You are on page 1of 12

Sample Reports

for
HAP v4.80 Example Problem

October, 2013

Carrier Software Systems

Copyright 2013 Carrier Corporation, All Rights Reserved

Introduction
This document contains reports generated using the Carrier Hourly Analysis Program (HAP) v4.80
example problem. Software users sometimes use this information to validate their installation of HAP by
comparing example problem results calculated on their computer versus the reference results shown in
the reports on the following pages. Please note this type of validation verifies the software is properly
installed and functioning on your computer.
To perform this type of validation, please use the following steps:
1. Print the reports found on the following pages.
2. Start HAP v4.80.
3. Create a new, untitled project.
4. Select the "Retrieve HAP v4.8 Data" option on the Project Menu.
5. In the Retrieve window select the HAP48_Example.E3A archive file.
6. After the data is retrieved and you are returned to the main window, save the project.
7. Then generate the same set of reports found on the following pages. The program will perform
calculations before displaying the reports.
8. Compare your results with the reference results on the following pages.
a. If the results match, then your installation is validated.
b. If the results do not match, please send an e-mail to the software support help desk explaining
your problem and attach this PDF and the reports which do not match the reference results.

Air System Sizing Summary for VAV Rooftop


Project Name: HAP48 Example
Prepared by: UTC

10/22/2013
08:19AM

Air System Information


Air System Name ................................... VAV Rooftop
Equipment Class ...................................... PKG ROOF
Air System Type .................................................. VAV

Number of zones ........................................................... 9


Floor Area ............................................................ 9559.0 ft
Location ........................................ Chicago IAP, Illinois

Sizing Calculation Information


Calculation Months ................................... May to Nov
Sizing Data ................................................ Calculated

Zone CFM Sizing ................... Peak zone sensible load


Space CFM Sizing ........... Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load ....................................................... 21.4
Total coil load ..................................................... 256.7
Sensible coil load ................................................ 152.7
Coil CFM at Aug 1600 ......................................... 3846
Max block CFM at Aug 1700 ................................ 3907
Sum of peak zone CFM ....................................... 3965
Sensible heat ratio .............................................. 0.595
ft/Ton ................................................................. 446.9
BTU/(hr-ft) ........................................................... 26.9
Water flow @ 10.0 F rise ..................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ................................................ Aug 1600


OA DB / WB ................................................... 91.0 / 74.0
Entering DB / WB ........................................... 90.4 / 73.4
Leaving DB / WB ............................................ 52.7 / 52.2
Coil ADP .................................................................. 51.2
Bypass Factor ........................................................ 0.038
Resulting RH ............................................................... 52
Design supply temp. ................................................. 55.0
Zone T-stat Check ................................................. 9 of 9
Max zone temperature deviation ................................ 0.0

F
F
F
F
%
F
OK
F

Preheat Coil Sizing Data


Max coil load ...................................................... 215.9 MBH
Coil CFM at Des Htg ............................................ 3653 CFM
Max coil CFM ...................................................... 3907 CFM
Water flow @ 20.0 F drop ................................... N/A

Load occurs at ................................................... Des Htg


Ent. DB / Lvg DB ............................................. -4.1 / 52.0 F

Supply Fan Sizing Data


Actual max CFM at Aug 1700 .............................. 3907 CFM
Standard CFM ..................................................... 3813 CFM
Actual max CFM/ft ............................................... 0.41 CFM/ft

Fan motor BHP ........................................................ 3.61 BHP


Fan motor kW .......................................................... 2.86 kW
Fan static ................................................................. 3.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 3558 CFM
CFM/ft ................................................................. 0.37 CFM/ft

Hourly Analysis Program v4.80

CFM/person ........................................................... 17.62 CFM/person

Page 1 of 5

Zone Sizing Summary for VAV Rooftop


Project Name: HAP48 Example
Prepared by: UTC

10/22/2013
08:19AM

Air System Information


Air System Name ................................... VAV Rooftop
Equipment Class ...................................... PKG ROOF
Air System Type .................................................. VAV

Number of zones ........................................................... 9


Floor Area ............................................................ 9559.0 ft
Location ........................................ Chicago IAP, Illinois

Sizing Calculation Information


Calculation Months ................................... May to Nov
Sizing Data ................................................ Calculated

Zone CFM Sizing ................... Peak zone sensible load


Space CFM Sizing ........... Individual peak space loads

Zone Sizing Data

Zone Name
D101 - Classroom
D102 - Classroom
D103 - Classroom
D104 - Classroom
D106 - Classroom
D107 - Classroom
D108 - Music Room
D113 - West Corridor
D114 - South Corridor

Maximum
Cooling
Sensible
(MBH)
9.3
9.3
9.3
9.6
10.8
10.3
18.8
3.1
2.7

Design
Airflow
(CFM)
449
449
449
455
513
487
893
145
126

Minimum
Airflow
(CFM)
449
449
449
449
449
449
813
79
69

Time of
Peak Load
Jun 1600
Jun 1600
Jun 1600
Aug 1700
Aug 1700
Jun 1700
Aug 1700
Jun 1600
Jun 1600

Maximum
Heating
Load
(MBH)
8.5
8.5
8.5
11.5
12.4
8.5
16.1
3.2
2.8

Reheat
Coil
Load
(MBH)
15.6
15.6
15.6
18.6
19.5
15.6
28.9
4.5
3.9

Reheat
Coil
Water
gpm
@ 20.0 F
-

Zone
Htg
Coil
Load
(MBH)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Zone
Htg
Water
gpm
@ 20.0 F
-

Mixing
Box Fan
Airflow
(CFM)
269
269
269
363
392
269
508
102
89

Zone
Floor
Area
(ft)
907.5
907.5
907.5
907.5
907.5
907.5
2140.0
1054.0
920.0

Zone
CFM/ft
0.49
0.49
0.49
0.50
0.57
0.54
0.42
0.14
0.14

Zone Terminal Sizing Data

Zone Name
D101 - Classroom
D102 - Classroom
D103 - Classroom
D104 - Classroom
D106 - Classroom
D107 - Classroom
D108 - Music Room
D113 - West Corridor
D114 - South Corridor

Space Loads and Airflows

Zone Name /
Space Name
D101 - Classroom
D101 - Typical Classroom
D102 - Classroom
D101 - Typical Classroom
D103 - Classroom
D101 - Typical Classroom
D104 - Classroom
D104 - Classroom
D106 - Classroom
D106 - Classroom
D107 - Classroom
D107 - Classroom
D108 - Music Room
Hourly Analysis Program v4.80

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

9.3

Jun 1600

449

8.5

907.5

0.49

9.3

Jun 1600

449

8.5

907.5

0.49

9.3

Jun 1600

449

8.5

907.5

0.49

9.6

Aug 1700

455

11.5

907.5

0.50

10.8

Aug 1700

513

12.4

907.5

0.57

10.3

Jun 1700

487

8.5

907.5

0.54

Page 2 of 5

Zone Sizing Summary for VAV Rooftop


Project Name: HAP48 Example
Prepared by: UTC

Zone Name /
Space Name
D108 - Music Room
D109 - Practice Room
D110 - Storage
D111 - Office
D113 - West Corridor
D113 - West Corridor
D114 - South Corridor
D114 - South Corridor

Hourly Analysis Program v4.80

10/22/2013
08:19AM

Mult.
1
1
1
1

Cooling
Sensible
(MBH)
16.0
0.6
0.5
1.8

Time
of
Load
Aug 1700
Aug 1700
Aug 1600
Jun 1700

Air
Flow
(CFM)
760
27
22
85

Heating
Load
(MBH)
10.3
1.6
1.5
2.7

Floor
Area
(ft)
1781.0
65.0
120.0
174.0

Space
CFM/ft
0.43
0.42
0.18
0.49

3.1

Jun 1600

145

3.2

1054.0

0.14

2.7

Jun 1600

126

2.8

920.0

0.14

Page 3 of 5

Ventilation Sizing Summary for VAV Rooftop


Project Name: HAP48 Example
Prepared by: UTC

10/22/2013
08:19AM

1. Summary
Ventilation Sizing Method ......................................... ASHRAE Std 62.1-2007
Design Condition ..................................................... Minimum flow (heating)
Occupant Diversity ................................................................................. 1.000
Uncorrected Ventilation Airflow Rate ........................................................ 2922 CFM
System Ventilation Efficiency .................................................................. 0.821
Design Ventilation Airflow Rate ................................................................ 3558 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


D101 - Classroom
D101 - Typical Classroom
D102 - Classroom
D101 - Typical Classroom
D103 - Classroom
D101 - Typical Classroom
D104 - Classroom
D104 - Classroom
D106 - Classroom
D106 - Classroom
D107 - Classroom
D107 - Classroom
D108 - Music Room
D108 - Music Room
D109 - Practice Room
D110 - Storage
D111 - Office
D113 - West Corridor
D113 - West Corridor
D114 - South Corridor
D114 - South Corridor
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.80

Minimum
Supply
Air
Mult.
(CFM)

Floor

Required

Area

Outdoor Air

(ft)

(CFM/ft)

Time

Required

Air

Required

Uncorrected

Space

Averaged

Outdoor Air

Distribution

Outdoor Air

Outdoor Air

Ventilation

Occupancy (CFM/person) Effectiveness

(CFM)

(CFM)

Efficiency

449

907.5

0.12

25.0

10.00

0.80

449

359

0.821

449

907.5

0.12

25.0

10.00

0.80

449

359

0.821

449

907.5

0.12

25.0

10.00

0.80

449

359

0.821

449

907.5

0.12

25.0

10.00

0.80

449

359

0.915

449

907.5

0.12

25.0

10.00

0.80

449

359

0.939

449

907.5

0.12

25.0

10.00

0.80

449

359

0.821

1
1
1
1

759
17
18
19

1781.0
65.0
120.0
174.0

0.06
0.06
0.12
0.06

50.0
1.0
0.0
1.0

10.00
10.00
0.00
5.00

0.80
0.80
0.80
0.80

759
17
18
19

607
14
14
15

0.834
0.834
0.834
0.834

79

1054.0

0.06

0.0

0.00

0.80

79

63

1.057

69
3653

920.0

0.06

0.0

0.00

0.80

69

55
2922

1.057
0.821

Page 4 of 5

Air System Design Load Summary for VAV Rooftop


Project Name: HAP48 Example
Prepared by: UTC

ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>> Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
>> Total System Loads
Central Cooling Coil
Preheat Coil
Terminal Reheat Coils
>> Total Conditioning
Key:

Hourly Analysis Program v4.80

10/22/2013
08:19AM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Aug 1600
HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 74.0 F
HEATING OA DB / WB -6.0 F / -7.2 F
Sensible
Latent
Sensible
Latent
Details
(BTU/hr)
(BTU/hr)
Details
(BTU/hr)
(BTU/hr)
504 ft
12066
504 ft
2576 ft
3141
2576 ft
16471
9559 ft
7365
9559 ft
29195
504 ft
3462
504 ft
21067
0 ft
0
0 ft
0
0 ft
0
0 ft
0
7585 ft
0
7585 ft
13265
0 ft
0
0 ft
0
0 ft
0
0 ft
0
9559 W
19054
0
0
0W
0
0
0
0W
0
0
0
202
36734
28660
0
0
0
0
0
0
0
0
0
0
0
0% / 0%
0
0
0%
0
0
81822
28660
79998
0
82813
28660
78647
0
20%
994
0
0
70%
17184
0
0
30%
9785
0
0
3846 CFM
0
3653 CFM
0
3558 CFM
32534
75299
3558 CFM
279562
0
3846 CFM
9427
3653 CFM
-8315
0
-1013
0%
0
0%
0
152736
103959
348882
0
152736
103959
0
0
0
215869
0
132973
152736
103959
348842
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative values are clg loads

Page 5 of 5

Monthly Simulation Results for VAV Rooftop


Project Name: HAP48 Example
Prepared by: UTC

10/22/2013
08:20AM

Air System Simulation Results (Table 1) :


Preheat Coil
Load
(kBTU)
31847

Preheat Eqpt
Load
(kBTU)
31847

Preheat Coil
Input
(kBTU)
38837

Preheat
Heating Misc.
Electric
(kWh)
0

Central
Cooling Coil
Load
(kBTU)
6

Central
Cooling Eqpt
Load
(kBTU)
6

Central Unit
Clg Input
(kWh)
0

February

26932

26932

32843

March

Month
January

21050

21050

25671

1107

1107

70

April

2573

2573

3138

3143

3143

198

May

252

252

307

16252

16252

1087

June

35434

35434

2326

July

8064

8064

618

August

30242

30242

1919

September

64

64

78

27132

27132

1727

2770

2770

3378

8797

8797

566

November

12989

12989

15841

2254

2254

140

December

21301

21301

25977

119781

119781

146075

132433

132433

8653

Air System Simulation Results (Table 2) :


Terminal
Terminal
Heating Coil
Heating Coil
Load
Input
Month
(kBTU)
(kWh)
January
27627
8097

Supply Fan
(kWh)
768

Terminal Fan
(kWh)
106

Lighting
(kWh)
2480

Electric
Equipment
(kWh)
0

October

Total

February

19928

5840

731

90

2358

March

16031

4698

842

98

2709

April

6208

1819

598

57

1905

May

1574

461

804

34

2480

June

36

11

712

2134

July

169

73

August

19

564

1563

920

270

805

23

2478

5523

1619

786

69

2480

15089

4422

735

86

2363

September
October
November
December
Total

24359

7139

621

92

2022

117313

34381

8134

658

25045

Hourly Analysis Program v4.80

Page 1 of 1

Annual Component Costs - Base Case Design


HAP48 Example
UTC

10/22/2013
08:20AM

Air System Fans 10.5%


29.8% Lights
Cooling 12.2%

Heating 47.5%

1. Annual Costs
Annual Cost
($)
1,013

($/ft)
0.106

Percent of Total
(%)
10.5

Cooling

1,171

0.123

12.2

Heating

4,571

0.478

47.5

Pumps

0.000

0.0

Heat Rejection Fans

0.000

0.0

Component
Air System Fans

HVAC Sub-Total

6,755

0.707

70.2

2,869

0.300

29.8

Electric Equipment

0.000

0.0

Misc. Electric

0.000

0.0

0.000

0.0

2,869

0.300

29.8

Grand Total
9,624
1.007
Note: Cost per unit floor area is based on the gross building floor area.

100.0

Lights

Misc. Fuel Use


Non-HVAC Sub-Total

Gross Floor Area ........................................ 9559.0 ft


Conditioned Floor Area ............................... 9559.0 ft

Hourly Analysis Program v4.80

Page 1 of 4

Monthly Energy Use by Component - Base Case Design


HAP48 Example
UTC

10/22/2013
08:20AM

1. Monthly Energy Use by System Component


Component
Jan

Feb

Mar

Apr

May

Jun

Jul

Aug

Sep

Oct

Nov

Dec

Air System Fans (kWh)

873

821

940

655

838

714

169

566

827

855

821

714

70

198

1087

2326

618

1919

1727

566

140

Natural Gas (Therm)

Fuel Oil (na)

Propane (na)

Remote HW (na)

Remote Steam (na)

Remote CW (na)

8097

5840

4698

1819

461

11

270

1619

4422

7139

388

328

257

31

34

158

260

Fuel Oil (na)

Propane (na)

Remote HW (na)

Remote Steam (na)

Pumps (kWh)

Heat Rej. Fans (kWh)

Cooling
Electric (kWh)

Heating
Electric (kWh)
Natural Gas (Therm)

Lighting (kWh)

2480

2358

2709

1905

2480

2134

73

1563

2478

2480

2363

2022

Electric Eqpt. (kWh)

Misc. Electric (kWh)

Propane (na)

Remote HW (na)

Remote Steam (na)

Misc. Fuel
Natural Gas (Therm)

Hourly Analysis Program v4.80

Page 2 of 4

Billing Details - Electric - Base Case Design


HAP48 Example
UTC

10/22/2013
08:20AM

1. Component Charges
Billing
Period
Jan

Energy Charges Demand Charges


($)
($)
486
518

Customer
Charges
($)
40

Taxes
($)
0

Total Charge
($)
1,044

Feb

383

504

40

927

Mar

357

458

40

855

Apr

194

416

40

650

May

207

257

40

503

Jun

220

483

40

743

Jul

37

61

40

137

Aug

172

424

40

636

Sep

225

381

40

647

Oct

234

355

40

629

Nov

329

485

40

854

Dec

419

464

40

924

3,265

4,806

480

8,551

Total Charges
($)
1,044

Total
Consumption
(kWh)
11,450

Avg Price
($/kWh)
0.0912

927

9,020

0.1028

Mar

855

8,417

0.1016

Apr

650

4,577

0.1421

May

503

4,867

0.1034

Jun

743

5,184

0.1433

Totals
2. Totals
Billing
Period
Jan
Feb

Jul

137

860

0.1594

Aug

636

4,053

0.1569

Sep

647

5,302

0.1220

Oct

629

5,519

0.1140

Nov

854

7,746

0.1103

Dec

924

9,874

0.0935

8,551

76,871

0.1112

3. Consumption Totals
Billing
Peak
Period
(kWh)
Jan
0

Mid-Peak
(kWh)
0

Normal Peak
(kWh)
0

Off-Peak
(kWh)
0

Overall
(kWh)
11,450

Totals

Feb

9,020

Mar

8,417

Apr

4,577

May

4,867

Jun

5,184

Jul

860

Aug

4,053

Sep

5,302

Oct

5,519

Nov

7,746

Dec

9,874

Totals

76,871

Hourly Analysis Program v4.80

Page 3 of 4

Billing Details - Electric - Base Case Design


HAP48 Example
UTC

4. Billing Demands
Billing
Period
Jan

10/22/2013
08:20AM

Peak
(kW)
0.0

Mid-Peak
(kW)
0.0

Normal Peak
(kW)
0.0

Off-Peak
(kW)
0.0

Overall
(kW)
46.1

Feb

0.0

0.0

0.0

0.0

44.8

Mar

0.0

0.0

0.0

0.0

40.7

Apr

0.0

0.0

0.0

0.0

37.0

May

0.0

0.0

0.0

0.0

22.8

Jun

0.0

0.0

0.0

0.0

33.3

Jul

0.0

0.0

0.0

0.0

4.2

Aug

0.0

0.0

0.0

0.0

29.2

Sep

0.0

0.0

0.0

0.0

26.3

Oct

0.0

0.0

0.0

0.0

31.6

Nov

0.0

0.0

0.0

0.0

43.1

Dec

0.0

0.0

0.0

0.0

41.3

Peak
(kW)
0.0

Mid-Peak
(kW)
0.0

Normal Peak
(kW)
0.0

Off-Peak
(kW)
0.0

Overall
(kW)
46.1

Feb

0.0

0.0

0.0

0.0

44.8

Mar

0.0

0.0

0.0

0.0

40.7

Apr

0.0

0.0

0.0

0.0

37.0

May

0.0

0.0

0.0

0.0

22.8

Jun

0.0

0.0

0.0

0.0

33.3

Jul

0.0

0.0

0.0

0.0

4.2

Aug

0.0

0.0

0.0

0.0

29.2

Sep

0.0

0.0

0.0

0.0

26.3

Oct

0.0

0.0

0.0

0.0

31.6

Nov

0.0

0.0

0.0

0.0

43.1

Dec

0.0

0.0

0.0

0.0

41.3

Mid-Peak
(m/d/h)
n/a

Normal Peak
(m/d/h)
n/a

Off-Peak
(m/d/h)
n/a

Overall
(m/d/h)
1/31/0700
2/7/0700

5. Maximum Demands
Billing
Period
Jan

6. Time Of Maximum Demands


Billing
Peak
Period
(m/d/h)
Jan
n/a
Feb

n/a

n/a

n/a

n/a

Mar

n/a

n/a

n/a

n/a

3/7/0700

Apr

n/a

n/a

n/a

n/a

4/25/0700

May

n/a

n/a

n/a

n/a

5/5/1500

Jun

n/a

n/a

n/a

n/a

6/8/1400

Jul

n/a

n/a

n/a

n/a

7/9/1700

Aug

n/a

n/a

n/a

n/a

8/22/1700

Sep

n/a

n/a

n/a

n/a

9/6/1200

Oct

n/a

n/a

n/a

n/a

10/3/0700

Nov

n/a

n/a

n/a

n/a

11/28/0700

Dec

n/a

n/a

n/a

n/a

12/5/0700

Hourly Analysis Program v4.80

Page 4 of 4

You might also like