You are on page 1of 5

1

A New Protection Scheme for DC Microgrid using


Line Current Derivative
A. Meghwani, S. C. Srivastava, Member, IEEE, S. Chakrabarti, Member, IEEE

AbstractProtection scheme for AC transmission systems are


well understood and matured. On the other hand, DC system is
still facing a challenge in developing proper protection scheme
because of its natural characteristics. A protection scheme,
which utilizes some of the developed techniques for AC system,
and modied to suit the DC system characteristics, is proposed
in this paper. The scheme is based on the concept of DC current
prole under transients, which depends on the fault location.
This property is combined with the directional feature to achieve
the protection of a DC microgrid. The proposed scheme is
demonstrated on the ring type DC microgrid system, which is
able to detect the fault in the DC system, and also ensure its
backup protection. The proposed concept is veried and tested
through MATLAB/Simulink simulations.
Index Terms - DC Microgrid, system protection, fault current.

I. I NTRODUCTION
A low or medium voltage electrical network, consisting of
distributed resources, especially renewable sources of energy,
storage devices, and loads, is known as a Microgrid [1]. The
electrical network can be AC, DC, or mixed, and may or may
not be connected to the main grid. DC distribution network has
advantage of high efciency [2], easy paralleling of sources
on DC bus [3], and more power transfer capacity [4].
One of the main challenge in adopting the DC distribution
system is the lack of effective solution to the fault protection.
Protection system includes protective devices such as fuses,
circuit breakers, load break switches, and relays. DC microgrid
may consist of Voltage Source Converters (VSCs) in the
network, which demand high speed protection and isolation
from the faulted network. Because of the presence of large
DC capacitors and low impedance offered by the DC cable, a
fault in the DC system may result into high transient currents
and voltages. The protection system should have the so-called,
4S property viz, selectivity, sensitivity, security and speed [5].
It should also provide redundancy and dependability at the
minimal cost.
A protection scheme based on handshake signal method
for Multi Terminal DC (MTDC) system is reported in [6].
In this scheme, as the fault is detected, all the VSCs are
disconnected from the AC side, and the capacitors on the DC
side support the load for short duration. As the system deenergises, the load is dropped during the fault, which is not a
desired situation.
Reference [7] studied the application of different system
parameters such as, over current, under voltage, di/dt, dv/dt
A
Meghwani
(e-mail:anjum@iitk.ac.in),
S.C.
Srivastava
(email:scs@iitk.ac.in) and S.Chakrabarti (e-mail:saikatc@iitk.ac.in), are with
the Department of Electrical Engineering, Indian Institute of Technology
Kanpur, 208016.

978-1-4673-8040-9/15/$31.00 2015 IEEE

during faults. The results illustrate that the peak magnitude


and the time of peak for the rate of change of fault current
is the same for over and under damped fault conditions. This
implies that the response is less dependent on the fault type,
and makes fault discrimination difcult.
Reference [8] had investigated a range of protection solutions and reported that the differential current scheme is
suitable for the DC system. Differential protection has highest
selectivity, and only operates in case of internal fault. Its
operation would not be affected by size and rating of the
system components. But it requires a reliable communication
channel for instantaneous data transfer between the terminals
of the protected element. Because of chances to possible
communication failure, differential protection will require a
separate backup protection scheme. This increases the total
cost and size of the protection system, and limits its application
in microgrids.
The concept of smart grid and microgrid requires sensors
and communication networks to be provided in order to
monitor the system condition and avoid outages. The communication may not be critical for monitoring functions, but
if it is used for protection, and if fails it may result into
system shutdown. Therefore, this paper proposes a scheme
with primary and secondary protection based local measured
system parameter characteristics that does not require any
communication channel. To increase the system reliability and
robustness, backup protection is also developed without using
any communication channel.
A mathematical analysis is presented in this paper to determine the parameters of the fault current derivative, such as
the peak magnitude and time of peak in terms of network parameter. A protection system design framework is developed,
which provides fault discrimination and fast operating speed.
The proposed scheme is tested on a typical DC microgrid
architecture.
II. S YSTEM C ONFIGURATION
A loop type DC micro grid system is considered for
designing the protection system, as shown in Fig. 1. The
loop type conguration is more robust and reliable under fault
condition [9]. Efciency of this system is high, especially for
small length of interconnected cables . The system consists of
the following elements:

Non deterministic generation: Sources with a non predictive generation, includes solar Photo Voltaic (PV)
connected through a DC-DC converter, and wind turbine using Permanent Magnet Synchronous Generator
(PMSG) connected through a VSC. Both the converters

F
1

PD

0.4
1
i (t) (pu)

PD

5.2
F
4

5.1

2.5

3.5

4.5

5.5

3.1

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5
Time (secs)

4.5

5.5

0
0.5
1
0.5

PD 3

DC DC

3.2

0
0.5
1

i34

F
3

i45

Cable

Battery

0.6

45

Cable
PD

4.2

0.5

work on the principle of maximum power point tracking


from the sources.
Deterministic generation: Either diesel generator or grid
of limited capacity connected through VSC is used as a
deterministic source.
Loads: Constant resistance type of DC loads are used in
this system
Energy storage system: To take care of load and generation unbalance, energy storage system is used. In this
work, Battery Energy Storage System (BESS) has been
considered, which is connected through a bi-directional
DC-DC converter.
The DC bus voltage is controlled by grid-VSC in grid
connected mode or by battery converter in islanded mode [10].
The power and component ratings of all the modules are given
in Table I [11]. Fig. 2 shows the current ow in various line
sections during normal operating condition. Power delivered
by sources connected to system with load and wind speed
variations is shown in Fig. 3. In this system, all converter
topologies incorporate protection of IGBTs but not the diodes.
In such a case, if a fault on DC bus is not cleared within 2
ms [3], then freewheeling diodes and other sensitive network
components may get damaged.
III. S YSTEM A NALYSIS D URING FAULT
In this section, analytical expressions of fault on DC bus
[12] are used to depict the response of the system. To general-

1
1
1.2

1
1

Grid

(pu)

Fig. 2. Line currents during load and wind speed variations.


0.4
0.2
0
0.2
1

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5

4.5

5.5

1.5

2.5

3.5

4.5

5.5

Batt

(pu)

0.2

0.2
1

PWind (pu)

TABLE I
R ATING OF DC M ICROGRID C OMPONENTS
DC Grid Voltage
1200 V
Base Power
2 MW
Battery DC-DC Converter
0.5 MW
Battery
300V, 1.3kAh, Nickel Cadmium
PV Converter
0.5 MW
Solar Panel
Vmp = 54.7, Imp =5.58 at STC
1 MW
Grid VSC
Wind Turbine
2 MW, PMSG
Cable Resistance
10 m per Km
Cable Inductance
100 H per Km
Filter Capacitor, C
25 mF
Load
Constant impedance load 2 MW

(pu)

Fig. 1. DC Microgrid Architecture

PV

Wind
VSC

Voltage (pu)

51

i (t) (pu)

PD 4
Wind
Turbine

0.4
0.2
1

4.1

PD

0.8
0.6
0.4
0.2
1
0.4
0.3
0.2
0.1
1
1.5

PLoad (pu)

PD: Protective Device

1.5

23

Cable

F
2

PD
PD

0.2

34

PD 5
Load

Grid

2.2

i23

i51
PD

Grid
VSC

0.5

F
5

Cable

PD 2

12

i12

PD
1.1

2.1

i (t) (pu)

Solar Panel

PD

Cable

i (t) (pu)

PD
1.2

i (t) (pu)

PD
1

DC-DC

1
0.5
0
1

Time (s)

Fig. 3. Power delivered by sources with load and wind speed variations.

ize the scheme, a small section of the DC network during fault


is considered in Fig. 4a for example fault F1 . A short circuit
in the DC system may results into high fault current due to
the presence of charged capacitors and low impedance offered
by the cable. The severity of the fault increases as the DC bus
voltage level increases and/or cable length reduces. During
fault, the current response of the equivalent RLC circuit, as
shown in Fig. 4b, is expressed as, [12],
i(s) =

vC (0)/L + iL (0)s
1
s2 + R
L s + LC

(1)

where iL (0) and vC (0) are the current through the inductor
and voltage across the capacitor respectively, just before occur-

r
VSC

vC

r
iL

RF

Fault

(a)

L
iL

vC

RF

Fault
(b)

Fig. 4. Faulted network section and its RLC equivalent circuit

rence of the fault. R is the series equivalent of fault resistance


RF and r. L and r are the equivalent series inductance and
resistance of the cable upto the fault point. In this expression,
the converter current contribution to the fault is assumed to
be negligible because of the slow response of the converter
controllers. In time domain, the fault current i(t) can be written
as,
vC (0)
[ep1 t ep2 t ]
i(t) =
L(p2 p1 )
iL (0)
[p1 ep1 t + p2 ep2 t ]
+
p2 p 1
where, p1 & p2 are the poles of (1), and are given by,
 
2
R
R
1

p1 , p2 =
2L
2L
LC

Primary Protection Zone

F5

1
PD
1.1

F1

PD
1.2

PD

2.1

TS
TP
(3)

(4)

vC (0)
di
|=
iL (0)(p1 + p2 )
(5)
dt
L
For RF = 0, R is equal to the equivalent cable resistance
upto fault point denoted by r. In this case (R/2L)2 is less
than 1/LC and hence, p1 and p2 will be complex conjugate
and only real part contribute to fault current. Therefore, the
contribution of the second term, compared to the rst in above
equation, to di/dt magnitude will be negligible, and only the
rst term may be considered. Therefore (5) reduces to the
following equation.
|

vC (0)
i
|=
(6)
t
L
As L changes with the length of line considered, the magnitude of di/dt, found by using (6) depends on the location of
the fault. This characteristics of di/dt during fault is utilized
to design the protection system.
For time t, immediately after the fault, at kth sampling
period, i is written as follows.
|

vC (0)
t
L

Secondary Protection Zone

Time to Trip

Immediately after the fault at t = 0, the magnitude of di/dt


will be given by the following equation.

i =

IV. P ROPOSED P ROTECTION S YSTEM D ESIGN


A high speed differential current protection was proposed
in [13], where central processing unit was used for fast assessment of the fault. This requires communication channel that
introduces a risk of single point of failure. It is desirable that
the protection system should be fast, sensitive and selective to
faults. From (7) one can observe that the i depends upon L,
which is the cable parameter and solely depends on the fault
location. This property can be combined with the directional
feature to achieve a localized fault detection technique.

(2)

Depending upon whether 1/LC is greater, equal or less than


(R/2L)2 , the values of p1 and p2 will be real or complex.
From (2), di/dt can be determined as,
vC (0)
di
=
[p1 ep1 t + p2 ep2 t ]
dt
L(p2 p1 )
iL (0) 2 p1 t
[p p
p22 ep2 t ]
+
p2 p 1 1

Here, i = ik ik1 and t = tk tk1 , ik is sampled


at time tk and ik1 at tk1 . ik1 and ik are the present and
one-sample-delay current values. The protective device PD is
activated once i reaches a threshold value.

(7)

'i

'is

'i p

'i

Fig. 5. Non-Directional characteristics of P D1.2

A. Protective Device (PD)


In Fig. 1, the PD consists of a digital relay, which gives trip
signal to a circuit breaker in case of a fault. Digital relays are
equipped with microcontroller for setting thresholds, and analog to digital converters to transform the analog measurements
to digital form. The difference between the present and the
previous sampled current, i, is compared with the threshold
setting to generate a trip signal.
The DC cables are protected by PDs connected on both
the ends as shown in Fig.1, and provided with the inter
trip circuits. In case a PD trips on sensing of fault through
relays, the other side breaker is also tripped on follow-me
instruction [5].
B. Pickup Threshold Settings
To calculate the threshold setting, the protection scheme is
divided into two parts, primary and secondary (backup). For
primary protection, the relay should pickup with denite time
delay of TP , while for secondary protection it will pickup
at TS as shown in Fig. 5. The secondary protection will act
only if the primary protection fails to respond. The threshold
settings for the primary protection are calculated based on the
equivalent circuit considered from the relay position upto the
fault point. The minimum pickup threshold, iP , for P D1.2
is determined by considering the fault F1 , close to P D2.1
i.e., at 100 % line length. If fault occurs close to P D1.2 , i
magnitude will be maximum.

iS secondary
protection
Threshold (Amp)

600
1028
1500
1420
766

-200
-600
-700
-300
-100

i45(t) (pu)

TABLE III
P ICKUP T HRESHOLD S ETTINGS FOR P Dx.1
P Dx.1

P D1.1
P D2.1
P D3.1
P D4.1
P D5.1

Fault
location
from
P Dx.1 (m)
1000
500
200
300
1000

Inter trip with


P Dx.2
P D5.2
P D1.2
P D2.2
P D3.2
P D4.2

i34(t) (pu)

23

iP Primary
Protection
Threshold (Amp)

iS Pickup
threshold setting
(Amp)
150
250
600
800
300

1) Pickup Threshold Settings for P Dx.2 : If the primary


protection fails, then the secondary protection should act. In
this scheme, the relay in the line adjacent to the faulted line
provides the backup either in the positive direction or in the
reverse direction. For example if P D1.1 fails to operate as
primary protection for fault F5 , P D1.2 will provide a backup.
Therefore, P D1.2 should be programmed for non directional
characteristics with different pick up thresholds. Table II shows
the primary protection threshold settings for P Dx.2 , where x
varies from 1 to 5.
2) Pickup Threshold Settings for P Dx.1 : On similar concept, if P D2.2 fails to operate for fault F2 , P D2.1 will act as
a backup. Hence, P D2.1 is set for secondary protection with
denite time delay of TS . The pickup threshold settings of
P Dx.1 relays are summarized in Table III.

i51(t) (pu)

P D1.2
P D2.2
P D3.2
P D4.2
P D5.2

Fault
location
from
P Dx.2 (m)
1000
500
200
300
1000

Voltage (pu)

P Dx.2

i (t) (pu)

12

i (t) (pu)

TABLE II
P ICKUP T HRESHOLD S ETTINGS FOR P Dx.2

20
10
0
10
1.995
10

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005
2.01
Time (secs)

2.015

2.02

0
10
20
1.995
5
0
5
10
1.995
5
0
5
1.995
4
2
0
2
1.995
1
0.5
0
0.5
1.995

Fig. 6. Line currents and bus voltage response for fault F1 occurred at t = 2s.

B. Backup Protection
In case P D1.2 fails, P D1.1 acts as a backup by comparing
i with iS . And if P D2.1 fails, P D2.2 acts as backup. All
secondary zones of protection activate at denite time delay of
TS and pickup only when the computed difference is greater
than the threshold.
P Dx.2 settings should be such that it provide trip under
forward directional current derivative as primary and negative
threshold setting for secondary, with time discrimination. Non
directional characteristic of P Dx.2 is shown in Fig. 5.
Similarly, P Dx.1 should operate on follow-me instruction
for primary zone of protection and positive pickup threshold
setting for secondary resembles the characteristics of directional relay. P Dx which is connected between the source
and the bus, activate with the backup protection only, and in
coordination with P Dx.1 .

C. Denite Time Delay Setting


Primary protection for forward direction faults (F1 to F5 )
are activated with denite time delay of TP . For secondary
protection, a constant time delay in addition to TP is provided
to trip at TS . In this scheme, the inverse time characteristic
is not desirable, because a delay in protection may cause
severe damage to the system and its components, especially
the converters.
V. P ROTECTION D EVICE C OORDINATION
A. Primary Protection
To achieve coordination among all protective devices (PDs),
it is essential that all the devices act quickly for faults in their
respective zones. For fault F1 , i is calculated and compared
with iP , which generate a trip signal at TP , for P D1.2 ,
along with a follow-me instruction for P D2.1 to isolate the
faulted cable. Similarly, for fault at F2 , P D2.2 should act with
follow-me instruction for P D3.1 , and so on.

VI. S IMULATION R ESULTS AND O BSERVATIONS


To demonstrate the proposed protection scheme, fault F1
in Fig. 1 is simulated at t = 2s. As shown in Fig. 6, high
transient currents cause a voltage collapse within 5 ms of the
fault occurrence. This implies that the protection required for
the DC system should be much faster as compared to the
AC system [3]. The line currents are sampled and monitored
continuously. As the fault F1 takes place, i12 is calculated
from sampled current, and compared with the threshold given
in Table II, to generate the trip signal. P D1.2 and P D2.1
operate and disconnect the faulted line within TP of 200 s,
thereby restoring the system, as shown in Fig. 7.
With the primary protection, only selective part of the
system is disconnected and as a result, the rest of the system
is rescued successfully. The current i12 merely reaches to
0.5 pu, which implies that the converters and other system
components are protected. The DC bus voltage momentarily
drops to 0.7 pu because of high di/dt during fault, and restore
back to 1 pu as fault clears.

But because of backup, the system is partially recovered and


system continue to operate at 0.9 pu, as shown in Fig. 8.

i12(t) (pu)

0.5
0

i34(t) (pu)

i23(t) (pu)

0.5
1.995
1

2.005

2.01

2.015

2.02

0
1
1.995
1

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

0.5
0

i45(t) (pu)

0.5
1.995
1
0.5

i51(t) (pu)

0
1.995
0
0.5

Voltage (pu)

1
1.995
1

0.5
1.995

VII. C ONCLUSION
The design of an effective protection system solution for a
DC microgrid has been proposed in this paper. The natural
characteristics of the fault current derivative, in the DC networks has been analyzed, and used to develop the protection
algorithm. Thresholds, which depend on the fault location,
have been calculated for all the line sections considering the
equivalent circuit upto the fault point and, compared with the
actual values. A protection solution for loop type DC microgrid system is demonstrated, which is easy to be extended
to other congurations. The scheme is fast in detecting and
isolating the faulty section through primary protection. It is
able to provide the backup protection successfully under the
failure of the primary protective relays. The proposed scheme
is veried and tested on the MATLAB/Simulink simulations.

Time (secs)

Fig. 7. Line currents after fault F1 is cleared by P D1.2 and P D2.1 act as
primary protection at TP = 200 s.
i12(t) (pu)

4
2

i34(t) (pu)

i23(t) (pu)

0
1.995
1

2.01

2.015

2.02

R EFERENCES

1
1.995
1

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005

2.01

2.015

2.02

2.005
2.01
Time (secs)

2.015

2.02

0.5
0

i45(t) (pu)
i51(t) (pu)

2.005

The authors would like to thank the Department of Science


and Technology, New Delhi, India for providing nancial
support to carry out this research work under project no.
DST/EE/20100258.

0.5
1.995
1.5
1
0.5
0
1.995
1
0.5
0
0.5
1.995

Voltage (pu)

ACKNOWLEDGMENT

0.9
0.8
0.7
1.995

Fig. 8. Line currents after fault F1 is cleared by P D1.1 as backup protection


on failure of P D1.2 at TS = 500 s.

The system is tested for backup protection also. It is


assumed that P D1.2 fails to operate for fault F1 . Hence, P D1.1
has to provide the backup, and restore the system back to the
normal condition. From Fig. 8, it is observed that, because of
the denite time delay TS of 500 s in the backup protection,
the current i12 reaches to 3 pu. This delay in protection keeps
the bus voltage to 0.8 pu for 500 s and recovers back to 0.9
pu as the fault clears.
Other observations with the result is that, after the fault
clearance, line current i51 reduces to zero. This implies that,
when the secondary protection acts, solar PV source is not able
to supply the power to the load because of activation of P D1.1 .
The primary protection failure will causes load shedding.

[1] R. H. Lasseter, Microgrids, in Proc. IEEE Power Engineering Society


Winter Meeting, vol. 1, no. 2, 2002, pp. 305308.
[2] M. Starke, L. Tolbert, and B. Ozpineci, Ac vs. dc distribution: A loss
comparison, in Proc. IEEE/PES Transmission Distribustion Conference
Exposition, 2008, pp. 17.
[3] D. Salomonsson, L. Soder, and A. Sannino, Protection of low-voltage
dc microgrids, IEEE Trans. Power Del., vol. 24, no. 3, pp. 10451053,
July 2009.
[4] M. Starke, L. Fangxing, L. M. Tolbert, and B. Ozpineci, Ac vs. dc
distribution: Maximum power transfer capability, in Proc. IEEE/PES
Conversion Delivery Electrctical Energy 21st Century, 2008, pp. 16.
[5] N. Hatziargyriou, Microgrids Architecture and Control. Wiley-IEEE
Press, 2013.
[6] L. Tang and B. Ooi, Locating and isolating dc faults in multi-terminal
dc systems, IEEE Trans. Power Del., vol. 22, no. 3, pp. 18771884,
July 2007.
[7] S. Fletcher, P. Norman, S. Galloway, and G. Burt, Analysis of the
effectiveness of non-unit protection methods within dc microgrids, in
Proc. IET Renewebale Power Generation, IET, Sep 2011, pp. 16.
[8] S. D. A. Fletcher, P. J. N. andS. J. Galloway, P. Crolla, and G. M.Burt,
Optimizing the roles of unit and non-unit protection methods within dc
microgrids, IEEE Trans. Smart Grid, vol. 3, no. 4, p. 20792087, Dec
2012.
[9] M. Saisho, T. Ise, and K. Tsuji, Conguration of dc loop type quality
control center, in Proc. IEEE Power Conversion Conference, vol. 2,
Sep 2002, pp. 434439.
[10] K. Shenai and K. Shah, Smart dc micro-grid for efcient utilization
of distributed renewable energy, in Proc. IEEE Energytech, 2011, pp.
16.
[11] L. Xu and D. Chen, Control and operation of dc microgrid with variable
generation and energy storage, IEEE Trans. Power Del., vol. 26, no. 4,
pp. 25132521, 2011.
[12] S. D. A. Fletcher, P. J. Norman, S. J. Galloway, and G. M. Burt,
Determination of protection system requirements for dc unmanned
aerial vehicle electrical power network for enhance capability and
survivability, in Proc. IET Electrical Systems in Transportation, vol. 1,
July 2011, pp. 137147.
[13] S. D. A. Fletcher, P. J. Norman, S. J. Galloway, P. Crolla, and G. M.Burt,
High speed differential protection for smart dc distribution system,
IEEE Trans. Smart Grid, vol. 5, no. 5, pp. 26102617, 2014.

You might also like