AL SAIL FACTORY

Calculation for Fire Fighting System:


References:
NFPA 10 Standard for portable fire extinguisher.
NFPA 13 Standard for the installation of automatic sprinkler system.
NFPA 14 Standard for the installation of standpipe and hose system.
NFPA 20 Standard for the installation of stationary pumps for fire protection.
NFPA 22 Standard for water tanks for private fire protection.
Sprinkler system is designed to the following hazard class:
A
Type of occupancy
Hazard class of protection
Min design density of discharge
Assumed area of protection
Max area coverage per sprinkler
Type of sprinkler
Orifice size
Orifice K-factor
Duration of water supply
Inside / outside hose flow

:
:
:
:
:
:
:
:
:
:

Offices.
Light Hazard -1
0.1 gpm /ft
1500 ft
130 ft
Standard response
1/2"
5.6
60 minutes
250 gpm

B
Type of occupancy
Hazard class of protection
Min design density of discharge
Assumed area of protection
Max area coverage per sprinkler
Type of sprinkler
Orifice size
Orifice K-factor
Duration of water supply
Inside / outside hose flow

:
:
:
:
:
:
:
:
:
:

Stores.
Ordinary Hazard group -1
0.15 gpm /ft
1500 ft
130 ft
Standard response
1/2"
5.6
60 minutes
250 gpm

C
Type of occupancy
Hazard class of protection
Min design density of discharge
Assumed area of protection
Max area coverage per sprinkler
Type of sprinkler
Orifice size
Orifice K-factor
Duration of water supply
Inside / outside hose flow

:
:
:
:
:
:
:
:
:
:

Workshop.
Ordinary hazard group -1
0.25 gpm /ft
1500 ft
130 ft
Early Suppression Fast response
3/4"
11.2
60 minutes
250 gpm

D
Type of occupancy
Hazard class of protection
Min design density of discharge
Assumed area of protection
Max area coverage per sprinkler
Type of sprinkler
Orifice size
Orifice K-factor
Duration of water supply
Inside / outside hose flow

:
:
:
:
:
:
:
:
:
:

Fire Pump Room.


Extra hazard group -2
0.2 gpm / ft
2500 ft2
100 ft2
Standard response
1/2"
5.6
60 minutes
250 gpm
2

Calculation Summary:
With reference to the attached hydraulic calculations
For most demand.
Calculated system flow rate : 620 gpm
Calculated inflow residual pressure : 56 psi
Assume factor of safety = 1.10
Flow = 620 x 1.10 = 682 gpm
Pressure = 56 x 1.10 = 61.6 psi

Pump selection
Choose Electric pump capacity 750 gpm @ 70 psi
Choose Diesel pump capacity 750 gpm @ 70 psi

Fire water tank capacity


Pump discharge = 750 gpm
Duration = 60 minutes
Fire Tank = 750 * 60 = 45000 g
Selected Fire Tank 170 M3.

Diesel tank capacity


Fire pump engine fuel consumption = 0.063 gpm
Refer to attached fire pump engine installation / operation data
For one day
Diesel tank capacity = 0.063 gpm x 60 x 24 = 90.72 gal
Refer to attached diesel tank data sheet,
Select double wall tank 120 gal capacity (with L = 1117 mm, D = 711 mm)