Module 3: Power Basics

Modular UPSs
Unit 3: UPS Design Configurations

Eduard Lucian BODOR


Data Centre Business Development
Manager for Central and Eastern Europe

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Symmetra PX
Right-sized, modular, scalable 3-phase power protection for any size data
center or high density power zone

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX Applications
Ranges: 16kW to 160kW
25kW to 2MW
Mission-critical
Systems
N+1 redundant
designs
Preventive alarms
Rapid disaster recovery

Data Center
Consolidation

Centralize server rooms


Reduce TCO
Increase efficiency
Reduce complexity

High Density
Computing
From server room to
data center
Increasing
power
requirements

Co-location
Facilities
Eliminate oversizing
costs
Right-size each
solution
Scale easily

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

InfraStruxure 48kW All-In-One Product


Design Benefits
Configurable Power
Distribution
Highly-customizable, factory-tested power
distribution solution fits the needs of any
data centerwithin the single-rack footprint
of the UPS

Fully Rated Inverter


In the power modules, improve
Return on Investment by providing
more real power, as output power
equals input power (kW = kVA)

Hot-Swappable Power Module

Power View

Provides the flexibility to scale power


capacity and adds N+1 capability

Easy to read and navigate through


menus and functions for the entire
redundant UPS and battery solution
through a single system display

Hot-Scalable Battery
Module
Connected in parallel for increased
availability and hot swappable for
easy replacement by a trained user

Redundant Intelligence
Module
Acts as back-up for the Main
Intelligence Module
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Built-in Static Bypass


Switch
Enables the UPS to transfer the
load to utility power, without
interruption, in case of heavy
overload or faulty conditions

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 48kW Product Design Benefits


Redundant
Intelligence Module
Back-up for the Main
Intelligence Module provides
increased availability

16kW Power Module


Provides the flexibility to scale
power capacity in an N+0 or
N+1 configuration with fully
rated inverters for providing
more real power

High Performance
Battery Module

Hot-Scalable Modular
Power Distribution
Safely expand and service without
forced shutdowns

Wrap Around System


Bypass
Isolates UPS from critical load while
maintaining power to your loads

Hot Swappable
Built-in Static Bypass
Switch
Enables the UPS to transfer the load
to utility power, without interruption, in
case of heavy overload or faulty
conditions

More powerful batteries help


reduce overall system footprint
No Rear Access
while the Extended Life Batteries
Space saving & more flexibility
(5 8 years) reduce total cost of
on where you place the UPS
ownership
Efficiency independently verified by TV
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 96kW Product Design Benefits


Redundant Intelligence
Module

Integrated Power Distribution &


Battery Cabinet

Back-up for the Main


Intelligence Module provides
increased availability

Distribution in the front of the cabinet and


batteries in the rear of the cabinet leave
more white space for your IT Racks and
minimizes the total size necessary for your
data center

16kW Power Modules

Provides the flexibility to scale


power capacity in an N+0 or
N+1 configuration; fully rated
inverters provide more real
power

Hot-Scalable Modular Power


Distribution

Safely expand and service without


forced shutdowns

High Density Footprint

Wrap Around System Bypass

Two frame design allows you to


scale from 16kW to 96kW
(power & runtime), saving
valuable floor space for your IT
equipment
Hot Swappable
Built-in Static Bypass
Switch

Isolates UPS from critical load while


maintaining power to your loads
Subfeed Breakers

Efficiency independently verified by TV

Enables the UPS to transfer the load to utility power, without


interruption, in case of heavy overload or faulty conditions
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Two subfeeds allow additional


distribution elements to be
integrated into your data center

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 160kW Product Design


Benefits
Integrated Power Distribution &
Battery Cabinet

Redundant
Intelligence
Module

Distribution in the front of the cabinet and


batteries in the rear of the cabinet leave
more white space for your IT Racks and
minimizes the total size necessary for your
data center

Back-up for the Main


Intelligence Module
provides increased
availability

Hot-Scalable Modular Power


Distribution

16kW Power Modules

Safely expand and service without


forced shutdowns

Provides the flexibility to


scale power capacity in an
N+0 or N+1 configuration;
fully rated inverters
provide more real power
High Density Footprint

Three frame design allows you


to scale from 16kW to 160kW
(power & runtime), saving
valuable floor space for your IT
equipment

Wrap Around System Bypass

Isolates UPS from critical load while


maintaining power to your loads
Hot Swappable
Built-in Static Bypass
Switch

Subfeed breakers
Two 160A subfeeds allow additional
distribution elements to be
integrated into your data center

Enables the UPS to transfer the load to


utility power, without interruption, in
case of heavy overload or faulty
conditions
Efficiency independently verified by TV

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

Symmetra PX 160kW Product Design


Benefits
Symmetra PX160
Three frame design available with
or without integrated PDU
High Density Footprint
Three frame design allows you to
scale from 16kW to 160kW (power &
runtime), saving valuable floor space
for your IT equipment
High Performance Battery Unit
More powerful batteries help reduce overall
system footprint while the extended life
expectancy (5 8 years) reduces total cost
of ownership
Battery Module
Connected in parallel for increased
availability, and hot swappable for easy
replacement by a trained user
Premium Line-Up and Match
Enclosures
Matches the look of other IT equipment
in your data center

Efficiency independently verified by TV

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L6: System plus System

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX User Interface Design


Benefits
Easy recognition of functions
Full System Level Display
Offers a clear overview of alarms, status data, instructional help
and configuration items on UPS and external batteries through a
single display

Uses a display interface design that is consistent


across product lines; intuitive navigation keys
resemble the keys of a computer keyboard

Fault LED

Help Key

When indicator is
red, a faulty
condition exists

Launches contextsensitive help that


provides short
descriptions of functions

Status Indicators
When green, UPS is providing power to the
load; the two yellow indicators show that
UPS is on battery or that power is being
supplied through the static bypass switch

Navigation Keys
Up and Down keys provide easy navigation
through menus, the Enter key opens menu
items and inputs changes to system
parameters, and Escape returns to the
previous screen

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

Symmetra PX Options and Related


Products

L6: System plus System

Modular Distribution
Units

External Battery
Enclosure

Up to 277kW of user
expandable power distribution
in a half-rack RPP or 5U RDP

Rack-based, scalable
design for extended
runtimes

Remote
Monitoring

Modular Distribution
Modules
Locally available modular hotscalable distribution allows fast
expansion & service without forced
shutdowns
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Monitoring and
performance trending of
enterprise power and
environmental
infrastructure

Symmetra PX 250/500
Right-sized, modular, scalable 3-phase power protection
for any size data center or high density power zone

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500 Applications


Range: 25kW to 2MW

Mission-critical Systems
N+1 redundant
designs
Preventive alarms
Rapid disaster recovery

High Density
Computing
From server room
to data center
Increasing
power
requirements

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Data Center
Consolidation

Centralize server rooms


Reduce TCO
Increase efficiency
Reduce complexity

Co-location Facilities
Eliminate oversizing
costs
Right-size each solution

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500kW
System Components

Static Switch
250kW / 500kW

Power Modules
25kW

Battery Unit
9.0 A/hr

76kg/95kg
(167lb/210lb)
491mm x 840mm x 591mm
(23.27in x 19.33in x 33.07 in)
(H x W x D)

43kg (95lb)
173mm x 452mm x 705mm
(6.8in x 17.8in x 27.8in)
(H x W x D)

25kg (55lb)

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

178mm x 108mm x
610mm
(7in x 4.25in x 24in)
(H x W x D)

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500 Product Design


Benefits
ECO Mode
Ultra-High Efficiency, Hot-Swappable Power Module
Provides the flexibility to scale power capacity in 25kW
increments and adds N+1 capability as well as a fully rated
inverter for providing more real power

Powerful, HotScalable Battery


Module
Connected in parallel
for increased
availability
Advanced battery
monitoring &
temperaturecompensated battery
charging included
Toolless replacement
means low Mean
Time To Repair

When bypass operation is


the preferred mode,
achieve even higher
operating efficiency when
in good power conditions
without sacrificing
protection. Depending on
configuration, efficiency
can exceed 99%.

Optional
Maintenance Bypass
with Distribution
(MBwD)*

Redundant Intelligence Module


Back-up for the Main Intelligence
Module provides increased availability

Space saving design


that provides power
distribution to your load
and, if required, isolation
from the UPS while
maintaining power to
your critical loads

*For parallel installations, a custom switchgear is used in place of the Maintenance Bypass with Distribution Panel.
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500 Product Design


Benefits
Dual Mains Input/Output
Premium Line-Up/Remote External
Battery Enclosure
A total of eight (8) enclosures can be
connected to the UPS for extended runtimes
and availability

MegaTie
2N solutions only.
During maintenance
procedures, maintain
full protection by
transferring the load
from one independent
Symmetra PX
250/500kW system to
another.

No Rear Access
Space saving & more flexibility on where you place the UPS
*Contact your sales representative to learn about special design

Allows for connection to 2


separate power inputs for
increased availability top or
bottom

Built-in Static Bypass


Switch
Hot swappable, the SSW
enables the UPS to transfer
the load to utility power,
without interruption, in case
of heavy overload or faulty
conditions

External Sync
Synchronize the UPS
output with any other
independent source for
use with downstream
static transfer switches.

considerations for back-to-back UPS or wall installations


400/415/480 V operation permits the use of 415V in NAM Data centers, offering the energy efficiency &
footprint savings of 415V distribution.
Efficiency independently verified by TV
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
Maintenance ByPass with Distribution (MBwD)
Right or left mounted
Top or bottom cable entry
3P + N + G or 3 + G (Dual/Single mains)
800A internal MCCB/MCS
3 Pole sub-feed breaker capacity limited by
breaker size
16 T1 (63 -100A)
12 T3 (125 - 225A)
8 T5 (300 - 400A)

Interrupt rating (Isc) : 50kAIC


Cannot be Installed in the middle of a row
PX250/500kW system does not require rear
access
400mm x 1991mm x 1070mm (WxHxD)

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500kW
MBwD Internal Door

Maintenance ByPass with Mimic


Security Lock
Sub Feed Panel

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500kW
MBwD Internals

Door Alarm Sensor


External Sync Signal
Load Test Port
MBwD and sub-feed monitoring
Q2, Q3, & Q5 status
Sub-feed branch circuits
Current, status, and Bypass voltage
Mounted via Adaptors

800A Frames - MCCB/MCS


Q2 - AC Output (MCCB)
Q3 - Maintenance Bypass (MCS)
Q5 - Input (MCS)

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Sub Feeds & Adaptors

T1 / T3 / T5 Sub feeds
63A 400A

Mounting
Adaptors

Mounting
Procedure

Breaker frame size

3 pole devices *

4 pole devices *

T1

16

12

T3

12

T5

8*

NA

* The poles outlined in the table are based on the use of a full panel of the single frame type.

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
UPS Input/Output Base Frame

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
UPS Input/Output Base Frame
One I/O base frame per either system
Identical frame for 250kW / 500kW

Black Box system log w/ event capture and graphs


Dual mains, top or bottom feed input
3P + N + G or 3 + G (Dual/Single mains)
UPS functions monitored/controlled remotely
Safety functions only controlled locally

Interrupt rating (Isc) : 65kAIC


10 touch-screen graphical system display
Houses the dual / single mains shorting bars and Q1 1200A
breaker
500kW dual-feed mains with bottom feed requires use of
bottom feed frame
No rear access required

600mm x 2000mm x 1070mm (WxHxD)

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
UPS Input/Output Base Frame

Contains hot swappable static switch


Main and redundant intelligence modules
(MIM/RIM)
Up to 4 NMC / I/O cards
Power Supplies

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

System Components

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

User Interface Screen Shots

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
250kW / 500kW Static Switch

SSW form factor Identical for 250kW and 500kW


110% Continuous
1000% over Current for 100mS
Integrate Document Drawer
Hot Swappable roll out roll in
Field replaceable fan

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
Power Frame

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500kW Platform


Power Module Frame

Hot Swapable
Each Power Module Frame Houses up to ten 25KW
modules
1 Frame will scale to 250kW (225kW N+1)
2 Frames will scale to 500kW (475kW N+1)

24 in x 78.7 in x 42.1in (WxHxD)


600mm x 2000mm x 1070mm (WxHxD)

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
25kW Power Module
25 kW max capacity allows for right sizing
Multiple voltage support for all countries - same input
and output
380V:380V
400V:400V
415V:415V
480V:480V
Double Conversion Topology
Input PF regulated to unity
1.0 output PF (kW=kVA)
96% Efficiency
THDi < 5% at full load (Generator Friendly)
Field replaceable fans
Redundant fans operate at 30%
2.5kW integrated battery chargers in each module
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
Battery Frame

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
Battery Frame
Each Battery Frame Houses 8 long life Battery
Modules (48 Units)
Frames
Line-up batteries have internal bus-bar connections
Intelligent Battery monitoring system in each frame
Motorized DC Breaker Shunt tripped
Remote frames connect via 300mm wide Battery Sidecar
Cabinet and DC cables
Batteries are hot swapable

Third-party/centralized batteries will be supported at a


later date

750mm x 2000mm x 1070mm (WxHxD)

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components
Battery Unit / Module

Unit
(SYBTU2-PLP)

12V 9Ah VRLA Battery with 5-8 yr life


+/- 288V DC voltage
6 battery Units comprise Module
55lb/25kg per Unit

Module
(SYBT9-B6)

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components

Battery Side Car

Attaches to side of battery frame for


remote battery
Enables DC cables to attach to bus
bars of battery cabinet

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX250/500kW
MBwD

Remote Battery Strategy


Battery Side Car

PX250

PX500

White Space

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Gray Space

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

System Components

Bottom Feed Enclosure

Allows cables to be installed from


bottom
Not required for all bottom feed
configs see config chart

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500 Parallel


Capability

Parallel up to 4 Symmetra PX
250/500 UPSs
For capacity
Parallel installation provides up to 2MW
of modular, scalable power protection
For redundancy
Parallel installation provides up to 1.5
MW of ultra-efficient N+1 system-level
redundancy

Parallel communication
Easy-to-install parallel cables (SYOPT008)
connect the UPSs and facilitate load-sharing
Localized touchscreen display
Any touchscreen display in the parallel system
supports configuration of parallel functionality;
centralized information about system
performance simplifies monitoring, diagnosis,
and repair of all four UPSs

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500kW User Interface Design


Benefits
10-inch LCD Touch
Screen Display
Offers a clear graphical /
text based overview of
alarms, status data, &
instructional help that
minimizes the risk of
operator errors

Multiple languages supported


Improved accessiblity to status reports and
other system data

System Wide Firmware Updates


On-the-fly upgrades via USB port on back of
display. Makes firmware updates easy and
increases system availability

Remote display
Download the display interface to your laptop or
computer to remotely monitor the complete system
-with up to 4 UPSs in parallel and configure a
sub-set of UPS parameters such as alarm
thresholds and battery test options

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX 250/500kW User Interface Design


Benefits
Full Screen Menus
Easy to follow menus provide
step-by-step start up, shut down
and system configuration
mitigating the risk of error.

Summary Screens
Graphical Summary screens
provide clear status information
for easier system management

Diagnostic Screens
Quickly and easily identify
component problems & errors,
reducing mean time to repair

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra PX Management Design Benefits


Navigation Tabs
Quickly link to system
data such as the UPS
configuration screens

Customizable Notification
Receive immediate notification
if any event or alarm you
specify is detected

Alarm and Event Logs


Search filters simplify
the review of logs;
optional automated file
transfer preserves UPS
history

Browser-Accessible
Quick access, remotely or
over the network

Diagnostics
View information on
each module (e.g.,
power, battery) in the
UPS system

Extensive Protocol Support


View the status of the
Symmetra PX solution using
Modbus, HTTP/HTTPS,
SNMPv1/v3, and Telnet/SSH

Main Status Screen


Overview of key
conditions of the
Symmetra PX

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

Symmetra PX 250/500 Options and


Related Products
Battery Sidecar
Extended Runtime (XR) Frame
To increase the number of minutes your
load can remain on battery, add optional
Battery Extended Runtime frames. A
maximum of 8 battery frames can be
connected to the Symmetra PX 250/500 to
extend runtime.

Install the batteries


remotely, then connect
the baterries by cables
to the UPS

Battery Breaker
Enclosure
Install the battery
breaker enclosure, then
use third-party battery
cabinets to supply
runtime to the load

Third-party battery cabinet


Front-access battery systems provide
high energy storage density ina smaller
footprint while eliminating the need to
reach over energized cables or battery
terminals to install, maintain, or replace
batteries.

Bottom Feed
Frame
For some configurations
greater than 250kW, use
the Bottom Feed Frame
to support dual bottomfeed utility input.

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L6: System plus System

Symmetra MW
P4 - Symmetra MW Rev 1

Symmetra MW 400 to 1600kVA


Modular
Scalable
Parallel
N+1

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW for Large Data Centers


Modular, fault-tolerant power protection for large facilities, data
centers and mission-critical applications
Large Data Centers (>100 racks)
Symmetra MW
InfraStruXure PDU
NetShelter SX
NetworkAIR IR RC/RP

Think big, think scalable introducing the worlds first modular Megawatt UPS
Symmetra
MW Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013
2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW
Modular, fault-tolerant power protection for large facilities, data
centers and mission-critical applications
Availability
Modular fault-tolerant design for increased availability

Agility
Load-sharing, scalable power modules for easy system
expansion

Total Cost of Ownership


Input power factor correction and fully rated power
reduce installation costs and eliminate UPS oversizing
needs

Serviceability
Self-diagnosing function and module-level repair reduce
Mean Time to Repair (MTTR)

Manageability

Symmetra MW

Configurable LCD touch-screen provides singleinterface management of multiple products via network
and the web

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

Power System Needs


Adaptability

Manageability
Availability
Maintainability
Life cycle

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

Modular UPS Design

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Adaptability
Standard components build to stock
Ease of upgrade
On-site assembly allows you to make connections while the modules show up at a
later date

Keep sensitive electronics out of the work area till time for
installation
Installation-friendly design

Service technicians helped design the product


Standard top or bottom, left or right cable entry

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW Product Design Benefits


Input/Output Section
High Efficiency

Spacious cable section for ease of


installation. Top or bottom, left or
right side cable entry.

Up to 97% efficiency at full


load provides reduced heat
dissipation and energy costs

Control Section: LCD


Touch-screen
Inverter Section
Load-sharing 200 kW power
modules provide the flexibility
to scale power capacity and
adds N+1 capability

Symmetra MW

Control Section: Static


Bypass Switch
The built-in static bypass switch (400
and 600kW models) provides for safe
transfer to an alternate source without
interrupting the supply to the load

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Configurable touch-screen
with network interface offers
easy access to all critical UPS
and ancillary equipment data.

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW Input/Output Section


Cable first in rough environments
The modular concept allows for the Input/Output section
to be installed first, in order to avoid dust, humidity etc
that could affect critical electronic components.

Top or bottom cable entry


Both options are available for
ease of installation and shorter
cable lengths

Spacious section
Right or left positioning

Symmetra MW

For increased adaptability the


Input/Output Section can be
positioned either to the left or the right
of the Inverter Section, whichever fits
the application best

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

For easy fitting of cables, the


Input/Output Section has
been made spacious

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW Control Section


LCD Touch-screen
Easy access to all critical UPS
and ancillary equipment data

Can Bus Application


Control
Developed for car industry
very rugged

Redundant Power
Supply

Main Static Switch

For enhanced availability

Main Controller
Advanced Micro Processor Control

Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Prevents backfeed to utility

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW User Interface Design Benefits


Home

Go to Top of Current Menu

Press to go to Start Screen

Escape function. Returns to previous screen displayed

Bypass Data Menu

Help Menu

Provides current status of


voltage, power, current,
frequency, etc. When the
system is operating in bypass
mode.

Launches context-sensitive
help that provides
descriptions of functions on
current page

Input Data Menu


Provides input-specific status
of voltage, power, current,
frequency, etc.

Symmetra MW

Output Data Menu


Provides output-specific
status of voltage, power,
current, frequency, etc.

Operation /Configuration
Menu

Battery Data Menu

Permits system operation and


monitoring, and provides the ability
to change display settings.

Provides battery-specific data


of voltage, current, remaining
runtime, temperature, power,
etc.

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW Inverter Section


Fault containment
200kW power sections

The inverter sections are


seperated by steel plates

Consists of 3 1-phase power


modules, a common 3-phase
delta transformer and a
common 3-phase power
module controller (PMC)

Slide in/out power


modules
For ease of service. A unique
crane that allows the module
to be changed by a single
person ships with the UPS

Seperate input/output
fusing and Contactors
To ensure that a faulty section
can be isolated

Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Redundant power supplies


For increased availability of the
inverter section

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Inverter section
Power Module Controller

Power Module

Input & Output Contactors


Input & Output Fuses

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW 1-phase 66.7kW power module

Semiconductor fuses
Provide short circuit
protection of power
inlets/outlets for fault
containment

Complete Delta and main


inverter

Galvanic isolated
control wiring

All critical components located in


draw-out module

Provides high resistance


against outside events

Redundant fans

Built-in crowbar
Part of fault containment
concept

Symmetra MW

100% redundancy on inverter fans

Electronic overcurrent
protection
Overload will not cause damage
to the Power Module

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Adaptability: Build as you grow

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Manageability
Locally

LCD screen contains information on all UPS-related, power accessory


and ancillary gear
Remotely

Able to work with APC Management Product offerings


Monitor via the network and the web
BMS, ModBus protocl, RS-485

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW User Interface Design Benefits


Home
Press to go to Start Screen

Go to Top of Current Menu


Escape function. Returns to previous screen displayed

Bypass Data Menu

Help Menu

Provides current status of


voltage, power, current,
frequency, etc. When the
system is operating in bypass
mode

Launches context-sensitive help


that provides descriptions of
functions on current page

Input Data Menu


Provides input-specific status of
voltage, power, current,
frequency, etc.

Symmetra MW

Output Data Menu


Provides output-specific status
of voltage, power, current,
frequency, etc.

Operation /Configuration
Menu

Battery Data Menu

Permits system operation and


monitoring, and provides the ability to
change display settings

Provides battery-specific data of


voltage, current, remaining
runtime, temperature, power,
etc.

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Touch-Screen LCD
System metering
User-friendly menudriven start-up and
shutdown procedures
User-friendly menudriven transfer
procedures

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Data Summary LCD

Alarms are categorized


into levels of urgency
Event log
Trend graph
Wave forms

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra
MW
Alarms:
3
levels.
Symmetra MW Alarm Types
Informational, warning, critical
Example:
Weak fan

Example:
Main PSU fault
Example:
Inverter module
high temperature

Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

Availability
N+I internal, fault-tolerant system
Where I = 1,2,3,4

Modular repair reduces mean time to repair (MTTR)


Easy to swap modules

Fault containment through parallel inverter technology


Layout of system

Reduce system variance through repeatable manufacturing processes


Leveraging the inherent learning curve

Spare parts readily available due to stocking of modules

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L6: System plus System

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Fault-Tolerant Design
Traditional Legacy UPS
No modularity

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Modular Symmetra MW
Fault tolerant design

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Maintainability
Make the system easier, and more intelligent to reduce MTTR

Component-level predictive failure analysis, continuous preventive


monitoring
Modular-level repair
Self-diagnostic system
Front Access for ease of maintenance

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Maintainability

Can be serviced by one


person
Crane ships with unit
Functions similar to
draw out switchgear

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Life Cycle
Scaleable design
Optimises your operating cash flow, utilize revenues in a
more constructive way.
Pay for only the protection your load needs today
Minimize impact on air conditioning systems
Impact of 1 MW system running at 20% load is greater then
impact of 400 kW running at 50% load

Service expense is modular


Service expenses are directly related to the size of your solution

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW Family 400kW


to 1,6MW

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

Keywords
Adaptability
Modular Upgradeable
Top or bottom cable entry as standard

Manageability
LCD Screen Battery Management
Single interface management of multiple products Monitor via network
Configurable display layout Advance 10 colour LCD touch screen

Availability
Built-in Redundancy Low MTTR (20-minute timeframe)

Maintainability
Self Diagnostic Modular design

Life cycle
Scalable High Efficiency
State-of-the-art energy optimised topology

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L6: System plus System

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Enhanced Delta Conversion On-line Topology


Power factor corrected input
Low input current distortion

Less then 5% input current THD

Rated for modern IT loads (kVA=kW)


High efficiency (up to 97%)
Reduced noise

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

The Delta Conversion. The Energy-saving


Trick!
Delta Conversion

Delta Conversion

Double Conversion
5th Floor

5th Floor

4th Floor
4th Floor

The delta conversion energy saving trick is achieved by converting the In/Out energy difference. A legacy double conversion
UPS will need to convert all energy from AC to DC and then back from DC to AC.

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Operation of T Bridge Inverter (Battery Op.)


Green arrows depict power flow
on the positive
half-cycle.
Red arrows depict power flow on
the negative half cycle.
Power expressed in kW (Real
Power)
No transformer required as a
result of T-Bridge inverter and
split DC bus design

1
384 Vdc

384 Vdc

Load

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Power Flow
Delta Conversion

Regulating
Regulating
the Delta,
delta, diff. in/out

Delta
Transformer

Delta Inverter

Main Inverter

Battery

1. Normal, regulated operation


2. Battery operation
3 Battery recharge

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

Symmetra MW Selection
Design and Selection
Regional issues and power requirements
Load and expansion needs
System availability

Verification
Submittal response
Factory Acceptance Test (FAT)
Site Preparation

Installation
Project management
Start-up and assembly services
Site Acceptance Test (SAT)
Symmetra MW

Final commissioning

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L5: Distributed Redundant

L6: System plus System

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW Options and Related Products


Battery Breaker Box
Battery Enclosure
Line-up and match
battery enclosure for
Valve Regulated Lead
Acid (VLRA) batteries

Maintenance Bypass
Panel
Line-up and match panel
that Incorporates a static
bypass switch to facilitate
transfers from UPS to
bypass

Overcurrent and short-circuit


protection in a line-up and
match cabinet

External Bypass Static


Switch
In a line-up and match desing
transfers the load from a
preferred source to an alternate
source without interrupting the
supply to the load

APC Global
Services
A variety of product
based and professional
services

Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Symmetra MW Summary
Modular, fault-tolerant power protection for large facilities, data
centers and mission-critical applications

Easy system expansion with load-sharing, scalable power modules


provides adaptability to changing environments
Fault-tolerant design provides high availability
Self-diagnosing function and modular-level repair reduce MTTR and
provide increased serviceability
Configurable LCD touch-screen with single-interface management of
multiple products provides manageability

Think big, think scalable The worlds first modular Megawatt UPS
Symmetra MW
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Free Access to Education: Energy University!


Recognizing the need and
importance for energy
education in all industries...
Schneider Electric, the
Architects of Efficiency,
developed a unique FREE
online education program
Energy University.

www.MyEnergyUniversity.com
2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

L1: Parallel Systems

L2: Capacity

L3: Isolated Redundant

L4: Parallel Redundant

L5: Distributed Redundant

L6: System plus System

Free Access to Education: Energy University!


Free, online e-learning means you have ready access to comprehensive
learning about energy efficiency
Self-paced, less than one hour modules
Courses can be taken anytime, anywhere there is an internet connection
24 hour access means you can learn when you want, at your convenience
200+ Energy Efficiency and Data Center courses available

Advantages of Row and Rack-Oriented Cooling Arhitectures


Alternative Power Generation Technologies
Building Controls
Calculating Total Power Requirements
Commissioning for Energy Efficiency
Compressed Air Systems
Data Center System Planning
Demand Response and The Smart Grid
Energy Efficiency Fundamentals, etc.

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013

Thank You !

2013 Schneider Electric All Rights Reserved Advanced Technical Training Power Course July 2013