Overview
Bulletin 193/592-E300 Overview
The E300 Electronic Overload Relay is the newest technology for overload protection. Its modular design, communication
options, diagnostic information, simplified wiring, and integration into Logix make this the ideal overload for motor control
applications in an automation system.
E300 Electronic Overload Relays provide the following benefits:
Intelligent motor control (EtherNet/IP enabled)
Scalable solution
Diagnostic Information
Integrated I/O
Adjustable trip class 530
Wide current range
Test/Reset button
Programmable trip and warning settings
True RMS current/voltage sensing (50/60 Hz)
Protection for single- and three-phase motors
NOTE: Your order must include 1) the Cat. No. of the sensing module, control module, and communication module selected,
and 2)if required, Cat. No. of any accessories.
Certifications
UL508
UL Listed
CE Marked
UL 60947-1
CSA Certified
UL 60947-4-1
CCC
EN 60947-1
KCC
EN 60947-4-1
CSA22.2, No. 14
CSA22.2, No. 60947-1
CSA22.2, No. 60947-4-1
GB 14048.4
Product Overview
The E300 consists of three modules: sensing, control and communications. Users have choices in each of the three with
additional accessories to tailor the electronic overload for their applications exact needs.
Overview
Sensing Module
Sensing Options
Voltage/current/ground fault
Current/ground fault
Current
Current Range [A]
0.530
660
10100
Control Module
Control Voltage
I/O
Inputs
Relay Outputs
Inputs
Relay Outputs
24V DC
Communication Module
EtherNet/IP
Overview
Thermal Overload
Thermal Utilization
The E300 Electronic Overload Relay provides overload protection through true RMS current measurement of the individual
phase currents of the connected motor. Based on this information, a thermal model that simulates the actual heating of the
motor is calculated. Percent of thermal capacity utilization (%TCU) reports this calculated value and can be read via a
communications network. An overload trip occurs when the value reaches 100%.
Adjustable Settings
Thermal overload protection setup is accomplished simply by programming the motors full load current (FLC) rating and the
desired trip class (530). Programming of the actual values through software programming ensures the accuracy of the
protection.
Thermal Memory
The E300 Electronic Overload Relay includes a thermal memory circuit designed to approximate the thermal decay for a trip
class 20 setting. This means that the thermal model of the connected motor is maintained at all times, even if the supply power
is removed.
Reset Modes
This flexibility allows the end-user in the ability to select between manual and automatic reset for an overload trip, allowing for
broad application. The point of reset is user adjustable from 1100% TCU.
Time to Trip
During an overload condition, the E300 Electronic Overload Relay provides an estimated time to trip that is accessible via a
communications network. This allows corrective action to be taken so that production may continue uninterrupted.
Overview
Time to Reset
Following an overload trip, the E300 Electronic Overload Relay will not reset until the calculated percentage of thermal capacity
utilization falls below the reset level. As this value decays, the time to reset, which is accessible via a communications network, is
reported.
Thermal Warning
The E300 Electronic Overload Relay provides the capability to alert in the event of an impending overload trip. A thermal
warning bit is set in the Current Warning Status when the calculated percentage of thermal capacity utilization exceeds the
programmed thermal warning level, which has a setting range of 0100% TCU.
Two-Speed Protection
The E300 Electronic Overload Relay offers a second FLA setting for 2-speed motor protection. What used to require two
separate overload relays - one for each set of motor windings - can now be accomplished with one device. Improved protection
is delivered as thermal utilization is maintained in one device during operation in both speeds.
Phase Loss
The E300 Electronic Overload Relay offers configurable phase loss protection, allowing the installer to enable or disable the
function plus set a time delay setting, adjustable from 0.125.0 seconds. The trip level is factory-set at a current imbalance
measurement of 100%.
Stall
"Stall" is defined as a condition where the motor is not able to reach full-speed operation in the appropriate amount of time
required by the application. This can result in motor overheating as current draw is in excess of the motors full load current
Overview
rating. The E300 Electronic Overload Relay provides user-adjustable stall protection. The trip setting has a range of 100600%
FLA, and the enable time is adjustable up to 250 seconds.
Jam (Overcurrent)
The E300 Electronic Overload Relay can respond quickly to take a motor off-line in the event of a mechanical jam, thereby
reducing the potential for damage to the motor and the power transmission components. Trip adjustments include a trip
setting adjustable from 50600% FLA and a trip delay time with a range of 0.125.0 seconds. A separate warning setting is
adjustable from 50600% FLA.
Underload (Undercurrent)
A sudden drop in motor current can signal conditions such as:
Pump cavitation
Tool breakage
Belt breakage
For these instances, rapid fault detection can help minimize damage and aid in reducing production downtime.
Additionally, monitoring for an underload event can provide enhanced protection for motors that are coded by the medium
handled (e.g., submersible pumps that pump water). Such motors can become overheated despite being underloaded. This
can result from an absence or an insufficient amount of the medium (due to clogged filters, closed valves, etc.).
The E300 Electronic Overload Relay offers underload trip and warning settings adjustable from 10100% FLA. The trip function
also includes a trip delay time with a range of 0.125.0 seconds.
Remote Trip
The remote trip function allows an external device (e.g., a vibration sensor) to induce the E300 Electronic Overload Relay to trip.
External device relay contacts are wired to the E300 Electronic Overload Relay discrete inputs. These discrete inputs are
configurable with an option for assigning the remote trip function.
Voltage Protection
The E300 sensing module with voltage, current, and ground fault current will provide the user with enhanced current-based
motor protection with the addition of voltage protection. With this option, users can protect against voltage issues (e.g.,
undervoltage, voltage imbalance, phase loss, frequency, and phase rotation).
Overview
Power Protection
While the motor is powering a load, the E300 sensing module with voltage, current, and ground fault current, will also protect
the motor based on power. This option will monitor and protect for both excessive and low real power (kW), reactive power
(kVAR), apparent power (kVA), and power factor for a specific application (e.g., pump applications).
Analog Protection
The E300 analog expansion module allows you to protect against over-analog readings from analog-based sensors
(overtemperature, overflow, overpressure, etc.)
Diagnostic Functions
The E300 Electronic Overload Relay allows the user to monitor the following diagnostic information over a communications
network:
Device status
Trip status
Warning status
Hours of operation
Number of starts
Status Indicators
The E300 Electronic Overload Relay provides the following LED indicators:
Power This green/red LED indicates the status of the overload relay.
8
Overview
TRIP/WARN This LED flashes a yellow code under a warning condition and a red code when tripped.
Inputs/Outputs
Inputs allow the connection of such devices as contactor and disconnect auxiliary contacts, pilot devices, limit switches, and
float switches. Input status can be monitored via the network and mapped to a controllers input image table. Inputs are rated
24V DC, 120V AC, or 240V AC and are current sinking. Power for the inputs is sourced separately with convenient customer
sources at terminal A1. Relay contact outputs can be controlled via the network or DeviceLogix function blocks for performing
such tasks as contactor operation.
Test/Reset Button
The Test/Reset button, located on the front of the E300 Electronic Overload Relay, allows the user to perform the following:
Test The trip relay contact will open if the E300 Electronic Overload Relay is in an untripped condition and the Test/
Reset button is pressed for 2 seconds or longer.
Reset The trip relay contact will close if the E300 Electronic Overload Relay is in a tripped condition, supply voltage is
present, and the Test/Reset button is pressed.
Single/Three-Phase Operation
The E300 Electronic Overload Relay can be applied to three-phase as well as single-phase applications. A programming
parameter is provided for selection between single- and three-phase operation. Straight-through wiring is afforded in both
cases.
EtherNet/IP Communications
The E300 EtherNet/IP communication module has two RJ45 ports that act as an Ethernet switch to support a star, linear, and
ring topology and supports the following:
2 concurrent Class 1 connections [1 exclusive owner + (1 input only or 1 listen only)]
6 simultaneous Class 3 connections (explicit messaging)
Embedded web server
SMTP server for trip and warning events (email and text messaging)
Embedded EDS file
RSLogix 5000 add-on profile
For more information on operation and maintenance of this product, please reference the user manual,
publication 193-UM015.
Overview
Notes:
10
Product Selection
Bulletin 193/592-E300 Product Selection
Sensing Modules
Description
Mounting Options
IEC Contactors
NEMA Contactors
660
10100
0.530
660
10100
0.530
660
10100
0.530
660
10100
0.530
660
10100
0.530
IEC Contactors
NEMA Contactors
660
10100
0.530
660
10100
0.530
660
10100
0.530
660
10100
0.530
660
10100
All contactors
NEMA Size 02
NEMA Size 3
Cat. No.
193-ESM-I-30A-C23
193-ESM-I-30A-C55
193-ESM-I-60A-C55
193-ESM-I-100A-C97
193-ESM-I-30A-T
193-ESM-I-60A-T
193-ESM-I-100A-T
193-ESM-I-30A-E3T
193-ESM-I-60A-E3T
193-ESM-I-100A-E3T
193-ESM-I-30A-P
193-ESM-I-60A-P
193-ESM-I-100A-P
592-ESM-I-30A-S2
592-ESM-I-60A-S2
592-ESM-I-100A-S3
193-ESM-IG-30A-C23
193-ESM-IG-30A-C55
193-ESM-IG-60A-C55
193-ESM-IG-100A-C97
193-ESM-IG-30A-T
193-ESM-IG-60A-T
193-ESM-IG-100A-T
193-ESM-IG-30A-E3T
193-ESM-IG-60A-E3T
193-ESM-IG-100A-E3T
193-ESM-IG-30A-P
193-ESM-IG-60A-P
193-ESM-IG-100A-P
592-ESM-IG-30A-S2
592-ESM-IG-60A-S2
592-ESM-IG-100A-S3
11
Product Selection
Description
Mounting Options
IEC Contactors
660
10100
0.530
660
10100
0.530
660
10100
0.530
0.530
660
10100
All contactors
Cat. No.
193-ESM-VIG-30A-C23
193-ESM-VIG-30A-C55
193-ESM-VIG-60A-C55
193-ESM-VIG-100A-C97
193-ESM-VIG-30A-T
193-ESM-VIG-60A-T
193-ESM-VIG-100A-T
193-ESM-VIG-30A-E3T
193-ESM-VIG-60A-E3T
193-ESM-VIG-100A-E3T
193-ESM-VIG-30A-CT
592-ESM-VIG-30A-S2
592-ESM-VIG-60A-S2
592-ESM-VIG-100A-S3
Control Modules
Description
I/O Module
I/O and Protection Module.
Thermistor (PTC) and External
Ground Fault Current(1)
No. of Inputs/Outputs
6 in/3 out
4 in/3 out
4 in/3 out
4 in/2 out
2 in/2 out
2 in/2 out
Cat. No.
193-EIO-63-24D
193-EIO-43-120
193-EIO-43-240
193-EIOGP-42-24D
193-EIOGP-22-120
193-EIOGP-22-240
(1) Requires Core Balanced Ground Fault Sensor Cat. No. 193-CBCT_.
Communication Modules
Description
EtherNet/IP
Cat. No.
193-ECM-ETR
Expansion Modules
Description
Digital Expansion Module, 24V DC
Digital Expansion Module, 120V AC
Digital Expansion Module, 240V AC
Analog Expansion Module: mA, V, RTD, and Resistance
No. of Inputs/Outputs
4 in/2 out
4 in/2 out
4 in/2 out
3 universal in/1 out
24V DC
110240V AC, 50/60 Hz
12
Cat. No.
193-EXP-DIO-42-24D
193-EXP-DIO-42-120
193-EXP-DIO-42-240
193-EXP-AIO-31 (1)
193-EXP-PS-DC
193-EXP-PS-AC
193-EOS-SCS
193-EOS-SDS (1)
Product Selection
Accessories
Description
193-EIOGP-42-24D
193-EIOGP-22-120
193-EIOGP-22-240
193-EIO-63-24D
193-EIO-43-120
193-EIO-43-240
193-EIOGP-42-24D
193-EIOGP-22-120
193-EIOGP-22-240
193-ESM-VIG-30A-CT
193-EXP-DIO-42-24D
193-EXP-DIO-42-120
193-EXP-DIO-42-240
193-EXP-AIO-31
193-EXP-PS-DC
193-EXP-PS-AC
193-ESM-I-30A-T
193-ESM-I-60A-T
193-ESM-IG-30A-T
193-ESM-IG-60A-T
193-ESM-VIG-30A-T
193-ESM-VIG-60A-T
193-ESM-I-30A-P
193-ESM-I-60A-P
193-ESM-IG-30A-P
193-ESM-IG-60A-P
193-ESM-VIG-30A-CT
193-ESM-I-100A-T
193-ESM-IG-100A-T
193-ESM-VIG-100A-T
193-ESM-I-100A-P
193-ESM-IG-100A-P
Replacement Connectors
Cat. No.
193-EIO-CM-C23
193-EIO-CM-C55
193-EIO-CM-C97
193-EXP-CBL-1M
193-EXP-CBL-3M
193-CBCT1
193-CBCT2,
193-CBCT3
193-CBCT4
193-NCIO-63-CNT
193-NCIO-43-CNT
193-NCIOGP-42-CNT
193-NCIOGP-22-CNT
193-NCSM-VIG-CNT
193-NCXP-DIO-CNT
193-NCXP-AIO-CNT
193-NCXP-PS-CNT
140M-C-N45(1)
193-ESM-SA-100(2)
13
Product Selection
Notes:
14
Specifications
Bulletin 193/592-E300 Specifications
Wiring Diagrams
Figure 1 - Control Module
193-EIO-_ _-_ _ _
A1 R03
A2
R04
IN0
193-EIOGP-_ _-_ _ _
A1 R03
IN1
A2
R04
IN0
IN1
RELAY 0
RELAY 0
RELAY 1
A1
A1
A2
(+)
IN2
IN3
IN4
PE R13
IN5
RELAY 1
RELAY 2
R14 R23
R24
(-)
A1
A1
(+)
A2
IN2
(-)
IN3
IT1
PTC
IT2
PE
R13
R14
S1
Ground
Fault
S2
+t
IN2 IN3
+
Source
IN0 IN1 INC
IN0
IN1 IN2
IN3 INC
15
Specifications
+
OUT+OUT-
24V DC
Power
Supply
-
INx+
INx-
INx-
3 Wire RTD
2 Wire RTD/Resistance
INx+
INx-
INx+
INxRSx
+
Source
-
A1
A2
A1 A2
Electrical Specifications
Motor/Load Ratings
Terminals
Rated Insulation Voltage Ui
Rated Operating Voltage Ue, IEC
Rated Operating Voltage Ue, UL
Rated Impulse Voltage (Uimp)
Rated Operating Current Ie
Rated Frequency
(1) Exception: Any E300 Overload Relay that uses an external ground fault sensor is limited to
50/60 Hz detection.
16
Specifications
24V DC
1130V DC
3 A for 30 ms
120V AC
85132V AC
10 A for 1 ms
240V AC
159265V AC
8 A for 3 ms
6W
8W
5 ms
5 ms
10 ms
10 ms
10 ms
10 ms
R03/R04
R13/R14
R23/R24
Form A SPST - NO
5A
300V AC
250V AC
3 A (@120V AC), 1.5 A (@240V AC)
0.25 A (@110V DC), 0.1 A (@220V DC)
10 mA @ 5V DC
B300
AC-15
5 A, 250V AC
5 A, 30V DC
2 A, 250V AC
2 A, 30V DC
1,000 A
KTK-R-6
(6 A, 600 V)
5,000,000
2,500,000
1,000,000
300,000
17
Specifications
IN0
IN1
IN2
IN3
IN4
IN5
120V AC
Current Sinking
74V AC
5 mA
20V AC
2.5 mA
2074V AC
2.55 mA
24V DC
11V DC
2 mA
5V DC
1.5 mA
5...11V DC
1.5...2.0 mA
240V AC
159V AC
5 mA
40V AC
2.5 mA
40159V AC
2.55 mA
Input ranges
Input resolution
Output ranges
Output Resolution
Voltage Output Load
Current Output Load
Output Impedance
Output Open Circuit detect
Max Inductive Load (current outputs)
Max Capacitive Load (voltage outputs)
18
Specifications
Terminals
Type of Control Unit
Maximum Number of Sensors
Maximum Cold Resistance of PTC Sensor Chain
Trip Resistance
Reset Resistance
Short-circuit Trip Resistance
Maximum Voltage @ PTC Terminals (RPTC = 4 k)
Maximum Voltage @ PTC Terminals (RPTC =open)
Response Time
Mark A
6
1500
3400 150
1600 100
25 10
7.5V DC
30V DC
800 ms
193-EXP-DIO-42- 24D
250V AC
2000Vrms for 1 s
NA
1000 A
KTK-R (6 A, 600V)
AC15, DC13
3
193-EXP-DIO-42- 120
250V AC
2000Vrms for 1 s
NA
1000 A
KTK-R (6 A, 600V)
AC15, DC13
3
193-EXP-DIO-42- 240
250V AC
2000Vrms for 1 s
NA
1000 A
KTK-R (6 A, 600V)
AC15, DC13
3
193-EXP-PS-AC
100250V AC
2640Vrms for 1 s
4 kV
NA
NA
NA
3
193-EXP-PS-DC
21.626.4V DC
500V for 60s
0.5 kV
NA
NA
NA
3
19
Specifications
Environmental Specifications
Note: The E300 Electronic Overload Relay expansion power supplies (Cat. Nos. 193-EXP-PS-AC and 193-EXP-PS-DC) surrounding
air temperature must not exceed 55 C (131 F).
Ambient Temperature
Storage
Operating (open)
Operating (enclosed)
40+85 C (40+185 F)
20+55 C (4+131 F)
20+40 C (4+104 F)
Humidity
Operating
Damp Heat Steady State (per IEC 68-2-3)
Damp Heat Cyclic (per IEC 68-2-30)
Cooling Method
Vibration (per IEC 68-2-6)
Shock (per IEC 68-2-27)
Maximum Altitude
Pollution Environment
Terminal Marking
Degree of Protection
595% Non-condensing
92% r.h., 40 C (104 F), 56 days
93% r.h., 25 C/40 C (77 F/104 F), 21 Cycles
Natural convection
2.5 G operating, 5 G non-operating
30 G
2000 m(1)
Pollution Degree 3
EN 50012
IP20
(1) Exception: Any E300 Overload Relay that uses an external ground fault sensor is limited to 50/60 Hz detection.
(1) Performance Criteria 1 requires the DUT to experience no degradation or loss of performance
(2) Environment 2
20
Specifications
Protection
General Protection
Overload
Phase Loss
Ground Fault
Stall
Jam
Underload
Thermistor (PTC)
Current Imbalance
Communication Fault
Communication Idle
Remote Trip
Blocked Start/Start Inhibit
Under Voltage L-L
Over Voltage L-L
Voltage Unbalance
Phase Rotation
Trip
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Warning
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Under Frequency
Over Frequency
Under Real Power (kW)
Over Real Power (kW)
Under Reactive Power Consumed (+kVAR)
Over Reactive Power Consumed (+kVAR)
Under Reactive Power Generated (-kVAR)
Over Reactive Power Generated (-kVAR)
Under Apparent Power (kVA)
Over Apparent Power (kVA)
Under Power Factor Lagging (-PF)
Over Power Factor Lagging (-PF)
Under Power Factor Leading (+PF)
Over Power Factor Leading (+PF)
Power Value Overflow (kW, kVAR or KVA)
Over Analog
Trip
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Warning
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Overload Protection
Type of Relay
Nature of Relay
FLA Setting
Trip Rating
Trip Class
Reset Mode
Overload Reset Level
Core Balanced
Equipment Protection
Class I and Class II
20100 mA
100500 mA
200 mA1.0 A
1.05.0 A
0.55.0 A
0.125.0 s
0250 s
21
Specifications
Accuracy
Metering
Current
Voltage
Power
Protection Timers
All E300 Electronic Overload Relay trip timers have a resolution of 0.1 s or 0.1 s/25 s (whichever is greater).
22
Specifications
Notes:
23
Specifications
24
Approximate Dimensions
Bulletin 193/592-E300 Approximate Dimensions
Dimensions are in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Figure 5 - E300 Overload Relay Mounted on Bulletin 100-C09-C23 Contactor
87
(3.40)
45
(1.76)
35
(1.37)
n 5 (0.18)
190 (7.49)
60 (2.36)
29 (1.14)
FROM
CONTACTOR
MTG. HOLE
122
(4.78)
25
Approximate Dimensions
104
(4.10)
35
(1.374)
n 5 (0.18)
190 (7.49)
(ADD 5 mm (0.19 in.)
FOR CONTACTOR COIL
ON LINE SIDE)
60 (2.36)
67 (2.65)
37 (1.48) FROM
CONTACTOR
MTG. HOLE
152 (5.98)
122 (4.81)
29 (1.13)
FROM
CONTACTOR
MTG. HOLE
122
(4.78)
54
(2.12)
45 (1.75)
n 5 (0.18)
60 (2.36)
190 (7.49)
(ADD 5 mm (0.19 in.)
FOR CONTACTOR COIL
ON LINE SIDE)
67 (2.65)
37 (1.48) FROM
CONTACTOR
MTG. HOLE
152 (5.98)
34 (1.34)
FROM
CONTACTOR
MTG. HOLE
45 (1.76)
26
122
(4.82)
Approximate Dimensions
71.6
(2.82)
5.4
(0.21)
55
(2.165)
101
(3.98)
235.1
(9.26)
(ADD 0.24 in. FOR
CONTACTOR COIL
ON LINE SIDE)
91.6
(3.60)
43.5
(1.71)
FROM
CONTACTOR
MTG. HOLE
177.6
(6.99)
129.5
(5.10)
38.9
(1.53)
135.2
(5.32)
FROM
CONTACTOR
MTG. HOLE
Figure 9 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 0 and Size 1 Contactor
90
(3.56)
n 6 (0.22)
180 (7.06)
157 (6.17)
249 (9.78)
12 (0.46)
35 (1.38)
125
(4.91)
70
(2.75)
27
Approximate Dimensions
Figure 10 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 2 Contactor
100.1 (3.94)
n 5.58 (0.22)
183.9
(7.24)
219.2
(8.63)
275.59
(10.85)
11.68 (0.46)
124.71
(4.91)
40.13
(1.58)
80.01
(3.15)
28
Approximate Dimensions
Figure 11 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 3 Contactor
138.2
(5.44)
11.35
(0.45)
161.6
(6.36)
19.9
(0.78)
219.9
(8.66)
7.9
(0.31)
274.1
(10.79)
368
(14.49)
121
(4.76)
138.4
(5.45)
139.85
(5.51)
155.45
(6.12)
Figure 12 - E300 Overload Relay, 193-ESM-___-30A-E3T and -60A-E3T, DIN Rail/Panel Mounted
30
(1.18)
126
(4.94)
45
(1.764)
6 (0.24)
9 (0.33)
46 (1.81)
4 (0.16)
q
148 (5.83)
135 (5.32)
4 (0.14)
6 (0.217)
101 (3.96)
4 (0.154)
n 5 (0.17)
8 (0.30)
29
Approximate Dimensions
5.5
(0.22)
17.7
(0.70)
41.2
(1.62)
139.9
(5.51)
60
(2.36)
130
(5.12)
76.6
(3.02)
41.4
(1.63)
4.05
(0.16)
141.5
(5.57)
Figure 14 - E300 Overload Relay, 193-ESM-___-30A-T and -60A-T, DIN Rail Mounted
SHOWN WITH PANEL MOUNT FEET ACCESSORY
CAT. NO. 140M-C-N45
11.35
(0.45)
n 4.8
(0.189)
39
(1.53)
135
(5.32)
WITH MTG. FEET
4.5
(0.18)
30.1
(1.19)
q
45
(1.76)
30
124
(4.88)
116.2
(4.58)
W/O MTG. FEET
125
(4.921)
5
(0.197)
Approximate Dimensions
60
(2.36)
11.4
(0.45)
41.2
(1.62)
WITH FEET
139.9
(5.51)
WITH FEET
120.7
(4.75)
W/O FEET
36.6
(1.44)
W/O FEET
130
(5.12)
q
52.9
(2.08)
71.6
(2.82)
n 5.8
(0.23)
141
(5.55)
Figure 16 - E300 Overload Relay, 193-ESM-___-30A-P, -30A-CT, and -60A-P, DIN Rail Mounted
11.35
(0.45)
FROM MOUNTING FOOT
MOUNTING HOLE TO
RESET BUTTON
21.5
(0.85)
FROM MOUNTING FOOT
MOUNTING HOLE TO
RESET BUTTON
n 4.8
(0.19)
102
(4.00)
W/ MTG. FEET
30.2
(1.19)
106.3
(4.18)
W/O MTG. FEET
45
(1.76)
123.5
(4.86)
91.5
(3.60)
108
(4.25)
W/ MTG. FEET
5
(0.20)
3 PIN CONNECTOR ONLY WITH
CAT. NO. 193-ESM-VIG-30A-CT
31
Approximate Dimensions
11.6
(0.46)
26.3
(1.04)
WITH FEET
109.9
(4.33)
WITH FEET
21.4
(0.84)
W/O FEET
106.3
(4.18)
W/O FEET
100
(3.94)
q
38.8
(1.53)
n 5.8
(0.23)
71.6
(2.82)
140.9
(5.55)
98 (3.86)
87 (3.43)
80.75 (3.18)
120
(4.73)
32
60
(2.36)
Approximate Dimensions
98 (3.86)
87 (3.43)
80.75 (3.18)
120
(4.73)
98
87
(3.86) (3.43)
120
(4.73)
80.75 (3.18)
12
(0.47)
18.5
(0.73)
13.5
(0.53)
45 (1.77)
33
Approximate Dimensions
18.5
(0.73)
70
(2.76)
n 22.1
(0.87)
13.5
(0.53)
34