The VAV retrofit actuator

that is truly plug-n-play

A real drop-in replacement that is simple to install


The HM series actuator mounts in the same
location as the current actuator.
The existing 5 pin Molex connector plugs directly
into the replacement actuator while 24 VAC/DC
power is applied to the separate plenum rated
power cable.
The HM series actuator is designed to work seam-
lessly with the existing VAV controller without any
need for modifications to hardware or software.

Reliability
The HM series actuator
is based on Belimos new
generation platform
and brushless motor
technology. This means
torque is increased from
35 in-lbs to 45 in-lbs and
the actuator runtime
remains constant
independent of load.
Best of all these actuators
carry Belimos 5-year
warranty.

From Production Date

LMB24-HM and LMB24-10P-HM


The HM series of actuators are intended for retrofit of
LM24-M and LM24-10P-M actuators that have
reached the end of their service life. These actuators
are specifically designed as a drop-in replacement
without any alteration to the existing VAV system.
This means faster installation and instant commissioning without the need for a balancer or systems
integrator.

VAV retrofit actuator plug-n-play


performance and function.

24 VDC Co

WARN

Technical Data

24 VAC 20% 50/60 Hz


24 VDC 10%

Power consumption

1.5 W (0.2 W)

Transformer sizing

2 VA (Class 2 power source)

Electrical connection

5 pin male Molex connector (Control Signal)


18 GA, 2 Conductor Plenum rated cable for
power

Overload protection

Electronic throughout 0 to 95 rotation

Angle of rotation

Max. 95, adjust with mechanical stop

Torque

45 in-lb

21

Lin

INSTALLATION NOTES
3

Actuators may also be powered by 24 VDC

21

Provide overload protection and disconnect as required.

24 VDC Control of LMB24-HM (10P-HM)


WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it maybe
necessary to work with live electrical components. Have a qualified licensed electrician
or other individual who has been properly trained in handling live electrical components
perform these tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.

Position indication

Reflective visual indicator (snap-on)

Manual override

External push button

Running time

95 seconds, constant independent of load

Humidity

5 to 95% RH non-condensing (EN 60730-1)

Ambient temperature

-22F to +122F [-30C to +50C]

Line

Blk

-40F to +176F [-40C to +80C]

Volts

Red

Storage temperature
Housing
Housing material
Agency listings 3
Noise level
21

NEMA 1/ IP20
INSTALLATION
NOTES
UL94-5VA
cULus
Actuators
may also be powered by 24 VDC
<35dB(A)
Provide
overload protection and disconnect as required.

Servicing

Maintenance free

Quality standard

ISO 9001

Weight

1.1 lbs [0.5 Kg]

LMB24-10P-HM
Feedback

10 kW , 1 W potentiometer

Belimo Americas
USA, Latin America, and the Caribbean: www.belimo.us
Canada: www.belimo.ca
Brazil: www.belimo.com.br
Belimo Worldwide: www.belimo.com

24

Volt

21

24 VAC Transformer

3
Common
+ Hot
1
2

5 PIN
Molex
Connector

3
4

10 k

LMB24-HM (10P-HM)

PF_15 - 06/08 Subject to change. Belimo Aircontrols (USA), Inc.

Power supply

Live Electrical
During installa
necessary to w
or other individ
perform these
to live electrica