TRANSFORMER EFFICIENCY AND REGULATION CALCULATION

===============================================================
REFERENCE No. :
:
15118.00
IRON LOSS(KW)
RATING (KVA)
:
120000
LOAD LOSS(KW)
% IMPEDANCE
:
12.00
IS TOL

:
:

---------------LOAD
---------------1.25
---------------1.00
---------------0.75
---------------0.50
---------------0.25
----------------

---- -----------------0.80 PF
---- -----------------%
99.628
---- -----------------%
99.682
---- -----------------%
99.728
---- -----------------%
99.754
---- -----------------%
99.704
---- ------------------

--------------------- ---U.P.F.
--------------------- ---99.702 %
--------------------- ---99.745 %
--------------------- ---99.782 %
--------------------- ---99.803 %
--------------------- ---99.763 %
--------------------- ----

------------------------0.95 PF
------------------------99.687
------------------------99.732
------------------------99.770
------------------------99.793
------------------------99.751
-------------------------

--- ------------------ ---0.90 PF


--- ------------------ ---%
99.669 %
--- ------------------ ---%
99.717 %
--- ------------------ ---%
99.758 %
--- ------------------ ---%
99.781 %
--- ------------------ ---%
99.737 %
--- ------------------ ----

-----------------0.85 PF
-----------------99.650
-----------------99.700
-----------------99.744
-----------------99.769
-----------------99.722
------------------

55.50
251.00

REGULATION AT FULL LOAD (1.0 PF)

0.93

REGULATION AT FULL LOAD (0.95PF)

4.59

REGULATION AT FULL LOAD (0.9 PF)

5.99

REGULATION AT FULL LOAD (0.85PF)

7.01

REGULATION AT FULL LOAD (0.8 PF)

7.81

% LOAD AT WHICH EFF. IS MAXIMUM

47.023

MAXIMUM EFFICIENCY

99.804

MAX
MAX

%
%
%
%
%