Professional Documents
Culture Documents
MANUAL
PTS 20.160G
OCTOBER 1993
PREFACE
PETRONAS Technical Standards (PTS) publications reflect the views, at the time of publication,
of PETRONAS OPUs/Divisions.
They are based on the experience acquired during the involvement with the design, construction,
operation and maintenance of processing units and facilities. Where appropriate they are based
on, or reference is made to, national and international standards and codes of practice.
The objective is to set the recommended standard for good technical practice to be applied by
PETRONAS' OPUs in oil and gas production facilities, refineries, gas processing plants, chemical
plants, marketing facilities or any other such facility, and thereby to achieve maximum technical
and economic benefit from standardisation.
The information set forth in these publications is provided to users for their consideration and
decision to implement. This is of particular importance where PTS may not cover every
requirement or diversity of condition at each locality. The system of PTS is expected to be
sufficiently flexible to allow individual operating units to adapt the information set forth in PTS to
their own environment and requirements.
When Contractors or Manufacturers/Suppliers use PTS they shall be solely responsible for the
quality of work and the attainment of the required design and engineering standards. In
particular, for those requirements not specifically covered, the Principal will expect them to follow
those design and engineering practices which will achieve the same level of integrity as reflected
in the PTS. If in doubt, the Contractor or Manufacturer/Supplier shall, without detracting from his
own responsibility, consult the Principal or its technical advisor.
The right to use PTS rests with three categories of users :
1)
2)
3)
Subject to any particular terms and conditions as may be set forth in specific agreements with
users, PETRONAS disclaims any liability of whatsoever nature for any damage (including injury
or death) suffered by any company or person whomsoever as a result of or in connection with the
use, application or implementation of any PTS, combination of PTS or any part thereof. The
benefit of this disclaimer shall inure in all respects to PETRONAS and/or any company affiliated
to PETRONAS that may issue PTS or require the use of PTS.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual
arrangements, PTS shall not, without the prior written consent of PETRONAS, be disclosed by
users to any company or person whomsoever and the PTS shall be used exclusively for the
purpose they have been provided to the user. They shall be returned after use, including any
copies which shall only be made by users with the express prior written consent of PETRONAS.
The copyright of PTS vests in PETRONAS. Users shall arrange for PTS to be held in safe
custody and PETRONAS may at any time require information satisfactory to PETRONAS in order
to ascertain how users implement this requirement.
LIST OF SECTIONS
PART 1
00.00.00
INTRODUCTION
01.00.00
PART 2
02.00.00
03.00.00
PART 3
04.00.00
05.00.00
PART 4
06.00.00
PART 5
07.00.00
PART 6
08.00.00
09.00.00
PART 7
10.00.00
PART 8
11.00.00
12.00.00
13.00.00
BIBLIOGRAPHY
INDEX
CONTENTS OF SECTION
10.00.00
10.01.00
10.01.01
Fire Prevention
10.01.02
Design Philosophy
10.02.00
10.02.01
10.03.00
10.03.01
Summary
10.03.02
10.03.03
10.03.04
10.03.05
10.03.06
10.03.07
10.03.08
10.03.09
10.03.10
10.03.11
10.03.12
10.03.13
10.03.14
Distinctive Colouring
10.03.15
Appendix 10.03.02
Appendix 10.03.03
Figure 10.03.04
Figure 10.03.05
Figure 10.03.06
Figure 10.03.07
Figure 10.03.08
Figure 10.03.09
Figure 10.03.10
Figure 10.03.11
Figure 10.03.12
Figure 10.03.13
Figure 10.03.14
Figure 10.03.15
Figure 10.03.16
Figure 10.03.17
Figure 10.03.18
Figure 10.03.19
Figure 10.03.20
Figure 10.03.21
Figure 10.03.22
Figure 10.03.23
Figure 10.03.24
Figure 10.03.25
Figure 10.03.26
Appendix 10.03.27
Figure 10.03.28
10.04.00
10.04.01
Types of Fire
10.04.02
Water
10.04.03
Foams
10.04.04
Carbon Dioxide
10.04.05
10.04.06
Appendix 10.04.02
10.00.00
10.01.00
10.01.01
Fire Prevention
The protection of personnel, equipment and product by the prevention of fires is the
responsibility of the Manager of any plant. Effective fire prevention depends on the design
and operation of a plant so as to minimise the risk of a fire starting. This entails ensuring
by regular review that facilities and equipment meet appropriate standards of design and
operation, and that personnel are taught enough about the properties of flammable
products that they understand and use the correct procedures for handling them safely.
Notwithstanding the above, the possibility of a fire occurring must be recognised. This
necessitates preparing and rehearsing effective emergency fire plans, ensuring that the
appropriate scale and type of fire fighting equipment is available and maintained in
satisfactory working order, and training all personnel (including office staff) in the correct
use of the fire fighting equipment provided. Fire escape routes must be provided and
prominently signposted. Wherever possible the co-operation should be sought of any
outside support such as the local fire brigade, nearby refinery or airfield brigade, and other
oil companies, both with respect to the type and quantity of equipment to be held and the
use of available manpower to be trained for fire fighting duties.
Details of fire fighting procedures, types of fire, extinguishing methods and techniques,
use and care of fire fighting equipment are given in 'Plant Operating Manual', Volume 1,
07.00.00.
10.01.02
Design Philosophy
Installations and depots are designed and operated in such a manner that the risk of fire is
remote. Fire fighting equipment is provided on a scale suitable for these proven design
and operational standards. As the size of installations and depots as well as the tanks
within them grow, so too must the scale of fire fighting effort required to protect them. The
scale of equipment described below generally refers to the total capacity that should be
available to protect the various facilities. However, every opportunity should be taken to
share this load and reduce the individual burden by combining men and material with
those of neighbouring installations/depots/refineries and local fire brigades.
A distinction can be drawn between the scale and standards of fire protection appropriate
to an installation or depot as defined in 02.01.00. Size is not the only criteria on which to
base a decision, since while an installation is usually an important strategic part of a
company's product distribution system, the same status may also apply to a depot if it
occupies and indispensable position in its location.
An installation fire protection system would normally be based on a water main and
hydrant system routed and equipped so as to be able to apply foam and water to all main
fire targets such as loading and jetties, buildings, etc. Water supply should preferably be
from a harbour, river or similar unlimited source, but if such are not available an
installation should have its own stock of water in a reservoir or tank. Furthermore,
pumping capacity would also be installed unless the local fire brigade or similar pumps are
always readily available, and their participation in the installation fire plan is organised and
rehearsed. The incorporation of base foam injection for tank protection would be decided
upon in accordance with considerations given in 10.03.15 below. The provision of more
sophisticated fire protection equipment such as self-propelled motorised fire engines,
continuously pressurised water mains, automatic or remote pump starting and control,
automatic foam generating or deluge systems, though not normally appropriate for other
than the largest installations, should nevertheless be considered in the light of the size
(physical as well as throughput), complexity and accessibility to effective outside help.
10.02.00
10.02.01
Specific duties: Each team member should be allocated specific tasks and be
trained in their execution in the correct sequence. After completion of their duties
they should gather together with any other spare manpower assembly point and
wait for further orders.
Direction and control: The most senior man on the site should take charge.
Provision should be made for setting up an easily recognisable control point at
which he will remain and from which he will direct the fire fighting. The policy and
manner of handing over control to more senior staff as they arrive should be
agreed including how and whether to pass control to outside authorities, the fire
brigade, etc. It is useful if the man in control can be clearly identified by
distinctive clothing e.g. yellow jacket or helmet.
Evacuation procedures: It may not always be necessary or advisable for all bulk
vehicles or personnel to leave the site. It is more important to get them away
from the fire without obstructing incoming fire appliances. In this respect the local
traffic police should be brought in on any procedures to be established.
Evacuation of personnel from offices, warehouses and other work sites must also
be organised which necessitates planned and prominently signposted escape
routes.
Relief and refreshment: Fire fighters require food, drink and rest and their
provision must be planned for in advance.
Liaison and outside contact: All aspects of the plan must be agreed in advance
with the local fire brigade, police must be agreed in advance with the local fire
brigade, police and similar emergency bodies. Contact during the fire may well
be needed with hospital and ambulance services, neighbouring oil industry sites,
suppliers of fire fighting equipment and foam, press and TV, as well as members
of the public. It can save a lot of stress on the leader of the fire fighting effort, if a
specific contact point and person are established for such purposes.
(b) Training
(i)
Basic use of equipment: All members of the fire fighting team must be
trained in the use of all items of fire fighting equipment in addition to being
rehearsed in their allocated duties under the fire plan. This will provide a
totally flexible force of men who can swap duties as necessary during an
emergency. Activities that should be covered by such basic training include
starting up and operating the fire pump; operating fire main and sprinkler
valves and being thoroughly familiar with their location; running out and
connecting fire hoses; fitting and handling nozzles, foam-making branch
pipes, foam monitors, and the system for foam compound induction; base
injection systems; and methods of directing cooling water or foam onto the
correct target. It is suggested that foam compound should be treated as a
consumable stock and up to 20% of stocks should be used in practices in
any one year.
(ii)
Rehearsal of fire plan: Fire plans must be rehearsed in order to train and test
the fire fighters and to test the equipment. Both these aspects are important
for a successful fire fighting capability - men may well be trained but they
must be provided with up-to-date equipment, in good repair, and foam
compound which has not deteriorated.
Rehearsals should be fully planned in the early stages of training until the
teams become familiar with what is expected of them. The next stage could
be to hold planned rehearsals or exercises but without warning of the
locations in the plant where they are to be held. The final stage would be to
hold unexpected exercises without any previous warning of time or location.
Two important principles should govern fire plan exercises for rehearsals.
These are:
The fire plan and the subsequent exercises must take place in all the
different locations in the plan where a fire could occur, and at different
times -e.g. outside normal working hours and at night, for instance during
tanker discharge operations.
(iii)
Joint exercises: Joint exercises should be held with the local fire brigade or
neighbouring installations in order to ensure a smooth combination of effort
and to make sure that equipment is compatible. These aspects should not be
underestimated. Outside help is nearly always required in an emergency and
pre-planning and practice are the only way to eliminate some of the
problems that are bound to arise.
(iv)
10.03.00
10.03.01
Summary
The purpose of an installation or depot fire fighting system is to provide two stages of fire
fighting capability.
Firstly, there must be an immediate action response based on own resources, using hand
or mobile extinguishers by the people working at or those first to arrive at the scene of
the fire.
Secondly, there must be a back-up either from one's own resources or by or in
conjunction with outside assistance to undertake the larger scale and more prolonged fire
fighting effort to extinguish or contain the fire, in the event that the immediate action is
unsuccessful.
The scale and type of protection provided depends not simply on whether the plant is an
installation or a depot, but rather on the number, scale and type of the various activities
that comprise the total operation, any of which may present unique problems, and all of
which must be appropriately protected.
By virtue of its size and importance in the distribution network, an installation would
normally be expected either to have its own fixed facilities comprising water supply,
pumping capacity, and fire main and hydrants system, or to have sufficient facilities (e.g.
a dry main and hydrants system with access to water) for a nearby local fire brigade to
use with its own manpower and equipment.
By definition, depots (distribution and airfield) present smaller, less potent targets and
therefore a reduced scale of fire protection may be adequate. On the other hand, depots
are often located in remote areas where outside help may be non-existent or of
unreliable quality. If such a depot cannot be by-passed or duplicated, for instance if it
occupies an indispensable position in its area, then the results of a loss or lengthy period
out of service have to be judged against both commercial and political repercussions. An
additional factor to be taken into consideration is whether a fire (for example a tank fire)
could pose a serious threat to adjacent property, particularly domestic. If such special
factors indicate that a particular risk exists or in order to comply with local requirements,
depots may in certain instances have to be treated as small installations, and their fire
fighting system must be designed and built accordingly.
10.03.02
The type and size of fire for which they are likely to be used. There are hand or
mobile extinguishers which can apply to any of the known fire fighting agents.
Section 10.04.00 gives information on the characteristics of different agents to
assist in selection of the best choice of extinguisher. Appendices 10.03.01 and
10.03.02 give data on different types of extinguishers and on the recommended
scale to be held at different locations.
(ii)
10.03.03
Adequate supply of water (m, gallons) in the right places to provide foam
making and/or cooling capacity for the necessary period of time.
(ii)
(iii)
Sufficient water pressure (bar, lb/sq inch) at all hydrant outlets to operate foam
making equipment and to reach high or distant fire targets.
Deficiency in any one of the above may well result in failure to extinguish or contain a
fire. The highest combination of foam making and cooling water must be used for the
design basis.
(a) Water supply
A supply of either fresh or salt water is required at a minimum main pressure at
distant hydrants of 10 bar. (Higher pressures may be required for base injection
systems, refer 10.03.15.) Except where water supply is unlimited, e.g. from sea,
harbour, rivers or other open sources, provision of a reservoir, tank or other water
storage must be considered. This will necessitate carefully estimating what water
stocks are necessary and practicable to hold.
Methods for estimating the quantity needed for foam making are given under (c). For
cooling purposes it is suggested a supply to permit at least 2 hours cooling be held,
but every practicable means of supplementing this should be sought; too much water
will never be an embarrassment during a real fire!
Note: During tank maintenance a back-up water supply must be arranged.
The water volume depends upon the scope of the facilities to be protected and must
be adequate for the highest combination of both the foam making requirements and
the cooling of adjacent tanks or other structures. Water is also used for fires not
involving petroleum products (i.e. offices, dry vegetation, etc.), however, quantities
provided for fighting oil fires will normally be more than adequate for these other
purposes. Provision for future expansion should be made where applicable.
The routing and extent of the fire main system plus the number and location of
hydrants must be carefully chosen so as to provide water for foam making and
cooling of adjacent tanks or facilities at all significant potential fire targets.
Water hydrants, each with two outlets, should be sited strategically throughout the
installation, at distances of between 30 to 50m from the items to be protected allowing for the possibility that access to any fire may be restricted by prevailing
winds and/or the fire situation itself being limited to only one predictable avenue of
attack. The aim should be to restrict hose strings to two or three standard lengths in
order to minimise pressure losses and the time taken to connect hoses.
Block valves should be incorporated in the ring main where it may be considered
useful to be able to isolate sections of the main, should it become damaged.
(b) Water flow rate - cooling (Appendix 10.03.01)
Cooling is required for fixed roof tanks holding Class I, II (2) or III (2) products and, in
addition, for tanks holding Class II (1) and III (1) products where these might become
endangered by adjacent fires. Class I, II (2) and III (2) tanks should be fitted with
water sprinklers to provide immediate all-over cooling, whereas Class II (1) and III (1)
tanks can be cooled using water hoses or monitors from the ground on the exposed
sides only.
The design of a tank farm cooling system requires careful consideration of the
several variables such as different combinations of tanks to be cooled, variation in
size and type of fire, products involved, wind conditions, presence of possible fire in
the bund, and changes that take place during a fire. No single water application rate
will cater exactly for all fires but proper design and operation can approach the ideal.
A final point is that the total water supply has to be shared simultaneously with the
demands of the foam making system used for fire fighting, see Appendix 10.03.27 Base Injection Design and Equipment.
A fixed cooling water system with an application rate of 1 litre/min/m of exposed
surface (shell plus roof for tanks) is recommended as providing a heat barrier and
cooling effect that can normally be turned on almost immediately thus leaving
personnel free to carry out other fire fighting duties. (For LPG requirements see
11.00.00.). Depending on the development of a fire it may become a tactical
requirement to supplement this basic level for a particularly exposed surface by
reducing application to a less exposed surface during an actual fire. Such application
would not necessarily require the total design cooling water rate to exceed 1
litre/min/m . It would be applied by utilising hoses and/or monitors wherever the
amount of sprinkler water is inadequate, for example, on any part of a tank shell.
This would be evident if all cooling water on exposed shell or roof turns into steam,
some parts of the shell are not receiving water, the shell metal is discolouring from
the effect of heat, vapour and/or flames are seen issuing from roof pressure/vacuum
valves, or total water flow and pressure are judged to be inadequate.
It takes careful design and operation to produce a tank farm sprinkler system that
gives close to 1 litre/min/m on all possible combinations of tanks. One solution for
setting and controlling sprinkler flow rates is to fit pressure gauges downstream of
each sprinkler line control valve. The pressure gauge sight glass can be marked with
the pressure reading known by previous trials to give the desired water flow rate to
that particular tank. As flow and pressure conditions vary during a fire, the sprinkler
line control valves can be adjusted so as to maintain as closely as possible the
various design flow rates. Such valves should of course be fitted outside bunds in
Class I products - shallow surface fire (e.g. spills): 4.9 litres/min/m of product
surface applied for 30 minutes.
Class I products - deep product fire (e.g. storage tanks, bunds, etc.):
7.4 litres/min/m of product surface, applied for 30 minutes.
Class II and II products - all types: 4.9 litres/min/m of products surface, applied
for 30 minutes.
20 m diameter
Product:
Gasoline
314 m
Flow rate:
69720 litres
The same basic foam solution flow rates are needed when foam is applied for tank
fires by base injection. In this case virtually all the foam reaches the burning surface
- which illustrates the main advantage of the base injection system (see 10.03.15 for
details).
The amount of foam making equipment and foam concentrates to be held depends
upon the scope and degree of assistance available from the local fire brigade and/or
other oil companies. Unless legislation requirements exceed this amount, the
guidelines outlined should be followed when determining minimum requirements.
10.03.04
10.03.05
10.03.06
Based on the maximum size of tanker acceptable at the berth, the water main should
be capable of supplying 50m/hour for each 30m length of ship at a minimum
pressure of 10 bars under full flow conditions at the most unfavourably sited
hydrants, up to a maximum total flow rate of 250m/hour.. This will permit the use of
mechanical foam generators (see Figure 10.03.11) or high-pressure spray nozzles,
see MESC 96.28.20.
Fire towers are not recommended for marketing installations. Where fire towers have
been erected, one or more branch lines should be installed to supply water to fixed
monitors, installed on top of the tower. The monitors should preferably be dual
controlled (local and remote) and should be able to throw jets of water for a distance
equal to the beam of the largest tanker likely to use the berth, and should be capable
of delivering water, fog or spray as required. The direction of any prevailing wind
should be borne in mind when siting towers. The total quantity of water required
should be increased accordingly.
Water jets are intended for dealing with fires on ship's superstructures until close
range fire fighting can be carried out. Fog or spray jets are particularly useful for
cooling purposes and to provide a protective curtain of water to assist personnel in
gaining access to the ship.
Water supplies may be from the harbour or other open source, or from an extension
to the installation fire water main.
Where jetties or berths are remote from installations it may be necessary to install
separate pumps or connections for the local fire brigade (shore or harbour) to
connect their pumps. Where the jetty or berth is either shared or operated by third
parties (other oil companies, harbour authorities) specific arrangements must be
made to ensure a viable fire protection system, properly maintained and manned
when required.
(b) Stocks of foam compound
Foam compounds should be readily available either in bulk or on a mobile trailer for
quick delivery to the fire site. The quantity should be 0.5m/30m length of ship. For
berths where chemical products are handled, consideration should be given to the
different types of fire fighting equipment that may be required as well as various
types of foam compound.
(c) International shore fire connection
The purpose of the International Shore Fire connection is to connect the fire water
supply from shore to ship's fire main or to interconnect the fire mains of two ships.
Reference should be made to Appendix E of the International Safety Guide for Oil
Tankers and Terminals.
(d) Portable fire fighting equipment
In addition to the above, sufficient hand and mobile fire extinguishers should be
provided at all berths or jetties to enable an immediate attack to be mounted on any
small fire that may occur on or near the berth, see Appendix 10.03.01.
(e) Fire fighting equipment for small wharves or those handling a few small vessels
and/or barges, or those handling only Class III products.
At small wharves handling ships of less than 18 000 tonnes and at a frequency of
less than 60 ships/year, or wharves handling only Class III products, at least two
275kg or four 150kg dry chemical or equivalent foam units should be provided unless
equivalent or better protection is already available on the wharf.
For bulk barge traffic only, carrying Class I, II or III products, the number and size of
mobile units may be reduced to a minimum of two 70kg dry chemical (or equipvalent
foam) units provided such movements are infrequent and the risk of a fire spreading
to neighbouring faciliftes is insignificant.
access ways to and from and between off-shore berths/ dolphins; personnel must
not be left unattended on isolated dolphins
small boat with both motor and paddles in case oil spillage makes use of motor
unsafe.
10.03.07
10.03.08
10.03.09
Fluoroprotein foams applied at three times the application rate needed for
fighting oil product fires (i.e. 22 litres/min/m unless flashpoint above 21C in
which case 15 litres/min/m).
For fires involving blends of gasoline with not more than 20% alcohol (ethanol or
methanol) fluoroprotein foam can be used at an application rate of 7.4 litres/min/m;
note that application must be smooth and gentle.
Spillages of alcohols can be rendered less flammable by flooding with water, e.g.
alcohol mixed with more than 20% water becomes equivalent to a Class II product;
with more than 92% is equivalent to a Class III product. Care must nevertheless be
taken with run-off since very small percentages of alcohol in water are toxic to
human/animal/plant life and normal oil/water interceptors will not separate solutions
of alcohol in water.
It is generally recommended that where the quantities of chemical solvents stored
are small relative to oil products, fire fighting should be based on fluoroprotein foam
rather than the special all purpose/alcohol resistant types. This avoids the
complications of holding two types of foam compound and of organising fire fighting
procedures to ensure the correct foam is used in the event of a fire. In addition,
although chemical solvent tanks require three times the application rate, in most
cases this will amount to a smaller flow than that provided for the larger oil product
tanks. Where all purpose/alcohol resistant type foams are nevertheless considered
necessary, they are obtainable from most foam suppliers, and can be applied using
standard foam-making equipment. As these foam compounds tend to be slightly
acidic, all equipment must be thoroughly washed after use and any bulk compound
containers must be specially lined.
Gentle application of all purpose/alcohol resistant foams to the burning surface of
alcohols is essential to obtain control and extinction of a fire. This is because, to
prevent foam breakdown, when the initial foam contacts the surface of the product, a
polymer film is formed on the surface. This film acts as a physical barrier to prevent
the breakdown of any further foam applied to the product surface and thus allows the
foam layer to build up until extinction is achieved. If the foam is applied forcefully,
the polymer film disintegrates and a foam layer cannot build up. The recommended
technique is to direct the foam against any vertical or sloping surface and so allow it
to run down onto the fire, or to bounce it off an adjacent flat surface.
For tank fires, over the top application by monitor or branch pipe is unlikely to give
the required gentle application, nor will the use of standard fixed top pourers unless
the level of product happened to be high enough that the foam does not have far to
fall. A device to overcome this weakness of fixed top pourers is illustrated in
Figure 10.03.12. Fixed to the inside of the tank shell and extending from the point
where the foam enters the tank at the top of the shell to the tank bottom, a vertical
conduit or chute contains staggered openings provided at intervals. The delivered
foam piles up inside the chute and emerges through the first opening immediately
above the product surface. Discharge of foam through the higher openings is
prevented by baffles and by ensuring the openings are large enough to
accommodate full foam flow. The maximum drop of foam is regulated by the vertical
spacing of the overflow outlets which should be at maximum of 1.5m apart.
Application by base injection is obviously not possible because of the intimate mixing
of the foam with product as it rises through the product. An alternative may be a
system of base injection which employs a flexible hose fitted in the foam inlet line
outside the tank. As foam is pumped into the tank the hose unfolds, floats to the
surface of the product and discharges the foam at the product surface thus keeping
foam and product separated from each other until the foam reaches the surface, see
Figure 10.03.13. PETRONAS experience with this device is limited particularly with
respect to its use in water miscible products.
(c) Other chemical products
If fire protection has to be provided for chemical products outside the above two
categories, advice may be found in the Handling and Safety manuals, the Depot
manual and the Safety Guide for Pesticides.
(d) General
Many agricultural products and some industrial and plastic products produce toxic
vapours in a fire. Fire fighting personnel may therefore require breathing apparatus
and protective clothing. Only personnel properly trained and experienced in the use
of breathing apparatus should be so employed since inexperienced users may put
themselves at considerable risk if they are not fully aware of the hazards and the
means to overcome them.
Water used for fire fighting may become contaminated by toxic products and must
be prevented from escaping into public drainage systems or waterways by using
segregated bund/drainage systems. Solutions of toxic chemicals in water are not
trapped by standard oil-water interceptors.
Other precautions are to segregate different types of fire by storing toxic/non-toxic
and flammable/non-flammable chemicals separately and to minimise the use of
water by basing the fire protection on dry powder or foam as far as possible. Refer
manual, 'Warehousing for Packed Chemicals and Other Products'.
10.03.10
10.03.11
10.03.12
10.03.13
10.03.14
Distinctive Colouring
Fire fighting equipment should be painted distinctively. Red is the accepted basic colour
(Shell standard colour No 11), but each type of extinguisher may be painted wholly or
partly in other colours for the purpose of ready identification, and a suggested
arrangement is as follows:
Water
Red
Foam
Cream
Carbon dioxide
Black
Blue
Green
Instruction labelling with black letters on a yellow background is generally more clearly
visible than other colour combinations.
Notices indicating the location of equipment should have white letters on a red
background. Fire boxes containing hoses, branch pipes and other equipment should be
painted red.
Fire precaution notices should have red letters on a white background, e.g. No smoking,
etc.
10.03.15
Black oils - because, if they burn for more than 5 to 10 minutes before
injection of foam starts, hot zones with temperatures exceeding 100C are
formed which are likely to convert the foam to steam and cause dangerous
frothing or boil-over; for white oils the hot zones stay far enough below
100C for this not to occur.
(ii)
One possible solution to both these obstacles is a recent development in which foam
is injected through a sealed container which is attached to the outside of the tank
shell and which contains a folded hose (see Figure 10.03.13). The hose is forced out
of the container by the foam/air pressure breaking the seal, and is pushed up through
the product to the burning surface where it expels the foam to extinguish the fire.
Thus the foam does not come into contact with the product until it reaches the
product surface. PETRONAS experience with this device, available from two
different suppliers, is at present limited.
(b) Recommendations
Base injection is generally regarded as one of the most effective means of
extinguishing white product petroleum fires in fixed roof tanks. Nevertheless, a
decision whether or not to install base injection on one or more tanks in a tank farm
should take account of the following:
(i)
(ii)
Irrespective of tank diameter or height, base injection has the advantage that
it is relatively safe from damage or obstruction should an explosion distort
the roof or tank shell.
(iii)
For tanks with properly fitted and maintained floating roofs or screens, which,
provided the ullage spaces are effectively ventilated to remove product
vapour, are themselves an important means of reducing the risk of fires,
base injection offers little benefit and is not normally recommended. Where
base injection already exists, or where no increased ventilation is provided,
the installing of floating screens should not seriously interfere with its
operation, however the fitting of two foam inlets would increase the likelihood
that one still works should the other be obstructed by a1screen sinking inside
the tank.
(iv)
(v)
Either fluoroprotein foam (not normal protein foam) or aqueous film forming
foam (e.g. light water) can be used, though the latter may be expensive,
requires higher water pressures, can be less stable and more difficult to
control, and is likely to leave small rim fires (caused by the effect of the hot
steel shell) which may have to be extinguished using hand extinguishers or
hoses.
(vi)
(vii)
In spite of the foregoing, there are locations where the risk of a fire starting
and/or of consequential damage or operational disruption may be judged too
small to warrant the cause of conversion of all or any tanks to base injection,
e.g. some up country depots in isolated areas and at small storage points.
Semi-fixed system
The fixed part of the system consists of the foam line which runs from
outside the tank bund to the tank inlet and is fitted with suitable valves and
an inlet manifold to which the foam generators can be connected when
needed. Since the tank valve has to be open to permit foam to enter, it must
either be remotely operated or be left permanently open, in which case it is
necessary to fit a second steel tank valve and/or bursting disc Just outside
the bund to contain the tank contents. If manually operated this valve must
be located and protected such that an operator can get to it quickly and open
it even when the tank and/or the bund is on fire. A possible arrangement is
shown in Figure 10.03.21. The foam compound, inductors, and generators
can be carried in a van or trailer and brought to a fire when required, for
connection by hoses between the water supply hydrants and the foam lines.
Foam generation is initiated by opening the water supply and foam line
valves and maintaining adequate supplies of water and foam compound.
The main advantage of the semi-fixed system is that only one set of
generators, inductors and foam compound is needed to cover perhaps
several tanks or different groups of tanks. This however carries with it the
main disadvantage of the system which is that it obviously takes time to
connect and start foam injection, and in addition a means to transport the
foam injection, and in addition a means to transport the foam and equipment
to the appropriate foam line manifold must be provided and kept in constant
readiness. Furthermore, suitable and protected access to every foam line or
manifold connecting point must be provided.
(ii)
Fixed system
The foam line and valve requirements within the bund are much the same as
for the semi-fixed system, but outside the bund all foam inductors and
generators plus a foam compound tank are installed as fixed parts of the
system (see Figures 10.03.16 to 20 inclusive). An obvious advantage of the
fixed system is the speed with which it can be operated, since there is no
delay while bringing up foam and equipment, connecting hoses, etc. A
disadvantage is the cost of the greater number of generators, inductors and
foam compound tanks that are required. However, judicious layout design
can minimise this by grouping tanks so that each battery of generators and
related equipment will serve several different tanks. One, two or at the most
three such batteries will normally be sufficient to cover most marketing tank
farms.
Generally, therefore, the fixed system is to be preferred since the additional
cost is not large compared with the longer delay and lower reliability of the
semi-fixed system which requires more manpower and the need to maintain
equipment in constant readiness. Furthermore, for Class I product tanks, a
fixed system that can be started up within 10 minutes can be designed for a
lower
foam
application
rate
with
obvious
cost
benefit
(see Appendix 10.03.27).
(iii)
(iv)
General arrangement
Deciding on the disposition of the various system components (pumps,
inductors, generators, foam solution lines, finished foam lines,
valves/bursting discs, etc.,) requires careful consideration of a number of
factors. These relate primarily to the distance from the water supply pump to
the tanks to be protected; the high back pressures on the system caused by
the product heads in high tanks; the need for the foam inlet valves being
open at the time of starting base injection; the inability for men to operate
valves or replenish foam compound within intolerable heat radiation levels of
tanks or bunds on fire, etc. To illustrate one typical problem area the
simplest system may be to group pump, foam compound indicators and
foam generators together so that foam can be directed via a manifold to any
one of a group of tanks. This necessitates pumping finished foam all the way
from the pump outlet to the tank inlet. However, if the tank is high and
(ii)
The inlet pressure specified for the high back-pressure generators used
(normally 7 bars but for some makes as high as 10 bars) must be maintained
continuously otherwise inferior quality foam may be produced leading to
extended extinction time or even failure to extinguish the fire. It is important
therefore that, during the actual base injection operation, significant changes
in demand on the water supply, (which could upset the flow/pressure supply
to the base injection system) do not occur.
(iii)
Extinguishers, spare gas cartridges and replacement charges should be visually inspected at
least monthly by a responsible person to make sure that appliances are in their proper
positions and have not been discharged, or lost pressure (in the case of extinguishers fitted
with a pressure indicator), or suffered obvious damage. The provision of brackets, shelves or
base blocks will help to show if any appliance is missing.
A more thorough inspection should be carried out at least twice a year by a competent
person, e.g. a properly trained member of staff, or a service man from the extinguisher
suppliers, or from a firm specialising in this type of work. The recommendations below are
intended as a guide.
Faulty, damaged or corroded parts should be replaced only by the correct component
supplied or recommended by the extinguisher manufacturer.
Before opening any extinguisher it is important to check the vent holes or other venting
device. Any blocked vent should be cleared before the extinguisher is opened, and then the
extinguisher should be opened slowly in order to allow any gas present to escape in a
controlled manner.
The dates of inspection and refilling should be indelibly recorded on a label securely attached
to the extinguisher or painted on the body (it should not be stamped into the body of the
extinguisher).
Extinguishers should be recharged in accordance with the supplier's instructions immediately
after they have been completely or partly discharged. Sufficient refills for this purpose should
always be kept available. The date of refilling should be recorded as above.
Periodic pressure testing of extinguishers other than carbon dioxide and halon extinguishers
is not considered necessary.
The correct pressure is shown on the indicating device or tell-tale indicator. Where
possible the extinguisher pressure should also be checked using an independent
pressure-measuring device.
(b)
(c)
The extinguisher should be test discharged at least once every two years.
After discharge see that:
1.
2.
On opening the extinguisher and examining the body internally using an illuminating
probe, corrosion is not visible.
3.
The nozzle, strainer, venting device and (where fitted) the internal discharge tube are
not clogged. Clean if necessary.
4.
5.
The sealing washers and hose (if fitted) are in good condition.
6.
The extinguisher is refilled with water, or with special solution in accordance with the
manufacturer's instructions.
7.
8.
Water (soda/acid)
At least twice a year see that:
1.
After carefully removing the acid bottle, the extinguisher is filled to the correct level.
2.
On pouring the main liquid charge into a clean container and examining the body
internally with an illuminating probe, corrosion is not visible. The body should also be
examined externally for corrosion.
3.
There has not been acid leakage, which can be caused by seepage past the lead
stopper in the case of some turn-over models, or which may result from a cracked
bottle. (Cracked bottles should be replaced.)
4.
The nozzle, strainer, vent holes in the cap and (where fitted) the internal discharge
tube and breather valve are not clogged. Clean if necessary.
5.
6.
The sealing washer and hose (if fitted) are in good condition.
7.
If there has not been a leakage of acid, the original main liquid is returned to the
extinguisher. Any slight loss should be made up with water. If leakage of acid or a
large loss of water has occurred the extinguisher should be recharged according to
the manufacturer's instructions.
8.
The extinguisher is correctly re-assembled and the safety device fitted. Each
extinguisher should be test discharged at least once every five years. Turn-over
models (loose stopper acid bottle), however, should be discharged every two years.
After discharge, extinguishers should be thoroughly washed out with clean water and
any pieces of glass or solid matter removed.
Foam (chemical)
At least twice a year see that:
1.
The extinguisher and inner container are filled to the correct levels.
2.
On pouring the liquids into separate clean containers and examining the extinguisher
body internally with an illuminating probe, corrosion is not visible. The body should
also be examined externally for corrosion.
3.
The nozzle, vent holes in the side of the cap, and breather valve (if fitted) are not
clogged. Clean if necessary.
4.
The operating mechanism and discharge valve (if fitted) move freely. Rectify or
replace if necessary.
5.
6.
The original liquid charges, including any undissolved powder, are returned to the
appropriate containers. Any slight losses should be made good with water. If large
losses have occurred, new charges supplied by the extinguisher manufacturer should
be used.
7.
The extinguisher is correctly re-assembled and the safety device fitted. It is not
necessary to stir the contents of this type of extinguisher and stirring may, in fact,
cause damage.
Every extinguisher should be test discharged at least once every two years.
2.
On pouring the main liquid charge into a clean container and examining the
extinguisher body internally with an illuminating probe, corrosion is not visible. The
body should also be examined externally for corrosion.
3.
The gas cartridge is weighed to detect any loss and if this exceeds 10 per cent of the
contents (or more than the percentage recommended by the manufacturers, (if less
than 10 per cent) the cartridge should be replaced. The sealing washer should also
be checked to ensure that it is in good condition.
4.
The nozzle, strainer, branch pipe, internal discharge tube, breather valve and vent
holes in the cap are not clogged. Clean if necessary.
5.
The operating mechanism and discharge valve (if fitted) move freely. Rectify or
replace if necessary.
6.
7.
8.
The extinguisher is refilled with the original main liquid charge. Any loss should be
made up with water.
If the charge is a pre-mixed foam solution and there has been a loss of more than 5
per cent by volume, then a new charge should be used.
9.
The correct pressure is shown on the indicating device or tell-tale indicator. Where
possible the extinguisher pressure should also be checked using an independent
pressure measuring device.
(b)
(c)
Every extinguisher should be test discharged at least once every four years.
After discharge see that:
1.
2.
On opening the extinguisher and examining the body internally using an illuminating
probe, corrosion is not visible.
3.
The nozzle, strainer, branch pipe, venting device and (where fitted) the internal
discharge tube are not clogged. Clean if necessary.
4.
5.
The sealing washers and hose (if fitted) are in good condition.
6.
7.
8.
After discharge, foam extinguishers should be thoroughly washed out with clean water and
any solid matter should be removed.
2.
On emptying the powder into a clean dry container, it is free-f lowing and does not
contain lumps or foreign bodies. If only small, soft lumps occur these can be
removed by sieving the powder. Otherwise powder should be replaced.
3.
On examining the body internally using an illuminating probe, corrosion is not visible.
The body should also be examined externally for corrosion.
4.
The gas cartridge is weighed to detect any loss and if this exceeds 10 per cent of the
contents (or more than the percentage recommended by the manufacturers if less
than 10 per cent) the cartridge should be replaced.
5.
The nozzle, hose, vent holes in the cap and internal discharge tube are not clogged.
Clean if necessary.
6.
7.
The operating mechanism and discharge control (where fitted) operate freely. Rectify
or replace if necessary. (Do not use grease or oil on these parts.)
8.
9.
The correct pressure is shown on the indicating device or tell-tale indicator. Where
possible the extinguisher pressure should also be checked using an independent
pressure measuring device.
2.
3.
4.
5.
6.
Where extinguishers are designed to have the operating mechanism removed, the
operating mechanism and discharge control (where fitted) move freely. Rectify or
replace if necessary. (Grease or oil should not be used on these parts.)
7.
Every extinguisher of the field refillable type should be discharged at least once every five
years.
After discharge see that:
(i)
(ii)
On opening the extinguisher and examining the body internally using an illuminating
probe, corrosion is not visible.
(iii)
The nozzle, hose, venting device and internal discharge tube are not clogged. Clean
if necessary.
(iv)
The operating mechanism and discharge valve (if fitted) move freely. Rectify or
replace if necessary. (Grease or oil should not be used on these parts.)
(v)
(vi)
(vii)
All dry powder extinguishers should be kept perfectly dry after discharged and not washed
out.
Carbon dioxide
At least once a year see that:
1.
2.
The weight of the extinguisher is correct. If a loss in weight of more than 10 per cent
of the contents (or more than the percentage recommended by the manufacturer, if
less than the percentage recommended by the manufacturer, if less than 10 per
cent) has occurred, then the extinguisher should be taken out of service and
replaced.
3.
4.
Where extinguishers are designed to have the operating mechanism removed, the
operating mechanism and discharge control (where fitted) move freely. Rectify or
replace if necessary.
5.
Every carbon dioxide extinguisher should be discharged at least once every ten years.
2.
3.
The correct pressure is shown on the indicating device (if fitted). Where possible the
extinguisher pressure should also be checked using an independent measuring
device. Extinguishers showing a significant loss of pressure (as defined in the
manufacturer's recommendations) should be taken out of service and replaced.
4.
Where extinguishers are designed to have the operating mechanism removed, the
operating mechanism and discharge control (where fitted) move freely. Rectify or
replace if necessary.
5.
Every halon (stored pressure) extinguisher should be discharged once every ten years.
Extinguishers containing carbon tetrachloride should not be used.
CAPACITY:
PRESSURE CHARGE:
OPERATING PRESSURE:
DURATION OF DISCHARGE:
Note:
90-litre AFFF (model SF 20 FN) and fluoroprotein foam (model PF 20 and SF20) mobile units of
similar design to this extinguisher are also available
CAPACITY :
11 litres (2.5 UK gal) foam compound (6% only)
OPERATING PRESSURE:
2 10.5 bars
At operating pressure of 3.5 bars it produces about 1400 litres foam during operating time of
4 minutes
CHUBB FL 2.5 HOSE REEL FOAM UNIT
CAPACITY :
WATER SUPPLY REQUIRED:
OPERATING PRESSURE:
OPERATING TIME:
Foam improver/nozzle
section in which foam
of correct consistency
is formed and expelled
as high-velocity rope
jet. For water spray
only, this section is
removed
Foam generator
section which
combines water,
foam liquid and air
Carrying handle
Connection for
aluminium foam
compound pick-up
tube/hose assembly
or for 1-inch hose
from wheeled foam
liquid tank
Swept-elbow
connector fitted with
two 2-inch
instantaneous male
couplings. (Other
couplings can be
fitted)
Swivelling base
plate allows
alteration of
elevation while the
unit is operating
JET LENGTH
JET HEIGHT
- FOAM
WATER FLOW :
FOAM COMPOUND
FIGURE 10.03.16
FIGURE 10.03.17
FIGURE 10.03.18
FIGURE 10.03.19 GENERATORS SEPARATED FROM PROPORTIONER MULTIPLE TANKS SEPARATE FOAM LINES TO EACH TANK
FIGURE 10.03.20
GENERATORS SEPARATED FROM PROPORTIONER MULTPLE TANKS SINGLE FOAM SOLUTION LINE
TO GENERATOR MANIFOLD
HBPG 225
HBPG 450
HBPG 900
HBPG 2250
225 litres/min
450 litres/min
900 litres/min
2250 litres/min
(500 lmp GPM)
FIGURE 10.03.23 CHUBB BIG 10, 20 AND 30 BASE INJECTION FOAM GENERATORS
MODEL
BIG 10
20
30
litres/min
455
910
1365
FOAM OUTPUT:
litres/min
1800
3600
5400
Bars
FIGURE 10.03.24
APPENDIX 10.03.27 -
A. General Description
The capacity of a base injection system for fixed roof tanks is based on the minimum
foam solution (water plus foam compound but not aerated) flow rate required to extinguish
a storage tank fire. The Recommended minimum rates are as follows:
Class I products -
Class III products - white oils - 4.9 litres/minute/m (0.10 UK gallon/minute/ft ) of product
surface to be protected.
- black oils - base injection not suitable.
Sufficient foam compound and water should be available to permit operation at the above
application rates for a period of 30 minutes.
The design of a base injection system involves a sequence of steps as follows:
(i)
Calculating the minimum acceptable foam solution flow rate. When more than
one tank is to be protected by the same system, the design flow rate is
determined by the tank requiring the highest flow rate.
(ii)
Selecting the number, size and distribution of foam generators plus the general
layout of water, foam solution and finished foam pipelines. Depending on the tank
farm layout as well as the location and orientation of water supply, the
combination and grouping of generators (and their related inductors) may vary
from:
(a) a single battery of generators to supply all needs via a foam distribution
manifold, to:
(b) a number of separate batteries of generators strategically located to serve
different groups of tanks.
The decision between semi-fixed and fixed systems will also have to be made at
this point in the calculation.
(iii)
Selecting the number of foam inlets for each storage tank, which is governed
primarily by the diameter of the tank in accordance with the 'Number of Inlets'
table shown in C5. An alternative arrangement using a single tank inlet and
multiple foam outlet points is shown in Figure 10.03.28.
(iv)
Estimating the foam inlet diameters. Foam inlets must be sized so that the
velocity of foam entering the tank is not greater than 3.0m/second (10ft/second)
for volatile products (flash-point less than 21C) or 6.0m/second (20ft/second) for
non-volatile products (flash-point equal to or greater than 210C). The correct
attitude of the inlets is horizontal (not upwards or downwards); a 45 chamfer is
acceptable, see Figure 10.03.26.
Foam velocities may be greater in the pipelines further upstream (which permits
the use of smaller pipelines) but pipelines must be increased to the correct inlet
diameter at a distance of not less than 20 times the pipe diameter from the inlet to
the tank. At no point should the foam velocity exceed 9.15m/second
(30ft/second).
The inlet diameters estimated at this stage will have to be checked at a later
stage in the design depending on the ultimate hydraulics of the system (see D(c)
below).
(v)
The design of foam generators is normally such that the maximum back
pressure downstream of the generator outlets (caused by pipeline losses plus
static head of product in the tank) must not exceed 25% of the inlet pressure
to the foam generators. This then is the starting point of the hydraulics
design and in situations with high tanks (i.e. high static head of product) and
high foam flow rate requirements, can result in substantial pressure
requirements. For this reason since pipeline pressure losses for water or
foam solution are much lower than for finished foam, a guiding principle is to
minimise the lengths of finished foam lines by positioning the foam
generators as far downstream as practically possible so as to limit the
distance finished foam has to be pumped before it enters the storage tank.
(vi)
Estimating the inlet pressures to the foam generators (i.e. 4 times the outlet back
pressures derived from (v) above): thence calculating the foam solution pipeline
sizes between the pump discharge and the generator inlets (including the
pressure losses sustained through the foam compound inductors).
(vii)
Estimating the volume of foam compound as well as the water flow rate and
water volume needed to provide base injection operation at the recommended
application rate for a period of 30 minutes.
From the above the base injection system for one or more tanks can be calculated in
isolation from the requirements for the rest of the fire fighting system. Section D below
describes the points to be considered to produce an overall tank farm fire fighting
protection system.
B. Design Factors
(i)
Foam pipelines should, whenever possible, run outside the bund area so as to be
less exposed to fire. This may lead to longer lines which will add to pipeline
friction losses. Where a foam line has to run inside the bund area flanges should
be eliminated or minimised. Wrapping and burying lines will provide additional
fire protection.
(ii)
Testing - once a base injection system has been installed it has to be tested in
order to prove the equipment as well as train personnel in its operation. This is
straightforward if the tank is still empty and the injected foam can be removed
from the tank. If however, the tank contains product, a perfectly adequate test
can be carried out if a foam outlet/sample point is installed in the foam line
upstream of the tank valve.
The sample points do not have to be close to the storage tanks but may be more
conveniently located near the foam generators (subject only to the 20m
minimum distance necessary to permit full development of the foam properties
or even in the foam solution lines in which case a generator would have to be
attached at the time of sampling. This will minimise consumption of foam
compound during tests and fire practices, and will also facilitate flushing out the
lines after such tests. A minimum slope of 1/240 with suitable drainage outlets
will facilitate flushing and draining foam lines after testing or usage.
(iii)
(iv)
The non-return valves should preferably be soft seated (but not spring-loaded).
Accepted materials for the soft seat are nitrile rubber, Viton and Buna-N but not
Neoprene. In the event that product passes the non-return valve and fills the line
from the tank to the generator manifold, the aerated foam is able to push the
product back to the tank without significant deterioration. If soft seated non-return
valves are not available, conventional non-return valves can be installed.
(v)
(vi)
The principle mentioned in A(v) above of converting foam solution into aerated
(finished) foam at the latest possible moment will help limit pressure
losses/reduce pipe diameters. Against this saving will have to be offset the
possible need for additional generators because rather than a single battery of
generators to cover all needs, locating generators further downstream in the
system may mean having to install more than one small battery of generators
resulting perhaps in a greater total number of generators required. The relative
economics of this must, of course, be estimated. Such a situation would probably
not occur with a semi-fixed system which depends on a common store of
generators which are taken to whichever is the appropriate foam inlet point.
(vii)
1. Fixed base injection system where tanks are only a short distance from fire
pump/water supply permitting the foam station [foam compound tank,
inductor(s), generator(s), etc.] to be positioned together near the pump
discharge.
(a)
(b)
2. Fixed base injection system where for distance and/or pressure drop reasons
the foam generators are separated from the inductor/proportioner units.
(a)
(b)
This layout (see Figure 10.03.19) is for multiple tank protection with
separate lines to each tank. A foam proportioner may be considered
here since it will automatically induce the correct rate of foam
compound depending on which foam control valve (VC) is opened,
and in addition has a much lower pressure drop compared with
inductors. As this system permits manual control it is ideal where
power supply (for remote valve operation) is unreliable. For foam
sampling see the comment given in 2(a) above.
(c)
(viii)
C. Design Example for Base Injection of Foam into Single Tank (see Fig 1)
1. Tank Details
Product
Gasoline
Tank size
10" (250mm)
150m
907.5m
7.4 litres/min/m
7.4 x 907.5
6716 litres/min
4.9 x 907.5
4447 litres/min
x 34 2
4
3. Foam Solution Flow Rate :
4500 litres/min
While these two large units are ideal for this particular single tank size, were
it intended to use the same set-up to supply foam to a number of tanks of
which this was the largest, a combination of say 1 x 2250 plus 2 x 900 and
1 x 450 litres/min generators would permit using various combinations to
match the different tank sizes.
5. Number of Inlets
The number of tank inlets required depends upon the diameter of the tank:
Minimum No of Inlets
Tank Diameter in Metres
Volatile products
(Flash-point<21.0C)
Non-volatile products
(Flash-point>21.0C)
18.5
18.5 - 35.5
35.5 - 42.5
42.5 - 48.5
48.5 - 55.0
55.0 - 61.0
465m
695m
Diameter needed
Can use product inlet (250mm) plus one new foam inlet.
7. Pressure Drops:
(a) Back pressure due to height of product (assume full tank).
22m x 0.7 (density) x 0.0978 = 1.51 bar
(b) (i) Pipeline friction loss if finished foam pumped whole distance (150m) from
pump to tank:
4500 litres/min solution
finished foam expansion
=18000 litres/min
=4
Pipe diameter
Loss (bar/100m)
250mm
0.3
0.45 bars
200mm
0.9
1.35 bars
150mm
3.5
5.25 bars
(ii) Friction loss if foam solution pumped 125m at 4500 litres/min (i.e. finished
foam only for final 25m (250mm) see A(v)
Pipe diameter
Loss (bar/100m)
150mm
0.62
0.77 bars
(iii) Assume alternative (ii) and base design on pumping foam solution through
125m of 6 inches (150mm) pipe to vicinity of tank before generating foam
which then passes through 25m of 10" (250mm) pipe system to tank inlets.
(c) Friction losses through fittings and line (250mm) downstream of generators refer Figure 1 of this Appendix, 50% of foam goes through each branch to tank.
Friction loss @ 9000 litres/min finished
0.2
0.17 bars
81.8
m
100
1.51 bars
0.17 bars
1.68 bars
Sub-totals
(e) Generator inlet pressure
1.68 bar
4 x 1.68
6.72 bar
7.0 bar
7.0 bar
24% OK
1.68
100
7.00
Note: In some cases the back pressure downstream of the generator may be
such that the required inlet pressure could be higher than 7.0 bar. For example if
the downstream back pressure came to 2.0 bar, then the generator inlet pressure
would have to be 2.0 x 4 = 8.0 bar. The effect of this would be to increase the
generator throughput from its design of 2250 litres/min at 7.0 bar to:
Throughput @ 8.0 bars
8
7
2250
This higher flow rate would marginally increase downstream friction losses which
would have to be checked before settling on the correct design flow rate for the
rest of the calculation. Additionally it will be necessary to check that tank inlet
velocities have not increased above the design maximum.
0.62 bar/100m
125
100
0.62
0.77 bar
0.62
0. 13 bar
Nil
(iv) Total
0.90 bar
21.4
100
12.0 bar
Volume
Flow rate
(iii)
Pressure
Diameter of largest
tank in m
Number of branch
pipes
Minimum operating
time in minutes
up to 10
10
10 - 20
20
20 - 29
20
30 - 37
30
over 37
30
marked on the face of the gauge so that in future the correct flow rate to each tank
can be set simply by adjusting each sprinkler line valve until the related gauge reads
the pre-determined pressure. During actual usage, the setting of these valves will
have to be back-checked and re-adjusted both at the time of initial opening to start
the cooling, and subsequently at intervals since fluctuations in water demand will
cause some pressure variations during the fire fighting activity.
Another situation which does not have any adverse effect is when the
product level in a tank is particularly low at the time of a fire. In such a case
the back pressure downstream of the generator is reduced and it might be
thought this would lead to an increase in flow rate and consequent tank inlet
velocity problems. That this does not occur in practice is because the foam
generator design is such that the foam throughput is only dependent on
upstream flow conditions and is independent of downstream conditions as
long as the 25% back pressure maximum is not exceeded.
(d) Result
From the above considerations, it should be possible to design a total tank farm
protection system which will, given sufficient stocks of foam compound and water,
provide the total demand to meet most foreseeable tank farm fire situations. It must
be realised however that the highest foam demand for a tank fire may not coincide
with the highest cooling water demand for adjacent tanks. For this reason all
combinations of tank foam plus adjacent cooling must be calculated to determine the
maximum total demand on which the overall design should be based.
10.04.00
10.04.01
Types of Fire
Fires are classified as follows:
A. Dry fires: combustible solid materials such as paper and wood.
Normally these fires can best be extinguished by cooling with water.
10.04.02
Water
Fresh or salt water can be applied in the form of jets, sprays or fog.
Sprays and fog are more effective for hydrocarbon fires because the particles of water
are more easily vaporised; the process of extraction of latent heat of vaporisation has a
cooling and therefore dampening effect upon the fire. Normally jets of water should not
be used is their effect as to spread hydrocarbon fires, the exception being if maximum
throw is required for example against strong winds.
The main uses of water for fighting fire are:
-
Spray cooling of burning product surfaces and equipment adjacent to the fire.
10.04.03
Foams
Mechanical foams are the usual type used. These are made from mixing foam
concentrate (compound) with water and then aerating the emulsion. Low expansion
foams are normally used for liquid hydrocarbon fires. Correctly applied foams form a
sealing blanket, have a smothering effect on the fire, suppress flammable vapours and
cool the product.
Low-expansion foams are not suitable for extinguishing LPG fires. High-expansion foams
can however be used for controlling LPG pool fires and to reduce heat radiation (refer
'Plant Operating Manual' Volume 3 for detailed information).
Although protein-based foams will gradually deteriorate during long-term storage,
particularly in ambient temperatures above 21C, much can be done to preserve this
valuable asset. Appendix 10.04.01, describe measures that should be taken to prolong
the shelf life of foam compounds. As a control measure compound containers should be
date marked when received so that they can be used on a first-in first-out basis for fire
training and fire drills. Notwithstanding the efforts taken there will be a need on occasion
to test the quality of foam compound and a simple field test is described in
Appendix 10.04.02.
The main types of foam are as follows:
(a) Fluoroprotein foam
This has largely replaced standard protein foam for fighting hydrocarbon fires
because of its better performance, higher fluidity and greater resistance to fuel
entrainment - particularly valuable for base injection into storage tanks, for which
standard protein foam is unsuitable. It can be used with fresh or sea-water.
10.04.04
Carbon Dioxide
Carbon dioxide being an inert gas extinguishes a fire by dilution or displacement of air. It
is particularly effective in sheltered locations containing electrical switches, motors or
other equipment. However, because of its suffocating effect its use in unventilated
spaces should be avoided except by an automatic atmospheric flooding system when
nobody is present.
10.04.05
10.04.06
APPENDIX 10.04.01-
Proper storage of foam compound is necessary for two reasons. First, to ensure that it will
work effectively when needed in a crisis and, secondly, for economic reasons. When stored
correctly as outlined in the 'Plant Operating Manual' Volume 1 (07.02.02), foam compound
has an indefinite shelf life. Provided that exposure of the foam compound to the atmosphere
is kept to a minimum, a storage life in excess of 10 years should be possible. High
temperatures and excessive contact with the air will shorten shelf life.
Storage recommendations are summarised below:
In sealed containers as supplied, or in static foam tanks with a small air space above
the foam compound.
(ii)
(ii)
Temperatures of 50C are permissible for short periods of a few months, but are too
high for long-term storage.
(iii)
The temperatures quoted relate to the foam compound, not the air. Daytime air temperatures
in some tropical climates may exceed 50C, but a bulk liquid store will not reach this value
because average ambient temperatures over a 24-hour period are lower than this.
(ii)
To minimise frothing when filling or topping-up bulk storage tanks, foam compound
should be introduced below the liquid surface.
(iii)
(iv)
Nitrogen purging may be used to exclude oxygen above the stored compound and
prevent oxidation. However, this is expensive and not necessary with modern
compounds, and it will not significantly increase storage life.
Protein-based fire fighting foam compounds will gradually deteriorate during long-term
storage. Naturally some form of testing is desirable to confirm the efficiency of the product
and samples of the compound should be returned to the original supplier for laboratory
testing. However, where this is not possible or practicable the simple test procedure
described below will establish whether the foam compound will meet the minimum standards
acceptable or whether it should be discarded.
Storage life
Maximum storage life is obtained when the foam compound is kept cool (below 21C) in its
original sealed container or in a full storage tank with an expansion dome and vent to
minimise the surface of the compound in contact with the air (see Appendix 10.04.01).
Storage conditions, temperature cycle and the original quality of the foam can affect the
storage life which can vary between a few years to over 20 years.
After some years of storage it is desirable to test whether the compound will still perform
efficiently. A one litre sample of the compound (preferably drawn from the middle of the tank
or number of containers, and taking care to clear any pipelines and remove sludge before the
sample is drawn) should be sent to the original suppliers for examination in their laboratories.
Appropriate testing will establish if the foam:
Is up to specification
Has deteriorated significantly and should not be retained for fire protection.
Test procedure
The test should be carried out in cool conditions with water and air temperatures as near to
10C as possible. (In hot climates an early morning test is most likely to provide acceptable
temperature conditions.)
An empty metal drum with a splash board is set up against a wall as shown in Figure 1. The
pressure gauge should be as near the upstream of the branch pipe as possible. If a foam
inductor is used this must be located upstream of the pressure gauge and not between the
gauge and the branch pipe (see Figure 2). If an Angus variable foam inductor is used it
should be set at a four percent pick-up, no setting is necessary for normal pick-up tubes.
The branch pipe should be held approximately 10 to 15 metres from the splash board. With
the water supply connected, the flow is adjusted to give a reading of 5 bar on the pressure
gauge. The pick-up tube is placed in the foam sample and foam is produced for a few
seconds before directing the foam stream at the splash board so that the foam falls into the
empty metal container. As soon as the container is full the foam stream is moved away and
the splash board is used as a scraper to remove the excess foam to give a level filling of the
container.
The splash board is then placed as a cover over the open top and the drum is left in the
shade. After 30 minutes the cover is removed and the distance from the top of the container
to the foam level is measured. The cover is replaced and the drum is left to stand for a
further three and a half hours at the end of that time the liquid collected at the bottom of the
container is poured into a calibrated vessel and the volume of liquid collected is noted. Any
expanded foam still present should be ignored. The liquid can be scooped out with a small
container or poured out provided that none is lost. An alternative method would be to use the
drum upside down with the bottom cut out and remove the liquid either through the bung or
by fitting a small tap.
Calculating results
(a) Foam stability
The distance from the top of the container to the foam level should not be more than ten
per cent of the total depth of the container i.e.:
Distance measured x 100
Depth of container
d2 h
4 10 6
870 mm
Diameter of container
580 mm
80 mm
34 litres
Volume of vessel
870 580 2
4000000
230 litres
Stability
80 100
870
Expansion
230
34
6.8
(d) Conclusion
The sample is satisfactory.
Recommendation
PETRONAS companies holding stocks of protein and fluoroprotein foam compound of
doubtful or unknown quality are recommended to carry out this test as soon as possible.
Where problems arise it might be useful to test fresh samples of the same make of
compound and compare results of tests on old samples of the same make of compound and
compare results of tests on old samples of compound as an indication of whether correct test
procedure has been carried out.
If the test results are well within the limits given, further testing in two or three years time
should suffice. If results are only marginally adequate it may be advisable to check annually.
In order to minimise costs and gain the most benefit from the exercise it may be appropriate
to run the test as part of a fire fighting training session or practice.
FIGURE 1
FIGURE 2