(Rack-Indipendent)
Technical Specifications
DPA UPScale highlights at a glance
DPA UPScale with Safe-Swap
Modules (SSM)
For premium power protection availability
Low total Cost of Ownership (TCO)
Cost saving during entire life-cycle
Flexibility/Scalability
Ease of power upgrade, pay as you grow
Enhanced Serviceability
Rapid fault recovery
Safe-Swap modular
power protection
Power range: 10-80kW per rack
Specifications are subject to change without notice
Edition 29.09.2011
Section-10
TABLE OF CONTENTS
10.1
DPA UPScale RI SYSTEM DESCRIPTION ...............................................................................................3
10.2
TECHNICAL CHARACTERISTICS DPA UPScale RI ...............................................................................4
10.2.1 MECHANICAL CHARACTERISTICS DPA UPScale RI (Rack Independent) Subracks ........................4
10.3
INPUT CHARACTERISTICS ......................................................................................................................6
10.3.1 GRAPH: INPUT PF VERSUS % LOAD..................................................................................................6
10.3.2 GRAPH: INPUT DISTORTION THDI VERSUS % LOAD.......................................................................7
10.4
BATTERY CHARACTERISTICS................................................................................................................7
10.5
OUTPUT CHARACTERISTICS ..................................................................................................................8
10.5.1 GRAPH: AC AC EFFICIENCY with Linier load @ cosphi 1 ................................................................8
10.5.2 GRAPH: Output Power in KW and KVA VERSUS cosphi.....................................................................9
10.6
ENVIRONMENTAL CHARACTERISTICS ...............................................................................................10
10.7
STANDARDS............................................................................................................................................10
10.8
COMMUNICATION ...................................................................................................................................11
10.8.1 POWER MANAGEMENT DISPLAY (PMD)..........................................................................................11
10.8.2 MIMIC DIAGRAM..................................................................................................................................11
10.8.3 DISPLAY ...............................................................................................................................................11
10.8.4 CUSTOMER INTERFACES Terminals X1X2 ..................................................................................12
10.8.5 CUSTOMER INPUTS DRY PORTs: Terminal block X2.......................................................................12
10.8.6 CUSTOMER OUTPUTS DRY PORTs : Terminal blocks X1...............................................................12
10.9
OPTIONS ..................................................................................................................................................13
10.9.1 SNMP card / WaveMon Management Software ..................................................................................13
10.10 BATTERY AUTONOMIES........................................................................................................................13
10.10.1
Examples of Internal Battery Autonomy of DPA UPScale RI 11, RI 12, RI 22 , RI 24.....................13
10.11 INSTALLATION PLANNING ....................................................................................................................14
10.11.1
HEAT DISSIPATION PER MODULE WITH NON-LINEAR LOAD...................................................14
10.12 WIRING AND BLOCK DIAGRAMS FOR ALL FRAMES AND MODULES.............................................15
10.12.1
TERMINAL CONNECTIONS OVERVIEW .......................................................................................15
10.12.2
SINGLE FEED INPUT ......................................................................................................................16
10.12.3
SINGLE FEED INPUT / Cable Sections...........................................................................................16
10.12.4
DUAL FEED INPUT..........................................................................................................................17
10.12.5
Dual FEED INPUT / Cable Sections.................................................................................................17
www.newaveups.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 2/17
Section-10
Highest Availability
Modular, Decentralized Parallel Architecture (DPA)
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 3/17
Section-10
UPScale RI 10
UPScale RI 11
UPScale RI 12
Configuration
accommodates:
Max.
kW
20
20
20
Dimensions (WxHxD)
mm
448x310x565 (7 HU)
kg
20
40
56
kg
39 up to 42
(with 1 Module)
59 up to 62
(with 1 Module)
75 up to 78
(with 1 Module)
UPScale RI 20
UPScale RI 22
UPScale RI 24
kW
40
40
40
mm
kg
25
66
93
kg
44 up to 47
(with 2 Modules)
104 up to 110
(with 2 Modules)
131 up to 137
(with 2 Modules)
Configuration
accommodates:
Max. Subrack connection
Dimensions (WxHxD)
Weight of Empty Frame
w/o modules and
w/o batteries
Weight of Frame with
modules and w/o batteries
Max.
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 4/17
Section-10
UPScale RI 40
DPA UPScale RI
Configuration
accommodates:
Max. Subrack connection
Dimensions (WxHxD)
Weight of Empty Frame
w/o modules and
w/o batteries
Weight of Frame with
modules and w/o batteries
Max.
kW
80
mm
kg
50
kg
124 up to 136
(with 4 Modules)
MODULES
UPScale M 10
UPScale M 20
KW
10
20
No.
20-50 *1)
30-50 *1)
Dimensions (WxHxD)
Weight UPS Module
Colors
mm
kg
21.5
Front : RAL 9005
Note : * 1) Depending of the effective load in kW used by the module (see chapter 10.5 Battery characteristics)
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 5/17
Section-10
UPScale M 10 or M 20
Module Type
UPScale M 10
UPScale M 20
10
10
20
20
kVA
KW
Input Frequency
Hz
Inrush Current
max. In
Sine-wave THDi = < 3 % @ 100% load
kW
10.5
21
15.2
30.4
kW
11.5
23
16.6
33.3
10.3.1 GRAPH:
0.96
0.8
0.985
0.99
0.99
0.6
0.4
0.2
0
25
50
75
100
load %
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 6/17
Section-10
10.3.2 GRAPH:
4.5
Input THDi
5.0
4.0
4.0
3.7
3.5
3.4
3.0
3.0
2.5
2.0
1.5
25
50
75
100
Load %
UPScale M 10 or M 20
Module Type
Variable Number of 12V Battery Blocks
Maximum Battery Charger Current
Battery Charging Curve
UPScale M 10
UPScale M 20
No.
20-50 *1)
30-50 *1)
4A
(optional 6 A)
4A
(optional 6 A)
Temperature compensation
Battery Test
Battery Type
Note : * 1) Depending of the effective load in kW used by the module (see table below)
Description
Number of battery blocks
Max. Power in KW
Max. autonomy (min.)
20
6
5
UPScale Module M 10
24
28
30
34-50
8
8
10
10
5
5
5
999
30
12
5
UPScale Module M 20
34
36
40
40
48-50
12
16
20
16
20
999
5
5
999
999
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 7/17
Section-10
UPScale
Module Type
M 10 or M 20
UPScale M 10
kVA
KW
A
V
Output Frequency
Hz
Bypass operation
Permissible Unbalanced Load
Deg.
UPScale M 20
10
20
10
20
14.5
29
3x380/220V or 3x400/230V or 3x415/240V
Static:
< +/- 1%
Dynamic (Step load 0%-100% or 100%-0%)
< +/- 4%
With Linear Load
< 1.5%
With Non-linear Load (EN62040-3:2001)
< 3%
50 Hz or 60 Hz
Synchronized with mains
< +/- 2 %
(selectable for bypass operation)
or < +/- 4 %
Free running
+/- 0.1 %
At Nominal Input voltage of 3x400 V
+/- 15%
or 190 V to 264 V ph-N
100%
+/- 0 deg.
125 % load
150 % load
Inverter :
Bypass :
10 min.
60 sec.
3 x In during 40 ms
10 x In during 20 ms
Crest - Factor
3:1
10.5.1 GRAPH:
%
100
95
90
94.5
85
80
95
95.5
95.5
75
70
25
50
75
100
Load %
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 8/17
Section-10
10.5.2 GRAPH:
22.0
21.0
20.0
19.0
18.0
17.0
16.0
15.0
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.0
UPSCALE 10 (kW)
6.0
5.0
4.0
UPSCALE 10 (kVA)
UPSCALE 20 (kW)
UPSCALE 20 (kVA)
3.0
2.0
1.0
0.0
0.90
0.95
1.00
0.95
UPScale Module
M 10
Ind.
cos
0.9
0.95
unity 1
0.95
0.9
0.85
0.8
0.75
0.7
0.6
0.90
0.85
0.80
0.75
0.70
0.60
UPScale Module
M 20
kW
kVA
kW
9
9.5
10
10
9
8.5
8
7.5
7
6
10
10
10
10
10
10
10
10
10
10
18
19
20
19
18
17
16
15
14
12
kVA
20
20
20
20
20
20
20
20
20
20
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 9/17
Section-10
Module Range
Module Type
UPScale M 10
UPScale M 20
55 / 49
57 / 49
dBA
Operation temperature
0 40
20 25
Storage Temperature
-25 - +70
Max. 6 months
1500 / 4850
2000 / 6600
2500 / 8250
3000 / 9900
0.95
0.91
0.86
0.82
Relative Air-humidity
Accessibility
Positioning
Load
M 20
M 10
:
:
:
100 %
95.5%
95.5%
75 %
95.5%
95.5%
50%
95%
95%
25%
94.5%
94.5%
98 %
10.7 STANDARDS
Safety
Electromagnetic Compatibility
EMC Classification for
EN 62040-1-1, EN 60950-1
EN 61000-6-4 Prod.standard: EN 62040-2
EN 61000-6-2 Prod.standard: EN 62040-2
EN 61000-4-2, EN 61000-4-3 - EN 61000-4-4 - EN 61000-4-5 - EN 61000-4-6
M 10
M 20
Emission Class
C2
C2
Immunity Class
C3
C3
Performance
EN62040-3
Product certification
CE
Degree of protection
IP 20
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 10/17
Section-10
10.8 COMMUNICATION
Power Management Display (PMD)
1 x system frame
For monitoring and integration in network management
USB
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 11/17
Section-10
Terminals X1X2
X2
X1
X2 / 1
NO
X2 / 2
NC
X2 / 3
X2 / 4
NO
X2 / 5
NC
X2 / 6
X2 / 7
NO
X2 / 8
NC
X2 / 9
X2 / 10
NO
X2 / 11
NC
X2 / 12
X2 / 13
NO
X2 / 14
NC
X2 / 15
Signal
On Display
Function
MAINS_OK
Mains Present
ALARM
Mains Failure
Common
LOAD_ON_INV
Message
Load on Inverter
(Load on Mains bypass)
Common
BATT_LOW
ALARM
Battery Low
Battery OK
Common
LOAD_ON_MAINS
Message
COMMON_ALARM
ALARM
X1 / 1
IN
X1 / 2
GND
X1 / 3
IN
X1 / 4
GND
X1 / 5
IN
X1 / 6
GND
X1 / 7
IN
X1 / 8
GND
X1 / 9
IN
X1 / 10
GND
+ 12Vdc
GND
+ 12Vdc
Customer IN 2
GND
+ 3.3Vdc
Temperature Battery
(If connected , the battery charger current if depending of the battery
GND
temp.)
+ 12Vdc
GND
down is connected)
+ 12Vdc
12 Vdc sourse
GND
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 12/17
Section-10
10.9 OPTIONS
- Modem/Ethernet card or Modem/GSM card for NewavewatchTM Management Software
- SNMP card and WaveMon Management Software , Modbus Protocol
- External Battery Cabinets
- In/Output Transformator for special voltages on request
- Temp. sensor for battery temp. control
10.9.1 SNMP card / WaveMon Management Software
The Simple Network Management Protocol (SNMP) is a worldwide-standardized communication-protocol. It is used
to monitor any device in the network via simple control language. The UPS-Management Software WaveMon also
provides its data in this SNMP format with its internal software agent. The operating system you are using must
support the SNMP protocol. We offer our WaveMon software with SNMP functionality for Novell, OS/2, all Windows
running on INTEL and ALPHA, DEC VMS, Apple.
Two types of SNMP interfaces with identical functionality are available: an external SNMP-Adapter (Box) and an
internal SNMP-Card. Both can manage a parallel system (N modules) and return either global values - which are
consistent for the whole parallel system - or specific values from the single modules.
UPS
External SNMP-Adapter
9
Ethernet
Internal SNMP-Card
UPScale RI 22
max. 80 blocks
1 modules ONLY
UPScale RI 22
max. 80 blocks
up to 2 modules
UPScale RI 22
With 2 Modules
8kW
10kW
12kW
(1x40)x7Ah / Module
(1x50)x7Ah / Module
11
8.
(1x40)x7Ah / Module
UPScale M 20
UPScale M 10
16kW
20KW
Module Type
1 x UPScale M 20
8kW
10kW
12kW
16kW
20KW
1x (2x40)x7Ah
21
15
12
Module Type
2 x UPScale M 10
2 x UPScale M 20
16kW
20kW
24kW
UPScale RI 22
1x (2x40)x7Ah
UPScale RI 24
2x (2x40)x7Ah
21
16
13
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
32KW
40kW
Page 13/17
Section-10
900mm
900 mm
Open
Doors
X
Battery
Cabinet
UPS
Frames
Open
Doors
Open Doors
UPS
Frames
Open Doors
Accessibility
Input and Output Power Cabling
Module Range
Module Type
M 10or M 20
UPScale M 10
UPScale M 20
550
1100
BTU/h
1887
3754
m3/h
150
150
120
150
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 14/17
Section-10
10.12 WIRING AND BLOCK DIAGRAMS FOR ALL FRAMES AND MODULES
The customer has to supply the wiring to connect the UPS to the local power source. The installation inspection
and initial start up of the UPS and extra battery cabinet must be carried out by a qualified service personnel such
as a licensed service engineer from the manufacturer or from an agent authorized by the manufacturer.
More details and procedure are mentioned in the user manual.
10.12.1 TERMINAL CONNECTIONS OVERVIEW
FRAME TYPE
Terminals (T)
Connection Bar (B)
Battery Earth
PE
UPScale
RI10/11/12
16/25mm (T)
UPScale
RI20/22/24
16/25mm (T)
UPScale RI40
Separate. Battery
(+ / N / - )
Input
(+ / N / - )
2
Input Bypass
Input Rectifier
Output load
3+N
3+N+PE
3+N+PE
5 x 10/16 mm (T)
5 x 16/25 mm (T)
3 x 10/16mm (T)
4 x 10/16 mm (T)
2x
2
(3 x 10/16mm ) (T)
3 x M5 (B)
4 x 16/25 mm (T)
4x
2
(3 x 10/16mm ) (T)
3 x M6 (B)
3 x 50 mm (T)
2
+ N 70/95 mm
(T)
50 mm (T)
Batt.
Common
Battery
Output
5 x 10/16 mm (T)
5 x 16/25 mm (T)
3 x 50 mm (T)
2
+ N 70/95 mm (T)
2
+PE 50 mm (T)
3 x 50 mm (T)
2
+ N 70/95 mm (T)
2
+PE 50 mm (T)
Batt.
Input
Output
UPScale RI 40
(on rear site)
Batt.
Input
Output
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 15/17
Section-10
MAINS 3x400/230V
F1 F2
UPS module 1
F1 F2
Rectifier
Cable E
Fuse
E
Inverter
Rectifier
Inverter
Static Switch
Frame
UPS module 5
Fuse
Cable A
Static Switch
M1
M2
Input 3x400V/230V
Enclosure
type
Upscale RI
Upscale RI
Upscale RI
Upscale RI
Upscale RI
Upscale RI
Upscale RI
10
11
12
20
22
24
40
Battery
2
Load
in KW
20
20
20
40
40
40
80
Fuse A
(Agl/CB)
3x40A
3x40A
3x40A
3x80A
3x80A
3x80A
3x160A
Cable A
2
(mm )
(IEC 609501:2001)
5x6
5x6
5x6
5x16
5x16
5x16
5x50
Cable D
2
(mm )
(IEC 609501:2001)
5x6
5x6
5x6
5x16
5x16
5x16
5x50
I nom
(A)
29 A
29 A
29 A
58 A
58 A
58 A
116 A
Fuse E
+/N/(Agl/CB)
3x63A
3x63A
3x63A
3x100A *1
3x100A *1
3x100A *1
3x224A*1
Cable E (mm )
Only for external Batteries
+/N/Com.
Battery
3x10
3x10
3x10
3x25 *1
3x25 *1
3x25 *1
3x95 *1
Sep. Battery
2x(3x10)
2x(3x10)
2x(3x10)
4x (3x10)
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 16/17
Section-10
Fuse B
Cable B
F1 F2
Inverter
UPS module 5
UPS module 1
F1 F2
Rectifier
Cable E
Fuse
E
MAINS 3x400/230V
Rectifier
Inverter
Static Switch
Static Switch
Frame
M2
M1
Cable D
Enclosure
type
Upscale RI
Upscale RI
Upscale RI
Upscale RI
Upscale RI
Upscale RI
Upscale RI
10
11
12
20
22
24
40
Output
3x400V/230V
@ cosphi 1.0
Bypass
3x400V/230V
Input 3x400V/230V
Battery
2
Load
in KW
20
20
20
40
40
40
80
Fuse B
(Agl/CB)
3x40A
3x40A
3x40A
3x80A
3x80A
3x80A
3x160A
Cable B
2
(mm )
(IEC 609501:2001)
5x6
5x6
5x6
5x16
5x16
5x16
5x50
Max. Input
Current
with battery
charging
(A)
Fuse C
(Agl/CB)
27
27
27
68
68
68
136 A
3x40A
3x40A
3x40A
3x80A
3x80A
3x80A
3x160A
Cable C
2
(mm )
Cable D
2
(mm )
(IEC
609501:2001)
(IEC
609501:2001)
I nom
4x6
4x6
4x6
4x16
4x16
4x16
4x50
5x6
5x6
5x6
5x16
5x16
5x16
5x50
29 A
29 A
29 A
58 A
58 A
58 A
116 A
Fuse E
+/N/(Agl/CB)
3x63A
3x63A
3x63A
3x100A *1
3x100A *1
3x100A *1
3x224A*1
Cable E (mm )
Only for external
Batteries
+/N/Com.
Battery
Sep.
Battery
3x10
3x10
3x10
3x25 *1
3x25 *1
3x25 *1
3x95 *1
2x(3x10)
2x(3x10)
2x(3x10)
4x (3x10)
www.newavenergy.com
04-0906_S10_NW_TDSDPA_UPSCALE_RI_GB_110929.DOC
Printed in Switzerland Modifications reserved
Page 17/17