You are on page 1of 7

LG Electronics

Air Conditioning Proposal

Air Conditioning Proposal


May 27, 2012

TOUFIC
JEDDAH

LG Electronics

Air Conditioning Proposal

Air Conditioning Proposal


TOUFIC
JEDDAH

SUBMITTED TO

DATE

GACA
ADDRESS

May 27, 2012


SALES ENGINEER

JEDDAH

TOUFIC

PHONE

PHONE :

E-MAIL

E-MAIL :

COMPLETION DATE

May 27, 2012

Valid for 30 days from above date

LG Electronics

TABLE OF CONTENTS
[1]. Building - Load Ouput Summary.
- 1. Project Name.
- 2. Date.
- 3. Location.
- 4. Design Conditions.
- 5. Cooling and Heating Loads.

[2]. Building - Load Output Detail.


- 1. Cooling Load.
- 2. Heating Load.
- 3. Cooling Load Profile.
- 4. Heating Load Profile.

Air Conditioning Proposal

LG Electronics

Building - Load Output

ICAD OFFICES- LOAD Summary


1. Project Name :ICAD OFFICES
2. Date :May 27, 2012
3. Location : JEDDA (Saudi Arabia), longuitude(0.0), latitude(21.5), elevation(10m)
4. Safe Factor : Cooling Sensible - 10.0, Cooling Latent - 10.0, Heating Sensible - 0.0 %
5. Design conditions

Out
door

Summer

Winter

DB Temp.[C]

46.0

13.9

WB Temp.[C]

29.4

RH[%]

30.0

6. Cooling and Heating Loads


Heating
load

Cooling load

Space
Name

OFFICES

Area
[m2]

1782

Total

Sensible

Airflow

On Coil
Condition

Off Coil
Condition

[W]

[W]

[CMM]

DB

WB

DB

WB

588438.2

440102.8

2270.0

22.0

15.7

13.2

12.6

Building - Load Output : 1 / 1

Peak
Time

Sensible

15:00

-55821.1

[W]

LG Electronics

Space Input Data

Space Name :OFFICES


TABLE 1. GENERAL SPACE DATA
GENERAL SPACE DATA
Space Name
OFFICES
Floor Area
1782.00 m2

MISCELLANESOUS
Heat Gain 10.80 W
SHF
1.00
Schedule
8h~18h

PEOPLE
Occupancy
Application
Activity
Sensible Gain
Latent Gain
Schedule

325.0 people
Office
Medium Work
86.50 W/person
133.30 W/person
8h~18h

LIGHTING
Heat Gain
Fixture Type
Multiplier
Schedule

41150.00 W
Recessed, Not Vented
1.0
8h~18h

INFILTRATION
Cooling
2.00 Air change rate
Heating
0.60 Air change rate
VENTILATION
Cooling
0.00 CMH/person
Heating
0.00 CMH/person
Schedule
8h~18h

TABLE 2. CONSTRUCTION DATA


Wall(W/m2C, m2)
U-Value

Roof
Skylight
Ceiling
Floor
E
W
N
S

1.2124

Glass(W/m2C, m2)

Area

U-Value

Adj.Region Temp

SC

U-Value

Area

*D

*P

Adj.Region Temp
Cooling(C) Heating(C)

1782.0

3.4068
1.2072
1.2072
2.2838
2.2838
2.2838
2.2838

Area

Door(W/m2C, m2)

0.0

0.82
46.00
46.00

0.0
1782.0
189.0
189.0
115.5
63.5

0.6000
0.6000
0.6000
0.6000

0.82
0.0 0.82
0.0 0.82
48.0 0.82
0.0

0.0123
0.0123
0.0123
0.0700

0.0
0.0
0.0
4.0

E
W
N
S

N
N
N
N

13.90
13.90

LG Electronics

Space - Load Output

Space Name :OFFICES

Out door

In door

Summer

Winter

DB Temp.[C]

46.0

13.9

WB Temp.[C]

29.4

RH[%]

30.0

DB Temp.[C]

22.0

RH[%]

51.0

22.0

1. COOLING LOAD
Item
External Load
Roof Cond
Glass Solar
Glass Cond
Wall Cond
Partition
Sub Total
Internal Load
Light
People
Misc
Sub Total
Infiltration / Ventilation
Infiltration
Ventilation
Sub Total
Grand Total

Space
Sens(W)

Space
Lat(W)

Net
Total(W)

Percent Of Total (%)

133324.3
8572.6

133324.3
8572.6

22.66
1.46

298.4
31850.6
56801.3
230847.2

298.4
31850.6
56801.3
230847.2

0.05
5.41
9.65
39.23

45265
30305.3
21170.2
96740.5

47654.8
0
47654.8

45265
77960.1
21170.2
144395.3

7.69
13.25
3.60
24.54

112515.2
0
112515.2
440102.9

100680.6
0
100680.6
148335.4

213195.8
0
213195.8
588438.3

36.23
0.00
36.23
100.00

Space
Sens(W)

Percent Of Total
(%)

-17500
-233.3
-10303.6
-17427.7
-45464.6

31.35
0.42
18.46
31.22
81.45

-10356.5
0
-10356.5
-55821.1

18.55
0.00
18.55
100.00

2. HEATING LOAD
Item
External Load
Roof Cond
Glass Cond
Wall Cond
Partition
Sub Total
Infiltration
Infiltration
Ventilation
Sub Total
Grand Total

Building - Load Output Detail: 1 / 1

LG Electronics

Air Conditioning Proposal

Space Name :OFFICES


10 ###
11 ###
12 ###
13 ###
14 ###
15 ###
16 ###
17 ###
18 ###
19 ###
20 ###
21 ###
22 ###
23 ###
24
Sens ###
###1 ###
###2 ###3 ###4 ###5 ###6 ###7 ###8 ###9 ###
Late
Total
# Cooling
load ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ###
Roof
Glass
###
Glas
Wall 298
Parti
###
Ligh
Peop
###
Misc ###0
Infil
Venti
# Heating
Roof
Glass
### load
Glas
Wall
Infil ###
Venti
0

3. Cooling Load Profile [SI Unit]


700000
600000
500000

Sensible
Latent
Total

Load

400000
300000
200000
100000
0
1

9 10 11 Time[hr]
12 13 14 15 16 17 18 19 20 21 22 23 24

Roof Cond
23%

Infiltration
36%
Misc
4%
People Light
8%
13%

Glass Solar
1%
Glass Cond
0%
Wall Cond
5%
Partition
10%

Space
Net
Heat
Gain
588438.2
W

4. Heating load Profile

Infiltration
18%
Wall Cond
30%

Roof Cond
33%
Glass Solar
0%

Glass Cond
18%

Building - Load Diagram: 1 / 1

Space
Heat Loss
-55821.1
W

You might also like