Appendix A

Technical Data
Item

Drawing Title

Drawing No. Rev.

1.

Technical Data Sheets (at 40 deg.C)

MRJE417632

2.

Technical Data Sheets (at 15 deg.C)

MRJE417640

3.

Technical Data Sheets (for UK, Europe grid)

MRJE417846

4.

Generator Capability Curves (for 50Hz)

MRJE417634

5.

Generator Capability Curves (for 60Hz)

MRJE417633

6.

Generator Capability Curves (for UK, Europe grid)

MRJE417838

7.

Generator Capability Diagram (for 50Hz)

MRJE417636 B

8.

Generator Capability Diagram (for 60Hz)

MRJE417635

9.

Generator Capability Diagram (for UK, Europe grid)

MRJE417839

10.

Generator Efficiency Curves with Load (for 50Hz at 40 deg.C)

MRJE417799

11.

Generator Efficiency Curves with Load (for 60Hz at 40 deg.C)

MRJE417798

12.

Generator Efficiency Curves with Load (for 50Hz at 15 deg.C)

MRJE417797

13.

Generator Efficiency Curves with Load (for 60Hz at 15 deg.C)

MRJE417796

14.

Generator Efficiency Curves with Load (for UK, Europe grid)

MRJE417837

15.

Calculated Generator Characteristics (for 50Hz at 40 deg.C)

MRJE417638

16.

Calculated Generator Characteristics (for 60Hz at 40 deg.C)

MRJE417637

17.

Calculated Generator Characteristics (for 50Hz at 15 deg.C)

MRJE417646

18.

Calculated Generator Characteristics (for 60Hz at 15 deg.C)

MRJE417645

19.

Calculated Generator Characteristics (for UK, Europe grid)

MRJE417840

20.

Permissible Duration of Negative Phase Sequence Current


MRJE417668

MRJE417667

MRJE417639

MRJE417841

(for 50Hz at 40 deg.C)


21.

Permissible Duration of Negative Phase Sequence Current


(for 60Hz at 40 deg.C)

22.

Permissible Duration of Negative Phase Sequence Current


(at 15 deg.C)

23.

Permissible Duration of Negative Phase Sequence Current


(for UK, Europe grid)

24.

Recommended Alarm & Trip Settings

MRJE418223

25.

Generator Voltage Exciter Field Current (for 60Hz at 15 deg.C)

MRJE417812

26.

Generator Voltage Exciter Field Current (for 50Hz at 15 deg.C)

MRJE417813

27.

Generator Voltage Exciter Field Current (for 60Hz at 40 deg.C)

MRJE417814

28.

Generator Voltage Exciter Field Current (for 50Hz at 40 deg.C)

MRJE417815

29.

Generator Voltage Exciter Field Current (for UK, Europe grid)

MRJE417844

30.

V-Curve (for 60Hz at 15 deg.C)

MRJE417804

31.

V-Curve (for 50Hz at 15 deg.C)

MRJE417805

32.

V-Curve (for 60Hz at 40 deg.C)

MRJE417806

33.

V-Curve (for 50Hz at 40 deg.C)

MRJE417807

34.

V-Curve (for UK, Europe grid)

MRJE417843

35.

Voltage & Frequency Limits

MRJE417631

36.

Voltage & Frequency Limits (for UK, Europe grid)

MRJE417842

37.

Volts / Hz Capability curve

MRJE417834 A

38.

Volts / Hz Capability curve (for UK, Europe grid)

MRJE417845 A

39.

Data Sheet for Exciter (at 15 deg.C)

MRJE417816 B

40.

Data Sheet for Exciter (at 40 deg.C)

MRJE417817 B

41.

Data Sheet for Exciter (for UK, Europe grid)

MRJE417849 B

42.

Characteristics Curves of Exciter (for 120Hz at15 deg.C)

MRJE417808 A

43.

Characteristics Curves of Exciter (for 100Hz at15 deg.C)

MRJE417809 A

44.

Characteristics Curves of Exciter (for 120Hz at40 deg.C)

MRJE417810

45.

Characteristics Curves of Exciter (for 100Hz at40 deg.C)

MRJE417811

46.

Exciter Open Circuit & Loaded Characteristics (for 60Hz at15 deg.C) MRJE418140

47.

Exciter Open Circuit & Loaded Characteristics (for 50Hz at15 deg.C) MRJE418141

48.

Data Sheet for PMG (at 15 deg.C)

MRJE417852

49.

Data Sheet for PMG (at 40 deg.C)

MRJE417853

50.

Characteristics Curves of PMG

MRJE417851 B

51.

Stator Winding Earth Fault Current versus Time

MRJE417854 A

Ref. : MRJE417846B -1/4


Customer : GE Energy / Aero Products Inc.

Date : 10 Aug. 2004

INFORMATION TO BE PROVIDED BY MANUFACTURER

Frequency

50 Hz

Governing Standard

IEC 60034 ( For UK, Europe grid )

E. Type of Cooling System

Open Ventilated

No. of Poles

A. Manufacturer

Meidensha Corporation, Tokyo, Japan

B. Model Number

800 LL04

C. Rotor Type
D.

TEWAC

Cylindrical Solid Rotor

Rated MVA

49.500

Rated kV

11.5

Rated Power Factor

0.8

Rated Speed, RPM

3000

Rated C. W. Temp. deg. C


Rated Air Temp. deg. C

30
40

F. Cooling System Fan Materials


G. Cooling System Air Flow, m3/min
Ext. Press. Drop, mmAq max.

Aluminium alloy
1074
40

1.04.9

H. Water Press. Range, 10 Pascal

305

I. Water Temp. Range, deg. C


Water Flow Rate, m3/hr
J. Bearing Type
K. Bearing Seal Type

185
Bracket/sleeve
Labyrinth sealing

L. Lube Oil Press. Range, Pascal

2.0 105

M. L. O. Flow Rate Range, L/min

150

Heat Rejection, kW
N.

Exciter Type

49
Brushless with a PMG Pilot Exciter

Exciter Field Current, A


At No Load Rated Voltage

1.8

At Full Load Rated Voltage

5.4

At Max. Field Forcing

9.8

Exciter Field Voltage, V

at 20/100/110 deg.C

At No Load Rated Voltage

15.8/20.9/21.4

At Full Load Rated Voltage

47.5/62.6/64.3

At Max. Field Forcing

86.2/114/117

Inherent Volt. Regulation, %

39

Ref. : MRJE417846B -2/4


Customer : GE Energy / Aero Products Inc.

Date : 10 Aug. 2004

INFORMATION TO BE PROVIDED BY MANUFACTURER

Frequency
Governing Standard
E. Type of Cooling System
No. of Poles
O.

50 Hz
IEC 60034 ( For UK, Europe grid )
Open Ventilated

TEWAC

DC Resistance, Ohms
at 20/100/110 deg. C
Generator rotor
Exciter field

0.470/0.617/0.636
8.80/11.6/11.9

P. DC Resistance of Stator, Ohms


per phase at 20/100/110 deg. C
Q.

0.0030/0.0039/0.0041

Efficiency at Rated Power


Factor, in %
Full load

98.2

3/4 load

98.0

1/2 load

97.5

1/4 load

95.7

R. Heat Loss Data, kW


S.

725

Reactances, at Continuous
Rated kVA and at 40 deg. C, %

T.

Xd (Unsat.)

226

X d (Sat.)

21.0

X d (Sat.)

15.0

X2 (Unsat)

17.0

Xo (Unsat.)

10.0

Xq (Unsat.)

213

X q (Unsat.)

22.0

X q (Sat.)

15.0

Short Circuit Ratio

0.5

Time Constants, in seconds


at 20 deg. C
T do

7.0

T d

0.64

T do

0.039

T d

0.028

Ref. : MRJE417846B -3/4


Customer : GE Energy / Aero Products Inc.

Date : 10 Aug. 2004

INFORMATION TO BE PROVIDED BY MANUFACTURER

Frequency

50 Hz

Governing Standard

IEC 60034 ( For UK, Europe grid )

E. Type of Cooling System

Open Ventilated

No. of Poles
U.

TEWAC

Capacitance of Stator to
Earth,F per phase

0.20
2

V. Total Moment of Inertia, WR ,


2

kg - m

940

W. Inertia Constant, H,
kWsec/kVA
X.

Weights. Kg
Rotor

14500

Stator

57000

Total
Y.

AA.

76000

81500

2.57

3.45

Dimensions, meters
Height

Z.

0.94

Width

2.638

Depth

7.46

Curves
Efficiency curves

MRJE417837A

Output vs. Air Temp

MRJE417838A

Capability Diagram

MRJE417839A

Open and Short Circuit

MRJE417840A

Open and Short Circuit with exciter

MRJE417844A

V - Curve

MRJE417843A

Negative Sequence Current

MRJE417841A

Voltage/Frequency Variation

MRJE417842B

Volts / Hz Capability

MRJE417845A

Drawings
General Arrangement

MR4R101531C

MR4R101532C

Rotor Geometry

MRBA210664

Wiring Diagrams

MREL110209B

Excitation System Model

By GEAEP

AVR Details

By GEAEP

Ref. : MRJE417846B -4/4


Customer : GE Energy / Aero Products Inc.

Date : 10 Aug. 2004

INFORMATION TO BE PROVIDED BY MANUFACTURER

RATING:49500KVA-2P-11500V-50Hz-0.8PF
Reactance data (per unit)
X1 : Leakage Reactance

0.13

X2 : Unsaturated Negative Sequence Reactance

0.17

X0 : Unsaturated Zero Sequence Reactance

0.10

Armature DC Component Time Constant Data ( Sec. at 100 deg.C)


Ta3 : Three Phase Short Circuit

0.39

Ta2 : Line to Line Short Circuit

0.45

Ta1 : Line to Neutral Short Circuit

0.86

Armature Winding Sequence Resistance Data (per unit)


R1 : Positive

0.0045

R2 : Negative

0.014

R0 : Zero

0.0015

Surge impedance (Ohms)

75

Full load & No load synchronous power (kW)

71,280 / 56,030

Synchronous coefficient (kW/rad.)

55504

Damping coefficient (per unit)

0.21

X/R ratio at 100 deg. C base

102

Motoring power(kW)

395

Magnetic centering force (kg) at the max. declination (0.25mm)

6.5

Description

Direct Axis

Quadrature Axis

Saturated synchronous reactance

Xdv

200%

Xqv

188%

Unsaturated synchronous reactance

Xdi

226%

Xqi

213%

Saturated transient reactance

Xdv

21%

Xqv

20%

Unsaturated transient reactance

Xdi

23%

Xqi

22%

Saturated subtransient reactance

Xdv

15%

X qv

15%

Unsaturated substransient reactance

Xdi

17%

Xqi

17%

Transient open-circuit time constant

T do

7.0 Sec.

Tqo

2.4 Sec.

Transient short-circuit time constant

T d

0.64 Sec.

Tq

0.17 Sec.

Sub-Transient open-circuit time constant

T do

0.039 Sec.

Tqo

0.22 Sec.

Sub-Transient short-circuit time constant

T d

0.028 Sec.

Tq

0.17 Sec.

Ref. No. MRJE418223


Recommended Alarm & Trip Settings
For 72,000kVA-13.8kV-60Hz-p.f0.85 at 15 deg. C (ANSI C50.14)

Item
Stator Winding Temperature (by RTD)
Lube Oil Outlet Temperature (by RTD)
Bearing Metal Temperature (by RTD)
Thrust Bearing Metal Temperature (by RTD)
Air Inlet Temperature (by RTD)
Exciter Air Outlet Temperature (by RTD)
Generator Air Outlet Temperature (by RTD)
Shaft Relative Vibration (Peak to Peak)

Alarm
120 deg. C
85 deg. C
100 deg. C
115 deg. C
45 deg. C
90 deg. C
90 deg. C
100 m 3)

Trip
130 deg. C
90 deg. C
105 deg. C
120 deg. C
55 deg. C
100 deg. C
100 deg. C
150 m 3)

Note;
1) Protection relay settings shall be confirmed in accordance with the generator characteristic data.
2) Lube oil & Bearing temperature settings are based on Lube oil inlet temperature at 60 deg. C.
3) Multiplier X1.5 during Start-up & Shut down.

For 64,500kVA-11.5kV-50Hz-p.f0.8 at 15 deg. C (IEC-60034)

Item
Stator Winding Temperature (by RTD)

Alarm
134 deg. C

Trip
144 deg. C

Lube Oil Outlet Temperature (by RTD)

85 deg. C

90 deg. C

Bearing Metal Temperature (by RTD)

100 deg. C

105 deg. C

Thrust Bearing Metal Temperature (by RTD)

105 deg. C

110 deg. C

Air Inlet Temperature (by RTD)

45 deg. C

55 deg. C

Exciter Air Outlet Temperature (by RTD)

90 deg. C

100 deg. C

Generator Air Outlet Temperature (by RTD)

90 deg. C

100 deg. C

Shaft Relative Vibration (Peak to Peak)

100 m

3)

150 m 3)

Note;
1) Protection relay settings shall be confirmed in accordance with the generator characteristic data.
2) Lube oil & Bearing temperature settings are based on Lube oil inlet temperature at 60 deg. C.
3) Multiplier X1.5 during Start-up & Shut down.

For 49,500kVA-11.5kV-50Hz-p.f0.8 at 40 deg. C (UK, Europe grid)

Item
Stator Winding Temperature (by RTD)

Alarm
134 deg. C

Trip
144 deg. C

Lube Oil Outlet Temperature (by RTD)

85 deg. C

90 deg. C

Bearing Metal Temperature (by RTD)

100 deg. C

105 deg. C

Thrust Bearing Metal Temperature (by RTD)

105 deg. C

110 deg. C

Air Inlet Temperature (by RTD)

45 deg. C

55 deg. C

Exciter Air Outlet Temperature (by RTD)

90 deg. C

100 deg. C

Generator Air Outlet Temperature (by RTD)

90 deg. C

100 deg. C

Shaft Relative Vibration (Peak to Peak)

100 m

3)

150 m 3)

Note;
3) Protection relay settings shall be confirmed in accordance with the generator characteristic data.
4) Lube oil & Bearing temperature settings are based on Lube oil inlet temperature at 60 deg. C.
3) Multiplier X1.5 during Start-up & Shut down.

MRJE418223

Ref. : MRJE417849B-1/2
Customer : GE Energy / Aero Products Inc.

Date : 29 Sep. 2004

DATA SHEET FOR EXCITERat 40 deg.C

Frequency
Governing Standard
E. Type of Cooling System

100 Hz
IEC 60034 (For UK, Europe grid)
Open Ventilated

TEWAC

No. of Poles

No. of Phase

Three

Rotor Type

Salient Pole

Rated KVA

203

Rated V

280

Rated Power Factor

0.9

Rated Speed (RPM)

3000

Exciter Field Current (A)


Exciter rated voltage at N.L ( i0 )

3.4

Exciter rated current at S.C ( i2 )

5.1

Exciter rated load ( i3 )

8.0

Generator rated voltage at N.L

1.8

( i00 )
Generator rated current at S.C

3.4

( i22 ) at 40 deg.C
Generator rated load ( i33 ) at 40 deg.C

5.4

At Max. Field Forcing

12.0

Exciter Field Voltage (V) at 20/100/110 deg. C


Exciter rated voltage at N.L ( i0 )

29.9/39.4/40.5

Exciter rated current at S.C ( i2 )

44.9/59.2/60.7

Exciter rated load ( i3 )

70.4/92.8/95.2

Generator rated voltage at N.L

15.8/20.9/21.4

( i00 )
Generator rated current at S.C

29.9/39.4/40.5

( i22 ) at 40 deg.C
Generator rated load ( i33 ) at 40 deg.C
At Max. Field Forcing

47.5/62.6/64.3
106/139/143

DC Resistance ohms at 20/100/110 deg. C


Armature coil
Field coil

0.00449/0.00590/0.00607
8.8/11.6/11.9

Xd sat

150

X d sat

22

Ref. : MRJE417849B-2/2
Customer : GE Energy / Aero Products Inc.

Short Circuit Ratio


Time Constants
T do
T d

Date : 29 Sep. 2004

0.66

in seconds

(SEC)
(SEC)

No Load Saturation & Short Circuit

2.11
0.30
MRJE417811A

Curves
No Load Saturation & Short Circuit
Curves combined with Main Generator

Notes;
N. L = No load
S.C = Three phase short circuit

MRJE417844A