You are on page 1of 2

System Checksums

By Trane
AHU 11F 1

Packaged Terminal Air Conditioner


COOLING COIL PEAK

Peaked at Time:
Outside Air:

Plenum
Sens. + Lat
Btu/h

0
0
0
32,967
6,849
2,740
10,580
0
0
53,136

0
0
0
0
0
2,306

29,761
55,679
31,280
116,721

7,440

Internal Loads
Lights
People
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Ov/Undr Sizing
Exhaust Heat
Sup. Fan Heat
Ret. Fan Heat
Duct Heat Pkup
Reheat at Design

2,028
0
0

2,306

0
7,440
-2,028
0
-2,230
0
0

Grand Total ==>

171,884
Total Capacity
ton
MBh

Main Clg
Aux Clg
Opt Vent

20.7
0.0
0.0

248.7
0.0
0.0

Total

20.7

248.7

Project Name:
Dataset Name:

Mo/Hr: 4 / 16
OADB/WB/HR: 78 / 70 / 97

Space
Sens. + Lat.
Btu/h
Envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass Cond
Wall Cond
Partition
Exposed Floor
Infiltration
Sub Total ==>

CLG SPACE PEAK

5,489

Mo/Hr: 4 / 16
OADB: 78

Net Percent
Total Of Total
Btu/h
(%)

TEMPERATURES

Mo/Hr: 13 / 1
OADB: 71

Space Percent
Sensible Of Total
Btu/h
(%)

Space Peak
Space Sens
Btu/h

Coil Peak Percent


Tot Sens Of Total
Btu/h
(%)

0
0
0
32,967
6,849
5,046
10,580
0
0
55,442

0.00
0.00
0.00
13.26
2.75
2.03
4.25
0.00
0.00
22.29

0
0
0
43,817
-5
3,471
6,356
0
0
53,638

0.00
0.00
0.00
29.65
0.00
2.35
4.30
0.00
0.00
36.30

Envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass Cond
Wall Cond
Partition
Exposed Floor
Infiltration
Sub Total ==>

0
0
0
0
3,786
202
5,197
0
0
9,184

0
0
0
0
3,786
393
5,197
0
0
9,375

0.00
0.00
0.00
0.00
45.71
4.74
62.75
0.00
0.00
113.21

37,202
55,679
31,280
124,161

14.96
22.39
12.58
49.92

29,761
30,933
31,280
91,974

20.14
20.93
21.17
62.24

Internal Loads
Lights
People
Misc
Sub Total ==>

0
0
0
0

0
0
0
0

0.00
0.00
0.00
0.00

0
71,330
0
-2,230
0
0
0
0

0.00
28.68
0.00
-0.90
0.00
0.00
0.00
0.00

2,166
0
0

40
0
0

0
8,178
0
-44
0
-9,228
0

0.00
98.75
0.00
-0.53
0.00
-111.44
0.00

248,704

100.00

147,779

COOLING COIL SELECTION


Sens Cap. Coil Airflow
MBh
cfm
169.5
0.0
0.0

HEATING COIL PEAK

8,496
0
0

Enter DB/WB/HR
F
F gr/lb

74.4
0.0
0.0

64.2
0.0
0.0

74.0
0.0
0.0

1.47 Ceiling Load


0.00 Ventilation Load
0.00 Ov/Undr Sizing
Exhaust Heat
OA Preheat Diff.
RA Preheat Diff.
Additional Reheat
100.00 Grand Total ==>

AREAS

Leave DB/WB/HR
F
F gr/lb
56.3
0.0
0.0

54.5
0.0
0.0

Prasarana HQ Level 11
C:\CDS\TRACE700\Projects\Prasarana HQ 3 - Ogos 2016\Level 11 Rev 1a.TRC

60.9
0.0
0.0

9,224
Gross Total

Floor
Part
ExFlr
Roof
Wall

7,822
4,394
0
0
2,669

8,281
Glass
ft2
(%)

0
1,197

0
45

Cooling
56.3
72.8
72.8
74.4
0.0
0.0
0.0

SADB
Plenum
Return
Ret/OA
Fn MtrTD
Fn BldTD
Fn Frict

Heating
68.0
68.0
68.0
68.9
0.0
0.0
0.0

AIRFLOWS
Vent
Infil
Supply
MinStop/Rh
Return
Exhaust
Rm Exh
Auxiliary

Cooling
2,455
0
8,496
0
8,496
2,455
0
0

Heating
2,455
0
8,496
0
8,496
2,455
0
0

ENGINEERING CKS
% OA
cfm/ft2
cfm/ton
ft2/ton
Btu/hr-ft2
No. People

Cooling
28.9
1.09
409.95
377.41
31.80
124

Heating
28.9
1.09

0.00

100.00

HEATING COIL SELECTION

Capacity Coil Airflow Ent


MBh
cfm
F

Lvg
F

Main Htg
Aux Htg
Preheat

0.0
0.0
0.0

0
0
0

0.0
0.0
0.0

0.0
0.0
0.0

Humidif
Opt Vent
Total

0.0
0.0
0.0

0
0

0.0
0.0

0.0
0.0

TRACE 700 v4.1 calculated at 11:19 AM on 08/24/2016


Alternative - 1 System Checksums Report Page 1 of 2

System Checksums
By Trane
AHU 11F 2

Packaged Terminal Air Conditioner


COOLING COIL PEAK

Peaked at Time:
Outside Air:

Plenum
Sens. + Lat
Btu/h

0
0
0
9,731
7,429
2,648
9,692
0
0
29,500

0
0
0
0
0
2,300

28,696
53,532
30,547
112,775

7,174

Internal Loads
Lights
People
Misc
Sub Total ==>
Ceiling Load
Ventilation Load
Ov/Undr Sizing
Exhaust Heat
Sup. Fan Heat
Ret. Fan Heat
Duct Heat Pkup
Reheat at Design

2,234
0
0

2,300

0
7,174
-2,234
0
-2,439
0
0

Grand Total ==>

144,508
Total Capacity
ton
MBh

Main Clg
Aux Clg
Opt Vent

18.3
0.0
0.0

219.9
0.0
0.0

Total

18.3

219.9

Project Name:
Dataset Name:

Mo/Hr: 4 / 15
OADB/WB/HR: 79 / 70 / 97

Space
Sens. + Lat.
Btu/h
Envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass Cond
Wall Cond
Partition
Exposed Floor
Infiltration
Sub Total ==>

CLG SPACE PEAK

4,802

Mo/Hr: 4 / 16
OADB: 78

Net Percent
Total Of Total
Btu/h
(%)

TEMPERATURES

Mo/Hr: 13 / 1
OADB: 71

Space Percent
Sensible Of Total
Btu/h
(%)

Space Peak
Space Sens
Btu/h

Coil Peak Percent


Tot Sens Of Total
Btu/h
(%)

0
0
0
9,731
7,429
4,948
9,692
0
0
31,800

0.00
0.00
0.00
4.43
3.38
2.25
4.41
0.00
0.00
14.46

0
0
0
34,399
-4,405
2,536
1,142
0
0
33,671

0.00
0.00
0.00
27.55
-3.53
2.03
0.91
0.00
0.00
26.97

Envelope Loads
Skylite Solar
Skylite Cond
Roof Cond
Glass Solar
Glass Cond
Wall Cond
Partition
Exposed Floor
Infiltration
Sub Total ==>

0
0
0
0
3,755
207
5,090
0
0
9,052

0
0
0
0
3,755
402
5,090
0
0
9,247

0.00
0.00
0.00
0.00
47.39
5.08
64.26
0.00
0.00
116.73

35,870
53,532
30,547
119,949

16.32
24.35
13.89
54.56

28,696
29,740
30,547
88,983

22.99
23.82
24.47
71.28

Internal Loads
Lights
People
Misc
Sub Total ==>

0
0
0
0

0
0
0
0

0.00
0.00
0.00
0.00

0
70,547
0
-2,439
0
0
0
0

0.00
32.09
0.00
-1.11
0.00
0.00
0.00
0.00

2,189
0
0

46
0
0

0
7,827
0
-50
0
-9,102
0

0.00
98.80
0.00
-0.64
0.00
-114.9
0
0.00

219,857

100.00

124,843

COOLING COIL SELECTION


Sens Cap. Coil Airflow
MBh
cfm
142.9
0.0
0.0

HEATING COIL PEAK

6,975
0
0

Enter DB/WB/HR
F
F gr/lb

74.9
0.0
0.0

64.7
0.0
0.0

75.8
0.0
0.0

1.75 Ceiling Load


0.00 Ventilation Load
0.00 Ov/Undr Sizing
Exhaust Heat
OA Preheat Diff.
RA Preheat Diff.
Additional Reheat
100.00 Grand Total ==>

AREAS

Leave DB/WB/HR
F
F gr/lb
55.9
0.0
0.0

54.4
0.0
0.0

Prasarana HQ Level 11
C:\CDS\TRACE700\Projects\Prasarana HQ 3 - Ogos 2016\Level 11 Rev 1a.TRC

61.1
0.0
0.0

9,098
Gross Total

Floor
Part
ExFlr
Roof
Wall

7,542
4,267
0
0
2,764

7,922
Glass
ft2
(%)

0
1,244

0
45

Cooling
55.9
72.9
72.9
74.9
0.0
0.0
0.0

SADB
Plenum
Return
Ret/OA
Fn MtrTD
Fn BldTD
Fn Frict

Heating
68.0
68.0
68.0
69.0
0.0
0.0
0.0

AIRFLOWS
Vent
Infil
Supply
MinStop/Rh
Return
Exhaust
Rm Exh
Auxiliary

Cooling
2,349
0
6,975
0
6,975
2,349
0
0

Heating
2,349
0
6,975
0
6,975
2,349
0
0

ENGINEERING CKS
% OA
cfm/ft2
cfm/ton
ft2/ton
Btu/hr-ft2
No. People

Cooling
33.7
0.92
380.68
411.65
29.15
119

Heating
33.7
0.92

0.00

100.00

HEATING COIL SELECTION

Capacity Coil Airflow Ent


MBh
cfm
F

Lvg
F

Main Htg
Aux Htg
Preheat

0.0
0.0
0.0

0
0
0

0.0
0.0
0.0

0.0
0.0
0.0

Humidif
Opt Vent
Total

0.0
0.0
0.0

0
0

0.0
0.0

0.0
0.0

TRACE 700 v4.1 calculated at 11:19 AM on 08/24/2016


Alternative - 1 System Checksums Report Page 2 of 2