PCV0620A
Daikin Industries, Ltd.s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.
JMI-0107
Dealer
JQA-1452
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global_ac/
c All rights reserved
Printed in Japan 09/07/004 Y.K.
Specifications, designs and other content appearing in this brochure are current as of September 2007 but subject to change without notice.
C OOLING ONLY
Cooling Only
50 Hz
A s ys tem with the high c apac ity needed to s uit large- s ized buildings
Benefits for
property
OWNERS
Benefits for
USERS
Air conditioning systems that use new refrigerant and save energy are the norm. However, we at Daikin
have gone much further by maximising our advanced technology developed over 20 years as the
leading manufacturer of individual air conditioning systems. Not only top level air conditioning
performance, we also offer minimal space utilisation, efficient building management and a multitude of
other added value features.
CONSULTANT
and DESIGN OFFICES
Benefits for
Benefits for
INSTALLERS
Daikin offers a compact design for VRVIII outdoor units by
further optimising equipment functions, exceeding the norm for
air conditioning systems. Compact units facilitate installation in
limited areas, such as rooftops, and take up less effective
space. Easier installation work realises fast completion with time
to spare.
A s e ns e of r e s pons ibility
High COPs/Energy savings
Compliant with the RoHS Directive
Less chances of refrigerant leakage
E nha nc e d c om for t
Outdoor units designed for quiet operation
Efficient compressor
Nighttime quiet operation function
Contents
Technologies..................................page 5
Main Features................................page 7
Control Systems............................page 15
Indoor Unit Lineup........................page 25
Outdoor Unit Lineup.....................page 36
Specifications................................page 38
Option List........................................page 48
Indoor units ....................................page 48
Outdoor units .................................page 50
C ontrol s ys tems .............................page 50
Cutting-Edge Technologies
New
N e w ly im p r o v e d f a n s a n d g r ille s
A higher external static pressure has been achievedfrom 58. 8 Pa to 78.4 Pathanks to
reduced internal pressure loss, use of the new fans and the new grilles.
New aero spiral fan and aero asymmetrical fan
The area of these new fan blades has been increased and optimised for each casing. This greatly reduces pressure loss, resulting in
a higher external static pressure.
Blade area
increased by
25% !
Blade area
increased by
Reluctance
DC motor
Neodymium magnet
Diameter of 540 mm x 2
New
Ferrite magnet
20% !
Diameter of 700 mm
Im p r o v in g t h e h ig h e f f ic ie n c y c o m p r e s s o r t o a c h ie v e
a h ig h C O P a n d la r g e r c a p a c it y
H e a t e x c ha nge r
The new heat exchanger contributes to a high COP
because of an increase from 7% to 10% of the effective
length as well as an optimised e-Pass heat exchanger.
S m o o th s in e w a v e D C In v e r te r
By adoption of the Sine
Wave, which smoothes
the rotation of the motor,
operation efficiency is
improved sharply.
C om pa c t a e ro box
Realises a compact casing by stacking the Inverter and
control PCBs plus optimising the internal design to suit
airflow speed. This achieves lower noise and reduces the
power required by the large-diameter fanned outdoor unit.
D C fa n m o to r
Across entire range of models (from 5 to 54 HP).
Efficiency improvement by approximately 40% especially
at low speed.
DC fan motor
structure
DC motor efficiency
100
Efficiency (%)
New
H e a t t r a n s f e r c ir c u it
DC motor
80
Approx.
60
40%
increase
40
AC motor
20
0
200 300
400 500
600
700 800
900 1000
Main Features
Major advances of the VRVIII over the VRVII for large-sized buildings
The latest technology is implemented in the VRVIII system. Surpassing even the VRVII, the new VRVIII
responds to more of the needs of our customers that require air-conditioning solutions for large-sized buildings.
L a r g e c a p a c it ie s f o r la r g e - s iz e d b u ild in g s
L a r g e c a p a c it ie s f o r la r g e - s iz e d b u ild in g s
In d o o r u n its
O u td o o r u n its
New
Daikins indoor unit system offers a large number of connectable indoor units64! Furthermore, our wide range
of indoor units includes 14 types and 79 models to meet the needs of customers.
VRVII
MA series
48 HP
5 4 HP
5 HP
8, 10 HP
Type
The previous outdoor unit had a maximum output of 48 HP. The new units have a top output
of 54 HP! Three morea 50 HP model, a 52 HP model, and a 54 HP modelhave been
introduced, as well as a single 18 HP model that may serve as the main unit in combination
solutions. With the introduction of these new models, outdoor unit combinations can be
made more compact and flexible to suit large-sized buildings.
Ceiling Mounted
Cassette
(Double Flow)
Ceiling Mounted
Cassette
(Multi Flow)
Ceiling Mounted
Cassette Corner
Slim Ceiling
Mounted Duct
Capacity Index
20
1 HP
1.25 HP 1.6 HP
25
31.25
40
2 HP
2.5 HP 3.2 HP
50
62.5
80
4 HP
5 HP
8 HP
10 HP
100
125
200
250
FXCQ-M
FXFQ-M
FXKQ-MA
FXDQ-PVE
FXDQ-PVET
FXDQ-NAVE
2 HP increments
FXDQ-NVET
Ceiling Mounted
Built-in
FXSQ-M
Ceiling Mounted
Duct
FXMQ-MA
Ceiling Suspended
Wall Mounted
Floor Standing
Concealed
Floor Standing
FXHQ-MA
FXAQ-MA
FXLQ-MA
FXNQ-MA
Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system.
C o n n e c tio n u n it s e r ie s in d o o r u n its
Type
Ceiling Suspended
Cassette
Capacity Range
Capacity Index
Connection Unit
0.8 HP
1 HP
1.25 HP
1.6 HP
2 HP
3 HP
4 HP
5 HP
20
25
31.25
40
50
71
100
125
Note: BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data for details.
Main Features
L a r g e c a p a c it ie s f o r la r g e - s iz e d b u ild in g s
New
L a r g e c a p a c it ie s f o r la r g e - s iz e d b u ild in g s
New
A n in c r e a s e d n u m b e r o f c o n n e c ta b le in d o o r u n its
The number of connectable indoor units has been drastically increased from 40 to 64!
E x te n d e d lo n g p ip in g le n g th
Piping length is drastically extended! The long piping length provides more design flexibility, which can match
even large-sized buildings.
40
Up to
64
indoor
units
Max. total
piping length
VRVII
MA series
150
165
175
190
510
50
1000 m
Multiple use
90 m
50 m
q
First
indoor branch
(RXQ8P-54P)
Single use
f
b
h
d
f
b
(RXQ5P)
r
s
New
C o m b in a tio n r a tio
Colours in the diagram above are merely for identifying pipes referenced with symbols such as a .
5 0 % 2 0 0 %
200%
Other indoor
unit models*
Example
Equivalent
piping length
165 m or less
a+f+g+h+i
190 m or less
1000 m or less
a+b+c+d+e+f+g+h+i
Between the first indoor branch and the farthest indoor unit
90 m or less*1
f+g+h+i
10 m or less
k+p
13 m or less
Level
Difference
Example
Outdoor Units
200%
160%
5 m or less
RXQ8P-54P
130%
15 m or less
* For the FXFQ25 models, maximum connection ratio is 130% for the entire range of outdoor units.
Note: If the operational capacity of indoor units is more than 130%, low airflow operation is
enforced in all the indoor units.
Maximum
allowable
piping length
Actual
piping length
Maximum
allowable
level difference
90 m or less
90 m or less
50 m or less
40 m or less
3 Available on request
RXQ8P-54P
RXQ5P
1. No special requirements up to 40 m. The maximum actual piping length can be 90 m, or less depending on conditions. Various conditions
and requirements have to be met to allow utilisation of 90 m piping length. Be sure to refer to the Engineering Data (the latest version of
the VRVIII Engineering Data) for details of these conditions and requirements.
2. 40 m or less if the outdoor unit is below.
3. Available on request if the difference in level is between 50 m and 90 m (if the outdoor unit is above).
10
Main Features
L a r g e c a p a c it ie s f o r la r g e - s iz e d b u ild in g s
New
L a r g e c a p a c it ie s f o r la r g e - s iz e d b u ild in g s
High-COP types (Energy saving types)
H ig h e x te r n a l s ta tic p r e s s u r e 7 8 . 4 P a ( 8 m m H 2 O )
Higher external static pressure has been achieved thanks to the fan grilles and the
dual DC fans that reduce internal pressure loss. Exceeding the previous 58.8 Pa (6
mm H2O) level, Daikin now offers 78.4 Pa
Approx.
(8 mm H2O) external static pressure by
field setting to meet the requirements for
increase!
installation on each floor, often requested
VRVII
MA series
for large-sized buildings.
HP
S ingle unit
78.4 Pa
33.3%
16
18
24
26
28
30
32
34
36
38
5
8
10
78.4 Pa
58.8 P a
12
14
New
S e le c ta b le fr o m tw o ty p e s o f c o m b in a tio n s
16
18
T ota l numbe r
of c onne c te d
outdoor units
10
12
14
18
20
22
24
26
28
30
32
34
36
HP
40
42
44
46
48
50
T ota l numbe r
of c onne c te d
outdoor units
S ingle unit
5
8
10
12
10
12
14
14
16
16
18
T ota l numbe r
of c onne c te d
outdoor units
18
1
38
40
42
44
46
48
50
52
54
E a s ie r in s t a lla t io n a n d m a in t e n a n c e
5
8
New
10
A u to m a tic te s t o p e r a tio n
Simply press the test operation button and the unit performs an automatic system check, including wiring,
shutoff valves, and sensors. The results are returned automatically after the check finishes.
12
14
16
New
18
T ota l numbe r
of c onne c te d
outdoor units
M e m o r y fu n c tio n fo r o p e r a tio n a l d a ta
Operating data for the preceding 3 minutes is automatically stored in memory. Should a malfunction occur, this
speeds up the process of identifying and fixing the cause of the problem. It also helps in developing measures
to eliminate malfunctions.
12
Main Features
A s e n s e o f r e s p o n s ib ilit y
H ig h C O P s
New
It has become essential for air conditioning manufacturers to develop systems that
provide high energy savings. We at Daikin have made great efforts in this field, and
the newly-developed VRVIII delivers highly efficient performance, contributing to high
energy savings.
New
51%*
increase!
4.28
3.47
3.17
3.18
4.27
VRVII
MA series
Operation sound level selectable from 3 steps for the night mode
1
Normal types
(Space saving types)
High-COP types
(Energy saving types)
New
16 HP
24 HP
Cooling operating conditions: Indoor temp. of 27CDB, 19.0 CWB, and outdoor temp. of 35CDB.
New
New
L e s s c h a n c e s o f r e fr ig e r a n t le a k a g e
Conventionally, shutoff valve connections are flanged or flared. In the VRVIII system, the connections for all
outdoor units are brazed, meaning less chance of refrigerant leakage.
100
Capacity %
Approx.
2.81
E ffic ie n t c o m p r e s s o r
New high-performance, low-sound scroll compressor operates at a
faster rate, reducing start-up time. This helps the unit to bring the
room temperature up to the set level quickly.
Ac hieving a high C OP
O u td o o r u n its d e s ig n e d fo r lo w - s o u n d o p e r a tio n
8 hrs
10 hrs
(Initial setting)
50
New
E n h a n c e d c o m fo r t
0
58
55
(Initial setting)
Night Mode
50
45
Step 1: 55 dB
Step 2: 50 dB
Step 3: 45 dB
8:00
12:00
16:00
20:00
4:00
8:00
13
14
Control Systems
I n div idu a l C o n t r o l S y s t e m s
Wired remote controller (Option)
BRC1C62
The same operation modes and settings as with wired remote controllers are
possible.
A signal receiver unit for a Ceiling Mounted Cassette (Double Flow, Multi Flow) type,
Ceiling Suspended type and Wall Mounted type is mounted into the indoor unit.
Signal receiver unit can be
installed on the panel
Wireless remote
controller
(Installed type)
Includes ventilation mode and airflow rate switching, the main functions of HRV series.
24-hour clock function (1-hour backup for power failures)
Programming function for each day of week.
Scheduling possible of start/stop and temperature limit (5 settings/day)
Programming can be enabled or disabled.
Copy function for programmed schedules.
Notes: 1. Standard remote controllers (BRC1C62) not required.
2. If the BRC1D61 is connected to the centralised remote controllers (DCS302CA61,
DCS301BA61, DST301BA61), the schedule function is not available.
BRC1D61
Concealed type
(For hotel use)
(BRC3A61)
Exposed type
(BRC2C51)
Widewired
The
variation
remote
of remote
controller
controllers
supportsfor
a wide
indoor
range
unitsof control functions
Control of Cool/Heat In all the series of VRV, Cool/Heat changeover in the same refrigerant
circuit can be changed by the remote controller of the indoor unit.
changeover
Group control
Remote controller
Equipment
related to the
central control
Outdoor
unit
Indoor unit
Remote controller
HRV
Remote control
FXCQ
FXFQ
FXKQ
FXDQ
FXSQ
FXMQ
FXHQ
FXAQ
FXL(N)Q
FXUQ
(BRC1C62)
(BRC1D61)
Remote
controller
Remote
controller
Remote controller
Remote controller
Remote controller
Remote controller
(BRC2C51)
15
16
Control Systems
C e n t r a lis e d C o n t r o l S y s t e m s
Up to 64 groups of indoor units (128 units) can be centrally controlled.
Unified on/off
controller
(DCS301BA61)
Connection of
up to 8 units
possible
DCS302CA61
Independent
and centralised
control of HRV
is possible.
Connectable number of
centralised control
equipment
Central remote
controller
2 units
Unified on /off
controller
8 units
Schedule timer
1 unit
DCS301BA61
Forced
shut-down
input
Central remote
controller
(DCS302CA61)
Up to 2 units
connectable
Central control
adaptor kit
(DTA107A55).
Outdoor-air
processing
unit can be
connected.
6 cores
Schedule timer (DST301BA61)
1 unit connection possible ;
8 weekly schedule control patterns possible
Wiring adaptor
for other airconditioners
(DTA103A51)
7 cores max.
DST301BA61
Part name
Model No.
DCS302A52
DTA102A52
For SkyAir, FD(Y)M-FA, FDYB-KA, FDY-KA,
FVY(P)J-A, FXUQ-MA
17
Function
Interface between the central monitoring board and central
control units. Combined with the central remote controller,
this adaptor enables the central monitoring board to
centralise such functions as the on/off control, operation
status monitoring, and normal/malfunction monitoring.(*1)
DTA107A55
For UAT(Y)-K(A), FD-K
DTA103A51
18
Control Systems
A dv a n c e d C o n t r o l S y s t e m s
New
S pe c ia l F u n c t io n s
N e w F e a ture s
Monitor and control from the remote site by Web browser (Option)
PPD data can be managed from the remote site by Web browser (Option)
Send malfunction report through the Internet by E-mail (Option)
Compliant with the RoHS Directive (DAM602B51/52)(refer to page 13 for details.)
Intranet/Internet
Malfunction report
by E-mail
Web Access
Web Access
Air Conditioning
Network Service System 1
(Optional Maintenance Service)
Features control and monitoring functions for central A/C products and an Air Conditioning
Network Service function.
Using an external contact via DIII-NET, monitors and controls equipment such as lighting,
fans, or building security systems.
Via internet
D -NET
DAM602B51/52
*
Light
Dio unit
(DEC102A51)
D -NET
Fan
Pump
Ai unit
(DAM101A51)
D -NET
Daikin Central
Air Conditioning
System
Contact signal
Fire alarm
Multi-PC
Ethernet
D -NET
VRV System
Local
monitoring
& control
HRV
Sub PC
19
*1. There are restrictions in applicable areas and release times, therefore please consult us separately for details.
Interfacing requirements vary depending on model, and some systems may not be suitable. Please contact your distributor for details.
Information on these systems is preliminary only. Please contact Daikin for formal information on the products.
20
Control Systems
A dv a n c e d C o n t r o l S y s t e m s
Interface for
Integrated control systems that recognise the trend of open control systems
Ethernet
Dio Unit
DEC102A51
PCMCIA
Flash
Memory
BMS
Dio Unit
DEC102A51
Function 5
Input
(Lights)
System
Set temperature
change command
Lift
Pump
Lighting,etc
Function 6
Function 1
DMS502B51
DMS504B51
VRV System
HRV
Local Controller
D -NET
Function 2
Public
phone line
Function 3
Trouble
reports
Pi Port
Connection to power consumption meter
when using power proportional distribution
function. (Option)
RS-232C
Indoor Unit
D -NET Plus Adaptor
DCS601A52 (option)
S ys te m
C ompone nts
ACC center
PC
Function 4
Mobile Phone
Compatibility with BMS enhanced by utilising the international communication standards, BACnet or LONWORKS .
HRV
Function 1
Support for centralised control from elsewhere using a PC with a Web browser (Option)
Function 2
Function 3
Built-in modem for connecting to Air Conditioning Network Service System (Option)
Function 4
Doubling of number of connectable indoor units by adding a D -NET Plus Adaptor (Option)
Function 5
Management of facilities/equipment other than A/C units (By adding Dio unit or Di unit)
Function 6
New
Up to 40 outdoor units and 256 indoor unit groups on one gateway. (optional adaptor)
*4
I/F unit
INTERNET
Colour LCD touch panel icon display
Small manageable size
Simplified engineering
Multi language (English, French, Italian, German, Spanish and Chinese)
Yearly schedule
PPD (Power Proportinal Distribution function) (Option)
Auto heat/cool change-over
Temperature limitation
Enhanced history function
21
ACC center
Mainfunction information
by E-mail
Local dealers
22
Control Systems
I n t e g r a t e d B u ildin g M o n it o r in g S y s t e m
DIII-NET Line
The high speed transmission of DIII-NET enables more advanced control of the VRV system, providing you
with enhanced comfort.
BACnet/Ethernet or LONWORKS
Network Communication Line
VRV
DAM602B51/52
(DCS601C51)
HRV unit
Central Remote
Controller
(DCS302CA61)
Telephone Line
ACC Center
BMS
Unified ON/OFF
Controller
(DCS301BA61)
Schedule Timer
(DST301BA61)
D -NET
Parallel Interface
(DPF201A51/52/53)
(Obtain locally)
Packaged
Air-conditioner
23
SkyAir
Di unit (DEC101A51)
Dio unit (DEC102A51)
Wiring adaptor
for electrical appendices
(KRP2A61/62/53)
Caution:
Limitation may apply to some models and functions. Please contact your local sales office for details.
Consultation is necessary before employing this control system. Please contact your local sales office before
making a purchase.
Note: BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning
Engineers (ASHRAE). LONWORKS is a registered trademark of Echelon Corporation. Ethernet is a
registered trademark of Xerox Corporation.
24
Type
Model name
Ceiling Mounted
Cassette
(Double Flow)
FXCQ-MVE
Ceiling Mounted
Cassette
(Multi Flow)
Super Cassette
FXFQ-MVE
Ceiling Mounted
Cassette Corner
FXKQ-MAVE
0.8 HP
20
1 HP
1.25 HP 1.6 HP
25 31.25 40
2 HP
2.5 HP
3.2 HP
4 HP
5 HP
8 HP
50
62.5
80
100
125
200 250
10 HP
FXDQ-PVE
(700 mm
width type)
Slim Ceiling
Mounted Duct
Capacity Range
Capacity Index
with
drain
pump
FXDQ-PVET without
(700 mm
drain
width type) pump
FXDQ-NAVE with
(900/1,100 mm drain
width type) pump
FXDQ-NVET without
(900/1,100 mm drain
width type) pump
Ceiling Mounted
Built-in
FXSQ-MVE
Ceiling Mounted
Duct
FXMQ-MAVE
Ceiling
Suspended
FXHQ-MAVE
Wall Mounted
FXAQ-MAVE
Floor Standing
FXLQ-MAVE
Concealed Floor
Standing
FXNQ-MAVE
350 mm
Ceiling
Suspended
Cassette
80
125
Capacity Range
Capacity Index
Connection Unit
0.8 HP
1 HP
1.25 HP
1.6 HP
2 HP
3 HP
4 HP
5 HP
20
25
31.25
40
50
71
100
125
600 mm
FXUQ-MAV1
Note: BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data for details.
25
63
25/32 40/50
Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system.
Type
20
(dB(A))
26
FXFQ25M/FXFQ32M/FXFQ40M
FXKQ25MA/FXKQ32MA
FXFQ50M/FXFQ63M/FXFQ80M
FXKQ40MA/FXKQ63MA
FXFQ100M/FXFQ125M
25
32
40
63
80
100
125
Operating
30/27 30/27 31/27 32/27 33(34) /28 36/31 39/33 42(43) /36
sound (H/L)
Note: Operating sound may increase more than that when using with 3-way discharge
or 2-way discharge, or when using together with a optional kit.
: The values of H mode Sound level represent those during cooling operation.
Those during heating operation are shown in brackets for two models only.
Branched
Closed
Piping
location
4.2 m
4.2 m
Pattern
setting
Prevention
setting
2 branches 2 patterns
Branched
Closed
25
25
60
Piping
location
27
60
10
10
40
40
Main body
500 mm
3 Setting
to prevent
soiling of ceiling
35
35
65
Panel s pac er
Pattern
2 Draft
Min.195 mm
1 Standard
Pattern
Main body
750 mm
20 mm
65
28
FXSQ20M/FXSQ25M/FXSQ32M
FXSQ40M/FXSQ50M/FXSQ63M
FXSQ80M/FXSQ100M/FXSQ125M
FXDQ20N(A)/FXDQ25N(A)/FXDQ32N(A)
FXDQ20P/FXDQ25P/FXDQ32P
FXDQ40N(A)/FXDQ50N(A)/FXDQ63N(A)
Great for
hotel use!
Only
700 mm
200
900 mm
200 mm
mm
S c reening
door
Air filter
240 mm
AIR
AIR
Suction grille*
*: To be obtained locally
FXDQ-P(NA)
20
25
32
40
50
63
Operating
sound (H/L)
33/29
33/29
33/29
34/30
35/31
36/32
The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB.
Values are based on the following conditions:
FXDQ-P: external static pressure of 10 Pa; FXDQ-N(A): external static pressure of 15 Pa.
29
Min.
350 mm
Ceiling return
Long-life filter
Long-life filter
Ac c es s panel
S c reening
door
Ac c es s panel
250 mm
Discharge grille*
Ac c es s panel
Air s uc tion
c anvas bellows
Long-life filter
20
25
32
(dB(A))
40
50
63
80
100
125
Operating 220V 37/32 37/32 38/32 38/32 41/36 42/35 43/37 43/37 46/41
Sound (H/L)
240V 39/34 39/34 40/34 40/34 43/38 44/37 45/39 45/39 48/43
750 mm
Ceiling
30
FXMQ40MA/FXMQ50MA
FXHQ32MA /FXHQ63MA
FXMQ63MA/FXMQ80MA
FXHQ100MA
FXMQ100MA/FXMQ125MA
Without drain
390 mm
Turbulent flow
is produc ed
Min.
450 mm
Indoor unit
750 mm
120 mm
(220V-240V)(dB(A))
FXHQ-MA
32
63
100
Operating sound
(H/L)
36/31
39/34
45/37
Installation is easy
Drain pump kit (option) c an be eas ily
inc orporated.
FXMQ200MA/FXMQ250MA
600 mm
Without drain
31
470 mm
With drain
Min.
530 mm
mm
222
Non-dew Flap
0~250
470 mm
Maintenance is easy
Non-dew Flap with no implanted bris tles
mm
100
Indoor unit
Indoor unit
32
FXAQ20MA/FXAQ25MA
FXLQ20MA/FXLQ25MA
FXAQ32MA/FXAQ40MA
FXLQ32MA/FXLQ40MA
FXAQ50MA/FXAQ63MA
FXLQ50MA/FXLQ63MA
70 mm
290 mm
200 mm
1,050 mm
(220V-240V)(dB(A))
FXAQ-MA
20
25
32
40
50
63
Operating
sound (H/L)
FXNQ20MA /FXNQ25MA
35/29
36/29
37/29
39/34
42/36
46/39
FXNQ32MA/FXNQ40MA
FXNQ50MA /FXNQ63MA
33
Wall hanging
Height of drain-up
1,000 mm
Indoor unit
Flexible installation.
Drain pipe c an be fitted to from either left
or right s ides .
C onnec ting
port
R efrigerant
piping
Applies also to Floor Standing type (FXNQ-MA).
34
C o o lin g o n ly
FXUQ71MAV1/FXUQ100MAV1
FXUQ125MAV1
5 HP
8, 10 HP
RXQ5P
RXQ8P
RXQ10P
RXQ12P
RXQ14P
RXQ16P
RXQ18P
RXQ20P
RXQ22P
RXQ24P
RXQ26P
RXQ28P
New
Connection unit is the device for connecting above indoor units to VRV III.
Connection unit
BEVQ71MAVE/BEVQ100MAVE/BEVQ125MAVE
External wiring layout
Connection unit for indoor unit
Liquid
pipe
VR V
s eries
outdoor unit
G as pipe
BEVQ-MAVE
Piping length*1
Indoor unit
R emote c ontroller
35
RXQ48P
RXQ50P
RXQ52P
RXQ54P
16, 18 HP
RXQ38P
RXQ40P
RXQ42P
RXQ44P
RXQ46P
High-COP type outdoor units offer highly efficient performance, contributing to energy savings, while a lineup
of 1650 HP models extends the range of applications.
NE W
*1
Model
FXUQ-MAV1
5m
Notes:
When connecting centralised-control device, it is
necessary to install an interface adaptor for an
indoor unit (DTA102A52).
Connection unit BEVQ-MA is necessary for each
indoor unit.
The refrigerant piping height difference between
the indoor units and the BEV unit must be within
4 m.
The BEV unit must be installed within a
maximum height difference between indoor units
of 15 m.
Branching of the refrigerant piping is not
possible downstream of the BEV unit.
24, 26 HP
RXQ16PH
RXQ18PH
28, 30 HP
RXQ24PH
RXQ26PH
RXQ28PH
RXQ30PH
Series Lineup
Series
Normal
Cooling types
only
High-COP
types
32, 34 HP
RXQ32PH
RXQ34PH
RXQ36PH
RXQ38PH
RXQ40PH
RXQ42PH
RXQ44PH
RXQ46PH
RXQ48PH
RXQ50PH
Capacity range
5 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP 22 HP 24 HP 26 HP 28 HP 30 HP 32 HP 34 HP 36 HP 38 HP 40 HP 42 HP 44 HP 46 HP 48 HP 50 HP 52 HP 54 HP
36
Specifications
INDOOR UNITS
O u t d o o r u n it c o m bin a t io n s
C e ilin g
N o r m a l T y p e s ( S p a c e S a v in g T y p e s )
HP
Model name
Combination
5 HP
RXQ5P
RXQ5P
8 (12)
8 HP
RXQ8P
RXQ8P
13 (20)
10 HP
RXQ10P
RXQ10P
16 (25)
12 HP
RXQ12P
RXQ12P
19 (30)
14 HP
RXQ14P
RXQ14P
23 (35)
16 HP
RXQ16P
RXQ16P
26 (40)
18 HP
RXQ18P
RXQ18P
29 (45)
20 HP
RXQ20P
RXQ8P + RXQ12P
32 (40)
22 HP
RXQ22P
RXQ10P + RXQ12P
35 (44)
24 HP
RXQ24P
RXQ8P + RXQ16P
39 (48)
26 HP
RXQ26P
RXQ8P + RXQ18P
42 (52)
28 HP
RXQ10P + RXQ18P
45 (56)
30 HP
RXQ28P
RXQ30P
RXQ12P + RXQ18P
48 (60)
32 HP
RXQ32P
RXQ16P x 2
52 (64)
34 HP
RXQ34P
RXQ16P + RXQ18P
55 (64)
36 HP
RXQ36P
RXQ18P x 2
58 (64)
38 HP
RXQ38P
61 (61)
40 HP
RXQ40P
RXQ8P + RXQ16P x 2
42 HP
RXQ42P
44 HP
RXQ44P
RXQ8P + RXQ18P x 2
46 HP
RXQ46P
RXQ10P + RXQ18P x 2
48 HP
RXQ48P
RXQ12P + RXQ18P x 2
50 HP
RXQ50P
RXQ14P + RXQ18P x 2
52 HP
RXQ52P
RXQ16P + RXQ18P x 2
54 HP
RXQ54P
RXQ18P x 3
BHFP22P100
M o u n te d C a s s e tte
Maximum number of
connectable indoor units*
MODEL
26 (32)
29 (36)
RXQ8P x 3
39 (39)
RXQ8P x 2 + RXQ10P
42 (42)
RXQ8P x 2 + RXQ12P
45 (45)
48 (48)
RXQ8P + RXQ12P x 2
52 (52)
RXQ34PH
RXQ10P + RXQ12P x 2
55 (55)
RXQ36PH
RXQ12P x 3
58 (58)
38 HP
RXQ38PH
RXQ12P x 2 + RXQ14P
61 (61)
40 HP
RXQ40PH
RXQ12P x 2 + RXQ16P
42 HP
RXQ42PH
RXQ12P x 2 + RXQ18P
44 HP
RXQ44PH
RXQ12P + RXQ16P x 2
46 HP
RXQ46PH
48 HP
RXQ48PH
RXQ16P x 3
50 HP
RXQ50PH
RXQ16P x 2 + RXQ18P
RXQ16PH
RXQ8P x 2
18 HP
RXQ18PH
RXQ8P + RXQ10P
24 HP
RXQ24PH
26 HP
RXQ26PH
28 HP
RXQ28PH
30 HP
RXQ30PH
32 HP
RXQ32PH
34 HP
36 HP
BHFP22P100
BHFP22P151
3,200
4,000
5,000
6,300
8,000
12,500
Btu/h(*1)
7,800
9,900
12,600
16,000
19,800
24,900
31,700
49,500
(*1)
2.3
2.9
3.7
4.7
5.8
7.3
9.3
14.5
(*2)
2.2
2.8
3.6
4.5
5.6
7.1
9.0
14.0
m3/min
7/5
9/6.5
9/6.5
12/9
12/9
16.5/13
26/21
33/25
cfm
247/177
318/230
318/230
424/318
424/318
582/459
918/741
1,165/883
dB 50 Hz/60 Hz 220V
(A) 50 Hz 240V
32/27
34/28
34/28
34/29
34/29
37/32
39/34
44/38
34/29
36/30
36/30
37/32
37/32
39/34
41/36
46/40
Dimensions (HX WX D)
mm
305X775X600
305X775X600
305X775X600
305X990X600
kg
Machine weight
26.0
26.0
26.0
31.0
32.0
35.0
47.0
6.4
6.4
6.4
6.4
6.4
9.5
9.5
9.5
Gas (Flare) mm
12.7
12.7
12.7
12.7
12.7
15.9
15.9
15.9
Drain piping
Panel(Option)
Dimensions
(HX WX D)
48.0
Model
BYBC32G-W1
BYBC50G-W1
BYBC63G-W1
BYBC125G-W1
Colour
White (10Y9/0.5)
mm
weight
kg
M o u n te d C a s s e tte
MODEL
8.0
8.0
8.0
8.5
8.5
9.5
12.0
12.0
64 (64)
( M u lt i F lo w ) T y p e
FXFQ25MVE FXFQ32MVE FXFQ40MVE FXFQ50MVE FXFQ63MVE FXFQ80MVE FXFQ100MVE FXFQ125MVE
Power supply
Cooling capacity
2,500
3,200
4,000
5,000
6,300
8,000
10,000
12,500
Btu/h(*1)
9,900
12,600
16,000
19,800
24,900
31,700
39,600
49,500
(*1)
2.9
3.7
4.7
5.8
7.3
9.3
11.6
14.5
(*2)
2.8
3.6
4.5
5.6
7.1
9.0
11.2
14.0
kW
Casing
Airflow rate (H/L)
13/10
13/10
15/11
16/11
18.5/14
20/15
26/21
30/24
cfm
459/353
459/353
530/388
565/388
653/494
706/530
918/741
1,059/847
30/27
30/27
31/27
32/27
33(34) /28
36/31
39/33
42(43) /36
dB(A)
Dimensions (HX WX D)
mm
Machine weight
246X 840X 840 246X 840X 840 246X 840X 840 246X 840X 840 246X 840X 840 246X 840X 840 288X 840X 840 288X 840X 840
24.0
24.0
24.0
24.0
25.0
25.0
29.0
6.4
6.4
6.4
6.4
9.5
9.5
9.5
9.5
Gas (Flare) mm
12.7
12.7
12.7
12.7
15.9
15.9
15.9
15.9
Panel(Option)
kg
Drain piping
Model
BYCP125D-W1
Colour
Dimensions
(HX WX D)
Note: For multiple connection of 16 HP systems and above, the above Daikin optional kit (separately sold) is required.
*Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double outdoor units, and
130% for triple outdoor units. Refer to page 9 for notes on connection capacity of indoor units.
37
2,500
Casing
C e ilin g
Maximum number of
connectable indoor units*
16 HP
2,000
64 (64)
Combination
kW
H ig h - C O P T y p e s ( E n e r g y S a v in g T y p e s )
Model name
Power supply
Cooling capacity
F lo w ) T y p e
Note: For multiple connection of 20 HP systems and above, the above Daikin optional kit (separately sold) is required.
*Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double outdoor units, and
130% for triple outdoor units. Refer to page 9 for notes on connection capacity of indoor units.
HP
( D o u b le
mm
weight
kg
29.0
White (10Y9/0.5)
45X 950X 950
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
38
Specifications
INDOOR UNITS
C e ilin g
M o u n te d C a s s e tte
MODEL
C orne r T ype
FXKQ25MAVE
Power supply
Cooling capacity
FXKQ32MAVE
3,200
4,000
6,300
Btu/h(*1)
9,900
12,600
16,000
24,900
(*1)
2.9
3.7
4.7
7.3
(*2)
2.8
3.6
4.5
7.1
m3/min 50 Hz
11/9
11/9
13/10
18/15
388/318
388/318
459/353
635/530
dB 50 Hz/60 Hz 220V
(A) 50 Hz 240V
38/33
38/33
40/34
42/37
40/35
40/35
42/36
44/39
mm
kg
Machine weight
50 Hz
31.0
31.0
31.0
34.0
6.4
6.4
6.4
9.5
Gas (Flare) mm
12.7
12.7
12.7
15.9
Drain piping
C e ilin g
Model
BYK45FJW1
mm
weight
kg
with
drain pump
without
drain pump
8.5
8.5
9.5
FXDQ20PVE
FXDQ20PVET
Power supply
Cooling capacity
FXDQ25PVET
FXDQ32PVE
FXDQ32PVET
2,000
2,500
3,200
Btu/h(*1)
7,800
9,900
12,600
(*1)
2.3
2.9
3.7
(*2)
2.2
2.8
3.6
8.0/6.4
8.0/6.4
8.0/6.4
cfm
282/226
282/226
282/226
30-10 1
Pa
dB(A)
33/29
33/29
33/29
Dimensions(HX WX D)
mm
kg
Machine weight
23.0
23.0
23.0
6.4
6.4
6.4
Gas (Flare) mm
12.7
12.7
12.7
Drain piping
39
2,500
3,200
4,000
5,000
6,300
Btu/h(*1)
7,800
9,900
12,600
16,000
19,800
24,900
(*1)
2.3
2.9
3.7
4.7
5.8
7.3
(*2)
2.2
2.8
3.6
4.5
5.6
7.1
m3/min
9.5/7.5
9.5/7.5
10.5/8.5
10.5/8.5
12.5/10.0
16.5/13.0
cfm
335/265
335/265
371/300
371/300
441/353
583/459
35/31
36/32
44-15 1
Pa
dB(A)
Dimensions(HX WX D)
mm
33/29
33/29
33/29
34/30
200X 900X 620 200X 900X 620 200X 900X 620 200X 900X 620 200X 900X 620 200X 1,100X 620
26.0
26.0
26.0
27.0
28.0
kg
6.4
6.4
6.4
6.4
6.4
9.5
Gas (Flare) mm
12.7
12.7
12.7
12.7
12.7
15.9
Drain piping
C e ilin g
kcal/h (*1)
Casing
2,000
Casing
31.0
M o u n t e d B u ilt - in T y p e
MODEL
Power supply
Cooling capacity
kW
FXDQ25PVE
kcal/h (*1)
kW
White (10Y9/0.5)
8.5
Cooling capacity
Machine weight
Power supply
BYK71FJW1
M o u n t e d D u c t T y p e ( 7 0 0 m m w id t h t y p e )
MODEL
with
drain pump
without
drain pump
MODEL
Colour
Dimensions
(HX WX D)
M o u n t e d D u c t T y p e ( 9 0 0 / 1, 10 0 m m w id t h t y p e )
Dimensions (HX WX D)
Panel (Option)
C e ilin g
FXKQ63MAVE
2,500
cfm
S lim
FXKQ40MAVE
kcal/h (*1)
Casing
S lim
kW
INDOOR UNITS
2,000
2,500
3,200
4,000
5,000
6,300
8,000
10,000
12,500
Btu/h(*1)
7,800
9,900
12,600
16,000
19,800
24,900
31,700
39,600
49,500
(*1)
2.3
2.9
3.7
4.7
5.8
7.3
9.3
11.6
14.5
(*2)
2.2
2.8
3.6
4.5
5.6
7.1
9.0
11.2
14.0
28/22
38/28
kW
Casing
Airflow rate (H/L)
External static pressure
Sound level (H/L)
Dimensions(HX WX D)
Machine weight
9/6.5
9/6.5
9.5/7
11.5/9
15/11
21/15.5
27/21.5
318/230
318/230
335/247
406/318
530/388
741/547
953/759
cfm
50 Hz
Pa
220V
dB
50 Hz
(A)
240V
mm
988/777 1,341/988
37/32
37/32
38/32
38/32
41/36
42/35
43/37
43/37
46/41
39/34
39/34
40/34
40/34
43/38
44/37
45/39
45/39
48/43
30.0
30.0
30.0
31.0
41.0
51.0
51.0
6.4
6.4
6.4
6.4
6.4
9.5
9.5
9.5
9.5
Gas (Flare) mm
12.7
12.7
12.7
12.7
12.7
15.9
15.9
15.9
15.9
Panel(Option)
Dimensions
(HX WX D)
kg
52.0
Drain piping
Model
Colour
White (10Y9/0.5)
mm
55X 650X 500 55X650X 500 55X650X 500 55X 800X 500 55X 800X 500 55X1,100X500 55X1,500X500 55X1,500X500 55X1,500X500
weight
kg
3.0
3.0
3.0
3.5
3.5
4.5
6.5
6.5
6.5
40
Specifications
INDOOR UNITS
C e ilin g
INDOOR UNITS
M o u n te d D u c t T y p e
MODEL
W a ll M o u n t e d T y p e
Power supply
Cooling capacity
MODEL
4,000
5,000
6,300
8,000
10,000
12,500
19,800
24,800
Btu/h(*1)
16,000
19,800
24,900
31,700
39,600
49,500
78,500
98,300
(*1)
4.7
5.8
7.3
9.3
11.6
14.5
23.0
28.8
(*2)
4.5
5.6
7.1
9.0
11.2
14.0
22.4
28.0
36/29
58/50
72/62
kW
Casing
Power supply
Cooling capacity
m3/min
14/11.5
14/11.5
14/11.5
19.5/16
cfm
494/406
494/406
494/406
688/565
Pa (50Hz)
dB 50 Hz/60 Hz 220V
(A)
50 Hz 240V
mm
Dimensions (HX WX D)
Machine weight
157-118
157-118
157-118
157-108
29/23
1
157-98
191-152
221-132
270-147
39/35
39/35
42/38
43/39
45/42
48/45
48/45
41/37
41/37
41/37
44/40
45/41
47/44
49/46
49/46
44.0
44.0
44.0
45.0
63.0
65.0
6.4
6.4
9.5
9.5
9.5
9.5
Gas (Flare) mm
12.7
12.7
15.9
15.9
15.9
15.9
Drain piping
137.0
FXHQ32MAVE
Power supply
Cooling capacity
FXHQ63MAVE
3,200
6,300
10,000
12,600
24,900
39,600
(*1)
3.7
7.3
11.6
(*2)
3.6
7.1
11.2
17.5 /14
25/19.5
cfm
424/353
618/494
883/688
dB(A)
36/31
39/34
45/37
mm
kg
24.0
28.0
33.0
6.4
9.5
9.5
Drain piping
15.9
15.9
41
2.9
3.7
4.7
5.8
7.3
2.2
2.8
3.6
4.5
5.6
7.1
m3/min
7.5/4.5
8/5
9/5.5
12/9
15/12
19/14
cfm
265/159
282/177
318/194
424/318
530/424
671/494
35/29
36/29
37/29
39/34
42/36
46/39
kg
14.0
11.0
11.0
11.0
14.0
14.0
6.4
6.4
6.4
6.4
6.4
9.5
Gas (Flare) mm
12.7
12.7
12.7
12.7
12.7
15.9
Drain piping
T y p e / C o n c e a le d F lo o r S t a n d in g
FXLQ
Cooling capacity
kcal/h (*1)
2,000
2,500
3,200
4,000
5,000
6,300
Btu/h(*1)
7,800
9,900
12,600
16,000
19,800
24,900
(*1)
2.3
2.9
3.7
4.7
5.8
7.3
(*2)
2.2
2.8
3.6
4.5
5.6
7.1
kW
FXNQ
Type
MODEL
White (10Y9/0.5)
12.7
2.3
(*2)
Casing
12 /10
Gas (Flare) mm
(*1)
Power supply
Btu/h(*1)
24,900
mm
FXHQ100MAVE
m3/min
Machine weight
19,800
PS1B
Dimensions(HX WX D)
16,000
dB(A)
9.5 1
kcal/h (*1)
Casing
6,300
12,600
White (3.0Y8.5/0.5)
19.1(Brazing) 22.2(Brazing)
kW
5,000
9,900
Dimensions (HX WX D)
S us pe nde d T ype
MODEL
4,000
7,800
F lo o r S t a n d in g
C e ilin g
3,200
Btu/h(*1)
Machine weight
137.0
9.5
2,500
390X 720X 690 390X 720X 690 390X 720X 690 390X 720X 690 390X 1,110X 690 390X 1,110X 690 470X 1,380X 1,100 470X 1,380X 1,100
kg
2,000
Casing
39/35
kW
m3/min
7/6
7/6
8/6
11/8.5
14/11
16/12
cfm
247/212
247/212
282/212
388/300
494/388
565/424
dB 50 Hz/60 Hz 220V
(A) 50 Hz 240V
35/32
35/32
35/32
38/33
39/34
40/35
37/34
37/34
37/34
40/35
41/36
42/37
FXLQ
FXNQ
FXLQ
25.0
25.0
30.0
30.0
36.0
36.0
FXNQ
27.0
Dimensions (HX WX D)
Machine weight
mm
kg
19.0
19.0
23.0
23.0
27.0
6.4
6.4
6.4
6.4
6.4
9.5
Gas (Flare) mm
12.7
12.7
12.7
12.7
12.7
15.9
Drain piping
21O.D.
42
Specifications
INDOOR UNITS
OUTDOOR UNITS
C e ilin g
S u s p e n d e d C a s s e tte
Model
Power supply
Indoor unit
Connection unit
Cooling capacity
Kcal/h(*1)
Btu/h(*1)
kW
Indoor
unit
Casing
Airflow rate (H/L)
(*1)
(*2)
m3/min
cfm
dBA
mm
kg
mm
7,100
28,300
8.3
8.0
19/14
671/494
40/35
165X 895X 895
25
Power supply
Cooling capacity
S a v in g
Type s )
RXQ8PY1
RXQ10PY1
kcal/h (*1)
12,100
19,400
24,300
29,000
34,600
39,000
42,400
Btu/h(*1)
48,100
76,800
96,200
115,000
137,000
155,000
168,000
(*1)
14.1
22.5
28.2
33.7
40.2
45.3
49.3
(*2)
14.0
22.4
28.0
33.5
40.0
45.0
49.0
28-100
20-100
14 -100
14 -100
10-100
10-100
9-100
Capacity control
FXUQ100MAV1
FXUQ125MAV1
BEVQ100MAVE
BEVQ125MAVE
1 phase, 220-240 V, 50 Hz
10,000
12,500
39,600
49,500
11.6
14.5
11.2
14.0
White(10Y9/0.5)
29/21
32/23
1,024/741
1,130/812
43/38
44/39
230X 895X 895
230X 895X 895
31
31
9.5 (Flare)
15.9 (Flare)
VP 20 (External Dia. 26/Internal Dia. 20)
(S pa c e
RXQ5PY1
MODEL
kW
Type
FXUQ71MAV1
BEVQ71MAVE
N orm a l Type s
RXQ12PY1
RXQ16PY1
RXQ18PY1
Casing colour
Compressor
Motor output kW
2.8X 1
3.8X 1
(1.2+4.5)X 1
(2.5+4.5)X 1
(0.3+4.5+4.5)X 1
(1.4+4.5+4.5)X 1
(3.0+4.5+4.5)X 1
m3/min
95
180
185
233
233
233
239
mm
Machine weight
kg
160
205
249
285
329
329
341
dB(A)
54
57
58
60
60
60
63
12.3
12.5
12.7
Airflow rate
Dimensions(HX WX D)
Refrigerant
R-410A
Refrigerant charge
kg
6.2
7.7
8.4
Refrigerant oil
Piping connections
MODEL
Liquid pipe mm
9.5 (Brazing)
9.5 (Brazing)
9.5 (Brazing)
12.7 (Brazing)
12.7 (Brazing)
12.7 (Brazing)
15.9 (Brazing)
15.9 (Brazing)
19.1 (Brazing)
22.2 (Brazing)
28.6 (Brazing)
28.6 (Brazing)
28.6 (Brazing)
28.6 (Brazing)
RXQ20PY1
RXQ22PY1
RXQ24PY1
RXQ26PY1
RXQ28PY1
RXQ30PY1
RXQ32PY1
Combination units
RXQ8PY1
RXQ12PY1
RXQ10PY1
RXQ12PY1
RXQ8PY1
RXQ16PY1
RXQ8PY1
RXQ18PY1
RXQ10PY1
RXQ18PY1
RXQ12PY1
RXQ18PY1
RXQ16PY1
RXQ16PY1
kcal/h (*1)
48,300
53,200
58,300
61,700
66,700
71,400
77,800
211,000
231,000
250,000
264,000
283,000
Gas pipe
mm
Power supply
Capacity control
10.0
Cooling capacity
(*1)
56.2
61.9
67.8
71.8
77.5
83.0
(*2)
55.9
61.5
67.4
71.4
77.0
82.5
Casing colour
Airflow rate
Dimensions(HX WX D)
90.5
90.0
5
5-100
Compressor
Motor output kW
(3.8X 1)+
((2.5+4.5)X 1)
((1.2+4.5)X 1)+
((2.5+4.5)X 1)
m3/min
180+233
185+233
(3.8X 1)+
(3.8X 1)+
((1.2+4.5)X 1)+
((2.5+4.5)X 1)+ ((1.4+4.5+4.5)X 1)+
((1.4+4.5+4.5)X 1) ((3.0+4.5+4.5)X 1) ((3.0+4.5+4.5)X 1) ((3.0+4.5+4.5)X 1) ((1.4+4.5+4.5)X 1)
180+233
180+239
185+239
233+239
233+233
mm
Machine weight
kg
205+285
249+285
205+329
205+341
249+341
285+341
329+329
dB(A)
62
62
62
64
64
65
63
8.4+12.7
10.0+12.7
12.5+12.5
Refrigerant
Refrigerant charge
R-410A
kg
7.7+10.0
8.4+10.0
7.7+12.5
Refrigerant oil
Piping connections
7.7+12.7
mm
15.9 (Brazing)
15.9 (Brazing)
15.9 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
28.6 (Brazing)
28.6 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
43
RXQ14PY1
Sound level : (*3) Anechoic chamber conversion value, measured at a point 1 m in front of
the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a
result of ambient conditions.
44
Specifications
OUTDOOR UNITS
N orm a l Type s
MODEL
(S pa c e
S a v in g
Type s )
RXQ36PY1
RXQ38PY1
RXQ40PY1
RXQ42PY1
RXQ44PY1
Combination units
RXQ16PY1
RXQ18PY1
RXQ18PY1
RXQ18PY1
RXQ8PY1
RXQ12PY1
RXQ18PY1
RXQ8PY1
RXQ16PY1
RXQ16PY1
RXQ8PY1
RXQ16PY1
RXQ18PY1
RXQ8PY1
RXQ18PY1
RXQ18PY1
kcal/h (*1)
81,400
85,100
91,200
97,200
101,000
104,000
Btu/h(*1)
323,000
338,000
362,000
386,000
399,000
413,000
(*1)
94.6
99.0
106
113
117
121
(*2)
94.0
98.0
105
112
116
120
5-100
4-100
4-100
4-100
4-100
4-100
kW
Capacity control
Casing colour
Dimensions(HX WX D)
((1.4+4.5+4.5)X 1)+
((3.0+4.5+4.5)X 1)
233+239
((3.0+4.5+4.5)X 1)+
((3.0+4.5+4.5)X 1)
239+239
(3.8X 1)+((2.5+4.5)X 1)+ (3.8X 1)+((1.4+4.5+4.5)X 1)+ (3.8X 1)+((1.4+4.5+4.5)X 1)+ (3.8X 1)+((3.0+4.5+4.5)X 1)+
((3.0+4.5+4.5)X 1)
((1.4+4.5+4.5)X 1)
((3.0+4.5+4.5)X 1)
((3.0+4.5+4.5)X 1)
180+233+239
180+233+233
180+233+239
180+239+239
mm
kg
329+341
341+341
205+285+341
dB(A)
65
66
65
Refrigerant
kg
12.5+12.7
12.7+12.7
7.7+10.0+12.7
Refrigerant oil
MODEL
Liquid pipe mm
Gas pipe
mm
7.7+12.5+12.5
7.7+12.5+12.7
7.7+12.7+12.7
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
RXQ48PY1
RXQ50PY1
RXQ52PY1
RXQ54PY1
RXQ10PY1
RXQ18PY1
RXQ18PY1
RXQ12PY1
RXQ18PY1
RXQ18PY1
RXQ14PY1
RXQ18PY1
RXQ18PY1
RXQ16PY1
RXQ18PY1
RXQ18PY1
RXQ18PY1
RXQ18PY1
RXQ18PY1
kcal/h (*1)
109,000
114,000
120,000
124,000
127,000
Btu/h(*1)
433,000
454,000
474,000
491,000
505,000
(*1)
127
133
139
144
148
(*2)
126
132
138
143
147
3-100
3-100
3-100
3-100
3-100
Combination units
Machine weight
kg
249+341+341
285+341+341
329+341+341
329+341+341
341+341+341
dB(A)
67
67
67
67
68
kg
8.4+12.7+12.7
10.0+12.7+12.7
12.3+12.7+12.7
12.5+12.7+12.7
12.7+12.7+12.7
R-410A
Piping connections
Liquid pipe mm
Gas pipe
mm
RXQ32PHY1
RXQ8PY1
RXQ10PY1
RXQ12PY1
RXQ8PY1
RXQ12PY1
RXQ12PY1
77,300
kcal/h (*1)
38,800
43,600
58,100
63,000
67,800
72,600
173,000
231,000
250,000
269,000
288,000
(*1)
45.1
50.7
67.6
73.2
78.8
84.4
(*2)
44.8
50.4
67.2
72.8
78.3
83.9
Airflow rate
89.4
5
5-100
Motor output kW
(3.8X 1)+(3.8X 1)
m3/min
180+180
mm
180+180+180
180+180+185
180+180+233
180+185+233
180+233+233
(1,680X 930X 765)+(1,680X 930X 765)+ (1,680X 930X 765)+(1,680X 930X 765)+ (1,680X 930X 765)+
(1,680X 1,240X 765)+
(1,680X 930X 765)
(1,680X 1,240X 765)
(1,680X 1,240X 765)
Machine weight
kg
205+205
205+249
205+205+205
205+205+249
205+205+285
205+249+285
205+285+285
dB(A)
60
61
62
62
63
63
64
7.7+7.7+10.0
7.7+8.4+10.0
7.7+10.0+10.0
Refrigerant
R-410A
kg
7.7+7.7
7.7+8.4
7.7+7.7+7.7
Refrigerant oil
Piping connections
MODEL
Liquid pipe mm
Gas pipe
mm
12.7 (Brazing)
15.9 (Brazing)
15.9 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
28.6 (Brazing)
28.6 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
34.9 (Brazing)
RXQ34PHY1
RXQ36PHY1
RXQ38PHY1
RXQ40PHY1
RXQ42PHY1
RXQ44PHY1
Combination units
RXQ10PY1
RXQ12PY1
RXQ12PY1
RXQ12PY1
RXQ12PY1
RXQ12PY1
RXQ12PY1
RXQ12PY1
RXQ14PY1
RXQ12PY1
RXQ12PY1
RXQ16PY1
RXQ12PY1
RXQ12PY1
RXQ18PY1
RXQ12PY1
RXQ16PY1
RXQ16PY1
kcal/h (*1)
82,200
87,700
92,900
97,200
101,000
108,000
Btu/h(*1)
326,000
348,000
368,000
386,000
399,000
427,000
(*1)
95.6
102
108
113
117
125
(*2)
95.0
101
107
112
116
124
5-100
5-100
4-100
4-100
4-100
4-100
Power supply
Cooling capacity
7.7+7.7+8.4
kW
%
Casing colour
Compressor
Motor output kW
m /min
3
((1.2+4.5)X 1)+((2.5+4.5)X 1)+ ((2.5+4.5)X 1)+((2.5+4.5)X 1)+ ((2.5+4.5)X 1)+((2.5+4.5)X 1)+ ((2.5+4.5)X 1)+((2.5+4.5)X 1)+ ((2.5+4.5)X 1)+((2.5+4.5)X 1)+ ((2.5+4.5)X1)+((1.4+4.5+4.5)X1)+
((1.4+4.5+4.5)X1)
((2.5+4.5)X 1)
((2.5+4.5)X 1)
((0.3+4.5+4.5)X1)
((1.4+4.5+4.5)X1)
((3.0+4.5+4.5)X1)
185+233+233
233+233+233
233+233+233
233+233+233
233+233+239
233+233+233
mm
Machine weight
kg
249+285+285
285+285+285
285+285+329
285+285+329
285+285+341
285+329+329
dB(A)
64
65
65
65
66
65
10.0+10.0+12.5
10.0+10.0+12.7
10.0+12.5+12.5
Dimensions(HX WX D)
Refrigerant charge
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
Refrigerant oil
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
Sound level : (*3) Anechoic chamber conversion value, measured at a point 1 m in front of
the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a
result of ambient conditions.
89.9
Compressor
19.1 (Brazing)
RXQ30PHY1
RXQ8PY1
RXQ8PY1
RXQ12PY1
Refrigerant
RXQ28PHY1
RXQ8PY1
RXQ8PY1
RXQ10PY1
RXQ8PY1
RXQ10PY1
Capacity control
Airflow rate
Refrigerant oil
RXQ26PHY1
RXQ8PY1
RXQ8PY1
kW
Capacity control
Refrigerant charge
RXQ24PHY1
Combination units
Btu/h(*1)
RXQ18PHY1
Power supply
Cooling capacity
Type s )
RXQ8PY1
RXQ8PY1
RXQ8PY1
Refrigerant charge
41.3 (Brazing)
Refrigerant
45
67
19.1 (Brazing)
Compressor
Dimensions(HX WX D)
65
34.9 (Brazing)
Casing colour
Airflow rate
64
RXQ46PY1
kW
Capacity control
205+341+341
19.1 (Brazing)
Power supply
Cooling capacity
205+329+341
205+329+329
R-410A
Refrigerant charge
( E n e r g y S a v in g
RXQ16PHY1
MODEL
Dimensions(HX WX D)
Machine weight
Type s
Casing colour
Compressor
Airflow rate
H ig h - C O P
RXQ34PY1
Power supply
Cooling capacity
OUTDOOR UNITS
Piping connections
R-410A
kg
8.4+10.0+10.0
10.0+10.0+10.0
10.0+10.0+12.3
mm
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
19.1 (Brazing)
34.9 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
Sound level : (*3) Anechoic chamber conversion value, measured at a point 1 m in front of
the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a
result of ambient conditions.
46
Specifications
Option List
OUTDOOR UNITS
H ig h - C O P
MODEL
Type s
Combination units
( E n e r g y S a v in g
RXQ48PHY1
RXQ50PHY1
RXQ12PY1
RXQ16PY1
RXQ18PY1
RXQ16PY1
RXQ16PY1
RXQ16PY1
RXQ16PY1
RXQ16PY1
RXQ18PY1
117,000
120,000
Btu/h(*1)
440,000
464,000
478,000
(*1)
129
136
140
(*2)
128
135
139
3-100
3-100
3-100
Compressor
Motor output kW
Dimensions(HX WX D)
m /min
3
kg
285+329+341
329+329+329
329+329+341
dB(A)
66
65
66
Refrigerant
Note:
kg
10.0+12.5+12.7
12.5+12.5+12.5
Liquid pipe mm
Gas pipe
mm
19.1 (Brazing)
19.1 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
41.3 (Brazing)
C e ilin g
No.
1
2
3
5
6
7
8
No.
BYBC50G-W1
KAFJ532G56
KAFJ533G56
KDDFJ53G56
KAFJ531G56
FXCQ63M
FXCQ80M FXCQ125M
BYBC63G-W1
KAFJ532G80
KAFJ533G80
KDDFJ53G80
KAFJ531G80
BYBC125G-W1
KAFJ532G160
KAFJ533G160
KDDFJ53G160
KAFJ531G160
( M u lt i F lo w ) T y p e
C e ilin g
BYCP125D-W1
KDBH55D160W
KDBP55H160WA
KAFP556D80
KAFP557D80
KAFP552H80
KAFP553H80
KDDFP55D160
KAFJ551C160
KAFP55D160
KAFJ55K160H
KDDP55D160
KDDP55D160K
KDDJ55X160
KDP55D80
KKSJ55K160
KDT-55D80
Decoration Panel
Panel Spacer
Long life replacement filter
Air discharge grille
Air discharge blind panel
Flexible duct (with shutter)
KDT-55D160
FXKQ63MA
BYK45FJW1
KPBJ52F56W
KAFJ521F56
K-HV7AW
KDBJ52F56W
KFDJ52FA56
M o u n te d D u c t T y p e
Type
KDP55D160
C orne r T ype
Item
KAFP556D160
KAFP557D160
KAFP552H160
KAFP553H160
BYK71FJW1
KPBJ52F80W
KAFJ521F80
K-HV9AW
KDBJ52F80W
KFDJ52FA80
(70 0
mm
FXDQ20P
w id t h t y p e
FXDQ25P
1)
FXDQ32P
KDT25N32
S lim
No.
1
47
Item
Note:
M o u n te d C a s s e tte
Panel related
No.
FXCQ50M
S lim
F lo w ) T y p e
FXCQ40M
BYBC32G-W1
KAFJ532G36
KAFJ533G36
KDDFJ53G36
KAFJ531G36
M o u n te d C a s s e tte
Item
C e ilin g
Note:
( D o u b le
FXCQ20M
FXCQ25M
FXCQ32M
Decoration Panel
Sealing member of air discharge outlet
Panel spacer
High efficiency filter unit 65%
High efficiency filter unit 90%
Replacement high efficiency filter 65%
Replacement high efficiency filter 90%
Filter related
Filter chamber
Long life replacement filter Non-woven type
Ultra long-life filter
Replacement ultra long-life filter
Without T shape and fan
Chamber type
With T shape without fan
Fresh air intake kit
Direct installation type
Branch duct chamber
Chamber connection kit
Insulation kit for high humidity
Sound level : (*3) Anechoic chamber conversion value, measured at a point 1 m in front of
the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a
result of ambient conditions.
12.5+12.5+12.7
19.1 (Brazing)
Type
Item
Filter related
M o u n te d C a s s e tte
Decoration Panel
R-410A
Refrigerant oil
Piping connections
mm
Machine weight
Refrigerant charge
No.
Casing colour
Airflow rate
C e ilin g
kcal/h (*1)
kW
Capacity control
Type s )
RXQ46PHY1
Power supply
Cooling capacity
INDOOR UNITS
C e ilin g
M o u n te d D u c t T y p e
Item
Insulation kit for high humidity
Type
FXDQ20N
( 9 0 0 / 1, 10 0
FXDQ25N
mm
FXDQ40N
KDT25N50
w id t h t y p e
FXDQ50N
1)
FXDQ63N
KDT25N63
48
Option List
INDOOR UNITS
C e ilin g
No.
1
2
4
5
OUTDOOR UNITS
M o u n t e d B u ilt - in T y p e
Type
Item
Decoration Panel
Access panel
1 Auxiliary
Model
(220 V240 V)
electric heater
Capacity
kW
2 High efficiency filter 65%
2 High efficiency filter 90%
Filter related
Long life replacement filter
For bottom suction
Filter
chamber
For rear suction
Air suction canvas
Air inlet and air
Screening door
discharge outlet
Air suction flange
related
Air discharge adaptor
Natural evaporating pan type humidifier 1
Panel related
N orm a l Type s
FXSQ20M
FXSQ25M
FXSQ32M
BYBS32DJW1
KTBJ25K36W
KEA25K32VE
0.75
KAFJ252L36
KAFJ253L36
KAFJ251K36
KAJ25L36D
KAJ25L36B
KSA-25K36
KBBJ25K36
KDJ2507K36
KDAJ25K36
KNM25K32V1
FXSQ40M
FXSQ50M
FXSQ63M
BYBS45DJW1
KTBJ25K56W
KEA25K50VE
1.2
KAFJ252L56
KAFJ253L56
KAFJ251K56
KAJ25L56D
KAJ25L56B
KSA-25K56
KBBJ25K56
KDJ2507K56
KDAJ25K56
KNM25K50V1
BYBS71DJW1
KTBJ25K80W
KEA25K63VE
1.4
KAFJ252L80
KAFJ253L80
KAFJ251K80
KAJ25L80D
KAJ25L80B
KSA-25K80
KBBJ25K80
KDJ2507K80
KDAJ25K71
KNM25K63V1
FXSQ80M
FXSQ100M
FXSQ125M
BYBS125DJW1
KTBJ25K160W
KEA25K100VE
KEA25K125VE
2.1
2.8
KAFJ252L160
KAFJ253L160
KAFJ251K160
KAJ25L160D
KAJ25L160B
KSA-25K160
KBBJ25K160
KDJ2507K160
KDAJ25K140
KNM25K125V1
Notes: 1 One adaptor for wiring (KRP1B61) per indoor unit is required if installing an electric heater or a natural evaporating pan type humidifier.
An electric heater cannot be used for VRV system cooling only.
2 If installing a high filter in the ceiling mounted built-in type, an assembly chamber for either bottom or rear suction is required.
C e ilin g
No.
M o u n te d D u c t T y p e
Type FXMQ40MA FXMQ50MA FXMQ63MA FXMQ80MA FXMQ100MA FXMQ125MA FXMQ200MA FXMQ250MA
Item
KAFP373A80
KAFP373A160
KAFJ373L280
Filter chamber
KDDFP37A80
KDDFP37A160
KDJ3705L280
KAFP371A80
KAFP371A160
KAFJ371L280
C e ilin g
No.
KDU-30L125VE
65%
KAFP372A80
90%
KDU30L250VE
KAFP372A160
KAFJ372L280
1
1-1
Type
FXHQ32MA
KDU50M60VE
KAFJ501D56
KHFP5M35
FXHQ63MA
KAFJ501D80
Type FXAQ20MA
Item
1
2
3
4
5
KRC1926A
Fixing box
KJB111A
KHRP26A22T
KHRP26A22T, KHRP26A33T
KWC26C160(E)
KWC26C280(E)
KWC26C450(E)
Type
Item
1-1
Cool/Heat Selector
FXAQ50MA
FXAQ63MA
KAFJ361K28
KAFJ361K45
KJB111A
KAFJ361K28
S u s p e n d e d C a s s e tte
Item
Replacement long-life filter
Sealing member of air discharge outlet
Decoration panel for air discharge
Vertical flap kit
L-shape piping kit
Type
(*1)
KAFJ361K45
KAFJ361K71
Type
FXUQ71MAV1
KDBHJ49F80
KDBTJ49F80
KDGJ49F80
KHRP26M73TP, KHRP26M73HP
BHFP22P100
FXUQ100MAV1
KAFJ495F140
KHFP49M140
BHFP22P151
KWC26C280(E)
KWC26C450(E)
KWC26C450(E)X 2
KWC26C280(E)
KWC26C450(E)X 2
KWC26C450(E)X 3
RXQ32PH
RXQ34PH
RXQ36PH
RXQ38PH
RXQ40PH
RXQ42PH
RXQ44PH
RXQ46PH
RXQ48PH
RXQ50PH
BHGP26A1(E)
Type s
( E n e r g y S a v in g
Type s )
Type
RXQ16PH
RXQ18PH
RXQ24PH
RXQ26PH
RXQ28PH
RXQ30PH
Item
1-1
Cool/Heat Selector
KRC1926A
Fixing box
KJB111A
KHRP26M73TP, KHRP26M73HP
BHFP22P100
BHFP22P151
KWC26C280(E)X 2
KWC26C280(E)X 2
KWC26C450(E)
KWC26C280(E)X 3
KWC26C280(E)
KWC26C450(E)X 2
KWC26C450(E)X 3
BHGP26A1(E)
CONTROL SYSTEMS
O p e r a t io n C o n t r o l S y s t e m
Type
KAFJ361K71
Item
RXQ48P
RXQ50P
RXQ52P
RXQ54P
KRC1926A
Fixing box
H ig h - C O P
RXQ38P
RXQ40P
RXQ42P
RXQ44P
RXQ46P
RXQ30P
RXQ32P
RXQ34P
RXQ36P
RXQ24P
RXQ26P
RXQ28P
RXQ20P
RXQ22P
No.
1
BHGP26A1(E)
Note: (*1): This option is necessary for setting up 2-way (opposing directional) airflow when the air conditioner is installed.
49
FXAQ40MA
Type
Item
C e ilin g
No.
FXAQ32MA
K-KDU572CVE
C o n c e a le d F lo o r S t a n d in g
No.
Item
Cool/Heat Selector
KHFP5M63
F lo o r S t a n d in g
No.
FXAQ25MA
RXQ12P
RXQ14P
RXQ16P
RXQ18P
RXQ8P
RXQ10P
RXQ5P
KAFJ501D112
Type s )
FXHQ100MA
KDU50M125VE
S a v in g
W a ll M o u n t e d T y p e
No.
Type
No.
S us pe nde d T ype
Item
No.
(S pa c e
FXUQ125MAV1
KDBHJ49F140
KDBTJ49F140
KDGJ49F140
No.
Type
Item
Wireless
O p t io n a l A c c e s s o r ie s
FXCQ-M
FXFQ-M
FXKQ-MA
FXDQ-P
FXDQ-N(A)
FXSQ-M
FXMQ-MA
FXHQ-MA
FXAQ-MA
FXLQ-MA
FXNQ-MA
FXUQ-MA
BRC7C67
BRC7E65
BRC4C63
BRC4C64
BRC4C64
BRC4C64
BRC7E66
BRC7E619
BRC4C64
BRC7C529W
Remote controller
BRC2C51
BRC2C51
BRC3A61
BRC3A61
KRP1B61
KRP1B59
KRP1B61
KRP1B56
KRP1B61
KRP1B3
6-1
KRP2A61
KRP2A62
KRP2A61
KRP2A53
KRP2A61
KRP2A62
KRP2A61
KRP2A61
KRP2A62
6-2
KRP4A51
KRP4A54
KRP4A51
KRP4A52
KRP4A51
KRP4A51
KRP4A53
BRC1C62
Wired
BRC1D61
KRP4A51
KRP4A53
Remote sensor
KRCS01-1
Note 2,3
Note 2,3
KRP1D98
KRP1B96
DTA104A61
DTA104A62
KRP1B61
KRCS01-1
DTA104A61
Note 4,6
KRP1B101
DTA104A53
Note 5
KRP4A91
DTA104A61
Note 3
KRP1C93
DTA104A62
Note 2,3
KRP4A93
DTA104A61
KRP1B97
DTA104A61
50
Option List
CONTROL SYSTEMS
S y s te m
C o n f ig u r a t io n
No.
1
1-1
2
Item
Model No.
DCS302CA61
KJB311A
DCS301BA61
2-2
KJB212A
DST301BA61
For UAT(Y)-K(A),FD-K
7-1
DTA102A52
DTA107A55
DTA103A51
-NET
DTA109A51
Expander Adaptor
Mounting plate
KRP4A92
Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
(128 units). Can turn units ON/OFF twice per day.
Item
* To us e any of the above optional c ontrollers , an appropriate adaptor mus t be ins talled on the
produc t unit to be c ontrolled.
1-1
1-2
intelligent Touch
Controller
Model No.
Basic
Option
DCS601A52
Software
PPD
DCS002C51
Web
DCS004A51
Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
KJB411A
128 units
Basic
Number of
Hardware units to be
connected
Software
256 units
DAM602B51
512 units
DAM602B51x 2
768 units
DAM602B51x 3
1024 units
DAM602B51x 4
Outdoor-Air
Processing Unit
PPD
DAM002A51
Web
DAM004A51
Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
ECONO
Ventilation
DAM003A51
2-4
DAM101A51
2-5
Di unit
DEC101A51
2-6
Dio unit
DEC102A51
DMS502B51
Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through BACnet communication.
DAM411B51
Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
independently.
Optional Di board
DAM412B51
Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
independently.
DMS504B51
Interface unit to allow communications between VRV and BMS. Operation and monitoring of airconditioning systems through LONWORKS communication.
Parallel interface
Basic unit
DPF201A51
Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to
4 units.
Temperature
measurement units
DPF201A52
Temperature
setting units
DPF201A53
DCS302A52
Interface between the central monitoring board and central control units.
Ventilation System
3-1
3-2
4
5
6
7
8
Contact/analog
signal
2-3
Humidification
VKM-GA Type
Ventilation
Air Processing*
Notes: *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS is a registered trade mark of Echelon Corporation.
*3. Installation box for adaptor must be obtained locally.
DAM602B52
Communication line
2-2
Function
A recent trend rapidly gaining popularity is for air treatment to be required as well as air conditioning. Daikins
Outdoor-Air Processing Unit can combine fresh air treatment and air conditioning, supplied from a single system.
It adjusts the temperature of air from outdoors using a fixed discharge temperature control. Along with Outdoor-Air
Processing Units, we also offer Heat Reclaim Ventilation (HRV) systems. The HRV VAM-GJ series units in
particular have been praised for their compactness, energy conservation and extensive operation range of
outdoor temperatures. This series provides higher enthalpy efficiency 1, due to the greatly enhanced performance
2
of the thin film element. Furthermore, improved external static pressure offers more flexibility for installation. The
HRV VKM-GAM series units, equipped with a DX-coil and a humidifier, provide further advanced features, such as
temperature adjustment to suit conditions indoors and to prevent cold air from blowing on people directly during
heating operation. The series also realises significant energy savings by exercising heat recovery.
DCS601C51
1-1
1-3
1-4
Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
communication system adopted for the VRV System.
M a n a g e m e n t S y s te m
No.
Air Processing*
Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
B u ild in g
Ventilation Humidification
KEK26-1
Note 2
Schedule timer
For SkyAir, FD(Y)M-FA, FDY-KA
FDYB-KA, FVY(P)J-A
Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
system.
Note 2
2-1
Function
Note 2
Components
of Indoor Air Quality
Humidification
Air Processing*
VAM-GJ Type
Ventilation Humidification
Air Processing*
Refrigerant Piping
Connectable
Connectable
Not connectable
Connections Wiring
with VRV III
After-cool &
After-heat Control
Connectable
Connectable
Connectable
Available
Available
Not available
Humidifier
Power Supply
Fitted
Option
Option
Option
220-240 V, 50 Hz
220-240 V, 50 Hz
220-240 V, 50 Hz/60 Hz
Airflow Rate
500 m3/Hr
1080 m /Hr
1680 m3/Hr
2100 m3/Hr
800 m3/Hr
1000 m3/Hr
150 m3/Hr
250 m3/Hr
350 m3/Hr
500 m3/Hr
650 m3/Hr
800 m3/Hr
1000 m3/Hr
1500 m3/Hr
2000 m3/Hr
*Refers to bringing outdoor air to near indoor temperature and delivering to a room.
51
52
Model Names
FXMQ125MFV1, FXMQ200MFV1,
FXMQ250MFV1
Air conditioning and outdoor air processing can be accomplished using a single system.
0%
H R
Re umi elat
lat dity ive
ive
Hu
m
idi 32
ty
Usage Limitations
ur
at
Air
Conditioning
Heating
Supported ange
R
Operation
5
Connection Conditions
When outdoor-air processing units are connected, the total connection capacity must be within 50% to 100% of that of the outdoor units.
When outdoor-air processing units and standard indoor units are connected, the total connection capacity of the outdoor-air processing units must not exceed 30% of that of the
outdoor units.
Outdoor-air processing units can be used without indoor units.
53
and
Supported Cooling
Operation Range
Ou
Outdoor
Air Supply
The following restrictions must be observed in order to maintain the indoor units connected to the same system.
r
pe
em
r T B)
i
A W
or (C
do
Indoor Unit
90
Indoor Unit
10
Fan
Operation
15
19
3 0%
ti
Rela
ve H
umid
ity
(33.5)
BRC1C62
Wired remote controller
(option)
The "self-diagnosis function" indicates the occurrence and nature of abnormalities in the system
by displaying codes on the remote controller.
VRV Series
Outdoor Units
1,080 m3/h
1,680 m3/h
2,100 m3/h
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
e
lativ
Re ity
20% umid
H
43
Notes
1. The data shown in the graph illustrates the supported operation ranges under
the following conditions.
Indoor and Outdoor Unit
Effective piping length: 7.5 m
Height differential: 0 m
2. The discharge temperature can be set using the remote controller. However,
the actual temperature may not match the temperature setting under some
circumstances due to the outdoor-air processing load or mechanical protection
controls.
3. The system will not operate in fan mode when the outdoor air temperature is
5C or below.
DCS302CA61
Central remote controller
(option)
systems.
54
STANDARD SPECIFICATIONS
Discharge side
A View
B View
613
760
1100
32- 7 hole
(All around)
11X 100=1100
1200
1230
Notes: *1. Filter chamber has a suction-type flange. (Main unit does not.)
Dimensions and weight of the equipment may vary depending on the options used.
Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
Some options may not be used in combination.
Operating sound may increase somewhat depending on the options used.
30
FXMQ125MFV1
12
20- 7 hole
(All around)
5X 100=500
600
630
A View
30
A View
390
61
296
KAFJ371L280
KAFJ372L280
KAFJ373L280
KDJ3705L280
245
60
25
FXMQ200/250MFV1
250
250
200
330
360
580
200
KDU30L250VE
KRP1B61
FXMQ250MFV1
25
KAFJ371L140
KAFJ372L140
KAFJ373L140
KDJ3705L140
FXMQ200MFV1
BRC1C62
DCS302CA61
DCS301BA61
DST301BA61
KRP2A61
KRP4A51
360
330
3X 100=300
FXMQ125MFV1
* These
250
Filters
2 11 6 4
Operation/control
Model
Operation remote controller
Central remote controller
Unified ON/OFF controller
Schedule timer
Wiring adaptor for electrical appendices (1)
Wiring adaptor for electrical appendices (2)
Long-life replacement filter
Colorimetry method 65%
High-efficiency
filter
Colorimetry method 90%
Filter chamber *1
Drain pump kit
Adaptor for wiring
1100 or more
(Service space)
30
OPTIONS
Indoor unit
B
Inspection hole 600 or more
346
Cooling
Heating
Cooling
Heating
Notes:
1. The attached piping in the diagram is for FXMQ200MFV1 and
2
FXMQ250MFV1 only. The gas piping connection port
(
in the
diagram) has a different bore form with FXMQ125MFV1.
2. An air filter is not supplied with this unit. Be sure to mount
an air
filter in the suction side.[Use a filter with dust collection
efficiency
of at least 50% (gravimetric method). This is available as an
option.]
supply
connection
Liquid
pipe connection
3.1 For
outdoor
ducts, be sure 7toPower
provide
heat wiring
insulation
to
2 Gas pipe connection
8 Transmission wiring connection
prevent
3 Drain
piping connection 9 Hanger bracket
condensation.
4 Electric parts box
10 Discharge companion flange
5 Ground terminal
11 Water supply port
6 Name plate
12 Attached piping (Note. 1)
360
330
3X 100=300
Operation range
(Fan mode operation between 15 and 19C)
D
(All around)
B
C
D
685
5X100=500 20- 4.7 hole
1296 11X100=1100 32- 4.7 hole
1296 11X100=1100 32- 4.7 hole
360
Product mass
Sound level *3
Connectable outdoor units *5 *6
mm
mm
mm
kg
dB(A)
A
744
1380
1380
250
Liquid
Gas
Drain
Model
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
390
Refrigerant
piping
Table of dimensions
296
Air filter
Airflow rate
m3/min
cfm
Pa
Model
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
Approx.
150
Fan
mm
WX Number
of units
1148
470
Casing
Dimensions (HXWXD)
Motor output
9
10
50
Heating capacity *1
FXMQ125/200/250MFV1
Cooling capacity *1
kcal/h
Btu/h
kW
kcal/h
Btu/h
kW
650 or more
(Service space)
Power supply
Type
Model
3X 100=300
Indoor unit
5X200=1000
16-M5 hole
(All around)
1230
10-M5 hole
(All around)
2X200=400
580
630
B View
200
330
250
360
1004
16-M5 hole
(All around)
55
5X200=1000
1230
56
Exhaust Fan
Heat Exchanger
Elements
Damper Motor
EA
Damper
(Exhaust air
to outdoors)
OA
RA
(Return air
from room)
HEP Element
(Anti-mould)
Operation of
the heat exchanger element
Outdoor
SA
DX-coil
(Control box)
Indoor
SA
30.6C
62% RH
(Supply air
to room)
Humidifier element
27.4C
63% RH
SA
Humidifier
RA
Temperature
and humidity
26C
50% RH
32C
70% RH
Integrallyformed liner
RA
DX-coil
Integrally-formed liner
Humidifier element
DX-coil
Cooling
Bypass ventilation
EA
RA
OA
SA
Air supply fan
Automatic
changeover
EA
RA
OA
SA
DX-coil (cooling)
Air conditioning and outdoor air processing can be accomplished using a single system.
Outdoor Air
Exhaust Air
Indoor Unit
Return
Air
Indoor Unit
Air-Conditioning Air
Air
Supply
heat recovery
80
60
humidifying
Other features
57
100
Effect of
humidification
20
VRV Series
Outdoor Units
Effect of heating
Effect of full heat exchange
5
10
15
20
25
30
Dry bulb temperature (CDB)
35
40
58
VKM50GAMV1
VKM80GAMV1
VKM100GAMV1
Refrigerant
VKM80GAV1
VKM100GAV1
1 phase, 220240 V, 50 Hz
500
750
950
70
150
120
100
440
100
70
60
110
80
70
Ultra-high (W)
560
620
670
560
620
670
490
560
570
490
560
570
420
470
480
420
470
480
Ultra-high (W)
560
620
670
560
620
670
High (W)
490
560
570
490
560
570
Low (W)
420
470
480
420
470
480
Heat
exchange High (W)
mode
Low (W)
Bypass
mode
640
820
440
640
820
Fan Motor
Type
Motor Output
kW
0.280 2
0.280 2
0.280 2
0.280 2
0.280 2
0.280 2
Ultra-high (dB)
Heat
exchange High (dB)
mode
Low (dB)
37/37.5/38
38.5/39/40
39/39.5/40
38/38.5/39
40/41/41.5
40/40.5/41
35/35.5/36
36/37/37.5
37/37.5/38
36/36.5/37
37.5/38/39
38/38.5/39
32/33/34
33/34/35.5
34/34.5/35.5
33.5/34.5/35.5
34.5/36/37
35/36/36.5
Ultra-high (dB)
37/37.5/38
38.5/39/40
39/39.5/40
38/38.5/39
40/41/41.5
40/40.5/41
High (dB)
35/35.5/36
36/37/37.5
37/37.5/38
36/36.5/37
37.5/38/39
38/38.5/39
Low (dB)
32/33/34
33/34/35.5
34/34.5/35.5
33.5/34.5/35.5
34.5/36/37
35/36/36.5
2.7
4.0
5.4
Ultra-high (%)
76
78
74
76
78
74
High
(%)
76
78
74
76
78
74
Low
(%)
77.5
79
76.5
77.5
79
76.5
Ultra-high (%)
64
66
62
64
66
62
High
(%)
64
66
62
64
66
62
Low
(%)
67
68
66
67
68
66
Ultra-high (%)
67
71
65
67
71
65
High
(%)
67
71
65
67
71
65
Low
(%)
69
73
69
69
73
69
Bypass
mode
Enthalpy Exchange
Efficiency (Cooling)
Enthalpy Exchange
Efficiency (Heating)
(kg/h)
Hanger bracket
4-14 x 40 oval hole
1688
160
RA
EA
Exhaust air to outdoors
210
SA
OA
Fresh air from outdoors
(Outdoor air)
160
153
Control box
Inspection
hatch
28
94
144
210
A
B
C
D
E
F
G
H
I
J
K
Maintenance cover
(For humidifier) *1
Inspection
hatch
VKM50GA(M)V1 VKM80/100GA(M)V1
832
1,214
248
439
431
622
164
183
420
592
248
439
878
1,262
137
89
137
89
196
246
250
263
Solenoid valve *1
Humidifier
(Natural evaporative type) *1
Maintenance Cover
1764
10
Heat exchanger
elements
515
322
102
I
Feed water connection port *1
(6.4C1220T)
Gas pipe
connection
Air filters
(12.7)
Liquid pipe connection
Drain outlet
(PT3/4 male screw)
(6.4)
OPTIONS
Air Filter
(kW)
2.8
4.5
5.6
2.8
4.5
Heating (Note 3)
(kW)
3.2
5.0
6.4
3.2
5.0
6.4
Height
(mm)
387
387
387
387
387
387
Width
(mm)
1,764
1,764
1,764
1,764
1,764
1,764
1,214
832
1,214
Dimensions
Depth
Connection Duct Diameter
Machine Weight
(mm)
832
(mm)
200
1,214
Net (kg)
102
120
125
107
129
134
250
200
96
Around Unit
OA (Note 9)
RA (Note 9)
5.6
1,214
250
109
114
RXYQ554PY1, RXYQ1650PHY1
the following condition: Ratio of rated external static pressure outdoor to indoor is kept constant at 7 to 1.
13. In heating operation, freezing of the outdoor units coil increases. Heating capability decreases and the
system goes into defrost operation. During defrost operation, the fans of the unit continues driving
(factory setting). The purpose of this is to maintain the amount of ventilation and humidifying.
14. When connecting with a VRV system heat recovery outdoor unit and bringing the RA (exhaust gas intake)
of this unit directly in from the ceiling, connect to a BS unit identical to the VRV indoor unit (master unit),
and use group-linked operation. (See the Engineering Data for details.)
15 When connecting the indoor unit directly to the duct, always use the same system on the indoor unit as
with the outdoor unit, perform group-linked operation, and make the direct duct connection settings from
the remote controller. (Mode No. 17 (27) First code No. 5 Second code No. 6.) Also, do not
connect to the outlet side of the indoor unit. Depending on the fan strength and static pressure, the unit
might back up.
Feed clean water (city water, tap water or equivalent). Dirty water may clog the
valve or cause dirt deposits in the water container, resulting in poor humidifier performance. (Never use
any cooling tower water and heating-purpose water.)
Also, if the supply water is hard water, use a water softener because of short life.
* Life of humidifying element is about 3 years (4,000 hours) under the supply water conditions of
hardness: 150 mg/l. (Life of humidifying element is about 1 year
(1,500 hours) under the supply water conditions of hardness: 400 mg/l.)
Annual operating hours: 10 hours/day x 26 days/month x 5 months = 1,300 hours
Applicable model
Item
Remote controller
Centralised Central remote controller
controlling Unified ON/OFF controller
device
Schedule timer
Wiring adaptor for electrical
appendices
For humidifier running ON signal output
For heater control kit
Controlling device
Air to Air Cross Flow Tot al Heat (Sensible + Latent Heat) Exchange
PC Board Adaptor
VKM50/80/100GA(M)V1
BRC1C62 *1
DCS302CA61
DCS301BA61
DST301BA61
KRP2A61
KRP50-2
BRP4A50
Type
FXDQ-P FXLQ-MA
For wiring (indoor unit of VRV) FXCQ-M FXFQ-M FXZQ-M8 FXKQ-MA FXSQ-M FXDYQ-M FXMQ-MA FXHQ-MA FXAQ-MA FXDQ-NA FXNQ-MA FXUQ-MA
Installation box for adaptor PCB
Note: 1.
2.
3.
4.
Item
Additional function
Insulating Material
235
Sirroco Fan
Casing
Damper plate
387
34
42
950
90
130
750
120
20
500
VKM50/80/100GA(M)V1
150
170
180
20
950
110
750
140
500
160
60
Power Consumption
950
Low
750
High
500
153
150 250
Ultra-high
DX-coil
Capacity
DIMENSIONS
Power Supply
59
VKM50GAV1
R-410A
Silencer
Applicable model
KRP1B61
Note 5
KRP4A91
KRP1B3
KRP1B56 KRP1B61
Note 3
Notes 2, 3 Notes 4, 6
KRP1B97
KRP1C93 KRP4A93 KRP1B101
VKM50GA(M)V1
K-DGL200B
200
KAF241G80M
KAF242G80M
K-FDS201C
K-FDS202C
VKM80GA(M)V1
VKM100GA(M)V1
KDDM24B100
250 mm
K-DGL250B
250
KAF241G100M
KAF242G100M
K-FDS251C
K-FDS252C
60
Model Names
VAM150GJVE, VAM250GJVE,
VAM350GJVE, VAM500GJVE,
VAM650GJVE, VAM800GJVE,
VAM1000GJVE, VAM1500GJVE,
VAM2000GJVE
28%!
20%
This VAM series provides higher enthalpy efficiency , due to the greatly enhanced performance of the thin film
element. Furthermore, improved external static pressure 2 offers more flexibility for installation. Along with these
three outstanding improvements, Daikins exclusive function nighttime free cooling operationcontributes to
energy conservation and more comfortable space.
For models: VAM150/250/350/650/800/1000/2000GJVE
2 For models: VAM150/350/500GJVE
1
Thickness of
the partition sheet
Outdoor
Exhaust air
High-humidity air
EA
(Exhaust air
to outdoors)
Pre-cool,
Pre-heat Control
Molecule of water
Miscellaneous gas
CO2 molecule, etc.
Sheet structure
Indoor
SA
RA
Precise, thin-film
material
(Return air
from room)
RA
(unclean
indoor air)
Outdoor air
(fresh air)
Low-humidity air
Supply air
2%
Exhaust air
OA
6%
Auto-ventilation Mode
Changeover Switching
SA
ON/OFF signal
Cooling/Heating mode signal
Set temperature signal
Ventilation signal
Humidifier ON/OFF signal
The air conditioning load reduction values may vary according to weather and
other environmental conditions at the location of the machine's installation.
(Supply air
to room)
The air conditioning load reduction values are based on the following conditions;
Application: Tokyo office building
Building form: 2 floors above ground, 6 floors underground, floor area 2,100 m2
Personnel density: 0.25 person/m2
Ventilation volume: 25 m3/h
Indoor air conditioning level: summer 25C 50% RH, intermediate seasons 24C 50%
RH, winter 22C 40% RH
Operating time: 2745 hours (9 hours per day, approx. 25 days per month)
Calculation method: simulation based on "MICRO-HASP/1982" of the Japan
Building Mechanical and Electrical Engineers Association.
28%
20%
0%
Normal
ventilation fan
VAM-GJ
Individual operation
VAM-GJ
Interlocked operation
with air conditioner
Interlocking
Nighttime free cooling operation is an energy-conserving function that works at night when air
heat load reduced by
*2
conditioners are off. By ventilating rooms
appr ox.
containing office equipment that raises the
room temperature, nighttime free cooling
The indoor accumulated heat is discharged at night.
This reduces the air conditioning load the next day thereby increasing efficiency.
operation reduces the cooling load when
air conditioners are turned on in the
morning. It also alleviates feelings of
Cold air
discomfort in the morning caused by heat
accumulated during the night.
Indoor
Indoor
5% !
HRV
Compact Equipment
Energy Conservation
With a height of just 306 mm, the unit easily fits in limited
spaces, such as above ceilings.
306 mm
61
**For VAM500GJVE
-15CDB
-20
-10
50CDB
10
20
30
40
50
Exhaust
heat
Generated
heat
Heat is discharged.
unit
unit
Exhaust
heat
Comfortable!
62
OPTIONS
Air suction/discharge grille (Obtain locally)
Models
Sound Level
dB(A)
[50 Hz/60 Hz]
For Cooling
Heat
Exchange
Mode
Bypass
Mode
79/79
75/75
79/79
74/74
75/75
72/72
78/78
72/72
77/77
High
79/79
75/75
79/79
74/74
75/75
72/72
Low
84/85
79/79
82/82
80/80.5
77/77.5
74/74.5
78/78
72/72
77/77
80.5/81
75.5/76
79/81
Ultra-High
72/72
71/71
70/70
67/67
67.5/67.5
65/65
70/70
65/65
72/72
High
72/72
71/71
70/70
67/67
67.5/67.5
65/65
70/70
65/65
72/72
Low
76/76.5
74/74
77/77
74/74.5
71.5/72
67.5/68
72.5/73
67/67.5
75/76
Ultra-High
66/66
63/63
66/66
55/55
61/61
61/61
64/64
61/61
62/62
High
66/66
63/63
66/66
55/55
61/61
61/61
64/64
61/61
62/62
Low
70/70.5
64/64.5
68.5/69
64/64.5
66/67
Ultra-High 27-28.5/28.5
66/66
70/70
59/59.5
64/64.5
27-29/29
31.5-33/33
33-35.5/34
34-36/36
26-27.5/27.5
26-27.5/28
30-31.5/30
31.5-34/32
33-34.5/34
Low
20.5-21.5/21
21-22/21
23-25/23
25-28.5/24
27.5-29.5/28
35-37.5/34
35-37.5/34.5
35-37.5/36
36-39/39
40.5-42/41
40.5-42.5/40.5
41-43/42.5
43-45.5/44
39-43/40
38.5-40/39
38.5-40.5/38.5 39.5-41/41.5
High
Low
40.5-45/42
Insulation Material
Dimensions (HX WX D)
Machine Weight
mm
kg
24
32
45
387X 1,111X 832 387X 1,111X 1,214 785X 1,619X 832 785X 1,619X 1,214
55
67
129
157
Air to air cross flow total heat (Sensible heat + latent heat) exchange
Air Filter
Type
SA
Silencer (Option)
Duct
(Obtain locally)
SA
Option List
Ultra-High
150/150
250/250
350/350
500/500
650/650
800/800
1,000/1,000
1,500/1,500
2,000/2,000
High
150/150
250/250
350/350
500/500
650/650
800/800
1,000/1,000
1,500/1,500
2,000/2,000
Low
100/95
155/155
230/230
320/295
500/470
700/670
860/840
1,320/1,260
1,720/1,580
Ultra-High
120/154
70/96
169/222
105/150
85/125
133/170
168/192
112/150
116/140
High
106/131
54/65
141/145
66/52
53/67
92/85
110/86
73/72
58/32
Low
56/60
24/20
67/30
32/18
35/38
72/61
85/60
56/50
45/45
Motor Output
kW
mm
0.030X 2
100
0.090X 2
150
0.140X 2
200
0.280X 2
250
0.280X 4
350
Note: 1. Sound level is measured at 1.5m below the centre of the body.
2. Airflow rate can be changed over to Low mode or High mode.
3. Sound level is measured in an anechoic chamber.
Sound level generally becomes greater than this value depending on the operating conditions, reflected sound, and peripheral noise.
4. The sound level at the air discharge port is about 8 dB higher than the unit's sound level.
5. The specifications, designs and information given here are subject to change without notice.
6. Temperature Exchange Efficiency is the mean value between cooling and heating.
7. Efficiency is measured under the following conditions:
Ratio of rated external static pressure has been maintained as follows; outdoor side to indoor side = 7 to 1.
8. In conformance with JIS standards (JIS B 8628), operating sound level is based on the value when one unit is operated, with the value converted for an anechoic chamber. This is
transmission sound from the main unit, and does not include sound from the discharge grille. Thus it is normal for the sound to be louder than the indicated value when the unit is
actually installed.
9. Sound level from the discharge port causes the value to be approximately 8 dB (models with the airflow rate of less than 150 to 500 m3/h) to approximately 11 dB (models with the
airflow rate of 650 m3/h or more) greater than the indicated value. Furthermore, fan rotation and noise from the discharge grille may increase depending on the on-site duct resistance
conditions. Please consider noise countermeasures when installing the unit.
10. With large models in particular (1500 and 2000 m3/h models), if the supply air (SA) grille is installed near the main unit, the noise of the main unit may be heard from the discharge
grille via the duct, and this will result in a marked increase in noise. In such cases, if peripheral effects are included (such as reverberation of the floor and walls, combination with
other equipment, and background noise), sound level may be as much as 15 dB higher than the indicated value. When installing a large model, please provide as much separation as
possible between the main unit and the discharge grille. If the equipment and discharge grille are near each other, please consider countermeasures such as the following:
Use a sound-muffling box, flexible duct and sound-muffling air supply/discharge grilles
Decentralised installation of discharge grilles
11. When installing in a location with particularly low background noise such as a classroom, please consider the following measures to avoid transmission sound from the main unit:
Use of ceiling materials with high sound insulating properties (high transmission loss)
Methods of blocking sound transmission, for example, by adding sound insulating materials around the bottom of the sound source.
Alternatively, consider supplementary methods such as installing the equipment in a different location (corridor, etc.)
Applicable model
Item
HRV remote controller
Centralised Central remote controller
controlling Unified ON/OFF controller
device
Schedule timer
Wiring adaptor for electrical
appendices
For humidifier
Installation box for adaptor PCB
For heater control kit
BRC301B61
DCS302CA61
DCS301BA61
DST301BA61
KRP2A61
KRP50-2
KRP50-2A90 (Mounted electric component assy of HRV)
BRP4A50
Type
For wiring (indoor unit of VRV) FXCQ-M
KRP1B61
Note 2, 3
KRP1B96
KRP1B61 KRP1B56
KRP1B61
Note 4, 6 Note 5
KRP1B101 KRP4A91
KRP1B3
Note 3
Note 2, 3
KRP1C93 KRP4A93
KRP1B61
KRP1B97
Applicable model VAM150GJVE VAM250GJVE VAM350GJVE VAM500GJVE VAM650GJVE VAM800GJVE VAM1000GJVE VAM1500GJVE VAM2000GJVE
KDDM24B50
KDDM24B100
KDDM24A100X 2
Silencer
Nominal pipe diameter (mm)
200
250
High efficiency filter
KAF242G25M
KAF242G50M
KAF242G65M KAF242G80M KAF242G100M KAF242G80MX 2 KAF242G100MX2
Air filter for replacement
KAF241G25M
KAF241G50M
KAF241G65M KAF241G80M KAF241G100M KAF241G80MX 2 KAF241G100MX2
Flexible duct (1m)
K-FDS101C
K-FDS151C
K-FDS201C
K-FDS251C
Flexible duct (2m)
K-FDS102C
K-FDS152C
K-FDS202C
K-FDS252C
YDFA25A1
Duct adaptor
Nominal pipe diameter (mm)
250
Item
HRV
SA
BRP4A50
Thermostat (Obtain locally)
(OFF when the temperature is at or more than 5C)
63
EA
OA
Sirroco fan
3
Round hood
(Obtain locally)
Branch duct
(Obtain locally)
High
Casing
Additional
function
Enthalpy
Exchange
Efficiency (%)
[50 Hz/60 Hz]
For Heating
Ultra-High
Controlling device
Temp. Exchange
Efficiency (%)
[50 Hz/60 Hz]
Flexible duct
(Option)
RA
PC Board Adaptor
Power Supply
Outdoor
EA
Heater
control kit
(Obtain locally)
OA
Thermostat
(Obtain locally)
(ON when the temperature
is at or below -10C)
Power supply (Obtain locally)
Relay box
64