Professional Documents
Culture Documents
TYPE
Generator Bus
Load Bus with Cap
Load Bus
Load Bus
Known
V1 /10=1/00 p.u
P and Q
P and Q
P and Q
Unknown
P and Q
V2 /20
V3 /30
V5 /40
Page 161
Bus 1 V1
y12 =0.993428-j32.339275
Bus 2
S2=P2+jQ2
y =0.434825-j4.361626
S2=0.5582+ j0.332 23
Bus 3
V2
y24=0.438818j4.3716651 Q3=0.3
To 1.8
Bus 4 V
4
V3
S3=P3+jQ3
S3=0.118437+j0.072
S4=P4+jQ4
S4=0.103948+j0.06
y23
0.693282-j4.206570
y24
0.695415-j4.203698
Bus No
S2
S3
S4
Q2
Bus
Bus
Bus
Bus
2
3
4
2
P (MW)
5.58210
0.8946
0.7898
-
Q
(MVAR)
3.31997
0.54898
0.48099
0.3 to 1.8
capacitive
P (p.u)
@
10MVA
base
0.558210
0.08946
0.07898
Q (p.u)
@
10MVA
base
0.331997
0.054898
0.048099
0.03 to
1.8
Page 162
6.9kV Bus V2
At bus 2 by KCL,
V2
aTRM1
V3
aTRL3A
V4
aTRL3B
S*
2
V2*
Scap j
Qcap
V2*
V3
) y23 V2
aTRM1
a
TRL3A
V2
V4
y24 V2
a
TRL3B
Scap *
S*
2
*
*
V2
V2
Page 163
S*
2
V2*
V2 aTRM1
S*
cap
y12V1 y23
V2*
V3
aTRL3A
y24
V4
aTRL3B
S*2 S*cap
12 V1 y23
V2*(k)
V2(k 1) aTRM1
V3(k)
aTRL3A
y24
V4(k)
aTRL3B
Equation (3.3.2)
V3
aTRL3A
S*
3
V3*
By KCL, vector sum of currents in equals vector sum of current out
of the bus 3.
V3
y23 V2
aTRL3A
S*
3
V3*
S*
3
V3 aTRL3A
V3*
y23 V2
y23
Page 164
S*
3
V3(k 1) aTRL3A
V2(k)
y V *(k)
23 3
Equation (3.3.4)
V4
aTRL3B
S*
4
V4*
V4 S*
4
y24 V2
aTRL3B V4*
S*4
V4*
V4 aTRL3B
y24 V2
y24
S*
4
V4(k 1) aTRL3B
V2(k)
y V *(k)
24 4
Equation (3.3.6)
Page 165
S*
2 j Q cap
V2(k 1) aTRM1
V2*(k)
y12 V1 y 23
V3(k)
aTRL3A
y 24
V4(k)
aTRL3B
y12 y 23 y 24
Equation (3.3.2)
S*
3
V3(k 1) aTRL3A
V2(k)
y V *(k)
23 3
Equation (3.3.4)
S*
(k)
4
aTRL3B
V2
y V *(k)
24 4
Equation (3.3.6)
V4(k 1)
Page 166
*
S*
2 jQcap
V2(1) aTRM1
V2*(0)
y12 V1 y23
V3(0)
aTRL3A
y24
V4(0)
aTRL3B
2.348687 - j40.751566
2.348687 - j40.751566
V2(1)
= 0.991826-j0.013226 p.u
For V3(1)
S*
3
V3(1) aTRL3A
V2(0)
y23V*(0)
(0.0894638 j0.0548985)*
V3(1) 1
1
1(0.693282 - j4.206570)
V3(1) = 0.983882-j0.018611p.u
For V4(1)
S*
4
V4(1) aTRL3B
V2(0)
y24 V*(0)
Page 167
(0.0789849 j0.0480991)*
V4(1) 1
1
0.695415 - j4.2036981
V4(1) = 0.985837-j0.016446 p.u
y
V
y
12 1
23
24
V2*(1)
aTRL3A
aTRL3B
y12 y23 y24
*
V2(2) aTRM1
2.348687 - j40.751566
0.959989 - j32.341297 1
2.348687 - j40.751566
2.348687 - j40.751566
V2(2)
00.990935 - j0.014447*
2.348687 - j40.751566
= 0.988826-j0.017198 p.u
For V3(2)
S*
3
V3(2) aTRL3A
V2(1)
y V *(1)
23 3
V3(2)
(0.0894638 j0.0548985)*
S*
4
V4(2) aTRL3B
V2(1)
y V *(1)
24 4
Page 168
V4(2) 1
(0.0789849 j0.0480991)*
Since all errors are still greater than 1x10-6 then further
iterations are required until the errors are less than 1x10-6 in which
case the solution is said to converge to the correct value.
Repeating the same calculation procedure until 15 iterations
yields an error e<1x10-6 equivalent to five (5) decimal point
Chapter 3-Load Flow Analysis-Case 2
Page 169
V2 (Bus 2)
V3 (Bus 3)
V4 (Bus 4)
0.991826-j0.013226
0.983882-j0.018611
0.985837-j0.016446
0.988826-j0.017198
0.975093-j0.031826
0.977186-j0.029665
0.987229-j0.02014
0.971692-j0.035725
0.973836-j0.033573
0.986561-j0.02102
0.969961-j0.038659
0.972121-j0.036508
0.986251-j0.021669
0.969207-j0.039516
0.971378-j0.037368
0.986103-j0.021862
0.968867-j0.040162
0.971042-j0.038015
0.986043-j0.022004
0.968701-j0.04035
0.970878-j0.038203
0.986011-j0.022046
0.968634-j0.040491
0.970813-j0.038344
0.985999-j0.022077
0.968598-j0.040532
0.970777-j0.038385
10
0.985992-j0.022086
0.968585-j0.040563
0.970764-j0.038416
11
0.98599-j0.022093
0.968577-j0.040571
0.970756-j0.038425
12
13
14
0.985989-j0.022095
0.985988-j0.022096
0.985988-j0.022096
0.968575-j0.040578
0.968573-j0.04058
0.968573-j0.040581
0.970754-j0.038431
0.970752-j0.038433
0.970752-j0.038435
15
0.985988-j0.022097
0.968572-j0.040582
0.970751-j0.038435
0.00817
3
0.00300
0
0.00159
7
0.00066
7
0.00031
0
V2
eimaginary
ereal
V3
eimaginary
ereal
V4
eimaginary
0.013226
0.01611
0.018611
0.01416
0.016446
0.003971
0.00878
0.013215
0.00865
0.013218
0.002942
0.00340
0.003899
0.00335
0.003908
0.000880
0.00173
0.002933
0.00171
0.002934
0.000648
0.00075
0.000857
0.00074
0.000860
Page 170
6
7
8
9
10
11
12
13
14
15
0.00014
0.000193
7
5.986E- 0.0001419
05
3.249E- 4.215E-05
05
1.142E- 3.088E-05
05
7.101E- 9.144E-06
06
2.154E- 6.686E-06
06
1.544E- 1.974E-06
06
4.001E- 1.441E-06
07
3.34E- 4.244E-07
07
7.291E- 3.092E-07
08
0.00034
0.000646
0.00033
0.000646
0.00016 0.0001874
6
6.64E-05 0.0001414
0.00016 0.0001882
4
6.56E-05 0.0001415
3.63E-05
4.071E-05
3.58E-05
4.09E-05
1.28E-05
3.078E-05
1.27E-05
3.079E-05
7.91E-06
8.803E-06
7.81E-06
8.847E-06
2.46E-06
6.666E-06
2.42E-06
6.668E-06
1.71E-06
1.895E-06
1.69E-06
1.905E-06
4.67E-07
1.437E-06
4.59E-07
1.437E-06
3.69E-07
4.06E-07
3.65E-07
4.083E-07
Calculation results:
V2(15) = 0.985988-j0.022097 p.u
V3(15) = 0.968572-j0.040582 p.u
V4(15) = 0.970751-j0.038435 p.u
Converting V2(15) to polar form:
V2 =
(0.985988)2+(-0.022097)2 =/Arctan(-0.022097/0.985988)0
V2 = 0.986235/-1.2830 p.u
Actual value of bus voltage is
V2 =(0.986235/-1.2830 )(Vbase)= (0.986235/-1.2830 )(6.9kV)
V2 = 6.805/-1.2830 kV
Converting V3(15) to polar form:
V3 =
(0.968572)2+(-0.040582)2 =/Arctan(-0.040582/0.968572)0
V3 = 0.969422/-2.3990
p.u
Page 171
V3= 465.322/-2.3990 V
Converting V4(15) to polar form:
V4 = (0.970751)2+(-0.038435)2 /Arctan(-0.038435/0.970751)0
V4 = 0.971512/-2.2670 p.u
Actual value of bus voltage is
V4 =(0.971512/-2.2670)(Vbase)=( 0.971512/-2.2670)(480V)
V4= 466.325/-2.2670 V
3.4.3 Current, Power Flow and Power Factor Calculation
Current Flows
Using equation 3.2.6 and admittance values from table 3.3.2 to
calculate the current flows:
Current flow from bus 1 to bus 2 (I12) as referred from the primary
side (6.9kV) of TRM1
I12=y12(V1-V2)
I12=( 0.959989-j32.341297) (1- 0.985988+j0.022097)
I12= 0.728104-j0.431945 p.u
Converting to polar form:
I12 =
Page 172
(0.079277)2 + (-0.0526870)2/Arctan(-0.0526870/0.079277)
(0.728104)2+ (-0.431945)2/Arctan(0.431945/0.728104)
Page 173
APPARENT
POWER FLOW
(MVA)
8.465/30.6790
Lagging
8.349/29.3950
87.126
Lagging
1.067/32.6510
84.198
Lagging
1.049/31.5360
0.93878/32.3240
85.232
84.504
Lagging
Lagging
0.92476/31.3410
85.409
Lagging
The bus voltages, power, current and power factor for the
next five steps of the capacitor bank are calculated using the same
procedure as above and the results are summarized in the
preceding tables.
Page 174
V2
0.96942/-2.3990 pu
465.322/-2.3990 V
0.970391/-2.3970 pu
465.788/-2.3970 V
0.971359/-2.395 pu
466.252/-2.395 V
0.972324/-2.393 pu
466.715/-2.393 V
0.973287/-2.392 pu
467.178/-2.392 V
0.974249/-2.390 pu
467.639/-2.390 V
V3
0.971512/-2.267 pu
466.325/-2.267 V
0.972479/-2.265 pu
466.790/-2.265 V
0.973444/-2.264 pu
467.253/-2.264 V
0.974407/-2.262 pu
467.715/-2.262 V
0.975368/-2.261 pu
468.176/-2.261 V
0.97632/-2.259 pu
468.637/-2.259 V
0.995
0.99
0.985
0.98
0.975
0.97
0.965
0
500
1000
kVAR
1500
2000
Page 175
kVAR
I1 (A)Bus 1 to
2
I2 (A) Bus 2 to 3
I3 (A) Bus 2 to 4
300
600
900
1200
1500
1800
354.187
347.779
341.750
336.116
330.894
326.102
1302.339
1301.039
1299.744
1298.454
1297.170
1295.890
1144.937
1143.799
1142.666
1141.538
1140.413
1139.294
1400.000
1200.000
1000.000
800.000
600.000
400.000
200.000
0.000
0
500
I1 (A)Bus 1 to 2
1000
kVAR
1500
2000
I2 (A) Bus 2 to 3
I3 (A) Bus 2 to 4
Figure 3.14 Line Current versus kVAR
Based on the above trend, the minimum current will occur
when all capacitor bank are on-line. It is also apparent that the
maximum current occurs if there is only one (1) capacitor bank is
on-line.
Page 176
S1
S2
S3
(MVA) (MVA) (MVA)
8.466
1.068
0.939
600
900
1200
1500
1800
8.313
8.169
8.034
7.909
7.795
1.068
1.068
1.068
1.068
1.068
0.939
0.939
0.939
0.939
0.939
300
9
8
7
6
5
4
3
2
1
0
0
500
S1 (MVA)
1000
kVAR
S2 (MVA)
1500
2000
S3 (MVA)
Page 177
kVAR
300
600
900
1200
1500
1800
TRL3A %
Loading
20.87
20.52
20.18
19.87
19.58
19.31
TRL3B %
Loading
34.99
34.99
34.99
34.99
34.99
34.99
30.83
30.83
30.83
30.83
30.83
30.83
% Loading
40.00
30.00
20.00
10.00
0.00
0
500
1000
kVAR
TRM1 % Loading
1500
2000
TRL3A % Loading
TRL3B % Loading
Figure 3.16 Transformer Loading(%) versus kVAR
There is an obvious reduction of apparent power flow
through TRM1 (S1) and as expected, there is very minimal effect on
power flow through TRL3A and TRL3B.
Page 178
Bus 2
PF2
(%)
Bus 3
PF2
(%)
300
600
900
1200
1500
1800
86.004
87.586
89.129
90.620
92.047
93.398
84.198
84.200
84.202
84.204
84.206
84.208
84.504
84.506
84.507
84.509
84.511
84.513
kVAR
94.000
92.000
90.000
88.000
86.000
84.000
82.000
0
500
1000
kVAR
Bus 2 PF2 (%)
1500
2000
Page 179
%VDTL1
0.01325
%VDTL2
0.27951
%VDTL3
0.27303
600
0.01303
0.27896
0.2725
900
0.01281
0.27842
0.27196
1200
0.01261
0.27787
0.27143
1500
0.01242
0.27733
0.2709
1800
0.01225
0.27679
0.27038
0.3
%VD
0.25
0.2
0.15
0.1
0.05
0
0
500
1000
kVAR
%VDTL1
%VDTL2
1500
2000
%VDTL3
Page 180
Loss
kVAR TL1
(kW)
300 6.572
600 6.337
900 6.119
1200 5.919
1500 5.736
1800 5.571
Loss
TL2
(kW)
4.472
4.463
4.454
4.445
4.436
4.427
Loss
TL3
(kW)
3.471
3.464
3.457
3.45
3.443
3.437
8
6
4
2
0
0
500
1000
kVAR
Loss TL2 (kW)
1500
2000
Page 181