INTRODUCTION: POWER QUALITYPOWER QUALITY is a term that mean different to different people. Institute of Electrical and
electrical engineers (IEEE) standard IEEE 1100 defines power quality as the concept of
powering and grounding sensitive electronic equipment in a manner suitable for the equipment.
In a simpler words PQ is a set of electrical boundaries that allows a part of equipment to work in
an intended manner without loss of performance or life expectancy. In recent years power
engineers are increasingly concerned over PQ due to following reasons:
REASONS FOR INCREASED CONCERN REGARDING POWER QUALITY
1. The most responsible reason is the newer-generation load equipment with
microprocessor-based controls and power electronic devices. Such loads are more
sensitive to power quality variations than the equipment used in the past.
2. The another reason is the increased use of power electronics devices such as electrical
drives ,fact devices, static relays etc due to the increased emphasis on improving overall
power system efficiency . This is resulting in increasing harmonic levels on power
systems and has concerned about the future impact on system capabilities.
3. Increased awareness of power quality issues among the end users.
4. Most of the systems are now interconnected in a network. Hence the processes are
integrated in which the failure of any component can results into important consequences.
Page 373
5. The globalization of industries has increased the awareness about deficiencies in power
quality around the world.
6. The economic value of power quality is also one important reason for its increased
concern. There is a big money associated with these power quality disturbances.
Many efforts have been taken by the utilities to meet the consumers PQ requirements. Hence
FACT devices and various other custom power devices are introduced in the electrical system to
improve the PQ of the electrical power.
TYPES OF POWER QUALITY PROBLEMS
1. Voltage sag (or dip)
It is a dip of .1 to .9 p.u. in rms voltage or current at the power frequency, for interval of 0,5
cycle to 1 minute.
Causes: Whenever a load end draws a heavy current suddenly. Thats why it is associated with
faults on the transmission or distribution network, faults in consumers installation , sudden
connection of heavy loads and start-up of large motors.
Consequences: Malfunction of microprocessor-based control systems (PCs, PLCs, ASDs, etc),
that may cause false tripping of contactors and electromechanical relays. Maloperation of
electric rotating machines.
Fig.1-Voltage sag
2. Very short interruptions
It is a total interruption or decrease of supply voltage or load current to less than .1 p.u. for few
milliseconds to one or two seconds.
Causes: It occurs due to failure of protecting devices, insulation failure, control malfunction.
Also due to delayed reclosing of the protecting devices.
Consequences: False tripping of protection devices, loss of information results in malfunction of
data processing equipment. Sensitive equipment stops working.
Page 374
Page 375
Page 376
Page 377
9. Voltage Unbalance
A maximum voltage variation in a three-phase system in which the three voltage magnitudes or
the phase angle differences between them are not equal.
Causes:, Incorrect distribution of all single-phase loads by the three phases of the system (this
may be also due to a fault). Large single-phase loads (induction furnaces, traction loads)
Consequences: It mostly affects three-phase induction machines. Unbalanced systems imply the
existence of a negative sequence that is harmful to all three phase loads.
It has found that among all the PQ issues voltage sag and swell are the most occurring problems
at the distribution end as shown in fig.8-
Page 378
with a nonlinear resistance (a metal oxide varistor or a zener diode) that limits excessive line
voltage and conduct any excess impulse energy to ground.
C. Constant Voltage Transformers
Constant voltage transformers (CVT) were one of the first PQ solutions used to mitigate the
effects of voltage sags and transients. To maintain the voltage constant, they use two principles
that are normally avoided : resonance and core saturation. Constant voltage transformer. When
the resonance occurs, the current will increase to a point that causes the saturation of the
magnetic core of the transformer. If the magnetic core is saturated, then the magnetic flux will
remain roughly constant and the transformer will produce an approximately constant voltage
output. If not properly used, a CVT will originate more PQ problems than the ones mitigated. It
can produce transients, harmonics (voltage wave clipped on the top and sides) and it is inefficient
(about 80% at full load). Its application is becoming uncommon due to technological advances in
other areas.
Page 379
Fig.10-Fig.10-Isolation Transformer
F. Thyristor Based Static Switch and FACTS devices: The static switch is a very efficint
device for switching a new element in to the circuit when the voltage support is needed. It has a
dynamic response time of about one cycle. To correct quickly for sags or interruptions, voltage
spikes the static switch can used to switch one or more devises such as capacitor, filter, alternate
power line, energy storage systems etc. The static switch can be used in the alternate power line
applications [20].
FACTS devices such as DSTATCOM and UPFC with their highly efficient control
scheme are found to be versatile in improving the power quality at distribution end as they can
control the reactive power by generating and absorbing the reactive power without using any
moving device such as motar.the UPFC can control the active power also. Hence by these we can
contol the power factor and harmonics also.
G. Distribution Statcom (DSTATCOM)
As for the Custom Power requirements [7], utility distribution networks, sensitive industrial
loads, and critical commercial operations can potentially suffer from various types of outages
and service interruptions. These can cost significant financial losses per incident based on
process down-time, lost production, idle work forces, and other measurable and non-measurable
factors. The types of interruptions that are experienced are classified as power quality problems
and are most often caused by voltage sags and swells, lightning strikes, and other distribution
system related disturbances. In many instances the use of Custom Power equipment, such as
Dynamic Voltage Restorers (DVR), Solid-State Transfer Switches (SSTS), or Distribution level
Static Compensators (D-STATCOM), can be some of the most cost-effective solutions to
mitigate these types of power quality problems. There have been numerous applications of
Custom Power technologies [9]. A D-ST A TCOM, which is schematically depicted in Fig. 2
consists of a two level voltage source converter (VSC), a dc energy storage device, a coupling
transformer connected in shunt to the distribution network through a coupling transformer [4].
Such configuration allows the device to absorb or generate controllable active and reactive
power. The D-STATCOM has been utilized mainly for regulation of voltage, correction of
power factor and elimination of current harmonics.
Page 380
H. Distributed Generation (DG). Distributed Generation units are small sources of energy
located at or near the point of use. DG technologies typically include photovoltaic (PV), wind,
fuel cells, micro turbines, and reciprocating internal combustion engines with generators. These
systems may be powered by either fossil or renewable sources. Some types of DG can also
provide combined heat and power by recovering some of the waste heat generated by the source
such as the micro turbine. This can significantly increase the efficiency of the DG unit [11, 12].
Most of the DG technologies require a power electronics interface in order to convert the energy
into grid compatible ac power. The power electronics interface contains the necessary circuitry to
convert power from one form to another. These converters may include both a rectifier and an
inverter or just an inverter. The converter is and contains the necessary output filters. The power
electronics interface can also contain protective functions for both the distributed energy system
and the local electric power system that allow paralleling and disconnection from the electric
power system. These power electronic interfaces provide a unique capability the DG units and
can enhance the operations of a grid [13, 14].
CONCLUSION:
It was observed through the literature that the power quality issues and custom power devices
plays an important role in power system efficient operation. Distributed generation is one of the
custom power device can be used in distribution system for better improvement of power quality;
its controls can be optimized using various method like genetic algorithms and particle swarm
optimization.
REFRENCES:
[1] R.C. Dugan, S. Santoso, M.F. McGranaghan, and H.W. Beaty, Electric Power System
Quality, McGraw-Hill, 2004.
[2] N. Hingorani, "FACTS-Flexible ac transmission systems
[3] A de Almedia, L. Moreira. J. Delgado, Power Quality problems and new solutions
International conference on renewable energies and power quality 03, Vigo, Spain Vol.1,2003.
[4] G. Venkataramana, and BJohnson, "A pulse width modulated power line conditioner for
sensitive load centers," IEEE Trans. Power Delivery, vol. 12, pp. 844-849, Apr. 1997.
[5] L Xu, O. Anaya-Lara, V. G. Agelidis, and E. Acha, "Development of prototype custom
power devices for power quality enhancement," in Proc. 9th ICHQP 2000, Orlando, FL, Oct
2000, pp. 775-783.
[6] W. Freitas, A. Morelato, "Comparitive study between power system block set and
PSCAD/EMTDC for transient analysis of custom power devices based on voltage source
converter," /PST, New Orleans, USA,
Page 381
[7] John J. Paserba Greogory F.Reed Masatoshi Takeda & Tomohiko Aritsuka, FACTS &
prototype custom power equipment for the enhancement of power transmission system
performance & power quality".
[8] N.G. Hingorani, Introducing Custom Power, IEEE Spectrum, June 199
[9] M. Takeda, H. Yamamoto, T. Aritsuka, I. Kamiyama G.F. Reed, Development of a Novel
Hybrid Switch Device and Application to a Solid-State Transfer Switch, Proceedings of the
IEEE PES Winter Power Meeting, New York, Jan./Feb. 1999, pp. 1151-1156.
[10] H. L. Willis, "Analytical methods and rules of thumb for modeling DG distribution
interaction," in Proc. 2000 IEEE Power Engineering Society Summer Meeting, vol. 3, Seattle,
WA, pp. 1643-1644,2000.
[11] D. Das, D. P. Kothari, A. Kalam, " Simple and efficient method for load flow solution of
radial distribution networks," Electrical Power & Energy Systems, Vol. 17, No.5, pp. 335346,1995
[12] K. Manjunatha Sharma and K. P. Vittal, "A Heuristic Approach to Distributed Generation
Source Allocation for Electrical Power Distribution Systems", Iranian Journal of Electrical &
Electronic Engineering, Vol. 6, No. 4, pp. 224-231, Dec. 2010
[13] M.F.Kotb, K.M.Shebl, M. El Khazendar and A. El Husseiny, "Genetic Algorithm for
Optimum Siting and Sizing of Distributed Generation", In Proceedings of 14th International
Middle East Power Systems Conference, pp. 433-440, Egypt, 2010.
[14] Deependra Singh, Devender Singh and K S Verma, "Distributed Generation Planning
Strategy with Load Models in Radial Distribution System", International Journal of Computer
and Electrical Engineering,Vol. 1, No. 3, pp. 362-375, Aug 2009.
[15] Wichit Krueasuk and Weerakorn Ongsakul, "Optimal Placement of Distributed Generation
using Particle Swarm Optimization", In Proceedings of Power Engineering Conference in
Australasian Universities, Australia, 2006.
[16] Soma Biswas and S.K. Goswami, "Genetic Algorithm based Optimal Placement of
Distributed Generation Reducing Loss and Improving Voltage Sag Performance", Proc. of Int.
Conf. on Advances in Electrical & Electronics, pp. 49-51, 2010.
[17] Russell C. Eberhart , Yuhui Shi , James Kennedy ,Swarm Intelligence, Morgan
Kaufmann; 1 edition,April 9, 2001
Page 382