Table 4.

34 Summary of Short Circuit Calculation

ANSI
NETWORK

Momentary

Interrupting

Fault Type

ISC F1 (kA)

ISC at F2 (kA)

ISC at F3 (kA)

ISC at F4 (kA)

13.8kV Power Plant


Bus

Primary terminals of
TRM1

6.9kV switchgear
(bus)

Primary terminals
TRL3A

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS

Asym,
RMS

Asym,
Peak

Three-Phase

23.24

37.52

62.39

23.09

37.1

61.77

20.12

32.42

53.93

19.61

29.7

50.15

Single-Lineto-ground

23.34

37.77

62.77

23.21

37.19

61.96

22.88

37

61.5

22.24

30.95

53.25

Line-to-Line

20.13

32.49

54.03

19.99

32.13

53.49

17.42

28.07

46.71

16.98

25.72

43.43

Double-lineto-ground Ib

23.22

37.54

62.4

23.14

37.24

61.98

21.74

35.12

58.39

22.33

32.86

55.85

Double-lineto-ground Ic

23.36

37.75

62.76

23.16

37.26

62.01

22.05

35.63

59.24

20.15

29.65

50.39

Three-Phase

20.44

Single-Lineto-ground

21.38

Line-to-Line

17.7

17.59

15.6

15.24

Double-lineto-ground Ib

20.91

20.85

19.98

20.55

Double-lineto-ground Ic

20.98

20.81

20.13

18.45

20.31
23.80

21.27

18.01
23.04

21.01

17.6
23.42

20.49

20.49

Note: highlighted values are the maximum values of short circuit current within the same ANSI network and fault point location

Chapter 4-Short Circuit Calculation

Page 266

(Continuation) Table 4.30 Summary of Short Circuit Calculation

ANSI
NETWORK

Fault Type

ISC at F5 (kA)

ISC at F6 (kA)

ISC at F7 (kA)

Primary terminals
TRL3B

MCC8 Bus

MCC9 Bus

Sym,
RMS

Momentary

Interrupting

Asym,
RMS

Asym,
Peak

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS

Asym,
RMS

Asym,
Peak

Three-Phase

19.56

29.43

49.77

46

61.18

106.2

47

62.26

108.2

Single-Line-to-ground

22.17

30.41

52.48

47.71

63.27

109.9

48.43

64.04

111.3

Line-to-Line

16.94

25.49

43.11

39.84

52.98

91.99

40.7

53.92

93.69

Double-line-to-ground Ib

22.38

32.65

55.6

46.81

62.16

108

47.56

62.95

109.4

Double-line-to-ground Ic

19.94

29.1

49.54

47.02

62.44

108.4

47.94

63.45

110.3

Three-Phase

17.56

Single-Line-to-ground

20.42

Line-to-Line

15.2

Double-line-to-ground Ib

20.59

Double-line-to-ground Ic

18.27

20.59

Note: highlighted values are the maximum values of short circuit current within the same ANSI network and fault point location

Chapter 4-Short Circuit Calculation

Page 267

ANSI
NETWORK

Fault Type

ISC F8 (kA)

ISC at F9 (kA)

ISC at F10 (kA)

ISC at F11 (kA)

PE-KM5806
Terminals

PE-YM7601
Terminals

PE-KM8639
Terminals

PE-KM8601
Terminals

Sym,
RMS

Momentary

Asym,
RMS

Asym,
Peak

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS

Three-Phase

16.91

16.92

17.8

16.06

Single-Lineto-ground

18.01

18.35

19.55

16.562

Line-to-Line

14.65

14.66

15.416

13.91

Double-lineto-ground Ib

20.56

20.35

21.64

19.33

Double-lineto-ground Ic

12.99

14.16

14.92

11.7

Chapter 4-Short Circuit Calculation

Asym,
RMS

Asym,
Peak

Page 268

ISC at F12 (kA)


ANSI
NETWORK

Fault Type

PC001 Terminals
Sym,
RMS

Momentary

Asym,
RMS

Asym,
Peak

GM1412 Terminals

GM1413 Terminals

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS

19.78

2.22

2.22

Single-Line-to-ground

22.49

Line-to-Line

17.13

1.56
1.920

1.56
1.920

Double-line-to-ground Ib

22.07

2.133

2.133

Double-line-to-ground Ic

20.95

1.882

1.882

Fault Type

Three-Phase

Asym,
Peak

ISC at F17 (kA)

KM5814 Terminals

GM8103A Terminals

GM8103S Terminals

Sym,
RMS

Sym,
RMS

Sym,
RMS

Asym,
RMS

Asym,
Peak

Asym,
RMS

Asym,
Peak

2.51

2.51

Line-to-Line

3.80
4.552

2.23
2.172

2.23
2.172

Double-line-to-ground Ib

5.256

2.529

2.529

Double-line-to-ground Ic

4.245

2.242

2.242

Chapter 4-Short Circuit Calculation

Asym,
RMS

ISC at F16 (kA)

5.26

Single-Line-to-ground
Momentary

ISC at F14 (kA)

Three-Phase

ISC at F15 (kA)


ANSI
NETWORK

ISC at F13 (kA)

Asym,
RMS

Asym,
Peak

Page 269

ISC at F18 (kA)


ANSI
NETWORK

Fault Type

MNDB Terminals
Sym,
RMS

Three-Phase

Asym,
Peak

YM7607 Terminals

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS
23.44

25.95
23.497

25.95
23.497

21.87
20.303

Double-line-to-ground Ib

29.382

29.382

24.477

Double-line-to-ground Ic

23.193

23.193

20.764

Line-to-Line

Fault Type

SM8645 Terminals
Sym,
RMS

Three-Phase

Asym,
RMS

Asym,
Peak

GM7612 Terminals

7601M1 Terminals

Sym,
RMS

Asym,
RMS

Asym,
Peak

Sym,
RMS
2.60

7.678
8.427

3.776
4.215

1.785
2.247

Double-line-to-ground Ib

10.028

4.979

2.518

Double-line-to-ground Ic

7.770

3.903

2.159

Chapter 4-Short Circuit Calculation

Asym,
Peak

ISC at F23 (kA)

4.87

Line-to-Line

Asym,
RMS

ISC at F22 (kA)

9.73

Single-Line-to-ground
Momentary

EMBD Terminals

27.13

ISC at F21 (kA)


ANSI
NETWORK

ISC at F20 (kA)

27.13

Single-Line-to-ground
Momentary

Asym,
RMS

ISC at F19 (kA)

Asym,
RMS

Asym,
Peak

Page 270

ISC at F24 (kA)


ANSI
NETWORK

Fault Type

KM8607 Terminals
Sym,
RMS

Three-Phase
Single-Line-to-ground
Momentary

Line-to-Line

1.89

1.381
1.637

Double-line-to-ground Ib

1.818

Double-line-to-ground Ic

1.625

Chapter 4-Short Circuit Calculation

Page 271

ANSI
NETWORK

Fault
Type

Momentar
y

ThreePhase
SingleLinetoground
Lineto-Line
Double
-linetoground
Ib
Double
-linetoground
Ic

ISC F1 (kA)
13.8kV Power Plant
Bus
ISYSTEM
ILOAD
( Sym,
( Sym,
RMS)
RMS)

ISC at F2 (kA)
Primary terminals of
TRM1
ISYSTEM
ILOAD
( Sym,
( Sym,
RMS)
RMS)

ISC at F3 (kA)
6.9kV switchgear
(bus)
ISYSTEM
ILOAD
( Sym,
( Sym,
RMS)
RMS)

ISC at F4 (kA)
Primary terminals
TRL3A
ISYSTEM
ILOAD
( Sym,
( Sym,
RMS)
RMS)

21.71

1.542

21.558

1.543

16.676

3.477

19.456

0.173

22.318

1.032

22.191

1.034

20.270

2.636

22.124

0.130

18.804

1.335

18.670

1.336

14.442

3.011

16.849

0.150

22.012

1.358

21.939

1.351

20.719

1.188

21.286

1.191

22.034

1.362

21.846

1.351

20.911

1.197

19.081

1.132

Chapter 4-Short Circuit Calculation

Page 272

ANSI
NETWORK

Fault
Type

Momentary

ThreePhase
SingleLinetoground
Lineto-Line
Doubleline-toground
Ib
Doubleline-toground
Ic

ISC F5 (kA)
Primary Terminal of TRL3B
ISYSTEM
ILOAD
( Sym,
( Sym,
RMS)
RMS)

ISC at F6 (kA)
MCC8
ISYSTEM
ILOAD
( Sym,
( Sym,
RMS)
RMS)

ISC at F7 (kA)
MCC9
ISYSTEM
ILOAD
( Sym,
( Sym,
RMS)
RMS)

19.341

0.239

43.542

2.609

43.501

3.684

22.002

0.181

46.011

1.804

46.019

2.530

16.749

0.207

37.708

2.259

37.673

3.191

21.329

1.191

44.417

2.696

45.119

2.751

18.879

1.125

44.402

2.702

45.266

2.761

Chapter 4-Short Circuit Calculation

Page 273