c o n t e n t s
p. 3
Table of Contents
I NTRODUCTION
6
6
7
9
Energy Efficiency
Design Flexibility
Clean Air
VKM F EATURES
Energy Efficiency
Design Flexibility
L INE - UP
C ONTROL S YSTEMS
Individual Control Systems
Centralised Control Systems
S PECIFICATIONS
VAM-FA
VKM-GM
VKM-G
O PTIONS
10
10
11
12
13
13
16
18
18
19
20
21
mov93585_EPCE05-44B
Daikin
p. 4
i n t r o d u c t i o n
Environmental Consciousness
Enhancing the present - safeguarding the future
Throughout the last 50 years or so the basic building blocks of life - air, water and the earth - have been
systematically subjected to increasing levels of pollution with little regard to their potentially devastating
effects on future generations.
Recently however, concern has grown regarding climate changes, acid rain, water and air pollution and
the constant degradation of Earths natural resources. The very technology that created these problems is
now being harnessed to halt and reverse them. Depletion of the ozone layer and global warming have
been highlighted and are now being addressed. Government legislation prohibiting the use of toxic
substances and the generation of pollutants has slowed down the destruction of the environment.
Daikin Europe is proud to have been pro active in this respect, closely following its Japanese parent in
implementing policies that have often pre-empted official legislative codes and directives. As a result, a
culture of environmental management has since 2001, played a key role in the companys day to day
activities and development strategies.
Top management commitment is reflected in the establishment of a number of action plans, which are
now strictly observed and implemented throughout the Daikin Group.
mov93585_EPCE05-44B
p. 5
HRV helps create a high quality environment by interlocking with the air
conditioning system
The Daikin HRV (Heat Reclaim Ventilation) recovers heat energy lost through
ventilation and holds down room temperature changes caused by
ventilation, thereby maintaining a comfortable and clean environment. This
also reduces the load on the air conditioning system and conserves energy.
In addition, the HRV interlocks with Daikins VRV system, Sky Air and other air
conditioning systems and automatically switches over ventilation mode,
further increasing the effects of energy conservation. HRV operation has
been centralised on the air conditioner remote control allowing total
control over air conditioning and ventilation via a simple configuration.
The current line-up includes models with DX coil and/or humidifier - the DX
coil helps prevent the direct impact of cold airflow upon personnel during
the heating cycle and vice versa. High static pressure enhances design
flexibility.
Components of Indoor Air Quality
Ventilation
HRV
Humidification
Airflow
150
250
350 500
650
mov93585_EPCE05-44B
p. 6
g e n e r a l
H R V
f e a t u r e s
Indoor
30.6C
62% RH
SA
27.4C
63% RH
Temperature
and humidity
RA
26C
50% RH
32C
70% RH
Integrally-formed liner
SA
Integrallyformed liner
RA
mov93585_EPCE05-44B
d e s i g n
f l e x i b i l i t y
p. 7
Cooling
Heat exchanger element
Exhaust fan Damper (heat recovery)
EA
RA
EA
Heating
Heat exchanger element
(heat recovery)
RA
Automatic
changeover
OA
SA
EA
RA
OA
SA
Automatic
changeover
OA
SA
DX coil (heating)
DX coil (cooling)
Humidifying
2 D ESIGN F LEXIBILITY
2.
Outdoor Operation Temperature down to -15C
If the outdoor air suction temperature falls below -10C, the unit switches to intermittent
operation to prevent freezing of the heat exchanger element and dew condensation within the
unit.
Intermittent operation = a thermistor (standard equipment) within the unit detects the outdoor
air temperature. Unit operation varies according to the detected temperature.
Slim Design
The slim design of the HRV unit enables it to be mounted in narrow ceiling voids and irregularly
shaped spaces.
269mm
VAM250FA
348mm
mov93585_EPCE05-44B
p. 8
d e s i g n
f l e x i b i l i t y
Switch box
Access door
Maintenance cover
Quiet Operation
Sound pressure levels are remarkable low at 20.5dBA (VAM150FA)
dB(A)
Perceived loudness
Sound
0
20
40
60
80
100
120
Treshold of hearing
Extremely soft
Very soft
Moderately loud
Very loud
Extremely loud
Threshold of feeling
Rustling leaves
Quiet room
Normal conversation
City traffic noise
Symphonic orchestra
Jet taking off
Daikin units
mov93585_EPCE05-44B
c l e a n
a i r
p. 9
3 C LEAN A IR
3.
Fresh-Up Operation
The user can select between 2 fresh-up modes via the remote control
2. Exhaust fresh-up:
Portion of fresh-up
operation
Air exhaust
HRV
Normal
ventilation fan
Air supply
Air exhaust
HRV
Air supply
Portion of
exhaust
operation
Floor area
Sick room
eg. Office
eg. Hospital
Dust Prevention
Prevents dust from falling thanks to directly mounted ducts
OFF
Dust
Blowing mode
With HRV
Filter Cleaning
A signal on the remote control indicates when the air filter needs cleaning
mov93585_EPCE05-44B
p. 10
e n e r g y
e f f i c i e n c y
Heat Exchanger
Elements
EA
(Exhaust air to outdours)
Damper Motor
Damper
DX coil
(Direct expansion coil)
OA
(Fresh air from outdoors)
RA
(Return air from room)
Float switch
Solenoid
valve
Humidifier element:
Utilizing the principle of capillary action,
water is permeated throughout the
humidifier element. The heated air from
the DX coil passes through the humidifier
and absorbs the moisture
water
AIRFLOW
Drain pan
SA
Drain
1.
1 E NERGY E FFICIENCY
Nighttime Free Cooling Operation
Nighttime free Cooling Operation is an energy
conserving function operating at night when the
air conditioning is switched off. By ventilating
rooms containing office equipment that increases
room temperature, night purge reduces the
cooling load when air conditioning is switched
on in the morning.
Nighttime free cooling operation works only if
connected to Multi or VRV systems.
Nighttime free cooling operation is factory set
to off but can be activated by your Daikin
dealer on request.
Temp.
40
VKM
Air
Conditioner
Outdoor Temp.
30
Setting Temp.
20
Indoor Temp.
ON
2 Hours
auto
start
OFF
ON
OFF
start
mov93585_EPCE05-44B
p. 11
d e s i g n
f l e x i b i l i t y
Efficient Outdoor Air Introduction with Heat Exchanger and Cooling/Heating Operation
Indoor unit with outdoor air treatment
The temperature can be brought close to room temperature with minimal cooling capacity
through the use of outdoor air
100 80
Outdoor air
temperature in summer
Effect of cooling
40
heat recovery
+
humidifying
Effect of
humidification
-5
20
60
Effect of
Effect
of heating
heat ng
Effect of
of full
full heat
exchange
Effect
heat exchange
10
15
20
25
30
35
40
2 D ESIGN F LEXIBILITY
2.
High Static Pressure
Modifications to the fan, including the use of multiple arc blades, a thinner scroll and optimized
fan scroll angle, help to boost efficiency.
Dramatically higher static pressure is achieved due to improved fan performance. This reduces
limitations on unit location and allows more flexibility in duct design.
Higher static pressure and reduced noise
The use of multiple, overlapping arc shaped fan
blades makes it possible to optimize the chord
lenght and blade outlet angle. This results in
higher static pressure and quieter operation
over the entire operating range.
mov93585_EPCE05-44B
p. 12
l i n e - u p
IV. Line-up
VAM-FA: ventilation
VA M 1 5 0 FA
VA M 5 0 0 FA
VA M 1 0 0 0 FA
VA M 2 5 0 FA
VA M 3 5 0 FA
VA M 6 5 0 FA
VA M 8 0 0 FA
VA M 1 5 0 0 FA
VA M 2 0 0 0 FA
V K M 5 0 G M
V K M 8 0 - 1 0 0 G M
V K M 5 0 G
V K M 8 0 - 1 0 0 G
mov93585_EPCE05-44B
c o n t r o l
s y s t e m s
p. 13
V. Control Systems
HRV can also be
connected to :
Operation of the air conditioner using the remote control is interlocked with
HRV operation, greatly simplifying overall system control. The same remote
control centralizes air conditioning and ventilation operations, obviating any
need for HRV remote control installation work. Using a centralized remote
control also frees the user to choose from a wide range of control systems
that integrate air conditioning and ventilation. By incorporating a variety of
centralized control[iPU]
equipment, the user can build a large, high grade centralized
control system.
Outdoor unit
Indoor
unit
VKM
Remote control
BRC1D52
9
9
9
9
9
9
9
9
9
9
BRC301B61
VAM remote control
mov93585_EPCE05-44B
p. 14
i n d i v i d u a l
c o n t r o l
s y s t e m s
Air Conditioner
Up to 16 units*1
HRV
BRC1D52
Up to 500m
*1: Count VKM unit as two air conditioners. For details, see Table 1 on page 15.
Air Conditioner
HRV
BRC1D52 (No.2)
Up to 500m
BRC1D52 (No.1)
Air Conditioner
HRV
Up to 500m
BRC1D52
2 remote control control possible
mov93585_EPCE05-44B
p. 15
System
characteristics
INDEPENDENT
O P E R AT I O N
S TA N D A R D S Y S T E M
BRC1D52
BRC301B61
BRC1D52/BRC301B61
HRV
HRV
BRC1D52(No. 1)/
BRC301B61
Operation is possible
using 2 remote controls
Multiple HRV units can
be simultaneously controlled in batch. (Up to 8
HRV units can be connected)
BRC1D52(No. 2)/
BRC301B61
Indoor unit
HRV
BRC1D52
3
10
4
8
5
6
BRC1D52
BRC301B61
6
4
7
2
8
0
BRC1D52
Group 1
M U LT I P L E G R O U P S
INTERLOCKED
O P E R AT I O N S Y S T E M
Necessary
accessories
Independent operation
of HRV is possible
HRV
S I M U LT A NEOUS
O P E R AT I O N
O F M U LT I P L E
UNITS
INDEPENDENT
O P E R AT I O N S Y S T E M
System construction
Indoor
unit
BRC1D52
Group 1
Indoor
unit
Indoor
unit
BRC1D52
Group 2
BRC1D52
Indoor
unit
BRC1D52
BRC1D52
KRP2A61
HRV
Group 2
HRV
mov93585_EPCE05-44B
p. 16
c e n t r a l i s e d
c o n t r o l
s y s t e m s
DCS302C51
DCS301B51
DST301B51
2 units
8 units
Schedule timer
1 unit
mov93585_EPCE05-44B
p. 17
System
characteristics
B AT C H / I N D I V I D U A L C O N T R O L
SYSTEM
HRV
Indoor unit
BRC1D52
DCS301B51
DST301B51
BRC1D52
HRV
Indoor unit
BRC1D52
Necessary
accessories
DCS301B51
or
DST301B51,
BRC1D52
If necessary:
DCS302C51
Zone 1
Indoor unit
BRC1D52
Zone 2
COMBINATION WITH
OTHER
TYPES OF
AIR CONDITIONERS
System construction
Indoor unit
DCS302C51
HRV
BRC1D52
HRV
BRC1D52
Adapter
HRV
Air conditioner
BRC1D52
Connecting line
can be extended
up to 50m
Simultaneous operation
of HRVs and air conditioners is possible via
BRC1D52
DCS302C51,
BRC1D52
If necessary:
DCS301B51,
DST301B51
Connection
adapter
(no-voltage Use of the HRV remote
a-contactcontrol enables to change
signal)
settings or operate HRVs
independently
mov93585_EPCE05-44B
p. 18
s p e c i f i c a t i o n s
VI. Specifications
VAM-FA
VA M 8 0 0 FA
Ventilation
VAM-FA
Temperature exchange efficiency (%)
for heating
for cooling
Power Supply
Sound pressure level dB(A)
Bypass mode
Casing
Insulation Material
Dimensions
Weight
Heat Exchange System
Heat Exchange Element Material
Air Filter
Fan
HxWxD
Type
Air Flow Rate (m3/h)
Motor Output
Connection Duct Diameter
Unit ambient condition
ultra-high
high
low
ultra-high
high
low
ultra-high
high
low
VE
ultra-high
high
low
ultra-high
high
low
mm
kg
ultra-high
high
low
ultra-high
high
low
kW
mm
150
250
350
500
74
74
79
64
64
69
58
58
64
72
72
77
64
64
68
58
58
62
75
75
80
65
65
70
61
61
67
74
74
77
62
62
67
58
58
63
27-28.5
26-27.5
20.5-21.5
27-28.5
26.5-27.5
20.5-21.5
28-29
26-27
21-22
28-29
27-28
21-22
150
150
110
69
39
20
250
250
155
64
39
20
0.030 x 2
100
800
1000
1500
2000
74
74
75
75
75
74
74
75
75
75
77
76
76.5
78
78
63
65
66
66
66
63
65
66
66
66
66
67
68
68
70
58
60
61
61
61
58
60
61
61
61
63
62
63
64
66
1 ~, 220~240V, 50Hz
32-34
33-34.5
34.5-35.5
36-37
36-37
39.5-41.5
40-42.5
31.5-33
31.5-33
33-34
34.5-36
35-36
38-39
38-41
23.5-26
24.5-26.5
27-28
31-32
31-32
34-36
35-37
32-34
33.5-34.5
34.5-35.5
36-37
36-37
40.5-41.5
40-42.5
31-32.5
32.5-33.5
34-35
34.5-36
35.5-36
38-39
38-41
24.5-26.5
25.5-27.5
27-28.5
31-33
31-32
33.5-36
35-37
galvanised steel plate
self-extinguishable urethane foam
285 x 812 x 800
348 x 988 x 852
348x988x1,140 710x1,498x852 710x1,498x1,140
33
48
61
132
158
air to air cross flow total heat (sensible heat + latent heat) exchange
specially processed non-flammable paper
multidirectional fibrous fleeces
sirroco fan
350
500
650
800
1,000
1,500
2,000
350
500
650
800
1,000
1,500
2,000
230
350
500
670
870
1,200
1,400
98
98
93
137
157
137
137
70
54
39
98
98
98
78
25
25
25
49
78
49
59
0.090 x 2
0.140 x 2
0.230 x 2
0.230 x 4
150
200
250
350
-15C ~ +50CDB, 80% RH or less
Notes: Air flow rate can be changed over to low mode or high mode.
Sound pressure level is measured at 1.5m below the center of the body.
Sound pressure level is measured in an anechoic chamber.
Sound pressure levels generally become higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound pressure level at the air discharge port is about 8dB higher than the unit's sound level.
Even when the outdoor temperature is below -15C, the system is operable down to -20C with the preheater installed at the outdoor air intake side.
650
mov93585_EPCE05-44B
p. 19
VKM-GM
Ventilation, DX coil & humidifier
DX coil capacity
Casing
Dimensions
Weight
Fan
Cooling
Heating
Material
Height
Width
Depth
Type
Air flow rate Heat exchange mode
Bypass mode
Motor
Temperature exchange efficiency
Enthalpy exchange
efficiency
Output
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Cooling
Heating
Humidifier
Operation range
Piping connection
System
Amount
Feed water pressure
N of elements
Around unit
Outdoor air
Return air
Heat
Sound pressure
exchange
mode
Bypass mode Sound pressure
Liquid
Gas
Type
Diameter
Type
Diameter
Water supply
Drain
Insulation material
Heat exchange system
Heat exchange element
Air filter
Connection duct diameter
Power supply
Notes:
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
V K M 8 0 - 1 0 0 G M
VKM50GM
VKM80GM
VKM100GM
kW
kW
4.71
5.58
9.12
10.69
mm
mm
mm
kg
387
1764
832
102
m3/h
m3/h
m3/h
m3/h
m3/h
m3/h
Pa
Pa
Pa
W
%
%
%
%
%
%
%
%
%
500
500
440
500
500
440
160
120
100
2 x 280
76
76
77.5
64
64
67
67
67
69
kg/h
MPa
2.7
0.02~0.49
1
dBA
dBA
dBA
dBA
dBA
dBA
37.5
35.5
33
37.5
35.5
33
flare connection
6.4
flare connection
12.7
6.4
7.46
8.79
Galvanised steel plate
387
1764
1214
120.0
Sirocco fan
750
750
640
750
750
640
140
90
70
2 x 280
78
78
79
66
66
68
71
71
73
Natural evaporating type
4.0
0.02~0.49
1
0C~40CDB, 80% RH or less
-15C~40CDB, 80% RH or less
0C~40CDB, 80% RH or less
39
37
34
39
37
34
flare connection
6.4
flare connection
12.7
6.4
PT3/4 external thread
Self-extinguishable urethane foam
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
Multidirectional fibrous fleeces
250
1~, 50Hz, 220-240V
mm
mm
mm
mm
V1
200
387
1764
1214
125.0
950
950
820
950
950
820
110
70
60
2 x 280
74
74
76.5
62
62
66
65
65
69
5.4
0.02~0.49
2
39.5
37.5
34.5
39.5
37.5
34.5
flare connection
6.4
flare connection
12.7
6.4
250
Indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDBIndoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB
Humidifying capacity is based on: Indoor temperature: 20CDB, 15CWB, outdoor temperature: 7CDB, 6CWB
Operation sound is measured at 1.5m below the center of the body.
Sound values are measured in an anechoic chamber built in accordance with JIS C 1502 condition. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound level at the air discharge port is about 8dB higher than the units operating sound.
For operation in a quiet room, it is required to take measures to lower the sound, for example install more than 2m soft duct near the air discharge grill.
Air flow rate can be changed over to Low mode or High mode.
Normal amplitude, input, efficiency depend on the other above conditions
mov93585_EPCE05-44B
p. 20
VKM-G
Ventilation & DX coil
DX coil capacity
Casing
Dimensions
Weight
Fan
Bypass mode
Motor
Temperature exchange efficiency
Enthalpy exchange
efficiency
Piping connection
VKM80G
VKM100G
kW
kW
4.71
5.58
9.12
10.69
mm
mm
mm
kg
387
1764
832
96.0
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
m3/h
m3/h
m3/h
m3/h
m3/h
m3/h
Pa
500
500
440
500
500
440
180
7.46
8.79
Galvanised steel plate
387
1764
1214
109.0
Sirocco fan
750
750
640
750
750
640
170
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Pa
Pa
W
%
%
%
%
%
%
%
%
%
150
110
2 x 280
76
76
77.5
64
64
67
67
67
69
100
70
2 x 280
74
74
76.5
62
62
66
65
65
69
Ultra-high
High
Low
Ultra-high
High
Low
dBA
dBA
dBA
dBA
dBA
dBA
38.5
36.5
34.5
38.5
36.5
34.5
flare connection
6.4
flare connection
12.7
120
80
2 x 280
78
78
79
66
66
68
71
71
73
0C~40CDB, 80% RH or less
-15C~40CDB, 80% RH or less
0C~40CDB, 80% RH or less
41
38
36
41
38
36
flare connection
6.4
flare connection
12.7
PT3/4 external thread
Self-extinguishable urethane foam
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
Multidirectional fibrous fleeces
250
1~, 50Hz, 220-240V
Output
Cooling
Heating
Operation range
VKM50G
Cooling
Heating
Material
Height
Width
Depth
Type
Air flow rate Heat exchange mode
Around unit
Outdoor air
Return air
Heat
Sound pressure
exchange
mode
Bypass mode Sound pressure
Liquid
Gas
Type
Diameter
Type
Diameter
V K M 8 0 - 1 0 0 G
mm
mm
Drain
Insulation material
Heat exchange system
Heat exchange element
Air filter
Connection duct diameter
Power supply
Notes:
mm
V1
200
387
1764
1214
114.0
950
950
820
950
950
820
150
40.5
38.5
36
40.5
38.5
36
flare connection
6.4
flare connection
12.7
250
mov93585_EPCE05-44B
o p t i o n s
p. 21
VII. Options
Air suction/discharge grille (accessory)
Flexible duct
(Accessory)
High efficiency filter
(Accessory)
RA
SA
Round hood
(Field supply)
Branch duct
(Field supply)
Silencer ( Accessory)
SA
Duct
(Field supply)
Thermal insulation material
(Field supply)
Air conditioner
remote control
Description
VAM remote control
Air conditioner remote control
Centralised remote control
Unified on/off control
Schedule timer
PC board adapter
OA
EA
Schedule timer
Reference
FXZQ
KRP1B57*
KRP1B101
*4/*6
FXFQ
KRP1B59*
KRP1D98
*2/*3
FXCQ
KRP1B61*
KRP1B96
*2/*3
FXKQ
-
BRC301B61*5
BRC1D52
DCS302C51
DCS301B51
DST301B51
KRP2A61
KRP50-2
BRP4A50
FXMQ
FXSQ
KRP1D61
KRP4A91
*5
FXDQ-N
KRP1B56
KRP1B101
*4/*6
FXHQ
KRP1B3
KRP1C93
*3
FXAQ
KRP4A93
*2/*3
FXLQ/FXNQ
KRP1B61
-
mov93585_EPCE05-44B
p. 22
p c
1 PC
1.
b o a r d
a d a p t e r
- BRP4A50
When the installation of an electric heater is required in a cold region, this adapter with an
internal timer function eliminates the complicated timer connecting work necessary with
conventional heaters.
INDOOR
RA
OUTDOOR
EA
HRV
SA
BRP4A50
Heater
control kit
(field supply)
OA
Temperature thermostat
(field supply)
(ON when the temperature
is at or below -10C)
mov93585_EPCE05-44B
p. 23
o p t i o n s
Silencer
Description
High efficiency filter
Replacement for air filter
Description
Silencer
Reference
Nom. piping diameter
VAM150FA
VAM250FA
VAM350FA
YAFM323F15
YAFF323F15
YAFM323F25
YAFF323F25
YAFM323F35
YAFF323F35
VAM500FA
VAM650FA
VAM800FA
KDDM24A50
200mm
YAFM323F50
YAFF323F50
VAM1000FA
Description
Silencer
Duct adapter
Reference
Nom. piping diameter
KDDM24A100
YAFM323F100
YAFF323F100
-
VKM50G(M)
Description
Silencer
Reference
Nom. piping diameter
KAF241G80M
KAF242G80M
KDDM24A100
250mm
YAFM323F65
YAFF323F65
VAM1500FA
VAM2000FA
K-DDM24A100 x 2
250mm
YAFM323F65
YAFF323F65
YAFM323F100 x 2
YAFF323F100 x 2
YDFA25A1
250mm
VKM80G(M)
VKM100G(M)
K-DDM24B100
250mm
KAF241G100M
KAF242G100M
mov93585_EPCE05-44B
Zandvoordestraat 300
B-8400 Oostende, Belgium
www.daikineurope.com