Modular UPSs
Unit 3: UPS Design Configurations
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Symmetra PX
Right-sized, modular, scalable 3-phase power protection for any size data
center or high density power zone
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra PX Applications
Ranges: 16kW to 160kW
25kW to 2MW
Mission-critical
Systems
N+1 redundant
designs
Preventive alarms
Rapid disaster recovery
Data Center
Consolidation
High Density
Computing
From server room to
data center
Increasing
power
requirements
Co-location
Facilities
Eliminate oversizing
costs
Right-size each
solution
Scale easily
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Power View
Hot-Scalable Battery
Module
Connected in parallel for increased
availability and hot swappable for
easy replacement by a trained user
Redundant Intelligence
Module
Acts as back-up for the Main
Intelligence Module
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
High Performance
Battery Module
Hot-Scalable Modular
Power Distribution
Safely expand and service without
forced shutdowns
Hot Swappable
Built-in Static Bypass
Switch
Enables the UPS to transfer the load
to utility power, without interruption, in
case of heavy overload or faulty
conditions
L2: Capacity
L2: Capacity
Redundant
Intelligence
Module
Subfeed breakers
Two 160A subfeeds allow additional
distribution elements to be
integrated into your data center
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Fault LED
Help Key
When indicator is
red, a faulty
condition exists
Status Indicators
When green, UPS is providing power to the
load; the two yellow indicators show that
UPS is on battery or that power is being
supplied through the static bypass switch
Navigation Keys
Up and Down keys provide easy navigation
through menus, the Enter key opens menu
items and inputs changes to system
parameters, and Escape returns to the
previous screen
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Modular Distribution
Units
External Battery
Enclosure
Up to 277kW of user
expandable power distribution
in a half-rack RPP or 5U RDP
Rack-based, scalable
design for extended
runtimes
Remote
Monitoring
Modular Distribution
Modules
Locally available modular hotscalable distribution allows fast
expansion & service without forced
shutdowns
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Monitoring and
performance trending of
enterprise power and
environmental
infrastructure
Symmetra PX 250/500
Right-sized, modular, scalable 3-phase power protection
for any size data center or high density power zone
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Mission-critical Systems
N+1 redundant
designs
Preventive alarms
Rapid disaster recovery
High Density
Computing
From server room
to data center
Increasing
power
requirements
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Data Center
Consolidation
Co-location Facilities
Eliminate oversizing
costs
Right-size each solution
L2: Capacity
Symmetra PX 250/500kW
System Components
Static Switch
250kW / 500kW
Power Modules
25kW
Battery Unit
9.0 A/hr
76kg/95kg
(167lb/210lb)
491mm x 840mm x 591mm
(23.27in x 19.33in x 33.07 in)
(H x W x D)
43kg (95lb)
173mm x 452mm x 705mm
(6.8in x 17.8in x 27.8in)
(H x W x D)
25kg (55lb)
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
178mm x 108mm x
610mm
(7in x 4.25in x 24in)
(H x W x D)
L2: Capacity
Optional
Maintenance Bypass
with Distribution
(MBwD)*
*For parallel installations, a custom switchgear is used in place of the Maintenance Bypass with Distribution Panel.
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
MegaTie
2N solutions only.
During maintenance
procedures, maintain
full protection by
transferring the load
from one independent
Symmetra PX
250/500kW system to
another.
No Rear Access
Space saving & more flexibility on where you place the UPS
*Contact your sales representative to learn about special design
External Sync
Synchronize the UPS
output with any other
independent source for
use with downstream
static transfer switches.
L2: Capacity
System Components
Maintenance ByPass with Distribution (MBwD)
Right or left mounted
Top or bottom cable entry
3P + N + G or 3 + G (Dual/Single mains)
800A internal MCCB/MCS
3 Pole sub-feed breaker capacity limited by
breaker size
16 T1 (63 -100A)
12 T3 (125 - 225A)
8 T5 (300 - 400A)
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra PX 250/500kW
MBwD Internal Door
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra PX 250/500kW
MBwD Internals
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
T1 / T3 / T5 Sub feeds
63A 400A
Mounting
Adaptors
Mounting
Procedure
3 pole devices *
4 pole devices *
T1
16
12
T3
12
T5
8*
NA
* The poles outlined in the table are based on the use of a full panel of the single frame type.
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
UPS Input/Output Base Frame
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
UPS Input/Output Base Frame
One I/O base frame per either system
Identical frame for 250kW / 500kW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
UPS Input/Output Base Frame
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
250kW / 500kW Static Switch
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
Power Frame
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Hot Swapable
Each Power Module Frame Houses up to ten 25KW
modules
1 Frame will scale to 250kW (225kW N+1)
2 Frames will scale to 500kW (475kW N+1)
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
25kW Power Module
25 kW max capacity allows for right sizing
Multiple voltage support for all countries - same input
and output
380V:380V
400V:400V
415V:415V
480V:480V
Double Conversion Topology
Input PF regulated to unity
1.0 output PF (kW=kVA)
96% Efficiency
THDi < 5% at full load (Generator Friendly)
Field replaceable fans
Redundant fans operate at 30%
2.5kW integrated battery chargers in each module
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
Battery Frame
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
Battery Frame
Each Battery Frame Houses 8 long life Battery
Modules (48 Units)
Frames
Line-up batteries have internal bus-bar connections
Intelligent Battery monitoring system in each frame
Motorized DC Breaker Shunt tripped
Remote frames connect via 300mm wide Battery Sidecar
Cabinet and DC cables
Batteries are hot swapable
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
Battery Unit / Module
Unit
(SYBTU2-PLP)
Module
(SYBT9-B6)
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
System Components
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra PX250/500kW
MBwD
PX250
PX500
White Space
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Gray Space
L2: Capacity
System Components
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Parallel up to 4 Symmetra PX
250/500 UPSs
For capacity
Parallel installation provides up to 2MW
of modular, scalable power protection
For redundancy
Parallel installation provides up to 1.5
MW of ultra-efficient N+1 system-level
redundancy
Parallel communication
Easy-to-install parallel cables (SYOPT008)
connect the UPSs and facilitate load-sharing
Localized touchscreen display
Any touchscreen display in the parallel system
supports configuration of parallel functionality;
centralized information about system
performance simplifies monitoring, diagnosis,
and repair of all four UPSs
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Remote display
Download the display interface to your laptop or
computer to remotely monitor the complete system
-with up to 4 UPSs in parallel and configure a
sub-set of UPS parameters such as alarm
thresholds and battery test options
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Summary Screens
Graphical Summary screens
provide clear status information
for easier system management
Diagnostic Screens
Quickly and easily identify
component problems & errors,
reducing mean time to repair
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Customizable Notification
Receive immediate notification
if any event or alarm you
specify is detected
Browser-Accessible
Quick access, remotely or
over the network
Diagnostics
View information on
each module (e.g.,
power, battery) in the
UPS system
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Battery Breaker
Enclosure
Install the battery
breaker enclosure, then
use third-party battery
cabinets to supply
runtime to the load
Bottom Feed
Frame
For some configurations
greater than 250kW, use
the Bottom Feed Frame
to support dual bottomfeed utility input.
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Symmetra MW
P4 - Symmetra MW Rev 1
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Think big, think scalable introducing the worlds first modular Megawatt UPS
Symmetra
MW Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
2013
L2: Capacity
Symmetra MW
Modular, fault-tolerant power protection for large facilities, data
centers and mission-critical applications
Availability
Modular fault-tolerant design for increased availability
Agility
Load-sharing, scalable power modules for easy system
expansion
Serviceability
Self-diagnosing function and module-level repair reduce
Mean Time to Repair (MTTR)
Manageability
Symmetra MW
Configurable LCD touch-screen provides singleinterface management of multiple products via network
and the web
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Manageability
Availability
Maintainability
Life cycle
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Adaptability
Standard components build to stock
Ease of upgrade
On-site assembly allows you to make connections while the modules show up at a
later date
Keep sensitive electronics out of the work area till time for
installation
Installation-friendly design
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Configurable touch-screen
with network interface offers
easy access to all critical UPS
and ancillary equipment data.
L2: Capacity
Spacious section
Right or left positioning
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Redundant Power
Supply
Main Controller
Advanced Micro Processor Control
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Help Menu
Launches context-sensitive
help that provides
descriptions of functions on
current page
Symmetra MW
Operation /Configuration
Menu
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Seperate input/output
fusing and Contactors
To ensure that a faulty section
can be isolated
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Inverter section
Power Module Controller
Power Module
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Semiconductor fuses
Provide short circuit
protection of power
inlets/outlets for fault
containment
Galvanic isolated
control wiring
Redundant fans
Built-in crowbar
Part of fault containment
concept
Symmetra MW
Electronic overcurrent
protection
Overload will not cause damage
to the Power Module
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Manageability
Locally
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Help Menu
Symmetra MW
Operation /Configuration
Menu
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Touch-Screen LCD
System metering
User-friendly menudriven start-up and
shutdown procedures
User-friendly menudriven transfer
procedures
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra
MW
Alarms:
3
levels.
Symmetra MW Alarm Types
Informational, warning, critical
Example:
Weak fan
Example:
Main PSU fault
Example:
Inverter module
high temperature
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Availability
N+I internal, fault-tolerant system
Where I = 1,2,3,4
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Fault-Tolerant Design
Traditional Legacy UPS
No modularity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Modular Symmetra MW
Fault tolerant design
L2: Capacity
Maintainability
Make the system easier, and more intelligent to reduce MTTR
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Maintainability
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Life Cycle
Scaleable design
Optimises your operating cash flow, utilize revenues in a
more constructive way.
Pay for only the protection your load needs today
Minimize impact on air conditioning systems
Impact of 1 MW system running at 20% load is greater then
impact of 400 kW running at 50% load
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Keywords
Adaptability
Modular Upgradeable
Top or bottom cable entry as standard
Manageability
LCD Screen Battery Management
Single interface management of multiple products Monitor via network
Configurable display layout Advance 10 colour LCD touch screen
Availability
Built-in Redundancy Low MTTR (20-minute timeframe)
Maintainability
Self Diagnostic Modular design
Life cycle
Scalable High Efficiency
State-of-the-art energy optimised topology
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Delta Conversion
Double Conversion
5th Floor
5th Floor
4th Floor
4th Floor
The delta conversion energy saving trick is achieved by converting the In/Out energy difference. A legacy double conversion
UPS will need to convert all energy from AC to DC and then back from DC to AC.
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
1
384 Vdc
384 Vdc
Load
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Power Flow
Delta Conversion
Regulating
Regulating
the Delta,
delta, diff. in/out
Delta
Transformer
Delta Inverter
Main Inverter
Battery
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra MW Selection
Design and Selection
Regional issues and power requirements
Load and expansion needs
System availability
Verification
Submittal response
Factory Acceptance Test (FAT)
Site Preparation
Installation
Project management
Start-up and assembly services
Site Acceptance Test (SAT)
Symmetra MW
Final commissioning
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Maintenance Bypass
Panel
Line-up and match panel
that Incorporates a static
bypass switch to facilitate
transfers from UPS to
bypass
APC Global
Services
A variety of product
based and professional
services
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
Symmetra MW Summary
Modular, fault-tolerant power protection for large facilities, data
centers and mission-critical applications
Think big, think scalable The worlds first modular Megawatt UPS
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
www.MyEnergyUniversity.com
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
L2: Capacity
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
Thank You !