You are on page 1of 58

Reading Tips

Dear Customers:
Thank you for purchasing and using our companys products. In order to safe, correct,
effective use of this device, please pay attention to the following important tips:

Please read the manual carefully, and in accordance with the instructions to adjust the
provisions, testing and operation.

It prohibited the live insertion device; touch the plug printed circuit board of the chip
and device.

Please use the qualified testing equipment and instruments to test and detection.

If the device have some abnormal or need to repair, please contact with our company
service hotline (0731) 84210990.

We reserve the right to modify the specifications. If there are discrepancies of products and
specifications, please contact with me, we will provide the corresponding services for you.

GTG-84X Generator Protection Measurement and Control Device

Catalogue
1 Outline.......................................................................................................................................3
1.1
Scope of Application...................................................................................................... 3
1.2
Function and Characteristics.......................................................................................... 3
2. Technical Index............................................................................................................................. 5
2.1 Rated Data........................................................................................................................... 5
2.2 Consumption....................................................................................................................... 5
2.3 Environment Condition....................................................................................................... 6
2.4 Anti-interference Performance............................................................................................ 6
2.5 Insulated Performance.........................................................................................................7
2.6 Mechanical Performance.....................................................................................................7
2.7 The Tuning Element Working Rang and Error....................................................................7
2.8 Delay Element Setting Range and Error............................................................................. 7
2.9 Telemeter, Remote Signal Measurement Precision............................................................. 8
3. Installed Hardware........................................................................................................................ 8
3.1 Chassis Structure................................................................................................................. 8
3.2 Main Plug............................................................................................................................ 9
4Function Introduction................................................................................................................10
4.1 Protection Function........................................................................................................... 10
4.2 Data Collection Function...................................................................................................11
4.3 Control Function................................................................................................................11
4.4 Communication Function.................................................................................................. 11
4.5 Debug Function................................................................................................................. 11
4.6 Safety Function................................................................................................................. 12
5. Protection Principle..................................................................................................................... 12
5.1 Ratio Restraint Differential Protection of Generator.........................................................12
5.2 Discrimination of TA disconnection................................................................................. 13
5.3 High sensitive zero-sequence current transverse differential protection........................... 13
5.4 Zero Sequence and Third Harmonic Voltage Stator Grounding Protection.......................14
5.5 Zero Sequence Current of Stator Grounding Protection................................................... 15
5.6 Rotor One-point Grounding Protection and Two-point Grounding Protection.................15
5.7 Loss of Excitation Protection............................................................................................ 16
5.8 Reverse Power Protection................................................................................................. 18
5.9 Compound Voltage (Memory) Over Current Protection................................................... 19
5.10 Excitation Transformer over Current Quick Break Protection........................................ 20
5.11 Quick Break Protection................................................................................................... 20
5.12 Negative Sequence Current Protection............................................................................20
5.13 Stator Overload Protection.............................................................................................. 20
5.14 Over Voltage Protection.................................................................................................. 21
5.15 Low Voltage Protection................................................................................................... 21
5.16 Abnormal Frequency Protection......................................................................................22
5.17 Non Electricity Protection Description........................................................................... 23
5.18 TV Disconnection Test.................................................................................................... 23
1

GTG-84X Generator Protection Measurement and Control Device


5.19 Control Circuit Abnormity Alarm................................................................................... 23
5.20 Device Fault Alarm......................................................................................................... 24
5.21 Telemetry, Remote Signal, Remote Control Function.....................................................24
5.22 Wave Recorder................................................................................................................ 24
5.23 GPS Time Synchronization............................................................................................. 24
6Setting....................................................................................................................................... 24
6.1 Soft Plate........................................................................................................................... 24
6.2 Setting and Control Word.................................................................................................. 25
7. The Man-machine Interface Operation Description....................................................................29
7.1 Panel Indicator Definition................................................................................................. 29
7.2 The Keyboard and Normal Display...................................................................................30
7.3 Menu List.......................................................................................................................... 30
7.3.1 Button Introduce..................................................................................................31
7.3.2 Main Menu.......................................................................................................... 31
7.3.3 Setting Operation.................................................................................................32
7.3.4 Report Information.............................................................................................. 36
7.3.5 Analog Value....................................................................................................... 37
7.3.6 System Configuration..........................................................................................38
7.3.7 Debug Operation................................................................................................. 41
7.4 Setting Management..........................................................................................................42
7.5 Debug Operation............................................................................................................... 43
8. Installation and Debugging On Site............................................................................................ 43
8.1 Debugging Document and Test Instrument Preparation....................................................43
8.2 Inspection before Energizing.............................................................................................43
8.3 Energizing Test..................................................................................................................44
9. Commissioning Instrument and Announcements........................................................................45
9.1 Set and Inspect Before Commission..................................................................................45
9.2 Normal Operation and Abnormal Signaling Indication.....................................................46
10Principle of Equipment and Wiring Diagram..........................................................................46

GTG-84X Generator Protection Measurement and Control Device

1 Outline
1.1

Scope of Application
GTG-84X digital generator protection measurement and control device is applicable to

50MW and the below capacity of running alone or with system of parallel operation of generator
protection and monitoring device, the series device with other protection measurement and control
device and LCU (units and public) composed of power plant automation monitoring system,
completion of the power plant automation control and protection.

1.2

Function and Characteristics


Functional Configuration Table
Classify

Protection
Function

Function Name

GTG-841

Generator differential motion protection

Generator transverse differential protection

Generator stator overload

Generator stator grounding

Generator rotor one-point grounding protection

Generator rotor two-point grounding protection

Loss of excitation protection

Generator frequency abnormal protection

Generator reverse power protection

Generator over voltage protection

Generator low voltage protection

Generator compound voltage over current protection

Generator negative sequence over current protection

Generator quick break protection

Generator zero sequence over current protection

Exciting dynamo(transformer)quick break protection

Exciting dynamo(transformer) over current protection

Generator non-electricity protection

TA disconnection test

TV disconnection test
Operation
circuit
Measuremen
t
And
Control
Function

GTG-842

Control circuit abnormal alarm

16 way remote signal input collection, device remote


signal shift, accident remote signal

Normal circuit break remote deciliter, remote deciliter

P, Q, IA, IB, IC, Ua, Ub, Uc, COS, f

Switch accident in statistics and event SOE etc

Fault recorder

Description
1

Power completely independent containing anti


adjustable locking function operation circuit

Description

GTG-84X Generator Protection Measurement and Control Device


Time hack

Realize GPS time hack,network time hack

Communicat
ion

Ethernet,RS232/458 communication interface

Description 1:
All actions have the exit protection are all arranged three outlet, respectively for the
stepout, shutdown, de-excitation, corresponding action by soft pressure control and exit from the
control word changeover;
Generator protection configuration as shown below:

Picture 1-2 Generator protection configuration diagram


Main Features
a.

4U standard aluminum chassis, combination of plug-in structure, after the plug case, each
functional

module

design

alone,

electricity

are

completely

separated,

strong

anti-interference ability, convenient field maintenance;


b.

CPU intelligent card design, open into the open plug-ins to achieve real-time complete
self-test; can be detected in each relay coil;

c.

Plug-in based on CANBUS bus links between, reduce the connection between the
connector plug, bad real time detection;

d.

Double 32 computer systems, the redundant system; protection function using the Dezhou
Instrument Company produced the 32 bit floating-point DSP processor, program and data

GTG-84X Generator Protection Measurement and Control Device


in the chip operation; operation speed, high reliability;
e.

Man-machine interface, network communication and other management functions by


Philips Company produced 32 ARM MCU, speed, on-chip memory capacity big, strong
ability of network interface;

f.

16 AD sampling, high measuring precision; weekly wave 48 sampling points, harmonic


processing capability;

g.

Protection module using computer assisted graphical interface design is convenient for the
two series of products development and functional modifications, flexible, efficient
engineering design;

h.

Complete the circuit breaker control circuit is provided with a remote control, jump,
closing, spring without stored energy blocking close function etc;

i.

Use 192*64 monochrome graphic LCD, Chinese menu interface; the flexibility to choose
double Ethernet and double 485 interface;

j.

Can save at least 500 report recent incidents and operation report;

k.

User management module using real-time multitask operating system, network interface,
tasks such as real-time;

l.

Can store 10 sets of protection setting value, double value zone self-test and mutual
combination, setting change safely and convenient.

m. Based on electric power industry standard DL / T667-1999 (IEC 60870-5-103) standard


communication protocol, and convenient with microcomputer monitoring or protect
management computer network communication.

2. Technical Index
2.1 Rated Data
a.

Rated AC voltage: 220V (110V orders indicate)

b.

Rated AC data:

phase voltage

100/ 3 V

Zero-sequence voltage

100V

AC current
Rated frequency
c.

allowable deviation +15-20

5A (1A orders indicate)


50Hz (60Hz orders indicate)

Thermal Stability:
AC voltage circuit: long time operation

1.4Un

AC current circuit: long time operation

2In

10s

20In

1s

40In

2.2 Consumption
a.

AC voltage circuit:

phase0.5VA;

b.

AC current circuit: when In=5A ,phase 1VAwhen In=1A, phase0.5VA;

c.

Protection power supply circuit: when in normal work, 10W; in protection action,
15W.
5

GTG-84X Generator Protection Measurement and Control Device

2.3 Environment Condition


a.

Environment temperature:
Work:

-25+55

Storage: -25+70Relative humidity of not more than 80%, the ambient air does
not contain acidic, alkaline or other corrosive and explosive gases prevent rain,
snow indoor; the limit without applying excitation volume, device is not
irreversible change in appearance, temperature after recovery, device can work
normally.
b.

Relative humidity: Most of the wet mean monthly maximum relative humidity is 90%,
and the monthly mean minimum temperature is 25 and the surface without gel. When
the maximum temperature is +40 , the average maximum humidity is not more than
50%.

c.

Atmospheric pressure:80kPa110kPaAltitude < 2km.

2.4 Anti-interference Performance


a.

Burst Disturbance Test: acceptable burst disturbance tests of 1MHz and 100 kHz
damped

oscillation waves (first half-wave voltage amplitude

common-mode is 2.5kV and differential mode is 1kV) in GB/T14598.13 - 1998.


b.

Fast Transient Disturbance Test: acceptable fast transient disturbance test whose
severity level is in Chapter 4, GB/T14598.10 - 1997.

c.

Radiated Electromagnetic Field Disturbance Test: accept radiated electromagnetic field


disturbance test whose severity level is in Chapter 4, GB/T14598.9 - 2002.

d.

Electrostatic Discharge Test: acceptable electrostatic discharge test whose severity level
is in Chapter 4, GB/T14598.14 - 1998.

e.

Electromagnetic Emission Test: acceptable GB/T14598.16 - 2002 Conducted emission


requirements in 4.1 and 4.2 limits the provisions of the electromagnetic radiation
emission limits for emission tests.

f.

Power Frequency Magnetic Field Immunity Test: acceptable power frequency magnetic
field

immunity tests whose severity level is in Chapter 5, GB/T17626.8-

1998.
g.

Pulse Magnetic Field Immunity Test: acceptable pulse magnetic field immunity tests
whose severity level is in Chapter 5, GB/T17626.9 - 1998.

h.

Damped oscillatory magnetic field immunity test: accept damp oscillatory magnetic
field immunity test whose severity level is in Chapter 5, GB/T17626.9 - 1998.

i.

Surge Immunity Test: acceptable surge immunity tests whose severity level is in
Chapter 4, IEC 60255-22-5: 2002.

j.

Immunity to Conducted Disturbances Test: acceptable immunity to conducted


disturbances test, induced by radio-frequency field in Chapter 4, IEC 60255-22-6: 2001

k.

Power Frequency Immunity Test: acceptable power frequency immunity tests in Chapter
4, IEC

60255-22-7: 2003.

GTG-84X Generator Protection Measurement and Control Device

2.5 Insulated Performance


a.

Insulation Resistance: the insulation resistance should be over 100M tested by test
equipment whose open-circuit is 500V between electric conductivity of circuits to each
(that is, non-charged case or exposed metal parts), the loop and the DC circuit or AC
current and AC voltage circuit loop.

b.

Dielectric Strength: communication circuit and 24V devices such as weak current input
and output terminals to each can withstand 50Hz, 500V (effective value) AC voltage
and no breakdown or flashover occurred during over 1min test; it can withstand 50Hz,
2kV (RMS) AC voltage and no breakdown or flashover occurred during over 1min test
between the rest charged in the conductive circuit to each (the shell or exposed metal
parts of non-electric), AC circuit and the DC circuit, AC current circuit and AC voltage
circuit.

c.

Impulse Voltage: communication circuit and 24V devices such weak current input and
output terminals to each can withstand 1kV (peak) of the standard lightning impact
test; it can withstand 5kV (peak) of the standard lightning impact test between electric
conductive terminals to each, AC circuit and the DC circuit, AC current circuit and AC
voltage circuit.

2.6 Mechanical Performance


a.

Vibration Response: acceptable vibration response tests whose severity level is I in GB /


T 11287-2000 4.2.1.

b.

Shock Response: acceptable shock response tests whose severity level is I in GB / T


11287-2000 4.2.1.

c.

Vibration Durability: acceptable vibration durability tests whose severity level is I in GB


/ T 11287-2000 4.2.1.

d.

Shock Durability: acceptable shock durability tests whose severity level is I in GB / T


11287-2000 4.2.1.

e.

Impact: acceptable impact tests whose severity level is I in GB / T 11287-2000 4.2.1.

2.7 The Tuning Element Working Rang and Error


a.

b.

Setting Value Range


DC Voltage

2V120V

DC Current

0.1In20In

Residual Current

0.02A12A

Setting Error
Current

< 2.5%

Voltage

< 2.5%

2.8 Delay Element Setting Range and Error


40ms Max. within 0s2s(including 2s); 2 of setting value Max. within 2s100s.

GTG-84X Generator Protection Measurement and Control Device

2.9 Telemeter, Remote Signal Measurement Precision


a.

Current, Voltage:

0.2 class;

b.

Power and others:

c.

Resolution of Remote signals:

d.

GPS Clock Synchronization (with pulse): < 1ms;

e.

Electrical Independent Contact out of the input, and AC 220V input.

0.5 class;
< 1ms;

3. Installed Hardware
3.1 Chassis Structure
The company series device chassis structure adopts the standard all-aluminum PC cases as
trunk, whose height is 4U, length is divided into half and full chest, where the length of the full
chest is 19 inches, and it has the same size as full chest when two half chests are piece together. Its
appearance is not only beauty but also beneficial to group screen. GTG-84X series adopts the
entire panel, including LCD panel, signal light, keyboard, corporate identity and so on. Device
unit chassis is reinforced and designed by strong anti-vibration and anti-interference, which ensure
that it is still high reliable installed in the harsh conditions. It is not required to add AC and DC
input interference module whether installed distributed or by groups.

181

25

Device dimension, as shown in figure 3-1:

262

Picture 3-1 Dimension


Device installation the size of holes, as shown in figure 3-2:

GTG-84X Generator Protection Measurement and Control Device

Picture 3-2 The size of holes

3.2 Main Plug


When viewed from behind, it consists of the following plug-ins from right to left: AC plug 1,
AC plug 2, CPU plug-ins, intelligent plug 1 and intelligent plug 2 (including power supply
module), LCD and buttons in front of the motherboard module.
a.

AC plug 1

Support for up to 6 current and 4 voltage circuits, for system secondary side current, voltage
converter for weak signal, by a multichannel selective switch is switched to the corresponding
analog value, delivery to the CPU plug in for AD conversion, and the strength of electrical
isolation effect.
b.

AC plug 2

Support for up to 6 current and 4 voltage circuits, for system secondary side current, voltage
converter for weak signal, by a multichannel selective switch is switched to the corresponding
analog value, delivery to the CPU plug in for AD conversion, and the strength of electrical
isolation effect.
c.

CPU plug-ins

CPU plug-ins consists of the ARM-based 32-bit microprocessor, 32-bit DSP microprocessor,
RAM, A/D transformation, Flash Memory, Ethernet ports, 485 ports, Optical (optional) and
related circuits form. ARM-based CPU is 32-bit fixed-point processor, clocked at 60MHz; while
DSP-based CPU is 32-bit floating-point processor, clocked at 60MHz; and A/D data conversion
accuracy reaches 16-bit. Integrated circuits all adopt industrial or military products, and ensure
high stability and reliability.
d.

Intelligent plug 1

Intelligent plug 1 mainly includes 8 bit SCM, open into the open drive circuit, CANBUS
circuit, tripping exit, remote signal, standby off into the open relay etc.
e.

Intelligent plug 2(including power supply module)

Intelligent plug 2 includes power supply module and extended into the open part. Power
supply module transfers external AC or DC power into the voltage operating required, output +5
V, 9V, and +24 V. Extended into the open part includes 8-bit intelligent SCM, CANBUS related

GTG-84X Generator Protection Measurement and Control Device


circuit, input remote signal and output relay etc.
Panel Module
It clouds LCD, intelligent SCM, press key, drive circuit and signal light circuit etc.

4Function Introduction
The main function includes protection, data collection, controlling, communication,
debugging and security. The device is applied to sub-computer workstation function designed. It
can not only be used separately as digital protection device, but also form systems with different
structures.

4.1 Protection Function


Protection is programmable. It is set when deliveries from factory, according to a certain
device object and different voltage level. However, it also can modify online or download from
our website to meet onsite requirements and avoid replace other device or change device software.
There are 10 sets protection setting values, which can be chosen the switch flexibly according
to operational state. Set several of protection soft clamps and control words in protection setting,
to implement multiple combinations of protection functions and satisfy operating safely and

10

GTG-84X Generator Protection Measurement and Control Device


stably.

4.2 Data Collection Function


It includes analog collection and on-off state quantity collection.
Analog include electricity and non electricity. Analog collection is all-AC input, and
implements multi-level isolation and digital filtering to ensure the device reliable. It adopts 16-bit
AD with high speed and precision to meet the request of data real time and high accuracy. It
makes meter precision reach 0.2 and protection level 0.5 that 48 bit data is used when collect each
wave pattern. Non electricity acquisition is mainly direct at temperature and oil level of
transformer, input signal and standard signal DC 0 ~ 20mA or 0 ~ 5V.
On-off state quantity collection includes breaker state, knife gate (handcart) position and
other contact reflected operation state. Normal on-off state quantity collection is 12-bit, and can be
extended to 24-bit according to the practical necessity. On-off quantity input is strong electric
220VDC input.

4.3 Control Function


Device control functions include local control, remote control. In the control circuit to
increase equipment running state detection device object, to prevent misoperation or device state
does not correspond to an operation. Operate circuit to realize electric power complete isolation.
Each device is provided with 5 control output contacts, 2 of them as breaker operation has been
integrated in the operating circuit of. Another 3 as spare contact can be realized according to the
required as other programmable logic device object control.

4.4 Communication Function


It can flexibly select communication ways, like Ethernet, dual-CANBUS, dual-485
communication plug-in and Ethernet+485, and communicate with Microsoft monitor or protection
management machine immediately, where the term is DL/T667-1999 (IEC-60870-5-103). In this
way, the device can work as a small computer workstation to share data with other device.

4.5 Debug Function


It can reliability inspect breakers and circuits which is used when input or output by internal
software before operating or during tested.

11

GTG-84X Generator Protection Measurement and Control Device

4.6 Safety Function


It is required by operating and own security, and includes password protection and
self-testing.
Password protection includes setting password protection, output password protection and
communication password protection. Only if enter relevant password can users operate or modify
the device.
Self-testing includes hardware self-testing and software self-testing. Because of plug-in
design and independent CPU in every plug, except plug-in module, hardware self-testing upgrades
component testing, to make GTTR<<0.5h. Software self-testing mutual and watchdog circuit
inspection.

5. Protection Principle
5.1 Ratio Restraint Differential Protection of Generator
Ratio restraint differential protection is main protection of internal phase to phase short
circuit fault.
Differential motion equations as follows:
Iop Iop.0

( Ires Ires.0 )

Iop Iop.0 + K(Ires Ires.0)

( Ires > Ires.0 )

Type : Iop for differential current, Iop.0 for differential minimum operating current setting
value, Ires for braking current, Ires.0 for minimum braking current setting value, K for ratio
restraint characteristic of slope. Each side current direction is to point to the generator as the
direction, as shown in figure9-2.

differential current

op

braking current

res

I
2

Type: I T I N respectively terminal, neutral current transformer ( TA )secondary side current,


polarity of TA see 5-1. Principle diagram to see 5-2.

12

GTG-84X Generator Protection Measurement and Control Device

Picture 5-1 Current polarity wiring diagram


(According to the needs of the project, you can use the TA polar end are defined as close to
the generator side)

Picture 5-2 Generator differential protection logic diagram


Note: stop including jumping machine end of circuit breaker, magnetic extinguishing,
valving / hydrofoil, similarly hereinafter

5.2 Discrimination of TA disconnection


When any phase differential current is greater than 0.2 times the rated current, starting the
discrimination of TA disconnection procedure, satisfying the following conditions that TA
disconnection:
The side of three-phase current in at least one phase current is zero;
The side of three-phase current in at least one phase current constant;
Maximum phase current is less than1.2 times the rated current.

5.3 High sensitive zero-sequence current transverse differential


protection
High sensitive zero-sequence transverse differential protection is main protection of
generator internal, as turn-to-turn, interphase short circuit and stator winding open welding.
The protection of generator stator winding detection of multiple branches of different neutral
point connection current (i.e., zero sequence current) I0 fundamental wave component, protection
13

GTG-84X Generator Protection Measurement and Control Device


criterion for:
Iop Iop.0
Type: Iop for transverse differential current, Iop.0 for action current setting value.
Normal operation of generator, connected to transverse differential protection between the
two neutral points, the unbalanced current is mainly the fundamental wave, in the external short
circuit, the unbalanced current is mainly third harmonic components, in order to reduce the
protection setting value and improve the sensitivity, and protection has also increased the third
harmonic wave function. Transverse differential protection instantaneous action is on export.

Picture 5-3 Transverse differential protection logic diagram

5.4 Zero Sequence and Third Harmonic Voltage Stator Grounding Protection
As the generator stator single-phase earth fault protection, when any point of generator stator
winding occurs single phase grounding, the protection according to the requirements of the time
limit for active trip or signal.
Fundamental wave zero-sequence voltage protection generator from the generator terminal
date of 85 ~95% of the stator winding single phase grounding;
Third harmonic voltage protects stator winding single-phase near generator neutral point
grounding.
Fundamental wave zero-sequence voltage action criterion for:
3U0Uop
Third harmonic voltage action criterion for:

U 3s K ' U 3n
The 3U0 usually takes a neutral point voltage, if neutral point without TV, so take from the
generator terminal zero sequence voltage, required TV disconnection interlock; Uop for
fundamental wave zero-sequence voltage setting value; U3S and U3n respectively for the
generator terminal TV open delta winding and the third harmonic component of a neutral TV
'

output; K for braking coefficient. Logic block diagram is shown in figure 5-4.

14

GTG-84X Generator Protection Measurement and Control Device

Picture 5-4 Stator grounding protection logic diagram

5.5 Zero Sequence Current of Stator Grounding Protection


For generation unit of the bus system and the expanded unit connection, should adopt the
zero sequence over current protection as a generator 95% protection, at present generator port
must be equipped with a special zero sequence current transformer.
criterion for

I 0p > I 0set

Type: I0p for zero sequence action current; I0set for zero sequence setting value. Its logic diagram
see picture 2-5.

Picture 5-5 Zero sequence over current protection logic diagram

5.6 Rotor One-point Grounding Protection and Two-point Grounding


Protection
The protection is mainly reflected the rotor loop one-point grounding fault and grounding
automatic or manual input two grounding monitoring component after one-point grounding.
The ping-pong style switching translated principle, by solving two different grounding loop
equation, real-time calculation of rotor grounding resistance and grounding position. Schematic
diagram see picture 4.5. Among them: S1, S2 for electronic switch by control microcomputer, Rg
for grounding resistance, for grounding location, E for rotor voltage. With two voltage dropping
resistor R and one measuring resistor R1.
Calculation of grounding position and memory, to determine the rotor two-point grounding
prepare for. In order to prevent the misoperation of protection and calculation overflow, ad hoc
initiation criterion: E >30V.

15

GTG-84X Generator Protection Measurement and Control Device

Picture 5-6 Rotor one-point grounding protection switch sampling principle connection diagram
When the Rg is less than or equal to the grounding resistance setting value, after the delay
send rotor one-point grounding signal or act on the trip.
Generator excitation circuit of one-point grounding fault, and it did not cause harm to
generator, but if the sequential second point grounding fault, it will threaten the safety of the
generator.
After one-point grounding fault, protection device continued measure grounding resistance
and grounding position, thereafter if the rotor another point grounding fault, is measured value
change, when the changes value exceeds a setting value, protection device on the confirmation
for rotor ground points fault already happened, was immediately trip. Protection criterion for:
| | > set

set for rotor two-point grounding position change setting value

Picture 5-7 Rotor one-point grounding and two-point grounding protection schematic diagrams
The device can display real-time rotor grounding resistance and grounding position.

5.7 Loss of Excitation Protection


Generator excitation system failure causes the excitation reduces or all magnetic loss, leading
to the generator and the system out of step, on the unit itself and the security of the power system
of causing significant harm. The terminal has a separate circuit breaker, a smaller capacity, loss of
excitation protection using static stability impedance signal, asynchronous impedance exports
jump terminal circuit breaker protection scheme, aimed directly at the generator operating
conditions reduce the abnormal operation of the external system, with TV disconnection interlock.
16

GTG-84X Generator Protection Measurement and Control Device


Loss of excitation protection main criterion can be by the following criterion:
The static stability boundary impedance main criterion: impedance fan round action
criterion
.
.
for matching generator static stability boundary circle, using 0 connection mode ( U ab I ab ),
action characteristics shown in Figure 4.6.1, after generator loss of excitation, terminal locus of
measured impedance by the graph I quadrant over time into the quadrant, of the static stability
boundary near the entry circle.
The static stability boundary impedance criterion is satisfied, at least delay 1s ~1.5s send
magnetic loss signal, pressure signal output or tripping, delay 1s ~1.5s is due to the oscillation of
the system. Fan and R axis angle between 10~15 is to avoid the generator outlet via a transition
resistance of interphase short circuit, as well as from the leading phase operation of generator
normal.

Picture 5-8 static stability boundary impedance criterion action characteristic


In order to prevent the loss of excitation protection misoperation, recommended in the static
stability sector loss-of-excitation protection criterion setting calculation method of xd value is: xd
= xd (nameplate) / 1.3.
Stable asynchronous boundary impedance criterion
The generator occurs that any can lead to deactivation step after loss of excitation, always to
the static stability boundary, and then transferred to the asynchronous operation, and steady-state
asynchronous operation. The criterion for action round is cast round under; it matches the
generator steady-state asynchronous boundary circle. Characteristic curve see picture 5-9.

Picture 5-9 Asynchronous impedance characteristic curve


Consider the generator loss of excitation faults on the generator itself and the impact of
system, according to the unit in the action and the status of the system and

the system structure,


17

GTG-84X Generator Protection Measurement and Control Device


the device provides for loss of excitation protection scheme is shown in figure 5-10.

Picture 5-10 loss of excitation logic diagram


Stable asynchronous boundary circle motion region is much smaller than the static stability
boundary sector action zone.
Protection scheme is characterized in that: the magnetic loss or partial loss of excitation step,
static stability impedance circle action, by tsc1=1s~1.5s delay send loss of excitation signal, is not
trip, allow loss of magnetic generator longer run continues to the system output power; the tsc2
delay, hop sectionalizing switch, reduce the generator load. Asynchronous impedance circle action
after long time delay tsc3 =1s ~300s tripping. In the diagram, while the asynchronous impedance
circle by Tsc3 delay single trip, but won't happen for setting error in normal during progressive
phase operation error jump, because the asynchronous impedance action round small, starting
current Iset take 0.3A
Tsc1 exit send loss of excitation signal, the Tsc2 after action act on the trip.

5.8 Reverse Power Protection


Reverse power protection for turbine generator active power of generator back there, turned
into a motor abnormal operation conditions of protection, protection with TV disconnection
interlock.
Reverse power protection response generator from the systemic absorption of active power
size. Voltage takes from motor terminal TV, current takes from motor terminal (or neutral) TA.
Protection based on three-phase wiring, active power:

P = U c a I c a cos c a
for point of view of voltage leading current, criterion for:
Pset is reverse power protection action setting value.
Protection by the time delay (1s ~600s) can be used to send signals, can also be used to trip.
Its protection characteristic curve see picture 1-11, protection logic diagram see picture 5-12.

18

GTG-84X Generator Protection Measurement and Control Device

Picture 5-11 Protection action characteristic

Picture 5-12 Generator reverse power protection logic

diagram

5.9 Compound Voltage (Memory) Over Current Protection


Compound voltage (memory) over current protection as the backup protection of transformer
or adjacent elements, current memory function is mainly used for self-shunt excitation generator
back-up protection.
The composite voltage components and three-phase over current element composed. One,
current memory function by software control word to select input or exit, when the exit is a
composite voltage over start current protection; negative sequence voltage component also by
software control word to select input or exit, choose to quit, for low voltage memory over
current or low voltage over current protection.
Criterion description:
a. composite voltage component
Composite voltage components by the negative sequence voltage and low voltage criterion,
the negative sequence voltage reflect the system's asymmetric fault, low voltage reflect system
symmetrical fault and asymmetric interphase fault.
To meet any conditions of the two, composite voltage component act.

U 2 > U 2op

U2op for negative sequence voltage setting value

U < U op

Uop for low voltage setting value, U for the minimum of the three line

voltage
b. over current element
Over current element connected to the current transformer secondary three-phase circuit,
protection can have a plurality of setting values, each section of current and time limit are
individually setting.
When and phase current satisfied the following conditions, protection act.

I > I op

Iop for action current setting value

19

GTG-84X Generator Protection Measurement and Control Device

Picture 5-13 Protection logic diagram

5.10 Excitation Transformer over Current Quick Break Protection


Over current protection can be used as a generator fault or overload sensitive start and delay
element. Protection judgment in three-phase current maximum value is greater than a setting value
action.

5.11 Quick Break Protection


Quick break protection can be used as the elimination of differential protection dead zone or
as a generator of interphase short circuit of auxiliary protection. Protection judgment in
three-phase current maximum value is greater than a setting value action.

5.12 Negative Sequence Current Protection


Negative sequence current protection can be used as a generator fault protection or
open-phase running protection (definite).

5.13 Stator Overload Protection

Stator over load protection used for generator as stator windings over current and stator
winding overload protection, connected with the three-phase, take the maximum phase current
distinguish. The main protection for generator stator winding overload or external fault caused by
the stator winding over current, by a definite time limit overload and inverse time limit over
current is composed of two parts.
Definite time limit overload according to generator permit long-term load current can
reliably return condition setting. Inverse time limit over current according to the allow flow
capacity of stator winding allowable to set. Generator stator winding under the short-time over
current multiple and the allowable duration relationship:

t=

20

K
I (1 + )
2
*

GTG-84X Generator Protection Measurement and Control Device


Type: K -- stator winding overload constant
I* -- stator rated current as the base of the per-unit value
-- related with the stator winding temperature rise characteristic and temperature margin,
usually 0.01 ~0.02.
Protection characteristic curve and logic diagram
Look picture 5-14, logic diagram see picture 5-15

Picture 5-14 Characteristic curve;

Picture 5-15 Over load protection logic diagram

5.14 Over Voltage Protection


Over voltage protection as overvoltage start, interlock and delay element. Protection takes
three-phase line voltage, when a line voltage is greater than the setting value, protection namely
action.

5.15 Low Voltage Protection


Low voltage protection taker three-phase line voltage, when either of the two-phase line
voltage is less than the setting value, the protection time delay protection action.

21

GTG-84X Generator Protection Measurement and Control Device

Picture 5-16 Low voltage logic diagram

5.16 Abnormal Frequency Protection


When power system has active and insufficient, it will generate low frequency. Low
frequency operation makes the turbine blade subjected to fatigue damage; this irreversible fatigue
damage is accumulated to a certain extent makes the blade fracture, resulting in serious fault. In
the electric power system of sudden load rejection or the occurrence of many faults, will produce
over frequency. Sometimes the turbine governor fault will lead to frequency.
Low frequency protection through two fixed value of F1, F2 to make frequency range
divided into two frequency bands, and F1 > f2.
When section I f1>ff2, time is t1
When section II f<f2, time is t2
Over frequency protection only with section I,
After abnormal frequency by a delay action to send signal or trip.
The protection is provided with line voltage low blocking criterion. Logic block diagram is
shown in figure5-17.

Picture 5-17 Abnormal frequency logic diagram

22

GTG-84X Generator Protection Measurement and Control Device

5.17 Non Electricity Protection Description


Device of non-electricity protection provided separate plug-in; with non-electric jump and
warning signal two types. Non electricity jump make non-electric signal in the power supply loop
(220V / 110V) heavy dynamic, output tripping out of contact, the above function from CPU weak
effects loop.
This plug-in will above all non-electricity information were collected, transported to the
protection system, to generate SOE reports and other information, used for local display and
monitoring system of transmission, but also by the CPU trip out of control. Non electric tripping
and alarm light panel of non electric signal, while simultaneously providing a power transient
signal and the centre signal contacts.
Protection Logic Diagram as follow:

Picture 5-18 Non Electricity Protection logic diagram

5.18 TV Disconnection Test


When three-phase input voltage and high side current of device meets the following one of
the three conditions for TV disconnection.
The maximum line and the minimum line voltage difference is greater than 18V, and 3U0
(self-produced, similarly hereinafter) is greater than 8V;
Three line voltage is less than 18V, and any phase have current (> 0.04In);
3U0 is greater than 8V, and the maximum line voltage less than 18V;
Control word input, to meet any of the above conditions, 10s reported the bus TV
disconnection. And according to the related control word to lock or latch low voltage protection of
low voltage protection. Do not meet the above conditions, and the line voltage is greater than 80V,
2s bus TV break return.

5.19 Control Circuit Abnormity Alarm


The device at the same time acquisition circuit breaker jumped and bit state, normal will have
only one jump or bit, otherwise, the 3s delay control circuit (disconnected) reported abnormal
alarm signal, but not blocking protection.
If the device only jump signal, at the same time an arbitrary phase current is larger than the
no flow threshold, the 10s delay newspaper jumped a flow alarm signal. The above conditions do
not meet 5s after returning.

23

GTG-84X Generator Protection Measurement and Control Device

5.20 Device Fault Alarm


The hardware of protection device break down( including setting error, setting code error,
opened a self-test alarm, internal element anomaly, module communication abnormal ), LCD in
device can display the fault information, and blocking protection for open circuit, at the same time
send the central signal.

Signal,, Remote Control Function


5.21 Telemetry, Remote Signal
Telemetry: differential and backup device for the measurement of loop with separate AC
input (IA, IB, IC) connected with the instrument TA, and protection circuit of the AC input left.
Differential device measurement of Ia, Ib, Ic, I0 etc; backup device for the measurement of Ua, Ub,
Uc, Ia, Ib, Ic, P, Q, S, cos, f etc;
Remote Signal: A variety of protection action signal and circuit breaker position remote,
open into the remote signal etc.
Remote Control: The remote control of jump, closing, plate cast back, modifies the definite
value etc.

5.22 Wave Recorder


Apparatus for recording protection trip before the 4 cycle, after tripping 6 cycle (weekly
cycle 48 points) of the sampled data, protection trip after sending substation automation master
station, or by independent fault analysis software, failure analysis and device tripping behavior.

5.23 GPS Time Synchronization


Device communicate with the substation automation, get the information of year, month, day,
hour, minute and second, and configure a GPS when opened, connecting to the GPS receiver
second pulse output, achieve millisecond timing accuracy, time is not more than 1ms.

6Setting
6.1 Soft Plate
Through the main menu -- setting operation -- soft plate cast back one level password (can
be input two level password) into, through button, can operate send and return. Completed
modified return through ok keys are cured, if cancel changes, press the return key can.
GTG-841soft plate shown in the table below:
No.

Abbreviation

Full Name

YCDS

Differential motion quick-break protection plate

YBLC

Ratio differential motion protection plate

YHCD

Transverse differential protection plate

YGL1

Exciting dynamo over current section I plate

YGL2

Exciting dynamo over current section II plate

GTG-842 soft plate shown in the table below:

24

Description

GTG-84X Generator Protection Measurement and Control Device


No.

Abbreviation

Full Name

YSD

Quick-break protection soft plate

YGL1

Repressing over current section I soft


plate

YGL2

Repressing over current section II soft


plate

YDSX

Definite time limit overload soft plate

YFSX

Inverse time limit overload soft plate

YFXG

Negative sequence over current


protection plate

YJD

Fundamental harmonic grounding soft


plate

YSXB

Third harmonic grounding soft plate

YJW

Static stability impedance soft plate

10

YYB

Asynchronous impedance soft plate

11

YDP1

Low frequency section I soft plate

12

YDP2

Low frequency section II soft plate

13

YGP

Over frequency protection soft plate

14

YNGL

Reverse power protection soft plate

15

YGDY

Over voltage protection soft plate

16

YZZD

Rotor one-point low setting soft plate

17

YZZG

Rotor one-point high setting soft plate

18

YLD

Rotor two-point grounding soft plate

19

YLXG

Zero sequence over current protection


plate

20

DDY

Low voltage protection soft plate

Description

6.2 Setting and Control Word


6.2.1 Setting
Through the main menu -- setting operation - modifying fixed value -- level two password
entry, corresponding to the selected value code start browsing the setting value, by selecting the
key into the individual value modify menu.
GTG-841 setting shown in the table below:
No.

Abbreviation

Full Name

Setting range and


description

TV1

System primary voltage ratio

11200

TA1

System primary current ratio

11200

In

Secondary current rated value

1 A5 A

Isd

Differential motion quick break current setting

010A

Idz

Ratio differential motion minimum action

010A

25

GTG-84X Generator Protection Measurement and Control Device


current
6

Izd

Ratio differential motion minimum braking


current

010A

Zdxs

Ratio differential motion braking coefficient

0.30.8

Ihc

Transverse differential protection setting

010A

Thc

Transverse differential protection delay

010S

10

Igl1

Exciting dynamo over current section I setting

0100A

11

Tgl1

Exciting dynamo over current section I delay

0100S

12

Igl2

Exciting dynamo over current section II setting

0100A

13

Tgl2

Exciting dynamo over current section II delay

0100S

GTG-842 setting shown in the table below:

26

Setting range and


description

No.

Abbreviation

Full Name

TV1

System primary voltage ratio

11200

TA1

System primary current ratio

11200

In

Secondary current rated value

1 A5 A

Isd

Current quick break setting

0100A

Bsfx

Repressing interlock negative sequence


voltage

030 V

Bsdy

Repressing interlock low voltage

0100 V

Igl1

Over current section I setting

0100 A

Tgly1

Over current section I delay

0100 S

Igl1

Over current section II setting

0100 A

10

Tgly1

Over current section II delay

0100 s

11

Igfh

Stator overload definite time limit current

0100 A

12

Tgfh

Stator overload definite time limit delay

0100 S

13

Ifgfh

Stator overload inverse time limit current

0100 A

14

Idfsx

Stator inverse time limit starting current

0100 A

15

Tfsxs

Stator inverse time limit shortest delay

0100 S

16

Tfsxx

Stator inverse time limit longest delay

0100 S

17

Dzgfh

Stator overload constant

010A

18

Srcs

Stator cooling constant

01

19

Ifxgl

Negative sequence over current setting

0100 A

20

Tfxgl

Negative sequence over current delay

0100 S

21

Ulxjb

Zero sequence harmonic voltage

0100 V

22

Tlxjb

Zero sequence harmonic delayed time

0100 s

23

3cxb

Zero sequence third harmonic scale factor

0.30.8

24

Tlx3c

Zero sequence third harmonic delayed


time

0100 s

25

Rjdg

Rotor grounding resistance high setting

050

26

Tjdg

Rotor high setting delayed time

0999

27

Rjdd

Rotor grounding resistance low setting

020

GTG-84X Generator Protection Measurement and Control Device


28

Tjdd

Rotor low setting delayed time

0999 s

29

Jdwz

Position of grounding changed

0100

30

Tjdys

Rotor two-point grounding delayed time

0999 s

31

Z1ajw

Static stability action impedance Z1a

020

32

Z1bjw

Static stability action impedance Z1b

050

33

Tjwzk1

Static stability impedance delay t1

0100 s

34

Tjwzk2

Static stability impedance delay t2

09999 s

35

Z2ayb

Asynchronous action impedance Z2a

120

36

Z2byb

Asynchronous action impedance Z2b

550

37

Tybzk

Asynchronous impedance delayed time

0300 s

38

DpId

Low frequency section I

4749.8Hz

39

TdpId

Low frequency section I delay t1

0100 s

40

DpIId

Low frequency section II

4549Hz

41

TdpIId

Low frequency section I delay t2

0100 s

42

Gpbh

Over frequency protection setting

5060 Hz

43

Tgp

Over frequency delay

0100s

44

Udybs

Low voltage interlock

0100V

45

Ngldz

Reverse power action value

05000W

46

Tngl

Reverse power action delay

09999s

47

Ugdy

Over voltage setting

90160

48

Tgdy

Over voltage action time

0100 s

49

Rf+

Positive terminal sampling resistor

032768

50

RF-

Negative terminal sampling resistor

032768

51

Ilxdl

Zero sequence current setting

010 A

52

Tlxdl

Zero sequence current delay

0100 S

53

Vdy

Low voltage setting

090 V

54

Tdy

Low voltage delay

0100 S

55

Klc

Exciting voltage coefficient

0.25

27

GTG-84X Generator Protection Measurement and Control Device


6.2.2 Control Word
After entering according to the method of 6.2.1, after browsing the setting value means
directly into the control word operation, through the button , can be send and return.
GTG-841control word shown in the table below:
No.

Abbreviation

Full Name

CLYX

Differential flow limit alarm cast back

TADX

TA disconnection test cast back

TABS

TA disconnection interlock related protection

THCD

Transverse differential protection trip cast


back

Description

GTG-842 control word shown in the table below:

28

No.

Abbreviation

Full Name

TVDX

TV disconnection test cast back

TVBS

TV disconnection interlock related protection

FXT

Compound voltage over current negative


sequence voltage cast back

JYGNT

Compound voltage over current memory function


cast back

FSXTMC

Stator inverse time limit jump out magnetic

FSXGQM

Stator inverse time limit close valve

DZDYT

Stator fundamental harmonic voltage trip

DZXBT

Stator harmonic voltage trip

ZZDZJD

Rotor one-point low resistance grounding trip

10

ZZJDT

Rotor one-point grounding trip

11

SCMC

Loss of excitation protection jump out magnetic


switch

12

SCGQM

Loss of excitation protection close valve

13

DP2T

Low frequency section II protection trip

14

DP2T

Low frequency section II jump out magnetic

15

DP2T

Low frequency section II jump valve

16

GPTZ

Over frequency protection jump machine end


export

17

GPTMC

Over frequency protection jump magnetic


blow-out switch

18

GPTQM

Over frequency protection jump valve

19

NGLT

Reverse power protection trip

20

NPMC

Reverse power jump out magnetic

21

NPGQM

Reverse power close valve

22

GDYT

Over voltage protection trip

23

GDYGQM

Over voltage jump out magnetic

24

GDYGQM

Over voltage close valve

Description

GTG-84X Generator Protection Measurement and Control Device


25

DDYT

Low voltage protection trip

26

DDYGQM

Low voltage jump out magnetic

27

DDYGQM

Low voltage close valve

28

TLXTZ

Zero sequence over current protection trip

7. The Man-machine Interface Operation Description


7.1 Panel Indicator Definition
GTG-841 device panel consists of 8 signal indicating lamps, from left to right respectively run,
alarm, trip, standby, TA disconnection, non-electricity, jump, bit signal lamp.
Running" light is green, when the equipment normal operation, for the green light, if the
light out means the management of CPU is system halted, if scintillation means management CPU
is in alarm state;
Warning" light is red, when normal operation goes out, when the device fault light;
Tripping" light is red, when normal operation goes out, when the protection action of exit
light;
Standby" light is red, for the special requirements of occasions;
TA disconnection light is red, when the TA disconnect light;
Non electricity light is red, when the non electricity action light;
Jump" light is green, the circuit breaker is lighten in the position of trip, extinguish in the
position of close;
Bit" light is red, the circuit breaker is lighten in the position of trip, extinguish in the
position of close;
GTG-842 device panel consists of 8 signal indicating lamps, from left to right respectively run,
alarm, trip, magnetic loss, grounding, standby, standby, standby, standby signal lamp.
Running" light is green, when the equipment normal operation, for the green light, if the
light out means the management of CPU is system halted, if scintillation means management CPU
is in alarm state;
Warning" light is red, when normal operation goes out, when the device fault light;
Tripping" light is red, when normal operation goes out, when the protection action of
exit light;
Magnetic loss" light is red, magnetic loss operation light;
Grounding" light is red, rotor one point grounding, stator single-phase ground motion
light;
Standby" light is red, for the special requirements of occasions;
Standby" light is red, for the special requirements of occasions;
Standby" light is red, for the special requirements of occasions;
The "alarm"," trip" ,magnetic loss, grounding as the action signal relay holds the light,
can throw the panel reset button return or remote reset. Other lights are real-time status signal
indicative, cannot return.

29

GTG-84X Generator Protection Measurement and Control Device

7.2 The Keyboard and Normal Display


Device using a 192 x 64 dot matrix LCD, adopt menu operation interface, Chinese display,
friendly interface. Take the lead in the use of intelligent key device operating system, greatly
improving efficiency. In a liquid crystal side split 3 keys, a total of 6 keys, key itself without
special printing logo, its function is directed from the liquid crystal window prompts Chinese
characters strings or icon indicating.
When device power up shows Changsha Guotong Electrical and Technology Co., Ltd"
interface, it means liquid crystal module start, after 2s entering the circulation display interface.
Main interface divide into 3 screens, followed by main wiring interface, analog value interface 1,
analog value interface 2 The main wiring l interface display connection, circuit breaker, indicating
the current time information; analog value interface 1 display system primary voltage, current,
active power, reactive power etc; analog value interface 2 display system power factor, frequency
etc.
Circulation interface can be locked and unlocked through the bottom in the lower right corner,
to achieve a long-term display interface, locked or unlocked indicate by the corresponding icon.

Schematic diagram of LCD and keys

7.3 Menu List


In the circular main interface display state, by pressing any key (lock / unlock key except),
enter the man-machine operation menu, through the corresponding button to go to the next menu,
after 3 ~ 4 times the selection button entering the desired operation interface.

Main menu tree structure diagram as shown in figure:

30

GTG-84X Generator Protection Measurement and Control Device

The tree directory structure chart

+1 6

7.3.1 Button Introduce


+2 0

ok

From left to right: the cursor shift left, the cursor shift right, page down, page up, return to
the previous menu, next menu, the cursor in digital plus one, the cursor in digital reduce one, view
the details, down 16, investment, exit, turn down 20 item, confirm.

7.3.2 Main Menu


After device power on or reset entering the normal cycle of the screen. As you can see, this
device has a total of 4 screen circuit interface, cyclic display main wiring and per analog value
information. Attention should be paid to every interface on the lower-right has a lock or unlock
the prompt, according to the corresponding key can be maintained (lock) the interface or releases
the hold.

G T G -8 4 2

2 0 0 7.0 6 . 2 3 1 1.0 3 . 0 3
Interface1

U a b = 6.00 0 kV
Uc b = 6.00 0 kV
I a = 5.0 0 A
Ic = 5.0 0 A
Interface2

31

GTG-84X Generator Protection Measurement and Control Device

IA = 0.0 0 0A
IC = 0 .0 0 0A
f = 5 0 .0 0 H z
Interface3

S = 0.0 0 0 M V A
P = 0.0 0 0 MV
Q = 0.0 0 0 M V ar
Interface4

Press any key (lock / unlock key except) into operation the main menu, main menu as follows:

Every menu corresponding to the keys, please click the button

to view details.

7.3.3 Setting Operation


Setting interface menu as follows:

7.3.3.1 Setting Zone Switch


Operations switch regions of the device setting value. Through the key

, and

combinations to input the set of "level one password", the system defaults to" * * * *".
"Switch to:" put the switching of 0 ~ 9 fixed value code.

32

GTG-84X Generator Protection Measurement and Control Device


7.3.3.2 Setting Modify
Through the key
, and
combinations to input the set of "level two password",
the system defaults to" * * * *". "Switch to:" put the modifying of 0 ~ 9 fixed value code.

Click on the button

ok

to enter the zone 1 to set, through the keys

and key

combinations into the numerical values to modify the page, as shown right picture shows.

ok
Click the button
to enter and modify the confirmation page, as shown as below. After
ok
click the key
in modify the confirmation page, the system will modify the content of curing,
otherwise the system will maintain the original value.

7.3.3.3 Check setting


Check setting menu as follows:

33

GTG-84X Generator Protection Measurement and Control Device

(1) Check Setting Zone: Look the current set value using the code.

(2) Look up setting: Press key


content.

ok

can enter the area code area to view all the fixed value

(3) Look up the soft plate: see soft plate cast return status.

7.3.3.4 The Investment and Return of Soft Plate


Through the key
, and
combinations to input the set of "level one password",
the system defaults to" * * * *". Investment, exit buttons can change the soft plate state.

34

GTG-84X Generator Protection Measurement and Control Device


ok
Click the button
to enter and modify the confirmation page, as shown as below. After
ok
click the key
in modify the confirmation page, the system will modify the content of curing,
otherwise the system will maintain the original value.

7.3.3.5 Time Setting


Set the system time. Through the key
time.

, key

combinations to input the set

7.3.3.6 Setting Copy


The source code of all constant values for all copied to the destination code.

7.3.3.7 Password Setup


Each level and each password set.

35

GTG-84X Generator Protection Measurement and Control Device

7.3.4 Report Information


Device report record of operation, action, and event report three. The record of operation
mainly refers to the man-machine interface interact to produce records, such as the set value
modification, report removal etc. Action report mainly refers to the protection action generated log
information and analog information. Event report mainly refers to the operation of various alarm
information and remote information.
Report information interface as follows:

7.3.4.1 Action Report


Reports product by protect action. Picture 013" means it has produced 13 action report
records, maximum 100. If the total number of reported more than 100 but no clear report operation,
the display of the position 100. 002" represents the current look is a second action report. Click
the button

to see the analog or running data in time value.

7.3.4.2 Event Report


039" means there are 39 event record, maximum 100. 002" mean the article 2 event
+2 0

record. Press the button

36

you can quickly switch to view the event report.

GTG-84X Generator Protection Measurement and Control Device


7.3.4.3 Operation Record
The operate record of device. 100" means there are 100 operating reports, maximum 100.
005" mean the article 5 operation report.

7.3.4.4 Clear Report


Through the key

combinations to input the set of "level two


ok
password", the system defaults to" * * * *". Press key
to enter the page to clear information.

Press the key


ok
key
to clear.

, and

to enter the right picture shows clear confirmation page. Press the

7.3.5 Analog Value


Display access device analog value.

37

GTG-84X Generator Protection Measurement and Control Device

7.3.6 System Configuration


System configuration interface as follows:

7.3.6.1 Software Version


Software version information includes management CPU version information, and the
information of check code.

7.3.6.2 Network Address


(1) Look up network address: display the device communication device address, IP address,
subnet mask information.

(2) Modify the network address: after input level 2 password, can modify the device address
and the device IP address.

38

GTG-84X Generator Protection Measurement and Control Device

7.3.6.3 Module Information


Check the plug-in working state.

7.3.6.4 Time Setting


System on time is divided into artificial time and automatically.
(1) Artificial time: The picture shows the right.

(2) Automatically: network communications right, GPS seconds right, GPS minutes right.

39

GTG-84X Generator Protection Measurement and Control Device

7.3.6.5 Device Information


Look up the types of device.

7.3.6.6 Enterprise Information


Look up the information of enterprise.

7.3.6.7 Operation Information


Look up the information of system hardware.

7.3.6.8 Serial Communication


Look up the serial communication baud rate.

40

GTG-84X Generator Protection Measurement and Control Device

7.3.7 Debug Operation


Debug operation interface as follows:

7.3.7.1 Remote Function


The remote function is used with the background communication system debugging. Select
the INF point table number to send to point test.

7.3.7.2 Open Gear


+1 6

Open the breaker. It can be used to detect hardware. Press the key
plug directly into the open position.

to enter the next

41

GTG-84X Generator Protection Measurement and Control Device

7.3.7.3 Input Examination


Input information shift display. Move around cursor display the specific meaning of the
cursor. 1"means that open into effective.

7.3.7.4 Open Examination


Open information shift display. Move around the cursor display the specific meaning of the
cursor. 1" means that the location is in action.

7.4 Setting Management


The above menu list visible, protection setting values can be obtained by setting the operation
menu setting, which set the value of switching, soft plate cast back to enter the correct level one
password (operation password ) or level two password( following the security password ) can
operate, make the staff on duty at the scene in the jurisdiction can be carried out operation;
modifying setting value, setting replication needed to enter the correct level two password
(following the security password ) can operate, generally only allow relay protection professionals
in the field operation, inspection of the debugging operation, to stop other personnel may mistake
operation.
Some of the other and protection of the principle of independent configuration setting by
system configuration menu set, for the sake of convenience, the operation menu may also enter the
42

GTG-84X Generator Protection Measurement and Control Device


system configuration.

7.5 Debug Operation


Field debugging of products, through the debug menu can be conveniently completed
debugging functions. Open transmission can check the output relay can correct action or not, input,
open examination can show that the output or output relay status, remote functions for background
supervisory control system of complete information table point to point test function, signal reset
can revert out keep signal relay and device panel signal, in order to proceed with the next a
protection simulation test.
Open transmission test must be in the device has been completely quit running, is carried on
by the professional personnel debugging conditions, so we need to enter the correct level two
password (following the security password ) to operate.

8. Installation and Debugging On Site


8.1 Debugging Document and Test Instrument Preparation
(1) Device technology and instruction for use;
(2) Subject protection screen design drawings;
(3) Design Institute relevant subject screen and other external circuit connection design
chart;
(4) Subjects were protected by a protective screen of the equipment master wiring and
associated secondary equipment electrical position schematic, layout and related
parameters;
(5) Microcomputer based relay protection tester. The instrument is easy to use, friendly
interface.
(6) The conventional relay protection testing equipment (such as analog station), general
requirements it can simulate the system common to a variety of different types of faults,
including all kinds of transient faults and permanent faults, which can be output by the
normal operation of the three-phase current voltage to the fault current and voltage
analog quantity, can also accept protection output the switch, so as to realize the fault
and fault removal.
(7) 0.5 level current voltage meter, meter, so that the amount of the amplitude and the phase
of the check.
(8) Multimeter or lamp with brightness

8.2 Inspection before Energizing


(1) Check device type and each electric parameter is consistent with the order, in particular
should pay attention to the DC supply voltage and field match.
(2) Check the plug location is in accord with description position one by one.
43

GTG-84X Generator Protection Measurement and Control Device


(3) The power wiring is correct, the first direct current electrical application of multimeter
tools such as confirmation of useless DC short circuit phenomenon.
(4) If necessary, well connected and installed printer printing paper (the printer power
supply AC 220V) printer cable connected correctly and reliably.
(5) Using a multimeter to check the screen (or device) external terminals TV secondary
circuit is not short, TA secondary circuit does not open.
(6) Check all of device ground terminal grounding whether reliable.
(7) Quit all protection trips (full screen debugging).
(8) If it is connected to the background, should check the Ethernet connection or serial
connection whether correct link connect.
(9) The above examination such as found in trouble, please click the relevant drawings
repair, if can not repaired, stop debugging, contact with the manufacturers.

8.3 Energizing Test


(1) Energize
First electricity should observe, accident should be timely power inspection. Liquid crystal
display device in general, electricity can hear 24V power monitoring relays and power on the
action of the relay. If the LCD display improperly, can pull out the power plug in addition to all
plug-ins, electrifying testing, liquid crystal display then insert the plug observation, to identify
abnormal plug.
(2) The plug-in module check
After electrifying running lights, alarm, tripping signal lamp should pass key return. Through
the configuration of the system -- the module information menu examination management CPU,
protection CPU, display CPU intelligent plug-in 1, smart plug-ins 2 indicators such as "normal",
show that the plug into a normal working state, can proceed to the next stage of commissioning.
Also it can through system configuration -- software version check and record for each CPU
module software version, CRC checksum etc.
(3) Setting
According to the dispatching departments setting form to set, soft plate cast back setting and
system configuration settings, see the 5 device set and setting. Only conduct a comprehensive
setting correctly to ensure the reliable, convenient debugging and operation.
(4) The switch input check
Through the debugging operation -- open check menu can check device remote open state is
correct. The wiring should be taken to ensure that open into the negative power supply access
(control), the open end and positive power short observation. In the LCD interface accord to the
display," 0" means invalid; "1" means valid. There are a number of remote signals input reflect the
breaker operating circuit real time status, so it is necessary to access the circuit breaker control
circuit and analog circuit can correctly reflect, such as jumping, closing position.
(5) Relay open circuit check
Through the debugging operation -- open transmission menu can check the relay is correct

44

GTG-84X Generator Protection Measurement and Control Device


action. Note it return automatically after transmission relay for 5s, so transmission should be ready
for multimeter or traffic lights junction. Note: must be quit running in the conditions of device
(screen) has been completely.
(6) Analog value input check
On screen ( device ) AC current, voltage input by adding rating, circulating in the main
interface analog value interface 1, analog interface 2 (A lockable interface ) the amount. If you
need to check the detailed protection analog value, measurement analog values size, phase
relations, through the analog value menu selection of observation.
Display error are protective current does not exceed the applied value of + 2.5%, voltage
does not exceed the rated value of + 0.2%, measuring current does not exceed the rated value +
0.2%.
Because the product manufactured before the strict testing has been done, the general site
does not need to adjust the scale; if a path error is too large or unusual, should be through a variety
of methods to confirm it is the device causes or external test equipment or junction, confirmation
device causes or did not find by the adjustment of professionals or contact with the manufacturers.
(7) Sequence check
Through the analog value menu, it can check each channel phase sequence of analog value.
(8) The entire group test
If the check is correct, device has basically no problem. As a precaution, through the entire
group test to inflict different analog value, to check the protection action, to confirm the use of
protection setting value is all correct.

9. Commissioning Instrument and Announcements


9.1 Set and Inspect Before Commission
(1) Quit the protection of outlet pressure plate.
(2) Cast DC power supply, then running light in the device panel is bright, liquid crystal
display normal.
(3) Voltage transformer and current transformer has one and only one ground point, ground
point should be located in the main control room, and shall be securely welded on the
ground of small bus.
(4) Check AC circuit three-phase voltage, current phase sequence and phase correct.
(5) Check LCD clock.
(6) Protect setting according to the dispatch setting notification setting, all the protection
setting after, print a copy of each protection setting value list, after verifying the correct
file.
(7) Before operation and exiting device drive test all test items, to avoid the normal
operation due to misoperation causes device malfunction.
(8) Check protection soft plate is correctly cast back," what" means input," X means quit.
(9) Check protection hard plate is correctly cast back, available in the output query menu
check," 1"means input," 0 means quit.
45

GTG-84X Generator Protection Measurement and Control Device

9.2 Normal Operation and Abnormal Signaling Indication


1.

Normal operating signal

"Running" light should be mercerized, breaker closed ( red ) or jump (green ) one of light,
corresponding to the real location status, alarm, jump, TA disconnect, standby and other red light
should not be bright.
2.

Central signal

The device sends the central signal: trip, alarm, control circuit disconnect. Trip is the signal
of protect action. Alarm signal send out in the fixed value self-checking error, opened a self-test
error and device fault, others such as TV TA disconnection and TV TA inverted sequence,
control circuit abnormality also sends out alarm signal.
3.

Setting modify, the investment and return of soft plate

Modify value or investment retreat soft plate should be disconnect tripping outlet pressure
plate, modified, checked, and then re-enter the trip switch; during normal operation, should not be
arbitrarily modifying fixed value.
4.

Quit protection

Unit is faulty or need protection shutdown, should be disconnect tripping outlet pressure plate,
and then disconnect the DC power switch.

10Principle of Equipment and Wiring Diagram


1 GTG-841 Schematic diagram 1/2/3/4
2 GTG-841 wiring diagram
3 GTG-841 terminal diagram
4 GTG-842 Schematic diagram 1/2/3
5 GTG-842 wiring diagram
6 GTG-842 terminal diagram

46

801102

Transverse differential

Reserve
Differential

Zero-sequence

4LH

Excitation
transformer
protection

Differential
Reverse-power
Measurement

7LH

4LHc

4LHb

4LHa

6LHc

6LHb

6LHa

1LHc

1LHb

1LHa

N471

L471

N441

C441

B441

A441

N461

C461

B461

A461

N411

C411

B411

A411

D15

D15

D13

D11

D21

D19

D17

D15

D13

D16

D16

D14

D12

D22

D20

D18

D16

D14

GTG-841
D11
D12

Transverse differential
current N

Transverse differential
protection current

Neutral point
of current

C phase protective
current

B phase protective
current

A phase protective
current

C phase protective
current
Neutral point
of current

B phase protective
current

A phase protective
current

C phase protective
current
Neutral point
of current

B phase protective
current

A phase protective
current

current circuit

SDJ

+220V

Project
No.

Scale

GT201108008

Shield ground

RS485B-2

RS485A-2

RS485B-1

RS485A-1

AGND

Analog value 2

Analog value 1

Device lose electric

Device power lost

Shield ground

0V

RJ45

C05

C04

C03

C02

C01

A31

A32

A30

A45

A44

A43

A42

A41

GTG-841

Communication circuit

8008011

etaD

.oN

GTG-841 Schematic diagram 1

47

Pre'd

Stage

Project

Date

Shkd.

Sheet

Of

Appr.

Drawing No.

Auth'd

Changsha Guotong Electric Technology Co.,ltd

GTG-841 generator differential


enterprise standard atlas
Drawing protection device schematic diagram
GT800 series digital protection device

Name
Item
standard atlas
Working drawing
201108 1 3
GT201108008-GTG841.YL

-L

+L

Output signal node Analog input

5LH
6LH

1LH
2LH
3LH

Bus

GTG-84X Generator Protection Measurement and Control Device

+KM

801102

48
A08

A05

A06

ZT6

BTQWS

FLSD

et a D

8008011

.o N

GTG-841 Schematic diagram 2


A22

A23

A24

BY

BY

BY

A21

A20

A19

FDL3 FDL4

FDL1 FDL2

Spare switch input

(YXa16)

Spare switch input

(YXa13)

Spare switch input

(YXa12)

Spare switch input

(YXa10)

Spare switch input

(YXa8)

Spare switch input

(YXa6)

Spare switch input

(YXa4)

Spare switch input

(YXa2)

Spare switch input

(YXa11)

Spare switch input

(YXa9)

Spare switch input

(YXa15)

(YXa14)

(YXa7)

(YXa5)

(YXa3)

(YXa1)

ontrol supply

ontrol supply-

Spare switch input

FDLP

DL

BHLP

Operator box
DL
TQ

HC

B14

B15

B16

B13

B08

B09

A10

A09

B07

B05

B10

Date

Sheet

Of

Switch input circuit of no-electricity plate


Pre'd

Shkd.

Appr.

Drawing No.

Project
No.

B04

YLD

B24

YX7

B23

YX6

KK

B22

YX5

B21

LCYB

B17

B03

HCYB

WCN

B02

CDYB

(YX3)

Scale

GT201108008

rip export

Off export 1

Off export 2

Switch input ofCB

Protective plate

Non-electricity plate

on-electricity trip

anual trip entrance

emote control
power entrance

anual off entrance

Spring not energy


storage signal
(YX16)

(YX15)

Spare switch input


(YX7)

oblin blade
position(YX6)

The lower knife/used


test positon (YX5)

xcitation transformer
protective plate (YX4)

Transverse differential
protection plate

Differential
hard plate (YX2)

(YX1)

Control supply+

B01

B06
YX1

Control supply-

B12

GTT-842

Auth'd

Changsha Guotong Electric Technology Co.,ltd

GTG-841 generator differential


Project
enterprise standard atlas
Drawing protection device schematic diagram
GT800 series digital protection device
Name
Item
standard atlas
Workinig drawing
201108 2 4
GT201108008-GTG841.YL
Stage

DC220V
+KM

Control circuit

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

Feedback
optocoupler

GTG-841

-KM

Switching input circuit of the control board

A18

A17

A07

A04

A03

A02

A01

B06

B12

ZT5

DC220V
-KM

GTG-84X Generator Protection Measurement and Control Device

801102

GXJ
CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

GTG-841

QDJ1

24VGND

Trouble signal

Spare signal

emote tripping

Protective trip

Protective trip

Protective trip

Protective trip
Protective trip

osition feedback
public end

B38

Project
No.

Spare signal
B36
B37

rotective tripping
signal

rip to the connect


position
ff to the connect
position

B35

B34

B20

B19

B18

A16

A15

A12

A11

Protective trip

B31
B32

Protective trip

B30

GT201108008

Scale

Device inside DC24V loop

etaD

8008011

.oN

GTG-841 Schematic diagram 3

49

Pre'd

Project

Shkd.

Appr.

Auth'd

Changsha Guotong Electric Technology Co.,ltd

GTG-841 generator differential protection


enterprise standard atlas
Drawing device schematic diagram
GT800 series digital protection device
Name
Item
standard atlas

201108 3 4
GT201108008-GTG841.YL
Working drawing
Stage
Date
Sheet
Of
Drawing No.

TWJ2

Protective trip
Protective trip

B28
B29

Protective trip

B27

Protective trip
Protective trip

B33

B11

Output signal node

HWJ

GXJ

BYJ

TXJ

HWJ

TWJ2

FDL4

FDL2

FDL3

FDL1

TZ3

TZ2

TZ2

TZ1

GTG-841

Output control node

TXJ

BYJ

YTJ

YHJ

TZ4

TZ3

TZ2

TZ1

QDJ2

QDJ1

24V+

GTG-84X Generator Protection Measurement and Control Device

50
Brake

KK

BHLP

YLJ

TWJ1
TWJ2

8008011

.oN

GTG-841 Schematic diagram 4

1-2
3-4
5-6
7-8

90 450
X
X

45 90

B4

B17

WCN

A9

A10

B9

YLD

FDLP

B8

B7

B5

B10

FDL1

BTJ

HWJ

TBJ

YTJ

YHJ

TBJV

TBJV

Stage

B14

B15

B16

137

107

HC

DL

TQ

operation
mechanism

DL

Date

Sheet

Of

Project
No.

Scale

GT201108008

(YX16)

Not energy
storage lockout

(YX15)

Non-electricity
plate
Non-electricity
trip

Trip export

Trip entrance

Remote control
switch
Remote control
supply
Remote control
break-brake

Prevent tripping
lockout

CNJ

102

Pre'd

Shkd.

Appr.

Drawing No.

Auth'd

Changsha Guotong Electric Technology Co.,ltd

GTG-841 generator differential


Project
enterprise standard atlas
Drawing protection device schematic diagram
GT800 series digital protection device

Name
Item
standard atlas
Working drawing
201108 4 4
GT201108008-GTG841.YL

CNJ

YLJ

TBJ

HBJ

TBJ

TBJV

B12

-KM

ontrol circuit

Contact

on

KK
LW12-16Z/4.5525.2

Note witch

HBJ

etaD

B13 YLJ

DC220V
B06

801102

101

GTG-841

+KM

GTG-84X Generator Protection Measurement and Control Device

1YMa
1YMb
1YMc

DL

801102

Protective CT
Protective CT

RJ45

Neutral point
protective current

Shield ground

RS485A-2
RS485B-2

RS485A-1
RS485B-1

I0

I0

AC current circuit

C
01
C
02
C
03
C
04
C
05

E
17
E
18

switch
switch
switch
switch
switch
switch

input(YXa8)
input(YXa9)
input(YXa10)
input(YXa11)
input(YXa12)
input(YXa13)

A41
A42
A43

Device
power

GTG-841 generator differential protection device

Communication circuit

Protective CT

8008011

etaD

.oN

GTG-841 Wiring diagram

51

Stage

Pre'd

Date
Shkd.

HC
TQ

DL
DL

Of

Appr.

Drawing No.

Drawing
Name

-KM
DC220V
+KM

Auth'd

GT201108008-GTG841.JX

GTG-841 generator differential protection


device wiring diagram

+L DC220V
-L

Scale

GT201108008

Operator box

KK

Project
No.

201108 4 4
Sheet

Changsha Guotong Electric Technology Co.,ltd enterprise standard atlas

GT800 series digital protection device standard atlas

Working drawing

Item

Project

A44

A16
FDXJ A15

BHLP

FDLP

5V DC value 1+
5V DC value 2+
5V DC value-

FGA
YX2
YX3
YX4
YX5
YX6
YX7
YLD
WCN
YXa1
YXa2
YXa3
YXa4
YXa5
YXa6
YXa7
YXa8
YXa9
YXa10
YXa11
YXa12
YXa13
YXa14
YXa15
YXa16

Non-electricity trip signal

TXJ B35

Output control node

Protective trip signal

SDJ A45

B34
GXJ B37

A15
FDL A16

B11
BH B33
A11
FDL A12

B29
BH B30
B31
BH B32

BH B28

B27

B08
B16
B15
B14

B09

Device lose electric

Device alarm signal

Non-electricity trip export 3

Non-electricity trip export 2

Protective trip export 5

Protective trip export 4

Protective trip export 3

Protective trip export 2

Off export 2
Off export 1
Trip export

Protective trip export 1

Protective plate

Non-electricity plate

Non-electricity trip export 1

Manually trip entrance

Spare switch input


AGND
Analog quantity 1
Analog quantity 2

Spare
Spare
Spare
Spare
Spare
Spare

Spare switch input(YXa2)


Spare switch input(YXa4)
Spare switch input(YXa6)

Spare switch input(YX5)


Spare switch input(YX6)
Spare switch input(YX7)
(YX15)

B12
B06
B01
(YX2) B02
(YX3) B03
(YX4) B21
B22
B23
B24
B04
B17
A01
A02
A03
A17
A18
A19
A04
A20
A05
A21
A06
A22
A23
A07
A08
A24
A30
A32
A31
B13
B10
B05
B07
A09
A10

+220V
0V
Shield ground

Output control node

N441

L441

IC2

IC2

IA2

Operation loop

C421

IA2

IA2

IA2

IC3

IC3

IA3

IA3

IA3

IA3

IC1

IC1

Protective current of
machine end side

B421

D
17
D
18
D
19
D
20
D
21
D
22

E
11
E
12
E
13
E
14
E
15
E
16

IA1
IA1

Analog
input

A421

C423

B423

A423

IA1
IA1

Switch input circuit of


non-electricity board

N421

N431

N411

C411

D
11
D
12
D
13
D
14
D
15
D
16

Shield ground

Switch input circuit


of the control board

B411

A411

D
01

power Control power +


Spare switch input(YX1)

Power Control
supply

GTG-84X Generator Protection Measurement and Control Device

801102

52

etaD

8008011

.oN

GTG-841 Terminal diagram

DC2(+)

DC(-)

DC1(+)

(YXa16)

(YXa13)

(YXa12)

(YXa10)

(YXa8)

(YXa6)

(YXa4)

(YXa2)

Supply pluginDI2)

A
41
A
42
A Shield ground
43
A
44
A
45
A Non-power direct A
01 tripping 1(YXa1) 17
A Non-power direct A
02 tripping 2 (YXa3) 18
A Non-power direct A
03 tripping 3 (YXa5) 19
A Non-power direct A
04 tripping 4 (YXa7) 20
A Spare switch
A
05 input 9 (YXa9)
21
A Spare switch
A
06 input 11 (YXa11) 22
A Non-power direct
A
07 tripping 5 (YXa14) 23
A Non-power direct
A
08 tripping 6 (YXa15) 24
A
A
09
25
A
A
10
26
Non-electricity
A
A
trip export 2
11
27
A Non-electricity
A
trip export 2
12
28
pare
A
A
13 switch output
29
pare
A
A
14 switch output
30
A Non-electricity
A
trip export 3
15
31
A Non-electricity
A
trip export 3
16
32
B
01
B
02
B
03
B
04
B
05
B
06
B
07
B
08
B
09
B
10
B
11
B
12
B
13
B
14
B
15
B
16
B
17
B
18
B
19
B
20
Smart pluginDI1

B
21
B
22
YX2
Transverse differential
B
protective plateYX3 23
B
YX15
24
The entrance of remote
B
control power
25
B
Control power+KM
26
B
Manual trip entrance 27
B
28
B
29
B
anual off entrance 30
B
rip export 5
31
B
32
B
33
B
Trip export
34
B
Off export 1
35
Off export 2
B
36
Spring not energy
B
storage signal (YX16) 37
B
38
B
39
B
40

Spare switch input


YX1

Alarm signal

Alarm signal

C
01
C
02
C
03
C
04
C
05

Ic2

Ic2

Ib2

Ib2

Ia2

Ia2

Ic1

Ic1

Ib1

Ib1

Ia1

Ia1

AC pluginAC

D
11
D
12
D
13
D
14
D
15
D
16
D
17
D
18
D
19
D
20
D
21
D
22

Pre'd

Stage

Item

Working drawing

Date
Shkd.

Of

Appr.

I0

I0

Ic3

Ic3

Ib3

Ib3

Ia3

Ia3

Scale

GT201108008

Empty plugin

D
11
D
12
D
13
D
14
D
15
D
16
D
17
D
18
D
19
D
20
D
21
D
22

Auth'd

GT201108008-GTG841.DZ

GTG-841 generator differential


protection device terminal diagram

Drawing No.

Drawing
Name

201108 1 1
Sheet

Changsha Guotong Electric Technology Co.,ltd


Project
enterprise standard atlas

Project
No.

Ethernet

Shield ground

485B-2

485A-2

485B-1

485A-1

CPUPlug-inCPU)

Protective trip signal

Signal common

Trip export 5

Trip export 4

Trip export 4

Trip export 3

Trip export 3

Trip export 2

Trip export 2

Spare switch input


(YX5)
Spare switch input
(YX6)
Spare switch input
(YX7)

Excitation transformer
over-current plate(YX4)

GTG-84X Generator Protection Measurement and Control Device

801102

Excitation transformer
protection

3LHc

3LHb

3LHa

Transverse differential motion 8LH

Reserve
Differential motion

Zero-sequence

4LH

Differential TA
Reverse-power
Measurement

5LHc

5LHb

5LHa

N
D01

D21

E15

E13

E11

D15

D13

D11

D19

N640 E07

L640 E06

Zero-sequence
voltage of
the neutral point

Zero-sequence
voltage
of the machine end

Neutral point of
the phase voltage

C phase voltage

B phase voltage

SDJ

Project
No.

etaD

8008011

.oN

GTG-842 Schematic diagram 1

53

AC voltage circuit
Pre'd

Stage

Date
Shkd.

Working drawing

Sheet

Appr.

Of

Drawing No.

201108 1 3

Scale

Auth'd

GT201108008-GTG842.YL

GTG-842 generator
backup protection
device schematic diagram

GT201108008

Ethernet interface

Shield ground

RS485B-2

RS485A-2

RS485B-1

RS485A-1

Shield ground

0V

+220V

RJ45

C05

C04

C03

C02

C01

A45

A44

A43

A42

A41

GTG-842

hangsha Guotong Electric Technology Co.,ltd

Project
enterprise standard atlas
Drawing

Name
Item

-L

+L

Communication circuit

N630 D07

L630 D06

N600 D05

C630 D04

A phase voltage

Shield ground

WV

Zero-sequence
current
Zero-sequence
current loop

A phase
measuring current
B phase
measuring current
C phase
measuring current
Measuring
current loop

A phase
protective current
B phase
protective current
C phase
protective current
Neutral point
of current

A phase
protective current
phase
protective current
Neutral point
of current

AC current circuit

B630 D03

D22

E16

E14

E12

D16

D14

D12

D20

GTG-842
D17
D18

A630 D02

N481

L481

N431

C431

B431

A431

N451

C451

B451

A451

N411

C421

A421

Device supply utput signal node

5LH
6LH

1LH
2LH
3LH

Bus

2LHc

2LHa

GTG-84X Generator Protection Measurement and Control Device

+KM

801102

54

B04

B05

SDYB

BY

etaD

8008011

.oN

GTG-842 Schematic diagram 2

B24

B25

B26

FGYB

GLYB

NGYB

B23

B22

B21

B07

B06

B03

ZZYB

B01

A07

A06

A05

B06

B12

B02

-KM

DZYB

DC220V

GTG-842

Switch input circuit of non-power board


Pre'd

Stage

Project

Date

Shkd.

Sheet

Of

Appr.

Drawing No.

Changsha Guotong Electric Technology Co.,ltd

enterprise standard atlas


Drawing
GT800 series digital protection
Name
Item
device standard atlas
Working drawing
201108 2 3

Project
No.

Auth'd

GT201108008-GTG842.YL

GTG-842 backup generator


protection device
schematic diagram

Scale

GT201108008

Direct tripping relay 3 switch output 2

Direct tripping relay 3 switch output 2


A29

Direct tripping relay 3 switch output 1

Direct tripping relay 3 switch output 1

Direct tripping relay 3-(-)

A28

A27

A26

A20

Direct tripping relay 3-(+)

Direct tripping relay 2 switch output 2

A25
A19

Direct tripping relay 2 switch output 2

Direct tripping relay 2 switch output 1

Direct tripping relay 2 switch output 1

Direct tripping relay 2-(-)

Direct tripping relay 2-(+)

Direct tripping relay 1 switch output 2

Direct tripping relay 1 switch output 2

Direct tripping relay 1 switch output 1

Direct tripping relay 1 switch output 1

Direct tripping relay 1-(-)

Direct tripping relay 1-(+)

A24

A23

A22

A18

A17

A13

A12

A11

A10

A09

A08

Direct tripping relay circuit

Reverse-power plate
(YX13)

vercurrent protective
plate (YX12)

(YX11)

Composite voltage
overcurrent plate

Abnormal frequency plate


(YX10)

Excitation-loss protective
plate (YX9)

Signal reset
(YX8)

(YX7)

Co-bit signal

Trip signal
(YX6)

(YX5)

Spare switch input

(YX4)

Quick-break plate

(YX3)

Rator ground plate

Stator ground plate


(YX2)

Spare switch input


(YX1)

(YXa3)

Spare switch input

Spare switch input


(YXa2)

Spare switch input


(YXa1)

Control power +

Control power -

GTT-842

GTG-84X Generator Protection Measurement and Control Device

801102

GXJ
CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

CPU

GTG-842

QDJ1

24VGND

rouble signal

Protection tripping signal

pare trip export

pare trip export

pare trip export

pare trip export

pare trip export

Tripping section switch

Tripping FMK

Tripping generator teminal breaker

Start relay 1

Internal power

Device inside DC24V circuit


Protection trip

B19

B18

B17

B40

B39

Pre'd

Stage

Date

Shkd.

Sheet

Of
Appr.

Drawing No.

Drawing
Name

Project
No.

Device alarm signal

Scale

Auth'd

GT201108008-GTG842.YL

GTG-842 backup generator


protection device
schematic diagram

GT201108008

Protection tripping signal

eedback signal common

Protection trip

Protection trip

Protection trip
Protection trip

B38

Protection trip

Output signal node

hangsha Guotong Electric Technology Co.,ltd


Project
enterprise standard atlas
GT800 series digital protection device
Item
standard atlas
Working drawing

201108 3

Protection trip
Protection trip

B37

B32

B31

B30

B29

Protection trip

Protection trip

B34

Tripping section switch

B33

Tripping section switch

B15
B16

Tripping FMK
Tripping FMK

B14

B12
B13

Tripping generator terminal export


Tripping generator terminal export

B11

GXJ

TXJ

TZ8

TZ7

TZ6

TZ5

TZ4

TZ3

TZ2

TZ1

GTG-842

Output control node

BHJ

TZ8

TZ7

TZ6

TZ5

TZ4

TZ3

TZ2

TZ1

QDJ1

24V+

GTG-84X Generator Protection Measurement and Control Device

etaD

8008011

.oN

GTG-842 Schematic diagram 3

55

1YMa
1YMb
1YMc

DL

801102

56

rotective CT

easuring CT

N411

rotective CT

etaD

8008011

.oN

GTG-842 Wiring diagram


L640
N640

N441

L441

Un2

End protection
current

Zero-sequence CT

Shield ground

AC current circuit

RS485A-2
RS485B-2

RS485A-1
RS485B-1

Output control node

RJ45

C
01
C
02
C
03
C
04
C
05

I0
U02

I0

Ib1
Ic1
Ic1

Ib1

Ia1

Ia1

Direct tripping input/output signal

C411

B411

D
12
D
11
D
14
D
13
D
16
D
15
D
21
D
22
E
06
E
07

Reverse-power
Measuring current
current

A411

GND

Ufd-

Ufd+

C431

B431

A431

C421

D
Ua
02
D
Ub
03
D
Uc
04
D
Un
05
D
U01
06
D
Un1
07
D
IA
17
D
IA
18
D
IC
19
D
IC
20
E
Ia3
11
E
Ia3
12
E
Ib3
13
E
Ib3
14
E
Ic3
15
E
Ic3
16
A
01
A
03
A
04 round
hree-phase
voltage

L630
N630
A421

C630
N630

B630

A630

Shield ground

Switch input circuit of control board

N431

N421

PT

D
01

A09

A08

A22

A18

A17

TZ3 B16

Tripping section switch

B37
TZ7 B38

Spare trip

Device
supply

GTG-842 backup generator protective and I/O device

Communication
circuit

B19

GZ

Project
No.

A41
A42
A43

A44
SDJ A45

B18

BH

B17

B40

B39

B31

B30

B29

-KM
DC220V
+KM

+L DC220V
-L

Scale

GT201108008

YX1
YX2
YX3
YX4
YX5
YX6
YX7
YX8
YX9
YX10
YX11
YX12
YX13
YXa1
YXa2
YXa3

Pre'd

Stage

Date

Shkd.

Sheet

Of

Appr.

Drawing No.

Auth'd

Changsha Guotong Electric Technology Co.,ltd

GTG-842 backup generator


Project
enterprise standard atlas
Drawing protective and I/O device
GT800 series digital protection

Name
wiring diagram
Item
device standard atlas
Working drawing
201108 4 4
GT201108008-GTG842.JX

+220V
0V

Device lose electric

Signal common
Protection signal
Alarm signal

TZ8

TZ6 B32

Spare trip

Spare trip

TZ5

Spare trip

B34

TZ4

Spare trip

B33

B15

B14

TZ2

B13

B11
TZ1 B12

ZJ3 A29

A28

ZJ3 A27

A26

A19
ZJ3 A20

ZJ2 A25

A24

ZJ2 A23

ZJ2

A12
ZJ1 A13

A10
ZJ1 A11

ZJ1

B08
B01
B02
B03
B04
B05
B06
B07
B21
B22
B23
B24
B25
B26
A05
A06
A07

Tripping FMK

ripping generator terminal

Direct tripping relay +


Direct tripping relay

1
1

(YX2)
(YX3)
(YX4)
(YX5)
(YX6)
(YX7)
(YX8)
(YX9)
(YX10)
(YX11)
(YX12)
(YX13)
(YXa1)
(YXa2)
(YXa3)

Spare switch input


Spare switch input
Spare switch input
Direct tripping relay 1+
Direct tripping relay 1Direct tripping 1 switch output
Direct tripping 1 switch output
Direct tripping 1 switch output
Direct tripping 1 switch output
Direct tripping relay +
Direct tripping relay

Control supplySpare switch input (YX1)

GTG-84X Generator Protection Measurement and Control Device

801102

A
05
A
06
A
07
A
08
A
09
A
10
A
11
A
12
A
13
A
14
A
15
A
16

A
17
A
18
A
19
A
20
A
21
A
22
A
23
A
24
A
25
A
26
A
27
A
28
A
29
A
30
A
31
A
32

Direct tripping 3
export 2
Direct tripping 3
export 2

Direct tripping 3
export 1

Direct tripping 2
export 2
Direct tripping 3
export 1

Direct tripping 2
export 1
Direct tripping 2
export 2

Direct tripping 2
export 1

irect tripping
relay3-

irect tripping
relay2
irect tripping
relay2irect tripping
relay3

Power pluginDI2)

Direct tripping 1
export 2

Direct tripping 1
export 2

Direct tripping 1
export 1

Direct tripping 1
export 1

irect tripping
relay
irect tripping
relay 1-

(YXa3)

(YXa2)

(YXa1)

A
41
A
42
A
43
A
44 evice lose electric
A
45 evice lose electric
A
01 DC measurement+
A
02
A
03 DC measurement
A
04 round
B
21
B
22
YX2
B
23
YX3
B
YX4
24
Spare switch input
B
YX5
25
Switch input of the
B
tripping position YX6 26
B
YX7
27
B
28
B
29
B
30
B
31
B
32
B
33
B
34
B
35
B
36
B
Signal common
37
B
rip signal
38
B
Alarm signal
39
B
40

Spare switch input


YX1

Smart pluginDI1

B
01
B
02
B
03
B
04
B
05
B
06
B
07
B
08
B
09
B
10
B
11
B
12
B
13
B
14
B
15
B
16
B
17
B
18
B
19
B
20
(YX4)

Pre'd

Stage

Un1

U01

Un

Uc

Ub

Ua

I0

I0

Ic2

Ic2

Ia2

Ia2

Ic1

Ic1

Ib1

Ib1

Ia1

AC plugin 2AC2

Shield ground

Ia1

Date
Shkd.

201108

Sheet

Of
Appr.

1 1

hangsha Guotong Electric Technology Co.,ltd


enterprise standard atlas
Working drawing

Item

Project

D
01
D
02
D
03
D
04
D
05
D
06
D
07

D
11
D
12
D
13
D
14
D
15
D
16
D
17
D
18
D
19
D
20
D
21
D
22

Shield ground

485B-2

485A-2

485B-1

485A-1

thernet

C
01
C
02
C
03
C
04
C
05

CPU pluginCPU)

rip export

rip export

rip export

rip export

rip export

rip export

rip export

rip export

rip export

rip export

(YX7)

(YX7)

vercurrent plate

omposite voltage
overcurrent
protective plate (YX7)

bnormal frequency
protective plate (YX6)

Excitation-loss
protection plate (YX5)

ground

Drawing No.

Drawing
Name

Project
No.

Scale

Ic3

Ic3

Ib3

Ib3

Ia3

Ia3

Auth'd

GT201108008-GTE842.DZ

GTG-842 backup generator


protection measurement
device terminal diagram

GT201108008

AC plugin 1AC1

E
01 Shield
E
02
E
03
E
04
E
05
E
06 U02
E
07 Un2

E
11
E
12
E
13
E
14
E
15
E
16
E
17
E
18
E
19
E
20
E
21
E
22

GTG-84X Generator Protection Measurement and Control Device

etaD

8008011

.oN

GTG-842 Terminal diagram

57