Technical Workshop

OLTC information for transformer manufacturers

How to select the suitable OLTC

MR Germany
Oliver Khne

Gnter Panzer

Maneesh Mandapathil

Area Sales Manager

Regional Sales Director

Order Processing

India, OEMs

Middle East, India, Africa

India

How to select the suitable OLTC

I.

Neutral End Application

II. Delta Application


1) At line end
2) At line end for two-column OLTC
3) In the center

III. Auto Transformer


IV. Additionally required project data
V. Summary

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 2

How to select the suitable OLTC

I. Neutral End Application

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 3

How to select the suitable OLTC


Step 1: Calculation of max. OLTC current & step voltage
Required transformer data

S = Power rating (MVA)


Number of phases

Example:
80 MVA
3

Vector group

YNyn0

U = Regulated voltage (kV)

230 kV

R = Regulation range (%)

+ 15 %

n = Number of steps

+ 12 steps

Umax = 264,5 kV
Umin = 195,5 kV

U st
Connection type

reversing

R U
n 3

1660V

I max

S
U min

236A
V III 250 Y not suitable! TD V, page 4

14 27 3W
Maschinenfabrik Reinhausen GmbH 2008

VV III 250 Y not suitable! TD VV, page 9


14.12.2011

Page 4

How to select the suitable OLTC


Step 2: Internal Insulation ( tap selector size selection)
2.1) Voltages during operation
Distance a:

Ua

Distance b:

Consider MR factor 2
TD M, page 20

Ub

R U
2
3
R
U
2

Ua
Ub

0.3 230kV
2
3
0.3
230kV
2

19.9kV
34.5kV

According to technical data book we select


tap selector size C

2.2) Voltages during transformer testing


To be provided by transformer manufacturer!
Example: You calculate:
a: 400 kVp / 90kVrms
b: 400 kVp / 90kVrms

According to technical data book we now need to go for


tap selector size D

M III 350 Y - ? / D -14 27 3W suitable!


VM III 350 Y - ? / D -14 27 3W suitable!
Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 5

How to select the suitable OLTC


Step 3: External Insulation ( OLTC voltage class selection)
3.1) Voltage during operation: Ub = 0
3.2) Voltages during transformer testing
insulation to ground (Distance f) TD M, page 19

= Neutral point insulation level (=HVN BIL)


Uniform Insulation

245 kV

Graded insulation

72.5 kV

123 kV

170 kV

To be provided by transformer manufacturer!


Example:

You specify HVN BIL: 550 kVp / 230kVrms


According to technical data book we need to go for Um = 123kV

TD M, page 6

M III 350 Y - 123 / D -14 27 3W suitable!


VM III 350 Y - 123 / D -14 27 3W suitable!
Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 6

How to select the suitable OLTC

II. Delta Application


Connection types

At line end

Maschinenfabrik Reinhausen GmbH 2008

in the center

14.12.2011

Page 7

How to select the suitable OLTC


Calculation of max. OLTC current & step voltage
Required transformer data

S = Power rating (MVA)


Number of phases
Vector group
U = Regulated voltage (kV)

Example:

120 MVA
3
Dyn11
Umax = 142.6 kV

132 kV

Umin = 121.4 kV

R = Regulation range (%)

+8%

n = Number of steps

+ 8 steps

U st
Connection type

reversing

R U
n

1320V

I max

S
U min 3

329.4 A
10 19 3W
Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 8

How to select the suitable OLTC


1) At line end
1.1) Voltages during operation

Insulation to ground (f)


& between phases (b):

Ub

U max

Ub

132kV 1.08 142.6kV

V III 350 D not suitable! TD V, page 4


Distance a:

VV III 400 D-145-10 19 3W


3x M I 351 -170/B-10 19 3W

Maschinenfabrik Reinhausen GmbH 2008

Ua

R
U
2

Ua

0.16
132kV 10.6kV
2

TD VV, page 5
TD M, page 6

14.12.2011

Page 9

How to select the suitable OLTC


1) At line end
1.2) Voltages during transformer testing
To be provided by transformer manufacturer!
Example: You calculate

a: 200 kVp / 50 kVrms


b & f: 650 kVp / 275 kVrms (as per IEC for U=132kV)

In line with technical data book we confirm selection of


VV III 400 D-145-10 19 3W

TD VV, page 5

3x M I 351 -170/B-10 19 3W

TD M, page 6

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 10

How to select the suitable OLTC


2) At line end (special connection for two-column OLTC)
2.1) Voltages during operation

Insulation to ground f: U b

Ub

132kV 1.08 142.6kV

Distance a:

Ua

R
U
2

Ua

0.16
132kV 10.6kV
2

Distance b:

Ub

R
U
2

Ub

0.16
132kV 10.6kV
2

b"

a"

U max

M III 350 K-170/B-10 19 3W

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 11

How to select the suitable OLTC


2) At line end (special connection for two-column OLTC)
2.2) Voltages during transformer testing
To be provided by transformer manufacturer!
Example: You calculate

a: 200 kVp / 50 kVrms


b"

b & f: 650 kVp / 275 kVrms (as per IEC for U=132kV)

a"

In line with technical data book we confirm selection of


M III 350 K-170/B-10 19 3W

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 12

How to select the suitable OLTC


3) In the center
3.1) Voltages during operation
Insulation to ground (f) and between phases (b):

Ub

U
2

Ub

132kV
2

Ua

0.16
132kV 10.6kV
2

0.08 132kV

76.6kV

Distance a:

Ua

R
U
2

VV III 400 D-145-10 19 3W

TD VV, page 5

3x M I 351 -123/B-10 19 3W

TD M, page 6

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 13

How to select the suitable OLTC


3) In the center
3.2) Voltages during transformer testing
To be provided by transformer manufacturer!
Example: You calculate

a: 200 kVp / 50 kVrms

b & f: 650 kVp / 275 kVrms (as per IEC for U=132kV)

According to technical data book we now need to go for Um =170 kV for M-type OLTC
VV III 400 D-145-10 19 3W
3x M I 351 -170/B-10 19 3W

Maschinenfabrik Reinhausen GmbH 2008

TD M, page 6

14.12.2011

Page 14

How to select the suitable OLTC

III. Auto Transformer


U1

U2

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 15

How to select the suitable OLTC


Step 1: Calculation of max. OLTC current & step voltage
Required transformer data

S = Power rating (MVA)


Number of phases

Example:
100 MVA
3

Vector group

YNa0d11

U1 = Regulated voltage (kV)

230 kV

Umax = 264.5 kV
Umin = 195.5 kV

U2 = Constant voltage (kV)

138 kV

R = Regulation range (%)

+ 15 %

n = Number of steps

+ 10 steps

U st
Connection type

reversing

R U
n 3

1992V

I max

S
U min

296A
V III 350 D not suitable!

12 23 3W
Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 16

How to select the suitable OLTC


Step 2: Internal Insulation ( tap selector size selection)
2.1) Voltages during operation

Example:

Distance a:

Ua

R
2

Distance b:

Ub

R
U
2

Consider MR factor 2

U
3

Ua

0.3 230kV
2
3

Ub

0.3
230kV
2

19.9kV
34.5kV

According to technical data book we select


- VV III 400 D TD VV, page 15
- M/VRC with tap selector size C TD M, page 20

2.2) Voltages during transformer testing


To be provided by transformer manufacturer!
Example: You calculate:
a: 400 kVp / 90kVrms
b: 400 kVp / 90kVrms

According to technical data book


- VV III 400 D is no longer suitable!
- We now need to go for M/VRC with tap selector size D

3x M I 351 - ? / D -12 23 3W suitable!


3x VRC I 401 - ? / D - 12 23 3W suitable!
Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 17

How to select the suitable OLTC


Step 3: External Insulation ( OLTC voltage class selection)
3.1) Voltages during operation
Refer to MR document EV1104

EV1104

U1

U1

U2

Connection as per figure 2a

Maschinenfabrik Reinhausen GmbH 2008

U2

Connection as per figure 2b

14.12.2011

Page 18

How to select the suitable OLTC

TD M, page 6
TD VRC, page 15
Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 19

How to select the suitable OLTC


Step 3: External Insulation ( OLTC voltage class selection)

3x M I 351 - 300 / D -12 23 3W


3x VRC I 401 - 245 / D - 12 23 3W
Maschinenfabrik Reinhausen GmbH 2008

3x M I 351 - 170 / D -12 23 3W


3x VRC I 401 - 170 / D - 12 23 3W
14.12.2011

Page 20

How to select the suitable OLTC


Step 3: External Insulation ( OLTC voltage class selection)
3.2) Voltages during transformer testing
To be provided by transformer manufacturer!
Example: You specify

insulation to ground f: 650 kVp / 275 kVrms (as per IEC for U=138kV)
In line with technical data book we confirm selection of
3x M I 351 - 300 / D -12 23 3W
for connection as per figure 2a

3x VRC I 401 - 245 / D - 12 23 3W

3x M I 351 - 170 / D -12 23 3W


3x VRC I 401 - 170 / D - 12 23 3W

Maschinenfabrik Reinhausen GmbH 2008

for connection as per figure 2b

14.12.2011

Page 21

How to select the suitable OLTC


Additionally required project data
Example:

- Name of the end customer

KPLC

- country of transformer installation

Kenya

- end customer specification


Enables MR to add end-customer specific accessories

KPLC schematic

Transformer manufacturers benefits:


- Drawings & schematics are already in line with end custumer requirements

- Price is more representative (Quoted price comes very close to final price in case of order)

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 22

Summary: Required information


- Power rating (MVA)
- Number of phases (Single- or Three-Phase?)
- Vector group
- Regulated Voltage (kV)
- Regulating range (%)
- Number of steps
- Connection type (linear, reversing, coarse/fine?)
- In case of Delta connection: Regulation at line end or in center?
- In case of auto transformer: Constant voltage (kV)
- OLTC voltage stresses during transformer testing, for example in case of Neutral End
application: BIL (OLTC)

- Name of the end customer & country of transformer installation


- Only OLTC prices required or also the enclosures (dimension drawings, schematics etc.)?

Maschinenfabrik Reinhausen GmbH 2008

14.12.2011

Page 23