You are on page 1of 9

GETCO / E / TS- MACC 2801 / R0 Dt.

26-10-2007

GUJARAT ENERGY TRANSMISSION


CORPORATION LTD.
SARADAR PATEL VIDYUT BHAVAN,
RACE COURSE, BARODA 390 007.

TECHNICAL SPECIFICATION
FOR

YARD LT AC DISTRIBUTION BOARD

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

Seal & Sign of Bidder

Page 1 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

SPECIAL INSTRUCTIONS TO BIDDER

Please read following instructions carefully before submitting your bid.

1.

All the drawings, i.e. elevation, side view, plan, cross sectional
view etc., in AutoCAD format and manuals in PDF format, for
offered item shall be submitted. Also the hard copies as per
specification shall be submitted.

2.

The bidder shall submit Quality Assurance Plan for manufacturing


process and Field Quality Plan with the technical bid.

3.

The bidder shall have to submit all the required type test reports
for the offered item. In absence of this, the evaluation shall be
carried out accordingly as non-submission of type test reports.

4.

The bidder must fill up all the point of GTP for offered item/s.
Instead of indicating refer drawing, or as per IS/IEC, the exact
value/s must be filled in.

5.

All the points other than GTP, which are asked to confirm in
technical specifications must be submitted separately with the bid.

6.

The bidder is required to impart training in view of manufacture,


assembly, erection, operation and maintenance for offered item,
at his works, to the person/s identified by GETCO, in the event of
an order, free of cost. The cost of logistics will be borne by
GETCO.

7.

Please note that the evaluation will be carried out on the strength
of content of bid only. No further correspondence will be made.

8.

The bidder shall bring out all the technical deviation/s only at the
specified annexure.

9.

The bidder should indicate manufacturing capacity by submitting latest


updated certificate of a Chartered Engineer (CE).

Seal & Sign of Bidder

Page 2 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

QUALIFYING REQUIREMENT DATA


(For Supply)
Bidder should satisfy the following requirements.

Sr.
No

1)

The bidder shall be Original Equipment Manufacturer


(OEM). The offered equipment have to be designed,
manufactured and tested as per relevant IS/IEC with latest
amendments.

2)

The minimum requirement of manufacturing capacity of


offered type, size and rating of equipment shall be 7 times
tender / bid quantity. The bidder should indicate
manufacturing capacity by submitting latest updated
certificate of a Chartered Engineer (CE).

3)

Equipment proposed shall be of similar or higher rating and


in service for a minimum period of THREE (3) years and
satisfactory performance certificate in respect of this is to
be available and submitted.

4)

The bidder should clearly indicate the quantity and Single


Value Contract executed during last FIVE (5) years, for the
offered equipment. Bidder should have executed one single
contract during last five years for the quantity equivalent to
tender / bid.
The details are to be submitted in following format,

ITEMS
SUPPLIED
TO

5)

ORDER
REFERENCE
No. & DATE

ITEMS

QUANTITY

ORDER
FULLY
EXECUTED.
YES/NO

STATUS, IF
ORDER
UNDER
EXECUTION

REMARK

Equipment offered shall have Type Test Certificates from


accredited laboratory (accredited based on ISO/IEC Guide
25 / 17025 or EN 45001 by the National accredition body of
the country where laboratory is located), as per IEC / IS /
technical specification, Type test reports shall not be older
than FIVE years and shall be valid up to the expiry of the
validity of the offer.

Seal & Sign of Bidder

Page 3 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

SPECIFICATIONS
FOR
YARD LT AC DISTRIBUTION BOARD
CONSTRUCTION:
The cubicle shall be constructed from good quality steel sheet. The
cubicle shall be robust in construction. The cubicle shall be made of steel
sheet of 2.0 mm size for all sides and 2.5 mm for bottom. It will be
reinforced by steel frame and shall be mechanically strong. It shall be
Outdoor, floor mounting, fixed standing type and naturally air-cooled type
designed for continuous operation in an ambient temperature of 50C.
Necessary phosphating treatment shall be given to the cubicle and shall
be painted with two coats of red oxide primer followed by a coat of gray
synthetic enamel paint, shed No. 631, IS: 05 on external side and on
internal side with glossy white colour.

The distribution board shall be of dust and vermin proof


construction and shall be provided with a degree of protection of IP:
55 as per IS 2147. The cubicle shall have minimum dimensions of
1200mm (H) (including base frame of the size 50 x 50 x 4) x 1000mm (W)
x 400mm (D) so that all the components shall be approached and replaced
easily. It will be provided with the front & rear side door with the handle
and handle lock. It should be possible to erect the cubicle side by side.
The replacement of the components and testing should be possible from
front and backside of cubicle. The cubicle shall be mounted on C Type
channel with opening for cable entry on rear side.
The cubicle shall be designed to receive two 31/2 core 50 mm2.
incoming armoured aluminum cables. One cable shall be used as Main
cables and other cable shall be used as standby. The punched holes shall
be provided for above cable entries. The dimensional drawing of the
cubicle with all mountings shall be furnished by the bidder. Necessary
cable glands shall be supplied with the ACDB.
There will be 20/12 Nos. A.C. outlets (for 20 feeders, 7 Nos of 63
amp rating + 13 Nos of 32 amp rating and for 12 feeders, 6 Nos of 63 amp
rating + 6 Nos of 32 amp rating ). Each outlet shall be controlled by TPN
MCBs (Miniature Circuit Breaker shall conform to IEC: 898-1987 and
IS: 8828) of respective current ratings. The cable gland for the cable size
31/2 core 25 & 10 mm2 armoured aluminum cables shall be provided at the
bottom for all the outlets. The LED type indicating lamps for incoming
feeders indicating availability of supply shall be provided inside of the
cubical.
There will be Main copper bus bar of electrolytic copper confirming
IS 8130/84, which will be liberally rated. It will receive A.C. input from
incoming cables through TBs and Switch & HRC fuse of 100 A, English
Electric/S&S/C&S make. The input to MCB of each outgoing feeder shall
Seal & Sign of Bidder

Page 4 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

be extended from the bus bars. The thickness and width of bus bar shall
not be less than 5 mm and 30 mm respectively. The bus bar shall be of
sufficient length to avoid congestion. The separation between connection
points of cable of two successive outgoing feeders on Bus shall be 4 Cms.
Bus bar shall be insulated to avoid accident while working inside A.C.D.B.
Insulation on the bus bar may reduce the rate of dissipation of heat
generated in bus bar. This will increase temperature of bulbar, which will
affect the insulation. Therefore bus bar design should take all these factors
into account so that there is no temperature rise. Each MCB shall be then
connected to Terminal Blocks by using insulated copper cable of suitable
size as per feeder ratings.
The wiring shall be neat and clean without any congestion and shall
be supported mechanically as well as tied up to withstand transit
vibrations. More than two wires shall not be terminated at a point.
Digital A.C. Voltmeter with voltage selector switch and self powered
transducer having two separate O/Ps of 4 20 mA to read A.C. voltage
upto 500 V shall be provided. Digital A.C. Ammeter with CTs , current
selector switch and self powered transducer having two separate O/Ps of
4 20 mA shall be provided to read current upto 100 A. The meters and
transducers shall be of good quality suitable to give a long and satisfactory
service.
A CFL of 14W with its fixture and door operated switch shall be
provided for cubicle illumination.
Space heater shall be provided in all the boards for preventing
harmful moisture condensation.
The space heaters shall be suitable for continuous operation on
240V AC, 50 Hz, single phase supply, and shall be automatically
controlled by thermostats. Necessary isolating switches and fuses shall
also be provided.
GENERAL:
1. The bidder shall be the manufacturer of the product. Offer from traders
are not acceptable.
2. The bidder shall provide detailed GA Drawing and Electrical Diagram
indicating all fuses and bus bars etc. with the size and rating. The offer
shall not be considered without the drawing.
3. The bidder shall clearly indicate deviations, if, any.
4. The bidder shall give the bill of materials including the make of the
components used of reputed make.
5. The bidder shall give the detailed list of the orders executed for supply
of similar equipment with performance certificate if any.
6. The bidder shall have minimum five years of experience in
manufacture & supply of such electrical cubicles.
7. The bidder shall furnish the Technical details of the DCDB offered in
Guaranteed technical particulars enclosed with the specification.

Seal & Sign of Bidder

Page 5 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

GUARANTEED TECHNICAL PARTICULARS


(To be furnished by the bidder)
1.
2.

Name of Manufacturer
Type & designation

:
:

3.

Size :

4.

5.

a) Height (mm)
b) Width (mm)
c) Depth (mm)
Colour of panel
a) Outside
b) Inside
Thickness of sheet steel

:
:
:
:
:
:
:

6.

Main Bus bars

a)
b)
c)
d)

Material
Rated current in Amp
Size (mm x mm)
Current density-A/mm2

:
:
:
:

e) Position, vertical/ Horizontal


Earth bus bar
a) Material
b) Size
Current transformer
a) Make
b) I.S. Applicable
c) Nos. of core
d) Accuracy class
e) VA Burden

:
:
:
:
:
:
:
:
:
:

f) I.S.F
g) C.T. Ratio
h) One min. P.F. withstand
voltage KV (rms)

:
:
:

i) Rated service voltage

7.

8.

Seal & Sign of Bidder

Page 6 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

9.

10

11

Ammeter
a) Make

:
:

b) Size
c) Flush mounted type
Voltmeter

:
:
:

a) Make

b) Size

c) Flush mounted type

Yes / No

Yes / No.

Transducer For Voltmeter


a) Make
b) Type
c) Accuracy Class
d) Input Volts
e) Output DC mA
f) Measuring range output.
g) % AC Ripple on output
h) Load Resistance in Ohm
i) Aux Voltage required
j) Response Time
k) Working Temp range

12

Transducer For Ammeter


a) Make
b) Type
c) Accuracy Class
d) CT ratio
e) Input amp
f) Output DC mA
g) Measuring range output
h) % AC Ripple on output
i) Load Resistance in Ohm
j) Aux Voltage required
k) Response time
l) Working temp range

Seal & Sign of Bidder

Page 7 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

13

14

15
16

17

18

19

Selector switches

a) Make

b) Rated capacity (Amp)

Indicating lamps

a) Make

b) Type

c) Wattage

Switch fuse unit for

a) 100 Amps. TPN

MCBs :

a) Whether ISI Marked

b) Make

Constructional details
a) Metal clad
b) Totally enclosed
c) Outdoor type
d) Floor mounting
e) Free standing
f) Panels shall be vermin proof
and highly corrosion
resistive.
g) Rubber gaskets provided to
the door
h) Maintenance can be carried
out from the front for switch
fuse unit / indicating meters /
indicating lamps.
i) GA drawing attached with
the tender.
j) Cable entry & exist from
bottom.

:
:
:
:
:
:
:

Yes / No.
Yes / No.
Yes / No.
Yes / No.
Yes / No.
Yes / No.

Yes / No.

Material of the wires used for


complete internal wiring of the
panel.
Terminal Blocks
a) Make
b) Voltage grade

SEAL OF THE FIRM

Seal & Sign of Bidder

Make

Yes / No.

:
Yes / No.
:
Yes / No.
:

Yes / No.

:
:

Yes / No.

SIGNATURE OF THE BIDDER

Page 8 of 9

GETCO / E / TS- MACC 2801 / R0 Dt. 26-10-2007

YARD LT A.C. DISTRIBUTION BOARD


SCHEDULE OF REQUIREMENTS
Sr.No.
Description
1.
Yard LT A.C. Distribution Board (ACDB) for 415V AC
supply as per specification.(20 outgoing feeders)
2
Yard LT A.C. Distribution Board (ACDB) for 415V AC
supply as per specification.(12 outgoing feeders)

Seal & Sign of Bidder

Page 9 of 9