You are on page 1of 8

COMPLIANCE STATEMENT

Project Name : Centro Riyadh

No.
PART 2
PRODUCTS

Spec.

Compliance

- The Contractor shall supply and


install factory assembled air cooled
packaged cooling only chiller. The
number and capacity of which shall
be as indicated in the capacity
schedule shown on the drawings.
- Each machine shall consist of at
least two accessible hermetic direct
drive screw compressors air-cooled
condenser, evaporator,
interconnecting refrigerant piping,
controls, safety devices, accessories,
and control power transformer as
applicable to limit control
voltage to 240 volts maximum. No
phase to neutral voltage shall be
required. Each compressor shall have
its independent circuit, evaporator,
condenser, microprocessor based
controls and a unit mounted motor
starter.
- The machine shall be completely
charged at the factory with
refrigerant R 134a. If a different
refrigerant has to be selected, it
should contain no CFC and shall be
subject to engineer approval. All
factory wiring and piping shall be
contained within the machine
enclosure. All electrical components
shall be protected from the weather.
- The refrigerant circuit components
shall include hot gas muffler, high
side pressure relief valve, liquid line
shut off valve filter drier, liquid line
sight glass, liquid line solenoid valve
and thermal expansion valve.
- Each machine shall be enclosed in a
sound attenuating, galvanized steel
casing, zinc phosphatized, with
corrosion resistant finish, and shall
be mounted on spring type vibration
isolators. Unit shall have primary
coating and an .acrylic weather proof

Noted (By
contractor)

Note

2.01
SCREW TYPE
CHILLERS

A. General

Comply

Comply

Comply with
note

Hot Gas muffler is not


required with screw
compressor according to
LG std

Comply with
note

The unit is open from the


upper half, with
protection grill, and
louvered panels are
applied on the lower part.
Spring vibration isolators
shall be supplied optional

Page 1 of 8

COMPLIANCE STATEMENT
paint.
- Each machine shall be capable of
operating satisfactorily at low
outdoor air temperatures.
- The manufacturer shall perform all
field testing, balancing and final
adjustment of the refrigeration
machines in accordance with the
applicable provisions of the relevant
ASHRAE Standards.
- The following data shall be
compiled and certified:
Temperature of chilled water "In
and Out".
Chilled Water flow (gpm).
Pressure drop in chiller (Feet of
Water).
Operating power consumption from
measured voltage, amperes and
power factor.
- Any part of the machines or system
failing to meet the contract
requirements shall be adjusted,
repaired or replaced
- Each chiller shall have protection
grills.
- Each packaged unit shall be factory
equipped to connect to only one
electrical power feeder with the
necessary built-in circuit breakers,
and one main disconnect switch.
Disconnect switch shall be accessible
from outside the chiller without
opening the panel door.
- Each packaged unit shall be
supplied with spring type vibration
isolators flexible enough to dampen
any vibrations supplied by chiller
manufacturer
- Each chiller shall have sound proof
enclosure on compressor and
condenser fan to maintain noise level
of 45 DB on roof. Condenser fan
shall be of the low RPM type.
Sound proof enclosure shall be
factory assembled and designed.
- Each packaged unit shall have a
microprocessor control unit to
provide all the control and safety
functions of the chiller with main
circuit breaker for each chiller.
- A multi-step sequence controller
factory designed and assembled to
satisfy the multiple operation of the

Comply with
Note

and installed by others


Lowest temperature of
operation shall be
specified

Comply

Comply

Noted

Please refer to LG Chiller


PDB

Comply

Comply with
Note

Below parts is optional


- Single point power
connection
- NFB
- Disconnect switch

Noted
(Optional)

Vibration isolators shall


be supplied optional and
installed by others

Comply with
Note

Compressor sound
proffering by acoustic
blanket, condenser fan
enclosure is not available
Sound Level: 79dB(A)
at 1 M

Comply

Comply

Page 2 of 8

COMPLIANCE STATEMENT

B. Compressor

chillers, shall be supplied for all the


chillers.
- Chiller shall be connected to
building management system with
pumps and all other equipment as
indicated in electrical drawings.
- The compressor shall be of the
accessible hermetic screw
compressor direct drive with sound
proof enclosure.

- The compressor shall have


separately housed pressure lubricated
rolling element bearing groups at
each end of both rotors.
- The compressor shall have fully
modulating capacity control by use
of a slide valve in the rotor section of
the compressors positioned by
hydraulic action.
- The compressor shall have squirrel
cage two pole induction motor,
suction gas cooled
- Compressor shall be provided with
oil separator and filtration devices
- The compressor shall have sound
attenuating enclosure.
- Motor and starter shall be in
accordance with the requirements of
these specifications regarding
Electrical Equipment.
- Each compressor shall be equipped
with the following controls and
instruments and their respective
connections:
- Part winding starters.
- Built-in automatic unloading
capacity control unloaded starting.
- High and low pressure cutout with
manual reset for the high pressure cut
out and automatic reset for the low
pressure cutout.
- Oil pressure failure cut out with
manual reset.
- Suction and discharge refrigerant
pressure gauges.
- Oil pressure gauge.
- The gauges shall comply with these
specifications regarding instruments.
- The compressor shall have hot gas
discharge muffler and liquid line
sight glass and filter drier all as
recommended by the manufacturer.

Comply

Modbus interface is std,


BACnet is optional

Comply

Acoustic enclosure is
optional
- semi-hermetic screw
compressor Standard
starting : Y-D
Optional starting : DOL

Comply

Comply (25%100%)
Comply
Comply
Comply

Optional

Noted

Specs shall be provided

Not Comply
Ok
OK

NA
Ok
Oil differential
pressure switch
Noted

Specs shall be provided

Noted

According to LG std

Page 3 of 8

COMPLIANCE STATEMENT
C. Evaporator

D. Air-Cooled
Condenser

- The evaporator shall be of the direct


expansion shell-and-tube type, with
removable heads.
- The shell shall be constructed and
tested in accordance with ASME
Code for Unfired Pressure Vessels.
- The tubes shall be made of
seamless copper tubes of the
individually replaceable type.
Support sheets shall be provided to
prevent sagging of the tubes.
- The shell shall be completely
insulated with 2"(50mm) thick
urethane foam insulation covered
with a sheet steel jacket.
- The shell shall be provided with an
electric heater cable under the
insulation.
- The evaporator shall be supplied
with the following controls and
instruments and their
respective connections:
- Liquid line solenoid shut-off
valve(s) and strainer(s).
- Thermostatic expansion valve(s).
- Control thermostat.
- Low limit thermostat (Freeze
protection).
- Thermometer to measure the
refrigerant gas temperature.
- Thermometers (well type) at the
chilled water inlet and outlet.
- Pressure gauge to measure the
refrigerant pressure.
- The Condenser shall be air-cooled,
upward air discharge type.
- The condenser coil shall be made of
seamless copper tubes, with
aluminum fins mechanically bonded
to the tubes with anti corrosion paint
similar to herisite coating or
approved equal.
- The condenser shall have an
integral subcooler.
- The condenser fans shall be of the
propeller type, constructed of
corrosion resistant blades such as
heavy gauge aluminum. The fan and
drive shall be held in proper
alignment. Fan assemblies shall be
provided with heavy gauge, close
mesh, electro- galvanized fan guards.
- Fan motors shall be drip-proof type,
with built-in over load protection,
and starting contactors. Motors shall
be mounted on vibration isolators,

Comply
Comply to GB
std
Comply

Comply with
note

Std insulation : 19mm,


optional : 38 mm

NA

OK
OK
OK
OK

Electronic EXV

Ok
Ok
OK
Comply
Comply with
note

The Aluminum fins are


pre-treated with
polyurethane coating

Comply
Comply

Fan materials : Plastic

Comply with
note

Not mounted on vibration


isolators

Page 4 of 8

COMPLIANCE STATEMENT

E. Starter Panel

F. Control
Panel

and provided with lubricated ball


bearings.
Chiller shall include a starter panel
containing motor starter, disconnect
switches with fuses, 3 phase current
transformer for motor overload
protection.
Control panel shall be a
microprocessor unit control module
that provides all the control and
safety functions including startup and
shut down, leaving chilled water
control, compressor and electronic
expansion valve modulation, fans
sequencing, anti-recycle logic,
automatic lead/lag compressor
starting and load limiting. Unit
protective functions shall include
loss of chilled water flow, evaporator
freezing, loss of refrigerant, low and
high refrigerant pressure, reverse
rotation, compressor starting and
running over current, phase loss,
phase unbalance, phase reversal and
loss of oil flow. The unit shall
include a menu driven digital
display that indicate the chilled water
set point, current limit set point,
leaving chilled water temperature,
evaporator and condenser refrigerant
pressures and temperatures.
The control panel section shall
include high and low pressure
gauges.
Microprocessor shall be able to
equalize the number of starts and the
operating of each compressor in the
chiller and to alternative between
compressors to have equal running
hours and start ups.
The microprocessor shall be able to
display the following readings.
- Entering and leaving chilled water
temperature.
- Ambient air temperature.
- Evaporator and condensing
refrigerant temperatures and
pressures.
- Compressor suction temperature.
- Present RLA for each compressor.
- Present line voltage.
- Compressor starts and running
hours.
- Active set points:
Chilled water set point.
Current limit set point.

Comply with
note

Disconnect switches with


fuses is Optional

Comply with
notes

Phase unbalance NA
Loss of oil flow-NA
(Oil level is standard)

Comply with
note

Display at display board

Comply

Ok
Ok
Ok
Ok
Ok
Not comply
Ok
Ok
Ok
Page 5 of 8

COMPLIANCE STATEMENT

G. Chillers
Motor Control
Center

Low ambient lockout set point.


- Part failure diagnostics:
Water temperature sensors
Refrigerant temperature sensors
Compressor contactors.
- Over 90 diagnostic and operating
conditions.
The Contractor shall supply and
install the chillers sequence
controller in the chillers motor
control center (which is supplied
under the electrical section) and as
specified under this section of the
specifications.
- Controller
The controller shall serve all the
chillers primary pumps and
secondary pumps and shall be
of the electronic micro-processor
type.

Not comply

The controller shall be complete with


all the necessary interlocking
devices, and all necessary items
required for satisfactory operation of
the central chilled water system as
generally described herein below.

Ok

This controller shall be supplied in


addition to the individual control
panels of each chiller which is
factory assembled and wired and as
specified under the chiller
specifications.
- Operation Sequence
All the chillers shall be electrically
interlocked with the primary chilled
water pumps such that no chiller
shall operate unless the primary
pump have run for a pre-set time as
recommended by the manufacturer.
Besides, each chiller shall be
interlocked with its own flow
switched installed in the water
outlet of the evaporator in such a
way that the chiller stops
automatically when the switch fails
to sense water circulation through it.
The contractor shall produce a
schematic line diagram showing the
manual and automatic control system
described hereinafter and shall
submit this diagram to the Engineer
for approval.
The control and operating sequence
shall be as follows:

Ok
Ok
Ok
Ok
By contractor

Ok

Ok

OK

By contractor
Noted (Minor
differences may
Page 6 of 8

COMPLIANCE STATEMENT
The system shall be started manually
by placing the selector switch on
Auto.
A variation in the system load causes
the 2-way valves to modulate the
flow rate through the cooling coils.
The resulting variation in flow is
sensed by a flow switch and flow
meter within the bypass line that
connects the suctions of the primary
and secondary pumps. The direction
of flow and the flow rate within the
bypass indicates to the controller
whether the secondary circuit is
using more or less water than is
being produced by the primary
circuit.
In response, the controllers either
start or stop a set of primary pump
and chiller, necessary to balance the
production of the chilled water with
that used by the secondary circuit.
At the time each primary pump is
energized, a time delay relay is
energized which holds the chiller offthe line for approximately 10 sec (as
per manufacturer recommendation).
This delay permits water to circulate
through the evaporator and gives the
unit temperature controller time to
sense the existing system load
conditions. Consequently, when the
chiller is started, it comes on the line
at the stage, of loading needed to
balance the load.
This time lapse control scheme helps
prevent unnecessary chiller cycling.
Following the startup of a primary
pump and chiller, the temperature
controller of the individual chiller
assumes control. The active chillers
than balance out to maintain the
desired supply water temperature.
A reduced water flow rate within the
secondary circuit causes water to
bypass the secondary circuit. when
the flow exceeds 115 percent of the
flow rate of one primary pump. This
de-energizing primary pumps until
normal flow is restored within the
bypass.
Once normal flow is restored, the
step controller is stopped. It then
holds position until a new signal is
received.
The motor control center should
include sequencing switches. The

exist, please
refer to LG std
sequence of
operation)

Page 7 of 8

COMPLIANCE STATEMENT
purpose of these switches is to
alternate the starting sequence of the
chillers and the primary pumps to
equalize running time.
The flow meter shall be adjustable
type having a control range from 0 to
140% of one primary pump flow
rate. The design flow in the bypass
line is 115% of the primary pump
flow rate. However, this is theoretical
and may be improved by field
experience.
H. APPROVED - Trane.
MANUFACTU - York.
RERS
- Carrier
- Or approved Equal.

LG
MCAWXXXB
Series

Page 8 of 8

You might also like