You are on page 1of 7

P R E PA R E D BY

DOC NO

ThomasSundstrm

99000Ext.Alarm

SECURITY

D O C R E S P O N S I B L E / A P P R OV E D

DAT E

REV

FILE

HasseStake

20120427

ExternalAlarminRNCrevB

External Alarm in access node Ljungby


Site id 88152
Updated 2012-04-27
Document history

Site id 88152

Revision Date
A
2006-09-22

Author
Sections modified
Thomas Sundstrm

Hasse Stake

2012-04-27

Type of modification
Doc in Excel format created with alarms for RNC
building.
New format of doc Modified for connection to Flexinode with one
extra external alarm module.Also some alarms
modified.

Page 1 of 7

3G Infrastructure Services AB
20020502

P R E PA R E D BY

DOC NO

ThomasSundstrm

99000Ext.Alarm

SECURITY

D O C R E S P O N S I B L E / A P P R OV E D

DAT E

REV

FILE

HasseStake

20120427

ExternalAlarminRNCrevB

Table of contents

Site id 88152

1.

Typ of External Alarm..............................................................................3

2.

Description and Connection of External Alarm.....................................3

Page 2 of 7

3G Infrastructure Services AB
20020502

P R E PA R E D BY

DOC NO

ThomasSundstrm

99000Ext.Alarm

SECURITY

D O C R E S P O N S I B L E / A P P R OV E D

DAT E

REV

FILE

HasseStake

20120427

ExternalAlarminRNCrevB

Plint.

Site id 88152

10

50

100

150

Page 3 of 7

RNC Externalarm 25-32

RNC Externalarm 17-24

RNC Externalarm 9-16

RNC Externalarm 1-8

High & Low Temp. Alarm

Generator Fuel Alarm

Main power failure Alarm

Input to Securitas

Fire Alarm

Rectifier Alarm 1-6

AC 3 Single Alarm 1-3

AC 2 Master Alarm 1-3

AC 1 Slave Alarm 1-3

Generator Alarm 11-12

Generator Alarm 1-10

Type of External Alarm on plinths in cabinet Elkapsling

200

3G Infrastructure Services AB
20020502

P R E PA R E D BY

DOC NO

ThomasSundstrm

99000Ext.Alarm

SECURITY

D O C R E S P O N S I B L E / A P P R OV E D

DAT E

REV

FILE

HasseStake

20120427

ExternalAlarminRNCrevB

Description and Connection of External Alarm


Type of
Equipment
Backup
Generator

Plant
Available
AC1-AC3
Generator
Brytare Q1
Utlst
skp G1

Site id 88152

Type of
Alarm
Low Oil
Pressure
Coolant
Temperature
N/A
AC Fault
Generator
Start Failed
Mains
Available
Set in Auto.
Mode
Mains Failed
Generator in
Operation
Clogged Filter
Generator
Failed

Alarm text in
Node B

A-Alarm
Generator Switch
Generator in
Operation
Clogged Filter
AC1+AC2+AC3
A-Alarm
Generator Failed

Severity

Pos. in cabinet
Elkapsling
(Plint-Par)
10-1

Position in
ADF for NodeB
(Plint-Par)

10-2

Not used

10-3
10-4

Not used
Not used

10-5
10-6

Not used
Not used

Major

10-10

1-7
Not used

Major

20-1
10-7

Minor
Major

Page 4 of 7

30-3
40-3
50-3
20-2
20-3
20-4

Position on
EMUA

Comments

Not used

2-5

S1

S9
S21

Summalarm. Seriekopplade i
skp Elkapsling.

S13

Summalarm. Parallellkopplade i
skp Elkapsling. Givare har
kontakter Normally Open.

3-8
2-10

3G Infrastructure Services AB
20020502

P R E PA R E D BY

DOC NO

ThomasSundstrm

99000Ext.Alarm

D O C R E S P O N S I B L E / A P P R OV E D

DAT E

REV

FILE

HasseStake

20120427

ExternalAlarminRNCrevB

Type of
Equipment

Type of
Alarm

Alarm text in
Node B

Fuel Tank

Low Fuel

AC1 AC 3

AC 1 Slave
AC 2 Master
AC 3 Single
General Alarm

A Alarm Low
Fuel
B-Alarm
AC1+AC2+AC3

AC1-AC 3
Battery

Rectifier
System

Fire Alarm
System

Site id 88152

Battery Charge
Alarm + Low
Battery
Voltage
Mains Failure
Urgent Alarm
Battery Failure
Blocking
Outgoing
Alarm
Not Urgent
Alarm
Add.
Undervolt
Alarm
Fire Alarm

SECURITY

Severity
Major

Pos. in cabinet
Elkapsling
(Plint-Par)
100-1

Position in
ADF for NodeB
(Plint-Par)
2-9

Position on
EMUA

30-1
40-1
50-1
30-2
40-2
50-2
10-8

3-9

S22

Summalarm. Seriekopplade i
skp Elkapsling.

3-10

S23

Summalarm. Seriekopplade i
skp Elkapsling.

2-7

S10

Summalarm. Seriekopplade i
skp Elkapsling..

Minor

Comments

S12

A-Alarm
AC1+AC2+AC3

Major

Battery Charge
Alarm + Low
Battery Voltage

Major

Rectifier Mains
Power Failure
A-Alarm Rectifier

Major

60-1

3-1

S14

Major

60-2
60-3
60-4

3-3

S16

B-Alarm Rectifier

Minor

60-5

3-4

S17

3-5

S18

20-5

60-6
Major

Page 5 of 7

70-1

3G Infrastructure Services AB
20020502

Larm frn slckcentral.

P R E PA R E D BY

DOC NO

ThomasSundstrm

99000Ext.Alarm

D O C R E S P O N S I B L E / A P P R OV E D

DAT E

REV

FILE

HasseStake

20120427

ExternalAlarminRNCrevB

Type of
Equipment
Fire Alarm
System

Securitas
System
Power
Supervisor

Type of
Alarm
Fire protection
released
Wrong of
System
Fire System
Blocked
Input of ext.
Alarm to
Securitas AB
Deltameter
Over-tension
controller
Power
Controller

Door Telco
Room

Intruder alarm
Door unlocked

Temp. sensor
Telco room

High
Temperature
Low
Temperature

Site id 88152

Alarm text in
Node B

SECURITY

Severity

Pos. in cabinet
Elkapsling
(Plint-Par)
70-2

Position in
ADF for NodeB
(Plint-Par)

Position on
EMUA

Comments

70-3
Fire System
Blocked

70-4
80
90-1

A-Alarm Overtension controller


Failure
A-Alarm Power
Controller Phase
1-3
Intruder alarm
Telco room
On site Telco
room
High Temp. Telco
room.
> 25 degr.
Low Temp. Telco
room.
< 10 degr.

Major

90-2

1-9

S3

Major

90-3

1-10

S4

Major

N/A

2-1

S5

Warning

N/A

2-2

S6

Major

110-1

2-3

S7

Major

110-2

2-4

S8

Page 6 of 7

3G Infrastructure Services AB
20020502

Kopplat enl. ritn. GF100-65PKHR.


Kopplat enl. ritn. GF100-65PKHR.

P R E PA R E D BY

DOC NO

ThomasSundstrm

99000Ext.Alarm

D O C R E S P O N S I B L E / A P P R OV E D

DAT E

REV

FILE

HasseStake

20120427

ExternalAlarminRNCrevB

Type of
Equipment

Type of
Alarm

Alarm text in
Node B

Temp. sensor
Power room

High
Temperature

High Temp.
Power room
room. > 25 degr.
Low Temp. Power
room. < 10 degr.
Intruder alarm
power room
On site power
room

Door Power
room

Low
Temperature
Intruder alarm
Door unlocked

SECURITY

Severity

Position in
ADF for NodeB
(Plint-Par)
1-8

Position on
EMUA

Major

Pos. in cabinet
Elkapsling
(Plint-Par)
110-3

Major

110-4

3-2

S15

Major

N/A

3-6

S19

Warning

N/A

3-7

S20

Ritning GF100-65PK-HR som visar inkoppling av drr- och inbrottslarm.

GF100-65PK-HR.pdf

Site id 88152

Page 7 of 7

3G Infrastructure Services AB
20020502

Comments

S2

Kopplat enl. ritn. GF100-65PKHR.


Kopplat enl. ritn. GF100-65PKHR.

You might also like