You are on page 1of 3

SIEMENS

MLFB code :
serial no.:
software :
order no. :

7VE6110-5EB02-0AA0/BB
BF0402062534
V04.00.08
802473/82

date of test:
test equip. :
tested by
:
page no.
:

24.02.2004 20:27:46
OMICRON UPS-10 / V04.01
655
1 / 3

Auxiliary voltage / Hilfsspannung


| setpoint
|
|
|

|meas. value| unit | deviation| phase | remarks / communication

220.000 |
29.000 |
6.500 |

219.960 | V
28.547 | mA
6.248 | W

| -0.02 % |
| -0.45 mA |
| -0.25 W |

| aux. voltage
| dc current
| power consumption

| stat.|
| PASS |
| PASS |
| PASS |

Test result: PASS

MLFB-Compare / MLFB-Vergleich
DEV-MLFBNr=7VE61105EB020AA0---------------Bootsystem=01.04.01
Test result: PASS

DEV-BFNr=BF0402062534

DEV-Soft=04.00.08

Hardware test
Max. Relay count= 11
LED test: OK
Display test: OK
Battery test: OK
Device clock: Date=24.2.2004
Test result: PASS

Time=20:29:53

HWT keyboard test / Folien-Tastatur


Test result: PASS

HWT binary inputs / Binr-Eingnge


Max. Bin-Input count= 6
Test result: PASS

HWT relay outputs / Relais-Ausgnge


Test result: PASS

HWT communication ports / Schnittstellen


Location A: DCF77-Interface : OK
Location C: Modem-Interface = RS485 : OK
Test result: PASS

Channel phase angle / Phasenwinkel


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

0.000
0.000
240.000
240.000
240.000
0.000
240.000

0.012
0.023
240.008
240.001
240.003
-0.002
240.003

Test result: PASS

|
|
|
|
|
|
|

| 0.01
| 0.02
| 0.01
| 0.00
| 0.00
| -0.00
| 0.00

|
|
|
|
|
|
|

L123E
L123E
L123E
L123E
L123E
L123E
L123E

|
|
|
|
|
|
|

50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:

Ub-Ua
Uc-Ua
Ud-Ua
Ue-Ua
Uf-Ua
Ug-Ua
Uh-Ua

PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|

SIEMENS
MLFB code :
serial no.:
software :
order no. :

7VE6110-5EB02-0AA0/BB
BF0402062534
V04.00.08
802473/82

date of test:
test equip. :
tested by
:
page no.
:

24.02.2004 20:27:46
OMICRON UPS-10 / V04.01
655
2 / 3

Channel correction factor / Abgleichfaktor


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000
1000.000

1002.520
995.596
994.415
992.963
1001.342
995.742
1001.195
999.460
999.091
993.160
992.080
990.573
998.070
993.377
997.835
996.138
998.486
994.118
992.628
990.704
997.201
994.197
997.267
995.289

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

0.25
-0.44
-0.56
-0.70
0.13
-0.43
0.12
-0.05
-0.09
-0.68
-0.79
-0.94
-0.19
-0.66
-0.22
-0.39
-0.15
-0.59
-0.74
-0.93
-0.28
-0.58
-0.27
-0.47

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

Ua
|
1.109|
1.103|
1.043|
-0.019|
1.080|
-0.006|
-0.028|
Ua
|
1.362|
1.377|
1.298|
0.010|
1.330|
0.013|
-0.014|
Ua
|
0.366|
0.328|
0.271|
-0.032|
0.339|
0.001|
-0.031|

50Hz Kl. Q 1-Q 2


50Hz Kl. Q 3-Q 4
50Hz Kl. Q 5-Q 6
50Hz Kl. Q 7-Q 8
50Hz Kl. Q 9-Q10
50Hz Kl. Q11-Q12
50Hz Intern
50Hz Intern
60Hz Kl. Q 1-Q 2
60Hz Kl. Q 3-Q 4
60Hz Kl. Q 5-Q 6
60Hz Kl. Q 7-Q 8
60Hz Kl. Q 9-Q10
60Hz Kl. Q11-Q12
60Hz Intern
60Hz Intern
16.67Hz Kl. Q 1-Q 2
16.67Hz Kl. Q 3-Q 4
16.67Hz Kl. Q 5-Q 6
16.67Hz Kl. Q 7-Q 8
16.67Hz Kl. Q 9-Q10
16.67Hz Kl. Q11-Q12
16.67Hz Intern
16.67Hz Intern

PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

Test result: PASS

Voltage analog inputs / Spannung analoge Eingnge


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000
100.000

99.986
100.001
99.998
99.998
99.998
100.004
99.991
99.997
99.996
100.001
99.987
100.001
99.992
99.995
99.992
99.989
100.008
100.004
100.007
99.994
99.984
99.989
100.009
99.992

Test result: PASS

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

-0.01
0.00
-0.00
-0.00
-0.00
0.00
-0.01
-0.00
-0.00
0.00
-0.01
0.00
-0.01
-0.00
-0.01
-0.01
0.01
0.00
0.01
-0.01
-0.02
-0.01
0.01
-0.01

%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

Ua
Ub
Uc
Ud
Ue
Uf
Ug
Uh
Ua
Ub
Uc
Ud
Ue
Uf
Ug
Uh
Ua
Ub
Uc
Ud
Ue
Uf
Ug
Uh

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
16Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
50Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:
60Hz:

Q 1-Q 2
Q 3-Q 4
Q 5-Q 6
Q 7-Q 8
Q 9-Q10
Q11-Q12
Intern
Intern
Q 1-Q 2
Q 3-Q 4
Q 5-Q 6
Q 7-Q 8
Q 9-Q10
Q11-Q12
Intern
Intern
Q 1-Q 2
Q 3-Q 4
Q 5-Q 6
Q 7-Q 8
Q 9-Q10
Q11-Q12
Intern
Intern

PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|

SIEMENS
MLFB code :
serial no.:
software :
order no. :

7VE6110-5EB02-0AA0/BB
BF0402062534
V04.00.08
802473/82

date of test:
test equip. :
tested by
:
page no.
:

24.02.2004 20:27:46
OMICRON UPS-10 / V04.01
655
3 / 3

Operating buffer / Betriebsmeldungen


Test result: PASS

Test parameter / Grund-Parameterierung


161: SYNC Function group 1= 1phase Synchro check
6101: Synchronizing Function= ON
Test result: PASS

Operational measuring values / Betriebsmewerte


3Ph-System: Fart=F-20

Ik=0.000A Uk=100.000V Pk=0.0

Freq=50.00Hz

| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|

100.000
100.000
100.000
100.000
100.000
100.000
50.000
50.000
50.000
50.000
50.000
50.000

100.000
100.000
100.000
100.000
100.000
100.000
50.000
50.000
50.000
50.000
50.000
50.000

3Ph-System: Fart=F-20

|
|
|
|
|
|
|
|
|
|
|
|

V
V
V
V
V
V
Hz
Hz
Hz
Hz
Hz
Hz

|
|
|
|
|
|
|
|
|
|
|
|

0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00

%
%
%
%
%
%
%
%
%
%
%
%

|
|
|
|
|
|
|
|
|
|
|
|

|
|
|
|
|
|
|
|
|
|
|
|

Ik=0.000A Uk=100.000V Pk=0.0

Voltage Ua
Voltage Ub
Voltage Uc
Voltage Ud
Voltage Ue
Voltage Uf
Frequency fa
Frequency fb
Frequency fc
Frequency fd
Frequency fe
Frequency ff

PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|
|
|
|
|
|

Freq=50.00Hz

| setpoint

|meas. value| unit | deviation| phase | remarks / communication

| stat.|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

|
|
|
|
|
|
|

100.000
50.000
100.000
50.000
0.000
0.000
0.000

100.000
50.000
99.900
50.000
0.000
0.000
0.000

|
|
|
|
|
|
|

V
Hz
V
Hz
V
Hz

| 0.00 %
| 0.00 %
| -0.10 %
| 0.00 %
| 0.00 V
| 0.00 Hz
| 0.00

|
|
|
|
|
|
|

|
|
|
|
|
|
|

U1
f1
U2
f2
dU
df
dalpha

PASS
PASS
PASS
PASS
PASS
PASS
PASS

|
|
|
|
|
|
|

Test result: PASS

Synchronization 98V and 102V


| setpoint

|meas. value| unit | deviation| phase | remarks / communication

|
|
|
|

|
|
|
|

1.000
98.000
1.000
102.000

1.000
97.982
1.000
101.951

|
|
|
|

dig
V
dig
V

| 0.00 %
| -0.02 %
| 0.00 %
| -0.05 %

|
|
|
|

OFF
-

|
|
|
|

| stat.|

Sync Start R3
|
Synchronization dU=-2V Stop-R1|
Sync Start R3
|
Synchronization dU=+2V Stop-R1|

Test result: PASS

Original start / Uranlauf


6101: Synchronizing Function= OFF
161: SYNC Function group 1= Disabled
Buffer Initial-Start: PASS
MLFB-Nr= 7VE61105EB020AA0----------------

Software= V04.00.08 : Test result: PASS

PASS
PASS
PASS
PASS

|
|
|
|