You are on page 1of 14

Saturday, November 26, 2016, 05:02 PM

PAGE NO.

****************************************************
*
*
*
STAAD.Pro
*
*
Version 2007
Build 04
*
*
Proprietary Program of
*
*
Research Engineers, Intl.
*
*
Date=
NOV 26, 2016
*
*
Time=
17: 0:32
*
*
*
*
USER ID: dPuJa
*
****************************************************

1. STAAD SPACE
INPUT FILE: balok museum.STD
2. START JOB INFORMATION
3. ENGINEER DATE 26-NOV-16
4. JOB NAME CASAMORA BLOK E
5. JOB CLIENT IBU MELYANA
6. JOB NO 100
7. JOB REV 1
8. JOB PART 1A
9. JOB REF IMOA
10. ENGINEER NAME DOODY
11. CHECKER NAME IR.TOTO
12. APPROVED NAME BUDI HC
13. END JOB INFORMATION
14. INPUT WIDTH 79
15. UNIT METER KG
16. JOINT COORDINATES
17. 1 0 0 0; 2 3.704 0 0; 3 7.6 0 0; 4 12.527 0 0; 5 17.454 0 0
18. MEMBER INCIDENCES
19. 1 1 2; 2 2 3; 3 3 4; 4 4 5
20. DEFINE MATERIAL START
21. ISOTROPIC CONCRETE
22. E 2.21467E+009
23. POISSON 0.17
24. DENSITY 2402.62
25. ALPHA 1E-005
26. DAMP 0.05
27. ISOTROPIC BETON_20MPA
28. E 2.1019E+009
29. POISSON 0.17
30. DENSITY 2400
31. END DEFINE MATERIAL
32. MEMBER PROPERTY AMERICAN
33. 1 TO 4 PRIS YD 0.45 ZD 0.2
34. CONSTANTS
35. MATERIAL BETON_20MPA ALL
36. SUPPORTS
37. 1 TO 5 PINNED
38. LOAD 1 LOADTYPE DEAD TITLE DEAD LOAD
39. MEMBER LOAD
40. 1 TO 4 UNI GY -1650

E:\Latihan Konstruksi\balok museum.anl

Page 1 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE
41.
42.
43.
44.
45.
46.
47.
48.
49.
50.

-- PAGE NO.

LOAD 2 LOADTYPE LIVE TITLE LIVE LOAD


MEMBER LOAD
1 CON GY -1000 1.852
2 CON GY -1000 1.948
3 4 CON GY -1000 2.4635
LOAD COMB 3 1.4DL
1 1.4
LOAD COMB 4 1.2DL+1.6LL
1 1.2 2 1.6
PERFORM ANALYSIS

P R O B L E M
S T A T I S T I C S
----------------------------------NUMBER OF JOINTS/MEMBER+ELEMENTS/SUPPORTS =

5/

4/

SOLVER USED IS THE OUT-OF-CORE BASIC SOLVER


ORIGINAL/FINAL BAND-WIDTH=
TOTAL PRIMARY LOAD CASES =
SIZE OF STIFFNESS MATRIX =
REQRD/AVAIL. DISK SPACE =

1/
1/
6 DOF
2, TOTAL DEGREES OF FREEDOM =
1 DOUBLE KILO-WORDS
12.0/ 143793.6 MB

***WARNING - INSTABILITY AT JOINT


5
DIRECTION = MX
PROBABLE CAUSE SINGULAR-ADDING WEAK SPRING
K-MATRIX DIAG= 1.3689139E+04 L-MATRIX DIAG= 3.6379788E-12 EQN NO
***NOTE - VERY WEAK SPRING ADDED FOR STABILITY

15

13

**NOTE** STAAD DETECTS INSTABILITIES AS EXCESSIVE LOSS OF SIGNIFICANT DIGITS


DURING DECOMPOSITION. WHEN A DECOMPOSED DIAGONAL IS LESS THAN THE
BUILT-IN REDUCTION FACTOR TIMES THE ORIGINAL STIFFNESS MATRIX DIAGONAL,
STAAD PRINTS A SINGULARITY NOTICE. THE BUILT-IN REDUCTION FACTOR
IS
1.000E-09
THE ABOVE CONDITIONS COULD ALSO BE CAUSED BY VERY STIFF OR VERY WEAK
ELEMENTS AS WELL AS TRUE SINGULARITIES.

51.
52.
53.
54.
55.
56.
57.
58.
59.

START CONCRETE DESIGN


CODE ACI
FC 2E+006 ALL
CLB 0.05 ALL
CLS 0.04 ALL
CLT 0.04 ALL
FYMAIN 2.4E+007 ALL
TRACK 0 ALL
DESIGN BEAM 1 TO 4

E:\Latihan Konstruksi\balok museum.anl

Page 2 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

=====================================================================
BEAM
LEN -

NO.

3704. MM

1 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2

73.
387.

B E A M

2 - 20MM
2 - 20MM

N O.

0.
2356.

1 D E S I G N

3090.
3704.

YES
NO

NO
YES

R E S U L T S - SHEAR

AT START SUPPORT - Vu=


24.77 KNS Vc=
59.50 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
3
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1477. MM
AT END
SUPPORT - Vu=
30.12 KNS Vc=
60.44 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1477. MM

___
1J____________________ 3703X 200X 450_____________________
2J____
|
|
|
===========================||
|
2No20|H 387.2356.TO 3704
|
| 9*12c/c189
|
|
|
9*12c/c189
|
| 2No20 H 73.
0.TO 3090
|
|
|
|
|
||==============================================================
|
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| |
| |
| |
| |
| |
| | oo | | oo |
| oo |
|
| |
| |
| |
| |
| |
| | 2#20| | 2#20|
| 2#20|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| |
|
|
|
| oo | | oo | | oo | | oo | | oo | | oo | | oo | |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

E:\Latihan Konstruksi\balok museum.anl

Page 3 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

=====================================================================
BEAM
LEN -

NO.

3896. MM

2 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2
3

73.
387.
387.

B E A M

2 - 20MM
2 - 20MM
2 - 20MM

N O.

824.
0.
2183.

2 D E S I G N

2909.
1550.
3896.

NO
YES
NO

NO
NO
YES

R E S U L T S - SHEAR

AT START SUPPORT - Vu=


25.21 KNS Vc=
58.61 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1573. MM
AT END
SUPPORT - Vu=
25.70 KNS Vc=
58.38 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1573. MM

___
2J____________________ 3895X 200X 450_____________________
3J____
|
|
||=============================
=================================||
| 2No20 H 387.
0.TO 1550|
|
|2No20 H|387.2183.TO 3896
|
| 10*12c/c189
|
|
|
|
|
|
|
|
10*12c/c189
|
|
2No20|H 73. 824.TO 2909 |
|
|
|
|
|
=========================================
|
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| oo | | oo | | oo | | oo | |
| | oo | | oo | | oo |
| oo |
| 2#20| | 2#20| | 2#20| | 2#20| |
| | 2#20| | 2#20| | 2#20|
| 2#20|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| |
| | 2#20| | 2#20| | 2#20| | 2#20| |
| |
|
|
|
|
| |
| | oo | | oo | | oo | | oo | |
| |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

E:\Latihan Konstruksi\balok museum.anl

Page 4 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

=====================================================================
BEAM
LEN -

NO.

4927. MM

3 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2
3

73.
387.
385.

B E A M

2 - 20MM
2 - 20MM
2 - 25MM

N O.

304.
0.
2204.

3 D E S I G N

3597.
1397.
4927.

NO
YES
NO

NO
NO
YES

R E S U L T S - SHEAR

AT START SUPPORT - Vu=


29.95 KNS Vc=
60.18 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM
AT END
SUPPORT - Vu=
37.65 KNS Vc=
56.72 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM

___
3J____________________ 4927X 200X 450_____________________
4J____
|
|
||====================
==========================================||
| 2No20 H 387.| 0.TO 1397
2No25 H|385.2204.TO|4927
|
| 13*12c/c189 | | |
| | | | | | |
13*12c/c189
|
|
2No20 H 73.|304.TO 3597
| | | | | | |
|
|
====================================================
|
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| oo | | oo | | oo | |
| | oo | | oo | | oo | | oo |
| oo |
| 2#20| | 2#20| | 2#20| |
| | 2#25| | 2#25| | 2#25| | 2#25|
| 2#25|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| |
| |
|
|
|
|
| | oo | | oo | | oo | | oo | | oo | |
| |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

E:\Latihan Konstruksi\balok museum.anl

Page 5 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

=====================================================================
BEAM
LEN -

NO.

4927. MM

4 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2

73.
385.

B E A M

2 - 20MM
2 - 25MM

N O.

585.
0.

4 D E S I G N

4927.
2108.

NO
YES

YES
NO

R E S U L T S - SHEAR

AT START SUPPORT - Vu=


42.51 KNS Vc=
59.49 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM
AT END
SUPPORT - Vu=
25.09 KNS Vc=
62.62 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM

___
4J____________________ 4926X 200X 450_____________________
5J____
|
|
||===============================
|
| 2No25 H 385.| 0.TO 2108| | |
|
| 13*12c/c189 | | | | | | |
13*12c/c189
|
|
2No20 H| 73. 585.TO|4927
|
|
==================================================================||
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| oo | | oo | | oo | | oo | |
| |
| |
| |
|
|
|
| 2#25| | 2#25| | 2#25| | 2#25| |
| |
| |
| |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20|
| 2#20|
|
| | oo | | oo | | oo | | oo | | oo | | oo | | oo |
| oo |
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

********************END OF BEAM DESIGN**************************

E:\Latihan Konstruksi\balok museum.anl

Page 6 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE
60.
61.
62.
63.

-- PAGE NO.

CONCRETE TAKE
MINMAIN 10 ALL
MAXMAIN 13 ALL
DESIGN BEAM 1 TO 4

E:\Latihan Konstruksi\balok museum.anl

Page 7 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

*** STAAD.Pro WARNING ***


INVALID MIN/MAX BAR SIZE SPECIFIED
VALID SIZES ARE: 6 ,8 ,10,12,16,20,25,32,40,50,60,60

=====================================================================
BEAM
LEN -

NO.

3704. MM

1 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2

73.
387.

B E A M

2 - 20MM
2 - 20MM

N O.

0.
2356.

1 D E S I G N

3090.
3704.

YES
NO

NO
YES

R E S U L T S - SHEAR

AT START SUPPORT - Vu=


24.77 KNS Vc=
59.50 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
3
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1477. MM
AT END
SUPPORT - Vu=
30.12 KNS Vc=
60.44 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1477. MM

E:\Latihan Konstruksi\balok museum.anl

Page 8 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

___
1J____________________ 3703X 200X 450_____________________
2J____
|
|
|
===========================||
|
2No20|H 387.2356.TO 3704
|
| 9*12c/c189
|
|
|
9*12c/c189
|
| 2No20 H 73.
0.TO 3090
|
|
|
|
|
||==============================================================
|
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| |
| |
| |
| |
| |
| | oo | | oo |
| oo |
|
| |
| |
| |
| |
| |
| | 2#20| | 2#20|
| 2#20|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| |
|
|
|
| oo | | oo | | oo | | oo | | oo | | oo | | oo | |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

*** STAAD.Pro WARNING ***


INVALID MIN/MAX BAR SIZE SPECIFIED
VALID SIZES ARE: 6 ,8 ,10,12,16,20,25,32,40,50,60,60

=====================================================================
BEAM
LEN -

NO.

3896. MM

2 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2
3

73.
387.
387.

B E A M

2 - 20MM
2 - 20MM
2 - 20MM

N O.

824.
0.
2183.

2 D E S I G N

2909.
1550.
3896.

NO
YES
NO

NO
NO
YES

R E S U L T S - SHEAR

AT START SUPPORT - Vu=


25.21 KNS Vc=
58.61 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1573. MM

E:\Latihan Konstruksi\balok museum.anl

Page 9 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

10

AT END
SUPPORT - Vu=
25.70 KNS Vc=
58.38 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 1573. MM

___
2J____________________ 3895X 200X 450_____________________
3J____
|
|
||=============================
=================================||
| 2No20 H 387.
0.TO 1550|
|
|2No20 H|387.2183.TO 3896
|
| 10*12c/c189
|
|
|
|
|
|
|
|
10*12c/c189
|
|
2No20|H 73. 824.TO 2909 |
|
|
|
|
|
=========================================
|
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| oo | | oo | | oo | | oo | |
| | oo | | oo | | oo |
| oo |
| 2#20| | 2#20| | 2#20| | 2#20| |
| | 2#20| | 2#20| | 2#20|
| 2#20|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| |
| | 2#20| | 2#20| | 2#20| | 2#20| |
| |
|
|
|
|
| |
| | oo | | oo | | oo | | oo | |
| |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

*** STAAD.Pro WARNING ***


INVALID MIN/MAX BAR SIZE SPECIFIED
VALID SIZES ARE: 6 ,8 ,10,12,16,20,25,32,40,50,60,60

=====================================================================
BEAM
LEN -

NO.

4927. MM

3 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2
3

73.
387.
385.

B E A M

2 - 20MM
2 - 20MM
2 - 25MM

N O.

304.
0.
2204.

3 D E S I G N

E:\Latihan Konstruksi\balok museum.anl

3597.
1397.
4927.

NO
YES
NO

NO
NO
YES

R E S U L T S - SHEAR

Page 10 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

11

AT START SUPPORT - Vu=


29.95 KNS Vc=
60.18 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM
AT END
SUPPORT - Vu=
37.65 KNS Vc=
56.72 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM

___
3J____________________ 4927X 200X 450_____________________
4J____
|
|
||====================
==========================================||
| 2No20 H 387.| 0.TO 1397
2No25 H|385.2204.TO|4927
|
| 13*12c/c189 | | |
| | | | | | |
13*12c/c189
|
|
2No20 H 73.|304.TO 3597
| | | | | | |
|
|
====================================================
|
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| oo | | oo | | oo | |
| | oo | | oo | | oo | | oo |
| oo |
| 2#20| | 2#20| | 2#20| |
| | 2#25| | 2#25| | 2#25| | 2#25|
| 2#25|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| |
| |
|
|
|
|
| | oo | | oo | | oo | | oo | | oo | |
| |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

*** STAAD.Pro WARNING ***


INVALID MIN/MAX BAR SIZE SPECIFIED
VALID SIZES ARE: 6 ,8 ,10,12,16,20,25,32,40,50,60,60

=====================================================================
BEAM
LEN -

NO.

4927. MM

4 DESIGN RESULTS - FLEXURE PER CODE ACI 318-05


FY -

235.

FC -

20.

MPA, SIZE -

200. X

450. MMS

LEVEL

HEIGHT
BAR INFO
FROM
TO
ANCHOR
(MM)
(MM)
(MM)
STA END
_____________________________________________________________________

1
2

73.
385.

2 - 20MM
2 - 25MM

E:\Latihan Konstruksi\balok museum.anl

585.
0.

4927.
2108.

NO
YES

YES
NO

Page 11 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

B E A M

-- PAGE NO.

N O.

4 D E S I G N

12

R E S U L T S - SHEAR

AT START SUPPORT - Vu=


42.51 KNS Vc=
59.49 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM
AT END
SUPPORT - Vu=
25.09 KNS Vc=
62.62 KNS Vs=
0.00 KNS
Tu=
0.00 KN-MET Tc=
1.7 KN-MET Ts=
0.0 KN-MET LOAD
1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 189. MM C/C FOR 2089. MM

___
4J____________________ 4926X 200X 450_____________________
5J____
|
|
||===============================
|
| 2No25 H 385.| 0.TO 2108| | |
|
| 13*12c/c189 | | | | | | |
13*12c/c189
|
|
2No20 H| 73. 585.TO|4927
|
|
==================================================================||
|
|
|___________________________________________________________________________|
_____
_____
_____
_____
_____
_____
_____
_____
_____
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
| oo | | oo | | oo | | oo | |
| |
| |
| |
|
|
|
| 2#25| | 2#25| | 2#25| | 2#25| |
| |
| |
| |
|
|
|
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|
| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20| | 2#20|
| 2#20|
|
| | oo | | oo | | oo | | oo | | oo | | oo | | oo |
| oo |
|
| |
| |
| |
| |
| |
| |
| |
|
|
|
|_____| |_____| |_____| |_____| |_____| |_____| |_____| |_____|
|_____|

********************END OF BEAM DESIGN**************************

64. CONCRETE TAKE


65. END CONCRETE DESIGN

E:\Latihan Konstruksi\balok museum.anl

Page 12 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

-- PAGE NO.

13

************** CONCRETE TAKE OFF **************


(FOR BEAMS AND COLUMNS DESIGNED ABOVE)
TOTAL VOLUME OF CONCRETE =

110.95 CU.FT

BAR SIZE
NUMBER
-------12
20
25

WEIGHT
(in lbs)
-------456.96
408.32
163.81
-----------*** TOTAL=
1029.09

66. FINISH

*********** END OF THE STAAD.Pro RUN ***********


**** DATE= NOV 26,2016

TIME= 17: 0:32 ****

************************************************************
*
For questions on STAAD.Pro, please contact
*
*
Research Engineers Offices at the following locations *
*
*
*
Telephone
Email
*
* USA:
+1 (714)974-2500
support@bentley.com
*
* CANADA
+1 (905)632-4771
detech@odandetech.com *
* UK
+44(1454)207-000
support@bentley.com
*
* NORWAY
+47 67 57 21 30
staad@edr.no
*
* SINGAPORE +65 6225-6158
support@bentley.com
*
* INDIA
+91(033)4006-2021
support@bentley.com
*
* JAPAN
+81(03)5952-6500
eng-eye@crc.co.jp
*
* CHINA
+86(411)8479-1166
support@bentley.com
*
* THAILAND +66(0)2645-1018/19
support@bentley.com
*
*
*
* North America
support@bentley.com
*
* Europe
support@bentley.com
*
* Asia
support@bentley.com
*
************************************************************

E:\Latihan Konstruksi\balok museum.anl

Page 13 of 14

Saturday, November 26, 2016, 05:02 PM


STAAD SPACE

E:\Latihan Konstruksi\balok museum.anl

-- PAGE NO.

14

Page 14 of 14

You might also like