BC CONTROLLER (WITH R2-SERIES, H2i R2-SERIES AND WR2-SERIES)

CMB-P-NU-G, NU-GA, NU-HA, NU-GB, NU-HB


1. SPECIFICATIONS.........................................................................................................................................................BC-2
2. EXTERNAL DIMENSIONS..........................................................................................................................................BC-12
3. ELECTRICAL WIRING DIAGRAMS............................................................................................................................BC-17
4. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS..........................................................................BC-27
CMB-P105, 1016NU-G1 (Single).............................................................................................................................BC-27
CMB-P1013 (Main)...................................................................................................................................................BC-28
CMB-P104, P108NU-GB1 (Sub)...............................................................................................................................BC-28
CMB-P108, P1010, P1016NU-HA1 (Main)...............................................................................................................BC-29
CMB-P1016NU-HB1 (Sub).......................................................................................................................................BC-29
5. SOUND PRESSURE LEVELS....................................................................................................................................BC-30
5-1. BC Controller Steady State Sound....................................................................................................................BC-30
5-2. BC Controller Peak Sound.................................................................................................................................BC-31
6. OPTIONAL PARTS......................................................................................................................................................BC-32
6-1. BV-Series Ball Valves.........................................................................................................................................BC-32
6-2. BV-Series Ball Valve Insulation..........................................................................................................................BC-32
6-3. CMY-R160-J1 Joint Adapter Kit for BC Controllers............................................................................................BC-33

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-1

1. SPECIFICATIONS
Model name

CMB-P105NU-G1

Number of branch

5
1-phase 208/230V

Power source
Power input
(208/230V)

Cooling

Current
(208/230V)

Cooling

Heating

Heating

kW

60Hz

0.073

0.033

0.35 / 0.32

0.16 / 0.14

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)

External finish

PURY-P72/96/120TLMU-A(-BS), PURY-P72/96/120YLMU-A(-BS),
PURY-HP72/96TKMU-A, PURY-HP72/96YKMU-A,
PQRY-P72/96/120THMU-A, PQRY-P72/96/120YHMU-A

Connectable outdoor unit

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Connectable outdoor unit


capacity

Refrigerant
piping
diameter

Model P54 or smaller


(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55.)
(Use the reducer [standard accessory] when the indoor unit Model 18 or smaller is connected.)
11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)
To outdoor unit
High press. pipe

Low press. pipe

to P72
in. (mm) O.D.

5/8 (15.88)
Brazed

3/4 (19.05)
Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05)
Brazed

7/8 (22.2)
Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05)
Brazed

1-1/8 (28.58)
Brazed
To indoor unit

Field drain pipe size


Net weight
Accessories
Note:

BC-2

Liquid pipe

Gas pipe

in. (mm) O.D.

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used.)

5/8 (15.88) Brazed


(1/2 (12.7) with attached reducer used,
3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)

in. (mm) O.D.

1-1/4 (32)

1-1/4 (32)

lbs (kg)

64 (29)

72 (32)

Drain Connection pipe (with flexible hose and insulation)


Reducer

Drain Connection pipe (with flexible hose and insulation)


Reducer

1. Works not included:


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this
specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low
background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
4. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

1. SPECIFICATIONS
Model name

CMB-P106NU-G1

Number of branch

CMB-P108NU-G1

8
1-phase 208/230V

Power source
Power input
(208/230V)

Cooling

Current
(208/230V)

Cooling

Heating

Heating

kW

60Hz

60Hz

0.086

0.112

0.040

0.053

0.41/0.37

0.54/0.49

0.19/0.17

0.25/0.23

Galvanized steel plate


(Lower part drain pan: Pre-coated galvanized sheets + powder coating)

External finish

PURY-P72/96/120TLMU-A(-BS), PURY-P72/96/120YLMU-A(-BS),
PURY-HP72/96TKMU-A, PURY-HP72/96YKMU-A,
PQRY-P72/96/120THMU-A, PQRY-P72/96/120YHMU-A
PQRY-P72/96/120ZKMU-A

Connectable outdoor unit

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Connectable outdoor unit


capacity

Refrigerant
piping
diameter

Model P54 or smaller


(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.)
11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)
To outdoor unit
High press. pipe

Low press. pipe

to P72
in. (mm) O.D.

5/8 (15.88)
Brazed

3/4 (19.05)
Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05)
Brazed

7/8 (22.2)
Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05)
Brazed

1-1/8 (28.58)
Brazed
To indoor unit

Field drain pipe size


Net weight

Gas pipe

in. (mm) O.D.

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used.)

5/8 (15.88) Brazed


(1/2 (12.7) with attached reducer used,
3/4 (19.05) and 7/8 (22.2) with optional joint pipe
used.)

in. (mm) O.D.

1-1/4 (32)

1-1/4 (32)

lbs (kg)

76 (34)
Drain Connection pipe (with flexible hose and
insulation)
Reducer

Accessories

Note:

Liquid pipe

84 (38)
Drain Connection pipe (with flexible hose and
insulation)
Reducer

1. Works not included:


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this
specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low
background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
4. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-3

1. SPECIFICATIONS
Model name

CMB-P1010NU-G1

Number of branch

CMB-P1013NU-G1

10

13
1-phase 208/230V

Power source
Power input
(208/230V)

Cooling

Current
(208/230V)

Cooling

Heating

Heating

kW

60Hz

60Hz

0.138

0.178

0.066

0.086

0.66/0.60

0.86/0.77

0.32/0.29

0.41/0.37

Galvanized steel plate


(Lower part drain pan :Pre-coated galvanized sheets + powder coating)

External finish

PURY-P72/96/120TLMU-A(-BS), PURY-P72/96/120YLMU-A(-BS),
PURY-HP72/96TKMU-A, PURY-HP72/96YKMU-A,
PQRY-P72/96/120THMU-A, PQRY-P72/96/120YHMU-A

Connectable outdoor unit

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Connectable outdoor unit


capacity

Refrigerant
piping
diameter

Model P54 or smaller


(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55.)
(Use the reducer [standard accessory] when the indoor unit Model 18 or smaller is connected.)
11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)
To outdoor unit
High press. pipe

Low press. pipe

to P72
in. (mm) O.D.

5/8 (15.88)
Brazed

3/4 (19.05)
Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05)
Brazed

7/8 (22.2)
Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05)
Brazed

1-1/8 (28.58)
Brazed
To indoor unit

Field drain pipe size


Net weight
Accessories
Note:

BC-4

Liquid pipe

Gas pipe

in. (mm) O.D.

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used.)

5/8 (15.88) Brazed


(1/2 (12.7) with attached reducer used,
3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)

in. (mm) O.D.

1-1/4 (32)

1-1/4 (32)

lbs (kg)

94 (42)

126 (57)

Drain Connection pipe (with flexible hose and insulation)


Reducer

Drain Connection pipe (with flexible hose and insulation)


Reducer

1. Works not included:


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this
specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low
background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
4. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

1. SPECIFICATIONS
Model name

CMB-P1016NU-G1

Number of branch

16
1-phase 208/230V

Power source
Power input

Cooling

(208/230V)

Heating

Current

Cooling

(208/230V)

Heating

kW

60Hz

0.217

0.106

1.04/0.94

0.51/0.46

Galvanized steel plate


(Lower part drain pan: Pre-coated galvanized sheets + powder coating)

External finish

PURY-P72/96/120TLMU-A(-BS), PURY-P72/96/120YLMU-A(-BS),
PURY-HP72/96TKMU-A, PURY-HP72/96YKMU-A,
PQRY-P72/96/120THMU-A, PQRY-P72/96/120YHMU-A

Connectable outdoor unit

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Connectable outdoor unit


capacity

Refrigerant
piping
diameter

Model P54 or smaller


(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.)
11-3/16 x 43-1/4 x 17-1/32 (284 x 1,098 x 432)
To outdoor unit
High press. pipe

Low press. pipe

to P72
in. (mm) O.D.

5/8 (15.88)
Brazed

3/4 (19.05)
Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05)
Brazed

7/8 (22.2)
Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05)
Brazed

1-1/8 (28.58)
Brazed
To indoor unit

in. (mm) O.D.


Field drain pipe size

in. (mm) O.D.

Net weight

lbs (kg)

Gas pipe

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used.)

5/8 (15.88) Brazed


(1/2 (12.7) with attached reducer used,
3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)
1-1/4 (32)
138 (62)

Drain Connection pipe (with flexible hose and insulation)


Reducer

Accessories

Note:

Liquid pipe

1. Works not included:


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this
specifications.
2. The equipment is for R410A refrigerant.
3. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low
background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
4. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-5

1. SPECIFICATIONS
Model name

CMB-P1013NU-GA1

Number of branch

13
1-phase 208/230V

Power source
Power input
(208/230V)
Current
(208/230V)

Cooling

kW

Heating
Cooling

Heating

0.086

0.86/0.77

0.41/0.37

Galvanized steel plate


(Lower part drain pan: Pre-coated galvanized sheets + powder coating)

External finish

PURY-P72/96/120/144/168/192/216/240T(S)LMU-A(-BS), PURY-P72/96/120/144/168/192/216/240Y(S)LMU-A(-BS),
PURY-HP72/96/144/192T(S)KMU-A, PURY-HP72/96/144/192Y(S)KMU-A,
PQRY-P72/96/120/144/168/192/216/240T(S)HMU-A, PQRY-P72/96/120/144/168/192/216/240Y(S)HMU-A

Connectable outdoor unit

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Refrigerant
piping
diameter

60Hz
0.178

Model P54 or smaller


(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.)
11-13/32 x 43-23/32 x 20-1/2 (289 x 1,110 x 520)
To outdoor unit (PURY)

Connectable outdoor unit


capacity

High press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

P193 to P216 in. (mm) O.D.

1-1/8 (28.58) Brazed

P217 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed


To heat source unit (PQRY)

Connectable heat source unit


capacity

High press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

P193 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed


To indoor unit
Liquid pipe

in. (mm) O.D.

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used.)
To other BC controller

Total indoor unit capacity


connected to this Sub BC
controller

High press. pipe


Liquid pipe

Field drain pipe size


Net weight
Accessories
Note:

BC-6

to P72
in. (mm) O.D.

5/8 (15.88) Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05) Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05) Brazed

in. (mm) O.D.

1-1/4 (32)

3/8 (9.52) Brazed

3/8 (9.52) Brazed

1/2 (12.7) Brazed

lbs (kg)

148 (67)
Drain Connection pipe (with flexible hose and insulation)
Reducer

1. Works not included:


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2. The equipment is for R410A refrigerant.
3. P204 to P240 type outdoor unit side high press. pipe can changed to "1-1/8 (28.58) Brazed".
4. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with low background noise,
position the BC CONTROLLER at least 5m away from any indoor units.)
5. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

1. SPECIFICATIONS
Model name

CMB-P108NU-HA1

Number of branch

8
1-phase 208/230 V 60Hz

Power source
Power input
(208/230V)
Current
(208/230V)

Cooling

kW

Heating
Cooling

Heating

External finish

0.076/0.098

0.074/0.086

0.37/0.43

Galvanized steel plate (Lower part drain pan: Pre-coated galvanized sheets + powder coating)
PURY-P-T(S)LMU-A(-BS), PURY-P7-Y(S)LMU-A(-BS), PURY-HP-T(S)KMU-A, PURY-HP-Y(S)KMU-A,
PQRY-P-T(S)HMU-A, PQRY-P-Y(S)HMU-A

Connectable outdoor unit

Connectable BC controller

Main BC

Sub BC

CMB-P104/108NU-GB1, CMB-P1016NU-HB1

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Refrigerant
piping
diameter

60Hz
0.152/0.196

Model P54 or smaller


(Use optional joint pipe combining 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.)
11-7/16 x 43-3/4 x 20-1/2 (289 x 1,110 x 520)
To outdoor unit (PURY)

Connectable outdoor unit


capacity

High press. pipe

Low press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

3/4 (19.05) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

7/8 (22.2) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed

P193 to P216 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-1/8 (28.58) Brazed

P217 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-3/8 (34.93) Brazed

P241 to P288 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-3/8 (34.93) Brazed

P289 to P336 in. (mm) O.D.

1-1/8 (28.58) Brazed

Connectable heat source unit


capacity

1-5/8 (41.28) Brazed


To heat source unit (PQRY)

High press. pipe

Low press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

3/4 (19.05) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

7/8 (22.2) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed

P193 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-1/8 (28.58) Brazed


To indoor unit

in. (mm) O.D.

Liquid pipe

Gas pipe

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used,
1/2 (12.7) with optional joint pipe used.)

5/8 (15.88) Brazed


(1/2 (12.7) with attached reducer used,
3/4 (19.05), 7/8 (22.2) with optional joint pipe used.)
To other BC controller

Total indoor unit capacity


connected to this Sub BC
controller

High press. pipe

Low press. pipe


Liquid pipe

5/8 (15.88) Brazed

to P72
in. (mm) O.D.

3/4 (19.05) Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed


1/2 (12.7) Brazed

7/8 (22.2) Brazed

P127 to P144
in. (mm) O.D.

1-1/8 (28.58) Brazed


1/2 (12.7) Brazed

7/8 (22.2) Brazed

P145 to P168
in. (mm) O.D.

1-1/8 (28.58) Brazed


5/8 (15.88) Brazed

in. (mm) O.D.

Net weight

1-1/4 (32)
lbs (kg)

124 (56)
Drain Connection pipe (with flexible hose and insulation)
Reducer

Accessories

Note:

7/8 (22.2) Brazed


3/8 (9.52) Brazed

P109 to P126
in. (mm) O.D.

Field drain pipe size

3/4 (19.05) Brazed


3/8 (9.52) Brazed

1. Use this product when connecting outdoor unit P264 or more.


2. Works not included: Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this
specifications.
3. The equipment is for R410A refrigerant.
4. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
5. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-7

1. SPECIFICATIONS
Model name

CMB-P1010NU-HA1

Number of branch

10
1-phase 208/230 V 60Hz

Power source
Power input
(208/230V)

Cooling

Current
(208/230V)

Cooling

Heating

Heating

kW

External finish

60Hz

0.183/0.236

0.092/0.118

0.88/1.03

0.45/0.52

Galvanized steel plate (Lower part drain pan: Pre-coated galvanized sheets + powder coating)
PURY-P-T(S)LMU-A(-BS), PURY-P-Y(S)LMU-A(-BS),
PURY-HP-T(S)KMU-A, PURY-HP-Y(S)KMU-A,
PQRY-P-T(S)HMU-A, PQRY-P-Y(S)HMU-A

Connectable outdoor unit

Connectable BC controller

Main BC

Sub BC

CMB-P104/108NU-GB1, CMB-P1016NU-HB1

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Refrigerant
piping
diameter

Connectable outdoor unit


capacity

Model P54 or smaller


(Use optional joint pipe combining 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.)
11-7/16 x 43-3/4 x 20-1/2 (289 x 1,110 x 520)
To outdoor unit (PURY)
High press. pipe

Low press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

3/4 (19.05) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

7/8 (22.2) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed

P193 to P216 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-1/8 (28.58) Brazed

P217 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-3/8 (34.93) Brazed

P241 to P288 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-3/8 (34.93) Brazed

P289 to P336 in. (mm) O.D.

1-1/8 (28.58) Brazed

Connectable heat source unit


capacity

1-5/8 (41.28) Brazed


To heat source unit (PQRY)

High press. pipe

Low press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

3/4 (19.05) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

7/8 (22.2) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed

P193 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-1/8 (28.58) Brazed


To indoor unit

in. (mm) O.D.

Total indoor unit capacity


connected to this Sub BC
controller

Liquid pipe

Gas pipe

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used,
1/2 (12.7) with optional joint pipe used.)

5/8 (15.88) Brazed


(1/2 (12.7) with attached reducer used,
3/4 (19.05), 7/8 (22.2) with optional joint pipe used.)
To other BC controller

High press. pipe

Low press. pipe


Liquid pipe

Field drain pipe


size
Net weight
Accessories
Note:

BC-8

to P72
in. (mm) O.D.

5/8 (15.88) Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05) Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05) Brazed

P127 to P144
in. (mm) O.D.

7/8 (22.2) Brazed

P145 to P168
in. (mm) O.D.

7/8 (22.2) Brazed

3/4 (19.05) Brazed


3/8 (9.52) Brazed
7/8 (22.2) Brazed
3/8 (9.52) Brazed
1-1/8 (28.58) Brazed
1/2 (12.7) Brazed
1-1/8 (28.58) Brazed
1/2 (12.7) Brazed
1-1/8 (28.58) Brazed
5/8 (15.88) Brazed

in. (mm) O.D.

1-1/4 (32)
lbs (kg)

131 (59)
Drain Connection pipe (with flexible hose and insulation)
Reducer

1. Use this product when connecting outdoor unit P264 or more.


2. Works not included: Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
3. The equipment is for R410A refrigerant.
4. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
5. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

1. SPECIFICATIONS
Model name

CMB-P1016NU-HA1

Number of branch

16
1-phase 208/230 V 60Hz

Power source
Power input
(208/230V)

Cooling

Current
(208/230V)

Cooling

Heating

Heating

kW

External finish

60Hz

0.274/0.353

0.137/0.177

1.32/1.54

0.66/0.77

Galvanized steel plate (Lower part drain pan :Pre-coated galvanized sheets + powder coating)
PURY-P-T(S)LMU-A(-BS),PURY-P-Y(S)LMU-A(-BS),
PURY-HP-T(S)KMU-A, PURY-HP-Y(S)KMU-A,
PQRY-P-T(S)HMU-A, PQRY-P-Y(S)HMU-A

Connectable outdoor unit

Connectable BC controller

Main BC

Sub BC

CMB-P104/108NU-GB1, CMB-P1016NU-HB1

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Refrigerant
piping
diameter

Connectable outdoor unit


capacity

Model P54 or smaller


(Use optional joint pipe combining 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.)
11-7/16 x 43-3/4 x 20-1/2 (289 x 1,110 x 520)
To outdoor unit (PURY)
High press. pipe

Low press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

3/4 (19.05) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

7/8 (22.2) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed

P193 to P216 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-1/8 (28.58) Brazed

P217 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-3/8 (34.93) Brazed

P241 to P288 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-3/8 (34.93) Brazed

P289 to P336 in. (mm) O.D.

1-1/8 (28.58) Brazed

Connectable heat source unit


capacity

1-5/8 (41.28) Brazed


To heat source unit (PQRY)

High press. pipe

Low press. pipe

to P72 in. (mm) O.D.

5/8 (15.88) Brazed

3/4 (19.05) Brazed

P73 to P108 in. (mm) O.D.

3/4 (19.05) Brazed

7/8 (22.2) Brazed

P109 to P126 in. (mm) O.D.

3/4 (19.05) Brazed

1-1/8 (28.58) Brazed

P127 to P192 in. (mm) O.D.

7/8 (22.2) Brazed

1-1/8 (28.58) Brazed

P193 to P240 in. (mm) O.D.

1-1/8 (28.58) Brazed

1-1/8 (28.58) Brazed


To indoor unit

in. (mm) O.D.

Total indoor unit capacity


connected to this Sub BC
controller

Field drain pipe


size
Net weight

Gas pipe
5/8 (15.88) Brazed
(1/2 (12.7) with attached reducer used,
3/4 (19.05), 7/8 (22.2) with optional joint pipe used.)
To other BC controller

High press. pipe

Low press. pipe


Liquid pipe

to P72
in. (mm) O.D.

5/8 (15.88) Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05) Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05) Brazed

P127 to P144
in. (mm) O.D.

7/8 (22.2) Brazed

P145 to P168
in. (mm) O.D.

7/8 (22.2) Brazed

3/4 (19.05) Brazed


3/8 (9.52) Brazed
7/8 (22.2) Brazed
3/8 (9.52) Brazed
1-1/8 (28.58) Brazed
1/2 (12.7) Brazed
1-1/8 (28.58) Brazed
1/2 (12.7) Brazed
1-1/8 (28.58) Brazed
5/8 (15.88) Brazed

in. (mm) O.D.

1-1/4 (32)
lbs (kg)

172 (78)
Drain Connection pipe (with flexible hose and insulation)
Reducer

Accessories

Note:

Liquid pipe
3/8 (9.52) Brazed
(1/4 (6.35) with attached reducer used,
1/2 (12.7) with optional joint pipe used.)

1. Use this product when connecting outdoor unit P264 or more.


2. Works not included: Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
3. The equipment is for R410A refrigerant.
4. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
5. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-9

1. SPECIFICATIONS
Model name

CMB-P104NU-GB1

Number of branch

CMB-P108NU-GB1

8
1-phase 208/230V

Power source
Power input
(208/230V)

Cooling

Current
(208/230V)

Cooling

Heating

Heating

kW

External finish

60Hz

60Hz

0.053

0.106

0.027

0.053

0.25/0.23

0.51/0.46

0.13/0.12

0.25/0.23

Galvanized steel plate (Lower part drain pan :Pre-coated galvanized sheets + powder coating)
Model P54 or smaller
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.)

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

11-3/16 x 25-17/32 x 17-1/32 (284 x 648 x 432)


To indoor unit

Refrigerant
piping
diameter
in. (mm) O.D.

Liquid pipe

Gas pipe

3/8 (9.52) Brazed


(1/4 (6.35) with attached reducer used.)

5/8 (15.88) Brazed


(1/2 (12.7) with attached reducer used,
3/4 (19.05) and 7/8 (22.2) with optional joint pipe used.)

To other BC controller

Total indoor unit capacity


connected to this Sub BC
controller

High press. pipe

Low press. pipe


Liquid pipe

Field drain pipe


size
Net weight
Accessories

Note:

BC-10

to P72
in. (mm) O.D.

5/8 (15.88) Brazed


3/8 (9.52) Brazed

3/4 (19.05) Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05) Brazed


3/8 (9.52) Brazed

7/8 (22.2) Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05) Brazed


1/2 (12.7) Brazed

1-1/8 (28.58) Brazed

in. (mm) O.D.

1-1/4 (32)

1-1/4 (32)

lbs (kg)

62 (28)

82 (37)

Drain Connection pipe (with flexible hose and insulation)


Reducer

Drain Connection pipe (with flexible hose and insulation)


Reducer

1. Works not included:


Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this
specifications.
2. The equipment is for R410A refrigerant.
3. To use the Sub BC controller, the Main BC controller is necessary to be connected with.
4. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.(For use in quiet environments with low
background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
5. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

1. SPECIFICATIONS
Model name

CMB-P1016NU-HB1

Number of branch

16
1-phase 208/230 V 60Hz

Power source
Power input
(208/230V)

Cooling

Current
(208/230V)

Cooling

kW

Heating

Heating

External finish

0.157

1.17/1.37

0.59/0.69

Main BC

CMB-P108/1010/1013/1016NU-GA1

Sub BC

CMB-P104/108NU-GB1, CMB-P1016NU-HB1

Indoor unit capacity


connectable to 1 branch

kW

External dimension H x W x D

in. (mm)

Low press. pipe

To indoor unit

in. (mm) O.D.

Liquid pipe

Gas pipe

3/8 (9.52) Brazed

5/8 (15.88) Brazed

(1/4 (6.35)with attached reducer used,


1/2 (12.7)with optional joint pipe used.)

(1/2 (12.7)with attached reducer used, 3/4 (19.05)


with optional joint pipe used.)

To other BC controller

Total indoor unit capacity


connected to this Sub BC
controller

High press. pipe

Low press. pipe


Liquid pipe

to P72
in. (mm) O.D.

5/8 (15.88) Brazed


3/8 (9.52) Brazed

3/4 (19.05) Brazed

P73 to P108
in. (mm) O.D.

3/4 (19.05) Brazed


3/8 (9.52) Brazed

7/8 (22.2) Brazed

P109 to P126
in. (mm) O.D.

3/4 (19.05) Brazed


1/2 (12.7) Brazed

1-1/8 (28.58) Brazed

P127 to P144
in. (mm) O.D.

7/8 (22.2) Brazed


1/2 (12.7) Brazed

1-1/8 (28.58) Brazed

P145 to P168
in. (mm) O.D.

7/8 (22.2) Brazed


5/8 (15.88) Brazed

1-1/8 (28.58) Brazed

in. (mm) O.D.

Net weight

11-3/16 x 43-1/4 x 17-1/32 (284 x 1098 x 432)

High press. pipe

in. (mm) O.D.

Field drain pipe size

Model P54 or smaller


(Use optional joint pipe combining 2 branches when the total unit capacity exceeds P55.)
(Use the reducer (standard accessory) when the indoor unit Model 18 or smaller is connected.

To outdoor unit

Connectable outdoor unit


capacity

1-1/4 (32mm)
lbs (kg)

136 (61)
Drain Connection pipe (with flexible hose and insulation)
Reducer

Accessories

Note:

Galvanized steel plate (Lower part drain pan: Pre-coated galvanized sheets + powder coating)

Connectable BC controller

Refrigerant
piping
diameter

60Hz
0.314

1. Works not included:


Installation/foundation work, electrical connection work, duct work, duct work, insulation work, power source switch, and other items are not specified
in this specifications.
2. The equipment is for R410A refrigerant.
3. For sub BC controller CMB-P1016NU-HB1 the connectable indoor unit capacities may sum to equal that or a P126 unit or less. However, if two sub
controllers are used
4. Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors. (For use in quiet environments with
low background noise, position the BC CONTROLLER at least 5m away from any indoor units.)
5. The data presented is based on a specific combination.

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-11

80

130

23 (29/32)

(5-1/8) (4-1/16)

(1-1/4)

31

:19.05(3/4)<Brazed>(use attachment pipe)


P72
P96,P108 :22.2(7/8)<Brazed>
:28.58(1-1/8)<Brazed>(use attachment pipe)
P126

90

46

76
(3)

200
(7-7/8)

(3-9/16) (1-13/16)

60 (2-3/8)

60 (2-3/8)

P72
:15.88(5/8)<Brazed>(use attachment pipe)
P96~P126 :19.05(3/4)<Brazed>
Y

248

Connection pipe of outdoor unit(Low pressure)

(5-1/8)

Detail of Y section

Connection pipe of outdoor unit(High pressure)

Detail of X section

58 (2-5/16)

Drain pipe
O.D.32(1-1/4")

(3-5/32)

181

130

103
130

(7-5/32)

(5-1/8)

14

27 (1-3/32)

10

60(2-3/8)C=D

60(2-3/8)C=D

11

(Lifting bolt pitch)

12

13

14

15

Control box

16

Indoor unit model (Note 4)


P18 or less :12.7(1/2)<Brazed>
P18 over :15.88(5/8)<Brazed>

Connection pipe of
indoor unit(Gas)

(200) (7-7/8)

A
B
CMB-P104NU-G1
CMB-P105NU-G1
648
702
CMB-P106NU-G1 (25-17/32) (27-21/32)
CMB-P108NU-G1
CMB-P1010NU-G1
CMB-P1013NU-G1 1098
1152
CMB-P1016NU-G1 (43-1/4) (45-3/8)

Connection pipe of
indoor unit(Liquid)
Indoor unit model (Note 4)
P18 or less :6.35(1/4)<Brazed>
P18 over :9.52(3/8)<Brazed>

Service
space

Access
door
450
(17-23/32)

C
3
4
5
7
9
12
15

(Note 2)

D
180(7-3/32)
240(9-15/32)
300(11-13/16)
420(16-9/16)
540(21-9/32)
720(28-3/8)
900(35-7/16)

(7-7/8)
200

<Accessories>
Note1.Suspension bolt(10),washer(M10),and nut(M10)
prepare in the field.
Refrigerant<Low pressure> conn.pipe2pcs.
Refrigerant<High pressure> conn.pipe1pc.
2.Take notice of service space as follows.
Cutting point
(Please give attention not to occupy service
Drain hose I.D.32(1-1/4")1pc.
(Indoor unit Model:P18 or less)
space by letting ducts and pipes through.)
Hose band1pc.
3.Install this product in a location where noise (refrigerant noise)
Tie band1pc.
emitted by the unit will not disturb the neighbors.
(For use in quiet enviroments with low background noise,position
the BC CONTROLLER at least 5m away from any indoor units.)
Detail of Z section
4.Refer to the Installation Manual for refrigerant piping diameter size
when connecting plural indoor units with 1 branch.

298 (1-3/4)

Cutting point

(Indoor unit Model:P18 over)

(Lifting bolt pitch)

12 (1/2)
255 (10-1/16)

70
362

30 (1-3/16)
(9-25/32)

284 (11-3/16)

(2-25/32)
(14-9/32)

(9/16)

128

250

Drain hose I.D.32(1-1/4")


(Accessory)

(5-1/16)

(700)(27-9/16)

BC-12
(9-27/32)

Band(Accessory)

2. EXTERNAL DIMENSIONS
CMB-P105, 106, 108, 1010, 1013, 1016NU-G1
Unit: mm (in.)

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

130

(3-5/32)

(9-31/32)

23 (29/32)

CMB-P108NU-GA1
CMB-P1010NU-GA1
CMB-P1013NU-GA1
CMB-P1016NU-GA1

A
7
9
12
15

B
420(16-9/16)
540(21-9/32)
720(28-3/8)
900(35-7/16)

12 (1/2)

90

46

76
(3)

200

(3-9/16) (1-13/16)

(7-7/8)

27 (1-3/32)

31

P126~P234:28.58(1-1/8)<Brazed>

(5-1/8)

60 (2-3/8)

60 (2-3/8)

10

60(2-3/8)A=B

60(2-3/8)A=B

11

1164 (45-27/32)
(Lifting bolt pitch)

1110 (43-23/32)

Cutting point

12

13

14

15

Control box

16

Indoor unit model (Note 5)


P18 or less :12.7(1/2)<Brazed>
P18 over :15.88(5/8)<Brazed>

Connection pipe of
indoor unit(Gas)

Connection pipe of
indoor unit(Liquid)
Indoor unit model (Note 5)
P18 or less :6.35(1/4)<Brazed>
P18 over :9.52(3/8)<Brazed>
90 (3-9/16)

388 (15-9/32)
(Lifting bolt pitch)

(1-1/4)

80

253

130

Connection pipe of outdoor unit


(Low pressure)

(5-1/8)

103
130

70
450 (17-23/32)

Drain pipe
O.D.32(1-1/4")

(5-1/8) (4-1/16)

(25-17/32)

(2-25/32)

268 (10-9/16)

Detail of X section

30 (1-3/16)

74 (2-5/16)

210 (8-9/32)

128

Access
door
450
(17-23/32)

(7-7/8) (7-7/8)
200 200 (Note 2,3)

Total capacity of indoor unit


at SUB BC CONTROLLER
P72 or less :19.05(3/4)<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
P73~P108 :22.2(7/8)<Brazed>
P108 over :28.58(1-1/8)<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)

Connection pipe of
SUB BC CONTROLLER
(Low pressure)

Total capacity of indoor unit


at SUB BC CONTROLLER
P108 or less :9.52(3/8)<Brazed>
P108 over
:12.7(1/2)<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)

(200) (7-7/8)

Service
space

74 (2-15/16)

66 (2-5/8)

(5-1/16)

:19.05(3/4)<Brazed>

Connection pipe of
SUB BC CONTROLLER
(Liquid)

P72 over

<Accessories>
Note1.Suspension bolt(10),washer(M10),and nut(M10)
Refrigerant<Low pressure> conn. pipe1pc.
prepare in the field.
Refrigerant<High pressure> conn. pipe2pcs.
2.Take notice of service space as follows.
(Indoor unit Model:P18 over)
Drain hose I.D.32(1-1/4")1pc.
(Please give attention not to occupy service
Hose band1pc.
space by letting ducts and pipes through.)
Cutting point
3.Please take service space for connection pipe of SUB BC CONTROLLER. Tie band1pc.
(Indoor unit Model:P18 or less)
4.Install this product in a location where noise (refrigerant noise)
emitted by the unit will not disturb the neighbors.
14
(For use in quiet enviroments with low background noise,position
(9/16)
the BC CONTROLLER at least 5m away from any indoor units.)
Connection pipe of
Detail of Y section
Detail of Z section
SUB BC CONTROLLER
5.Refer to the Installation Manual for refrigerant piping diameter size
(High pressure)
Connection pipe of outdoor unit(High pressure)
when connecting plural indoor units with 1 branch.
Total capacity of indoor unit
P126:19.05(3/4)<Brazed>(use attachment pipe)
at SUB BC CONTROLLER
P72 or less :15.88(5/8)<Brazed>
P144~P192:22.2(7/8)<Brazed>
(use attachment pipe of
P204~P234:28.58(1-1/8)<Brazed>(use attachment pipe)
SUB BC CONTROLLER)

268 (9-25/32)

128

103

(4-1/16)

Drain hose I.D.32(1-1/4")


(Accessory)

289 (11-13/32)

BC Controllers (August 2015)


260 (10-1/4)

(700) (27-9/16)

2015 Mitsubishi Electric US, Inc.


250
(9-27/32)

Band(Accessory)

2. EXTERNAL DIMENSIONS
CMB-P1013NU-GA1
Unit: mm (in.)

BC-13

(3-5/32)

(1-1/4)

31

80

253

Detail of Y section

23 (29/32)

A
7
9
15

200
(7-7/8)

(3)

76

60 (2-3/8)

60 (2-3/8)

10

60(2-3/8)A=B

60(2-3/8)A=B

11

(Lifting bolt pitch)

1164 (45-27/32)

1110 (43-23/32)

Detail of Z section

12

13

14

15

Control box

(Indoor unit Model:P18 or less)

Cutting point

(Indoor unit Model:P18 over)

16

Indoor unit model (Note 6)


P18 or less :12.7<Brazed>
P18 over :15.88<Brazed>

Connection pipe of
indoor unit(Gas)

Indoor unit model (Note 6)


P18 or less :6.35<Brazed>
P18 over :9.52<Brazed>
90 (3-9/16)

Connection pipe of
indoor unit(Liquid)

(7-7/8) (7-7/8)
200 200 (Note 2,3)

Total capacity of indoor unit


at SUB BC CONTROLLER
P72 or less :19.05(3/4)<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
P73~P108 :22.2(7/8)<Brazed>
P108 over :28.58(1-1/8)<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)

Connection pipe of
SUB BC CONTROLLER
(Low pressure)

Total capacity of indoor unit


at SUB BC CONTROLLER
P108 or less :9.52(3/8)<Brazed>
P109~P144 :12.7(1/2)<Brazed>
(use attachment pipe of
SUB BC CONTROLLER)
P144 over :15.88(5/8)<Brazed>
(use attachment pipe of
JOINT<option>)

Access
door
450
(17-23/32)

(200) (7-7/8)

Service
space

74 (2-15/16)

66 (2-5/8)

(5-1/16)

128

Connection pipe of
SUB BC CONTROLLER
(Liquid)

P126 over :22.2(7/8)<Brazed>


(use attachment pipe of
JOINT<option>)

CMB-P108, 1010, 1016NU-HA1

B
420(16-9/16)
540(21-9/32)
900(35-7/16)

46

(2-9/16) (1-13/16)

90

P264~P336:28.58(1-1/8)<Brazed>

P264~P336:34.93(1-3/8)<Brazed>

CMB-P108NU-HA1
CMB-P1010NU-HA1
CMB-P1016NU-HA1

14
(9/16)

Connection pipe of outdoor unit(Low pressure)

130

(5-1/8)

260 (10-1/4)

(9-31/32)

(5-1/8)

130

103

130

Drain pipe
O.D.32(1-1/4")

289 (11-13/16)

388 (15-9/32)

Connection pipe of outdoor unit


(High pressure)

268 (10-9/16)

128

(Lifting bolt pitch)

Detail of X section

(5-1/8) (4-1/16)
(5-1/16)

70
450 (17-23/32)

30 (1-3/16)
74 (2-15/16)

(2-25/32)

268 (10-9/16)

12 (1/2)

27 (1-3/32)

210 (8-9/32)
(4-1/16)

Drain hose I.D.32(1-1/4")


(Accessory)

103

<Accessories>
Note1.Suspension bolt(10),washer(M10),and nut(M10)
Refrigerant<Low pressure> conn. pipe1pc.
prepare in the field.
Drain hose I.D.32(1-1/4")1pc.
2.Take notice of service space as follows.
Hose band1pc.
(Please give attention not to occupy service
Tie band1pc.
space by letting ducts and pipes through.)
3.Please take service space for connection pipe of SUB BC CONTROLLER.
4.When using an outdoor unit-28HP(P700) or more,use this product.
Connection pipe of
SUB BC CONTROLLER
5.Install this product in a location where noise (refrigerant noise)
(High pressure)
emitted by the unit will not disturb the neighbors.
Total capacity of indoor unit
(For use in quiet enviroments with low background noise,position
at SUB BC CONTROLLER
P72 or less:15.88(5/8)<Brazed>
the BC CONTROLLER at least 5m away from any indoor units.)
(use attachment pipe of
6.Refer to the Installation Manual for refrigerant piping diameter size
SUB BC CONTROLLER)
P73~P126 :19.05(3/4)<Brazed>
when connecting plural indoor units with 1 branch.

250

Cutting point

(700) (27-9/16)

BC-14
(9-27/32)

Band(Accessory)

2. EXTERNAL DIMENSIONS
Unit: mm (in.)

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

(3-3/32)

80

181

BC Controllers (August 2015)

CMB-P104NU-GB1
CMB-P108NU-GB1

A
3
7

B
180(7-3/32)
420(16-9/16)

169

23 (29/32)

248 (9-25/32)

12 (1/2)

(1-1/4)

31

Total capacity of indoor units at SUB BC CONTROLLER


P72 or less :19.05(3/4)<Brazed>(use attachment pipe)
P73~P108 :22.2(7/8)<Brazed>
P108 over :28.58(1-1/8)<Brazed>(use attachment pipe)

130

(5-1/8)

58 (2-5/16)

30 (1-3/16)

Connection pipe of MAIN BC CONTROLLER


(Low pressure)

130

103
130

(7-5/32)
(5-1/8)

45 (1-25/32)

128

(5-1/16)

Drain pipe
O.D.32(1-1/4")

27 (1-3/32)

90

46

76
(3)

(7-7/8)

60(2-3/8)A=B

60 (2-3/8)

60 (2-3/8))

60(2-3/8)A=B

702 (27-21/32)
(Lifting bolt pitch)

648 (25-17/32)

Control box

Indoor unit model (Note 5)


P18 or less :12.7(1/2)<Brazed>
P18 over :15.88(5/8)<Brazed>

Connection pipe of
indoor unit(Gas)

Indoor unit model (Note 5)


P18 or less :6.35(1/4)<Brazed>
P18 over :9.52(3/8)<Brazed>

Connection pipe of
indoor unit(Liquid)

(200) (7-7/8)

Service space

Access
door
450
(17-23/32)

(7-7/8)
200

(Note 2)

CMB-P104, 108NU-GB1

200

(3-9/16) (1-13/16)

Total capacity of indoor units at SUB BC CONTROLLER


P108 or less :9.52(3/8)<Brazed>
P108 over :12.7(1/2)<Brazed>(use attachment pipe)

298 (11-3/4)
(Lifting bolt pitch)

Total capacity of indoor units at SUB BC CONTROLLER


P72 or less :15.88(5/8)<Brazed>(use attachment pipe)
P72 over :19.05(3/4)<Brazed>

(5-1/8) (4-1/16)

284 (11-3/16)

(2-25/32)

<Accessories>
Note1.Suspension bolt(10),washer(M10),and nut(M10)
Refrigerant<Low pressure> conn. pipe4pcs.
prepare in the field.
(Indoor unit Model:P18 over)
Refrigerant<High pressure> conn. pipe2pcs.
2.Take notice of service space as follows.
Refrigerant<Liquid> conn. pipe2pcs.
(Please give attention not to occupy service
Cutting point
Drain hose I.D.32(1-1/4")1pc.
space by letting ducts and pipes through.)
(Indoor unit Model:P18 or less)
Hose band1pc.
3.Can't use singleness.(MAIN BC CONTROLLER is necessary.)
Tie band1pc.
4.Install this product in a location where noise (refrigerant noise)
14
emitted by the unit will not disturb the neighbors.
(9/16)
(For use in quiet enviroments with low background noise,position
Detail of X section
Detail of Y section
Detail of Z section
the BC CONTROLLER at least 5m away from any indoor units.)
Connection pipe of MAIN BC CONTROLLER
5.Refer to the Installation Manual for refrigerant piping diameter size
(High pressure)
Connection pipe of MAIN BC CONTROLLER(Liquid)
when connecting plural indoor units with 1 branch.

(6-21/32)

255 (10-1/16)

70
362 (14-9/32)

Cutting point

250

Drain hose I.D.32(1-1/4")


(Accessory)

(700) (27-9/16)

2015 Mitsubishi Electric US, Inc.


(9-27/32)

Band(Accessory)

2. EXTERNAL DIMENSIONS
Unit: mm (in.)

BC-15

30 (1-3/16)

(1-1/4)

31

Detail of Y section

(7-5/32)

(3-5/32)

Drain pipe
O.D.32(1-1/4")

(5-1/8)

(200) (7-7/8)

Service
space

Access
door
450
(17-23/32)

(Note 2)

Total capacity of indoor units at SUB BC CONTROLLER


P72 or less :19.05(3/4)<Brazed>(use attachment pipe)
P73~P108 :22.2(7/8)<Brazed>
P108 over :28.58(1-1/8)<Brazed>(use attachment pipe)
(7-7/8)
200

Connection pipe of MAIN BC CONTROLLER


(Low pressure)
(5-1/8)

130

Total capacity of indoor units at SUB BC CONTROLLER


P72 or less :15.88(5/8)<Brazed>(use attachment pipe)
P73~P126 :19.05(3/4)<Brazed>
P126 over :22.2(7/8)<Brazed>(use attachment pipe)

80

181

130

45 (1-25/32)

103

23 (29/32)

130

Detail of X section

(5-1/8) (4-1/16)

284 (11-3/16)

Connection pipe of MAIN BC CONTROLLER


(High pressure)

248 (9-25/32)

14

(700) (27-9/16)

169 (6-21/32)
255 (10-1/16)

(9/16)

58 (2-5/16)

Drain hose I.D.32(1-1/4")


(Accessory)

90

46

76
(3)

(7-7/8)

(3-9/16) (1-13/16)

200

27 (1-3/32)

60 (2-3/8)

60 (2-3/8)

10

11

12

60(2-3/8)15=900(35-7/16)

60(2-3/8)15=900(35-7/16)

1152 (45-3/8)

1098 (43-1/4)

(Lifting bolt pitch)

13

14

15

Control box

16

<Accessories>
Note1.Suspension bolt(10),washer(M10),and nut(M10)
Refrigerant<Low pressure> conn. pipe4pcs.
prepare in the field.
Refrigerant<High pressure> conn. pipe2pcs.
Cutting point
2.Take notice of service space as follows.
Refrigerant<Liquid> conn. pipe2pcs.
(Indoor unit Model:P18 over)
(Please give attention not to occupy service
Drain hose I.D.32(1-1/4")1pc.
space by letting ducts and pipes through.)
Cutting point
3.Can't use singleness.(MAIN BC CONTROLLER is necessary.) Hose band1pc.
(Indoor unit Model:P18 or less)
4.Install this product in a location where noise (refrigerant noise) Tie band1pc.
emitted by the unit will not disturb the neighbors.
(For use in quiet enviroments with low background noise,position
the BC CONTROLLER at least 5m away from any indoor units.)
Detail of Z section
5.Refer to the Installation Manual for refrigerant piping diameter size
when connecting plural indoor units with 1 branch.
Connection pipe of MAIN BC CONTROLLER(Liquid)
Total capacity of indoor units at SUB BC CONTROLLER
P108 or less :9.52(3/8)<Brazed>
P109~P144 :12.7(1/2)<Brazed>(use attachment pipe)
P144 over :15.88(5/8)<Brazed>(use attachment pipe)

128

(5-1/16)

70

12 (1/2)
250
(9-27/32)

Indoor unit model (Note 5)


P18 or less :12.7(1/2)<Brazed>
P18 over :15.88(5/8)<Brazed>

Connection pipe of
indoor unit(Gas)

Indoor unit model (Note 5)


P18 or less :6.35(1/4)<Brazed>
P18 over :9.52(3/8)<Brazed>

Connection pipe of
indoor unit(Liquid)

(2-25/32)

BC-16
298 (11-3/4)
(Lifting bolt pitch)
362 (14-9/32)

Band(Accessory)

2. EXTERNAL DIMENSIONS
CMB-P1016NU-HB1
Unit: mm (in.)

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

2015 Mitsubishi Electric US, Inc.

TH16

TH15

TH12

TH11

PS3

PS1

3
2
1

3
2
1

ON

BC Controllers (August 2015)


1

CN05
(Red)

M
LEV1

LEV3

SW6

SW5

1 2 3 4 5 6

CN07
(Yellow)

OFF

ON

OFF

SW4

SW1

1 2 3 4 5 6

CN11

ON

OFF

SW2
1

DSA

ZNR01

ZNR02

CN12

F01
250VAC
6.3A F

3 5

X21

CN36(Green)

X33

X7

X8

CN29(Green)

X32

CN28(Blue)

X31

X3

X4

CN27(Red)

X5

CN26

X30

X1

X2

3
10

CN02

CN03
(Yellow)

CNTR
(Red)

X6

CN10

CN13
(Red)

CNP3

2 1

3 2 1

1
2

1
2

CNP1
(Black)

1
2

CONT.B

TR

T4

T3

T2

T1

L1

L2

POWER SUPPLY
~208V-230V
60Hz

FUSE(16A) BREAKER(16A)

PULL BOX

SVM1

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

SV1A

SV1B

Indoor/outdoor
Transmission Line

TO NEXT
TB01 INDOOR UNIT

1616

1515

1414

1313

1212

11 11

1010

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

M1

TB02
S(SHIELD)
M2

Terminal
Fuse AC250V 6.3A F

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

F01

Solenoid valve
T1~4

Solenoid valve

Pressure sensor
Circuit
BC controller
board
Terminal block
(for power source)
Terminal block
(for Transmission)

Expansion valve

Thermister sensor

SVM1

SV1~4A,B,C

TB02

TB01

CONT.B

PS1,3

LEV1,3

TH11,12,15,16

TR

Name
Transformer

(Symbol explanation)
Symbol

3. ELECTRICAL WIRING DIAGRAMS


CMB-P104NU-G1

BC-17

BC-18

TH16

TH15

TH12

TH11

PS3

PS1

3
2
1

3
2
1

CN11

ON

LEV1

LEV3

CN05
(Red)

SW6

SW5

SW4

SW1

1 2 3 4 5 6

OFF

ON

OFF

ON

OFF

SW2
1

1 2 3 4 5 6

CN07
(Yellow)

DSA

ZNR01

CN12

L1

ZNR02

1
3 5

F01
250VAC
6.3A F

L2

4 4

3 3

2 2

1 1

1616

1515

1414

1313

1212

11 11

1010

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

FUSE(16A) BREAKER(16A)

T5

T4

T3

T2

T1

SV5C

SV5A

SV5B

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

SV1A

SV1B

Indoor/outdoor
Transmission line

2
3
3

T6

SVM1

SV6C

SV6A

SV6B

1 CMB-P106NU-G1 ONLY

M1

TB02
S(SHIELD)
M2

1 1

POWER SUPPLY
~208V-230V
60Hz

CN36(Green)

X21

X35

X11

X12

CN31(Yellow)

X34

X9

X10

PULL BOX

TO NEXT
TB01 INDOOR UNIT

CN30(Black)

X33

X7

X8

CN29(Green)

X32

X5

CN28(Blue)

X31

X3

X4

CN27(Red)

CN26

X30

X1

X2

CNTR
(Red)

3
10

CN03
(Yellow)

X6

CN10

CN13
(Red)

CNP3

2 1

CN02

3 2 1

1
2

1
2

CNP1
(Black)

1
2

CONT.B

TR

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

F01

Terminal
Fuse AC250V 6.3A F

Solenoid valve
T1~6

Solenoid valve
SVM1

Pressure sensor
Circuit
BC controller
board
Terminal block
(for power source)
Terminal block
(for Transmission)

Expansion valve

Thermister sensor

Name
Transformer

SV1~6A,B,C

TB02

TB01

CONT.B

PS1,3

LEV1,3

TH11,12,15,16

TR

Symbol

(Symbol explanation)

3. ELECTRICAL WIRING DIAGRAMS


CMB-P105, 106NU-G1

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

TH16

TH15

TH12

TH11

PS3

PS1

3
2
1

3
2
1

CN10

LEV1

CN05
(Red)

LEV3

SW6

SW5

SW4

SW2 SW1

OFF

ON

OFF

ON

OFF

ON

1 2 3 4 5 6

CN07
(Yellow)

CN11

CN02

CN03
(Yellow)

10

2 1

3 2 1

1 2 3 4 5 6

1 CN13
2 (Red)

1
2 CNP3
3

CNP1
(Black)

1
2
3

CONT.B
CN51

654321

7654321

CN12

1 3 5

ZNR02

DSA F01
250VAC
6.3A F

1 3

CN38

ZNR01

CN50

X30

5
7

X3
X31

X34

5
7

X11
X35

X21
3

CN36(Green)

X12

CN31(Yellow)

X9

X10

CN30(Black)

X33

X7

X8

CN29(Green)

X32

X5

X6

CN28(Blue)

X4

X1

CN27(Red)

X2

CN26

CNTR
(Red)

L2

L1

TB01

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

2
4

SV1A

SV1B

SV6C

SV6A

SV6B

SV5C

SV5A

SV5B

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

CN39
3
1

SVM1

FUSE(16A) BREAKER(16A)

16
16

POWER SUPPLY
~208V-230V
PULL BOX
60Hz

T6

T5

T4

T3

T2

T1

TO NEXT INDOOR UNIT

CMB-P1010NU-G1 ONLY

3
1

3
1

12 11 10
12 11 10

T9

CN53

6 5 4 3 2 1

CMB-P1010NU-G1 ONLY

15 14 13
15 14 13

T10

SV10C
X20

Indoor/outdoor
Transmission line

CN35(Blue)

SV10A
X19

SV9C
X18

SV10B
X39

SV9A
X17

TB02

M1

CN34(Black)

SV9B
X38

T8

8
8

9
9

SV8C
X16

S(SHIELD)
M2

CN33(Red)

SV8A
5

7
7

CN32

5
5

6
6

CN52

2 1

SV7B
4
4

T7
3

7 6 5 4 3 2 1

X15

SV7C
X14

SV8B
X37

SV7A
X13

2015 Mitsubishi Electric US, Inc.


X36

TR

REL.B

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

(Symbol explanation)
Symbol
Name
Transformer
TR
TH11,12,15,16 Thermister sensor
Expansion valve
LEV1,3
Pressure sensor
PS1,3
REL.B
Circuit Relay
board BC controller
CONT.B
Terminal block
TB01
(for power source)
Terminal
block
TB02
(for Transmission)
SV1~10A,B,C Solenoid valve
SVM1
Solenoid valve
T1~10
Terminal
F01
Fuse AC250V 6.3A F

3. ELECTRICAL WIRING DIAGRAMS


CMB-P108, 1010NU-G1

BC Controllers (August 2015)

BC-19

TH16

TH15

TH12

TH11

PS3

PS1

ON

SW6

SW5

SW4

LEV1

1 2 3 4 5 6

CN05
(Red)

OFF

SW2 SW1

10

LEV3

1 2 3 4 5 6

CN07
(Yellow)

OFF

OFF

ON

ON

CN11

CN10

CN13
(Red)

CNVCC1 CN03
(Blue) (Yellow)

2 CNP3

CNP1
(Black)

CN02

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

3
2
1

3
2
1

CONT.B

CN12

1
3

DSA F01
250VAC
6.3A F

ZNR01

CNOUT3

CNOUT1

ZNR02

CN38

X32

X5

X6

X21
3

CN36(Green)

X35

X11

X12

CN31(Yellow)

X34

X9

X10

CN30(Black)

X33

X7

X8

CN28(Blue)

X31

X3

X4

CN27(Red)

X30

X1

X2

CN26

CN29(Green)

CNTR
(Red)

M1

TB02

S(SHIELD)
M2

L1

2
3

2
3

T6

T5

T4

T3

T2

T1

L2

SV1A

SV1B

POWER SUPPLY
~208V-230V
60Hz

SV6C

SV6A

SV6B

SV5C

SV5A

SV5B

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

FUSE(16A) BREAKER(16A)

PULL BOX

TB01 TO NEXT INDOOR UNIT

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

Indoor/outdoor
Transmission line

16
16

T10

CNOUT2

CNOUT4

1
2
3
4

1
2
3
4
5
6
7
8

15 14 13
15 14 13

SV10A

X20

10
10

T9

12 11
12 11

SV9A

X18

SV10B

X19

SV9C
X17

SV10C

X39

SV9B
X38

7
7

8
8

T8

9
9

SV8A

X16

4
4

5
5

T7

6
6

SV7A

X14

SV8C
X15

SV7B

X13

SV8B
X37

SV7C

X36

BC-20
7

CN39

TR

CNVCC2
(Blue)

X57

X55

X56

CN45(Green)

X54

X52

X53

CN44(Yellow)

X51

X49

X50

CN43(Red)

X48

X46

X47

CN42

X45

X43

X44

CN41(Green)

X42

X40

X41

CN40
(Yellow)

SV11A

SV11B

SV14A

4 4

3 3

2 2

1 1

1616

1515

SV16B
SV16A

1
2
3

1
2
3

SVM1

SV16C

3 T16
4

2
2
3

SV15C

SV15A

SV15B

3 T15
1414

1313

SV14C

SV14B

3 T14

CMB-P1016NU-G1 ONLY

SV13C

SV13A

SV13B

SV12C

SV12A

SV12B

SV11C

3T13

3T12

3T11

1
2
3

1212

11 11

1010

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

REL.B

Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F

Terminal block
(for power source)
Terminal block
(for Transmission)

TB02
SV1~16A,B,C
SVM1
T1~16
F01

TB01

(Symbol explanation)
Symbol
Name
Transformer
TR
TH11,12,15,16 Thermister sensor
Expansion valve
LEV1,3
Pressure sensor
PS1,3
REL.B
Circuit Relay
board BC controller
CONT.B

3. ELECTRICAL WIRING DIAGRAMS


CMB-P1013, 1016NU-G1

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

CN32

CN33(Red)

CN34(Black)

CN35(Blue)

TH16

TH15

TH12

TH11

PS3

3
2
1

2
2

ON

M
LEV1

LEV3

CN05
(Red)

OFF

ON

OFF

1 2 3 4 5 6

CN07
(Yellow)

CN11

OFF

SW6

SW5
8

SW1

SW4

SW2

1 2 3 4 5 6

CN12

F01
250VAC
6.3A F
3

DSA

ZNR02

ZNR01

X60
3

CN46(Yellow)

X21

CN36(Green)

X35

X11

X12

CN31(Yellow)

X34

X9

X10

CN30(Black)

X33

X7

X8

CN29(Green)

X32

CN28(Blue)

X31

X3

X4

CN27(Red)

X30

X1

X2

CN26

4
1

X5
10

CN38

CNTR
(Red)

ON

CN02

CN50

X6

CN10

CN03
(Yellow)

7 6 5 4 3 2 1

2 (Red)

1 CN13

2 CNP3

CNP1
(Black)

6 5 4 3 2 1

L1
L2

TB01

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

T6

T5

T4

T3

T2

T1
SV1A

SV1B

SV6C

SV6A

SV6B

SV5C

SV5A

SV5B

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

FUSE(16A) BREAKER(16A)

POWER SUPPLY
~208V-230V
PULL BOX
60Hz

TO NEXT
INDOOR UNIT

4
4

SVM2

PS1

CN51

3
3

2
2

1
1

3
1

CN39

SVM1

T10

6 5 4 3 2 1

7
7

8
8

T8

9
9

7 6 5 4 3 2 1

10
10

T9

12 11
12 11

CN52

Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F

5
5

6
6

4
4

2
3

2
3

T7
4

REL.B
7

Terminal block
(for power source)
Terminal block
(for Transmission)

TB02
SV1~10A,B,C
SVM1,2
T1~10
F01

TB01

Name
Transformer
Thermister sensor
Expansion valve
Pressure sensor
Circuit Relay
board BC controller

Symbol
TR
TH11,12,15,16
LEV1,3
PS1,3
REL.B
CONT.B

(Symbol explanation)

CMB-P1010NU-GA1 ONLY

15 14 13
15 14 13

CN53

16
16

CN35(Blue)

3
2
1

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

CN34(Black)

CONT.B

CN33(Red)

Indoor/outdoor
Transmission line

SV10A
X20

SV7A

TB02

CN32

S(SHIELD)
M2
M1

SV10C

X19

SV9A
X18

SV10B
X39

SV9C

X17

SV8A
X16

SV9B
X38

SV8C

X15

SV7C
X14

SV8B
X37

SV7B
X13

2015 Mitsubishi Electric US, Inc.


X36

TR

3. ELECTRICAL WIRING DIAGRAMS


CMB-P108, 1010NU-GA1

BC Controllers (August 2015)

BC-21

3
2
1

CN05
(Red)

CN11

CN10

CN13
(Red)

CN07
(Yellow)

ON

OFF

ON

OFF

ON

OFF

SW6

SW5

SW4

SW2 SW1

10

CNVCC1 CN03 CN02


(Blue) (Yellow)

2 CNP3

CNP1
(Black)

CONT.B

1 2 3 4 5 6

1 2 3 4 5 6

CN12

1
3

DSA F01
250VAC
6.3A F

ZNR01

CNOUT3

CNOUT1

Note:1.TB02 is transmission terminal


block.Never connect power line
to it.
2.The initial set values of switch
on CONT.B are as follows.
SW1:0
SW2:0

LEV1

LEV3

TH16

TH15

TH12

TH11

PS3

PS1

3
2
1

ZNR02
U

CN38

CN26

X60
3

CN46(Yellow)

X21

CN36(Green)

X35

X11

X12

CN31(Yellow)

X34

X9

X10

CN30(Black)

X33

X7

X8

CN29(Green)

X32

X5

X6

CN28(Blue)

X31

X3

X4

CN27(Red)

X30

X1

X2

CNTR
(Red)

L1

L2

T6

T5

T4

T3

T2

T1
SV1A

SV1B

SV6C

SV6A

SV6B

SV5C

SV5A

SV5B

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

POWER SUPPLY
~208V-230V
PULL BOX
60Hz

2
3

Indoor/outdoor
Transmission line

FUSE(16A) BREAKER(16A)

TO NEXT
TB01 INDOOR UNIT

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

M1

TB02

S(SHIELD)
M2

16

16

CNOUT2

CNOUT4

1
2
3
4

1
2
3
4
5
6
7
8

13
13

14
14

T10

15
15

SV10A

X20

10
10

11
11

T9

12
12

SV9A

X18

SV10C
X19

SV9C
X17

SV10B
X39

SV9B
X38

7
7

8
8

T8

9
9

SV8A

X16

4
4

5
5

T7

6
6

SV7A

X14

SV8B

X15

SV7B

X13

SV8C

X37

SV7C

X36

BC-22
CN39

TR

X42

X40

X41

CNVCC2
(Blue)
CN40
(Yellow)

X57

X55

X56

CN45(Green)

X54

X52

X53

CN44(Yellow)

X51

X49

X50

CN43(Red)

X48

X46

X47

CN42

X45

X43

X44

CN41(Green)

4 4

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

REL.B

SV13A

SV14A

SV16B
SV16A

2
3

SVM2

SVM1

SV16C

3 T16
4

SV15C

SV15A
4

SV15B
3 T15

SV14C

SV14B

CMB-P1016NU-GA1 ONLY
3 T14

SV13C

3T13
4

SV13B
2

SV12C

SV12A
4

SV12B
3T12

SV11C

SV11A

SV11B

Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F

Terminal block
(for power source)
Terminal block
(for Transmission)

Name
Transformer
Thermister sensor
Expansion valve
Pressure sensor
Circuit Relay
board BC controller

3 T11

TB02
SV1~16A,B,C
SVM1,2
T1~16
F01

TB01

Symbol
TR
TH11,12,15,16
LEV1,3
PS1,3
REL.B
CONT.B

(Symbol explanation)

3. ELECTRICAL WIRING DIAGRAMS


CMB-P1013NU-GA1

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

CN32

CN33(Red)

CN34(Black)

CN35(Blue)

BC Controllers (August 2015)

3
2
1

3
2
1
2

SW6

SW5
8

SW1

SW4

SW2

1
2
3
4
5
6

CN05
(Red)

1
2
3 CN07
4(Yellow)
5
6

CN38

CNOUT1

LD1:CPU in
operation

CONT.B

CN12

DSA

1
3

F01
250VAC
6.3A F
5

ZNR02

ZNR01

CNOUT3

OFF

ON

OFF

ON

OFF

ON

CN11

CN10

CN13
(Red)

CNP3

10

CNVCC1 CN03 CN02


(Blue) (Yellow)

1
2

1
2

CNP1
(Black)

1
2

Note:1.TB02 is transmission terminal


block.Never connect power line
to it.
2.The initial set values of switch
on CONT.B are as follows.
SW1:0
SW2:0

LEV1

LEV3

TH16

TH15

TH12

TH11

PS3

PS1

X10

X61

X62

CN47

X60

CN46(Yellow)

X21

CN36(Green)

X35

X11

X12

CN31(Yellow)

X34

X09

CN30(Black)

X33

X07

X08

CN29(Green)

X32

X05

X06

CN28(Blue)

X31

X03

X04

CN27(Red)

X30

X01

X02

CN26

CNTR(Red)

L2

L1

TB01

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

M1

SV1B

SV6C

T6 SV6A

SV6B

SV5C

T5 SV5A

SV5B

SV4C

T4 SV4A

SV4B

SV3C

T3 SV3A

SV3B

SV2C

T2 SV2A

SV2B

SV1C

T1 SV1A

FUSE(16A) BREAKER(16A)

POWER SUPPLY
~208V-230V
PULL BOX
60Hz

TO NEXT
INDOOR UNIT

2
3

16
16

T10

CNOUT2

CNOUT4

1
2
3
4

1
2
3
4
5
6
7
8

15 14 13
15 14 13

4
1

T9

12 11 10
12 11 10

T8

7
7

8
8

9
9

REL.B

CMB-P10101016NU-HA1 ONLY
SV10A

X20

Indoor/outdoor
Transmission line

SV10B

X19

SV9A

X18

SV10C

X39

SV9B

X17

TB02

CN34(Black)

SV9C

X38

S(SHIELD)
M2

CN33(Red)

SV8A

X16

T7

4
4

5
5

6
6

SV7A

X14

SV8B

X15

SV7B

X13

SV8C

X37

SV7C

X36

2015 Mitsubishi Electric US, Inc.


CN39

TR

X41
X40
X42

X56
X55
X57

CN45(Green)

X53
X52
X54

CN44(Yellow)

X50
X49
X51

CN43(Red)

X47
X46
X48

CN42

X44
X43
X45

CNVCC2
(Blue)

CN40
(Yellow)

CN41(Green)

5
6

5
6

8 8

6 6

SVM1b

SVM2b

SVM2

SVM1

SV16C
4

SV16B
T16 SV16A
3

7 7

1
2

5 5

SV15C

SV15B
T15 SV15A
3

4 4

3 3

2 2

1 1

16 16

15 15

14 14

SV14C
1

T14 SV14A
4

SV14B

SV13C

T13 SV13A

SV13B

SV12C

T12 SV12A

SV12B

SV11C

2
3

13 13

SV11B

CMB-P1016NU-HA1 ONLY
T11 SV11A

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

Solenoid valve
Solenoid valve
Terminal
Fuse AC250V 6.3A F

Terminal block
(for power source)
Terminal block
(for Transmission)

Name
Transformer
Thermister sensor
Expansion valve
Pressure sensor
Circuit Relay
board BC controller

TB02
SV1~16A,B,C
SVM1,2,1b,2b
T1~16
F01

TB01

Symbol
TR
TH11,12,15,16
LEV1,3
PS1,3
REL.B
CONT.B

(Symbol explanation)

3. ELECTRICAL WIRING DIAGRAMS


CMB-P108, 1010, 1016NU-HA1

BC-23

CN32

CN35(Blue)

BC-24

TH15

TH12

CN07
(Yellow)

OFF

ON

OFF

LEV3

1 2 3 4 5 6

CN11

ON

OFF

SW1

SW6

SW5

SW4

SW2
8

DSA

ZNR01

ZNR02

CN12

L2

16 16

15 15

14 14

13 13

12 12

6.3A F

11 11

L1

X33

X7

X8

10 10

9 9

8 8

250VAC

CN29(Green)

X32

7 7

6 6

5 5

TB01

CN28(Blue)

X31

X3

X4

4 4

3 3

2 2

1 1

T1

POWER SUPPLY
~208V-230V
60Hz

SV4C

SV4A

SV4B

SV3C

SV3A

FUSE(16A) BREAKER(16A)

PULL BOX

T4

T3

SV3B

SV2C

SV2A

SV2B

SV1C

SV1A

SV1B

Transmission Line

Indoor/outdoor

T2

TO NEXT
INDOOR UNIT

2
3

M1

TB02
S(SHIELD)
M2

F01

CN26

CN27(Red)

X30

X1

X2

CNTR
(Red)

X5

10

CN02

ON

X6

CN10

CN13
(Red)

CN03
(Yellow)

CONT.B

TR

Name

Expansion valve
Circuit
BC controller
board
Terminal block
(for power source)
Terminal block
(for Transmission)
Terminal
Fuse AC250V 6.3A F

T1~4
F01

SW2:0

SW1:0

are as follows.

of switch on CONT.B

2.The initial set values

line to it.

Never connect power

terminal block.

Note:1.TB02 is transmission

Solenoid valve

SV1~4A,B,C

TB02

TB01

CONT.B

Thermister sensor

LEV3

Transformer

TH12,15

TR

Symbol

(Symbol explanation)

3. ELECTRICAL WIRING DIAGRAMS


CMB-P104NU-GB1

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

TH15

TH12

ON

BC Controllers (August 2015)

LEV3

1 2 3 4 5 6

CN07
(Yellow)

OFF

ON

OFF

OFF

ON

CN11

CN10

CN13
(Red)

SW6

SW5

SW4

CN02

SW2 SW1

10

CN03

7 6 5 4 3 2 1

ZNR01

CN12

250VAC
6.3A F

DSA F01

CN50

1
3

ZNR02

CN38

X35

X11

X12

CN31(Yellow)

X34

X9

X10

CN30(Black)

X33

X7

X8

CN29(Green)

X32

X5

X6

CN28(Blue)

X31

X3

X4

CN27(Red)

X30

X1

X2

CN26

CNTR
(Red)

L2

L1

TB01

3 3

2 2

1 1

16 16

15 15

14 14

13 13

12 12

11 11

10 10

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1
2

T6

T5

T4

T3

T2

T1

FUSE(16A) BREAKER(16A)

PULL BOX

3
1

CN39

POWER SUPPLY
~208V-230V
60Hz

SV6C

SV6A

SV6B

SV5C

SV5A

SV5B

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

SV1A

SV1B

TO NEXT INDOOR UNIT

2
3

2
3

16
16

15 14 13
15 14 13

X20

X19

X39

Indoor/outdoor
Transmission line

CN34(Black)
CN35(Blue)

CONT.B

M1

7
7

8
8

T8

9
9

7 6 5 4 3 2 1

10
10

12 11
12 11

CN33(Red)

TB02

X18

CN32

4
4

T7

5
5

6
6

CN52

SV7A

S(SHIELD)
M2

X17

SV8A
X16

SV7B

TR

X38

SV8C

X15

REL.B

(Symbol explanation)
Symbol
Name
Transformer
TR
Thermister sensor
TH12,15
Expansion valve
LEV3
REL.B
Circuit Relay
board BC controller
CONT.B
Terminal block
TB01
(for power source)
Terminal block
TB02
(for Transmission)
SV1~8A,B,C
Solenoid valve
T1~8
Terminal
F01
Fuse AC250V 6.3A F

X14

SV8B
X37

SV7C

X13

2015 Mitsubishi Electric US, Inc.


X36

Note:1.TB02 is transmission
terminal block.
Never connect power
line to it.
2.The initial set values
of switch on CONT.B
are as follows.
SW1:0
SW2:0

3. ELECTRICAL WIRING DIAGRAMS


CMB-P108NU-GB1

BC-25

LEV3

TH15

TH12

2 1

CN07
(Yellow)

CN12

DSA

ZNR02

3 5

F01
250VAC
6.3A F

ZNR01

CNOUT3

3 1

Note:1.TB02 is transmission terminal


block.Never connect power line
to it.
2.The initial set values of switch
on CONT.B are as follows.
SW1:0
SW2:0

1
2
3
4
5
6

CN11

CNOUT1

SW6

SW5

SW4

LD1:CPU in
operation

CN38

CONT.B

OFF

ON

OFF

ON

SW1

SW2

CN10

CN13
(Red)

ON

OFF

10

1
2

3 2 1

CNVCC1 CN03 CN02


(Blue) (Yellow)

3 2 1

X35

X11

X12

CN31(Yellow)

X34

X09

X10

CN30(Black)

X33

X07

X08

CN29(Green)

X32

X05

X06

CN28(Blue)

X31

X03

X04

CN27(Red)

X30

X01

X02

CN26

CNTR(Red)

TB02

L2

L1

TB01

3 3

2 2

1 1

T6
SV6C

SV6A

SV6B

SV5C

SV5A

SV5B

SV4C

SV4A

SV4B

SV3C

SV3A

SV3B

SV2C

SV2A

SV2B

SV1C

SV1A

SV1B

FUSE(15A) BREAKER(15A)

POWER SUPPLY
~208V-230V
PULL BOX
60Hz

3 T5

3 T4

3 T3

3 T2

3 T1

2
3

TO NEXT
INDOOR UNIT

1616

1515

1414

1313

1212

11 11

1010

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

Indoor/outdoor
Transmission line

16
16

T10

CNOUT2

CNOUT4

1
2
3
4

1
2
3
4
5
6
7
8

15 14 13
15 14 13

SV10A

X20

M1

SV10B

X19

T9

12 11 10
12 11 10

SV9A

X18

SV10C
X39

SV9B

X17

S(SHIELD)
M2

CN34(Black)

SV9C
X38

TR

7
7

8
8

T8

9
9

REL.B

CN33(Red)

SV8A

X16

4
4

5
5

T7

6
6

SV7A

X14

SV8B

X15

SV7B

X13

SV8C
X37

SV7C
X36

BC-26
CN39

3 2 1

CNVCC2
(Blue)

X57

X55

X56

CN45(Green)

X54

X52

X53

CN44(Yellow)

X51

X49

X50

CN43(Red)

X48

X46

X47

CN42

X45

X43

X44

CN41(Green)

X42

X40

X41

CN40
(Yellow)

1 3

4 4

3 3

2 2

1 1

1616

1515

3 T16

3 T15

2
1414

1313

3 T14

3 T13

3 T12

3 T11

1212

11 11

1010

9 9

8 8

7 7

6 6

5 5

4 4

3 3

2 2

1 1

SV16C

SV16A

SV16B

SV15C

SV15A

SV15B

SV14C

SV14A

SV14B

SV13C

SV13A

SV13B

SV12C

SV12A

SV12B

SV11C

SV11A

SV11B

TB02
SV1~16A,B,C
T1~T16
F01

TB01

Symbol
TR
TH12,15
LEV3
REL.B
CONT.B

Name
Transformer
Thermister sensor
Expansion valve
Circuit Relay
board BC controller
Terminal block
(for power source)
Terminal block
(for Transmission)
Solenoid valve
Terminal
Fuse AC250V 6.3A F

(Symbol explanation)

3. ELECTRICAL WIRING DIAGRAMS


CMB-P1016NU-HB1

BC Controllers (August 2015)

2015 Mitsubishi Electric US, Inc.

CN32

CN35(Blue)

(1) CMB-P104 - P1016NU-G1

4. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS


CMB-P105, 1016NU-G1 (Single)
SVC/SVA/SVB
Solenoid valve block

TH15

Gas/Liquid
separator

LEV3
TH12
PS1
TH11
HIC-A

PS3

HIC-B

LEV1

TH16
Check valve block

SVM1

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.
HWE14090

- 82 -

BC-27
GB

(1) CMB-P104 - P1016NU-G1

4. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS


CMB-P1013 (Main)
SVC/SVA/SVB
Solenoid valve block

TH15

Gas/Liquid
separator

LEV3
TH12
PS1

PS3

HIC-B

LEV1

TH11

TH16

HIC-A

Check valve block

[3-6 BC Controller Refrigerant Circuit Diagrams


]
SVM1

3-6

BC Controller Refrigerant Circuit Diagrams

(1) CMB-P104 - P1016NU-G1

CMB-P104, P108NU-GB1 (Sub)


SVC/SVA/SVB
Solenoid valve block

TH15

Gas/Liquid
separator

LEV3
TH12
PS1
TH11
HIC-A

BC-28
HWE14090

PS3

HIC-B

LEV1

TH16
Check valve block

SVM1

BC Controllers (August 2015)

- 82 -

2015 Mitsubishi Electric US, Inc.GB

(1) CMB-P104 - P1016NU-G1

4. REFRIGERANT CIRCUIT DIAGRAMS AND THERMAL SENSORS


CMB-P108, P1010, P1016NU-HA1 (Main)
SVC/SVA/SVB
Solenoid valve block

TH15

Gas/Liquid
separator

LEV3
TH12
PS1

PS3

HIC-B

LEV1

TH11

TH16

HIC-A

Check valve block

[3-6 BC Controller Refrigerant Circuit Diagrams


]
SVM1

3-6

BC Controller Refrigerant Circuit Diagrams

(1) CMB-P104 - P1016NU-G1

CMB-P1016NU-HB1 (Sub)
SVC/SVA/SVB
Solenoid valve block

TH15

Gas/Liquid
separator

LEV3
TH12
PS1
TH11
HIC-A

PS3

HIC-B

LEV1

TH16
Check valve block

SVM1

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.
HWE14090

- 82 -

BC-29
GB

5. SOUND PRESSURE LEVELS


5-1. BC Controller Steady State Sound

DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,


SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW

BC-30

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

5. SOUND PRESSURE LEVELS


5-2. BC Controller Peak Sound

DUE TO CONTINUING RESEARCH AND PRODUCT IMPROVEMENT,


SPECIFICATIONS AND DATA ARE STILL UNDER REVIEW

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-31

6. OPTIONAL PARTS
6-1. BV-Series Ball Valves

Size available: 1/4; 3/8; 5/8.


Fully factory assembled.
Furnace brazed and pressure tested.
Each ball valve is equipped with 4-1/4 Schrader Valve
for refrigerant service.
Design working pressure: 700 PSIG.
Temperature range:-40 F to +325 F (-40 C to +149 C).
Polytetrafluoroethylene (PTFE) seals and gaskets
Part Number
(no synthetic O-rings).
Seal cap design permits valve operation without
BV14BBSI
removal of seal cap.
BV38BBSI
One year limited materials and workmanship
TECHNICALBV12BBSI
SPECIFICATIONS
586WBS-XXSW
ENVELOPE
warranty
on Ball Valves.
MAX WORKING
PRESSURE

VALUE DIMENSIONS

LEAK RATE

PART NO.

"A"

"B"

Cv

586WBS-4S

0.25

0.31

1.80

586WBS-6S

0.38

0.31

3.60

586WBS-8S

0.50

0.38

7.40

586WBS-10S

0.63

0.50

14.60

US

LISTED 891N
REFRIGERANT
VALVE

SAE
Braze

1/4"

6.26

2.67

1.81

1.23

1.42

3/8"

6.30

2.67

1.81

1.23

1.42

1/2"
B

800 PSI

BV58BBSI
5/8"
< 0.1oz/YR ATMOSPHERE

6.51

2.67

1.81

6.64

2.67

1.81

1.23 REVISIONS
1.42
A
JL 07-12-13 ECO14058
B JWE 12-22-14 ECO14336
1.23

1.42

<0.5oz/YR BALL SEAL

come with an insulation piece.


OPERATING*Ball valves
+300F

TEMPERATURE

-40F

10
9

11

13

ACCESS FITTING (ITEMS 12 &


13) PER ARI 720 (INCLUDES
VALVE CORE AND SEAL CAP)

12

TORQUE CORE 12 TO 3 IN/LB.

2
4
A"

B"
ITEM
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

15

15
8

(.500)
BALL PORT

SECTION A-A
SCALE 1 : 1
(1.42)

(3.45)

14

(3.06)
(6.50)
A

RELEASED TO PRODUCTION

MAX WORKING PRESSURE 800 PSI WAS 700


OPERATING TEMPERATURE -40 F WAS -400

PROPRIETARY INFORMATION
INCLUDED HEREIN IS INFORMATION PROPRIETARY TO SHERWOOD VALVE LLC. THIS INFORMATION IS FURNISHED
IN CONFIDENCE SUBJECT TO RETURN UPON DEMAND BY SHERWOOD VALVE LLC. THIS DRAWING SHALL NOT BE
RELEASED OUTSIDE THE ORGANIZATION TO WHOM SENT BY SHERWOOD VALVE LLC, NOR USED, DUPLICATED OR
DISCLOSED IN WHOLE OR IN PART FOR ANY PURPOSE WHATSOEVER EXCEPT AS AUTHORIZED IN WRITING BY
SHERWOOD VALVE LLC.

MATERIALS OF CONSTRUCTION
MATERIAL
DESCRIPTION
PACKING - UPPER
Acetal Resin, White Delrin
PACKING - LOWER
Acetal Resin, Black Delrin
STEM
Steel, High Strength Low Alloy
AUX BODY SUB ASY
Welded Brass, & Copper
SEAL CAP
Brass, C37700
BALL
Brass, C36000
PACKING NUT
Brass, Soft Yellow C3600
BALL SEAL
Generic PTFE
GASKET
Acetal Resin, White Delrin
SEAL CAP NUT
Brass, Soft Yellow C3600
SEAL CAP GASKET
Nylon-6/6
VALVE CORE
Stainless Steel
C3600
SEAL CAP (ACCESS)
Brass, C37700
UNI-BODY W/ACCESS
PROTECTIVE CAP
UHMW, Red

UNLESS OTHERWISE SPECIFIED


ALL DIMENSIONS ARE IN INCHES
TOLERANCES
.XXX = 0.005
.XX = 0.01
ANGULAR = 2
EDGES OR CORNERS TO BE FILLETED OR BROKEN
.005 R OR CHAM
ALL DIAMETERS TO BE CONCENTRIC WITHIN .008
T.I.R.

TITLE

DWN DATE

SCALE

CHK BY

CHK DATE

SHEET

APPD BY

APPD DATE

FORMAT

J. LANG
JWE

DWG NO.

REV

Sherwood Valve LLC

CHANGE

6-2. BV-Series Ball Valve Insulation

WELDED BALL VALVE

DWN BY

7/12/2013

SCALE: 1:1

SHEET: 1 OF 1

12/29/2014

ANSI - B

586WBS-XXSW ENVELOPE

REV

Materials:
InsulationInner and outer layer Polyethylene foam (PEF)
CoveringAdhesive tape of Polyvinyl chloride (PVC)
SeparatorSoft film of Polyvinyl chloride (PVC)
Physical Properties of the Insulation
Density
Heat Conductivity (at 23C)
Tensile Strength
Heat Resistant
UL-94

Model Number
HKG-20HF

BC-32

d1
1-3/8"
(30mm)

t
(D)
L1
(d2)
3/4"
2-3/4"
8-9/16"
7/8"
(20mm) (70mm) (220mm) (11mm)

(d3)
1-9/64"
(29mm)

(L2)
1-15/32"
(37mm)

1.87 lb./ft.3 (30 kg/m3)


0.040 W/mK
23 N/cm2
176F (80C)
HF-1

(L3)
2-7/8"
(73mm)

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

6. OPTIONAL PARTS
6-3. CMY-R160-J1 Joint Adapter Kit for BC Controllers
Joint kit "CMY-R160-J1" for BC controller is used to combine 2 ports of the BC controller at a PURY-P-T(S)LMU/Y(S)LMU
system so as to enable down-stream Indoor capacity above P80 as shown in Fig. 1.
The Joint kit include following items:
1 Instruction 2 Joint pipe(Small) 3 Joint pipe(Large)

4 Cover 1

5 Cover 2

6 Cover 3

7 Band

8 Reducer 1 9 Reducer 2
OD19.05-ID22.2 OD19.05-ID15.88

This sheet

1pc

1pc

1pc

2pcs

1pc for gas side

1pc

3 Joint pipe (for gas side)

60(2-3/8")

mm(in.)
15.88(5/8")

60(2-3/8")

9.52(3/8")

9.52(3/8")

1pc

2 Extension pipe for refrigerant circuit

19.05(3/4")

2 Joint pipe (for liquid side)

8pcs

1pc for Iiquid side

Please prepare the following items in the field. 1 Tape for insulation material sealing

9.52(3/8")

15.88(5/8")

226(8-29/32")

1. Designing CMY-R160-J1 to a PURY-P-T(S)LMU/Y(S)LMU system


The maximum down-stream Indoor capacity for 1 port of BC
controller is P54. When the down-stream Indoor capacity is
above P54, Joint kit CMY-R160-J1 is needed to combined 2
ports of BC controller to enlarge the capacity, like Group 2 and
3 in Fig. 1.
Maximum 3 Indoor units are allowed to connect to 1 port of BC
controller or 2 combined ports of BC controller using CMYR160-J1.
When connecting Indoor units to 1 port of BC controller or 2
combined ports of BC controller using CMY-R160-J1 or CMYY102SS-G2 is applicable, like Group 1 and 2 in Fig. 1
Caution: Mixed cooling and heating mode at the same time for
Indoor units connecting to 1 port or 2 combined ports is not
available.

226(8-29/32")

PURY-P-T(S)LMU/Y(S)LMU
BC controller

Joint
CMY-Y102SS-G2

IU
IU
Group1
Total Indoor Capacity
<=P54

IU

IU
IU
Group2
Total Indoor Capacity
P55 to P96

Joint kit
CMY-R160-J1

IU

IU
Group3
Indoor Capacity
P72 to P96

Fig.1. CMY-R160-J1 applying scheme

2. Piping at the installation site


The connection of CMY-R160-J1 to BC controller and pipe leading to Indoor units is referable to Fig. 2. Non-oxidized brazing is
necessary. All piping must be careful to avoid foreign material getting inside.
After piping and air-tight testing, insulation work to the Joint and pipe should be done. Details is available at the Installation Manual.
Cutting point

2 Joint pipe (for liquid side)

Piping to indoor unit


(Non-oxidized brazing)

Have pipe expansion of indoor unit connecting port by


cutting the piping at the cutting point.
Remove burr after cutting the piping to prevent entering
the piping.
Check that there is no crack at the pipe expansion part.

3 Joint pipe(for gas side)

Fig.2. Connecting CMY-R160-J1

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.

BC-33

BC-34

BC Controllers (August 2015)


2015 Mitsubishi Electric US, Inc.