FDBG-A Series
Cooling Only
ED41-015B
2. Functions.................................................................................................3
2.1 FDBG-A Series.........................................................................................3
4. Specification............................................................................................5
4.1 50Hz .........................................................................................................5
6. Dimensions ...........................................................................................11
6.1 Indoor Unit..............................................................................................11
6.2 Outdoor Unit ...........................................................................................16
6.3 Installation Service Space for R71FU ....................................................18
7. Piping Diagrams....................................................................................20
7.1 Indoor Unit + Outdoor Unit .....................................................................20
8. Wiring Diagrams....................................................................................23
8.1 Indoor Unit..............................................................................................23
8.2 Outdoor Unit ...........................................................................................24
8.3 Field Wiring ............................................................................................27
11.Operation Limit......................................................................................35
11.1 Operation Limit .......................................................................................35
13.Electric Characteristics..........................................................................38
13.1 Cooling Only...........................................................................................38
15.Installation .............................................................................................41
15.1 FDBG-A Series.......................................................................................41
FDBG-A Series
ED41-015B
1.1.1
Indoor Unit
FDBG25A
FDBG35A
FDBG50A
1.1.2
Outdoor Unit
R25J
R35J
1.1.3
FDBG60A
FDBG71A
R50G
R71FU
Remote Controller
KRC47-2
KRC47-4
1.1.4
R60G
KRC47-1
Model Series
Outdoor Unit
Indoor Unit
50Hz
FDBG25AVE
R25JV1
FDBG35AVE
R35JV1
FDBG50AVE
R50GV1
FDBG60AVE
R60GV1(K)
FDBG71AVE
R71FUV1, Y1
FDBG-A Series
ED41-015B
Functions
2. Functions
2.1
FDBG-A Series
Points and Functions
Auto Restart
PE Fin
{ : Function Exists
FDBG-A Series
ED41-015B
3.1.1
Power Supply
Symbol
Power Supply
V1
1, 220~240V, 50Hz
3, 380~415V, 50Hz
(4 wires)
Y1
Note:
3.1.2
Indoor Unit
Outdoor Unit
FDBG25AVE
R25JV1
FDBG35AVE
R35JV1
FDBG50AVE
R50GV1
FDBG60AVE
R60GV1(K)
FDBG71AVE
R71FUV1
FDBG71AVE
R71FUY1
Nomenclature
Indoor Unit
FDB
35
VE
Duct Connection Low Static Pressure Type
FDB : Cooling Only
DIT Products
Capacity Index
Indicates Major Design Category
Power Supply Symbol
VE : 1 200~240V/220V 50Hz/60Hz
(P0001-1)
Outdoor Unit
35
V1
K
Outdoor Unit
R : Cooling Only
Capacity Index
Indicates Major Design Category
Power Supply Symbol
V1 : 1 220~240V 50Hz
Y1 : 3 380~415V 50Hz
High Outdoor Temperature Application
(P1247-1)
FDBG-A Series
ED41-015B
Specification
4. Specification
4.1
50Hz
Indoor Unit
Model
Outdoor Unit
FDBG25AVE
FDBG35AVE
FDBG50AVE
FDBG60AVE
FDBG71AVE
V1
R25JV1
R35JV1
R50GV1
R60GV1, R60GV1K
R71FUV1
Y1
R71FUY1
kW
Btu/h
kcal/h
2.64 / 2.60 /
9,000 / 8,900 /
2,270 / 2,250 /
3.54 / 3.50 /
12,100 / 11,900 /
3,040 / 3,010 /
mm
260900580
Indoor Unit
FDBG25AVE
Dimensions
Coil
Fan
HWD
Type
RowStagesFin Pitch
Face Area
Model
Type
Motor Output
Air Flow Rate
W
m/min
kg
mm
mm
in.
Weight
Liquid
Gas
Drain
Wired
Wireless
Piping Connections
Remote Controller
Outdoor Unit
Color
Dimensions
Coil
HWD
Type
RowStagesFin Pitch
Face Area
Model
Comp.
Fan
FDBG35AVE
FDBG60AVE
260900580
260900580
2601,300580
Cross Fin Coil (Waffle Louver Fins and Hi-XA Tubes)
2101.75
3101.75
3101.75
0.189
0.189
0.231
Sirocco Fan
Sirocco Fan
Sirocco Fan
45
45
65
(H) 13 (L) 11
(H) 13 (L) 11
(H) 18 (L) 15
22
23
31
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
3/4B
3/4B
3/4B
KRC47-1 KRC47-2 KRC47-1 KRC47-2 KRC47-1 KRC47-2
2101.75
0.189
Sirocco Fan
45
(H) 13 (L) 11
22
6.4 (Flare)
9.5 (Flare)
3/4B
KRC47-1 KRC47-2
R25JV1
R35JV1
R50GV1
R60GV1, R60GV1K
R71FUV1
Y1
R71FUY1
mm
Ivory White
560695265
Ivory White
560695265
Ivory White
685800300
Ivory
816880370
m
V1
Y1
1241.6
0.333
RC30BV1R2T
2222.0
0.372
RC46AV1TRT
Ivory White
540750270
Cross Fin Coil
2222.0
0.372
RC70AV1TRT
2282.0
0.465
NH41VMDT
2362.0
0.653
H23A35QABKA
H23A35QDBEA
Hermetically Sealed
Type
2.2
P45J11SM
Propeller
50
46
87
84
9.5 (Flare)
15.9 (Flare)
26.0 (Hole)
Thermal Protector for
Outdoor Fan Motor
and Indoor Fan Motor.
Internal Pressure
Relief Valve
(Compressor).
Motor Protector
(Compressor).
100 0
Weight
kg
Piping Connections
Liquid
Gas
Drain
W
m/min
V1
Y1
mm
mm
mm
0.7
1.1
1.7
2.2
PZ380
PZ380
PZ380
PZ430
Propeller
Propeller
Propeller
Propeller
25
25
45
53
28 / 30
26.5 / 28
27
40
27
33
42
61
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
6.4 (Flare)
9.5 (Flare)
12.7 (Flare)
15.9 (Flare)
15.9 (Flare)
18.0 (Hole)
18.0 (Hole)
18.0 (Hole)
18.0 (Hole)
Thermal Protector for Compressor (50 model), Outdoor Fan Motor and Indoor Fan Motor.
Internal Protector of Compressor. Fuse.
Safety Devices
Capacity Step
Refrigerant Control
Standard Length
%
m
Ref. Piping
Max. Length
25
Charge
kg
Model
Charge
15
R22
0.8
(Charged for 10m)
SUNISO 4GS DI
0.40
15
R22
1.0
(Charged for 10m)
SUNISO 4GS DI
0.50
Refrigerant
Ref. Oil
100 0
Drawing No.
100 0
100 0
100 0
Capillary Tube
5
25
30
30
Note:
15
15
R22
R22
1.20
1.50
(Charged for 10m)
(Charged for 5m)
SUNISO 4GS DI
MS 32
0.85
1.20
C : 4D024196
5
50 (Equivalent Length
70m)
30
R22
2.10
(Charged for 5m)
SUNISO 3GS
1.48
C : 4D024536
Conversion Formulae
Cooling
Piping Length
Hz-Volts
Standard
(1)
5m (Horizontal)
50Hz-220V
(2)
5m (Horizontal)
50Hz-220V
FDBG-A Series
(3)
3101.75
0.231
Sirocco Fan
65
(H) 18 (L) 15
31
9.5 (Flare)
15.9 (Flare)
3/4B
KRC47-1 KRC47-2
V1
Type
Motor Output
Model
Type
Motor Output
Air Flow Rate
FDBG71AVE
2601,300580
kcal/h=kW860
Btu/h=kW3414
cfm=m/min35.3
SSA 385/386
Optional Accessories
ED41-015B
5. Optional Accessories
5.1
Optional Accessories
5.1.1
Option List
Indoor Unit
Kit Name
FDBG25A
FDBG35A
FDBG50A
Optional Accessory
FDBG60A
FDBG71A
KRC47-1
KRC47-2
KRC47-4
Suction Grille
KDGF19A45
KDGF19A71
KKD19A1
C : 4D024220A
Note:
1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor.
2. Central controls using with VRV controller are available on request. Please consult DAIKIN.
Outdoor Unit
Name of Option
Drain Piping Kit
Kit Name
R25 35J
R50 60G
KIS95
R71FU
KKPJ5F180
KPW937A4
KKP937A4 (Note 1)
C : 3D005955A
Note:
5.1.2
FDBG-A Series
ED41-015B
5.1.3
Optional Accessories
2. Holder
FDBG-A Series
Optional Accessories
ED41-015B
4. Wire Cable
5.1.4
Cable length : 4m
Connecting cable between 1. Digital Remote Controller and 3. Control Board (Box).
HEAT
HIGH
MED
COOL
LOW
POWER
FAN
TEMP +
TEMP -
For other parts 2. Holder, 3. Control Board (Box), 4. Wire Cable will be the same as KRC 47-2.
(P0007)
FDBG-A Series
ED41-015B
5.1.5
Optional Accessories
KRC47-1
ELECTRONIC
CONTROL
TEMPERATURE
CONTROL
CONTROL BOARD
OFF
ON
P1
P2
P3
P4
P5
P6
(ON/OFF)
L
P2
P3
P4
FDBG-AVE
Comp.
(THERMOSTAT)
FAN
(P0008)
KRC47-2
REMOTE CONTROLLER
THERMISTOR
CONTROL BOARD
P8
P9
FDBG-AVE
P4
P3
P2
P1
P7
L
(ON/OFF)
Comp.
(THERMOSTAT)
FAN
FDBG-A Series
P3
P2
P1
(P0009)
Optional Accessories
ED41-015B
KRC47-4
REMOTE CONTROLLER
THERMISTOR
CONTROL BOARD
P8
P9
FDBG-AVE
P4
P3
P2
P1
P7
L
(ON/OFF)
FAN
Comp.
(THERMOSTAT)
P6
P3
P2
P1
DUCT HEATER
(FIELD SUPPLIED)
(P0010)
10
FDBG-A Series
ED41-015B
Dimensions
6. Dimensions
6.1
Indoor Unit
FDBG-A Series
C : 3D024661A
Unit (mm)
FDBG25AVE
11
Dimensions
ED41-015B
12
C : 3D024662A
Unit (mm)
FDBG35AVE
FDBG-A Series
ED41-015B
Dimensions
FDBG-A Series
C : 3D024663A
Unit (mm)
FDBG50AVE
13
Dimensions
ED41-015B
14
C : 3D024664A
Unit (mm)
FDBG60AVE
FDBG-A Series
ED41-015B
Dimensions
FDBG-A Series
C : 3D024665A
Unit (mm)
FDBG71AVE
15
Dimensions
6.2
ED41-015B
Outdoor Unit
R25JV1
R35JV1
Unit (mm)
3D028041A
R50GV1
Unit (mm)
3D004855D
16
FDBG-A Series
ED41-015B
Dimensions
R60GV1
R60GV1K
Unit (mm)
3D004856G
R71FUV1
R71FUY1
396
Unit (mm)
C : 3D001674A
FDBG-A Series
17
Dimensions
6.3
ED41-015B
3D001951A-1
18
FDBG-A Series
ED41-015B
Dimensions
3D001951A-2
FDBG-A Series
19
Piping Diagrams
ED41-015B
7. Piping Diagrams
7.1
FDBG25AVE + R25JV1
INDOOR HEAT EXCHANGER
OUTDOOR UNIT
FILTER
INDOOR UNIT
C : 3D020878D
FDBG35AVE + R35JV1
INDOOR HEAT EXCHANGER
OUTDOOR UNIT
FILTER
INDOOR UNIT
C : 3D020877C
20
FDBG-A Series
ED41-015B
Piping Diagrams
FDBG50AVE + R50GV1
FDBG60AVE + R60GV1
FDBG60AVE + R60GV1K
FDBG-A Series
21
Piping Diagrams
ED41-015B
FDBG71AVE + R71FUV1
FDBG71AVE + R71FUY1
C : 3D001310A
22
FDBG-A Series
ED41-015B
Wiring Diagrams
8. Wiring Diagrams
8.1
Indoor Unit
FDBG25AVE
FDBG35AVE
FDBG50AVE
FDBG60AVE
FDBG71AVE
C : 3D023740C
FDBG-A Series
23
Wiring Diagrams
8.2
ED41-015B
Outdoor Unit
R25JV1
3D024713B
R35JV1
3D024714B
24
FDBG-A Series
ED41-015B
Wiring Diagrams
R50GV1
RED
RED
WHT
BLU
RED
TO INDOOR UNIT
X1M
YLW
6
RED
RED
C11R
3.15A
BLK
BLK
BLK
14
13
BLK
BLK
RED
ORG
RED
BLK
POWER SUPPLY
A2
A1
BLK
RED
M1C
M
1~
X11A
F1U
M
1~
WHT
M1F
C12R
K1M
Q1L
F1S
F2S
C11R,C12R
F1U
F1S
F2S
K1M
L
M1C
:RUNNING CAPACITOR
:FUSE
:SURGE ARRESTER
:SURGE ARRESTER
:COMPRESSOR RELAY
:LIVE
:COMPRESSOR MOTOR
NOTES
1. REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
3D005285A
R60GV1
R60GV1K
RED
X1M
TO INDOOR UNIT
RED
BLU
C
C11R
YLW
2
WHT
RED
RED
RED
L
H
3.15A
BLK
BLK
BLK
13
14
WHT
BLK
RED
BLK
POWER SUPPLY
BLK
ORG
M
1~
RED
A1
A2
K1M
M1C
S1T
F1U
M
1~
WHT
RED
C12R
X11A
M1F
F1S
F2S
C11R,C12R
F1S
F2S
F1U
K1M
L
M1C
:RUNNING CAPACITOR
:SURGE ARRESTER
:SURGE ARRESTER
:FUSE
:COMPRESSOR RELAY
:LIVE
:COMPRESSOR MOTOR
NOTES
1. REFER TO THE NAMEPLATE FOR
THE POWER REQUIREMENTS.
3D004030A
FDBG-A Series
25
Wiring Diagrams
ED41-015B
R71FUV1
3D010789A
R71FUY1
3D000995C
26
FDBG-A Series
ED41-015B
8.3
Wiring Diagrams
Field Wiring
Note:
1.
2.
3.
4.
5.
6.
7.
8.
9.
FDBG-A Series
27
Capacity Table
ED41-015B
9. Capacity Table
9.1
Capacity Table
FDBG25AVE + R25JV1
FDBG
C : 3D008374B
FDBG35AVE + R35JV1
FDBG
C : 3D024206A
28
FDBG-A Series
ED41-015B
Capacity Table
FDBG50AVE + R50GV1
FDBG
C : 3D024207A
FDBG60AVE + R60GV1(K)
7.04
7.22
7.38
7.47
7.51
7.72
7.80
4.46
4.50
4.53
4.56
4.57
4.61
4.63
6.88
7.05
7.22
7.30
7.35
7.55
7.64
4.38
4.43
4.46
4.48
4.49
4.53
4.56
6.65
6.82
6.99
7.07
7.12
7.32
7.41
4.28
4.32
4.35
4.37
4.38
4.43
4.45
6.55
6.73
6.89
6.97
7.03
7.23
7.31
4.23
4.27
4.31
4.33
4.34
4.38
4.40
6.39
6.56
6.73
6.81
6.86
7.06
7.15
4.15
4.20
4.23
4.25
4.26
4.31
4.33
6.19
6.37
6.53
6.62
6.66
6.87
6.95
4.07
4.10
4.14
4.15
4.16
4.22
4.23
FDBG
C : 3D024208A
FDBG-A Series
29
Capacity Table
ED41-015B
FDBG71AVE + R71FUV1
FDBG71AVE + R71FUY1
FDBG
C : 3D024209A
30
FDBG-A Series
ED41-015B
9.2
9.2.1
Capacity Table
Note:
9.2.2
1.
100
(%)
95
90
85
71
80
0
10
15
20
25
30
35
Length of refrigerant piping (Total length)
40
45
50 (m)
(P0015)
Note:
FDBG-A Series
1.
line: Correction factor for cooling capacity
2. The correction ratio remains the same whether the outdoor unit is to be installed above or below the
indoor unit.
31
Fan Performance
ED41-015B
Fan Performance
FDBG25AVE
FDBG35AVE
Note:
32
FDBG-A Series
ED41-015B
Fan Performance
FDBG50AVE
Note:
FDBG-A Series
33
Fan Performance
ED41-015B
FDBG60AVE
FDBG71AVE
Note:
34
FDBG-A Series
ED41-015B
Operation Limit
Operation Limit
R25JV1
R35JV1
R60GV1
R50GV1
R60GV1K
R71FUV1
R71FUY1
FDBG-A Series
35
Sound Level
ED41-015B
Sound Level
Note :
220V
240V
Measuring Location
FDBG25AVE
41
38
43
40
FDBG35AVE
41
38
43
40
FDBG50AVE
41
38
43
40
FDBG60AVE
42
39
45
42
FDBG71AVE
42
39
45
42
FDBG-A
2
DUCT
DUCT
AIR
(SUCTION SIDE)
Microphone
(P1022)
Sound level will be raised more than 5dB, if a suction grille is put exactly under the fan.
Outdoor Unit
dB(A)
Model
220V
240V
R25JV1
46
48
R35JV1
48
49
R50GV1
49
50
R60GV1
R60GV1K
54
54
55
55
R71FUV1
52
380V
415V
52
R71FUY1
Note:
36
50Hz
Measuring Location
R25 35J
R50 60G
R71FU
4D002309
FDBG-A Series
ED41-015B
Sound Level
FDBG60AVE
FDBG71AVE
C : 4D024214
C : 4D024213
Outdoor Unit
R25JV1
R35JV1
4D029157A
R60GV1
R60GV1K
4D000697C
R71FUV1
R71FUY1
DW527-217F
FDBG-A Series
R50GV1
DW525-597E
: 220V, 380V
: 240V, 415V
4D002309
37
Electric Characteristics
ED41-015B
Cooling Only
Unit Combination
Indoor
Outdoor
Power Supply
Hz - Volts
Voltage Range
Compressor
MCA
TOCA
R25JV1
9.05
17.5
(2)
IFM
LRA
RLA
kW
FLA
kW
FLA
15
19.0
20.0
21.0
3.46
3.64
3.82
0.025
0.27
0.045
0.5
(1)
FDBG25AVE
OFM
MFA
6.7
13.9
15
26.0
27.0
28.0
4.90
5.45
5.99
0.025
0.27
0.045
0.5
13.6
20
42
44
46
9.0
9.1
9.1
0.045
0.3
0.045
0.5
R60GV1
R60GV1K
14.5
25
55
58
60
11.9
12.0
12.1
0.053
0.6
0.060
0.7
FDBG71AVE
R71FUV1
16.5
22.1
25
78
12.4
0.050
0.6
0.060
0.7
FDBG71AVE
R71FUY1
6.2
8.1
15
35
4.2
0.050
0.6
0.060
0.7
FDBG35AVE
R35JV1
FDBG50AVE
R50GV1
FDBG60AVE
50 - 220
50 - 230
50 - 240
50 - 380/220
50 - 400/230
50 - 415/240
Max.50Hz 264V
Min.50Hz 198V
Max.50Hz
456/264V
Min.50Hz
342/198V
C : 3D024204
38
FDBG-A Series
ED41-015B
Field Piping
Field piping
R50 60G
25 m
30 m
50 m (Equivalent Length 70 m)
15 m
15 m
30 m
R71FU
y Select the amount of refrigerant which matches a length which exceeds the charge-less length from
Table 1 and 2, and add it.
Write down the amount of extra refrigerant added in accordance with the precaution plate on the rear
surface of the front plate, as this is necessary for after-sales service.
R25J 35J 50G
Table 1
<Unit : g>
Additional Charge
R60G
20g/m (Exceeding 10 m)
20g/m (Exceeding 5 m)
R71FU
Table 2 (The maximum allowable pipe length is 50 meters.)
<unit : kg>
5m
10m
15m
20m
25m
30m
35m
40m
45m
50m
0.13
0.25
0.38
0.50
0.63
0.75
0.88
1.00
1.13
FDBG-A Series
39
Field Piping
ED41-015B
Precautions
5. Close the liquid-side stop valve fully. (Refer to Fig.1) If the valve is not fully closed it could cause burn-out of
the compressor.
6. After the pressure gauge indication has dropped to 0
kgf/cm2G, close the gas stop valve fully and press the
Stop button on the remote controller.
Necessity of a trap
Since there is fear of the oil held inside the riser piping
flowing back into the compressor when stopped and
causing liquid compression phenomenon, or cases of
deterioration of oil return, it will be necessary to provide a
trap at an appropriate place in the riser gas piping.
Indoor unit
Oil trap
Gas piping
Liquid piping
Outdoor unit
Note:
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.
Caution to be taken when brazing refrigerant piping
Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based
flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the
refrigerant oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)
(Remark) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing
temperature and the heating time exceed a certain point, the phoshor changes into the gaseous state
(e.g . BCuP -1 to 5 : between 700 and 800C) which causes pin holes and results in refrigerant leakage.
C : 1PN01324A-2
40
FDBG-A Series
ED41-015B
Installation
15. Installation
15.1
FDBG-A Series
Select an installation site that fulfills the following conditions and meets the customers approval.
Units: mm
H* 270 (Min.)
When exposing the body of this unit, install the unit where
the bottom is move than 2.5 m high so that the user can not
touch.
Use suspension bolts to install the unit. Check whether or
not the ceiling is strong enough to support the weight of
the unit. If there is a risk that the ceiling is not strong
enough, reinforce the ceiling before installing the unit.
400 or more
Gas pipe
Wiring port
Liquid pipe
In case of
bottom
suction
Drain pipe
Units: mm
55
Model
FDBG60 71AVE
755
900
1 155
1300
580
FDBG25 35 50AVE
Units: mm
126
(Installation example)
Ceiling slab
Anchor
Long nut or turn-buckle
Suspension bolt
Indoor unit
FDBG-A Series
41
Installation
ED41-015B
While installing unit, Take care that dust etc. should not drop into the
drainpan.
Use a water level or water-filled vinyl tubes to check that the unit is
level at all four corners as shown in the drawing.
Tighten the top nuts.
Water level
Vinyl tubes
Select an installation site that fulfills the following conditions and meets the customers approval.
It is well-ventilated.
It is safe and can withstand the units weight and vibration. The unit can be installed on a level surface.
The unit does not bother next-door neighbors.
There is no possibility of a flammable gas leak.
The water draining from the outdoor unit will not damage anything.
Sufficient clearance for servicing is ensured.
(Three sides facing three walls)
R25 R35
100 mm
or more
50 mm
or more
R50 R60
150mm
or more
150 mm
or more
100 mm
or more
150 mm
or more
300 mm
or more
A mm
or more
50 mm
or more
50 mm
or more
50 mm
or more
H = 1000 mm or less
Units: mm
Dimension A
300
H = 1000 mm or more
600
C : 1PN04069-1A-2
42
FDBG-A Series
ED41-015B
Installation
Installation
If the unit drains badly, place
it on concrete blocks.
C
B
(Anchor bolt
hole pitch)
Units: mm
C
R25 35
288
470
115
R50
R60
290
330
530
540
100
130
Units: mm
Insulation dimensions
Gas pipe insulation
Thickness
I.D.
R25 12 to 15 mm
10 mm
R35 14 to 16 mm
minimum
R50 60 16 to 20 mm
Inter-unit wiring
O.D.
Thickness
R25
9.5 mm 0.8 mm
R35
12.7 mm 0.8 mm
R50 60 15.9 mm 1.0 mm
Gas pipe
Liquid pipe
Liquid pipe
O.D. ........... 6.4 mm
Thickness .. 0.8 mm
Finishing tape
Drain hose
Insulation material
Polyethylene foam
Heat transfer rate:
0.035 to 0.045 kcal/m hC
Insulate connecting piping
completely.
The highest temperature of
gas piping became 120C.
Use the insulator that the
highest temperature can be
resisted.
NOTE) Be sure that both the gas and liquid pipes are insulated according to the above insulation dimensions.
Remove burrs.
(Cut at exact
right angles.)
Flare.
(Attach at the
exact position
shown below.)
Check.
Dimension
above the die
Die
Rigid Imperial
0.5 mm 1.0 mm
FDBG-A Series
43
Installation
ED41-015B
Providing the connecting piping between the indoor unit and the outdoor unit
Table 1
Clamp 5
(x4)
Flare shape
8.3 to 8.7
12.0 to 12.4
15.4 to 15.8
1420 to 1720Ncm
(144 to 176kgfcm)
3270 to 3990Ncm
9.5
(333 to 407kgfcm)
4950 to 6030Ncm
12.7
(504 to 616kgfcm)
6180 to 7540Ncm
15.9
(630 to 770kgfcm)
6.4
Flare dimension
B (mm)
R0.4 to 0.8
45
Pipe
gauge Tightening torque
90 0.5
Torque wrench
18.6 to 19.0
Sealing pad 4
(Wrap the piping union with the sealing pad.)
Insulation for fitting 2 (for gas piping)
Pipe fixing plate
Insulation for fitting 3 (for liquid piping)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
Gauge manifold
Open
Liquid stop
valve
Gas stop
valve
Service port
Vacuum pump
C : 1PN04069-1A-4
44
FDBG-A Series
ED41-015B
Installation
Rubber plug
Nominal diameter 26
Completely insulate.
Completely insulate.
Do not leave
in water.
Units: mm
Pour some water into the drain pan to check that the water drains smoothly.
Make sure that water does not leak from the drain piping,
connecting parts and the drain plug.
Watering can
C : 1PN04069-1A-5
FDBG-A Series
45
Installation
ED41-015B
Wiring
For models 71, see the installation manual attached to the outdoor unit.
CAUTION
Ground the air conditioner.
When grounding the air conditioner, use a ground wire of 100 or less.
CAUTION
Fan speed
H, L
HH, H
2 to 7 mm H2O
NOTE)Refer to the wiring diagram and to the installation manual of the remote controller.
Line
1 2 3
Earth
terminal
Neutral
Comp.
A B C D E F
To outdoor unit
Ground
Remote controller
Fan speed
control
Line
Neutral
Comp.
A B C D E F
1 2 3
Earth
terminal
: Optional accessory
Power supply
V1-1PH : 50 Hz, 220 to 240 V
The Fuse for interconnection cable is
not built into outdoor unit.
Select the interconnection cable size
with Field fuse. (See right table.)
Indoor unit
To remote controller
Ground
To outdoor unit
1 2 3
Ground
leakage
breaker
Safety breaker
R25 35JV1 : 15A
R50GV1
: 20A
R60GV1
: 25A
L N
Outdoor unit
C : 1PN04069-1A-6
46
FDBG-A Series
ED41-015B
Installation
When using the optional KRC47-1 or the KRC47-2 remote controllers, which have three fan speed settings, refer to the
following.
Remote Controller
Neutral F
Line E
Low B
Comp. D
Neutral F
Line E
Low C
High
MediumB
Comp. D
To indoor unit
High
To indoor unit
Remote Controller
Indoor unit
Wire
Ring type terminal
Connect wires
of the same
gauge on both
sides.
Do not connect
wires of the same
gauge to only one
side.
Do not connect
wires of different
gauges.
Outdoor unit
Terminal block
Terminal block
Earth terminal
Wire clamp
Wire plate
Ground
screw
Service
cover
C : 1PN04069-1A-7
FDBG-A Series
47
Installation
ED41-015B
C : 1PN04069-1A-8
48
FDBG-A Series
Certificate Number.
Dealer
Head Office:
Umeda Center Bldg., 4-12, Nakazaki-Nishi
2-chome, Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 18-1, Konan
2-chome, Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
The specifications, designs, and information in this brochure are subject to change without notice.
ED 41-015B
Printed in Japan 05/2005 FS