You are on page 1of 20

Transfer Pump Calculations - A type

Sl. No
1

Decription
Pump Flow calculation
Roof water tank size

2
x
560
(1 Ltr per sec = 15.85 US galons per min)
Flow rate
2 Lts
Time reqquired to fill 1120 Gallons
Summary
Flow
Time
2

=
=

2.0 Lts per sec


35 mins

Pump Head Calculation


Description
Height of the building
Id 40 dia PPR
Id 40 dia T bend
NRV
Id 40 dia PPR
NRV
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Gate Valves
Sockets
Total

1120.00
15.85
31.70
35.33

Total Head

Length
7
0.3
1
1
0.3
1
1
0.74
1
0.45
1
1
0.8
1
7.2
1
0.86
1
2.6
1
2.5
1
2
5

Static Head (height of Building)


Friction Head
Friction Head losses
Pressure required at roof
Static Head

Eq. Length
7
0.3
0.3
0.5
0.3
0.5
0.5
0.74
0.5
0.45
0.5
0.5
0.8
0.5
7.2
0.5
0.86
0.5
2.6
0.5
2.5
0.5
1
1
23.55 meters

Static head + Friction Head + Pressure required

= 7.0 meters
= 3.28/100 x friction head loss (feet / 100 feet of pipe)
x total equivalent length of pipe
= 4.58 (feet / 100 feets)
= 1 bar (1 bar = 10 mts)
7.00 Mtrs

Friction Head
Pressure required
Safety Factor
4

3.54 Mtrs
10.00 Mtrs
20.54 Mts
22.59 Mts

Final Summary
Working Presssure requirement
Flow
Time

(2.1 Bar)
(2.3 Bar)

2.5 Bar
1.5 Lts / sec
47 mins

Calculations - A type

US gallons
US gallons per min
mins

+ Friction Head + Pressure required at roof

riction head loss (feet / 100 feet of pipe)

Transfer Pump Calculations - B type


Sl. No
1

Decription
Pump Flow calculation
Roof water tank size

2
x
500
(1 Ltr per sec = 15.85 US galons per min)
Flow of water
(2 Ltr per sec As per design Dwgs)
Time reqquired to fill 1000 Gallons
Summary
Flow
Time
2

=
=

2.0 Lts per sec


32 Mins

Pump Head Calculation


Description
Height of the building
Id 40 dia PPR
Id 40 dia T bend
NRV
Id 40 dia PPR
NRV
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Id 40 dia PPR
Id 40 dia 90 bend
Gate Valves
Sockets
Total

1000.00
15.85
31.70
31.55

Total Head

Length
7
0.3
1
1
0.3
1
1
0.74
1
0.45
0.8
1
7.2
1
1
2.6
1
2.5
1
2
5

Static Head (height of Building)


Friction Head
Friction Head losses
Pressure required at roof
Static Head
Friction Head
Pressure required

Eq. Length
7
0.3
0.3
0.5
0.3
0.5
0.5
0.74
0.5
0.45
0.8
0.5
7.2
0.5
0.5
2.6
0.5
2.5
0.5
1
1
21.69 meters

Static head + Friction Head + Pressure required

= 7.5 meters
= 3.28/100 x friction head loss (feet / 100 feet of pipe)
x total equivalent length of pipe
= 4.58 (feet / 100 feets)
= 1 bar (1 bar = 10 mts)
7.00 Mtrs
3.26 Mtrs
10.00 Mtrs
20.26 Mts

(2.0 Bar)

Safety Factor
4

22.28 Mts

Final Summary
Working Presssure requirement
Flow
Time

(2.3 Bar)

2.5 Bar
2.0 Lts / sec
32 mins

Calculations - B type

US gallons
US gallons per min
US gallons per min
mins

+ Friction Head + Pressure required at roof

riction head loss (feet / 100 feet of pipe)

Transfer Pump Calculations - C type


Sl. No
1

Decription
Pump Flow calculation
Roof water tank size

2
x
400
(1 Ltr per sec = 15.85 US galons per min)
Flow of water
(1.5 Ltr per sec As per design Dwgs)
Time reqquired to fill 800 Gallons
Summary
Flow
Time
2

=
=

Total Head

Length
6.5
0.3
1
1
0.3
1
1
0.45
1
1
0.86
1
2.6
1
2.5
1
2
5

Static Head (height of Building)


Friction Head
Friction Head losses
Pressure required at roof
Static Head
Friction Head
Pressure required at roof
Safety Factor
4

1.5 Lts per sec


34 Mins

Pump Head Calculation


Description
Height of the building
Id 32 dia PPR
Id 32 dia T bend
NRV
Id 32 dia PPR
NRV
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Gate Valves
Sockets
Total

800.00
15.85
23.78
33.65

Final Summary

Eq. Length
6.5
0.3
0.3
0.5
0.3
0.5
0.5
0.45
0.5
0.5
0.86
0.5
2.6
0.5
2.5
0.5
1
2.5
14.81 meters

Static head + Friction Head + Pressure require


= 6.5 meters
= 3.28/100 x friction head loss (feet / 100 feet of pipe)
x total equivalent length of pipe
= 4.58 (feet / 100 feets)
= 1 bar (1 bar = 10 mts)
6.50 Mtrs
2.22 Mtrs
10.00 Mtrs
18.72 Mts
20.60 Mts

(1.9 Bar)
(2.0 Bar)

Working Presssure requirement


Flow
Time

2.0 Bar
1.5 Lts / sec
34 mins

alculations - C type

US gallons
US gallons per min
US gallons per min
mins

+ Friction Head + Pressure required at roof

n head loss (feet / 100 feet of pipe)

Transfer Pump Calculations - D type


Sl. No
1

Decription
Pump Flow calculation
Roof water tank size

2
x
275
(1 Ltr per sec = 15.85 US galons per min)
Flow of water
(1.0 Ltr per sec As per design Dwgs)
Time reqquired to fill 550 Gallons
Summary
Flow
Time
2

=
=

1.0 Lts per sec


35 mins

Pump Head Calculation


Description
Height of the building
Id 32 dia PPR
Id 32 dia T bend
NRV
Id 32 dia PPR
NRV
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Gate Valves
Sockets
Total

550.00
15.85
15.85
34.70

Total Head

Length
6
0.3
1
1
0.3
1
1
0.74
1
0.45
1
1
0.8
1
0.86
1
2.5
1
2
5

Static Head (height of Building)


Friction Head
Friction Head losses
Pressure required at roof
Static Head
Friction Head
Pressure required
Safety Factor

Eq. Length
6
0.3
0.3
0.5
0.3
0.5
0.5
0.74
0.5
0.45
0.5
0.5
0.8
0.5
0.86
0.5
2.5
0.5
1
2.5
14.25 meters

Static head + Friction Head + Pressure required

= 6.0 meters
= 3.28/100 x friction head loss (feet / 100 feet of pipe)
x total equivalent length of pipe
= 4.58 (feet / 100 feets)
= 1 bar (1 bar = 10 mts)
6.00 Mtrs
2.14 Mtrs
10.00 Mtrs
18.14 Mts
19.95 Mts

(1.8 Bar)
(2.0 Bar)

Final Summary
Working Presssure requirement
Flow
Time

2.0 Bar
1.0 Lts / sec
35 mins

Calculations - D type

US gallons
US gallons per min
US gallons per min
mins

+ Friction Head + Pressure required at roof

riction head loss (feet / 100 feet of pipe)

Transfer Pump Calculations - E type


Sl. No
1

Decription
Pump Flow calculation
Roof water tank size

2
x
275
(1 Ltr per sec = 15.85 US galons per min)
Flow of water
(1.0 Ltr per sec As per design Dwgs)
Time reqquired to fill 550 Gallons
Summary
Flow
Time
2

=
=

1.0 Lts per sec


35 mins

Pump Head Calculation


Description
Height of the building
Id 32 dia PPR
Id 32 dia T bend
NRV
Id 32 dia PPR
NRV
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Id 32 dia PPR
Id 32 dia 90 bend
Gate Valves
Sockets
Total

550.00
15.85
15.85
34.70

Total Head

Length
6
0.3
1
1
0.3
1
1
0.74
1
0.45
1
1
0.8
1
0.86
1
2.5
1
2
5

Static Head (height of Building)


Friction Head
Friction Head losses
Pressure required at roof
Static Head
Friction Head
Pressure required
Safety Factor

Eq. Length
6
0.3
0.3
0.5
0.3
0.5
0.5
0.74
0.5
0.45
0.5
0.5
0.8
0.5
0.86
0.5
2.5
0.5
1
2.5
14.25 meters

Static head + Friction Head + Pressure required

= 6.0 meters
= 3.28/100 x friction head loss (feet / 100 feet of pipe)
x total equivalent length of pipe
= 4.58 (feet / 100 feets)
= 1 bar (1 bar = 10 mts)
6.00 Mtrs
2.14 Mtrs
10.00 Mtrs
18.14 Mts
19.95 Mts

(1.8 Bar)
(2.0 Bar)

Final Summary
Working Presssure requirement
Flow
Time

2.0 Bar
1.0 Lts / sec
35 mins

Calculations - E type

US gallons
US gallons per min
US gallons per min
mins

+ Friction Head + Pressure required at roof

riction head loss (feet / 100 feet of pipe)

You might also like