42DW

HORIZONTAL DUCTED FAN COIL UNITS


Unit size

42DWC 07

42DWC 09

42DWC 12

42DWC 16

42DWD 09

42DWD 16

Low

Medium High

Low

Medium High

Low

Low

Low

Low

l/s
m3/h
Pa

228
820
40

250
900
50

260
935
55

253
910
35

303
1090
50

349
1256
65

478 562
1719 2024
35
50

632
2276
60

601 655
2162 2359
40
50

692
2491
55

301 368
1083 1323
0
0

433
1560
0

658 738
2369 2655
0
0

805
2899
0

Water pressure drop

kW
kW
l/s
l/h
kPa

5.08
4
0.24
870
16

5.5
4.33
0.26
940
21.1

5.67
4.47
0.27
980
23.2

5.88
4.54
0.28
1020
16.1

6.81
5.32
0.33
1170
21.5

7.69
6.05
0.38
1355
27.5

9.29
7.53
0.45
1630
38

11.15
9.28
0.54
1950
55

12.44
10
0.59
2135
48.3

13.39
10.59
0.64
2305
56.1

13.65
10.72
0.67
2425
58.4

6.34
4.92
0.31
1110
26

7.33
5.79
0.35
1275
32

8.19
6.55
0.40
1425
39

11.32
9.38
0.56
2010
48

12.12
10.16
0.60
2150
54

12.64
10.69
0.63
2250
58

2-pipe heating mode


Heating capacity*

kW

6.74

7.28

7.6

7.95

9.31

10.5

13.09 14.8

16.26

17.35 18.71

19.76

Water pressure drop

kW
l/h
l/h
kPa

8.24
0.19
700
15

9.3
0.22
775
17

10.15
0.24
850
21

15.35
0.35
1265
45

16.41
0.38
1370
51

17.28
0.40
1440
56

Electric heater capacity

3000

Sound levels
Sound power level
Sound pressure level**
NR value***

dBA
dBA

51
33
28

71
58
48

73
55
50

Electrical data
Power supply
Power input
Current draw

V-ph-Hz
W
A

230-1-50
85
95
0.37 0.41

Dimensions
Coil outlet/inlet diameter
Length A
Height B
Depth C
Weight

inch
mm
mm
mm
kg

3/4
925
285
750
35

Fan speed
Fan
Air flow

HORIZONTAL DUCTED FAN COIL UNITS 42DW

Static pressure
Cooling mode
Total cooling capacity*
Sensible cooling capacity*
Water flow rate

4-pipe heating mode


Heating capacity*
Water flow rate

3000
53
35
30

10.36
8.52
0.51
1825
45

3000

54
36
31

52
34
29

105
0.45

230-1-50
125 165
0.55 0.71
3/4
925
285
750
37

Medium High

56
38
33

Medium High

3000

60
42
37

57
39
34

61
43
38

195
0.85

230-1-50
265 310
1.16 1.37

3000

63
45
40

63
45
40

360
1.57

230-1-50
370 410
1.63 1.76

3/4
1325
285
750
48

Medium High

65
47
42

3000

67
49
44

53
35
30

450
1.94

230-1-50
135 175
0.58 0.76

3/4
1325
285
750
53

Medium High

58
40
35

63
45
40

69
51
46

220
0.95

230-1-50
400 460
1.82 2.04

3/4
925
285
750
37

Based on standard Eurovent conditions:


Cooling 27C db/19C wb air temperature, 7C/12C entering/leaving water temperature
2-pipe heating: 20C air temperature, 50C entering water temperature, same water flow rate as in cooling
4-pipe heating: 20C air temperature, 70C/60C entering/leaving water temperature

**

Sound pressure levels are based on a hypothetical acoustic attenuation for the room and the system (diffuser, ductwork, ceiling) of -18 dB(A) for a 2-pipe system

3/4
1325
285
750
53

Dimensions

35BD/SR linear diffuser (supply and return air)

510
2.24

Electronic thermostat

Two versions, A and B, with potentiometer


Automatic or manual three-speed selection
Automatic or manual change-over
Electric heat control
Comfort/economy/frost protection modes

FEATURES

Available in four sizes with two-pipe, two-pipe plus electric heater or four-pipe
coils, with an air flow range from 230 to 800 l/s, a cooling capacity range
from 5 to 14 kW and a heating capacity range from 7 to 20 kW

Compact ducted chilled-water fan coil units, designed for installation above
false ceilings

Reliable and efficient heating and cooling for light commercial and residential
applications

Minimised size, using a V-shaped coil, and reduced height of 285 mm

Air return from the rear or below for increased installation flexibility

Air outlet modularity (sleeve or spigots), outlets on the front or at the sides

High-capacity unit with low sound levels

Four-speed motor, offering a choice of two medium comfort speeds

High-pressure centrifugal fans

Compatible with the 35BD/SR air diffuser range

Safe factory-installed electric heater for single or two-stage hot water heating

Low hydraulic pressure drop with a valve mounted, compatible with all chiller
pump kits

Quick installation with factory-installed options (controls, valves)

Improved market competitiveness

HDB controller

Digital display or infra-red terminal


Unit grouping capability
Adjustable settings and parameters
Timer and daily scheduling
NTC communicating controller

Network communication
Aquasmart Evolution system compatible
IAQ and DCV management
Motorised blinds and lighting control

OPTIONS/ACCESSORIES

Factory-installed two- or four-way valves


High-efficiency filter

42DW HORIZONTAL DUCTED FAN COIL UNITS

STANDARD CONTROLS