Professional Documents
Culture Documents
GS 112-11
August 1993
Document Title
DC POWER SUPPLIES
(Replaces BP Standard 228)
APPLICABILITY
Regional Applicability:
International
AMENDMENTS
Amd
Date
Page(s)
Description
___________________________________________________________________
CONTENTS
Section
Page
FOREWORD .................................................................................................................. ii
1. SCOPE....................................................................................................................... 1
2. DUTY REQUIREMENTS ........................................................................................ 1
2.1 Service Life...................................................................................................... 1
2.2 Ambient Conditions ......................................................................................... 1
2.3 Quality Assurance ............................................................................................ 1
3. ELECTRICAL REQUIREMENTS.......................................................................... 2
3.1 AC Power Supplies .......................................................................................... 2
3.2 DC Output Voltage.......................................................................................... 2
3.3 Rating and Duty............................................................................................... 2
3.4 Battery............................................................................................................. 3
3.5 Battery Charger ............................................................................................... 3
4. EQUIPMENT ARRANGEMENT AND OPERATION .......................................... 4
4.1 Configuration................................................................................................... 4
4.2 Parallel Operation ............................................................................................ 5
4.3 Isolation........................................................................................................... 5
4.4 Protection ........................................................................................................ 5
4.5 System Earth.................................................................................................... 6
4.6 Alarms ............................................................................................................. 6
4.7 Instrumentation................................................................................................ 6
4.8 Maintenance..................................................................................................... 7
5. CONSTRUCTION .................................................................................................... 7
5.1 Enclosures ....................................................................................................... 7
5.2 Forced Ventilation ........................................................................................... 8
5.3 Components..................................................................................................... 8
5.4 Earthing ........................................................................................................... 10
5.5 Nameplate, Labels and Marking ....................................................................... 11
6. TESTING .................................................................................................................. 11
6.2 Type Tests ....................................................................................................... 12
6.3 Routine Tests................................................................................................... 13
6.4 Test Certificates ............................................................................................... 13
7. ADDITIONAL REQUIREMENTS .......................................................................... 13
APPENDIX A.................................................................................................................. 21
DEFINITIONS...................................................................................................... 21
APPENDIX B.................................................................................................................. 22
LIST OF REFERENCED DOCUMENTS ............................................................. 22
GS 112-11
DC POWER SUPPLIES
PAGE i
FOREWORD
Introduction to BP Group Recommended Practices and Specifications for Engineering
The Introductory Volume contains a series of documents that provide an introduction to the
BP Group Recommended Practices and Specifications for Engineering (RPSEs). In
particular, the 'General Foreword' sets out the philosophy of the RPSEs. Other documents in
the Introductory Volume provide general guidance on using the RPSEs and background
information to Engineering Standards in BP. There are also recommendations for specific
definitions and requirements.
Value of this Guidance for Specification
BP is increasingly seeking to purchase equipment which is to a manufacturer's normal
standard whilst being entirely suitable for the application which BP has in mind. This
document seeks to allow a dialogue to be set up between the purchaser and the supplier so
that both are fully aware of the others requirements and capabilities and an entirely suitable
equipment will result by the use of this Specification. It therefore supplies guidance, based
upon past experience, as to those characteristics which require careful thought if an
optimum arrangement is to result.
Application
This Guidance for Specification is intended to guide the purchaser in the use or creation of a
fit-for-purpose specification for enquiry or purchasing activity.
Text in italics is Commentary. Commentary provides background information which supports
the requirements of the Specification, and may discuss alternative options. It also gives
guidance on the implementation of any 'Specification' or 'Approval' actions; specific actions
are indicated by an asterisk (*) preceding a paragraph number.
This document may refer to certain local, national or international regulations but the
responsibility to ensure compliance with legislation and any other statutory requirements lies
with the user. The user should adapt or supplement this document to ensure compliance for
the specific application.
Specification Ready for Application
A Specification (BP Spec 112-11) is available which may be suitable for enquiry or purchasing
without modification. It is derived from this BP Group Guidance for Specification by
retaining the technical body unaltered but omitting all commentary, omitting the data page
and inserting a modified Foreword.
GS 112-11
DC POWER SUPPLIES
PAGE ii
GS 112-11
DC POWER SUPPLIES
PAGE iii
1.
SCOPE
This Specification gives BP requirements for d.c. power supply systems comprising
battery charger, batteries and d.c. distribution board.
This Specification does not apply to stabilised d.c. power supply systems which do not
incorporate rechargeable battery systems.
2.
DUTY REQUIREMENTS
2.1
Service Life
All components, excluding batteries, used in the d.c. power supplies
system shall be designed for a 20 year life under the specified operating
conditions.
A specified 20 year service life is standard industry practice and manufacturers
equipment will be designed to achieve this. However, thought should be given to
any operator specified deviation.
2.2
Ambient Conditions
The equipment, which will be located indoors, shall be suitable for
continuous rated duty under the ambient conditions specified.
The ambient conditions must be defined on the data sheets.
Any special conditions must be identified and manufacturers consulted to ascertain
if any special features need to be included to cater for such special conditions.
Batteries should normally be rated such that the specified duties can be met under
all defined conditions. However, if very low ambient conditions are specified then
in order to meet the necessary discharge duty very large batteries may be required.
Careful thought and specification are required in defining the load and ambient
conditions which will actually be encountered.
2.3
Quality Assurance
Verification of the vendor's quality system is normally part of the pre-qualification
procedure, and is therefore not specified in the core text of this specification. If
this is not the case, clauses should be inserted to require the vendor to operate and
be prepared to demonstrate the quality system to the purchaser. The quality system
should ensure that the technical and QA requirements specified in the enquiry and
purchase documents are applied to all materials, equipment and services provided
by sub-contractors and to any free issue materials.
Further suggestions may be found in the BP Group RPSEs Introductory Volume
GS 112-11
DC POWER SUPPLIES
PAGE 1
3.
ELECTRICAL REQUIREMENTS
3.1
AC Power Supplies
Unless otherwise specified on the Data Sheet incoming power supplies
will be fuse protected 3 phase, 4 wire with a solidly earthed neutral.
Consultations with manufacturers should be held at an early stage to ascertain the
standard power input parameters for the apparatus and these should be specified
whenever practicable so that a standard design results.
Full tolerance limits of the supply should be included on the data sheets including
any transient variations caused by frequent motor starting or similar system
switching duties.
3.2
DC Output Voltage
3.2.1
The d.c. output voltage of the system, measured at the d.c. distribution
board, shall be within the limits specified on the Data Sheets for all
conditions of d.c. load, battery charge and discharge.
Early consultations with the users of the d.c. supply should be held to ascertain the
voltage tolerance required. This is especially critical for 24 V systems where a
small undervoltage tolerance will lead to extremely large battery capacity.
Tolerance limits of +10% -20% will provide a reasonably economic system.
3.2.2
The d.c. output voltage ripple shall be less than 5% rms. total harmonic
distortion.
3.2.3
Radio interference of the d.c. power supplies system shall be within the
limits specified in BS 800 or similar local standard.
3.3
3.3.1
The rated load, with the exception of that for switchgear duty, shall be
taken as 110% of the continuous load plus a due allowance for
intermittent load.
It is useful to produce a load profile in block form to enable the manufacturer to
more accurately size the batteries for the system.
3.3.2
The rated load and duty for switchgear application shall be determined
from the switchgear manufacturers requirements.
The items required from the switchgear manufacturer are standing loads (due
account being taken of loads associated with protection relays), trip coil
consumption and closing coil/closing motor requirements.
A load profile should be compiled for the worst anticipated sequences of closing
and tripping assuming that the charger is not working. Such a profile should take
GS 112-11
DC POWER SUPPLIES
PAGE 2
into account the operating experience obtained at the site where the equipment is to
be installed.
A typical profile would be standing load supplied at all times for a 4 hour period
during which there is a simultaneous trip of all breakers, sequential closing of each
circuit breaker with inter-sequence pauses no greater than 2 seconds until all
circuit breakers are closed, simultaneous trip of 50% of breakers and then a
simultaneous trip of the remaining breakers.
3.4
Battery
3.4.1
Each battery shall have sufficient capacity to supply 100% of the design
load for the full specified standby time with no charger available, whilst
maintaining the d.c. voltage measured at the distribution switchboard,
within the tolerances specified.
3.4.2
3.4.3
3.4.4
3.5
Battery Charger
3.5.1
3.5.2
3.5.3
GS 112-11
DC POWER SUPPLIES
PAGE 3
within the period specified in the Data Sheet taking into account the
specified electrolyte topping up interval.
Consideration should be given to the time period over which the normal charge
rate provides sufficient battery capacity for the required duty. This should be
chosen to provide an acceptable balance between operational requirements and
excessive battery capacity. A period of 12 hours will normally produce an
oversized battery. A longer period is recommended.
When necessary the manufacturer may provide two levels of normal charging, to
achieve the required performance:Float:
Recharge:
3.5.4
Where sealed batteries are specified the charger shall be provided with
automatic charge variation to compensate for changes in the batteries
ambient temperature.
3.5.5
Fast charging shall be provided for battery types that are suitable.
Fast charging is not required for sealed batteries.
Fast charging should be undertaken off line if possible. On line fast charging is not
recommended as it requires devices to be built in to maintain output voltage
tolerances during fast charge.
Where fast charging is specified it should be capable of providing full battery
capacity in 7 hours from an end-of-standby discharge state.
Where off-line fast charging is specified for systems employing two or more
battery/charger sets in parallel, the equipment under fast charge shall be
automatically reconnected to the d.c.distribution board at the completion of
charge, or if any failure to the on-line equipment occurs. When automatically
reconnected, the battery shall revert to the 'normal' charge.
4.
Configuration
The system configuration shall comply with the Schematic Diagram
shown on the Data Sheets. Where cable interconnections are required
between component parts of the system these shall be specified and
supplied by the manufacturer, complete with all associated installation
materials.
GS 112-11
DC POWER SUPPLIES
PAGE 4
Where battery and charger are not a continuous suite the cable route lengths must
be shown on the schematic diagram. The equipment manufacturer is then required
to provide the inter-connecting cables so as to ensure that the overall system
complies fully with the specification, especially in connection with output voltage
tolerances.
4.2
Parallel Operation
Where more than one identical battery/charger system is specified, it
shall be arranged that each battery/charger system equally shares the
load on the distribution switchboard.
Each charger and its associated battery shall be capable of operating as a separate
unit in any charging mode.
When chargers are specified to be capable of supplying the design load with the
battery disconnected they shall maintain the output voltage within the tolerances
specified.
4.3
Isolation
Equipment and components shall be arranged in compartments, such
that discrete parts of the system can be isolated under full load
conditions and made safe for maintenance work to be undertaken with
the remainder of the apparatus in service.
The recommended minimum requirement is isolation of all poles, including any
neutrals, of:-
4.4
(a)
(b)
(c)
(d)
(e)
Protection
Protection systems shall be arranged to provide perfect discrimination
throughout the system including the source of supply.
Fuse protection throughout is the preferred method of protection.
Where charger short-circuit current is limited below the fuse or other protection
device operating point, by a charger current limit feature, the manufacturer shall
ensure that the equipment is undamaged by continuous operation in this mode and
that an alarm is given.
GS 112-11
DC POWER SUPPLIES
PAGE 5
4.5
System Earth
The d.c. supply system shall be earthed as specified on the Data Sheets.
Where an earth fault monitoring system is specified (unearthed d.c. systems) it shall
circulate 1 mA or less through an earth fault unless the detection circuit
disconnects the earth current flow directly after detection.
Consideration should be given to providing a test facility (where earth fault
monitoring is specified) in order to locate the fault to an individual circuit.
Provision of a fully rated duplicate busbar for this in order to avoid disruption to
operation is not recommended.
4.6
Alarms
4.6.1
Alarms shall be provided for failures that affect the integrity of the
battery/charger/distribution board system. Such alarms shall not be
initiated because of transient conditions.
The minimum recommended local alarms to be provided are:(a)
(b)
(c)
(d)
(e)
4.6.2
4.6.3
4.7
Instrumentation
Means shall be provided to give indication of the main electrical input
and output parameters.
It is recommended that incoming supply volts and amps are metered and that
selector switches are fitted to permit readings in all phases. Battery
charge/discharge should be indicated by a centre zero ammeter. Output current
and busbar voltage meters should be fitted.
GS 112-11
DC POWER SUPPLIES
PAGE 6
Lamp colours should be in accordance with IEC 73. Lamp test facilities to allow
testing of all lamps during normal operation are recommended.
Consideration should be given to including a control/indication mimic with LED
indication or liquid crystal display, in place of the standard type of indicating lamp
arrangement.
4.8
Maintenance
4.8.1
The system and its component parts, with the exception of batteries and
ventilation air filters, shall be designed such that they can operate,
without maintenance, for at least 104 weeks continuously.
Where manning levels are restricted, consideration should be given to including a
battery cell monitoring system.
Where air filters or batteries require maintenance the system shall be so designed
that they can be serviced in safety with no effect on the system other than
disconnection of the batteries.
4.8.2
4.8.3
5.
CONSTRUCTION
5.1
Enclosures
5.1.1
Sheet steel enclosures shall be provided for all component parts of the
system, other than batteries, and these should form a uniform matching
suite. The overall degree of protection of the suite shall be a minimum
of IP 22 to IEC 529. The degree of protection between cubicles
installed as a suite shall be to a minimum of IP 20 to IEC 529.
GS 112-11
DC POWER SUPPLIES
PAGE 7
5.1.2
5.1.3
Gland plates shall be provided for cables of the types and sizes specified
on the Data Sheets, entering from the direction specified. Where cables
enter from below, the gland plate shall be at least 400 mm above floor
level.
Where a cubicle containing sealed batteries forms part of a suite advice should be
taken on the necessity of making through connections from the battery cubicle to
the charger cubicle and/or distribution board cubicle, gas tight.
5.2
Forced Ventilation
Power supplies for ventilation equipment shall be derived from the main
incoming power supply, not an auxiliary supply.
5.3
Components
5.3.1
5.3.2
5.3.3
Fuses shall comply with IEC 269-1 and 2. Fuse holders shall be selfcoloured black. Link holders shall be self-coloured white. All
unearthed poles of supplies shall be fused. Earthed poles shall be
connected by a link holder.
5.3.4
GS 112-11
DC POWER SUPPLIES
PAGE 8
5.3.5
5.3.6
Indicating lamps shall be flush mounting and shall have a life of not less
than 10,000 hours with the operating voltage at its maximum tolerance.
5.3.7
5.3.8
5.3.9
5.3.10
Insulation
Colour
Black
Grey
Green/Yellow
Orange
GS 112-11
DC POWER SUPPLIES
Identification
Ferrule Colour
Phases-Red, Yellow,
Blue Neutral - None
None
None
None
PAGE 9
Size of internal wiring should be based on the duty. Minimum preferred size is 1.0
mm2 but smaller sizes can be utilised for electronic/PC type applications.
Wiring across door hinges should be protected against mechanical damage
preferably by the use of flexible conduit.
It is advisable to keep wires operating at different voltages physically separated,
input cables to an enclosure should not be run in close proximity to internal or
output cables.
The method of connecting internal wiring to components should be in accordance
with the recommendations made by the component manufacturers.
5.3.11
5.3.12
5.4
Earthing
All metal work, cable gland plates and component or sub-assembly
chassis shall be bonded to the earth bar.
The earth bar shall be marked green/yellow and of minimum cross
section 70 mm2. It shall extend the length of the suite. Joints shall be
provided between each transport section. At each end of the earth bar,
a size M12 brass terminal shall be provided fitted with a lug or a 70
mm2 copper external protective conductor.
GS 112-11
DC POWER SUPPLIES
PAGE 10
5.5
5.5.1
Item Number
Cooling Method
Date of Order
Order Placed By
6.
TESTING
6.1
GS 112-11
DC POWER SUPPLIES
PAGE 11
It is not usual to perform the tests with the order battery and this is not
recommended.
It is recommended that tests should be carried out covering all modes of operation
and should demonstrate that the equipment performs in accordance with the
specification.
A schedule of tests should be submitted with the tender for approval by the
purchaser.
6.2
Type Tests
Type tests as detailed in IEC 146-1-1 clause 4.1.4 shall be applied to at
least one complete apparatus of each type or design. Additionally, the
following type tests shall be included:(a)
(b)
Load Tests
The load test shall allow for the gradual increase of load from
no load to full load, followed by in sequence:-
Checking the Co-ordination of Protective Devices (as IEC 1461-1, clause 4.2.10)
Short circuit faults shall be simulated at the following points of
the complete system:(i)
(ii)
GS 112-11
DC POWER SUPPLIES
PAGE 12
Routine Tests
The following routine tests shall be applied on each complete
apparatus:(a)
(b)
6.4
Test Certificates
The manufacturer shall provide certificates for all tests undertaken
whether or not witnessed by a purchasers representative. The
certificates shall state values for all test results where appropriate.
Certificates for tests witnessed by the manufacturers representative
shall be available for signature by the representative on the day of the
test.
7.
ADDITIONAL REQUIREMENTS
7.1
7.2
Drawing symbols shall comply with IEC 617. Each drawing supplied
by the manufacturer shall incorporate the following information:Manufacturer's name and address
Drawing title
Name of project
Manufacturer's order or contract number
Purchaser's order number
Manufacturer's drawing number and revision number
Date of original issue and dates of any revisions with details.
GS 112-11
DC POWER SUPPLIES
PAGE 13
7.3
7.4
7.5
7.6
7.7
GS 112-11
DC POWER SUPPLIES
PAGE 14
A.
1.
2.
3.
4.
5.
Installation Site
Job name/Job No
Equipment name
Order No
Item No
B.
SUPPLY
6.
7.
8.
9.
10.
V
pH
+
+
Power
Hz
Wire
%
%
Control
Type
No of cores
Conductor Cu/A1
Core size mm2
11. Fault level of supply switchboard
C.
ENVIRONMENT
C
C
C
Under 1000 m
REMARKS
No Date
Remarks
By
GS 112-11
DC POWER SUPPLIES
App
PAGE 15
D.
PERFORMANCE
E.
V
+
Required
%
%
Not required
mins
ARRANGEMENT
Duplicate 100%
capacity
batteries
No
Reduced rate
parallel
connected high
security battery
On-line
Single battery
Off-line
52 weeks
12 hours
Allowed
Not allowed
Unearthed
Positive pole
Mid-point
No
Yes
(a) Battery electrolyte
low
(b) Ventilation
equipment fail
(c) Normal/standby
supply fail
(d) d.c. output circuit fail
No
Yes
Group 1
Alarm
groupings
Group 2
Fuses
REMARKS
No Date
Remarks
By
GS 112-11
DC POWER SUPPLIES
App
PAGE 16
F.
CONSTRUCTION
Vented
Lead acid
Nickel cadmium
Top
Top
Front only
Yes
Supply cables
d.c. cables
33.
34.
35.
36.
37.
38.
Cubicle access
Batteries to be housed cubicles
Battery room layout drawing
Drip trays
Language for labels
Cell condition for despatch
G.
DESIGN LOADS
Sealed
Tubular
Pocket plate
Plante
Sintered
Bottom
Bottom
Front and rear
No
Required
Not required
Charged
Dry
Starting
A
Secs
Running
A
Secs
Cycles/
hour
for
secs
Ccts
for
secs
REMARKS
No Date
Remarks
By
GS 112-11
DC POWER SUPPLIES
App
PAGE 17
H.
CIRCUITS
Cct Name
Max load
A
Cable type
Cable size
mm2
Not equipped
Max load
A
REMARKS
No Date
Remarks
By
GS 112-11
DC POWER SUPPLIES
App
PAGE 18
I.
SCHEMATIC DIAGRAM
(For a non-continuous suite, cable route lengths between items of equipment
should be indicated).
REMARKS
No Date
Remarks
By
GS 112-11
DC POWER SUPPLIES
App
PAGE 19
55.
56.
57.
58.
59.
Charger
Battery
Manufacturers tender ref.
Manufacturers works order no
No of cells per battery
Cell capacity
Total battery internal resistance
Battery capacity prior to duty specified
Battery terminal voltage following duty
specified
Charger rating/Duty Class (IEC 146-1-1
clause 3.10.3.5)
Current cut-off level
Manufacturers recommended supply
fuse rating (to IEC 269)
(Fuse to be supplied by purchaser)
Normal output voltage (Float/Recharge)
Fast charge voltage
Max heat dissipation of equipment
Estimated max temperature in:
Charger/d.c. distribution/battery
Maximum
Fundamental
a.c. supply
Harmonic
current
Value % of fundamental
C at
ohms at
hour rate
%
V
A. D.C/duty class
A D.C.
A
V D.C.
V D.C.
watts
C
C
A
REMARKS
No Date
Remarks
By
GS 112-11
DC POWER SUPPLIES
App
PAGE 20
APPENDIX A
DEFINITIONS
Definitions
Standardised definitions may be found in the BP Group RPSEs Introductory Volume.
GS 112-11
DC POWER SUPPLIES
PAGE 21
APPENDIX B
LIST OF REFERENCED DOCUMENTS
A reference invokes the latest published issue or amendment unless stated otherwise.
Referenced standards may be replaced by equivalent standards that are internationally or
otherwise recognised provided that it can be shown to the satisfaction of the purchaser's
professional engineer that they meet or exceed the requirements of the referenced standards.
Where a British Standard only is listed, no corresponding IEC Standard exists.
IEC 51
IEC 73
IEC 76
Power transformers.
IEC 146
Semiconductor convertors.
IEC 228
IEC 269
Low-voltage fuses.
IEC 289
Reactors.
IEC 408
IEC 417
IEC 529
IEC 617
Graphical symbols.
IEC 947
British Standards
BS 800
BS 6231
GS 112-11
DC POWER SUPPLIES
PAGE 22
BS 9000
GS 112-11
DC POWER SUPPLIES
PAGE 23