c o n t e n t s
p. 3
Table of Contents
INTRODUCTION
1. Energy Efficiency
2. Design Flexibility
3. Clean Air
VKM FEATURES
1. Energy Efficiency
2. Design Flexibility
SPECIFICATIONS
CONTROL SYSTEMS
1. Individual Control Systems
2. Centralised Control Systems
OPTIONS
10
10
11
13
15
15
18
20
21
SPECIFICATIONS
CONTROL SYSTEMS
1. Individual Control Systems
2. Centralised Control Systems
OPTIONS
23
24
25
25
26
27
27
27
28
29
29
30
SPECIFICATIONS
30
1.
2.
3.
4.
30
30
30
31
System Specifications
Combination Table
Expansion Valve kit
Control Box
CONTROL SYSTEMS
1. Control of Air Temperature via Daikin Control
OPTIONS
32
32
32
p. 4
Daikin Europe
NV
i n t r o d u c t i o n
Environmental Awareness
Enhancing the present - safeguarding the future
Throughout the last 50 years or so the basic building blocks of life - air, water and the earth - have been
systematically subjected to increasing levels of pollution with little regard to their potentially devastating
effects on future generations.
Recently however, concern has grown regarding climate changes, acid rain, water and air pollution and
the constant degradation of Earths natural resources. The very technology that created these problems is
now being harnessed to halt and reverse them. Depletion of the ozone layer and global warming have
been highlighted and are now being addressed. Government legislation prohibiting the use of toxic
substances and the generation of pollutants has slowed down the destruction of the environment.
Daikin Europe is proud to have been pro active in this respect, closely following its Japanese parent in
implementing policies that have often pre-empted official legislative codes and directives. As a result, a
culture of environmental management has since 2001, played a key role in the companys day to day
activities and development strategies.
Top management commitment is reflected in the establishment of a number of action plans, which are
now strictly observed and implemented throughout the Daikin Group.
p. 5
g e n e r a l
H R V
f e a t u r e s
Ventilation
HRV
Humidification
Airflow
Line-up
Air flow rate (m3/h)
VAM-FA
Ventilation
VKM-GAM:
Ventilation, DX coil
& humidifier
VKM-GA:
Ventilation & DX coil
150
250
350 500
650
p. 6
g e n e r a l
H R V
f e a t u r e s
E NERGY E FFICIENCY
Outdoor
Indoor
30.6C
62% RH
SA
27.4C
63% RH
Temperature
and humidity
RA
26C
50% RH
32C
70% RH
Integrally-formed liner
SA
Integrallyformed liner
RA
p. 7
g e n e r a l
H R V
f e a t u r e s
Cooling
Heat exchanger element
Exhaust fan Damper (heat recovery)
RA
EA
EA
Heating
Heat exchanger element
(heat recovery)
RA
Automatic
changeover
OA
SA
EA
RA
OA
SA
Automatic
changeover
OA
SA
DX coil (heating)
DX coil (cooling)
Humidifying
D ESIGN F LEXIBILITY
269mm
VAM250FA
348mm
p. 8
g e n e r a l
H R V
f e a t u r e s
Switch box
Access door
Maintenance cover
Quiet Operation
Sound pressure levels are remarkable low at 20.5dBA (VAM150FA)
dB(A)
Perceived loudness
Sound
0
20
40
60
80
100
120
Treshold of hearing
Extremely soft
Very soft
Moderately loud
Very loud
Extremely loud
Threshold of feeling
Rustling leaves
Quiet room
Normal conversation
City traffic noise
Symphonic orchestra
Jet taking off
Daikin units
p. 9
g e n e r a l
H R V
f e a t u r e s
C LEAN A IR
Fresh-Up Operation
The user can select between 2 fresh-up modes via the remote control
2. Exhaust fresh-up:
Portion of fresh-up
operation
Air exhaust
HRV
Normal
ventilation fan
Air supply
Air exhaust
HRV
Floor area
Air supply
Portion of
exhaust
operation
Sick room
eg. Office
eg. Hospital
Dust Prevention
Prevents dust from falling thanks to directly mounted ducts
OFF
Dust
Blowing mode
With HRV
Filter Cleaning
A signal on the remote control indicates when the air filter needs cleaning
V K M
f e a t u r e s
p. 10
VKM Features
Exhaust Fan
Heat Exchanger
Elements
EA
(Exhaust air to outdours)
Damper Motor
Damper
DX coil
(Direct expansion coil)
OA
(Fresh air from outdoors)
RA
(Return air from room)
Float switch
Solenoid
valve
Humidifier element:
Utilizing the principle of capillary action,
water is permeated throughout the
humidifier element. The heated air
from the DX coil passes through the
humidifier and absorbs the moisture
water
AIRFLOW
Drain pan
SA
Drain
E NERGY E FFICIENCY
Temp.
40
VKM
Air
Conditioner
Outdoor Temp.
30
Setting Temp.
20
Indoor Temp.
ON
2 Hours
auto
start
OFF
ON
OFF
start
p. 11
V K M
f e a t u r e s
Efficient Outdoor Air Introduction with Heat Exchanger and Cooling/Heating Operation
Indoor unit with outdoor air treatment
The temperature can be brought close to room temperature with minimal cooling capacity
through the use of outdoor air
100 80
Outdoor air
temperature in summer
Effect of cooling
40
heat recovery
+
humidifying
Effect of
humidification
-5
20
60
Effect of
Effect
of heating
heating
Effect of
of full
full heat
exchange
Effect
heat exchange
10
15
20
25
30
35
40
2 D ESIGN F LEXIBILITY
2.
High Static Pressure
Modifications to the fan, including the use of multiple arc blades, a thinner scroll and optimized
fan scroll angle, help to boost efficiency.
Dramatically higher static pressure is achieved due to improved fan performance. This reduces
limitations on unit location and allows more flexibility in duct design.
Higher static pressure and reduced noise
The use of multiple, overlapping arc shaped fan
blades makes it possible to optimize the chord
lenght and blade outlet angle. This results in
higher static pressure and quieter operation
over the entire operating range.
p. 12
s p e c i f i c a t i o n s
Specifications
VAM-FA
VA M 8 0 0 FA
Ventilation
VAM-FA
Temperature exchange efficiency (%)
for heating
for cooling
Power Supply
Sound pressure level dB(A)
Bypass mode
Casing
Insulation Material
Dimensions
Weight
Heat Exchange System
Heat Exchange Element Material
Air Filter
Fan
HxWxD
Type
Air Flow Rate (m3/h)
Motor Output
Connection Duct Diameter
Unit ambient condition
ultra-high
high
low
ultra-high
high
low
ultra-high
high
low
VE
ultra-high
high
low
ultra-high
high
low
mm
kg
ultra-high
high
low
ultra-high
high
low
kW
mm
150
250
350
500
74
74
79
64
64
69
58
58
64
72
72
77
64
64
68
58
58
62
75
75
80
65
65
70
61
61
67
74
74
77
62
62
67
58
58
63
27-28.5
26-27.5
20.5-21.5
27-28.5
26.5-27.5
20.5-21.5
28-29
26-27
21-22
28-29
27-28
21-22
150
150
110
69
39
20
250
250
155
64
39
20
0.030 x 2
100
650
800
1000
1500
2000
74
74
75
75
75
74
74
75
75
75
77
76
76.5
78
78
63
65
66
66
66
63
65
66
66
66
66
67
68
68
70
58
60
61
61
61
58
60
61
61
61
63
62
63
64
66
1 ~, 220~240V, 50Hz
32-34
33-34.5
34.5-35.5
36-37
36-37
39.5-41.5
40-42.5
31.5-33
31.5-33
33-34
34.5-36
35-36
38-39
38-41
23.5-26
24.5-26.5
27-28
31-32
31-32
34-36
35-37
32-34
33.5-34.5
34.5-35.5
36-37
36-37
40.5-41.5
40-42.5
31-32.5
32.5-33.5
34-35
34.5-36
35.5-36
38-39
38-41
24.5-26.5
25.5-27.5
27-28.5
31-33
31-32
33.5-36
35-37
galvanised steel plate
self-extinguishable urethane foam
285 x 812 x 800
348 x 988 x 852
348x988x1,140 710x1,498x852 710x1,498x1,140
33
48
61
132
158
air to air cross flow total heat (sensible heat + latent heat) exchange
specially processed non-flammable paper
multidirectional fibrous fleeces
sirroco fan
350
500
650
800
1,000
1,500
2,000
350
500
650
800
1,000
1,500
2,000
230
350
500
670
870
1,200
1,400
98
98
93
137
157
137
137
70
54
39
98
98
98
78
25
25
25
49
78
49
59
0.090 x 2
0.140 x 2
0.230 x 2
0.230 x 4
150
200
250
350
-15C ~ +50CDB, 80% RH or less
Notes: Air flow rate can be changed over to low mode or high mode.
Sound pressure level is measured at 1.5m below the center of the body.
Sound pressure level is measured in an anechoic chamber.
Sound pressure levels generally become higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound pressure level at the air discharge port is about 8dB higher than the unit's sound level.
Even when the outdoor temperature is below -15C, the system is operable down to -20C with the preheater installed at the outdoor air intake side.
p. 13
VKM-GAM
Ventilation, DX coil & humidifier
V K M 8 0 - 1 0 0 G A M
DX coil capacity
Casing
Dimensions
Weight
Fan
Cooling
Heating
Material
Height
Width
Depth
Type
Air flow rate Heat exchange mode
Bypass mode
Motor
Temperature exchange efficiency
Enthalpy exchange
efficiency
Output
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Cooling
Heating
Humidifier
Operation range
Piping connection
System
Amount
Feed water pressure
N of elements
Around unit
Outdoor air
Return air
Heat
Sound pressure
exchange
mode
Bypass mode Sound pressure
Liquid
Gas
Water supply
Drain
Insulation material
Heat exchange system
Heat exchange element
Air filter
Connection duct diameter
Power supply
Notes:
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Type
Diameter
Type
Diameter
Ultra-high
High
Low
Ultra-high
High
Low
VKM50GAM
VKM80GAM
VKM100GAM
kW
kW
4.71
5.58
9.12
10.69
mm
mm
mm
kg
387
1,764
832
102
m3/h
m3/h
m3/h
m3/h
m3/h
m3/h
Pa
Pa
Pa
W
%
%
%
%
%
%
%
%
%
500
500
440
500
500
440
160
120
100
2 x 280
76
76
77.5
64
64
67
67
67
69
kg/h
MPa
2.7
0.02~0.49
1
dBA
dBA
dBA
dBA
dBA
dBA
37.5
35.5
33
37.5
35.5
33
flare connection
6.4
flare connection
12.7
6.4
7.46
8.79
Galvanised steel plate
387
1,764
1,214
120
Sirocco fan
750
750
640
750
750
640
140
90
70
2 x 280
78
78
79
66
66
68
71
71
73
Natural evaporating type
4.0
0.02~0.49
1
0C~40CDB, 80% RH or less
-15C~40CDB, 80% RH or less
0C~40CDB, 80% RH or less
39
37
34
39
37
34
flare connection
6.4
flare connection
12.7
6.4
PT3/4 external thread
Self-extinguishable urethane foam
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
Multidirectional fibrous fleeces
250
1~, 50Hz, 220-240V
mm
mm
mm
mm
V1
200
387
1,764
1,214
125
950
950
820
950
950
820
110
70
60
2 x 280
74
74
76.5
62
62
66
65
65
69
5.4
0.02~0.49
2
39.5
37.5
34.5
39.5
37.5
34.5
flare connection
6.4
flare connection
12.7
6.4
250
Indoor temperature: 27CDB, 19CWB, outdoor temperature: 35CDBIndoor temperature: 20CDB, outdoor temperature: 7CDB, 6CWB
Humidifying capacity is based on: Indoor temperature: 20CDB, 15CWB, outdoor temperature: 7CDB, 6CWB
Operation sound is measured at 1.5m below the center of the body.
Sound values are measured in an anechoic chamber built in accordance with JIS C 1502 condition. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound level at the air discharge port is about 8dB higher than the units operating sound.
For operation in a quiet room, it is required to take measures to lower the sound, for example install more than 2m soft duct near the air discharge grill.
Air flow rate can be changed over to Low mode or High mode.
Normal amplitude, input, efficiency depend on the other above conditions
p. 14
VKM-GA
Ventilation & DX coil
DX coil capacity
Casing
Dimensions
Weight
Fan
Bypass mode
Motor
Temperature exchange efficiency
Enthalpy exchange
efficiency
Piping connection
VKM80GA
VKM100GA
4.71
5.58
9.12
10.69
mm
mm
mm
kg
387
1,764
832
96
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
m3/h
m3/h
m3/h
m3/h
m3/h
m3/h
Pa
Pa
Pa
W
%
%
%
%
%
%
%
%
%
500
500
440
500
500
440
180
150
110
2 x 280
76
76
77.5
64
64
67
67
67
69
Ultra-high
High
Low
Ultra-high
High
Low
dBA
dBA
dBA
dBA
dBA
dBA
38.5
36.5
34.5
38.5
36.5
34.5
flare connection
6.4
flare connection
12.7
7.46
8.79
Galvanised steel plate
387
1,764
1,214
109
Sirocco fan
750
750
640
750
750
640
170
120
80
2 x 280
78
78
79
66
66
68
71
71
73
0C~40CDB, 80% RH or less
-15C~40CDB, 80% RH or less
0C~40CDB, 80% RH or less
41
38
36
41
38
36
flare connection
6.4
flare connection
12.7
PT3/4 external thread
Self-extinguishable urethane foam
Air to air cross flow total heat (sensible + latent heat) exchange
Specially processed non-flammable paper
Multidirectional fibrous fleeces
250
1~, 50Hz, 220-240V
Cooling
Around unit
Outdoor air
Return air
Heat
Sound pressure
exchange
mode
Bypass mode Sound pressure
Liquid
Gas
Ultra-high
High
Low
Ultra-high
High
Low
Ultra-high
High
Low
Output
Heating
Operation range
VKM50GA
kW
kW
Cooling
Heating
Material
Height
Width
Depth
Type
Air flow rate Heat exchange mode
Type
Diameter
Type
Diameter
V K M 8 0 - 1 0 0 G A
mm
mm
Drain
Insulation material
Heat exchange system
Heat exchange element
Air filter
Connection duct diameter
Power supply
Notes:
mm
V1
200
387
1,764
1,214
114
950
950
820
950
950
820
150
100
70
2 x 280
74
74
76.5
62
62
66
65
65
69
40.5
38.5
36
40.5
38.5
36
flare connection
6.4
flare connection
12.7
250
p. 15
c o n t r o l
s y s t e m s
Control Systems
HRV can also be
connected to :
Operation of the air conditioner using the remote control is interlocked with
HRV operation, greatly simplifying overall system control. The same remote
control centralizes air conditioning and ventilation operations, obviating any
need for HRV remote control installation work. Using a centralized remote
control also frees the user to choose from a wide range of control systems
that integrate air conditioning and ventilation. By incorporating a variety of
centralized control equipment, the user can build a large, high grade centralized
control system.
Outdoor unit
Indoor
unit
VKM
Remote control
BRC1D52
9
9
9
9
9
9
9
9
9
9
BRC301B61
VAM remote control
i n d i v i d u a l
c o n t r o l
p. 16
s y s t e m s
Air Conditioner
Up to 16 units*1
HRV
BRC1D52
Up to 500m
*1: Count VKM unit as two air conditioners. For details, see Table 1 on page 15.
Air Conditioner
HRV
BRC1D52 (No.2)
Up to 500m
BRC1D52 (No.1)
Air Conditioner
HRV
Up to 500m
BRC1D52
2 remote control control possible
p. 17
c o n t r o l
s y s t e m s
System
characteristics
INDEPENDENT
O P E R AT I O N
S TA N D A R D S Y S T E M
BRC1D52
BRC301B61
BRC1D52/BRC301B61
HRV
HRV
Operation is possible
using 2 remote controls
Multiple HRV units can
be simultaneously controlled in batch. (Up to 8
HRV units can be connected)
BRC1D52(No. 2)/
BRC301B61
BRC1D52(No. 1)/
BRC301B61
Indoor unit
HRV
BRC1D52
3
10
4
8
5
6
BRC1D52
BRC301B61
6
4
7
2
8
0
BRC1D52
Group 1
M U LT I P L E G R O U P S
INTERLOCKED
O P E R AT I O N S Y S T E M
Necessary
accessories
Independent operation
of HRV is possible
HRV
S I M U LT A NEOUS
O P E R AT I O N
O F M U LT I P L E
UNITS
INDEPENDENT
O P E R AT I O N S Y S T E M
System construction
Indoor
unit
Group 1
Indoor
unit
Indoor
unit
BRC1D52
BRC1D52
Group 2
BRC1D52
Indoor
unit
BRC1D52
BRC1D52
KRP2A61
HRV
Group 2
HRV
p. 18
c o n t r o l
s y s t e m s
DCS302C51
DCS301B51
DST301B51
2 units
8 units
Schedule timer
1 unit
p. 19
c o n t r o l
s y s t e m s
System
characteristics
B AT C H / I N D I V I D U A L C O N T R O L
SYSTEM
HRV
Indoor unit
BRC1D52
DCS301B51
DST301B51
BRC1D52
HRV
Indoor unit
BRC1D52
Necessary
accessories
DCS301B51
or
DST301B51,
BRC1D52
If necessary:
DCS302C51
Zone 1
Indoor unit
BRC1D52
Zone 2
COMBINATION WITH
OTHER
TYPES OF
AIR CONDITIONERS
System construction
Indoor unit
DCS302C51
HRV
BRC1D52
HRV
BRC1D52
Air conditioner
BRC1D52
Connecting line
can be extended
up to 50m
Simultaneous operation
of HRVs and air conditioners is possible via
BRC1D52
DCS302C51,
BRC1D52
If necessary:
DCS301B51,
DST301B51
Connection
adapter
(no-voltage Use of the HRV remote
a-contactcontrol enables to change
signal)
settings or operate HRVs
independently
p. 20
o p t i o n s
Options
Air suction/discharge grille (accessory)
Flexible duct
(Accessory)
High efficiency filter
(Accessory)
RA
SA
Round hood
(Field supply)
Branch duct
(Field supply)
Silencer ( Accessory)
SA
Duct
(Field supply)
Thermal insulation material
(Field supply)
Air conditioner
remote control
Description
VAM remote control
Air conditioner remote control
Centralised remote control
Unified on/off control
Schedule timer
PC board adapter
OA
EA
Schedule timer
Reference
FXZQ
KRP1B57*
KRP1B101
*1/*4
FXFQ
KRP1H98*
*2/*3
FXCQ
KRP1B61*
KRP1B96
*2/*3
FXKQ
-
BRC301B61*5
BRC1D52
DCS302C51
DCS301B51
DST301B51
KRP2A61
KRP50-2
BRP4A50
FXMQ
FXSQ
KRP1D61
KRP4A91
*6
FXDQ-N
KRP1B56
KRP1B101
*1/*4
FXHQ
KRP1B3
KRP1C93
*3
FXAQ
KRP4A93
*2/*3
FXLQ/FXNQ
KRP1B61
-
o p t i o n s
1 PC
1.
p. 21
- BRP4A50
When the installation of an electric heater is required in a cold region, this adapter with an
internal timer function eliminates the complicated timer connecting work necessary with
conventional heaters.
INDOOR
RA
OUTDOOR
EA
HRV
SA
BRP4A50
Heater
control kit
(field supply)
OA
Temperature thermostat
(field supply)
(ON when the temperature
is at or below -10C)
p. 22
o p t i o n s
Silencer
Description
High efficiency filter
Replacement for air filter
Description
Silencer
Reference
Nom. piping diameter
VAM150FA
VAM250FA
VAM350FA
YAFM323F15
YAFF323F15
YAFM323F25
YAFF323F25
YAFM323F35
YAFF323F35
VAM500FA
VAM650FA
KDDM24A50
200mm
YAFM323F50
YAFF323F50
VAM1000FA
Description
Silencer
Duct adapter
Reference
Nom. piping diameter
KDDM24A100
YAFM323F100
YAFF323F100
-
VKM50GA(M)
Description
Silencer
Reference
Nom. piping diameter
KAF241G80M
KAF242G80M
VAM800FA
KDDM24A100
200mm
250mm
YAFM323F65
YAFF323F65
VAM1500FA
VAM2000FA
KDDM24A100 x 2
250mm
YAFM323F65 x 2
YAFF323F65 x 2
YAFM323F100 x 2
YAFF323F100 x 2
YDFA25A1
250mm
VKM80GA(M)
VKM100GA(M)
KDDM24B100
250mm
KAF241G100M
KAF242G100M
f e a t u r e s
p. 23
FXMQ-MFV1
Fresh Air Treatment Unit
Features
Combined fresh air treatment
conditioning via a single system.
and
air
Line-up
Air flow rate (m3/h)
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
1.080
1.680
2.100
p. 24
f e a t u r e s
S INGLE S YSTEM
Air conditioning and fresh air treatment can be accomplished via a single system.
Connection Conditions
The following restrictions must be
observed in order to maintain the
indoor units connection to the same
system.
Indoor Unit
Air Conditioning
Indoor Unit
A fresh air treatment unit can also be used exclusively. The connected capacity of the fresh air treatment unit
must be between 50% and 100% of the capacity of the air conditioning outdoor unit.
Connectable outdoor units: VRV and systems
System Example
Check that system connected capacity is within the
appropriate range.
20HP System
20HP System
5HP
Outdoor-Air Processing Unit
5HP
Indoor Unit x3
f e a t u r e s
p. 25
p. 26
s p e c i f i c a t i o n s
Specifications
FXMQ-MFV1
F X M Q 2 0 0 - 2 5 0 M F V 1
Ventilation
Capacity
Casing
Dimensions
Cooling
Heating
Cooling
Heating
Material
Unit
Weight
Heat Exchanger
Unit
Dimensions
Power Input
Fan
Fin
Type
Air Flow Rate
External static pressure
Motor
Piping connections
Liquid (OD)
Gas
Drain
Heat Insulation
Air Filter
Refrigerant control
Temperature control
Safety devices
Safety devices
Power Supply
Current
Voltage range
Frequency
Voltage
Minimum circuit amps (MCA)
Maximum fuse amps (MFA)
Full load amps (FLA)
Minimum
Maximum
kW
kW
kW
kW
Height
Width
Depth
mm
mm
mm
kg
Nr of Rows
Fin Pitch
Face Area
mm
m2
Nr of Stages
Fin type
Cooling
Heating
Standard
Model
Output (high)
Drive
Type
Diameter
Type
Diameter
Diameter
Medium
Medium
m3/min
m3/min
Pa
W
mm
mm
mm
Hz
V
A
A
A
V
V
FXMQ125MFV1
FXMQ200MFV1
FXMQ250MFV1
14.0
8.9
0.359
0.359
Galvanised steel
22.4
13.9
0.548
0.548
Galvanised steel
28.00
17.40
0.638
0.638
Galvanised steel
470
470
744
1380
1100
1100
86
123
3
3
2.00
2.00
0.28
0.65
26
26
Cross fin coil
Cross fin coil
Sirocco fan
Sirocco fan
18.0
28.0
18.0
28.0
185
225
D13/4G2DA1
D13/4G2DA1
380
380
Direct drive
Direct drive
Flare connection
Flare connection
9.5
9.5
Flare connection
Brazing/Brazing connection
15.9
19.1
PS1B
PS1B
Glass fiber
Glass fiber
As option
As option
Electronic expansion valve
Electronic expansion valve
Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating
Fuse
Fuse
Fan motor thermal protector
Fan motor thermal protector
50
50
220-240
220-240
1.90
3.30
15
15
1.50
2.60
-10%
-10%
10%
10%
Notes: Nominal cooling capacities are based on : outdoor temperature : 33CDB, 28CWB (68%RH), discharge set temperature : 18CDB, equivalent piping length 7.5m (horizontal)
Nominal heating capacities are based on : outdoor temperature : 0CDB, -2.9CWB (50%RH), discharge set temperature : 25CDB, equivalent piping length 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method(gravity method) 50% or more.
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA <= 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker
470
1380
1100
123
3
2.00
0.65
26
Cross fin coil
Sirocco fan
35.0
35.0
205
D13/4G2DA1
380
Direct drive
Flare connection
9.5
Brazing/Brazing connection
22.2
PS1B
Glass fiber
As option
Electronic expansion valve
Microprocessor thermostat for cooling and heating
Fuse
Fan motor thermal protector
50
220-240
3.80
15
3.00
-10%
10%
c o n t r o l
s y s t e m s
p. 27
Control Systems
FXMQ-MFV1 can also be
connected to :
As with the VRV III system, a variety of control systems can be deployed,
including remote control from distances of up to 500m.
Note:
- Group control is not possible between this unit and standard type indoor units. Connect remote controllers
to each unit.
- Not all functions are available when using centralised control. Please refer to your local installer for detailed
information.
BRC1D52
9
9
9
9
9
9
C ENTRALISED
DCS302C51
centralised remote control
REMOTE CONTROL
A central control system compatible with the VRVIII System can be installed.
Providing individual control of 64 groups (zones) of indoor units
9 A maximum of 64 groups (128 indoor units, max. 10 outdoor units) can
be controlled
9 A maximum of 128 groups (128 indoor units, max. 10 outdoor units) can
be controlled via 2 centralised remote controls in separate locations
9 Zone control
9 Group control (up and down buttons are added for group selection)
9 Control of HRV air flow direction and air flow rate
9 Expanded timer function
9 Malfunction code display
9 Maximum wiring length of 1,000m (total: 2,000m)
Note:
- The remote control wired to the FXMQ-MFV1 cannot be set as master remote control. Otherwise, when set
to auto, the operation mode will switch according to outdoor air conditions, regardless of indoor
temperature.
- Temperature setting and PPD are not possible, even when Intelligent Touch Controller or Intelligent
Manager are installed.
p. 28
o p t i o n s
DCS301B51
UNIFIED ON/OFF
CONTROL
DST301B51
SCHEDULE
TIMER
Options
FXMQ125MFV1
Description
Operation / Control
Filters
Filter chamber *1
Drain pump kit
Adapter for wiring
Notes : *1 Filter chamber has a suction-type flange. (Main unit does not).
Dimensions and weight of the equipment may vary depending on the options used.
Some options may not be usable due to the equipment installation conditions. Please confirm prior to ordering.
Some options may not be used in combination.
Operating sound may increase somewhat depending on the options used.
FXMQ200MFV1
FXMQ250MFV1
BRC1D52
DCS302C51
DCS301B51
DST301B51
KRP2A61
KRP4A51
KAFJ371L140
KAFJ372L140
KAFJ373L140
KDJ3705L140
KAFJ371L280
KAFJ372L280
KAFJ373L280
KDJ3705L280
KDU30L250VE
KRP1B61
f e a t u r e s
p. 29
VRV+EXV-kit
VRV Air Handling Application
Features
Daikin has introduced a new range of R-410A inverter condensing units to provide ventilation
and air conditioning for air handling installations in medium and large commercial spaces.
This system is unique because it combines the flexibility of Daikin VRV units with Air Handling
Applications.
Because of the simplicity of the system, it is very easy to design the air conditioning system.
1 S YSTEM O VERVIEW
In order to maximise combination potential, Daikin offers different expansion kits and anown
control system.
BRC1D52 is used to set the set joint temperature (connected to the EKEXMCB)
gas pipe
liquid pipe
F1, F2 communication
EXV-kit
(Field
Supply)
p. 30
s p e c i f i c a t i o n s
2 L ARGE R ANGE
2.
OF
EKEXV
EKEXV
EKEXV
EKEXV
EKEXV
EKEXV
EKEXV
EKEXV
50
63
80
100
125
140
200
250
0.76
0.96
1.22
1.53
1.91
2.14
3.06
3.82
0.96
1.22
1.53
1.91
2.14
3.06
3.82
4.78
5.6
7.1
9.0
11.2
14.0
16.0
22.4
22.0
6.2
7.8
9.9
12.3
15.4
17.6
24.6
30.8
Specifications
1 S YSTEM S PECIFICATIONS
1.
RXQ-P(A)
Cooling only
RXQ-P(A)
Capacity range
Capacity
Power input (Nominal)
Dimensions
Weight
Sound Level
Air Flow Rate (nominal at 230V)
Operation Range
Refrigerant
Power Supply
Max n of indoor units to be connected
Piping connections
cooling
cooling
HxWxD
sound power
sound pressure
cooling
cooling
liquid (OD)/gas
cooling
cooling
min~max
HP
kw
kw
mm
kg
dBA
dBA
m/min
CDB
mm
5
5
14.0
3.52
1,680x635x765
157
72
54
95
8
8
22.4
5.56
1,680x930x765
185
78
57
171
10
10
28.0
7.42
1,680x930x765
238
78
58
185
8
9.5 / 15.9
13
9.5 / 19.1
16
9.5 / 22.2
12
12
33.5
9.62
1,680x930x765
238
80
60
196
-5.0~43.0
R-410A
3N~/400V/50Hz
19
12.7 / 22.2
14
14
40.0
12.4
1,680x1,240x765
315
80
60
233
16
16
45.0
14.2
1,680x1,240x765
315
80
60
233
18
18
49.0
16.2
1,680x1,240x765
323
83
63
239
23
12.7 / 28.6
26
12.7 / 28.6
29
15.9 / 28.6
s p e c i f i c a t i o n s
p. 31
2 C OMBINATION TABLE
Combination table
CONTROL BOX
CONTROL Z
EKEXMCB
x
x
x
x
x
x
x
Outdoor unit
RXQ5P
RXQ8P
RXQ10P
RXQ12P
RXQ14PA
RXQ16PA
RXQ18PA
3ph
CLASS 50
EKEXV50
x
x
x
x
x
x
x
CLASS 63
EKEXV63
x
x
x
x
x
x
x
CLASS 250
EKEXV250
x
x
x
x
x
x
x
X = Quantity determined by connection ratio or maximum number of indoor units (the EKEVX-kit is considered as one of the indoor units
colour
unit
Weight
Piping Connection
Sound Pressure Level
Operation Range
unit
liquid
nominal
cooling
height
width
depth
min
max
Ivory White
401
215
78
2.9
9.52
45 (max. at 10cm from motor)
-5.0
46.0
mm
mm
mm
kg
mm
dB(A)
CDB
CDB
4 C ONTROL B OX
Control box
Casing
Dimensions
Control box
colour
unit
Weight
Operation Range
unit
cooling
Power Supply
name
phase
frequency
voltage
voltage range
height
width
depth
min
max
mm
mm
mm
kg
CDB
CDB
minimum
maximum
Hz
V
V
V
White grey
132
400
200
3.5
-5.0
46.0
V3
1
50
230
-10%
10%
Wiring connections
quantity
remark
quantity
remark
quantity
remark
quantity
remark
quantity
remark
quantity
Remark
Quantity
Remark
Remark
3
Earth wire included
2
F1-F2
2
P1,P2
6
Y1~Y6
2
R1,R2
2
R3,R4
2
R5,R6
T1,T2
Bottom
p. 32
Control Systems
1.
1 C ONTROL
OF
A IR T EMPERATURE
D AIKIN C ONTROL
ON / OFF
KRP4A51
Ts
Daikin
control box:
EKEXMCB
VIA
Te
AHU
TR
BRC1D52
Td
Room
Options
EKEXMCB
Wired remote control
Wiring adapter for electrical appendices
Valve kits
BRC1D52
KRP4A51
EKEXV 50, 63, 80, 100, 125, 140, 200, 250
Caution: Only use this system in combination with a field supplied air handling unit. Do not connect this system to other indoor units.
n o t e s
Notes
p. 33
p. 34