You are on page 1of 8

1.

DATA SHEET
To be filled by vendor
(VENDOR TO FURNISH ALL THE DETAILS REQUIRED HEREUNDER WITHOUT WHICH THE
OFFER IS DEEMED TO BE INCOMPLETE)
S. NO

DESCRIPTION

UNIT

VALUE

1.

Cooling Tower Type

FRP Induced Draft


Counter Flow
Cooling Tower

2.

Cooling tower Make

Paltech Cooling
Towers &
Equipments Limited

3.

Cooling Tower Model

2PCFR-2929C

4.

No. of cells (operating/Standby)

5.

Cooling tower capacity per cell

Cu.m/hr

435

6.

Rated circulated water Flow

Cu.m/hr

435

7.

Hot water temperature

Deg.C

40

8.

Cold water temperature

Deg.C

30

9.

Design Cooling Range

Deg.C

10

10.

Design ambient Wet bulb


temperature
Design relative humidity

Deg.C

Deg.C.

15.

Wet bulb temperature at the tower


inlet
Relative humidity at the tower
inlet
Relative humidity at the stack
outlet
Evaporation loss

16.

11.
12.
13.
14.

%
%

25
60
25
60
100

1.53

Drift Loss

0.05

17.

Tower capability

100

18.

Cooling tower dimensions

A.

Width

5.4864

B.

Length of tower

10.9728

C.

Tower plan area (Inside)

sq.m.

60.20

D.

Basin size (inside)

(W x L)

As per Client

E.

Fore bay size

WxLxH

As per Client

F.

Cold water channel size

WxLxH

As per Client

G.

Height from curb to fan deck

4.020

H.

Air opening depth or height

1.3

I.

Rain zone height

0.9

J.

Total static head above basin curb

K.
L.

Distance between the top of fill &


bottom
of distribution nozzle
Fan stack height

M.

Ventury Height

N.

Fan stack inlet diameter

mm

During detail Engg.

O.

Fan stack throat diameter

mm

During detail Engg.

P.

Fan stack outlet diameter

mm

During detail Engg.

Q.

Dry weight

Kgs

During detail Engg.

R.

Wet weight

Kgs

During detail Engg.

19.

Fan :

A.

Quantity per cell

B.

Make

PALTECH

C.

Type

Axial Flow Propeller


Type

D.

Fan Diameter

mm

4268

E.

Hub Diameter

mm

650

F.

Fan Speed

RPM

272

G.
H.

Fan tip Speed (maximum 65


m./sec.)
No. of blades

I.

Fan blade pitch angle

J.

Fan blade material

K.

Hub material

L.

Fan hub cover material

M.

Total Fan Efficiency

20.

Fan Stack

A.

Type

B.

Height

C.

D.

Elevation of top of fan stack from


basin kerb
Diameter

21.

Gear Box :

A.

Type of gear

B.

Make

m
mm

2.68
During detail Engg.
During detail Engg.
During detail Engg.

m/sec.

60.75
6

Deg.

During Detail Engg.


FRP
MSHDG
N.A.

78

Velocity recovery
trype

Later on
Later on
Later on
Spiral Bevel
Paltech

C.

Reduction ratio

D.

Transmission efficiency

E.

Bearing type & No.

F.

Life of bearings

G.
H.

Service factor at rated HP of driver


(Min. 2)
Gear box casing material

I.

Gear material

J.

Gear shaft material

K.

Yoke material

L.
22.

Base frame material for gear box &


motor
Screen

A.

Number per tower

One coarse and one


fine screen per cell

B.

Size & material of bars

After Award of offer

23.

Fill

A.

Type

PVC Film Fill

B.

Make

MM Aqua/ Cool Deck

C.

Model No.

D.

Material

E.

No. of layers

F.

Fill depth

G.

Quantity per layer

H.

Average air density

I.

5.51:1
%

97
Taper Roller Bearing

Hrs

100000
>2
Grey Cast iron
Case Hardening Alloy
Steel
MSHDG
CI
MSHDG
SS304

C-10-12
PVC
3
m

0.9
335

kg/cu.m.

1.1362

Fill pack area for the tower

Sq.m.

30.10 per cell

J.

Fill volume for the tower

Cu.m.

27.09 per cell

K.

Wetted surface / cu.m.

L.

Wetted surface area for the tower

M.

Fill support material

N.
24.

Maximum allowable temperature


on the fills
Drift Eliminator

A.

Type

Honey comb Type

B.

Make

MM Aqua/ Cool Deck

C.

Number of passes

Sq.m/cu.
m
Sq.m.

249
6744.55 per cell
MSHDG

Deg.C

55

Double pass

25.

Spray Nozzle

A.

Type

B.

No. of nozzles per cell

C.

Make

D.

Material

E.

Flow through each nozzle

Lit/sec.

6.1 m3/hr

Pressure drop across the nozzle

mmwc

0.1

Non Clogging
72

PP

26.

Hot water distribution duct

A.

Width

B.
C.

Height
Volume of Hot water distribution
duct
Lateral distribution pipes

mm
cu.m.

Size OD x thk./ Length of pipe for


the Tower
No. of lateral distribution pipes

mm x
mm

27.
A.
B.

Monorail, Chain Pulley Hoist


and Accessories
A.
Maximum handling capacity of
chain & pulley block provided at
fan deck level
B.
Maximum handling capacity of
chain & pulley block provided at
end wall davit assembly
C.
Maximum handling capacity of
chain & pulley block provided for
screen handling
29. Sluice Gates

mm

Later on

Later on
Later on

28.

Tonnes
Tonnes
Tonnes

N.A
N.A
N.A

A.

Number per cold water outlet

B.

Name of the manufacturer

C.

Type

D.

Gate Size

E.
F.

Confirms to IS 3042 (Indicate also


the applicable calss
Material of Construction

G.

Frame

C.I.

H.

Spindle

Mild Steel

I.

Fasteners

J.

Embedded parts

30. Valves (Isolating valve in Sludge


pit

1
Bankim
Gate
350mmx350mm

Confirm

Carbon Steel
C.I.

A.

Numbers offered

B.

Nominal size

C.

Type

Gate

D.

Make

Bankim

E.

MOC Body and stem

C.I. / SS

1
100mm

31. Performance data :


A.

Minimum operating load per cell

Cu.m/hr/
sq.m.
mwc

B.
C.

Pressure head required from the


basin curb to spray nozzle outlet
Water loading

D.

Air loading

E.

Configuration ratio (L/G ratio)

F.

Dry Air Density

Kg/m3

1.1478

G.

Wet air density

Kg/m3

1.1246

H.

Total wet air per fan

Kg/hr

353520

I.

Heat transfer coeffieient

Confidential

J.

Tower characteristics

KaV/L

1.523

3.405

14.45
2.68 (Static)

kg/hr./sq.m.

14368.52

kg/hr. /
sq.m.

12753.23
1.127

32. Air side pressure drop


A.

Inlet

mmwc

B.

Rain zone

mmwc

C.

Fills

mmwc

D.

Distribution level

mmwc

E.

Drift eliminator

mmwc

1.526

F.

Plenum

mmwc

0.606

G.

Stack

mmwc

0.1

H.

Any other

mmwc

NIL

I.

Total static pressure

mmwc

16.754

J.

Velocity pressure at fan throat

mmwc

2.827

K.

Velocity pressure at stack exit

mmwc

2.425

L.

Velocity recovery pressure

mmwc

0.2814

M.

Total pressure

mmwc

19.178

N.

Air velocity at tower inlet

m/sec.

6.62

O.

System pressure drop (Pressure drop


from air inlet to drift eliminator)

mmwc

11.116

16.047

P.

Velocity pressure at tower inlet

mmwc

Q.
R.

Velocity pressure ratio (system


pressure drop / velocity pressure at
tower inlet)
Average fill velocity

m/sec.

3.19

S.

Fan exit velocity

m/sec.

6.50

T.

Air flow per cell

kg/hr.

383824

U.

Density of air @ tower inlet

Kg/cu.m.

1.1478

V.

Density of air @ fan exit

Kg/cu.m.

1.1246

W.

Enthalpy of air at inlet

Kcal/kg.

18.04

X.

Enthalpy of air at outlet

Kcal/kg.

29.89

Y.

Air outlet temperature

Deg.C

34.46

Z.

Fan capacity per cell

Cu.m./hr.

382500
23.61

4.71

AA.

Fan power

kW

BB.

Motor shaft power per cell


(Fan power / transmission
efficiency)
Power consumption at motor inlet
terminal per cell (motor shaft power
/ efficiency of motor)
Motor selected

kW

CC.
DD.

3.405

24.34
kW
26.46
kW

30

2. DRAWING AND DOCUMENT SCHEDULE


Vendor has to submit the following Drawings and documents after order placement.
SI.
DESCRIPTION
SUBMI
CATEGORY
REMARKS
NO.

SSION

DATE
1

Design basis both mechanical &


civil for cooling tower package.
GA drawing of cooling tower
indicating plan, sections with

Approval

Approval

overall dimensions
Foundation loading data,
3

foundation design calculation &


foundation detailed drawings

Approval

Linked with
payment
Linked with
payment.

Linked with
payment.

including excavation drawings


General Arrangement drawing of
4

Mechanical equipment handling


facility for Fan, Screen & Sluice
gate.
General arrangement drawing of
Gear box, Fan, Fill support.
Complete civil, structural design

Approval

Approval

calculations for the cooling tower


basin, fore bay, super structure,
louver, cold water channel, fan
stack, staircase, ladder etc. The
6

civil / structural design calculations


prepared by vendor shall be

Approval

approved by purchaser / Owner.


Complete drawing submissions
should be completed within twelve
(12) weeks from the order
finalization date.
Installation drawing for all basins
7

and fore bay fittings along with

Approval

puddle pipe details


Hot water distribution drawing
8

showing the hot water header,

Information

lateral pipes and nozzles


Test certificates of the materials for
9

10

various components of cooling


tower..
Fan selection and thermal
calculation.

11

Drive selection calculation

12

Drive data sheet, Performance

Information

Information
Information
Approval

Linked with
payment
Linked with
payment.

curves, General Arrangement


drawing & QAP.
13

Air side pressure drop calculation.

Information

14

Lubrication schedule.

Information

15
16

17

18

Vendor project & Document


schedule
Erections drawings as applicable
for the cooling tower package.
Performance test procedure,
correction curves, log sheets, etc.
required for performance testing of
cooling tower
Spare parts documents, packing
list, Painting specification

Approval
Information

Approval

Approval

You might also like