)
(i)
(ii)

(i)
(ii)

(i)
(ii)
(i)
MCA
(ii)
MFA

Unit Characteristics

026

(i) 220V/1Ph/60Hz
11.2
55
0.9
32
15
-

13.2
56
0.9
32
18
-

06

08

150
1
1.1
0.8
0.7

150
1
1.4
0.95
0.75

16.2
65
0.9
40
21
-

19.4
90
0.9
50
25
-

Indoor Unit: DCYP-60Hz


Unit Size
Motor

Type
Size
Quantity

Maximum
Amps

Speed

DCYP
Watts
#
High
Medium
Low

10
12
15
18
21
220V/1Ph/60Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
1
2
2
2
2
1.5
2.2
2.8
3
3.4
1.25
1.6
1.9
2.5
2.6
0.9
1.4
1.5
1.8
1.9

Air Conditioning Equipment . Built in the Gulf... for the World

21
150
2
3.4
2.6
1.9

13

SKM Ducted Mini Split Systems


Electrical Data - RXH-D & DCYP
Side Discharge Outdoor Unit: RXH-D-50Hz
Model

RXH- 5DC

Electrical

Power Supply
Comp. RLA
LRA
Condenser motor FLA

020

MCA
MFA

10.5
50
0.61
14
25

DCYP

06

Watts
#
High
Medium
Low

150
1
1.3
0.9
0.8

Unit Characteristics

025
030
220-240V/1Ph/50Hz
13.2
17
65
112
0.79
1.38
18
23
32
40

040
19.3
112
1.38
26
50

045

050
060
380-415V/3Ph/50Hz
10.7
10.7
10
60
60
67
0.695 X 2
0.695 X 2
0.695 X 2
15
15
14
32
32
25

Indoor Unit: DYDP-50Hz


Unit Size
Motor

Type
Size
Quantity

Maximum
Amps

Speed

08
10
12
15
18
220-240V/1Ph/50Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
1
1
2
2
2
1.4
1.3
2.6
2.8
2.6
1.1
1.1
1.8
2.2
2.2
0.8
0.8
1.6
1.6
1.6

21
150
2
2.8
2.2
1.8

Side Discharge Outdoor Unit: RXH-D-60Hz

Electrical

Model

RXH- 6DC

020

025

RLA
LRA

9.3
56
0.78
13
25

12.8
66.51
0.78
17
32

06

08
10
12
15
18
220V/1Ph/60Hz,3 Speed Electric Motor with Permanent Split Capacitor
150
150
150
150
150
1
1
2
2
2
1.4
1.5
2.2
2.8
3
0.95
1.25
1.6
1.9
2.5
0.75
0.9
1.4
1.5
1.8

Power Supply
COMPRESSOR
Condenser motor FLA
MCA
MFA

Unit Characteristics

030
220V/1Ph/60Hz
15.4
95
1.35
21
40

040

045

050

060

19.8
158
1.35
26
50

22.9
164
0.72 X 2
30
63

22.9
164
0.72 X 2
30
63

27.1
188
0.72 X 2
36
63

Indoor Unit: DYDP-60Hz


Unit Size
Motor

Type
Size
Quantity

Maximum
Amps

Speed

14

DCYP
Watts
#
High
Medium
Low

150
1
1.1
0.8
0.7

Air Conditioning Equipment . Built in the Gulf... for the World

21
150
2
3.4
2.6
1.9

SKM Ducted Mini Split Systems


Options
Thermostat
Thermostat is wall mounted decorative type, with large LCD and backlight. Buttons are provided for power on/off, fan speed selection,
cooling or heating mode selection, set point adjustment and sleep mode selection. Indoor temperature and set point are displayed
simultaneously. Apart from that, display provides fan mode (high, medium, low or auto) and operating mode (cool or heat).

Note: Optional remote control and remote sensor are available on request.

Electric Heater
Electric heaters are available as an option with U shaped finned tubular heating elements with automatic reset thermal safety
cut-out. Order should specify FEH1 for Variant 1 and FEH2 for Variant 2. With the indoor units.

Unit Size

No. Of Heater Elements x kW


Variant 1

Variant 2

1 x 1.0

2 X 1.0

08

1 x 1.5

2 X 1.5

10

1 x 1.0 + 1 x 1.5

3 X 1.5

12

1 x 3.0

2 X 3.0

15

1 x 3.0

2 X 3.0

18

1 x 4.0

2 X 4.0

21

1 x 4.0

2 X 4.0

06

Heater Contactors are not included as standard and must be field supplied and installed.

Expansion Valves
Expansion Valves instead of orifice for the following combinations:
RXV-020 + DCYP-06/3 up to RXV-040 + DCYP-12/3 for 50Hz.
RXV-021 + DCYP-06/3 up to RXV-041 + DCYP-12/3 for 60Hz.
RXH-5DC & RXH-6DC combination for DCYP (All models).

Air Conditioning Equipment . Built in the Gulf... for the World

15

SKM Ducted Mini Split Systems


Fan Performance - 50Hz
3 Rows
Speed

DCYP

06
08
10
High

12
15
18
21
06
08
10

Medium

12
15
18
21
06
08
10

Low

12
15
18
21

16

4 Rows

External Static Pressure


inwg

0.1

0.2

0.3

0.4

0.1

0.2

0.3

0.4

Pa
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s

25
686
324
785
371
1061
501
1331
628
1536
725
1914
903
2200
1038
517
244
604
285
721
340
1023
483
1231
581
1442
681
1665
957
397
187
485
229
465
219
776
366
957
451
987
466
1122
836

50
667
315
759
358
1002
473
1291
609
1490
703
1798
848
2021
954
501
236
590
278
730
344
990
467
1202
567
1430
675
1636
897
384
181
466
220
466
220
744
351
918
433
1012
478
1151
814

75
643
304
736
347
924
436
1241
586
1445
682
1655
781
1830
864
481
227
574
271
711
336
947
447
1165
550
1369
646
1552
822
358
169
445
210
474
224
691
326
876
413
993
469
1113
775

100
613
289
711
336
835
394
1178
556
1388
655
1491
703
1623
766
454
214
553
261
669
315
887
419
1116
526
1268
599
1430
736
324
153
421
199
448
211
625
295
828
391
899
424
990
721

25
680
321
777
367
1046
493
1317
622
1519
717
1882
888
2150
1015
514
243
601
284
724
341
1016
480
1224
578
1444
681
1680
933
396
187
482
228
464
219
773
365
951
449
988
466
1150
831

50
660
312
753
355
983
464
1276
602
1476
696
1761
831
1943
917
498
235
587
277
728
344
982
463
1194
563
1422
671
1626
869
381
180
463
219
467
220
738
348
912
431
1014
478
1168
804

75
636
300
730
345
906
428
1223
577
1429
674
1618
763
1759
830
478
225
571
270
706
333
937
442
1155
545
1354
639
1532
795
355
167
442
209
474
224
684
323
870
411
987
466
1117
761

100
604
285
704
332
817
386
1156
546
1368
645
1456
687
1562
737
449
212
549
259
661
312
875
413
1104
521
1251
590
1404
711
321
152
419
198
445
210
618
291
822
388
889
419
990
705

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


Fan Performance - 60Hz
3 Rows
Speed

DCYP

06
08
10
High

12
15
18
21
06
08
10

Medium

12
15
18
21
06
08
10

Low

12
15
18
21

4 Rows

External Static Pressure


inwg

0.1

0.2

0.3

0.4

0.1

0.2

0.3

0.4

Pa
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s
cfm
l/s

25
581
274
735
347
984
464
1147
541
1457
688
1804
851
2190
1034
442
209
565
267
612
289
876
414
1148
542
1180
557
1362
862
327
155
452
213
517
244
635
299
888
419
1015
479
1132
638

50
587
277
724
341
990
467
1151
543
1433
676
1813
856
2141
1010
426
201
547
258
585
276
841
397
1111
524
1156
545
1355
852
302
143
427
202
447
211
585
276
841
397
895
422
1005
640

75
583
275
711
335
991
467
1136
536
1406
664
1811
854
2057
971
404
191
528
249
594
280
795
375
1071
506
1204
568
1420
834
275
130
403
190
396
187
532
251
794
375
813
383
921
639

100
570
269
696
328
982
463
1106
522
1374
648
1789
844
1955
923
379
179
508
240
627
296
744
351
1030
486
1263
596
1472
809
247
117
380
179
367
173
478
226
748
353
771
364
884
632

25
583
275
732
346
986
465
1150
543
1450
684
1807
853
2180
1029
440
208
562
265
607
287
871
411
1140
538
1172
553
1355
858
326
154
449
212
511
241
630
297
882
416
1001
472
1112
638

50
587
277
721
340
991
468
1149
542
1425
673
1814
856
2097
990
423
200
544
257
584
275
834
394
1103
520
1158
547
1362
846
300
142
425
201
443
209
581
274
835
394
887
418
992
640

75
581
274
707
334
989
467
1130
533
1397
659
1807
853
2007
947
401
189
525
248
597
282
788
372
1064
502
1214
573
1436
826
273
129
401
189
394
186
528
249
789
372
808
382
915
638

100
566
267
692
327
978
461
1095
517
1364
643
1780
840
1901
897
376
177
505
238
630
298
737
348
1023
483
1267
598
1473
799
246
116
378
178
366
173
475
224
743
351
770
363
882
630

Air Conditioning Equipment . Built in the Gulf... for the World

17

SKM Ducted Mini Split Systems


Recommended Suction and Liquid Line Sizes
Recommended Suction And Liquid Line Sizes For Various Length of Run to Evaporator Side- Ft. (m)

RXV Model(Vertical Discharge


Condensing Unit)
020
025
030
040
045
050
060
070

25 (7.6)
Suction
5/8
5/8
5/8
3/4
3/4
3/4
7/8
7/8

021
026
031
041
046
051
061
071

50 (15.2)
Liquid
3/8
3/8
3/8
3/8
3/8
3/8
1/2
1/2

Suction
5/8
3/4
3/4
3/4
7/8
7/8
1 1/8
1 1/8

Liquid
3/8
3/8
3/8
3/8
1/2
1/2
1/2
1/2

75 (22.9)
Suction
3/4
3/4
3/4
7/8
7/8
1 1/8
1 1/8
1 1/8

Liquid
3/8
3/8
1/2
1/2
1/2
1/2
1/2
1/2

100 (30.5)
Suction
3/4
3/4
7/8
7/8
1 1/8
1 1/8
1 1/8
1 1/8

Liquid
3/8
3/8
1/2
1/2
1/2
1/2
1/2
1/2

120 (36.6)
Suction
3/4
3/4
7/8
7/8
1 1/8
1 1/8
1 1/8
1 1/8

Liquid
3/8
1/2
1/2
1/2
1/2
1/2
1/2
1/2

Recommended Suction And Liquid Line Sizes For Various Length of Run to Evaporator Side- Ft. (m)

RXH-D Model
(Side Discharge
Condensing Unit)

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

Suction

Liquid

20
25
30
40
45
50
60

5/8
5/8
5/8
3/4
3/4
3/4
7/8

3/8
3/8
3/8
3/8
3/8
3/8
1/2

5/8
3/4
3/4
3/4
7/8
7/8
1 1/8

3/8
3/8
3/8
3/8
1/2
1/2
1/2

3/4
3/4
3/4
7/8
7/8
1 1/8
1 1/8

3/8
3/8
1/2
1/2
1/2
1/2
1/2

3/4
3/4
7/8
7/8
1 1/8
1 1/8
1 1/8

3/8
3/8
1/2
1/2
1/2
1/2
1/2

3/4
3/4
7/8
7/8
1 1/8
1 1/8
1 1/8

3/8
1/2
1/2
1/2
1/2
1/2
1/2

25 (7.6)

50 (15.2)

75 (22.9)

120 (36.6)

100 (30.5)

Notes :
1. Pipe diameters are based on equivalent length of copper tubing sizes.
2. Pipe sizes are based on 2F (1.1C) or less temperature losses for liquid and suction line in equivalent pipe length.
3. If the condensing unit is below the evaporating unit, the maximum lift should not exceed to 66 feet.
4. Do not exceed 120 feet piping length without checking with SKM.
5. These sizes are for guidance only. For detailed proper piping, refer to recognized piping references like ASHRAE
Guide and Data Book.
The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant connections
available on the outdoor or indoor unit. Necessary transformation may be required and its field performed.

18

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


Typical Refrigeration Piping - RXV & DCYP
Legend:

1. RXV Air Cooled Condensing Unit


2. DX DCYP Fan Coil Unit
3. Liquid Line
4. Suction Line
5. Metering Device (orifice/exp. valves)
6. Packed Valves

REFRIGERANT PIPING

Correct design and size of refrigerant


piping is necessary for proper operation.
The refrigerant piping generally should be
designed to accomplish the following:
a. To ensure proper refrigerant feed to
the evaporator.
b. To provide practical refrigerant line
sizes without excessive pressure
drop.
c. To maintain uniform return of
lubricating oil to the compressor.
d. To prevent refrigerant from entering
the compressor and causing compressor
damage due to slugging.

Air Conditioning Equipment . Built in the Gulf... for the World

19

SKM Ducted Mini Split Systems


Typical Refrigeration Piping - RXH-D & DCYP
1

Legend:
1. RXH-D Air Cooled Condensing Unit
2. DX DCYP Fan Coil Unit
3. Liquid Line
4. Suction Line
5. Metering Device (orifice/exp. valves)
6. Packed Valves
6

3
4
2
2

4
1

20

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


Typical Wiring Diagram - RXV & DCYP

THERMOSTAT WITH 3SPEED SWITCH


(BY OTHERS / OPTION)

** 220~240V/1PH/50HZ
L

** 220~240V/1PH/50HZ
FIELD SUPPLY
L N

CONTA CTO R

CAPACI TO R

L1

L2

C1

RUN CAP ACITOR

T1

T2

ANTI SHO RT
C YCLE TIME R

LPS

H PS

220~240V

FAN MO TOR

FIELD SIDE

EQUIP . GRND.

TO IND OOR UNIT

1
FROM INDOO R UNIT
FIELD CONNE CTIO NS
2

JN. BO X FOR
CUSTOM ER
CONNECTION

C
S

FIELD WIRING (BY OT HERS)

FAN
MOTOR
1

START CAPACITOR

OUTDOOR UNIT MODEL (RXV - 020,025,030 & 040)

MOTO R BODY
EARTHING
E

FL

FM

FH

FL

FM

FH

STAR T
RE LAY

UNIT SIDE

CO MP RE SS OR

FAN
MOTOR
2

(IF APPLICABLE)

INDOOR UNIT(DCYP)

** (380~415V / 3PH / 50HZ)


L1 L2 L3

THERMOSTAT WITH 3SPEED SWITCH


(BY OTHERS / OPTION)

** 220~240V/1PH/50HZ

Grd

GROUNDING LUG

L1

T1

L2

T2

L3

T3

ANTI SHOR T
CYCLE TIMER

220 -240V

CONTACTO R
C
(AUX. CO NTACT)

LP S

FIELD SIDE

C RANKCAS E
HE ATER

HP S

FR OM INDO OR UNIT
FIELD CONNECTIO NS

FROM INDOO R UNIT


FIELD CONNE CTIO NS
2

OUTDOOR UNIT MODEL (RXV - 045,050,060 & 070)

FAN
MOTOR
1

UNIT SIDE

MOTO R BODY
EARTHING
E

FL

FM

FH

CONDE NSER FAN


MO TO R

FL

CO MPR ESS OR
M OTOR

FM

3~
MOTOR

3~
MOTOR

FH

JN. BO X FOR
CUSTOM ER
CONNECTION

FAN
MOTOR
2

FIELD WIRING (BY OT HERS)

INDOOR UNIT(DCYP)

Air Conditioning Equipment . Built in the Gulf... for the World

21

T3

XT2

L-PRO

H-PRO

Air Conditioning Equipment . Built in the Gulf... for the World

RED

POWER

CAP2

BLUE

XT1

RED

L N

N 1

TDR

RED

BLACK

RED

TDR

TO INDOOR UNIT

XT3

Y/G

KM1

A2

BLUE

BLACK

A1

OUTDOOR UNIT(RXH- 020 5DC & RXH- 025 5DC)

Y&G

FAN

BLACK

BLACK

22
TERMINAL
TIME DELAY RELAY

TDR

HIGH/LOW PRESSURE SWITCH

XT3

2WAY TERMINAL

KM1

H/L-PRO

OUT DOOR FAN


AC CONTACTOR

FAN
5WAY TERMINAL

COMPRESSOR

COMP.

XT2

OUT DOOR FAN CAPACITOR

CAP 2

XT1

COMPRESSOR CAPACITOR

Y&G

PART NAME

COMP

CAP 1

WHITE

CODE

RED

RED

CAP1

RED/GREY
BLUE

BLACK

FAN
MOTOR

YLO-GRN
WHITE

INDOOR UNIT(DCYP- 06 & 08)

JUNCTION BOX

FROM
N
OUTDOOR UNIT

Y/G

THERMOSTAT WITH 3SPEED SWITCH


(BY OTHERS / OPTION)

FIELD SIDE
UNIT SIDE

POWER SUPPLY:- 220~240/1PH/50HZ

SKM Ducted Mini Split Systems

Typical Wiring Diagram - RXH-D & DCYP

Air Conditioning Equipment . Built in the Gulf... for the World

WHITE

POWER

BLACK

RED

K3

N E

XT4

XT2

TO INDOOR UNIT

RED

TRANS

CN208

CN203

CN206

CN9

L N

RED

SW1

BLACK

1 2 4

CN40

CN38
CN39

TO INDOOR UNIT

CT2

P.C.B

XT1
OUT DOOR FAN
ROOM TEMPARATURE

FAN
T4

TEMPARETURE PROTECTOR SWITCH


P.C. BOARD SOCKETS

TERMINAL

CN100-208

CONTACTOR

XT3, XT4
K2

CURRENT DETECT

KM8

CONNECTORS

CT2

XP1~ 2, XS1~ 2

PIPE TEMPARATURE

POWER TRANSFORMER

TRANS

T3

HIGH, LOW PRESSURE SWITCH

FAN

CAPACITOR

RED

BLACK

CAP2

XT3

Y/G

K1, K3

PART NAME

RED

BLUE

WHITE

COMP.

CAP 1, 2

CODE

CU-32A

A2

CU-32A

A1

RED

S
WHITE

CAP1

BLACK

KM8

OUTDOO R UNIT(RXH- 030 5DC & RXH- 040 5DC)

BLACK

T4

BLACK

RED

BLACK

WHITE

XP1 XS1

K1

BLACK

XP2 XS2

T3

K2

BLACK

CN200

RED

CN201

BLUE

RED
RED
BLACK

6
22

BLACK

5
21

RED

2
4

RED

BLUE

BLACK
1
3
JUNCTION BOX

L
FROM
N
OUT DOOR UNIT
1

Y/G

YLO-GRN

RED/GREY
BLUE

BLACK

YLO-GRN
WHITE

(APPLICABLE FO R
RXH- 040 5DC + DCYP- 12)

MOTOR BODY
EARTHING

THERMOSTAT WITH 3SPEED SWITCH


(BY OTHERS / OPTION)

INDOO R UNIT(DCYP- 10 & 12)

BLACK

FAN
MOTOR

BLUE

RED/GREY

FAN
MOTOR

WHITE

FIELD SIDE
UNIT SIDE

POWER SUPPLY: 220~240V/1PH/50HZ

SKM Ducted Mini Split Systems

23

XP8

XP9

XS9

Air Conditioning Equipment . Built in the Gulf... for the World

CAP4

XT6

BLUE

YELLOW

FAN4

RED

Y/G

WHITE

CAP3

YELLOW

FAN3

RED

Y/G

XT7

BLUE

XT5

XT2

BLACK

CN206

TO INDOOR UNIT

1 2 3 4

RED

BLACK

BLACK

CN100

1
3
5

WHITE
BLUE

TOINDOOR UNIT

CN208
Y/G

COMP.

W(T3)

KM1

CN203
U(T1)

Y/G

RED

WHITE
V(T2)

BLUE

22

A2

T5

POWER
380~ 415V/3PH/50Hz

21

A1

RED

XT1

CT1

ORANGE

A B C N

RED

CN200

YELLOW

OUTDOOR UNIT(RXH- 045, 050 & 060 5DC)

WHITE

WHITE

RT3 XS8

WHITE

T3

BLACK

T4

CN201

WHITE

HI-PRO K1

BLUE

CN09

JUNCTION BOX

FROM
N
OUT DOOR UNIT

YLO-GRN

RED/GREY
BLUE

BLACK

BLUE

FAN
MOTOR
2

MOTOR BODY
EARTHING

AC CONTACTOR
5 WAY TERMINAL
CONNECTOR
CONNECTORS

XT1
XT5, XT6
XS8-9, XP8-9

P.C. BOARD S OCKETS

4WAY TER MINAL


XT2
CN100-208

LOW PRESS URE S WITCH


L.P. SW

TEMP. PROTECT SWITCH

PIPE TEMP. SENSOR


R T3

K1

TRANS FOR MER


T5

CURR ENT DETECTOR

FAN CAPACITOR
KM1

HIGH PRESS UR E SWITCH

OUT DOOR FAN


CAP3,CAP4

CT1

COMPR ESSOR
FAN3,FAN4

H-PRO

PART NAME

CODE
COMP

THERMOSTAT WITH 3SPEED SWITCH


(BY OTHERS / OPTION)

RED/GREY
WHITE

WHITE

INDOOR UNIT(DCYP- 15,18 & 21)

FAN
MOTOR
1

Y/G

BLACK

L.P. SW

YLO-GRN

24
FIELD SIDE
UNIT SIDE

POWER SUPPLY:- 380~415V/3PH/50HZ

SKM Ducted Mini Split Systems

SKM Ducted Mini Split Systems


Dimensional Data

OUTDOOR UNITS - VERTICAL DISCHARGE

Model: RXV-020 to 040


4
[102]

0.75
[19]

2
[51]

DIMEN SIO NS ARE IN INCH ES [MM]

4
[102]

MO DEL

1.7
[44]

MOUNT. HOLES
3/8 [9.5] x 4 NOS.

RXV- 020

23
[584]

23
[584]

25
[635]

24
[610]

RXV- 025

23
[584]

23
[584]

33
[838]

32
[813]

RXV- 030

26
[660]

26
[660]

37
[940]

36
[914]

RXV- 040

26
[660]

26
[660]

37
[940]

36
[914]

1
3

0.79
[20]

SUCTION
LIQUID

ACCESS
CABLE ENTRY
HOLE 25MM(WITH
RUBBER GROMMET)

1
[25]

4
[102]

Model: RXV-045 to 070

0.75
[19]

2
[51]

LEGEND
1. CONDENSER FAN
2. COMPRESSOR
3. CONTROL PANEL
4. CONDENSER COIL
NOTE: MODEL RXV- 045 (1 ROW)

0.79
[20]

4
[102]

MODEL RXV- 050,060 & 070 ( 2 ROWS)


1.8
[45]

MOUNT. HOLES
3/8 [9.5] x 4 NOS.
29
[736]

29
[737]

32
[813]

3
SUCTION
2

ACCESS

LIQUID
CABLE ENTRY
HOLE 25MM(WITH
RUBBER GROMMET)

1
[25]

33
[838]

Air Conditioning Equipment . Built in the Gulf... for the World

25

SKM Ducted Mini Split Systems


OUTDOOR UNITS - SIDE DISCHARGE
Models: RXH-020-5DC & RXH-025-5DC

Models: RXH-030-5DC & RXH-040-5DC


39
[990]

.5
[13]

27.3
[694]

37.8
[960]

33.3
[845]

24.6
[624]

15.6
[396]

7.1
[181]

22.1
[560]

14.2
[360]

12.3
[313]

13.2
[335]

14.2
[360]
13.2
[336]

5.6
[141]

ALL DIMENSIONS ARE IN INCHES [MM]

Models: RXH-045-5DC, RXH-050-5DC & RXH-060-5DC

15.4
[390]

14.6
[370]
13.4
[340]

49
[1245]

37
[940]

5.9
[150]

25.6
[650]

ALL DIMENSIONS ARE IN INCHES [MM]

26

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


Dimensional Data
DCYP INDOOR UNITS
UNIT SIZES 06 - 10
1

UNIT SIZES 12 - 21
4-5/8 [16]
MTG.HOLES
WITH RUBBER
GROMMETS

TERMINAL
CONNECTION

TERMINAL
CONNECTION

DRAIN
3/4 [19]

2
[51]

DRAIN
3/4 [19]

1.5
[38]

1.5
[38]

8.5
[216]

8.5
[216]

0.75
[19]

0.75
[19]

11.25
[286]

1
[25]

1
[25]

LIQUID

D1

FILTER
REMOVAL
SUCTION

FREE RETURN-STANDARD

1.5

1
[25]

INSULATED R.A.PLENUM

SUPPLY FAN

FAN MOTOR

COOLING COIL

ACCESS PANEL

FILTER

06
08
12
15

06

DDP
K
L
M
UNIT
DIMENSIONS FOR
INCH MM INCH MM INCH MM
MODEL

LEGEND

DDP
UNIT
MODEL

[38]

LEFT HAND UNIT SHOWN


RIGHT HAND UNIT OPPOSITE

DxA

2
[51]

FILTER
REMOVAL

22

559 27.68 703

3R / 4R + HEATER 21.78 553 29.41 747

2.64

67

4.61 117

26.12 663 29.93 760

0.79

20

3R / 4R + HEATER 26.82 681 31.66 804

1.82

46

3R / 4R

10
18
21

5
REAR RETURN-OPTIONAL
(DUCTED)

3R / 4R

CONNECTION SIZES
A

D1

L IQ UID

SUC TION

3R

INCH MM INCH MM INCH MM INCH MM INCH MM INCH MM


23

584

33

838 21.5

546

12

305 12.5
305 12.5

4R
3R
4R
INCH MM INCH MM INCH MM INCH MM INCH MM

317

15

381 16.42 417

3/8

10

3/8

10

317

15

381 16.42 417

5/8

16

5/8

16

08

27

686

37

940 25.5

648

3/8

10

3/8

10

5/8

16

5/8

16

10

27

686

37

940 25.5

648 14.5

368 14.84 377 17.32 440 18.67 474

3/8

10

3/8

10

5/8

16

5/8

16

12

39

991

49

1245 37.5

952

12

305 12.5

317

15

381 16.42 417

3/8

10

3/8

10

5/8

16

7/8

22

15

45

1143

55

1397 43.5 1105

12

305 12.5

317

15

381 16.42 417

1/2

13

1/2

13

7/8

22

7/8

22

18

45

1143

55

1397 43.5 1105 14.5

368 14.84 377 17.32 440 18.67 474

1/2

13

1/2

13

1 1/8

29

1 1/8

29

21

51

1295

61

1549 49.5 1257 14.5

368 14.84 377 17.32 440 18.67 474

1/2

13

1/2

13

1 1/8

29

1 1/8

29

12

ALL DIMENSIONS ARE IN INCHES [MM]

Air Conditioning Equipment . Built in the Gulf... for the World

27

SKM Ducted Mini Split Systems


Outdoor Unit Clearance & Spacing

AIR OUT
AIR IN

1525mm

No obstacle

POWER
SOURCE
CONTROL CIRCUIT
CONTROL
PANEL

SPACING FOR
SE RVICE

LIQUID
SUCTION

SPACING FOR AI R
FLOW

AIR IN

30
[762]

14
[356]

AIR IN

SPACING FOR
SE RVICE

SPACING FOR AI R
FLOW

30
[762]

30
[762]

30
[762]

14
[356]

SINGLE UNIT

14
[356]

30
[762]

30
[762]

45
[1143]

MULTIPLE UNITS

28

30
[762]
ALL DIMENSIONS ARE IN INCHES[MM]

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems

SINGLE UNIT:SPACING FOR


SERVICE

20
[ 50
8]

1
[ 30 2
5]

12 ]
5
[ 30
33 ]
8
[ 83

2
[ 50 0
8]

1
[ 30 2
5]

12 ]
5
[ 30

48 9]
1
[12

ALL DIMENSIONS ARE IN INCHES[MM]

Air Conditioning Equipment . Built in the Gulf... for the World

29

SKM Ducted Mini Split Systems


GUIDE SPECIFICATIONS
Ducted mini split Air Conditioning system shall composed of a compact design indoor fan coil unit and floor or Rooftop
mounted outside air cooled condensing unit, rated with AHRI standards 210/240.

CONDENSING UNIT:

The condensing unit shall composed of compressor, motor, coil, and condenser fan.

CONDENSER COIL

The condenser coil shall be air cooled constructed of high efficiency inner grooved copper tube with 3/8 O.D. and
mechanically expanded into hydrophilic aluminum corrugated fins.

COMPRESSOR

Compressor shall be hermetic type, refrigerant gas cooled, furnished with internal overload protection device.

CONDENSER FAN

The condenser fan shall be direct driven propeller type, equipped with statically and dynamically balanced plastic (ASG20)
blades. Complete fan assembly is equipped with heat protect BW 130C condenser fan guard having side discharge air delivery.
For top discharge air delivery, the fan shall be equipped with statically and dynamically balanced alloy blades, and inherent
corrosion resistant shaft. Complete fan assembly is mounted downward on the strong and acrylic coated fan guard.

MOTOR

The motor shall be totally enclosed air over (TEAO), six pole.

CONTROLS

Condensing unit shall be provided with a control panel enclosure comprising all electrical control devices except for the field
supplied room thermostat and shall include the following components as minimum:
Compressor and condenser fan motor contactor
Anti recycling time delay relay
Terminal for external connections.

INDOOR UNIT:

The indoor unit/air handler shall be composed of evaporator coil, fan motor assembly and the metering device.

EVAPORATOR COIL

Evaporator coil shall be constructed of seamless copper tubes with 5/16 OD, mechanically bonded to aluminium fins. The coil
consists of headers of seamless copper and flow control distributor.

EVAPORATOR FAN

Fan shall be double inlet, double width, direct driven with centrifugal type wheel. Fan wheel shall be with multi forward curved
blades. Fan shall be statically and dynamically balanced. Fan housing and wheel shall be made of galvanized steel sheet.

MOTOR

Motor shall be single phase, 3 speed permanent split capacitor type, suitable for 220-240V/1Ph/50-60Hz.Highly efficient with
integral thermal protection. Motor shall have high power factor and shall be with permanent lubricated sleeve bearings.

METERING DEVICE

Indoor unit shall be equipped with refrigerant flow control device.

CASING

The unit casing shall be made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM-A525 that shall be
phospatized and then electro statically dry powder coated of approx 60 microns to provide an extremely tough, scratch resistance,
and excellent anti corrosive protection.

30

Air Conditioning Equipment . Built in the Gulf... for the World

SKM Ducted Mini Split Systems


NOTES:

Air Conditioning Equipment . Built in the Gulf... for the World