PARAMETER LIST

AGC Automatic Gen-set Controller


PARAMETER LIST

• Alarm list
• Parameter list

Document no.: 4189340563C


AGC-3 Alarm and Parameter List

Table of contents

1. ABOUT THIS DOCUMENT................................................................................................ 5


GENERAL PURPOSE...................................................................................................................... 5
INTENDED USERS ......................................................................................................................... 5
CONTENTS/OVERALL STRUCTURE ................................................................................................. 5
2. WARNINGS AND LEGAL INFORMATION........................................................................ 6
LEGAL INFORMATION AND RESPONSIBILITY .................................................................................... 6
ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 6
SAFETY ISSUES ............................................................................................................................ 6
DEFINITIONS ................................................................................................................................ 6
3. ALARM LIST ...................................................................................................................... 7
ALARM TABLE OVERVIEW .............................................................................................................. 8
REVERSE POWER AND OVERCURRENT PROTECTION..................................................................... 11
VOLTAGE PROTECTIONS ............................................................................................................. 14
FREQUENCY PROTECTIONS......................................................................................................... 16
BUSBAR VOLTAGE PROTECTIONS ................................................................................................ 19
BUSBAR FREQUENCY PROTECTIONS ............................................................................................ 22
MAINS FAILURE PROTECTIONS .................................................................................................... 25
OVERLOAD PROTECTIONS .......................................................................................................... 26
CURRENT UNBALANCE PROTECTION ............................................................................................ 28
VOLTAGE UNBALANCE PROTECTION ............................................................................................ 28
REACTIVE POWER IMPORT (LOSS OF EXCITATION) PROTECTION .................................................... 29
REACTIVE POWER EXPORT (OVEREXCITATION) PROTECTION ........................................................ 29
NEGATIVE SEQUENCE................................................................................................................. 30
ZERO SEQUENCE ....................................................................................................................... 31
DIRECTIONAL OVERCURRENT PROTECTION .................................................................................. 32
BUSBAR UNBALANCE VOLTAGE ................................................................................................... 33
TIME-DEPENDENT UNDERVOLTAGE.............................................................................................. 33
NON-ESSENTIAL LOAD TRIP (LOAD SHEDDING) ............................................................................. 36
UNDERVOLTAGE AND REACTIVE POWER LOW ............................................................................... 38
SYNCHRONISATION AND BREAKER ALARMS .................................................................................. 39
SYNCHRONISATION AND BREAKER ALARMS .................................................................................. 39
REGULATION ALARMS ................................................................................................................. 42
DIGITAL INPUT 23-27 SETUP ....................................................................................................... 43
DIGITAL INPUT 43-55 SETUP ....................................................................................................... 43
DIGITAL INPUT 91-97 SETUP ....................................................................................................... 44
DIGITAL INPUT 102-108 SETUP ................................................................................................... 45
DIGITAL INPUT 112-117 SETUP ................................................................................................... 46
EMERGENCY STOP ..................................................................................................................... 47
DIGITAL INPUT 127-133 SETUP ................................................................................................... 47
ANALOGUE INPUT SETUP (OPTION M15.6) ................................................................................... 48
MULTI-FUNCTIONAL ANALOGUE INPUT SETUP ............................................................................... 52
SPEED AND RUNNING FEEDBACK SETUP ...................................................................................... 64
ANALOGUE INPUT SETUP (OPTION M15.8) ................................................................................... 66
AUX. SUPPLY SETUP ................................................................................................................... 69
STOP COIL WIREBREAK AND INTERNAL COMMUNICATION ALARMS .................................................. 70
ENGINE HEATER FAILURE ............................................................................................................ 70
BATTERY TESTS ......................................................................................................................... 71
MAX. VENTILATION ..................................................................................................................... 73
SWITCHBOARD ERROR ............................................................................................................... 74
SWITCHBOARD ERROR ............................................................................................................... 74
EXTERNAL COMMUNICATION ERROR ............................................................................................ 75
ENGINE INTERFACE COMMUNICATION ALARMS ............................................................................. 76

DEIF A/S Page 2 of 137


AGC-3 Alarm and Parameter List

POWER MANAGEMENT COMMUNICATION ERROR........................................................................... 79


INTERNAL CAN COMMUNICATION ERROR ..................................................................................... 79
EXTERNAL I/O ALARM SETUP ...................................................................................................... 80
4. PARAMETER LIST .......................................................................................................... 82
PARAMETER TABLE OVERVIEW .................................................................................................... 82
SYNCHRONISATION .................................................................................................................... 85
REGULATION .............................................................................................................................. 87
DIGITAL OUTPUT SETUP .............................................................................................................. 92
ANALOGUE OUTPUT LIMITS ......................................................................................................... 96
TRANSDUCER OUTPUTS .............................................................................................................. 97
REGULATOR OUTPUT SELECTION .............................................................................................. 101
SYSTEM................................................................................................................................... 102
GENERAL SETUP ...................................................................................................................... 102
COUNTERS AND TIMERS ........................................................................................................... 104
ALARM HORN ........................................................................................................................... 105
RUN COIL SETUP ...................................................................................................................... 105
RUNNING, START AND STOP ...................................................................................................... 106
BREAKER CONTROL .................................................................................................................. 107
POWER DERATE ....................................................................................................................... 108
IDLE START .............................................................................................................................. 108
ENGINE HEATER ....................................................................................................................... 109
ANALOGUE LOAD SHARING LINES OUTPUT.................................................................................. 109
MASTER CLOCK........................................................................................................................ 110
COOLING VENTILATION ............................................................................................................. 110
SUMMER/WINTER TIME ............................................................................................................. 110
FUEL TRANSFER PUMP LOGIC.................................................................................................... 111
ALARM JUMP ............................................................................................................................ 111
MAINS SETUP ........................................................................................................................... 112
TEST ....................................................................................................................................... 113
CONTROLLER SETTINGS ........................................................................................................... 113
MAINS FAILURE ........................................................................................................................ 114
Y1(X1) DROOP CURVE ............................................................................................................. 115
Y2(X2) DROOP CURVE ............................................................................................................. 116
EXTERNAL COMMUNICATION ..................................................................................................... 118
POWER MANAGEMENT INTERNAL COMMUNICATION ..................................................................... 118
ENGINE INTERFACE COMMUNICATION ........................................................................................ 119
EXTERNAL I/O COMMUNICATION SETUP ..................................................................................... 120
EVENT PRINTER ....................................................................................................................... 121
POWER MANAGEMENT SETUP ................................................................................................... 122
JUMP MENUS............................................................................................................................ 128
COMMAND TIMERS ................................................................................................................... 132
GSM SETTINGS ....................................................................................................................... 133
PASSWORDS............................................................................................................................ 133
VDO 102 ................................................................................................................................ 134
VDO 105 ................................................................................................................................ 136
VDO 108 ................................................................................................................................ 136
MULTI-INPUT SELECTIONS......................................................................................................... 136
EXTERNAL DIGITAL OUTPUTS .................................................................................................... 137
EXTERNAL MODULE STATUS ...................................................................................................... 137

DEIF A/S Page 3 of 137


AGC-3 Alarm and Parameter List

This document is valid for the following products:

AGC Software version 3.5X.X or later.

DEIF A/S Page 4 of 137


AGC-3 Alarm and Parameter List

1. About this document

This chapter includes general user information about this handbook concerning the general
purpose, the intended users and the overall contents and structure.

General purpose
This document is the complete parameter list for DEIF’s Multi-line units with software version 3.
The document includes all parameters, which means that some of the option parameters included
may not be accessible in the system in question.

Intended users
The parameter list is mainly intended for the person responsible for the unit parameter setup. In
most cases, this would be a panel builder designer. Naturally, other users might also find useful
information here.

Contents/overall structure
The Parameter List is divided into chapters and in order to make the structure of the document
simple and easy to use, each chapter will begin from the top of a new page. The following will
outline the contents of each of the chapters.

About this document


This first chapter includes general information about this handbook as a document. It deals with
the general purpose and the intended users of the Parameter List. Furthermore, it outlines the
overall contents and structure of the document.

Warnings and legal information


The second chapter includes information about general legal issues and safety precautions
relevant in the handling of DEIF products. Furthermore, this chapter will introduce note and warning
symbols, which will be used throughout the handbook.

Procedure for parameter setup


This chapter deals with the procedure to be followed, when the parameters are set up or changed.
By use of various illustrations this chapter will guide the user through the procedure for parameter
setup step by step.

Alarm list
This chapter includes a complete standard alarm list for setup. Therefore, this chapter is to be
used for reference, when information about specific alarms is needed.

Parameter list
This chapter includes a complete standard parameter list for setup. Therefore, this chapter is to be
used for reference, when information about specific parameters is needed.

DEIF A/S Page 5 of 137


AGC-3 Alarm and Parameter List

2. Warnings and legal information

This chapter includes important information about general legal issues relevant in the handling of
DEIF products. Furthermore, some overall safety precautions will be introduced and
recommended. Finally, the highlighted notes and warnings, which will be used throughout this
handbook, are presented.

Legal information and responsibility


DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt
about how to install or operate the generator set controlled by the unit, the company responsible for
the installation or the operation of the set must be contacted.

The units are not to be opened by unauthorised personnel. If opened anyway, the
warranty will be lost.

Electrostatic discharge awareness


Sufficient care must be taken to protect the terminals against static discharges during the
installation. Once the unit is installed and connected, these precautions are no longer necessary.

Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorised personnel who understand the risks involved in working
with live electrical equipment.

Be aware of the hazardous live currents and voltages. Do not touch any AC
measurement inputs as this could lead to injury or death.

Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.

Notes

The notes provide general information which will be helpful for the reader to
bear in mind.

Warnings

The warnings indicate a potentially dangerous situation which could result in


death, personal injury or damaged equipment, if certain guidelines are not
followed.

DEIF A/S Page 6 of 137


AGC-3 Alarm and Parameter List

3. Alarm list

In the following, these abbreviations are used:


G: Generator
GB: Generator breaker
TB: Tie breaker (for mains unit)
MB: Mains breaker
BTB: Bus tie breaker
BA: Busbar A (BTB unit)
BB: Busbar (BTB unit: Busbar B)
N/A: Not available

This chapter includes a complete alarm list, including all possible options. Therefore, this
chapter is to be used for reference when specific information about the individual parameters is
needed for the unit setup. An overview list can be seen on the next page.

The table consists of the following possible adjustments:

Setpoint: The alarm setpoint is adjusted in the setpoint menu. The setting is a percentage
of the nominal values.

Delay: The timer setting is the time that must expire from the alarm level is reached
until the alarm occurs.

Relay output A: A relay can be activated by output A.

Relay output B: A relay can be activated by output B.

Enable: The alarm can be activated or deactivated. ON means always activated, RUN
means that the alarm has run status. This means it is activated when the
running signal is present.

Fail class: When the alarm occurs the unit will react depending on the selected fail class.

Fail classes are:

Fail class DG (diesel Mains unit BTB (bus tie


generator) breaker)
F1 Block Block Block
F2 Warning Warning Warning
F3 Trip GB Trip TB Trip BTB
F4 Trip + Stop Trip MB N/A
F5 Shutdown N/A N/A
F6 Safety stop N/A N/A
F7 N/A N/A N/A
F8 N/A N/A N/A

Small differences due to the character of the parameters may exist between the
individual tables.

DEIF A/S Page 7 of 137


AGC-3 Alarm and Parameter List

It is also possible to configure the


parameters by using the PC utility
software. It will be possible to make the
same configurations as described above.

By using the PC utility software, extra


functionality is available. For all the
protections it is possible to make an
automatic acknowledgement of the
alarm.

Alarm table overview

Protection - Analogue input setup


1000 G/M/BA -P> 1 4000 4-20 mA 91.1
1010 G/M/BA -P> 2 4010 4-20 mA 91.2
1030 G/M/BA I> 1 4020 W. fail ana 91
1040 G/M/BA I> 2 4030 4-20 mA 93.1
1050 G/M/BA I> 3 4040 4-20 mA 93.2
1060 G/M/BA I> 4 4050 W. fail ana 93
4060 4-20 mA 95.1
1100 G Iv > 1-6 4070 4-20 mA 95.2
1110 G Iv > 4080 W. fail ana 95
1130 G/M/BA I>> 1 4090 4-20 mA 97.1
1140 G/M/BA I>> 2 4100 4-20 mA 97.2
1150 G/M/BA U> 1 4110 W. fail ana 97
1160 G/M/BA U> 2
1170G/M/BA U< 1 Multi-analogue input setup (-contd)
1180 G/M/BA U< 2 4120 4-20mA 102.1
1190 G/M/BA U< 3 4130 4-20mA 102.2
1200 G/M/BA voltage trip 4140 V DC 102.1
1210 G/M/BA f> 1 4150 V DC 102.2
1220 G/M/BA f> 2 4160 PT 102.1
1230 G/M/BA f> 3 4170 PT 102.2
1240 G/M/BA f< 1 4180 VDO oil 102.1
1250 G/M/BA f< 2 4190 VDO oil 102.2
1260 G/M/BA f< 3 4200 VDO water 102.1
1270 BB U> 1 4210 VDO water 102.2
1280 BB U> 2 4220 VDO fuel 102.1
1290 BB U> 3 4230 VDO fuel 102.2
1300 BB U< 1 4240 W. fail 102
1310 BB U< 2 4250 4-20mA 105.1
1320 BB U< 3 4260 4-20mA 105.2
1330 BB U< 4 4270 V DC 105.1
1340 BB Voltage trip 4280 V DC 105.2
1350 BB f> 1 4290 PT 105.1
1360 BB f> 2 4300 PT 105.2
1370 BB f> 3 4310 VDO oil 105.1

DEIF A/S Page 8 of 137


AGC-3 Alarm and Parameter List

1380 BB f< 1 4320 VDO oil 105.2


1390 BB f< 2 4330 VDO water 105.1
1400 BB f< 3 4340 VDO water 105.2
1410 BB f< 4 4350 VDO fuel 105.1
1420 df/dt (ROCOF) 4360 VDO fuel 105.2
1430 Vector jump 4370 W. fail 105
1440 BB pos seq volt 4380 4-20mA 108.1
1450 G/M/BA P> 1 4390 4-20mA 108.2
1460 G/M/BA P> 2 4400 V DC 108.1
1470 G/M/BA P> 3 4410 V DC 108.2
1480 G/M/BA P> 4 4420 PT 108.1
1490 G/M/BA P> 5 4430 PT 108.2
1500 G/M Unbalance current 4440 VDO oil 108.1
1510 G/M Unbalance volt 4450 VDO oil 108.2
1520 G -Q> 4460 VDO water 108.1
1530 G Q> 4470 VDO water 108.2
1540 G/M Neg. Seq. current 4480 VDO fuel 108.1
1550 G/M Neg. seq. voltage 4490 VDO fuel 108.2
1560 Neg. seq. select 4500 W. fail 108
1570 G/M/BA zero seq. current 4510 Overspeed 1
1580 G/M/BA zero seq. Voltage 4520 Overspeed 2
1590 Zero seq. Select 4530 Crank failure
1600 G/M/BA Directional overcurrent 1 4540 Run feedb. fail
1610 G/M/BA Directional overcurrent 2 4550 MPU wirebreak
1620 BB Unbalance U 4560 Hz/V failure
1630 Ut< SP 1-3 1 4570 Start failure
1640 Ut< SP 4-6 1 4580 Stop failure
1650 Ut< Activate 1
1660 Ut< 1 4960 U< aux. term. 1
1670 Ut< SP 1-3 2 4970 U> aux. term. 1
1680 Ut< SP 4-6 2 4980 U< aux. term.98
1690 Ut< Activate 2 4990 U> aux. term.98
1700 Ut< 2
1800 NEL 1 I> System
1810 NEL 2 I> - General setup
1820 NEL 3 I> 6270 Stop coil wire fail
1830 NEL 1 BB f> 6280 Int. comm. fail
1840 NEL 2 BB f> 6330 Engine heater 1
1850 NEL 3 BB f>
1860 NEL 1 P> 6410 Battery test
1870 NEL 2 P> 6420 Auto battery test
1880 NEL 3 P> 6430 Battery asymmetry
1890 NEL 1 P>> 6440 Battery asymmetry 1
1900 NEL 2 P>> 6450 Battery asymmetry 2
1910 NEL 3 P>>
1960 U and Q < 1 6470 Max ventilation 1
1970 U and Q < 2 6480 Max ventilation 2
1980 GB ext. tripped
6500 Blk. Swbd error
Control 6510 Stp. Swbd error
- Synchronisation
2120 Sync window 6540 Not in Auto
2130 GB/TB/BTB sync failure
2140 MB sync failure System
2150 Phase seq error - Communication
2160 GB/TB/BTB open fail 7520 Ext. Comm. Error
2170 GB//TB/BTB close fail 7530 CAN fail mode
2180 GB/TB/BTB pos. fail
2200 MB open fail 7570 EI comm. Error
2210 MB close fail 7580 EIC warning
2220 MB pos. fail 7590 EIC shutdown
2270 Close before excitation fail 7600 EIC overspeed
7610 EIC coolant t. 1
- Regulation 7620 EIC coolant t. 2
2560 GOV reg. fail 7630 EIC oil press. 1

DEIF A/S Page 9 of 137


AGC-3 Alarm and Parameter List

2630 Deload error 7640 EIC oil press. 2


2680 AVR reg. fail 7650 EIC oil temp. 1
7660 EIC oil temp. 2
Input/output
- Binary input setup 7870 Any BTB missing/appl Hazard
3000 Dig input 23
3010 Dig. input 24 7930 CAN 1 Comm error
3020 Dig. input 25 7940 CAN 2 Comm error
3030 Dig. input 26
3040 Dig. input 27 - External I/O
12000 Ext. Ain 1.1
3130 Dig. Input 43 12010 Ext. Ain 1.2
3140 Dig. Input 44
3150 Dig. Input 45 12030 Ext. Ain 2.1
3160 Dig. Input 46 12040 Ext. Ain 2.2
3170 Dig. Input 47
3180 Dig. Input 48 12060 Ext. Ain 3.1
3190 Dig. Input 49 12070 Ext. Ain 3.2
3200 Dig. Input 50
3210 Dig. Input 51 12090 Ext. Ain 4.1
3220 Dig. Input 52 12100 Ext. Ain 4.2
3230 Dig. Input 53
3240 Dig. Input 54 12120 Ext. Ain 5.1
3250 Dig. Input 55 12130 Ext. Ain 5.2

3330 Dig. Input 91 12150 Ext. Ain 6.1


3340 Dig. Input 92 12160 Ext. Ain 6.2
3350 Dig. Input 93
3360 Dig. Input 94 12180 Ext. Ain 7.1
3370 Dig. Input 95 12190 Ext. Ain 7.2
3380 Dig. Input 96
3390 Dig. Input 97 12210 Ext. Ain 8.1
12220 Ext. Ain 8.2
3400 Dig. input 102
3410 Dig. input 105 12540 Ext dig. In 1
3420 Dig. input 108 12550 Ext dig. In 2
12560 Ext dig. In 3
3430 Dig. input 112 12570 Ext dig. In 4
3440 Dig. input 113 12580 Ext dig. In 5
3450 Dig. input 114 12590 Ext dig. In 6
3460 Dig. input 115 12600 Ext dig. In 7
3470 Dig. input 116 12610 Ext dig. In 8
3480 Dig. input 117 12620 Ext dig. In 9
12630 Ext dig. In 10
3490 Emergency stop 12640 Ext dig. In 11
12650 Ext dig. In 12
3500 Dig. input 127 12660 Ext dig. In 13
3510 Dig. input 128 12670 Ext dig. In 14
3520 Dig. input 129 12680 Ext dig. In 15
3530 Dig. input 130 12690 Ext dig. In 16
3540 Dig. input 131
3550 Dig. input 132
3560 Dig. input 133

DEIF A/S Page 10 of 137


AGC-3 Alarm and Parameter List

Reverse power and overcurrent protection

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1000 G/M/BA reverse power 1

G/M/BA -110.0% Designer’s The alarm and fail class


1001 Setpoint -10.0%
–P> 1 0.0% Reference are activated when the
G/M/BA 0.1 s Handbook reverse power has been
1002 Delay 5.0 s continuously above the
–P> 1 300.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1003 Option Not used delay.
–P> 1 output A
dependent
Not used
G/M/BA Relay
1004 Option Not used
–P> 1 output B
dependent
G/M/BA OFF
1005 Enable ON
–P> 1 ON
G/M/BA Trip GB
1006 Fail class F1…F7
–P> 1 (F3)

1010 G/M/BA reverse power 2

G/M/BA -110.0% Designer’s The alarm and fail class


1011 Setpoint -15.0%
–P> 2 0.0% Reference are activated when the
G/M/BA 0.1 s Handbook reverse power has been
1012 Delay 1.0 s continuously above the
–P> 2 300.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1013 Option Not used delay.
–P> 2 output A
dependent
Not used
G/M/BA Relay
1014 Option Not used
–P> 2 output B
dependent
G/M/BA OFF
1015 Enable ON
–P> 2 ON
G/M/BA Trip GB
1016 Fail class F1…F7
–P> 2 (F3)

1030 G/M/BA overcurrent 1

G/M/BA 50.0% Designer’s The alarm and fail class


1031 Setpoint 110.0%
I> 1 200.0% Reference are activated when the
G/M/BA 0.1 s Handbook current has been
1032 Delay 20.0 s continuously above the
I> 1 3200.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1033 Option Not used delay.
I> 1 output A
dependent
Not used
G/M/BA Relay
1034 Option Not used
I> 1 output B
dependent
G/M/BA OFF
1035 Enable ON
I> 1 ON
G/M/BA Trip GB
1036 Fail class F1…F7
I> 1 (F3)

1040 G/M/BA overcurrent 2

G/M/BA 50.0% Designer’s The alarm and fail class


1041 Setpoint 120.0%
I> 2 200.0% Reference are activated when the

DEIF A/S Page 11 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

G/M/BA 0.1 s Handbook current has been


1042 Delay 10.0 s
I> 2 3200.0 s continuously above the
Not used programmed value
G/M/BA Relay during the programmed
1043 Option Not used
I> 2 output A delay.
dependent
Not used
G/M/BA Relay
1044 Option Not used
I> 2 output B
dependent
G/M/BA OFF
1045 Enable ON
I> 2 ON
G/M/BA Trip GB
1046 Fail class F1…F7
I> 2 (F3)

1050 G/M/BA overcurrent 3

G/M/BA 50.0% Designer’s The alarm and fail class


1051 Setpoint 130.0%
I> 3 200.0% Reference are activated when the
G/M/BA 0.1 s Handbook current has been
1052 Delay 3.0 s continuously above the
I> 3 3200.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1053 Option Not used delay.
I> 3 output A
dependent
Not used
G/M/BA Relay
1054 Option Not used
I> 3 output B
dependent
G/M/BA OFF
1055 Enable ON
I> 3 ON
G/M/BA Trip GB
1056 Fail class F1…F7
I> 3 (F3)

1060 G/M/BA overcurrent 4

G/M/BA 50.0% Designer’s The alarm and fail class


1061 Setpoint 140.0%
I> 4 200.0% Reference are activated when the
G/M/BA 0.1 s Handbook current has been
1062 Delay 1.0 s continuously above the
I> 4 3200.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1063 Option Not used delay.
I> 4 output A
dependent
Not used
G/M/BA Relay
1064 Option Not used
I> 4 output B
dependent
G/M/BA OFF
1065 Enable ON
I> 4 ON
G/M/BA Trip GB
1066 Fail class F1…F7
I> 4 (F3)

1100 Voltage dependent overcurrent curve setting

@50% Designer’s Settings relate to


Setpoint 50.0%
1101 G Iv > 110.0% nom. Reference nominal generator
I1 200.0%
voltage Handbook current.
@60% The condition has to be
Setpoint 50.0% true i.e.
1102 G Iv > 125.0% nom.
I2 200.0% I1<I2<I3<I4<I5<I6.
voltage
If this is not fulfilled, the
@70% worst-case setpoint I1
Setpoint 50.0%
1103 G Iv > 140.0% nom. will be used.
I3 200.0%
voltage

DEIF A/S Page 12 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

@80%
Setpoint 50.0%
1104 G Iv > 155.0% nom.
I4 200.0%
voltage
@90%
Setpoint 50.0%
1105 G Iv > 170.0% nom.
I5 200.0%
voltage
@100
Setpoint 50.0%
1106 G Iv > 200.0% % nom.
I6 200.0%
voltage

1110 Voltage dependent overcurrent alarm

0.1 s Designer’s The alarm and fail class


1111 G Iv > Timer 1.0 s
300.0 s Reference are activated when the
Not used Handbook overcurrent has been
Relay continuously above the
1112 G Iv > Option Not used
output A programmed value
dependent
during the programmed
Not used delay. Values are set in
Relay
1113 G Iv > Option Not used parameters 1101-1106.
output B
dependent
OFF
1114 G Iv > Activate ON
ON
Trip GB
1115 G Iv > Fail class F1…F7
(F3)

1130 G/M/BA fast overcurrent 1

G/M/BA 150.0% Designer’s The alarm settings


1131 Setpoint 200.0%
I>> 1 350.0% Reference relate to the nominal
G/M/BA 0.0 s Handbook current setting.
1132 Delay 0.5 s The alarm and fail class
I>> 1 100.0 s
are activated when the
Not used current has been
G/M/BA Relay
1133 Option Not used continuously above the
I>> 1 output A
dependent programmed value
Not used during the programmed
G/M/BA Relay
1134 Option Not used delay.
I>> 1 output B
dependent
G/M/BA OFF
1135 Enable OFF
I>> 1 ON
G/M/BA Trip GB
1136 Fail class F1…F7
I>> 1 (F3)

1140 G/M/BA fast overcurrent 2

G/M/BA 50.0% Designer’s The alarm and fail class


1141 Setpoint 300.0%
I>> 2 200.0% Reference are activated when the
G/M/BA 0.1 s Handbook current has been
1142 Delay 0.2 s continuously above the
I>> 2 100.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1143 Option Not used delay
I>> 2 output A
dependent
Not used
G/M/BA Relay
1144 Option Not used
I>> 2 output B
dependent
G/M/BA OFF
1145 Enable OFF
I>> 2 ON
G/M/BA Trip GB
1146 Fail class F1…F7
I>> 2 (F3)

DEIF A/S Page 13 of 137


AGC-3 Alarm and Parameter List

Voltage protections

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1150 G/M/BA overvoltage 1

G/M/BA 100.0% Designer’s The alarm and fail class


1151 Setpoint 105.0%
U> 1 120.0% Reference are activated when the
G/M/BA 0.1 s Handbook voltage has been
1152 Timer 5.0 s continuously above the
U> 1 300.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1153 Option- Not used delay.
U> 1 output A
dep.
Not used
G/M/BA Relay
1154 Option- Not used
U> 1 output B
dep.
G/M/BA OFF
1155 Enable OFF
U> 1 ON
G/M/BA Fail Warning
1156 F1…F7
U> 1 class (F2)

1160 G/M/BA overvoltage 2

G/M/BA 100.0% Designer’s The alarm and fail class


1161 Setpoint 115.0%
U> 2 120.0% Reference are activated when the
G/M/BA 0.1 s Handbook voltage has been
1162 Timer 1.0 s continuously above the
U> 2 300.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1163 Option- Not used delay.
U> 2 output A
dep.
Not used
G/M/BA Relay
1164 Option- Not used
U> 2 output B
dep.
G/M/BA OFF
1165 Enable OFF
U> 2 ON
G/M/BA Fail Warning
1166 F1…F7
U> 2 class (F2)

1170 G/M/BA undervoltage 1

G/M/BA 40.0% Designer’s The alarm and fail class


1171 Setpoint 95.0%
U< 1 100.0% Reference are activated when the
G/M/BA 0.1 s Handbook voltage has been
1172 Timer 5.0 s continuously under the
U< 1 100.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1173 Option- Not used delay.
U< 1 output A
dep.
Not used
G/M/BA Relay
1174 Option- Not used
U< 1 output B
dep.
G/M/BA OFF
1175 Enable OFF
U< 1 ON
G/M/BA Fail Warning
1176 F1…F7
U< 1 class (F2)

1180 G/M/BA undervoltage 2

G/M/BA 40.0% Designer’s The alarm and fail class


1181 Setpoint 80.0%
U< 2 100.0% Reference are activated when the

DEIF A/S Page 14 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

G/M/BA 0.1 s Handbook voltage has been


1182 Timer 3.0 s
U< 2 100.0 s continuously under the
Not used programmed value
G/M/BA Relay during the programmed
1183 Option- Not used
U< 2 output A delay.
dep.
Not used
G/M/BA Relay
1184 Option- Not used
U< 2 output B
dep.
G/M/BA OFF
1185 Enable OFF
U< 2 ON
G/M/BA Fail Warning
1186 F1…F7
U< 2 class (F2)

1190 G/M/BA undervoltage 3

G/M/BA 40.0% Designer’s The alarm and fail class


1191 Setpoint 70.0%
U< 3 100.0% Reference are activated when the
G/M/BA 0.1 s Handbook voltage has been
1192 Timer 1.0 s continuously under the
U< 3 100.0 s
programmed value
Not used during the programmed
G/M/BA Relay
1193 Option- Not used delay.
U< 3 output A
dep.
Not used
G/M/BA Relay
1194 Option- Not used
U< 3 output B
dep.
G/M/BA OFF
1195 Enable OFF
U< 3 ON
G/M/BA Fail Warning
1196 F1…F7
U< 3 class (F2)

1200 G/M/BA Voltage trip

Designer’s Selection between


Reference phase-phase or phase-
Handbook neutral voltage
detection.
When phase-phase
tripping is selected, the
G/M/BA Ph-Ph
1201 Setpoint Ph-Ph voltage alarms relate to
Voltage trip Ph-N
the nominal voltage.
When phase-neutral
tripping is selected, the
voltage alarms relate to
the nominal voltage
divided by √3.

DEIF A/S Page 15 of 137


AGC-3 Alarm and Parameter List

Frequency protections

Frequency settings relate to the nominal frequency setting.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1210 G/M/BA overfrequency 1

G/M/BA 100.0% Designer’s The alarm and fail class


1211 Setpoint 105.0%
f> 1 120.0% Reference are activated when the
G/M/BA 0.2 s Handbook frequency has been
1212 Timer 3.0 s continuously above the
f> 1 100.0 s
programmed value
Not during the programmed
G/M/BA Relay used delay.
1213 Not used
f> 1 output A Option- Frequency settings
dep. relate to nominal
Not frequency setting.
G/M/BA Relay used
1214 Not used
f> 1 output B Option-
dep.
G/M/BA OFF
1215 Enable OFF
f> 1 ON
G/M/BA Warning
1216 Fail class F1…F7
f> 1 (F2)

1220 G/M/BA overfrequency 2

G/M/BA 100.0% Designer’s The alarm and fail class


1221 Setpoint 105.0%
f> 2 120.0% Reference are activated when the
G/M/BA 0.2 s Handbook frequency has been
1222 Timer 5.0 s continuously above the
f> 2 100.0 s
programmed value
Not during the programmed
G/M/BA Relay used delay.
1223 Not used
f> 2 output A Option-
dep.
Not
G/M/BA Relay used
1224 Not used
f> 2 output B Option-
dep.
G/M/BA OFF
1225 Enable OFF
f> 2 ON
G/M/BA Warning
1226 Fail class F1…F7
f> 2 (F2)

1230 G/M/BA overfrequency 3

G/M/BA 100.0% Designer’s The alarm and fail class


1231 Setpoint 110.0%
f> 3 120.0% Reference are activated when the
G/M/BA 0.2 s Handbook frequency has been
1232 Timer 1.0 s continuously above the
f> 3 100.0 s
programmed value
Not during the programmed
G/M/BA Relay used delay.
1233 Not used
f> 3 output A Option-
dep.
Not
G/M/BA Relay used
1234 Not used
f> 3 output B Option-
dep.

DEIF A/S Page 16 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Not
G/M/BA used
1235 Enable Not used
f> 3 Option-
dep.
G/M/BA Warning
1236 Fail class F1…F7
f> 3 (F2)

1240 G/M/BA underfrequency 1

G/M/BA 80.0% Designer’s The alarm and fail class


1241 Setpoint 95.0%
f< 1 100.0% Reference are activated when the
G/M/BA 0.2 s Handbook frequency has been
1242 Timer 5.0 s continuously under the
f< 1 100.0 s
programmed value
Not during the programmed
G/M/BA Relay used delay.
1243 Not used
f< 1 output A Option-
dep.
Not
G/M/BA Relay used
1244 Not used
f< 1 output B Option-
dep.
G/M/BA OFF
1245 Enable OFF
f< 1 ON
G/M/BA Warning
1246 Fail class F1…F7
f< 1 (F2)

1250 G/M/BA underfrequency 2

G/M/BA 80.0% Designer’s The alarm and fail class


1251 Setpoint 93.0%
f< 2 100.0% Reference are activated when the
G/M/BA 0.2 s Handbook frequency has been
1252 Timer 3.0 s continuously under the
f< 2 100.0 s
programmed value
Not during the programmed
G/M/BA Relay used delay.
1253 Not used
f< 2 output A Option-
dep.
Not
G/M/BA Relay used
1254 Not used
f< 2 output B Option-
dep.
G/M/BA OFF
1255 Enable OFF
f< 2 ON
G/M/BA Warning
1256 Fail class F1…F7
f< 2 (F2)

1260 G/M/BA underfrequency 3

G/M/BA 80.0% Designer’s The alarm and fail class


1261 Setpoint 90.0%
f< 3 100.0% Reference are activated when the
G/M/BA 0.2 s Handbook frequency has been
1262 Timer 1.0 s continuously under the
f< 3 100.0 s
programmed value
Not during the programmed
G/M/BA Relay used delay.
1263 Not used
f< 3 output A Option-
dep.
Not
G/M/BA Relay used
1264 Not used
f< 3 output B Option-
dep.

DEIF A/S Page 17 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

G/M/BA OFF
1265 Enable OFF
f< 3 ON
G/M/BA Warning
1266 Fail class F1…F7
f< 3 (F2)

DEIF A/S Page 18 of 137


AGC-3 Alarm and Parameter List

Busbar voltage protections

Voltage settings relate to the nominal voltage setting.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1270 Busbar overvoltage 1

100.0% Designer’s The alarm and fail class


1271 BB U> 1 Setpoint 110.0%
120.0% Reference are activated when the
0.0 s Handbook voltage has been
1272 BB U> 1 Timer 5.0 s continuously above the
99.9 s
programmed value during
Not used the programmed delay.
Relay
1273 BB U> 1 Option- Not used
output A
dep.
Not used
Relay
1274 BB U> 1 Option- Not used
output B
dep.
OFF
1275 BB U> 1 Enable ON
ON
Fail Warning
1276 BB U> 1 F1…F7
class (F2)

1280 Busbar overvoltage 2

100.0% Designer’s The alarm and fail class


1281 BB U> 2 Setpoint 115.0%
120.0% Reference are activated when the
0.0 s Handbook voltage has been
1282 BB U> 2 Timer 0.5 s continuously above the
99.9 s
programmed value during
Not used the programmed delay.
Relay
1283 BB U> 2 Option- Not used
output A
dep.
Not used
Relay
1284 BB U> 2 Option- Not used
output B
dep.
OFF
1285 BB U> 2 Enable ON
ON
Fail Warning
1286 BB U> 2 F1…F7
class (F2)

1290 Busbar overvoltage 3

100.0% Designer’s The alarm and fail class


1291 BB U> 3 Setpoint 120.0%
120.0% Reference are activated when the
0.0 s Handbook voltage has been
1292 BB U> 3 Timer 0.1 s continuously above the
99.9 s
programmed value during
Not used the programmed delay.
Relay
1293 BB U> 3 Option- Not used
output A
dep.
Not used
Relay
1294 BB U> 3 Option- Not used
output B
dep.
OFF
1295 BB U> 3 Enable OFF
ON
Fail Trip GB
1296 BB U> 3 F1…F7
class (F3)

DEIF A/S Page 19 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1300 Busbar undervoltage 1

40.0% Designer’s The alarm and fail class


1301 BB U< 1 Setpoint 95.0%
100.0% Reference are activated when the
0.00 s Handbook voltage has been
1302 BB U< 1 Timer 5.00 s continuously under the
99.99 s
programmed value during
Not used the programmed delay.
Relay
1303 BB U< 1 Option- Not used
output A
dep.
Not used
Relay
1304 BB U< 1 Option- Not used
output B
dep.
OFF
1305 BB U< 1 Enable ON
ON
Fail Warning
1306 BB U< 1 F1…F7
class (F2)

1310 Busbar undervoltage 2

40.0% Designer’s The alarm and fail class


1311 BB U< 2 Setpoint 80.0%
100.0% Reference are activated when the
0.00 s Handbook voltage has been
1312 BB U< 2 Timer 0.50 s continuously under the
99.99 s
programmed value during
Not used the programmed delay.
Relay
1313 BB U< 2 Option- Not used
output A
dep.
Not used
Relay
1314 BB U< 2 Option- Not used
output B
dep.
OFF
1315 BB U< 2 Enable ON
ON
Fail Trip GB
1316 BB U< 2 F1…F7
class (F3)

1320 Busbar undervoltage 3

40.0% Designer’s The alarm and fail class


1321 BB U< 3 Setpoint 70.0%
100.0% Reference are activated when the
0.00 s Handbook voltage has been
1322 BB U< 3 Timer 0.30 s continuously under the
99.99 s
programmed value during
Not used the programmed delay.
Relay
1323 BB U< 3 Option- Not used
output A
dep.
Not used
Relay
1324 BB U< 3 Option- Not used
output B
dep.
OFF
1325 BB U< 3 Enable OFF
ON
Fail Trip GB
1326 BB U< 3 F1…F7
class (F3)

1330 Busbar undervoltage 4

40.0% Designer’s The alarm and fail class


1331 BB U< 4 Setpoint 60.0%
100.0% Reference are activated when the
0.00 s Handbook voltage has been
1332 BB U< 4 Timer 0.10 s continuously under the
99.99 s

DEIF A/S Page 20 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Not used programmed value during


Relay
1333 BB U< 4 Option- Not used the programmed delay.
output A
dep.
Not used
Relay
1334 BB U< 4 Option- Not used
output B
dep.
OFF
1335 BB U< 4 Enable OFF
ON
Fail Trip GB
1336 BB U< 4 F1…F7
class (F3)

1340 Busbar voltage trip

Designer’s Selection between phase-


Ph-Ph
1341 BB voltage trip Setpoint Ph-Ph Reference phase or phase-neutral
Ph-N
Handbook voltage detection.

DEIF A/S Page 21 of 137


AGC-3 Alarm and Parameter List

Busbar frequency protections

Frequency settings relate to the nominal frequency setting.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1350 Busbar overfrequency 1

100.0% Designer’s The alarm and fail class


1351 BB f> 1 Setpoint 105.0%
120.0% Reference are activated when the
0.00 s Handbook frequency has been
1352 BB f> 1 Timer 5.00 s continuously above the
99.99 s
programmed value
Not used during the programmed
Relay
1353 BB f> 1 Option- Not used delay.
output A
dep.
Not used
Relay
1354 BB f> 1 Option- Not used
output B
dep.
OFF
1355 BB f> 1 Enable ON
ON
Warning
1356 BB f> 1 Fail class F1…F7
(F2)

1360 Busbar overfrequency 2

100.0% Designer’s The alarm and fail class


1361 BB f> 2 Setpoint 110.0%
120.0% Reference are activated when the
0.00 s Handbook frequency has been
1362 BB f> 2 Timer 3.00 s continuously above the
99.99 s
programmed value
Not used during the programmed
Relay
1363 BB f> 2 Option- Not used delay.
output A
dep.
Not used
Relay
1364 BB f> 2 Option- Not used
output B
dep.
OFF
1365 BB f> 2 Enable ON
ON
Trip GB
1366 BB f> 2 Fail class F1…F7
(F3)

1370 Busbar overfrequency 3

100.0% Designer’s The alarm and fail class


1371 BB f> 3 Setpoint 120.0%
120.0% Reference are activated when the
0.00 s Handbook frequency has been
1372 BB f> 3 Timer 1.00 s continuously above the
99.99 s
programmed value
Not used during the programmed
Relay
1373 BB f> 3 Option- Not used delay.
output A
dep.
Not used
Relay
1374 BB f> 3 Option- Not used
output B
dep.
OFF
1375 BB f> 3 Enable OFF
ON
Trip GB
1376 BB f> 3 Fail class F1…F7
(F3)

DEIF A/S Page 22 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1380 Busbar underfrequency 1

80.0% Designer’s The alarm and fail class


1381 BB f< 1 Setpoint 96.0%
100.0% Reference are activated when the
0.00 s Handbook frequency has been
1382 BB f< 1 Timer 5.00 s continuously under the
99.99 s
programmed value
Not used during the programmed
Relay
1383 BB f< 1 Option- Not used delay.
output A
dep.
Not used
Relay
1384 BB f< 1 Option- Not used
output B
dep.
OFF
1385 BB f< 1 Enable ON
ON
Warning
1386 BB f< 1 Fail class F1…F7
(F2)

1390 Busbar underfrequency 2

80.0% Designer’s The alarm and fail class


1391 BB f< 2 Setpoint 93.0%
100.0% Reference are activated when the
0.00 s Handbook frequency has been
1392 BB f< 2 Timer 5.00 s continuously under the
99.99 s
programmed value
Not used during the programmed
Relay
1393 BB f< 2 Option- Not used delay.
output A
dep.
Not used
Relay
1394 BB f< 2 Option- Not used
output B
dep.
OFF
1395 BB f< 2 Enable ON
ON
Trip GB
1396 BB f< 2 Fail class F1…F7
(F3)

1400 Busbar underfrequency 3

80.0% Designer’s The alarm and fail class


1401 BB f< 3 Setpoint 92.0%
100.0% Reference are activated when the
0.00 s Handbook frequency has been
1402 BB f< 3 Timer 3.00 s continuously under the
99.99 s
programmed value
Not used during the programmed
Relay
1403 BB f< 3 Option- Not used delay.
output A
dep.
Not used
Relay
1404 BB f< 3 Option- Not used
output B
dep.
OFF
1405 BB f< 3 Enable OFF
ON
Trip GB
1406 BB f< 3 Fail class F1…F7
(F3)

1410 Busbar underfrequency 4

80.0% Designer’s The alarm and fail class


1411 BB f< 4 Setpoint 90.0%
100.0% Reference are activated when the
0. 00 s Handbook frequency has been
1412 BB f< 4 Timer 1.00 s continuously under the
99.99 s

DEIF A/S Page 23 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Not used programmed value


Relay
1413 BB f< 4 Option- Not used during the programmed
output A
dep. delay.
Not used
Relay
1414 BB f< 4 Option- Not used
output B
dep.
OFF
1415 BB f< 4 Enable OFF
ON
Trip GB
1416 BB f< 4 Fail class F1…F7
(F3)

DEIF A/S Page 24 of 137


AGC-3 Alarm and Parameter List

Mains failure protections

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1420 Df/dt (ROCOF)

1.5 Hz/s Option A1 The alarm and fail class


1421 Df/dt (ROCOF) Setpoint 5.0 Hz/s
10.0 Hz/s are activated when the
3 per df/dt rate has been
1422 Df/dt (ROCOF) Timer 6 per continuously above the
20 per
programmed value during
Not used the programmed number
Relay
1423 Df/dt (ROCOF) Option- Not used of periods (delay).
output A
dep.
Not used
Relay
1424 Df/dt (ROCOF) Option- Not used
output B
dep.
OFF
1425 Df/dt (ROCOF) Enable OFF
ON
Trip MB
1426 Df/dt (ROCOF) Fail class F1…F7
(F4)

1430 Vector jump

1.0 deg. Option A1 The alarm and fail class


1431 Vector jump Setpoint 10.0 deg.
90.0 deg. are activated when a
Not used vector jump is detected.
Relay
1432 Vector jump Option- Not used
output A
dep.
Not used
Relay
1433 Vector jump Option- Not used
output B
dep.
OFF
1434 Vector jump Enable OFF
ON
Trip MB
1435 Vector jump Fail class F1…F7
(F4)

1440 Busbar positive sequence voltage low

10.0% Option A4 The alarm and fail class


1471 BB pos seq volt Setpoint 70.0%
110.0% are activated when the
1 per symmetrical (positive
1472 BB pos seq volt Timer 2 per sequence) voltage has
9 per
been continuously below
Not used the programmed value
Relay
1473 BB pos seq volt Option- Not used during the programmed
output A
dep. delay.
Not used The timer factory setting is
Relay set to 2 periods. This
1474 BB pos seq volt Option- Not used
output B means that the error has
dep.
to be active in 2 whole
OFF
1475 BB pos seq volt Enable OFF periods before the alarm
ON
will be tripped.
E.g. in a 50Hz system, the
alarm will be activated if
the positive sequence is
Trip MB below 70% of U nominal
1476 BB pos seq volt Fail class F1…F7
(F4) voltage for 40 ms. The
alarm will trip the fail class
as soon as possible after
this delay.

DEIF A/S Page 25 of 137


AGC-3 Alarm and Parameter List

Overload protections

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1450 G/M/BA overload 1

G/M/BA -200.0% Designer’s Settings relate to nominal


1451 Setpoint 95.0%
P> 1 200.0% Reference power.
G/M/BA 0.1 s Handbook The alarm and fail class
1452 Timer 20.0 s are activated when the
P> 1 3200.0 s
power has been
Not used continuously above the
G/M/BA Relay
1453 Option- Not used programmed value during
P> 1 output A
dep. the programmed delay.
Not used
G/M/BA Relay
1454 Option- Not used
P> 1 output B
dep.
G/M/BA OFF
1455 Enable ON
P> 1 ON
G/M/BA Warning
1456 Fail class F1…F7
P> 1 (F2)

1460 G/M/BA overload 2

G/M/BA -200.0% Designer’s The alarm and fail class


1461 Setpoint 110.0%
P> 2 200.0% Reference are activated when the
G/M/BA 0.1 s Handbook power has been
1462 Timer 10.0 s continuously above the
P> 2 3200.0 s
programmed value during
Not used the programmed delay.
G/M/BA Relay
1463 Option- Not used
P> 2 output A
dep.
Not used
G/M/BA Relay
1464 Option- Not used
P> 2 output B
dep.
G/M/BA OFF
1465 Enable ON
P> 2 ON
G/M/BA Trip GB
1466 Fail class F1…F7
P> 2 (F3)

1470 G/M/BA overload 3

G/M/BA -200.0% Designer’s The alarm and fail class


1471 Setpoint 115.0%
P> 3 200.0% Reference are activated when the
G/M/BA 0.1 s Handbook power has been
1472 Timer 5.0 s continuously above the
P> 3 100.0 s
programmed value during
Not used the programmed delay.
G/M/BA Relay
1473 Option- Not used
P> 3 output A
dep.
Not used
G/M/BA Relay
1474 Option- Not used
P> 3 output B
dep.
G/M/BA OFF
1475 Enable OFF
P> 3 ON
G/M/BA Trib GB
1476 Fail class F1…F7
P> 3 (F3)

1480 G/M/BA overload 4

G/M/BA -200.0% Designer’s The alarm and fail class


1481 Setpoint 120.0%
P> 4 200.0% Reference are activated when the

DEIF A/S Page 26 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

G/M/BA 0.1 s Handbook power has been


1482 Timer 3.0 s
P> 4 100.0 s continuously above the
Not used programmed value during
G/M/BA Relay the programmed delay.
1483 Option- Not used
P> 4 output A
dep.
Not used
G/M/BA Relay
1484 Option- Not used
P> 4 output B
dep.
G/M/BA OFF
1485 Enable OFF
P> 4 ON
G/M/BA Trip GB
1486 Fail class F1…F7
P> 4 (F3)

1490 G/M/BA overload 5

G/M/BA -200.0% Designer’s The alarm and fail class


1491 Setpoint 130.0%
P> 5 200.0% Reference are activated when the
G/M/BA 0.1 s Handbook power has been
1492 Timer 1.0 s continuously above the
P> 5 100.0 s
programmed value during
Not used the programmed delay.
G/M/BA Relay
1493 Option- Not used
P> 5 output A
dep.
Not used
G/M/BA Relay
1494 Option- Not used
P> 5 output B
dep.
G/M/BA OFF
1495 Enable OFF
P> 5 ON
G/M/BA Trip GB
1496 Fail class F1…F7
P> 5 (F3)

DEIF A/S Page 27 of 137


AGC-3 Alarm and Parameter List

Current unbalance protection

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1500 G/M/BA unbalanced current

G/M/BA 0.0% Designer’s Settings relate to nominal


1501 Setpoint 30.0%
unbalance curr. 100.0% Reference generator current.
G/M/BA 0.1 s Handbook The alarm and fail class
1502 Timer 10.0 s are activated when the
unbalance curr. 100.0 s
difference between the
Not used max. reading and the min.
G/M/BA Relay
1503 Option- Not used reading of the 3 measured
unbalance curr. output A
dep. currents has been
Not used continuously above the
G/M/BA Relay
1504 Option- Not used programmed value during
unbalance curr. output B
dep. the programmed delay.
G/M/BA OFF
1505 Enable ON
unbalance curr. ON
G/M/BA Warning
1506 Fail class F1…F7
unbalance curr. (F2)

Voltage unbalance protection

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1510 G/M/BA unbalanced voltage

G/M/BA 0.0% Designer’s Settings relate to


1511 Setpoint 10.0%
unbalance volt. 50.0% Reference nominal voltage.
G/M/BA 0.1 s Handbook The alarm and fail class
1512 Timer 10.0 s are activated when the
unbalance volt. 100.0 s
difference between the
Not used max. reading and the
G/M/BA Relay
1513 Option- Not used min. reading of the 3
unbalance volt. output A
dep. measured generator
Not used voltages has been
G/M/BA Relay
1514 Option- Not used continuously above the
unbalance volt. output B
dep. programmed value
during the programmed
G/M/BA OFF
1515 Enable ON delay.
unbalance volt. ON
G/M/BA Warning
1516 Fail class F1…F7
unbalance volt. (F2)

DEIF A/S Page 28 of 137


AGC-3 Alarm and Parameter List

Reactive power import (loss of excitation) protection

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1520 G/M/BA reactive power import (loss of excitation)

0.0% Designer’s Settings relate to


1521 G/M/BA –Q> Setpoint 50.0%
150.0% Reference nominal power.
0.1 s Handbook The alarm and fail class
1522 G/M/BA –Q> Timer 10.0 s are activated when
100.0 s
imported VAr has been
Not used continuously above the
Relay
1523 G/M/BA –Q> Option- Not used programmed value
output A
dep. during the programmed
Not used delay.
Relay
1524 G/M/BA –Q> Option- Not used
output B
dep.
OFF
1525 G/M/BA –Q> Enable ON
ON
Trip GB
1526 G/M/BA –Q> Fail class F1…F7
(F3)

Reactive power export (overexcitation) protection

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1530 G/M/BA reactive power export (overexcitation)

0.0% Designer’s Settings relate to


1531 G/M/BA Q> Setpoint 75.0%
100.0% Reference nominal power.
0.1 s Handbook The alarm and fail class
1532 G/M/BA Q> Timer 10.0 s are activated when
100.0 s
exported VAr has been
Not used continuously above the
Relay
1533 G/M/BA Q> Option- Not used programmed value
output A
dep. during the programmed
Not used delay.
Relay
1534 G/M/BA Q> Option- Not used
output B
dep.
OFF
1535 G/M/BA Q> Enable ON
ON
Trip GB
1536 G/M/BA Q> Fail class F1…F7
(F3)

DEIF A/S Page 29 of 137


AGC-3 Alarm and Parameter List

Negative sequence

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1540 G/M/BA negative sequence current

G/M/BA neg 1.0% Option C2 Settings relate to


1541 Setpoint 20.0%
seq I 100.0% nominal current.
G/M/BA neg 0.2 s The alarm and fail
1542 Timer 0.5 s class are activated
seq I 100.0 s
when the negative
G/M/BA neg Relay Not used sequence has been
1543 Not used
seq I output A Option-dep. continuously above the
G/M/BA neg Relay Not used programmed value
1544 Not used
seq I output B Option-dep. during the programmed
delay.
G/M/BA neg OFF
1545 Enable OFF
seq I ON
G/M/BA neg Fail Trip MB
1546 F1…F7
seq I class (F4)

1550 G/M/BA negative sequence voltage

G/M/BA neg 1.0% Option C2 Settings relate to


1551 Setpoint 5.0%
seq U 100.0% nominal voltage.
G/M/BA neg 0.2 s The alarm and fail
1552 Timer 0.5 s class are activated
seq U 100.0 s
when the negative
G/M/BA neg Relay Not used sequence has been
1553 Not used
seq U output A Option-dep. continuously above the
G/M/BA neg Relay Not used programmed value
1554 Not used
seq U output B Option-dep. during the programmed
delay.
G/M/BA neg OFF
1555 Enable OFF
seq U ON
G/M/BA neg Fail Trip MB
1556 F1…F7
seq U class (F4)

1560 G/M/BA negative sequence selection

Option C2 Selection between


G/MBA
generator or busbar
G/M/BA neg measurement G/MBA
1561 Setpoint measurement of
seq select BB measurement
negative sequence
measurement
voltage.

DEIF A/S Page 30 of 137


AGC-3 Alarm and Parameter List

Zero sequence

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1570 G/M/BA zero sequence current

G/M/BA zero 0.0% Option C2 Settings relate to


1571 Setpoint 20.0%
seq I 100.0% nominal current.
G/M/BA zero 0.2 s The alarm and fail
1572 Timer 0.5 s class are activated
seq I 100.0 s
when the zero
G/M/BA zero Relay Not used sequence has been
1573 Not used
seq I output A Option-dep. continuously above the
G/M/BA zero Relay Not used programmed value
1574 Not used
seq I output B Option-dep. during the programmed
delay.
G/M/BA zero OFF
1575 Enable OFF
seq I ON
G/M/BA zero Fail Trip MB
1576 F1…F7
seq I class (F4)

1580 G/M/BA zero sequence voltage

G/M/BA zero 0.0% Option C2 Settings relate to


1581 Setpoint 5.0%
seq U 100.0% nominal voltage.
G/M/BA zero 0.2 s The alarm and fail
1582 Timer 0.5 s class are activated
seq U 100.0 s
when the zero
G/M/BA zero Relay Not used sequence has been
1583 Not used
seq U output A Option-dep. continuously above the
G/M/BA zero Relay Not used programmed value
1584 Not used
seq U output B Option-dep. during the programmed
delay.
G/M/BA zero OFF
1585 Enable OFF
seq U ON
G/M/BA zero Fail Trip MB
1586 F1…F7
seq U class (F4)

1590 G/M/BA zero sequence selection

G/MBA Option C2 Selection between


G/M/BA zero measurement G/MBA generator or busbar
1591 Setpoint
seq select BB measurement measurement of zero
measurement sequence voltage.

DEIF A/S Page 31 of 137


AGC-3 Alarm and Parameter List

Directional overcurrent protection

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1600 G/M/BA directional overcurrent 1

G/M/BA I> direct -200.0% Option A5 Settings relate to


1601 Setpoint 120.0%
1 200.0% nominal current.
G/M/BA I> direct 0.0 s The alarm and fail class
1602 Timer 0.1 s are activated when the
1 100.0 s
directional current has
Not used been continuously above
G/M/BA I> direct Relay
1603 Option- Not used the programmed value
1 output A
dep. during the programmed
Not used delay.
G/M/BA I> direct Relay
1604 Option- Not used The current measure-
1 output B
dep. ment is positive when
current is supplied from
G/M/BA I> direct OFF
1605 Enable OFF the mains to the plant.
1 ON
The current measure-
G/M/BA I> direct Trip MB ment is negative when
1606 Fail class F1…F7 current is being supplied
1 (F4)
to the mains.

1610 G/M/BA directional overcurrent 2

G/M/BA I> direct -200.0% Option A5 Settings relate to


1611 Setpoint 130.0%
2 200.0% nominal current.
G/M/BA I> direct 0.0 s The alarm and fail class
1612 Timer 0.1 s are activated when the
2 100.0 s
directional current has
Not used been continuously above
G/M/BA I> direct Relay
1613 Option- Not used the programmed value
2 output A
dep. during the programmed
Not used delay.
G/M/BA I> direct Relay
1614 Option- Not used The current measure-
2 output B
dep. ment is positive when
current is supplied from
G/M/BA I> direct OFF
1615 Enable OFF the mains to the plant.
2 ON
The current measure-
G/M/BA I> direct Trip MB ment is negative when
1616 Fail class F1…F7 current is being supplied
2 (F4)
to the mains.

DEIF A/S Page 32 of 137


AGC-3 Alarm and Parameter List

Busbar unbalance voltage

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1620 BB unbalance U

0.0% Designer’s Settings relate to average


1621 BB unbalance U Setpoint 10.0%
50.0% Reference actual voltage.
0.1 s 10.0 s Handbook The alarm and fail class
1622 BB unbalance U Timer are activated when the
100.0 s
difference between the
Not used max. reading and the min.
Relay
1623 BB unbalance U Option- Not used reading of the 3 measured
output A
dep. busbar voltages has been
Not used continuously above the
Relay
1624 BB unbalance U Option- Not used programmed value during
output B
dep. the programmed delay.
OFF
1625 BB unbalance U Enable OFF
ON
Warning
1626 BB unbalance U Fail class F1…F7
(F2)

Time-dependent undervoltage
No. Setting Min. Factory Notes Ref. Description
setting
Max.

1630 Time-dependent undervoltage 1 1-3

30.0% Option A1 Curve setting for time-


1631 Ut < 1 Setting 1 30.0%
120.0% dependent under-
Ut < 1 0.00 s voltage.
1632 Delay 1 0.15 s Settings relate to
20.00 s
nominal generator
Ut < 1 30.0% voltage.
1633 Setting 2 70.0%
120.0% The condition has to be
Ut < 1 0.00 s true i.e.
1634 Delay 2 0.15 s
20.00 s Ut(1)1≤Ut(2)≤Ut(3)≤
Ut(4)≤Ut(5)≤Ut(6).
Ut < 1 30.0%
1635 Setting 3 70.0% If this is not fulfilled, the
120.0%
worst-case setpoint Ut(6)
Ut < 1 0.00 s will be used.
1636 Delay 3 0.70 s
20.00 s

1640 Time-dependent undervoltage 1 4-6

30.0% Option A1 Curve setting for time-


1641 Ut < 1 Setting 4 90.0%
120.0% dependent under-
Ut < 1 0.00 s voltage.
1642 Delay 4 1.50 s Settings relate to
20.00 s
nominal generator
Ut < 1 30.0% voltage.
1643 Setting 5 90.0%
120.0% The condition has to be
Ut < 1 0.00 s true i.e.
1644 Delay 5 2.00 s
20.00 s Ut(1)1≤Ut(2)≤Ut(3)≤
Ut(4)≤Ut(5)≤Ut(6).
Ut < 1 30.0%
1645 Setting 6 90.0% If this is not fulfilled, the
120.0%
worst-case setpoint Ut(6)
Ut < 1 0.00 s will be used.
1646 Delay 6 3.00 s
20.00 s

DEIF A/S Page 33 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1650 Time-dependent undervoltage 1 activation

0.0% Option A1 Activate is the voltage


1651 Ut < act 1 Activate 90%
120.0% value where the function
Ut < act 1 0.0% timer starts.
1652 Reset 95% Reset is the value where
120.0%
the function timer is
Ut < act 1 0.0 s reset to 0 ms.
1653 Delay 1.00 s
320.0 s Delay is the delay timer
Ut < act 1 Not used for the reset.
Relay
1654 Option- Not used The relay outputs will
output A
dep. activate immediately
when the function timer
Ut < act 1 Not used
Relay starts.
1655 Option- Not used
output B
dep.
Ut < act 1 OFF
1656 Enable OFF
ON

1660 Time-dependent undervoltage 1

Not used Option A1 The alarm and fail class


Relay
1661 Ut < 1 Option- Not used is activated
output A
dep. instantaneously when
Ut < 1 Not used the voltage value is
Relay under the programmed
1662 Option- Not used
output B value curve.
dep.
Ut < 1 OFF
1663 Enable OFF
ON
Ut < 1 Trip GB
1664 Fail class F1…F5
(F3)

1670 Time-dependent undervoltage 2 1-3

30.0% Option A1 Curve setting for time-


1671 Ut < 2 Setting 1 30.0%
120.0% dependent undervoltage.
Ut < 2 0.00 s Settings relate to
1672 Delay 1 0.15 s nominal generator
20.00 s
voltage.
Ut < 2 30.0% The condition has to be
1673 Setting 2 70.0%
120.0% true i.e.
Ut < 2 0.00 s Ut(1)1≤Ut(2)≤Ut(3)≤
1674 Delay 2 0.15 s
20.00 s Ut(4)≤Ut(5)≤Ut(6).
If this is not fulfilled, the
Ut < 2 30.0%
1675 Setting 3 70.0% worst-case setpoint Ut(6)
120.0%
will be used.
Ut < 2 0.00 s
1676 Delay 3 0.70 s
20.00 s

1680 Time-dependent undervoltage 2 4-6

30.0% Option A1 Curve setting for time-


1681 Ut < 2 Setting 4 90.0%
120.0% dependent undervoltage.
Ut < 2 0.00 s Settings relate to
1682 Delay 4 1.50 s nominal generator
20.00 s
voltage.
Ut < 2 30.0% The condition has to be
1683 Setting 5 90.0%
120.0% true i.e.
Ut < 2 0.00 s Ut(1)1≤Ut(2)≤Ut(3)≤
1684 Delay 5 2.00 s
20.00 s Ut(4)≤Ut(5)≤Ut(6).
If this is not fulfilled, the
Ut < 2 30.0%
1685 Setting 6 90.0% worst-case setpoint Ut(6)
120.0%

DEIF A/S Page 34 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Ut < 2 0.00 s will be used.


1686 Delay 6 3.00 s
20.00 s

1690 Time-dependent undervoltage 2 activation

0.0% Option A1 Activate is the voltage


1691 Ut < act 2 Activate 90%
120.0% value where the function
Ut < act 2 0.0% timer starts.
1692 Reset 95% Reset is the value where
120.0%
the function timer is
Ut < act 2 0.0 s reset to 0 ms.
1693 Delay 1.00 s
320.0 s Delay is the delay timer
Ut < act 2 Not used for the reset.
Relay
1694 Option- Not used The relay output will
output A
dep. activate immediately
when the function timer
Ut < act 2 Not used
Relay starts.
1695 Option- Not used
output B
dep.
Ut < act 2 OFF
1696 Enable OFF
ON

1700 Time-dependent undervoltage 2

Not used Option A1 The alarm and fail class


Relay
1701 Ut < 2 Option- Not used is activated
output A
dep. instantaneously when
Ut < 2 Not used the voltage value is
Relay under the programmed
1702 Option- Not used
output B value curve.
dep.
Ut < 2 OFF
1703 Enable OFF
ON
Ut < 2 Trip GB
1704 Fail class F1…F5
(F3)

DEIF A/S Page 35 of 137


AGC-3 Alarm and Parameter List

Non-essential load trip (load shedding)

Setting values relate to the nominal setting.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1800 NEL 1 overcurrent

50.0% Designer’s Trip of non-essential load


1801 NEL 1 I> Setpoint 100.0%
200.0% Reference due to overcurrent. This
0.1 s Handbook function activates NEL
1802 NEL 1 I> Timer 5.0 s group 1.
100.0 s
OFF
1803 NEL 1 I> Enable OFF
ON

1810 NEL 2 overcurrent

50.0% Designer’s Trip of non-essential load


1811 NEL 2 I> Setpoint 100.0%
200.0% Reference due to overcurrent. This
0.1 s Handbook function activates NEL
1812 NEL 2 I> Timer 8.0 s group 2.
100.0 s
OFF
1813 NEL 2 I> Enable OFF
ON

1820 NEL 3 overcurrent

50.0% Designer’s Trip of non-essential load


1821 NEL 3 I> Setpoint 100.0%
200.0% Reference due to overcurrent. This
0.1 s Handbook function activates NEL
1822 NEL 3 I> Timer 10.0 s group 3.
100.0 s
OFF
1823 NEL 3 I> Enable OFF
ON

1830 NEL 1 busbar underfrequency

70.0% Designer’s Trip of non-essential load


1831 NEL 1 bus f< Setpoint 95.0%
100.0% Reference due to low frequency. This
0.1 s Handbook function activates NEL
1832 NEL 1 bus f< Timer 5.0 s group 1.
100.0 s
OFF
1835 NEL 1 bus f< Enable OFF
ON

1840 NEL 2 busbar underfrequency

70.0% Designer’s Trip of non-essential load


1841 NEL 2 bus f< Setpoint 95.0%
100.0% Reference due to low frequency. This
0.1 s Handbook function activates NEL
1842 NEL 2 bus f< Timer 8.0 s group 2.
100.0 s
OFF
1845 NEL 2 bus f< Enable OFF
ON

1850 NEL 3 busbar underfrequency

70.0% Designer’s Trip of non-essential load


1851 NEL 3 bus f< Setpoint 95.0%
100.0% Reference due to low frequency. This
0.1 s Handbook function activates NEL
1852 NEL 3 bus f< Timer 10.0 s group 3.
100.0 s
OFF
1855 NEL 3 bus f< Enable OFF
ON

DEIF A/S Page 36 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1860 NEL 1 overload

10.0% Designer’s Trip of non-essential load


1861 NEL 1 P> Setpoint 100.0%
200.0% Reference due to overload. This
0.1 s Handbook function activates NEL
1862 NEL 1 P> Timer 5.0 s group 1.
100.0 s
OFF
1865 NEL 1 P> Enable OFF
ON

1870 NEL 2 overload

10.0% Designer’s Trip of non-essential load


1871 NEL 2 P> Setpoint 100.0%
200.0% Reference due to overload. This
0.1 s Handbook function activates NEL
1872 NEL 2 P> Timer 8.0 s group 2.
100.0 s
OFF
1875 NEL 2 P> Enable OFF
ON

1880 NEL 3 overload

10.0% Designer’s Trip of non-essential load


1881 NEL 3 P> Setpoint 100.0%
200.0% Reference due to overload. This
0.1 s Handbook function activates NEL
1882 NEL 3 P> Timer 10.0 s group 3.
100.0 s
OFF
1885 NEL 3 P> Enable OFF
ON

1890 NEL 1 high overload

10.0% Designer’s Trip of non-essential load


1891 NEL 1 P>> Setpoint 110.0%
200.0% Reference due to high overload. This
0.1 s Handbook function activates NEL
1892 NEL 1 P>> Timer 1.0 s group 1.
100.0 s
OFF
1895 NEL 1 P>> Enable OFF
ON

1900 NEL 2 high overload

10.0% Designer’s Trip of non-essential load


1901 NEL 2 P>> Setpoint 110.0%
200.0% Reference due to high overload. This
0.1 s Handbook function activates NEL
1902 NEL 2 P>> Timer 1.0 s group 2.
100.0 s
OFF
1905 NEL 2 P>> Enable OFF
ON

1910 NEL 3 high overload

10.0% Designer’s Trip of non-essential load


1911 NEL 3 P>> Setpoint 110.0%
200.0% Reference due to high overload. This
0.1 s Handbook function activates NEL
1912 NEL 3 P>> Timer 1.0 s group 3.
100.0 s
OFF
1915 NEL 3 P>> Enable OFF
ON

DEIF A/S Page 37 of 137


AGC-3 Alarm and Parameter List

Undervoltage and reactive power low

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1960 U and Q < 1

70.0% Option A1 The setting relates to the


1961 U and Q < 1 Setpoint 85.0%
100.0% generator nominal
0.0 s voltage.
1962 U and Q < 1 Delay 5.0 s The condition for trip is
10.0 s
that the actual voltage
Relay Option drops below the setting
1963 U and Q < 1 Not used
output A dep. value and that the
Relay Option reactive power is ≤ 0
1964 U and Q < 1 Not used
output B dep. kVAr.
OFF
1965 U and Q < 1 Enable OFF
ON
Warning
1966 U and Q < 1 Fail class F1…F5
(F2)

1970 U and Q < 2

70.0% Option A1 The setting relates to the


1971 U and Q < 2 Setpoint 85.0%
100.0% generator nominal voltage.
1.0 s The condition for trip is that
1972 U and Q < 2 Delay 5.0 s the actual voltage drops
10.0 s
below the setting value
Relay Option and that the reactive power
1973 U and Q < 2 Not used
output A dep. is ≤ 0 kVAr.
Relay Option
1974 U and Q < 2 Not used
output B dep.
OFF
1975 U and Q < 2 Enable OFF
ON
Warning
1976 U and Q < 2 Fail class F1…F5
(F2)

DEIF A/S Page 38 of 137


AGC-3 Alarm and Parameter List

Synchronisation and breaker alarms

No. Setting Min. Factory Notes Ref. Description


setting
Max.

2120 Synchronisation window

2.0% Designer’s The alarm will activate if


2121 Sync window Setpoint 15%
20.0% Reference the actual voltage deviates
0.1 s Handbook from nominal voltage with
2122 Sync window Timer 0.5 s the set percentage.
2.0 s
Not used
Relay
2123 Sync window Option- Not used
output A
dep.
Not used
Relay
2124 Sync window Option- Not used
output B
dep.
OFF
2125 Sync window Enable OFF
ON

2130 GB/TB/BTB breaker synchronisation failure

GB/TB/BTB sync 30.0 s Designer’s GB: Generator breaker


2131 Delay 60.0 s
failure 300.0 s Reference TB: Tie breaker (Mains
Not used Handbook unit)
GB/TB/BTB sync Relay BTB: Bus tie breaker.
2132 Option- Not used
failure output A The controller has
dep.
unsuccessfully tried to
Not used synchronise the breaker to
GB/TB/BTB sync Relay
2133 Option- Not used the busbar within the time
failure output B
dep. delay.
GB/TB/BTB sync OFF
2134 Enable ON
failure ON
GB/TB/BTB sync Warning
2135 Fail class F1…F7
failure (F2)

2140 Mains breaker synchronisation failure

30.0 s Designer’s The controller has


2141 MB sync failure Delay 60.0 s
300.0 s Reference unsuccessfully tried to
Not used Handbook synchronise the breaker to
Relay the busbar within the time
2142 MB sync failure Option- Not used
output A delay.
dep.
Not used
Relay
2143 MB sync failure Option- Not used
output B
dep.
OFF
2144 MB sync failure Enable ON
ON
Warning
2145 MB sync failure Fail class F1…F7
(F2)

2150 Phase sequence error

Not used Designer’s During synchronisation the


Relay
2151 Phase seq error Option- Not used Reference controller has detected that
output A
dep. Handbook the rotation direction of the
Not used generator phases is
Relay opposite direction as the
2152 Phase seq error Option- Not used
output B busbar.
dep.
Block
2153 Phase seq error Fail class F1…F7
(F1)

DEIF A/S Page 39 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

2160 GB/TB/BTB open failure

GB/TB/BTB open 1.0 s Designer’s The breaker open failure


2161 Delay 2.0 s
fail 5.0 s Reference will occur, if the unit has
Not used Handbook transmitted a breaker open
GB/TB/BTB open Relay signal and the breaker
2162 Option- Not used
fail output A feedback has not changed
dep.
position from ON to OFF
Not used within 2 s.
GB/TB/BTB open Relay
2163 Option- Not used
fail output B
dep.
GB/TB/BTB open OFF
2164 Enable ON
fail ON
GB/TB/BTB open Warning
2165 Fail class F1…F7
fail (F2)

2170 GB/TB/BTB breaker close failure

GB/BTB/BTB 1.0 s Designer’s The breaker close failure


2171 Delay 2.0 s
close fail 5.0 s Reference will occur, if the unit has
Not used Handbook transmitted a breaker close
GB/BTB/BTB Relay signal and the breaker
2172 Option- Not used
close fail output A feedback has not changed
dep.
position from OFF to ON
Not used within 2 s.
GB/BTB/BTB Relay
2173 Option- Not used
close fail output B
dep.
GB/BTB/BTB OFF
2174 Enable ON
close fail ON
GB/BTB/BTB Warning
2175 Fail class F1…F7
close fail (F2)

2180 GB/TB/BTB breaker position failure

GB/TB/BTB pos 1.0 s Designer’s This alarm will occur if the


2181 Delay 1.0 s
fail 5.0 s Reference breaker feedbacks for ON
Not used Handbook and OFF are both missing
GB/TB/BTB pos Relay or active for more than 2 s
2182 Option- Not used
fail output A at the time,
dep.
Not used
GB/TB/BTB pos Relay
2183 Option- Not used
fail output B
dep.
GB/TB/BTB pos OFF
2184 Enable ON
fail ON
GB/TB/BTB pos Warning
2185 Fail class F1…F7
fail (F2)

2200 MB open failure

1.0 s Designer’s The breaker open failure


2201 MB open fail Delay 2.0 s
5.0 s Reference will occur, if the unit has
Not used Handbook transmitted a breaker open
Relay signal and the breaker
2202 MB open fail Option- Not used
output A feedback has not changed
dep.
position from ON to OFF
Not used within 2 s.
Relay
2203 MB open fail Option- Not used
output B
dep.
OFF
2204 MB open fail Enable ON
ON

DEIF A/S Page 40 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Warning
2205 MB open fail Fail class F1…F7
(F2)

2210 MB close failure

1.0 s Designer’s The breaker close failure


2211 MB close fail Delay 2.0 s
5.0 s Reference will occur, if the unit has
Not used Handbook transmitted a breaker close
Relay signal and the breaker
2212 MB close fail Option- Not used
output A feedback has not changed
dep.
position from OFF to ON
Not used within 2 s.
Relay
2213 MB close fail Option- Not used
output B
dep.
OFF
2214 MB close fail Enable ON
ON
Warning
2215 MB close fail Fail class F1…F7
(F2)

2220 MB position failure

1.0 s Designer’s This alarm will occur if the


2221 MB pos fail Delay 1.0 s
5.0 s Reference breaker feedbacks for ON
Not used Handbook and OFF are both missing
Relay or active for more than 2 s.
2222 MB pos fail Option- Not used
output A
dep.
Not used
Relay
2223 MB pos fail Option- Not used
output B
dep.
OFF
2224 MB pos fail Enable ON
ON
Warning
2225 MB pos fail Fail class F1…F7
(F2)

2270 Close before excitation failure

0.0 s Designer’s This alarm will occur if the


2271 Cl.bef.exc.fail Delay 5.0 s
999.0 s Reference generator and breaker are
Not used Handbook not operating within the
Relay limits of the Close Before
2272 Cl.bef.exc.fail Option- Not used
output A Excitation. The alarm will
dep.
open the generator breaker
Not used and enable the regulation
Relay
2273 Cl.bef.exc.fail Option- Not used synchronising the generator
output B
dep. in a normal way.
OFF
2274 Cl.bef.exc.fail Enable OFF
ON
Warning
2275 Cl.bef.exc.fail Fail class F1…F7
(F2)

DEIF A/S Page 41 of 137


AGC-3 Alarm and Parameter List

Regulation alarms

No. Setting Min. Factory Notes Ref. Description


setting
Max.

2560 Governor regulation fail

1.0% Designer’s The alarm is activated, if


2561 Gov. reg fail Deadband 30.0%
100.0% Reference the difference between the
10.0 s Handbook measured value and the
2562 Gov. reg fail Delay 60.0 s setpoint is outside the
300.0 s
deadband for a longer time
Not used period than specified by the
Relay
2563 Gov. reg fail Option- Not used delay setpoint.
output A
dep.
Not used
Relay
2564 Gov. reg fail Option- Not used
output B
dep.
Warning
2565 Gov. reg fail Fail class F1…F7
(F2)

2630 Deload error

0.0 s Designer’s The alarm is activated, if


2631 Deload error Delay 10.0 s
60.0 s Reference the generator fails to deload
Not used Handbook within the time delay.
Relay
2632 Deload error Option- Not used
output A
dep.
Not used
Relay
2633 Deload error Option- Not used
output B
dep.
OFF
2634 Deload error Enable ON
ON
Warning
2635 Deload error Fail class F1…F7
(F2)

2680 AVR regulation failure

1.0% Option: The alarm is activated, if


2681 AVR reg. failure Deadband 30.0%
100.0% VAr the difference between the
10.0 s control measured value and the
2682 AVR reg. failure Delay 60.0 s (D1) setpoint is outside the
300.0 s
setting ‘Deadband’ for a
Not used longer time period than
Relay
1153 AVR reg. failure Option- Not used specified in the timer
output A
dep. setpoint.
Not used
Relay
1154 AVR reg. failure Option- Not used
output B
dep.
Warning
1155 AVR reg. failure Fail class F1…F7
(F2)

These parameters are used when a digital input are used as protection inputs or
to activate a limit relay.

DEIF A/S Page 42 of 137


AGC-3 Alarm and Parameter List

Digital input 23-27 setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

3000 Digital input 23

0.0 s Designer’s The input is


3001 Dig. input 23 Delay 10.0 s
100.0 s Reference configurable and can
Relay Not used Handbook have different
3002 Dig. input 23 Not used functions in different
output A Option-dep.
units.
Relay Not used Inputs 24-27 are by
3003 Dig. input 23 Not used
output B Option-dep. default used for
OFF breaker feedback.
3004 Dig. input 23 Enable OFF
ON These inputs are only
available if no MB or
Warning
3005 Dig. input 23 Fail class F1…F7 TB is present in the
(F2)
application.
N/O
3006 Dig. input 23 N/X N/O
N/C

The same settings apply to inputs 24-27, settings 3010 to 3040.

Digital input 43-55 setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

3130 Digital input 43

0.0 s Option M12 The input is


3131 Dig. input 43 Delay 10.0 s
100.0 s configurable and can
Relay Not used have different
3132 Dig. input 43 Not used functions in different
output A Option-dep.
units.
Relay Not used
3133 Dig. input 43 Not used
output B Option-dep.
OFF
3134 Dig. input 43 Enable OFF
ON
Warning
3135 Dig. input 43 Fail class F1…F7
(F2)
N/O
3136 Dig. input 43 N/X N/O
N/C

The same settings apply to inputs 44-55, settings 3140 to 3250.

DEIF A/S Page 43 of 137


AGC-3 Alarm and Parameter List

Digital input 91-97 setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

3330 Digital input 91

0.0 s Option: The input is


3331 Dig. input 91 Delay 10.0 s
100.0 s 7 binary configurable and can
Relay Not used inputs in slot have different
3332 Dig. input 91 Not used #6 functions in different
output A Option-dep.
units.
Relay Not used
3333 Dig. input 91 Not used
output B Option-dep.
OFF
3334 Dig. input 91 Enable OFF
ON
Warning
3335 Dig. input 91 Fail class F1…F7
(F2)
N/O
3336 Dig. input 91 N/O - N/C N/O
N/C

The same settings apply to inputs 92-97, settings 3340 to 3390.

DEIF A/S Page 44 of 137


AGC-3 Alarm and Parameter List

Digital input 102-108 setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

3400 Digital input 102

OFF Designer’s The input is


3401 Wire fail 102 Enable OFF
ON Reference configurable and can
0.0 s Handbook have different
3402 Dig. input 102 Delay 10.0 s functions in different
100.0 s
units.
Relay Not used (Only available if multi-
3403 Dig. input 102 Not used
output A Option-dep. input 102 is configured
Relay Not used to ‘digital’).
3404 Dig. input 102 Not used
output B Option-dep.
OFF
3405 Dig. input 102 Enable OFF
ON
Warning
3406 Dig. input 102 Fail class F1…F7
(F2)

3410 Digital input 105

OFF Designer’s The input is


3411 Wire fail 105 Enable OFF
ON Reference configurable and can
0.0 s Handbook have different
3412 Dig. input 105 Delay 10.0 s functions in different
100.0 s
units.
Relay Not used (Only available if multi-
3413 Dig. input 105 Not used
output A Option-dep. input 105 is configured
Relay Not used to ‘digital’).
3414 Dig. input 105 Not used
output B Option-dep.
OFF
3415 Dig. input 105 Enable OFF
ON
Warning
3416 Dig. input 105 Fail class F1…F7
(F2)

3420 Digital input 108

OFF Designer’s The input is


3421 Wire fail 108 Enable OFF
ON Reference configurable and can
0.0 s Handbook have different
3422 Dig. input 108 Delay 10.0 s functions in different
100.0 s
units.
Relay Not used (Only available if multi-
3423 Dig. input 108 Not used
output A Option-dep. input 108 is configured
Relay Not used to ‘digital’).
3424 Dig. input 108 Not used
output B Option-dep.
OFF
3425 Dig. input 108 Enable OFF
ON
Warning
3426 Dig. input 108 Fail class F1…F7
(F2)

DEIF A/S Page 45 of 137


AGC-3 Alarm and Parameter List

Digital input 112-117 setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

3430 Digital input 112

0.0 s Designer’s The input is


3431 Dig. input 112 Delay 10.0 s
100.0 s Reference configurable and can
Relay Not used Handbook have different
3432 Dig. input 112 Not used functions in different
output A Option-dep.
units.
Relay Not used
3433 Dig. input 112 Not used
output B Option-dep.
OFF
3434 Dig. input 112 Enable OFF
ON
Warning
3435 Dig. input 112 Fail class F1…F7
(F2)
N/O
3436 Dig. input 112 N/X N/O
N/C

The same settings apply to inputs 113-117, settings 3440 to 3480.

DEIF A/S Page 46 of 137


AGC-3 Alarm and Parameter List

Emergency stop

No. Setting Min. Factory Notes Ref. Description


setting
Max.

3490 Emergency stop

0.0 s Designer’s Emergency stop input


3491 Emer. stop Delay 0.0 s
60.0 s Reference is intended for a
Not used Handbook normally closed
Relay contact.
3492 Emer. stop Option- Not used
output A
dependent
Not used
Relay
3493 Emer. stop Option- Not used
output B
dependent
OFF
3494 Emer. stop Enable ON
ON
Shutdown
3495 Emer. stop Fail class F1…F7
(F5)

Digital input 127-133 setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

3500 Digital input 127

0.0 s Option M13.8: The input is


3501 Dig. input 127 Delay 10.0 s
100.0 s 7 binary configurable and can
Relay Not used inputs in slot have different
3502 Dig. input 127 Not used #8 functions in different
output A Option-dep.
units.
Relay Not used
3503 Dig. input 127 Not used
output B Option-dep.
OFF
3504 Dig. input 127 Enable OFF
ON
Warning
3505 Dig. input 127 Fail class F1…F7
(F2)
N/O
3506 Dig. input 127 N/X N/O
N/C

The same settings apply to inputs 128-133, settings 3510 to 3560.

DEIF A/S Page 47 of 137


AGC-3 Alarm and Parameter List

Analogue input setup (option M15.6)

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4000 4-20 mA 91.1

4 mA Option Configurable analogue


4001 4-20 mA 91.1 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4002 4-20 mA 91.1 Delay 120.0 s mA inputs
600.0 s
Not used
Relay
4003 4-20 mA 91.1 Option- Not used
output A
dep.
Not used
Relay
4004 4-20 mA 91.1 Option- Not used
output B
dep.
OFF
4005 4-20 mA 91.1 Enable OFF
ON
Warning
4006 4-20 mA 91.1 Fail class F1…F7
(F2)

4010 4-20 mA 91.2

4 mA Option Configurable analogue


4011 4-20 mA 91.2 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4012 4-20 mA 91.2 Delay 120.0 s mA inputs
600.0 s
Not used
Relay
4013 4-20 mA 91.2 Option- Not used
output A
dep.
Not used
Relay
4014 4-20 mA 91.2 Option- Not used
output B
dep.
OFF
4015 4-20 mA 91.2 Enable OFF
ON
Warning
4016 4-20 mA 91.2 Fail class F1…F7
(F2)

4020 Wire fail 4-20 mA 91

Not used Option The wire fault will detect


Relay
4021 W. fail ana 91 Option- Not used M15.6: if the current drops
output A
dep. 4 x 4-20 below 2mA or exceeds
Not used mA inputs 22 mA. In both cases the
Relay alarm will be activated.
4022 W. fail ana 91 Option- Not used
output B
dep.
OFF
4023 W. fail ana 91 Enable OFF
ON
Warning
4024 W. fail ana 91 Fail class F1…F7
(F2)

4030 4-20 mA 93.1

4 mA Option Configurable analogue


4031 4-20 mA 93.1 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4032 4-20 mA 93.1 Delay 120.0 s mA inputs
600.0 s

DEIF A/S Page 48 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Not used
Relay
4033 4-20 mA 93.1 Option- Not used
output A
dep.
Not used
Relay
4034 4-20 mA 93.1 Option- Not used
output B
dep.
OFF
4035 4-20 mA 93.1 Enable OFF
ON
Warning
4036 4-20 mA 93.1 Fail class F1…F7
(F2)

4040 4-20 mA 93.2

4 mA Option Configurable analogue


4041 4-20 mA 93.2 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4042 4-20 mA 93.2 Delay 120.0 s mA inputs
600.0 s
Not used
Relay
4043 4-20 mA 93.2 Option- Not used
output A
dep.
Not used
Relay
4044 4-20 mA 93.2 Option- Not used
output B
dep.
OFF
4045 4-20 mA 93.2 Enable OFF
ON
Warning
4046 4-20 mA 93.2 Fail class F1…F7
(F2)

4050 Wire fail 4-20 mA 93

Not used Option The wire fault will detect


Relay
4051 W. fail ana 93 Option- Not used M15.6: if the current drops
output A
dep. 4 x 4-20 below 2mA or exceeds
Not used mA inputs 22mA. In both cases the
Relay alarm will be activated.
4052 W. fail ana 93 Option- Not used
output B
dep.
OFF
4053 W. fail ana 93 Enable OFF
ON
Warning
4054 W. fail ana 93 Fail class F1…F7
(F2)

4060 4-20 mA 95.1

4 mA Option Configurable analogue


4061 4-20 mA 95.1 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4062 4-20 mA 95.1 Delay 120.0 s mA inputs
600.0 s
Not used
Relay
4063 4-20 mA 95.1 Option- Not used
output A
dep.
Not used
Relay
4064 4-20 mA 95.1 Option- Not used
output B
dep.
OFF
4065 4-20 mA 95.1 Enable OFF
ON
Warning
4066 4-20 mA 95.1 Fail class F1…F7
(F2)

4070 4-20 mA 95.2

DEIF A/S Page 49 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4 mA Option Configurable analogue


4071 4-20 mA 95.2 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4072 4-20 mA 95.2 Delay 120.0 s mA inputs
600.0 s
Not used
Relay
4073 4-20 mA 95.2 Option- Not used
output A
dep.
Not used
Relay
4074 4-20 mA 95.2 Option- Not used
output B
dep.
OFF
4075 4-20 mA 95.2 Enable OFF
ON
Warning
4076 4-20 mA 95.2 Fail class F1…F7
(F2)

4080 Wire fail 4-20 mA 95

Not used Option The wire fault will detect


Relay
4081 W. fail ana 95 Option- Not used M15.6: if the current drops
output A
dep. 4 x 4-20 below 2mA or exceeds
Not used mA inputs 22 mA. In both cases the
Relay alarm will be activated.
4082 W. fail ana 95 Option- Not used
output B
dep.
OFF
4083 W. fail ana 95 Enable OFF
ON
Warning
4084 W. fail ana 95 Fail class F1…F7
(F2)

4090 4-20 mA 97.1

4 mA Option Configurable analogue


4091 4-20 mA 97.1 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4092 4-20 mA 97.1 Delay 120.0 s mA inputs
600.0 s
Not used
Relay
4093 4-20 mA 97.1 Option- Not used
output A
dep.
Not used
Relay
4094 4-20 mA 97.1 Option- Not used
output B
dep.
OFF
4095 4-20 mA 97.1 Enable OFF
ON
Warning
4096 4-20 mA 97.1 Fail class F1…F7
(F2)

4100 4-20 mA 97.2

4 mA Option Configurable analogue


4101 4-20 mA 97.2 Setpoint 10 mA
20 mA M15.6: input.
0.0 s 4 x 4-20
4102 4-20 mA 97.2 Delay 120.0 s mA inputs
600.0 s
Not used
Relay
4103 4-20 mA 97.2 Option- Not used
output A
dep.
Not used
Relay
4104 4-20 mA 97.2 Option- Not used
output B
dep.

DEIF A/S Page 50 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

OFF
4105 4-20 mA 97.2 Enable OFF
ON
Warning
4106 4-20 mA 97.2 Fail class F1…F7
(F2)

4110 Wire fail 4-20 mA 97

Not used Option The wire fault will detect


Relay
4111 W. fail ana 97 Option- Not used M15.6: if the current drops
output A
dep. 4 x 4-20 below 2mA or exceeds
Not used mA inputs 22mA. In both cases the
Relay alarm will be activated.
4112 W. fail ana 97 Option- Not used
output B
dep.
OFF
4113 W. fail ana 97 Enable OFF
ON
Warning
4114 W. fail ana 97 Fail class F1…F7
(F2)

DEIF A/S Page 51 of 137


AGC-3 Alarm and Parameter List

Multi-functional analogue input setup

Multi-input no. 102

The available menus for multi-input no. 102 depend on the input type configured
in the PC utility software (menu 10980).

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4120 4-20 mA 102.1

4 mA Designer’s The multi-input 102 has


4121 4-20 mA 102.1 Setpoint 10 mA
20 mA Reference been configured as 4-
0.0 s Handbook 20mA.
4122 4-20 mA 102.1 Delay 120.0 s
999.0 s
Relay Not used
4123 4-20 mA 102.1 Not used
output A Option-dep.
Relay Not used
4124 4-20 mA 102.1 Not used
output B Option-dep.
OFF
4125 4-20 mA 102.1 Enable OFF
ON
Warning
4126 4-20 mA 102.1 Fail class F1…F7
(F2)

4130 4-20 mA 102.2

4 mA Designer’s The multi-input 102 has


4131 4-20 mA 102.2 Setpoint 10 mA
20 mA Reference been configured as 4-
0.0 s Handbook 20mA.
4132 4-20 mA 102.2 Delay 120.0 s
999.0 s
Relay Not used
4133 4-20 mA 102.2 Not used
output A Option-dep.
Relay Not used
4134 4-20 mA 102.2 Not used
output B Option-dep.
OFF
4135 4-20 mA 102.2 Enable OFF
ON
Warning
4136 4-20 mA 102.2 Fail class F1…F7
(F2)

4140 V DC 102.1

0.0 V DC 20.0 V Designer’s The multi-input 102 has


4141 V DC 102.1 Setpoint
40.0 V DC DC Reference been configured as V
0.2 s Handbook DC.
4142 V DC 102.1 Delay 10.0 s
999.0 s
Relay Not used
4143 V DC 102.1 Not used
output A Option-dep.
Relay Not used
4144 V DC 102.1 Not used
output B Option-dep.
OFF
4145 V DC 102.1 Enable OFF
ON
Warning
4146 V DC 102.1 Fail class F1…F7
(F2)

4150 V DC 102.2

0.0 V DC 20.0 V Designer’s The multi-input 102 has


4151 V DC 102.2 Setpoint
40.0 V DC DC Reference been configured as V

DEIF A/S Page 52 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.2 s Handbook DC.


4152 V DC 102.2 Delay 10.0 s
999.0 s
Relay Not used
4153 V DC 102.2 Not used
output A Option-dep.
Relay Not used
4154 V DC 102.2 Not used
output B Option-dep.
OFF
4155 V DC 102.2 Enable OFF
ON
Warning
4156 V DC 102.2 Fail class F1…F7
(F2)

4160 Pt100 102.1

-49 Designer’s The multi-input 102 has


4161 PT 102.1 Setpoint 80
482 Reference been configured as
0.0 s Handbook Pt100.
4162 PT 102.1 Delay 5.0 s Pt100 setpoint can be
999.0 s
in deg. C or Fahrenheit,
Relay Not used dependent on the unit
4163 PT 102.1 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4164 PT 102.1 Not used
output B Option-dep.
OFF
4165 PT 102.1 Enable OFF
ON
Warning
4166 PT 102.1 Fail class F1…F7
(F2)

4170 Pt100 102.2

-49 Designer’s The multi-input 102 has


4171 PT 102.2 Setpoint 80
482 Reference been configured as
0.0 s Handbook Pt100.
4172 PT 102.2 Delay 10.0 s Pt100 setpoint can be
999.0 s
in deg. C or Fahrenheit,
Relay Not used dependent on the unit
4173 PT 102.2 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4174 PT 102.2 Not used
output B Option-dep.
OFF
4175 PT 102.2 Enable OFF
ON
Warning
4176 PT 102.2 Fail class F1…F7
(F2)

4180 VDO oil 102.1

0.0 Designer’s The multi-input 102 has


4181 VDO oil 102.1 Setpoint 4.0
145.0 Reference been configured as
0.0 s Handbook VDO oil pressure.
4182 VDO oil 102.1 Delay 5.0 s Oil pressure setpoint
999.0 s
can be in Bar or PSI,
Relay Not used dependent on the unit
4183 VDO oil 102.1 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4184 VDO oil 102.1 Not used
output B Option-dep.
OFF
4185 VDO oil 102.1 Enable OFF
ON
Warning
4186 VDO oil 102.1 Fail class F1…F7
(F2)

4190 VDO oil 102.2

DEIF A/S Page 53 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.0 Designer’s The multi-input 102 has


4191 VDO oil 102.2 Setpoint 5.0
145.0 Reference been configured as
0.0 s Handbook VDO oil pressure.
4192 VDO oil 102.2 Delay 5.0 s Oil pressure setpoint
999.0 s
can be in Bar or PSI,
Relay Not used dependent on the unit
4193 VDO oil 102.2 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4194 VDO oil 102.2 Not used
output B Option-dep.
OFF
4195 VDO oil 102.2 Enable OFF
ON
Warning
4196 VDO oil 102.2 Fail class F1…F7
(F2)

4200 VDO water 102.1

-49 Designer’s The multi-input 102 has


4201 VDO water 102.1 Setpoint 100
482 Reference been configured as
0.0 s Handbook VDO water
4202 VDO water 102.1 Delay 5.0 s temperature.
999.0 s
Water temperature
Relay Not used setpoint can be in deg.
4203 VDO water 102.1 Not used
output A Option-dep. C or Fahrenheit,
Relay Not used dependent on the unit
4204 VDO water 102.1 Not used
output B Option-dep. selection (setting
10970).
OFF
4205 VDO water 102.1 Enable OFF
ON
Warning
4206 VDO water 102.1 Fail class F1…F7
(F2)

4210 VDO water 102.2

-49 Designer’s The multi-input 102 has


4211 VDO water 102.2 Setpoint 110
482 Reference been configured as
0.0 s Handbook VDO water
4212 VDO water 102.2 Delay 5.0 s temperature.
999.0 s
Water temperature
Relay Not used setpoint can be in deg.
4213 VDO water 102.2 Not used
output A Option-dep. C or Fahrenheit,
Relay Not used dependent on the unit
4214 VDO water 102.2 Not used
output B Option-dep. selection (setting
10970).
OFF
4215 VDO water 102.2 Enable OFF
ON
Warning
4216 VDO water 102.2 Fail class F1…F7
(F2)

4220 VDO fuel level 102.1

0% Designer’s The multi-input 102 has


4221 VDO fuel 102.1 Setpoint 10%
100% Reference been configured as
0.0 s Handbook VDO fuel level.
4222 VDO fuel 102.1 Delay 10.0 s
999.0 s
Relay Not used
4223 VDO fuel 102.1 Not used
output A Option-dep.
Relay Not used
4224 VDO fuel 102.1 Not used
output B Option-dep.
OFF
4225 VDO fuel 102.1 Enable OFF
ON
Warning
4226 VDO fuel 102.1 Fail class F1…F7
(F2)

DEIF A/S Page 54 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4230 VDO fuel level 102.2

0% Designer’s The multi-input 102 has


4231 VDO fuel 102.2 Setpoint 5%
100% Reference been configured as
0.0 s Handbook VDO fuel level.
4232 VDO fuel 102.2 Delay 10.0 s
999.0 s
Relay Not used
4233 VDO fuel 102.2 Not used
output A Option-dep.
Relay Not used
4234 VDO fuel 102.2 Not used
output B Option-dep.
OFF
4235 VDO fuel 102.2 Enable OFF
ON
Warning
4236 VDO fuel 102.2 Fail class F1…F7
(F2)

4240 Wire fail 102

Relay Not used Designer’s The wire break fault


4241 W. fail 102 Not used
output A Option-dep. Reference detection is activated.
Relay Not used Handbook
4242 W. fail 102 Not used
output B Option-dep.
OFF
4243 W. fail 102 Enable OFF
ON
Warning
4244 W. fail 102 Fail class F1…F7
(F2)

DEIF A/S Page 55 of 137


AGC-3 Alarm and Parameter List

Multi-input no. 105

The available menus for multi-input no. 105 depend on the input type configured
in the PC utility software (menu 10990).

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4250 4-20 mA 105.1

4 mA Designer’s The multi-input 105 has


4251 4-20 mA 105.1 Setpoint 10 mA
20 mA Reference been configured as 4-
0.0 s Handbook 20mA.
4252 4-20 mA 105.1 Delay 120.0 s
999.0 s
Relay Not used
4253 4-20 mA 105.1 Not used
output A Option-dep.
Relay Not used
4254 4-20 mA 105.1 Not used
output B Option-dep.
OFF
4255 4-20 mA 105.1 Enable OFF
ON
Warning
4256 4-20 mA 105.1 Fail class F1…F7
(F2)

4260 4-20 mA 105.2

4 mA Designer’s The multi-input 105 has


4261 4-20 mA 105.2 Setpoint 10 mA
20 mA Reference been configured as 4-
0.0 s Handbook 20mA.
4262 4-20 mA 105.2 Delay 120.0 s
999.0 s
Relay Not used
4263 4-20 mA 105.2 Not used
output A Option-dep.
Relay Not used
4264 4-20 mA 105.2 Not used
output B Option-dep.
OFF
4265 4-20 mA 105.2 Enable OFF
ON
Warning
4266 4-20 mA 105.2 Fail class F1…F7
(F2)

4270 V DC 105.1

0.0 V DC 20.0 V Designer’s The multi-input 105 has


4271 V DC 105.1 Setpoint
40.0 V DC DC Reference been configured as V
0.2 s Handbook DC.
4272 V DC 105.1 Delay 10.0 s
999.0 s
Relay Not used
4273 V DC 105.1 Not used
output A Option-dep.
Relay Not used
4274 V DC 105.1 Not used
output B Option-dep.
OFF
4275 V DC 105.1 Enable OFF
ON
Warning
4276 V DC 105.1 Fail class F1…F7
(F2)

4280 V DC 105.2

0.0 V DC 20.0 V Designer’s The multi-input 105 has


4281 V DC 105.2 Setpoint
40.0 V DC DC Reference been configured as V
0.2 s Handbook DC.
4282 V DC 105.2 Delay 10.0 s
999.0 s

DEIF A/S Page 56 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Relay Not used


4283 V DC 105.2 Not used
output A Option-dep.
Relay Not used
4284 V DC 105.2 Not used
output B Option-dep.
OFF
4285 V DC 105.2 Enable OFF
ON
Warning
4286 V DC 105.2 Fail class F1…F7
(F2)

4290 Pt100 105.1

-49 Designer’s The multi-input 105 has


4291 PT 105.1 Setpoint 80
482 Reference been configured as
0.0 s Handbook Pt100.
4292 PT 105.1 Delay 5.0 s Pt100 setpoint can be
999.0 s
in deg. C or Fahrenheit,
Relay Not used dependent on the unit
4293 PT 105.1 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4294 PT 105.1 Not used
output B Option-dep.
OFF
4295 PT 105.1 Enable OFF
ON
Warning
4296 PT 105.1 Fail class F1…F7
(F2)

4300 Pt100 105.2

-49 Designer’s The multi-input 105 has


4301 PT 105.2 Setpoint 80
482 Reference been configured as
0.0 s Handbook Pt100.
4302 PT 105.2 Delay 10.0 s Pt100 setpoint can be
999.0 s
in deg. C or Fahrenheit,
Relay Not used dependent on the unit
4303 PT 105.2 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4304 PT 105.2 Not used
output B Option-dep.
OFF
4305 PT 105.2 Enable OFF
ON
Warning
4306 PT 105.2 Fail class F1…F7
(F2)

4310 VDO oil 105.1

0.0 Designer’s The multi-input 105 has


4311 VDO oil 105.1 Setpoint 4.0
145.0 Reference been configured as
0.0 s Handbook VDO oil pressure.
4312 VDO oil 105.1 Delay 5.0 s Oil pressure setpoint
999.0 s
can be in Bar or PSI,
Relay Not used dependent on the unit
4313 VDO oil 105.1 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4314 VDO oil 105.1 Not used
output B Option-dep.
OFF
4315 VDO oil 105.1 Enable OFF
ON
Warning
4316 VDO oil 105.1 Fail class F1…F7
(F2)

4320 VDO oil 105.2

0.0 Designer’s The multi-input 105 has


4321 VDO oil 105.2 Setpoint 5.0
145.0 Reference been configured as

DEIF A/S Page 57 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.0 s Handbook VDO oil pressure.


4322 VDO oil 105.2 Delay 5.0 s
999.0 s Oil pressure setpoint
Relay Not used can be in Bar or PSI,
4323 VDO oil 105.2 Not used dependent on the unit
output A Option-dep.
selection (setting
Relay Not used 10970).
4324 VDO oil 105.2 Not used
output B Option-dep.
OFF
4325 VDO oil 105.2 Enable
ON
OFF

Warning
4326 VDO oil 105.2 Fail class F1…F7
(F2)

4330 VDO water 105.1

VDO water -49 Designer’s The multi-input 105 has


4331 Setpoint 100
105.1 482 Reference been configured as
VDO water 0.0 s Handbook VDO water
4332 Delay 5.0 s temperature.
105.1 999.0 s
Water temperature
VDO water Relay Not used setpoint can be in deg.
4333 Not used
105.1 output A Option-dep. C or Fahrenheit,
VDO water Relay Not used dependent on the unit
4334 Not used
105.1 output B Option-dep. selection (setting
10970).
VDO water OFF
4335 Enable OFF
105.1 ON
VDO water Warning
4336 Fail class F1…F7
105.1 (F2)

4340 VDO water 105.2

VDO water -49 Designer’s The multi-input 105 has


4341 Setpoint 110
105.2 482 Reference been configured as
VDO water 0.0 s Handbook VDO water
4342 Delay 5.0 s temperature.
105.2 999.0 s
Water temperature
VDO water Relay Not used setpoint can be in deg.
4343 Not used
105.2 output A Option-dep. C or Fahrenheit,
VDO water Relay Not used dependent on the unit
4344 Not used
105.2 output B Option-dep. selection (setting
10970).
VDO water OFF
4345 Enable OFF
105.2 ON
VDO water Warning
4346 Fail class F1…F7
105.2 (F2)

4350 VDO fuel level 105.1

0% Designer’s The multi-input 105 has


4351 VDO fuel 105.1 Setpoint 10%
100% Reference been configured as
0.0 s Handbook VDO fuel level.
4352 VDO fuel 105.1 Delay 10.0 s
999.0 s
Not used
Relay
4353 VDO fuel 105.1 Option Not used
output A
dependent
Relay Not used
4354 VDO fuel 105.1 Not used
output B Option-dep.
OFF
4535 VDO fuel 105.1 Enable OFF
ON
Warning
4356 VDO fuel 105.1 Fail class F1…F7
(F2)

DEIF A/S Page 58 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4360 VDO fuel level 105.2

0% Designer’s The multi-input 105 has


4361 VDO fuel 105.2 Setpoint 5%
100% Reference been configured as
0.0 s Handbook VDO fuel level.
4362 VDO fuel 105.2 Delay 10.0 s
999.0 s
Relay Not used
4363 VDO fuel 105.2 Not used
output A Option-dep.
Relay Not used
4364 VDO fuel 105.2 Not used
output B Option-dep.
OFF
4365 VDO fuel 105.2 Enable OFF
ON
Warning
4366 VDO fuel 105.2 Fail class F1…F7
(F2)

4370 Wire fail 105

Not used Designer’s The wire break fault


Relay
4371 W. fail 105 Option Not used Reference detection is activated.
output A
dependent Handbook
Relay Not used
4372 W. fail 105 Not used
output B Option-dep.
OFF
4373 W. fail 105 Enable OFF
ON
Warning
4374 W. fail 105 Fail class F1…F7
(F2)

DEIF A/S Page 59 of 137


AGC-3 Alarm and Parameter List

Multi-input no. 108

The available menus for multi-input no. 108 depend on the input type configured
in the PC utility software (menu 11000).

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4380 4-20 mA 108.1

4 mA Designer’s The multi-input 108 has


4381 4-20 mA 108.1 Setpoint 10 mA
20 mA Reference been configured as 4-
0.0 s Handbook 20mA.
4382 4-20 mA 108.1 Delay 120.0 s
999.0 s
Relay Not used
4383 4-20 mA 108.1 Not used
output A Option-dep.
Relay Not used
4384 4-20 mA 108.1 Not used
output B Option-dep.
OFF
4385 4-20 mA 108.1 Enable OFF
ON
Warning
4386 4-20 mA 108.1 Fail class F1…F7
(F2)

4390 4-20 mA 108.2

4 mA Designer’s The multi-input 108 has


4391 4-20 mA 108.2 Setpoint 10 mA
20 mA Reference been configured as 4-
0.0 s Handbook 20mA.
4392 4-20 mA 108.2 Delay 120.0 s
999.0 s
Relay Not used
4393 4-20 mA 108.2 Not used
output A Option-dep.
Relay Not used
4394 4-20 mA 108.2 Not used
output B Option-dep.
OFF
4395 4-20 mA 108.2 Enable OFF
ON
Warning
4396 4-20 mA 108.2 Fail class F1…F7
(F2)

4400 V DC 108.1

0.0 V DC 20.0 V Designer’s The multi-input 108 has


4401 V DC 108.1 Setpoint
40.0 V DC DC Reference been configured as V
0.2 s Handbook DC.
4402 V DC 108.1 Delay 10.0 s
999.0 s
Relay Not used
4403 V DC 108.1 Not used
output A Option-dep.
Relay Not used
4404 V DC 108.1 Not used
output B Option-dep.
OFF
4405 V DC 108.1 Enable OFF
ON
Warning
4406 V DC 108.1 Fail class F1…F7
(F2)

4410 V DC 108.2

0.0 V DC 20.0 V Designer’s The multi-input 108 has


4411 V DC 108.2 Setpoint
40.0 V DC DC Reference been configured as V
0.2 s Handbook DC.
4412 V DC 108.2 Delay 10.0 s
999.0 s

DEIF A/S Page 60 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Relay Not used


4413 V DC 108.2 Not used
output A Option-dep.
Relay Not used
4414 V DC 108.2 Not used
output B Option-dep.
OFF
4415 V DC 108.2 Enable OFF
ON
Warning
4416 V DC 108.2 Fail class F1…F7
(F2)

4420 Pt100 108.1

-49 Designer’s The multi-input 108 has


4421 PT 108.1 Setpoint 80
482 Reference been configured as
0.0 s Handbook Pt100.
4422 PT 108.1 Delay 5.0 s Pt100 setpoint can be
999.0 s
in deg. C or Fahrenheit,
Relay Not used dependent on the unit
4423 PT 108.1 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4424 PT 108.1 Not used
output B Option-dep.
OFF
4425 PT 108.1 Enable OFF
ON
Warning
4426 PT 108.1 Fail class F1…F7
(F2)

4430 Pt100 108.2

-49 Designer’s The multi-input 108 has


4431 PT 108.2 Setpoint 80
482 Reference been configured as
0.0 s Handbook Pt100.
4432 PT 108.2 Delay 10.0 s Pt100 setpoint can be
999.0 s
in deg. C or Fahrenheit,
Relay Not used dependent on the unit
4433 PT 108.2 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4434 PT 108.2 Not used
output B Option-dep.
OFF
4435 PT 108.2 Enable OFF
ON
Warning
4436 PT 108.2 Fail class F1…F7
(F2)

4440 VDO oil 108.1

0.0 Designer’s The multi-input 108 has


4441 VDO oil 108.1 Setpoint 4.0
145.0 Reference been configured as
0.0 s Handbook VDO oil pressure.
4442 VDO oil 108.1 Delay 5.0 s Oil pressure setpoint
999.0 s
can be in Bar or PSI,
Relay Not used dependent on the unit
4443 VDO oil 108.1 Not used
output A Option-dep. selection (setting
Relay Not used 10970).
4444 VDO oil 108.1 Not used
output B Option-dep.
OFF
4445 VDO oil 108.1 Enable OFF
ON
Warning
4446 VDO oil 108.1 Fail class F1…F7
(F2)

4450 VDO oil 108.2

0.0 Designer’s The multi-input 108 has


4451 VDO oil 108.2 Setpoint 5.0
145.0 Reference been configured as

DEIF A/S Page 61 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.0 s Handbook VDO oil pressure.


4452 VDO oil 108.2 Delay 5.0 s
999.0 s Oil pressure setpoint
Relay Not used can be in Bar or PSI,
4453 VDO oil 108.2 Not used dependent on the unit
output A Option-dep.
selection (setting
Relay Not used 10970).
4454 VDO oil 108.2 Not used
output B Option-dep.
OFF
4455 VDO oil 108.2 Enable OFF
ON
Warning
4456 VDO oil 108.2 Fail class F1…F7
(F2)

4460 VDO water 108.1

VDO water -49 Designer’s The multi-input 108 has


4461 Setpoint 100
108.1 482 Reference been configured as
VDO water 0.0 s Handbook VDO water
4462 Delay 5.0 s temperature.
108.1 999.0 s
Water temperature
VDO water Relay Not used setpoint can be in deg.
4463 Not used
108.1 output A Option-dep. C or Fahrenheit,
VDO water Relay Not used dependent on the unit
4464 Not used
108.1 output B Option-dep. selection (setting
10970).
VDO water OFF
4465 Enable OFF
108.1 ON
VDO water Warning
4466 Fail class F1…F7
108.1 (F2)

4470 VDO water 108.2

VDO water -49 Designer’s The multi-input 108 has


4471 Setpoint 110
108.2 482 Reference been configured as
VDO water 0.0 s Handbook VDO water
4472 Delay 5.0 s temperature.
108.2 999.0 s
Water temperature
VDO water Relay Not used setpoint can be in deg.
4473 Not used
108.2 output A Option-dep. C or Fahrenheit,
VDO water Relay Not used dependent on the unit
4474 Not used
108.2 output B Option-dep. selection (setting
10970).
VDO water OFF
4475 Enable OFF
108.2 ON
VDO water Warning
4476 Fail class F1…F7
108.2 (F2)

4480 VDO fuel level 108.1

0% Designer’s The multi-input 108 has


4481 VDO fuel 108.1 Setpoint 10%
100% Reference been configured as
0.0 s Handbook VDO fuel level.
4482 VDO fuel 108.1 Delay 10.0 s
999.0 s
Relay Not used
4483 VDO fuel 108.1 Not used
output A Option-dep.
Relay Not used
4484 VDO fuel 108.1 Not used
output B Option-dep.
OFF
4485 VDO fuel 108.1 Enable OFF
ON
Warning
4486 VDO fuel 108.1 Fail class F1…F7
(F2)

4490 VDO fuel level 108.2

DEIF A/S Page 62 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0% Designer’s The multi-input 108 has


4491 VDO fuel 108.2 Setpoint 5%
100% Reference been configured as
0.0 s Handbook VDO fuel level.
4492 VDO fuel 108.2 Delay 10.0 s
999.0 s
Relay Not used
4493 VDO fuel 108.2 Not used
output A Option-dep.
Relay Not used
4494 VDO fuel 108.2 Not used
output B Option-dep.
OFF
4495 VDO fuel 108.2 Enable OFF
ON
Warning
4496 VDO fuel 108.2 Fail class F1…F7
(F2)

4500 Wire fail 108

Relay Not used Designer’s The wire break fault


4501 W. fail 108 Not used
output A Option-dep. Reference detection is activated.
Relay Not used Handbook
4502 W. fail 108 Not used
output B Option-dep.
OFF
4503 W. fail 108 Enable OFF
ON
Warning
4504 W. fail 108 Fail class F1…F7
(F2)

DEIF A/S Page 63 of 137


AGC-3 Alarm and Parameter List

Speed and running feedback setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4510 Overspeed 1

100.0% Designer’s The setpoint in


4511 Overspeed 1 Setpoint 110.0%
150.0% Reference percentage relates to
0.0 s Handbook nominal RPM.
4512 Overspeed 1 Delay 5.0 s
100.0 s
Relay Not used
4513 Overspeed 1 Not used
output A Option-dep.
Relay Not used
4514 Overspeed 1 Not used
output B Option-dep.
OFF
4515 Overspeed 1 Enable ON
ON
Warning
4516 Overspeed 1 Fail class F1…F7
(F2)

4520 Overspeed 2

100.0% Designer’s The setpoint in


4521 Overspeed 2 Setpoint 120.0%
150.0% Reference percentage relates to
0.0 s Handbook nominal RPM.
4522 Overspeed 2 Delay 1.0 s
100.0 s
Relay Not used
4523 Overspeed 2 Not used
output A Option-dep.
Relay Not used
4524 Overspeed 2 Not used
output B Option-dep.
OFF
4525 Overspeed 2 Enable ON
ON
Shutdown
4526 Overspeed 2 Fail class F1…F7
(F5)

4530 Crank failure

1 RPM Designer’s If MPU is chosen as the


4531 Crank failure Setpoint 50 RPM
400 RPM Reference primary running
0.0 s Handbook feedback, this alarm
4532 Crank failure Delay 2.0 s will be raised if the
20.0 s
specified rpm is not
Relay Not used reached before the
4533 Crank failure Not used
output A Option-dep. delay has expired.
Relay Not used
4534 Crank failure Not used
output B Option-dep.
OFF
4535 Crank failure Enable OFF
ON
Warning
4536 Crank failure Fail class F1…F7
(F2)

4540 Running feedback failure

0.0 s Designer’s If running is detected


4541 Run feedb. fail Delay 2.0 s
20.0 s Reference on the frequency
Relay Not used Handbook (secondary), but the
4542 Run feedb. fail Not used primary running
output A Option-dep.
feedback, e.g. digital
Relay Not used input, has not detected
4543 Run feedb. fail Not used
output B Option-dep.

DEIF A/S Page 64 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

OFF running, this alarm will


4544 Run feedb. fail Enable ON
ON be raised after the
Warning adjusted delay time.
4545 Run feedb. fail Fail class F1…F7
(F2)

4550 Magnetic pickup wirebreak

Relay Not used Designer’s The wirebreak


4551 MPU wirebreak Not used
output A Option-dep. Reference monitoring is only
Relay Not used Handbook active when the engine
4552 MPU wirebreak Not used is at standstill.
output B Option-dep.
OFF
4553 MPU wirebreak Enable OFF
ON
Warning
4554 MPU wirebreak Fail class F1…F7
(F2)

4560 Hz/Voltage failure

1.0 s Designer’s If the frequency and


4561 Hz/V failure Delay 30.0 s
99.0 s Reference voltage are not within
Relay Not used Handbook the limits after the
4562 Hz/V failure Not used running feedback is
output A Option-dep.
received, this alarm
Relay Not used will be raised when the
4563 Hz/V failure Not used
output B Option-dep. delay time has
OFF expired.
4564 Hz/V failure Enable ON
ON
Block
4565 Hz/V failure Fail class F1…F7
(F1)

4570 Start failure

Relay Not used Designer’s The start failure alarm


4571 Start failure Not used
output A Option-dep. Reference occurs, if the gen-set
Relay Not used Handbook has not started after
4572 Start failure Not used the number of start
output B Option-dep.
attempts.
Block
4573 Start failure Fail class F1…F7
(F1)

4580 Stop failure

10.0 s Designer’s A stop failure alarm


4581 Stop failure Delay 30.0 s
120.0 s Reference will appear if the
Relay Not used Handbook primary running
4582 Stop failure Not used feedback or the
output A Option-dep.
generator voltage and
Relay Not used frequency are still
583 Stop failure Not used
output B Option-dep. present after the delay
OFF time has expired.
4584 Stop failure Enable ON
ON
Shutdown
4585 Stop failure Fail class F1…F7
(F5)

DEIF A/S Page 65 of 137


AGC-3 Alarm and Parameter List

Analogue input setup (option M15.8)

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4800 4-20 mA 127.1

4 mA Option: Configurable analogue


4801 4-20 mA 127.1 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4802 4-20 mA 127.1 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4803 4-20 mA 127.1 Not used
output A Option-dep.
Relay Not used
4804 4-20 mA 127.1 Not used
output B Option-dep.
OFF
4805 4-20 mA 127.1 Enable OFF
ON
Warning
4806 4-20 mA 127.1 Fail class F1…F7
(F2)

4810 4-20 mA 127.2

4 mA Option: Configurable analogue


4811 4-20 mA 127.2 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4812 4-20 mA 127.2 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4813 4-20 mA 127.2 Not used
output A Option-dep.
Relay Not used
4814 4-20 mA 127.2 Not used
output B Option-dep.
OFF
4815 4-20 mA 127.2 Enable OFF
ON
Warning
4816 4-20 mA 127.2 Fail class F1…F7
(F2)

4820 wire fail 4-20 mA 127

Relay Not used Option: The wire fault will


4821 W. fail ana 127 Not used
output A Option-dep. 4 x 4-20 mA detect if the current
Relay Not used inputs drops below 2mA or
4822 W. fail ana 127 Not used (M15.8) exceeds 22mA. In both
output B Option-dep.
cases the alarm will be
OFF activated.
4823 W. fail ana 127 Enable OFF
ON
Warning
4824 W. fail ana 127 Fail class F1…F7
(F2)

4830 4-20 mA 129.1

4 mA Option: Configurable analogue


4831 4-20 mA 129.1 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4832 4-20 mA 129.1 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4833 4-20 mA 129.1 Not used
output A Option-dep.
Relay Not used
4834 4-20 mA 129.1 Not used
output B Option-dep.
OFF
4835 4-20 mA 129.1 Enable OFF
ON

DEIF A/S Page 66 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Warning
4836 4-20 mA 129.1 Fail class F1…F7
(F2)

4840 4-20 mA 129.2

4 mA Option: Configurable analogue


4841 4-20 mA 129.2 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4842 4-20 mA 129.2 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4843 4-20 mA 129.2 Not used
output A Option-dep.
Relay Not used
4844 4-20 mA 129.2 Not used
output B Option-dep.
OFF
4845 4-20 mA 129.2 Enable OFF
ON
Warning
4846 4-20 mA 129.2 Fail class F1…F7
(F2)

4850 Wire fail 4-20 mA 129.2

Relay Not used Option: The wire fault will


4851 W. fail ana 129 Not used
output A Option-dep. 4 x 4-20 mA detect if the current
Relay Not used inputs drops below 2mA or
4852 W. fail ana 129 Not used (M15.8) exceeds 22mA. In both
output B Option-dep.
cases the alarm will be
OFF activated.
4853 W. fail ana 129 Enable OFF
ON
Warning
4854 W. fail ana 129 Fail class F1…F7
(F2)

4860 4-20 mA 131.1

4 mA Option: Configurable analogue


4861 4-20 mA 131.1 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4862 4-20 mA 131.1 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4863 4-20 mA 131.1 Not used
output A Option-dep.
Relay Not used
4864 4-20 mA 131.1 Not used
output B Option-dep.
OFF
4865 4-20 mA 131.1 Enable OFF
ON
Warning
4866 4-20 mA 131.1 Fail class F1…F7
(F2)

4870 4-20 mA 131.2

4 mA Option: Configurable analogue


4871 4-20 mA 131.2 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4872 4-20 mA 131.2 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4873 4-20 mA 131.2 Not used
output A Option-dep.
Relay Not used
4874 4-20 mA 131.2 Not used
output B Option-dep.
OFF
4875 4-20 mA 131.2 Enable OFF
ON
Warning
4876 4-20 mA 131.2 Fail class F1…F7
(F2)

DEIF A/S Page 67 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4880 Wire fail 4-20 mA 131

Relay Not used Option: The wire fault will


4881 W. fail ana 131 Not used
output A Option-dep. 4 x 4-20 mA detect if the current
Relay Not used inputs drops below 2mA or
4882 W. fail ana 131 Not used (M15.8) exceeds 22mA. In both
output B Option-dep.
cases the alarm will be
OFF activated.
4883 W. fail ana 131 Enable OFF
ON
Warning
4884 W. fail ana 131 Fail class F1…F7
(F2)

4890 4-20 mA 133.1

4 mA Option: Configurable analogue


4891 4-20 mA 133.1 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4892 4-20 mA 133.1 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4893 4-20 mA 133.1 Not used
output A Option-dep.
Relay Not used
4894 4-20 mA 133.1 Not used
output B Option-dep.
OFF
4895 4-20 mA 133.1 Enable OFF
ON
Warning
4896 4-20 mA 133.1 Fail class F1…F7
(F2)

4900 4-20 mA 133.2

4 mA Option: Configurable analogue


4901 4-20 mA 133.2 Setpoint 10 mA
20 mA 4 x 4-20 mA input.
0.0 s inputs
4902 4-20 mA 133.2 Delay 120.0 s (M15.8)
600.0 s
Relay Not used
4903 4-20 mA 133.2 Not used
output A Option-dep.
Relay Not used
4904 4-20 mA 133.2 Not used
output B Option-dep.
OFF
4905 4-20 mA 133.2 Enable OFF
ON
Warning
4906 4-20 mA 133.2 Fail class F1…F7
(F2)

4910 Wire fail 4-20 mA 133

Relay Not used Option: The wire fault will


4911 W. fail ana 133 Not used
output A Option-dep. 4 x 4-20 mA detect if the current
Relay Not used inputs drops below 2mA or
4912 W. fail ana 133 Not used (M15.8) exceeds 22mA. In both
output B Option-dep.
cases the alarm will be
OFF activated.
4913 W. fail ana 133 Enable OFF
ON
Warning
4914 W. fail ana 133 Fail class F1…F7
(F2)

DEIF A/S Page 68 of 137


AGC-3 Alarm and Parameter List

Aux. supply setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

4960 U< auxiliary power supply terminal 1

8.0 V DC Designer’s The power supply on


4961 U< aux. term. 1 Setpoint 18.0 V DC
32.0 V DC Reference terminal 1 and 2 has
0.0 s Handbook been continuously
4962 U< aux. term. 1 Delay 1.0 s below the adjusted
999.0 s
setpoint until the delay
Relay Not used timer was expired.
4963 U< aux. term. 1 Not used
output A Option-dep.
Relay Not used
4964 U< aux. term. 1 Not used
output B Option-dep.
OFF
4965 U< aux. term. 1 Enable ON
ON
Warning
4966 U< aux. term. 1 Fail class F1…F7
(F2)

4970 U> auxiliary power supply terminal 1

12.0 V DC Designer’s The power supply on


4971 U> aux. term. 1 Setpoint 30.0 V DC
36.0 V DC Reference terminal 1 and 2 has
0.0 s Handbook been continuously
4972 U> aux. term. 1 Delay 1.0 s above the adjusted
999.0 s
setpoint until the delay
Relay Not used timer was expired.
4973 U> aux. term. 1 Not used
output A Option-dep.
Relay Not used
4974 U> aux. term. 1 Not used
output B Option-dep.
OFF
4975 U> aux. term. 1 Enable ON
ON
Warning
4976 U> aux. term. 1 Fail class F1…F7
(F2)

4980 U< auxiliary power supply terminal 98

8.0 V DC Designer’s The power supply on


4981 U> aux. term. 98 Setpoint 18.0 V DC
32.0 V DC Reference terminal 98 and 99 has
0.0 s Handbook been continuously
4982 U> aux. term. 98 Delay 1.0 s below the adjusted
999.0 s
setpoint until the delay
Relay Not used timer was expired.
4983 U> aux. term. 98 Not used
output A Option-dep.
Relay Not used
4984 U> aux. term. 98 Not used
output B Option-dep.
OFF
4985 U> aux. term. 98 Enable ON
ON
Warning
4986 U> aux. term. 98 Fail class F1…F7
(F2)

4990 U> auxiliary power supply terminal 98

8.0 V DC Designer’s The power supply on


4991 U> aux. term. 98 Setpoint 30.0 V DC
32.0 V DC Reference terminal 98 and 99 has
0.0 s Handbook been continuously
4992 U> aux. term. 98 Delay 1.0 s above the adjusted
999.0 s
setpoint until the delay
Not used timer was expired.
Relay
4993 U> aux. term. 98 Option Not used
output A
dependent

DEIF A/S Page 69 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Not used
Relay
4994 U> aux. term. 98 Option Not used
output B
dependent
OFF
4995 U> aux. term. 98 Enable ON
ON
Warning
4996 U> aux. term. 98 Fail class F1…F7
(F2)

Stop coil wirebreak and internal communication alarms

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6270 Stop coil wirebreak

Stop coil Relay Not used Designer’s The wirebreak


6271 Not used
wirebreak output A Option-dep. Reference monitoring is only
Stop coil Relay Not used Handbook active when the stop
6272 Not used coil output is
wirebreak output B Option-dep.
deactivated.
Stop coil OFF
6273 Enable OFF
wirebreak ON
Stop coil Warning
6274 Fail class F1…F7
wirebreak (F2)

6280 Internal communication fail

Relay Not used Designer’s This is the alarm for


6281 Int. comm. fail Not used
output A Option-dep. Reference communication fail
Relay Not used Handbook between the main
6282 Int. comm. fail Not used processor and the
output B Option-dep.
engine interface
Warning processor.
6283 Int. comm. fail Fail class F1…F7
(F2)

Engine heater failure

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6330 Engine heater 1

10 deg Designer’s
6331 Engine heater 1 Setpoint 30 deg
250 deg Reference
0.0 s Handbook
6332 Engine heater 1 Timer 10.0 s
300.0 s
Relay Not used
6333 Engine heater 1 Not used
output A Option-dep.
Relay Not used
6334 Engine heater 1 Not used
output B Option-dep.
OFF
6335 Engine heater 1 Enable OFF
ON
Warning
6336 Engine heater 1 Fail class F1…F7
(F2)

DEIF A/S Page 70 of 137


AGC-3 Alarm and Parameter List

Battery tests

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6410 Battery test

8.0 V Designer’s If the battery voltage


6411 Battery test Setpoint 18.0 V
32.0 V Reference drops below setpoint
1s Handbook during crank test the
6412 Battery test Timer 20 s alarm activates.
300 s
Power supply
Multi-input
102
Power
6413 Battery test Type Multi-input
supply
105
Multi-input
108
Relay Not used
6414 Battery test Not used
output A Option-dep.
OFF
6415 Battery test Enable OFF
ON
Warning
6416 Battery test Fail class F1…F7
(F2)

6420 Auto battery test

On Designer’s Automatic battery test


6421 Auto batt test Enable Off
Off Reference time setting.
Monday Handbook
6422 Auto batt test Day Monday
Sunday
0h
6423 Auto batt test Hours 10h
23 h
1
6424 Auto batt test Week 52
52
Start relay
6425 Auto batt test Relay Start relay
Option-dep.

6430 Battery asymmetry

Power supply Designer’s Battery asymmetry


Multi-input Reference input selections.
102 Handbook
Multi-input
6431 Batt. asymmetry T1 Multi-input
105
105
Multi-input
108
Power supply
Multi-input
102
Power
6432 Batt. asymmetry RF1 Multi-input
supply
105
Multi-input
108
Power supply
Multi-input
102
Multi-input
6433 Batt. asymmetry T2 Multi-input
108
105
Multi-input
108

DEIF A/S Page 71 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Power supply
Multi-input
102
Multi-input
6434 Batt. asymmetry RF2 Multi-input
102
105
Multi-input
108

6440 Battery asymmetry 1

0.1 V Designer’s If the battery voltage


6441 Battery asym 1 Setpoint 1.0 V
15.0 V Reference asymmetry between the
0.0 s Handbook single batteries
6442 Battery asym 1 Timer 1.0 s exceeds the setting, the
10.0 s
alarm will activate.
Relay Not used
6443 Battery asym 1 Not used
output A Option-dep.
Relay Not used
6444 Battery asym 1 Not used
output B Option-dep.
OFF
6445 Battery asym 1 Enable OFF
ON

6450 Battery asymmetry 2

0.1 V Designer’s If the battery voltage


6451 Battery asym 2 Setpoint 1.0 V
15.0 V Reference asymmetry between the
0.0 s Handbook single batteries
6452 Battery asym 2 Timer 1.0 s exceeds the setting, the
10.0 s
alarm will activate.
Relay Not used
6453 Battery asym 2 Not used
output A Option-dep.
Relay Not used
6454 Battery asym 2 Not used
output B Option-dep.
OFF
6455 Battery asym 2 Enable OFF
ON

DEIF A/S Page 72 of 137


AGC-3 Alarm and Parameter List

Max. ventilation

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6470 Max vent 1

20 deg Designer’s If the cooling fans fail to


6471 Max vent 1 Setpoint 95 deg
250 deg Reference operate and the coolant
0.0 s Handbook temperature exceeds
6472 Max vent 1 Timer 1.0 s the setting, the alarm
60.0 s
will activate.
Relay Not used
6473 Max vent 1 Not used
output A Option-dep.
Relay Not used
6474 Max vent 1 Not used
output B Option-dep.
OFF
6475 Max vent 1 Enable OFF
ON
Warning
6476 Max vent 1 Fail class F1…F7
(F2)

6480 Max vent 2

20 deg Designer’s If the cooling fans fail to


6481 Max vent 2 Setpoint 98 deg
250 deg Reference operate and the coolant
0.0 s Handbook temperature exceeds
6482 Max vent 2 Timer 1.0 s the setting, the alarm
60.0 s
will activate.
Relay Not used
6483 Max vent 2 Not used
output A Option-dep.
Relay Not used
6484 Max vent 2 Not used
output B Option-dep.
OFF
6485 Max vent 2 Enable OFF
ON
Shutdown
6486 Max vent 2 Fail class F1…F7
(F5)

DEIF A/S Page 73 of 137


AGC-3 Alarm and Parameter List

Switchboard error

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6500 Block switchboard error

0.0 s Designer’s If the binary input


6501 Blk. swbd error Timer 10.0 s
999.0 s Reference “switchboard error”
ON Handbook activates, a stopped
6502 Blk. swbd error Parallel OFF generator will be
OFF
blocked for start.
Relay Not used Parameter 6502:
6503 Blk. swbd error Not used
output A Option-dep. OFF: only AMS start is
Relay Not used affected
6504 Blk. swbd error Not used
output B Option-dep. ON: All starts are
affected.
OFF
6505 Blk. swbd error Enable OFF
ON
Warning
6506 Blk. swbd error Fail class F1…F7
(F2)

6510 Stop switchboard error

0.0 s Designer’s If the binary input


6511 Stp. swbd error Timer 1.0 s
999.0 s Reference “switchboard error”
Relay Not used Handbook activates, the gen-set
6512 Stp. swbd error Not used will be stopped.
output A Option-dep.
Relay Not used
6513 Stp. swbd error Not used
output B Option-dep.
OFF
6514 Stp. swbd error Enable OFF
ON
Shutdown
6515 Stp. swbd error Fail class F1…F7
(F5)

Switchboard error

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6540 Not in auto

10.0 s Designer’s
6541 Not in auto Timer 300.0 s
900.0 s Reference
Relay Not used Handbook
6542 Not in auto Not used
output A Option-dep.
Relay Not used
6543 Not in auto Not used
output B Option-dep.
OFF
6544 Not in auto Enable OFF
ON
Warning
6545 Not in auto Fail class F1…F7
(F2)

DEIF A/S Page 74 of 137


AGC-3 Alarm and Parameter List

External communication error

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7520 External communication error

1.0 s Option: Supervision of the


7521 Ext. comm. error Delay 10.0 s
100.0 s Modbus (H2) external communication
Relay Not used Profibus (H3) line. The alarm will
7522 Ext. comm. error Not used occur when there has
output A Option-dep.
not been any
Relay Not used communication during
7523 Ext. comm. error Not used
output B Option-dep. the time delay.
OFF
7524 Ext. comm. error Enable OFF
ON
Warning
7525 Ext. comm. error Fail class F1…F7
(F2)

7530 Internal communication ID

Designer’s The mode decides the


Manual Reference reaction of the power
CAN fail. Semi auto Handbook management system in
7532 Int. comm. ID Manual case of different errors
mode No mode
change on the CAN
communication lines.
Missing all Warning Mode:
7533 Int. comm. ID F1…F7
units (F2) - Manual
Fatal CAN Warning - Semi auto
7534 Int. comm. ID F1…F7
error (F2) - No mode change
Any DG Warning
7535 Int. comm. ID F1…F7
missing (F2)
Any mains Warning
7536 Int. comm. ID F1…F7
missing (F2)

DEIF A/S Page 75 of 137


AGC-3 Alarm and Parameter List

Engine interface communication alarms

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7570 EI comm. Error

0.0 s Option: Supervision of the EIC


7571 EI comm. error Timer 0.0 s
100.0 s J1939 and communication line.
Relay Not used MTU ADEC/ The alarm will occur
7572 EI comm. error Not used MDEC (H5) when there has not
output A Option-dep.
Cummins been any
Relay Not used Modbus communication during
7573 EI comm. error Not used
output B Option-dep. (H6) the time delay.
OFF J1939 (H7)
7574 EI comm. error Enable ON
ON
Warning
7575 EI comm. error Fail class F1…F7
(F2)

7580 EIC warning

0.0 s Option:
7581 EIC warning Timer 0.0 s
100.0 s J1939 and
Relay Not used MTU ADEC/
7582 EIC warning Not used MDEC (H5)
output A Option-dep.
Cummins
Relay Not used Modbus
7583 EIC warning Not used
output B Option-dep. (H6)
OFF J1939 (H7)
7584 EIC warning Enable ON
ON
Warning
7585 EIC warning Fail class F1…F7
(F2)

7590 EIC shutdown

0.0 s Option:
7591 EIC shutdown Timer 0.0 s
100.0 s J1939 and
Relay Not used MTU ADEC/
7592 EIC shutdown Not used MDEC (H5)
output A Option-dep.
Cummins
Relay Not used Modbus
7593 EIC shutdown Not used
output B Option-dep. (H6)
OFF J1939 (H7)
7594 EIC shutdown Enable ON
ON
Shutdown
7595 EIC shutdown Fail class F1…F7
(F5)

7600 EIC overspeed

100.0% Option:
7601 EIC overspeed Setpoint 110.0%
150.0% J1939 and
0.0 s MTU ADEC/
7602 EIC overspeed Timer 5.0 s MDEC (H5)
100.0 s
Cummins
Relay Not used Modbus
7603 EIC overspeed Not used
output A Option-dep. (H6)
Relay Not used J1939 (H7)
7604 EIC overspeed Not used
output B Option-dep.
OFF
7605 EIC overspeed Enable ON
ON
Warning
7606 EIC overspeed Fail class F1…F7
(F2)

DEIF A/S Page 76 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7610 EIC coolant temp. 1

-40 deg Option:


7611 EIC coolant t. 1 Setpoint 100 deg
410 deg J1939 and
0.0 s MTU ADEC/
7612 EIC coolant t. 1 Timer 5.0 s MDEC (H5)
100.0 s
Cummins
Relay Not used Modbus
7613 EIC coolant t. 1 Not used
output A Option-dep. (H6)
Relay Not used J1939 (H7)
7614 EIC coolant t. 1 Not used
output B Option-dep.
OFF
7615 EIC coolant t. 1 Enable ON
ON
Warning
7616 EIC coolant t. 1 Fail class F1…F7
(F2)

7620 EIC coolant temp. 2

-40 deg Option:


7621 EIC coolant t. 2 Setpoint 110 deg
410 deg J1939 and
0.0 s MTU ADEC/
7622 EIC coolant t. 2 Timer 5.0 s MDEC (H5)
100.0 s
Cummins
Relay Not used Modbus
7623 EIC coolant t. 2 Not used
output A Option-dep. (H6)
Relay Not used J1939 (H7)
7624 EIC coolant t. 2 Not used
output B Option-dep.
OFF
7625 EIC coolant t. 2 Enable ON
ON
Warning
7626 EIC coolant t. 2 Fail class F1…F7
(F2)

7630 EIC oil pressure 1

0.0 bar Option:


7631 EIC oil press. 1 Setpoint 2.0 bar
145.0 bar J1939 and
0.0 s MTU ADEC/
7632 EIC oil press. 1 Timer 5.0 s MDEC (H5)
100.0 s
Cummins
Relay Not used Modbus(H6)
7633 EIC oil press. 1 Not used
output A Option-dep. J1939 (H7)
Relay Not used
7634 EIC oil press. 1 Not used
output B Option-dep.
OFF
7635 EIC oil press. 1 Enable ON
ON
Warning
7636 EIC oil press. 1 Fail class F1…F7
(F2)

7640 EIC oil pressure 2

0.0 bar Option:


7641 EIC oil press. 2 Setpoint 1.0 bar
145.0 bar J1939 and
0.0 s MTU ADEC/
7642 EIC oil press. 2 Timer 5.0 s MDEC (H5)
100.0 s
Cummins
Relay Not used Modbus
7643 EIC oil press. 2 Not used
output A Option-dep. (H6)
Relay Not used J1939 (H7)
7644 EIC oil press. 2 Not used
output B Option-dep.
OFF
7645 EIC oil press. 2 Enable ON
ON

DEIF A/S Page 77 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Shutdown
7646 EIC oil press. 2 Fail class F1…F7
(F5)

7650 EIC oil temp 1

0 deg. Option:
7651 EIC oil temp. 1 Setpoint 40 deg.
410 deg J1939 and
0.0 s MTU ADEC/
7652 EIC oil temp. 1 Timer 5.0 s MDEC (H5)
100.0 s
Cummins
Relay Not used Modbus
7653 EIC oil temp. 1 Not used
output A Option-dep. (H6)
Relay Not used J1939 (H7)
7654 EIC oil temp. 1 Not used
output B Option-dep.
OFF
7655 EIC oil temp. 1 Enable ON
ON
Warning
7656 EIC oil temp. 1 Fail class F1…F7
(F2)

7660 EIC oil temp 2

0 deg. Option:
7661 EIC oil temp. 2 Setpoint 50 deg.
410 deg J1939 and
0.0 s MTU ADEC/
7662 EIC oil temp. 2 Timer 5.0 s MDEC (H5)
100.0 s
Cummins
Relay Not used Modbus
7663 EIC oil temp. 2 Not used
output A Option-dep. (H6)
Relay Not used J1939 (H7)
7664 EIC oil temp. 2 Not used
output B Option-dep.
OFF
7665 EIC oil temp. 2 Enable ON
ON
Shutdown
7666 EIC oil temp. 2 Fail class F1…F7
(F5)

DEIF A/S Page 78 of 137


AGC-3 Alarm and Parameter List

Power management communication error

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7870 Any BTB missing/appl hazard

Block Designer’s The “Any BTB missing”


7871 Any BTB missing Fail class F1…F7
(F1) Reference alarm is activated, if the
ON Handbook communication to any
7872 Appl hazard Enable ON BTB unit failed.
OFF
The application hazard
alarm is activated, if
Block different applications are
7873 Appl hazard Fail class F1…F7
(F1) installed in the
controllers.

Internal CAN communication error

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7930 CAN1 communication error

2.0 s Option: If both options H8.x are


7931 CAN1 com error Delay 10.0 s
600.0 s External I/O present, an error on
Relay Not used modules any of these will
7932 CAN1 com error Not used (H8.2) activate the alarm.
output A Option-dep.
Relay Not used
7933 CAN1 com error Not used
output B Option-dep.
OFF
7934 CAN1 com error Enable OFF
ON
Block
7935 CAN1 com error Fail class F1…F7
(F1)

7940 CAN2 comm error

2.0 s Option: If both options H8.x are


7941 CAN2 comm error Delay 10.0 s
600.0 s External I/O present, an error on
Relay Not used modules any of these will
7942 CAN2 comm error Not used (H8.8) activate the alarm.
output A Option-dep.
Relay Not used
7943 CAN2 comm error Not used
output B Option-dep.
OFF
7944 CAN2 comm error Enable OFF
ON
Block
7945 CAN2 comm error Fail class F1…F7
(F1)

DEIF A/S Page 79 of 137


AGC-3 Alarm and Parameter List

External I/O alarm setup

The alarms based on external I/O modules can only be configured using the PC
utility software.

Analogue inputs

No. Setting Min. Factory Notes Ref. Description


setting
Max.

12000 Ext. Ain 1.1

-3100 Option:
Ext. Ain 1.1 Setpoint 10
3100 External I/O
0.1 s modules
Ext. Ain 1.1 Delay 10.0 s (H8.x)
600.0 s
Warning
Ext. Ain 1.1 Fail class F1…F7
(F2)
Relay Not used
Ext. Ain 1.1 Not used
output A Option-dep.
Relay Not used
Ext. Ain 1.1 Not used
output B Option-dep.
OFF
Ext. Ain 1.1 Enable OFF
ON

12010 Ext. Ain 1.2

-3100 Option:
Ext. Ain 1.2 Setpoint 10
3100 External I/O
0.1 s modules
Ext. Ain 1.2 Delay 10.0 s (H8.x)
600.0 s
Warning
Ext. Ain 1.2 Fail class F1…F7
(F2)
Relay Not used
Ext. Ain 1.2 Not used
output A Option-dep.
Relay Not used
Ext. Ain 1.2 Not used
output B Option-dep.
OFF
Ext. Ain 1.2 Enable OFF
ON

The same order for settings external analogue inputs 2-8, settings 12030-12220.

DEIF A/S Page 80 of 137


AGC-3 Alarm and Parameter List

Digital inputs

No. Setting Min. Factory Notes Ref. Description


setting
Max.

12540 Ext. dig. in 1

1.0 s Option:
Ext. dig. in 1 Delay 10.0 s
600.0 s External
Warning I/O
Ext. dig. in 1 Fail class F1…F7 modules
(F2)
(H8.x)
Relay Not used
Ext. dig. in 1 Not used
output A Option-dep.
Relay Not used
Ext. dig. in 1 Not used
output B Option-dep.
OFF
Ext. dig. in 1 Enable OFF
ON
N/O
Ext. dig. in 1 N/X N/O
N/C

The same order for settings External digital inputs 2-16, settings 12550-12690.

DEIF A/S Page 81 of 137


AGC-3 Alarm and Parameter List

4. Parameter list

The parameter list contains settings for regulators and other non-alarm related settings.

Parameter table overview

Control - General setup (continued)


- Synchronisation 6290 Idle start
2000 Sync. Type
2020 Dynamic sync. 6320 Engine heater
2030 Static sync.
2040 f sync. Control Analogue 6380 Load share out
2050 f sync. control Relay 6390 Load share type
2060 Phase sync. Control Analogue
2070 Phase sync. control relay 6400 Master Clock

2110 Sync. Blackout 6460 Max ventilation

2240 Separate sync relay 6490 Summer/winter time


2250 Close before excitation
2260 Breaker Sequence 6550 Fuel transfer pump logic

- Regulation 6900 Alarm jump


2510 Frequency control analogue
2530 Power control analogue - Mains setup
2540 Power load sharing control analogue 7000 Mains power
2550 Analogue gov. offset 7010 Daytime period
7020 Start generator
2570 f control relay 7030 Stop generator
2580 P control relay 7040 Test
2590 Load sharing control relay 7050 Controller settings
2600 Relay control 7060 U mains failure
2610 Power ramp up 7070 f mains failure
2620 Power ramp down 7080 Mains breaker control

2640 Voltage control analogue 7120 Y1(X1) Deadband


2650 Reactive power control analogue 7130 P (X1) Slope
7140 Droop curve 1
2660 Reactive power load sharing control analogue 7150 Y2(X2) Deadband
2670 Analogue AVR output offset 7160 Q(X2) Slope
7170 PF(X2) Slope
2690 U control relay 7180 Droop curve 2
2700 Q control relay
2710 Q load sharing control relay -External communication
2720 Relay control (AVR) 7500 communication control
7510 External communication
2740 Delay reg.
- Power management internal comm.
2760 Overlap 7530 Internal communication ID
2770 EIC speed control
2780 Reg. output - Engine interface communication
2950 Base load 7560 Engine I/F

- Output setup -External I/O communication setup


5000 Relay 05 7950 KL 320x setup
5010 Relay 08 7970 CAN 1
5020 Relay 11 7980 CAN 2
5030 Relay 14 7990 Event printer
5040 Relay 17
5050 Relay 20

DEIF A/S Page 82 of 137


AGC-3 Alarm and Parameter List

5060 Relay 21 -Power management setup


5110 Relay 57 8000 Load dependent start
5120 Relay 59 8010 Load dependent stop
5130 Relay 61 8020 Start/stop selection
5140 Relay 63 8030 Priority selection
5150 Relay 65
5160 Relay 67 8080 Priority (1-5)
5170 Relay 69 8090 Priority (6-11)
5180 Relay 71 8100 Priority (12-16)
5190 Relay 90 8110 Running hours
5200 Relay 92 8120 Ground relay
5210 Relay 94 8140 Stop non-connected generators
5220 Relay 96 8170 Fuel optimize
5230 Relay 126
5240 Relay 128 8200 Heavy consumer 1
5250 Relay 130 8210 Heavy consumer 2
5260 Relay 132 8220 Avail. power 1
5270 Transistor setup 8230 Avail. power 2
8240 Avail. power 3
-Analogue output 8250 Avail. power 4
5720 PWM 68 limits 8260 Avail. power 5
5780 Aout 66 limits 8280 Asymmetric load share
5790 Aout 71 limits 8880 Load dependent start/stop
5800 Aout 91 limits 8920 Secure mode
5810 Aout 95 limits 8930 Heavy consumer 1 variable load
8940 Heavy consumer 2 variable load
-Transducer outputs
5820 P output 1 -Jump menus
5830 P output 2 9000 Software version
5840 P output 3 9010 Display character test
5850 S output 9020 Service port
5860 Q output
5870 PF output 9070 M4 SW version

5880 f output 9100 Device type


5890 U output 911X User password
5900 I output 9120 Service menu
5910 U BB output 9130 AC config.
5920 f BB output 9140 Angle compensation BB/G
5930 Multi-input 102 9150 Backlight dim
5940 Multi-input 105 9160 Application
5950 Multi-input 108 9170 Internal CAN protocol
5960 P total consumed 9180 Quick setup
5970 P total available 9190 Application broadcast

-Analogue regulator output setup - Command timers


5980 Governor output 10000-10310 Cmd timer 1-8
5990 AVR output
- Utility Software
System 10320 GSM pin code
- General setup 10330-10370 Telephone no. 1-5
6000 Nom. Settings 1
6010 Nom. Settings 2 10390 Password language page
6020 Nom. Settings 3 10400 Password log page
6030 Nom. Settings 4 10410 Password control page
6040 G/M/BA transformer
6050 BB transformer 10970 Engineering units
10980 Multi-inp. Conf. 102
6070 Gen-set Mode 10990 Multi-inp. Conf. 105
6080 Language 11000 Multi-inp. Conf. 108
6100 Counters
6110 Service timer 1 - VDO inputs
6120 Service timer 2 10460-10620 VDO 102
6130 Alarm horn 10630-10790 VDO 105
6150 Run coil setup 10800-10960 VDO 108

DEIF A/S Page 83 of 137


AGC-3 Alarm and Parameter List

6160 Run status -External digital outputs


6170 Running detect. 12790-12940 Ext. dig. out
6180 Starter
6190 Start attempts - External module status
6200 Shutdown override 12950-12980 Ext. module STATUS
6210 STOP
6220 Hz/V OK
6230 GB/MB/BTB control

6260 Power derate

DEIF A/S Page 84 of 137


AGC-3 Alarm and Parameter List

Synchronisation

No. Setting Min. Factory Notes Ref. Description


setting
Max.

2000 Sync type

Designer’s Static sync aims at a


Reference frequency difference of
Handbook 0 Hz.
Dynamic sync aims at a
Static
2001 Sync. type Type Dynamic frequency difference
Dynamic
(midpoint between
setting 2021 dfMax. and
2022 dfMin.).

2020 Dynamic synchronisation

Dynamic 0.0Hz Designer’s Setting 2020 is only


2021 dfMax. 0.3Hz
sync. 0.5Hz Reference available if ‘Dynamic
Dynamic -0.5Hz Handbook sync.’ Is chosen in
2022 dfMin. 0.0Hz setting 2001.
sync. 0.3Hz
Dynamic 2%
2023 dUMax. 5%
sync. 10%
Dynamic Sync t. 40ms
2024 50ms
sync. GB/BTB/TB 300ms
Dynamic 40ms
2025 Sync t. MB 50ms
sync. 300ms

2030 Dynamic synchronisation

0.00Hz Designer’s Setting 2030 is only


2031 Static sync. dfMax. 0.10Hz
0.50Hz Reference available if ‘Static sync.’
2% Handbook Is chosen in setting
2032 Static sync. dUMax 5% 2001.
10%
0.1 deg
2033 Static sync. Close window 10.0 deg
20.0 deg
0.1 s
2034 Static sync. Delay 1.0 s
99.0 s

2040 Frequency synchronisation control analogue

0.00 Option PID controller for


2041 f sync f Kp 0.50
60.00 E1, E2, dynamic sync
0.00 s EF2, EF4. This setting is only
2042 f sync f Ti 5.00 s EF5 available if “analogue”
60.00 s
or “PWM” or “EIC” is
0.00 s selected in setting
2043 f sync f Td 0.00 s
2.00 s 2780.

2050 Frequency synchronisation control relay

Designer’s This setting is only


0 Reference available if “relay” is
2051 f sync Kp 10
100 Handbook selected in setting
2780.

2060 Phase sync analogue

0.00 Designer’s PID controller for static


2061 Phase sync Phase Kp 0.50
60.00 Reference sync.

DEIF A/S Page 85 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.00 s Handbook This setting is only


2062 Phase sync Phase Ti 5.00 s
60.00 s available if “analogue”
or “PWM” or “EIC” is
0.00 s selected in setting
2063 Phase sync Phase Td 0.00 s
2.00 s 2780.

2070 Phase control relay

Designer’s This setting is only


0 Reference available if “relay” is
2071 Phase Kp 10
100 Handbook selected in setting
2780.

2110 Synchronisation blackout

Sync. 0.0Hz Designer’s Settings are accepted


2111 dfMax. 3.0Hz
Blackout 5.0Hz Reference limits for closing of the
Handbook breaker, referring to
Sync. 2% nominal frequency and
2112 dUMax 5%
Blackout 10% voltage.

2240 Separate synchronisation relay

Not used Designer’s The output activates


Sep sync
2241 Relay GB Option- Not used Reference during synchronisation
relay
dep. Handbook and thereby a separate
Not used synchronising unit can
Sep sync be activated.
2242 Relay MB Option- Not used
relay
dep.

2250 Close before excitation

Close bef. 0 rpm Designer’s If set ON the function


2251 Setpoint 400 rpm
Exc. 4000 rpm Reference will close the breaker at
Close bef. 0.0 s Handbook the selected speed.
2252 Timer 5.0 s The relay output is
Exc. 999,0 s
used for the excitation
Not used ON signal. Remember
Close bef. Relay
2253 Option- Not used to set the selected
Exc. output A
dep. relay in “Limit” mode.
Close bef. OFF
2554 Enable OFF
Exc. ON

2260 Breaker sequence

Close GB Designer’s The sequence is used


Close
2261 Breaker seq. Break Close Reference for the closed before
GB
GB+TB Handbook excitation function. The
0.0 s excitation will be
2262 Breaker seq. Timer 5.0 s activated at the
999.0 s
selected speed.
0 rpm
2263 Breaker seq. RpmOK 1450 rpm
4000 rpm

DEIF A/S Page 86 of 137


AGC-3 Alarm and Parameter List

Regulation

No. Setting Min. Factory Notes Ref. Description


setting
Max.

2510 Frequency control analogue

0.00 Designer’s PID controller for


2511 f control f Kp 0.50
60.00 Reference frequency control.
0.00 s Handbook This menu is only
2512 f control f Ti 5.00 s available if ‘analogue’
60.00 s
is chosen in menu
0.00 s 2781.
2513 f control f Td 0.00 s
2.00 s

2530 Power control analogue

0.00 Designer’s PID controller for


2531 P control P Kp 0.50
60.00 Reference power control.
0.00 s Handbook This menu is only
2532 P control P Ti 5.00 s available if ‘analogue’
60.00 s
is chosen in menu
0.00 s 2781.
2533 P control P Td 0.00 s
2.00 s

2540 Power load sharing control analogue

0.00 Designer’s PID controller for load


2541 P LS control P LS Kp 0.50
60.00 Reference sharing control.
0.00 s Handbook This menu is only
2542 P LS control P LS Ti 5.00 s available if ‘analogue’
60.00 s
is chosen in menu
0.00 s 2781.
2543 P LS control P LS Td 0.00 s
2.00 s

2550 Analogue governor offset

Designer’s PID controller for


Reference power control.
0% Handbook This menu is only
2551 Analogue GOV Offset 50 %
100 % available if ‘analogue’
is chosen in menu
2781.

2570 Frequency control relay output

0.2% Designer’s This menu is only


2571 f control relay Deadband 1.0%
10.0% Reference available if ‘relay’ is
0 Handbook chosen in menu 2781.
2572 f control relay Kp 10
100

2580 Power control relay output

0.2% Designer’s This menu is only


2581 P control relay Deadband 2.0%
10.0% Reference available if ‘relay’ is
0 Handbook chosen in menu 2781.
2582 P control relay Kp 10
100

2590 Load sharing control relay output

0.2% Designer’s This menu is only


2591 LS ctrl. relay f deadband 1.0%
10.0% Reference available if ‘relay’ is
0 Handbook chosen in menu 2781.
2592 LS ctrl. relay LS Kp 10
100

DEIF A/S Page 87 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.2%
2593 LS ctrl. relay P deadband 2.0%
10.0%
0.0 %
2594 LS ctrl. relay P weight 10.0 %
100.0 %

2600 Relay control

GOV ON 10 ms Designer’s This menu is only


2601 Relay control 500 ms
time 6500 ms Reference available if ‘relay’ is
GOV period 50 ms Handbook chosen in menu 2781.
2602 Relay control 2500 ms
time 32500 ms
Not used
Increase
2603 Relay control Option- Not used
relay
dep.
Not used
Decrease
2604 Relay control Option- Not used
relay
dep.

2610 Power ramp up

0.1%/s Designer’s The delay point


2611 Power ramp up Speed 2.0%/s
20.0%/s Reference determines when the
1% Handbook generator will make a
2612 Power ramp up Delay point 10% temporary stop
100%
ramping up after
0s closing of the generator
2613 Power ramp up Delay time 10 s
9900 s breaker to preheat the
OFF engine before
2614 Power ramp up Load share OFF
ON commencing load
taking.
If the delay function is
not needed, set this
0 time to 0. Power %
2615 Power ramp up Steps 1
100 settings relate to
nominal generator
power.

2620 Power ramp down

Power ramp 0.1%/s Designer’s The breaker open point


2621 Speed 10.0%/s
down 20.0%/s Reference determines when the
Handbook ‘open breaker’ relay
output is activated to
open the generator
Power ramp Breaker 1% breaker before reaching
2623 5%
down open point 20% 0 kW. Power % settings
relate to nominal
generator power.

2640 Voltage control analogue

0.00 Option: PID controller for


2641 U control U Kp 0.50
60.00 AVR voltage control
0.00 s control This menu is only
2642 U control U Ti 5.00 s (D1/D2) available if analogue
60.00 s
output is chosen in
0.00 s menu 2782.
2643 U control U Td 0.00 s
2.00 s

2650 Reactive power control analogue

0.00 Option: PID controller for


2651 Q control Q Kp 0.50
60.00 AVR reactive power control.

DEIF A/S Page 88 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.00 s control The reactive power


2652 Q control Q Ti 5.00 s
60.00 s (D1) control is used for
power factor as well as
reactive power control.
0.00 s This menu is only
2653 Q control Q Td 0.00 s available if analogue
2.00 s
output is chosen in
menu 2782.

2660 Reactive power load sharing control analogue

0.00 Option: The VAr (Q) load


2661 Q load sh. ctrl Q LS Kp 5.00
60.00 AVR sharing is based on a
0.00 s control mix of voltage and VAr
2662 Q load sh. ctrl Q LS Ti 5.00 s (D1) control. The setting
60.00 s
2664 is setting the
0.00 s impact of the VAr
2663 Q load sh. ctrl Q LS Td 0.00 s
2.00 s controller over the
voltage controller.
This menu is only
0.0%
2664 Q load sh. ctrl Q weight 10.0% available if analogue
100.0%
output is chosen in
menu 2782.

2670 Analogue AVR output offset

Option: Setting 2671 sets the


AVR offset of the analogue
control output when starting
0% (D1/D2) the generator.
2671 Analogue AVR Offset 50%
+100% This menu is only
available if analogue
output is chosen in
menu 2782.

2690 Voltage control relay

0.0% Option: PI controller for voltage


2691 U control U DB 2.0%
10.0% AVR control.
control This menu is only
0 (D1/D2) available if ‘relay’ is
2692 U control U Kp 10
100 chosen in menu 2782.

2700 Reactive power control relay

0.0% Option: PI controller for


2701 Q control Q DB 2.0%
10.0% AVR reactive power control.
control The reactive power
(D1) control is used for
power factor as well as
0 10 reactive power control.
2702 Q control Q Kp
100 This menu is only
available if ‘relay’ is
chosen in menu 2782.

2710 Reactive power load sharing control relay

0.0% Option: The VAr (Q) load


2711 Q load sh. ctrl U deadband 1.0%
10.0% AVR sharing is based on a
0 control mix of voltage and VAr
2712 Q load sh. ctrl U Kp 10 (D1) control. The setting
100
2664 is setting the
0.0% impact of the VAr
2713 Q load sh. ctrl Q deadband 2.0%
10.0%

DEIF A/S Page 89 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

controller over the


voltage controller.
0.0% 10.0%
2714 Q load sh. ctrl Q weight This menu is only
100.0%
available if ‘relay’ is
chosen in menu 2782.

2720 Relay control setup (AVR)

AVR ON 10 ms Option: Relay outputs for


2721 Relay control 100 ms
time tN 3000 ms AVR voltage/VAr/power
AVR per 50 ms control factor control.
2722 Relay control 500 ms (D1) This menu is only
time tP 1500 ms
available if ‘relay’ is
Not used chosen in menu 2782.
2723 Relay control U increase Option- Not used
dep.
Not used
2724 Relay control U decrease Option- Not used
dep.

2740 Delay regulation

0s Designer’s Delay regulation is the


2741 Delay reg. Delay 0s
9900 s Reference waiting time before
Not used Handbook synchronising after the
Relay engine has started. It is
2742 Delay reg. Option- Not used
output A used if the engine
dep.
needs to stabilise after
Not used start before attempting
Relay
2743 Delay reg. Option- Not used to synchronise.
output B
dep.
OFF
2744 Delay reg. Enable OFF
ON

2760 Overlap

OFF Designer’s If set ON the generator


2761 Overlap Enable OFF
ON Reference and mains breaker will
Handbook never both be closed for
0.10 s a longer time period
2762 Overlap Timer 0.30 s
99.90 s than the selected.

2770 EIC speed control

0.0% Only Option: Setting of speed control


2771 Scania control Droop 0.0%
25.0% available J1939 via engine communi-
if (H5 or cation interface.
User ‘Scania’ H7)
1500 RPM is selec-
2772 Scania control rpm User ted in
1800 RPM
Low idle menu
7561.
Only
available
when
0.00 ‘Cum-
2773 Cummins Gain Kp 5.00
10.00 mins’ is
selected
in menu
7561.

2780 Regulator output

DEIF A/S Page 90 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Designer’s Selection of the speed


Reference output: Relay,
Handbook analogue or engine
Relay
2781 Reg. output GOV Relay interface
EIC
communication.
Analogue and EIC are
option dependent.
Option: Generator voltage
AVR control based on relay
control or analogue output
Relay (D1/D2) signals.
2782 Reg. output AVR Relay
Analogue Analogue selection is
only available if option
E1, E2, EF2, EF4 or F2
is present.

2950 Base load


10% Designer’s Setting and enabling of
2951 Base load Power set 90%
120% Reference base load running.
Handbook Note: Base load is only
OFF possible in semi auto
2952 Base load Enable OFF
ON mode.

DEIF A/S Page 91 of 137


AGC-3 Alarm and Parameter List

Digital output setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

5000 Relay 05

Alarm Designer’s Function selections:


5001 Relay 05 Function Horn
Horn Reference - Alarm
0.0 s Handbook - Limit
5002 Relay 05 OFF delay 5.0 s - Horn
999.9 s

5010 Relay 08

Alarm Designer’s Function selections:


5011 Relay 08 Function Alarm
Horn Reference - Alarm
Handbook - Limit
- Horn
0.0 s This relay is only
5012 Relay 08 OFF delay 5.0 s available if no mains
999.9 s
breaker is controlled by
the AGC.

5020 Relay 11

Alarm Designer’s Function selections:


5021 Relay 11 Function Alarm
Horn Reference - Alarm
Handbook - Limit
- Horn
0.0 s This relay is only
5022 Relay 11 OFF delay 5.0 s available if no mains
999.9 s
breaker is controlled by
the AGC.

5030 Relay 14

Alarm Designer’s Function selections:


5031 Relay 14 Function Alarm
Horn Reference - Alarm
Handbook - Limit
- Horn
0.0 s This relay is only
5032 Relay 14 OFF delay 5.0 s available if no mains
999.9 s
breaker is controlled by
the AGC.

5040 Relay 17

Alarm Option G4 Function selections:


5041 Relay 17 Function Alarm
Horn and G5 - Alarm
0.0 s - Limit
5042 Relay 17 OFF delay 5.0 s - Horn
999.9 s

5050 Relay 20

Alarm Designer’s Function selections:


5051 Relay 20 Function Alarm
Horn Reference - Alarm
Handbook - Limit
- Horn
0.0 s This relay is only
5052 Relay 20 OFF delay 5.0 s available if no mains
999.9 s
breaker is controlled by
the AGC.

5060 Relay 21

DEIF A/S Page 92 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Alarm Designer’s Function selections:


5061 Relay 21 Function Alarm
Horn Reference - Alarm
Handbook - Limit
- Horn
0.0 s This relay is only
5062 Relay 21 OFF delay 5.0 s available if no mains
999.9 s
breaker is controlled by
the AGC.

5110 Relay 57

Alarm Option M12 Function selections:


5111 Relay 57 Function Alarm
Horn - Alarm
0.0 s - Limit
5112 Relay 57 OFF delay 5.0 s - Horn
999.9 s

5120 Relay 59

Alarm Option M12 Function selections:


5121 Relay 59 Function Alarm
Horn - Alarm
0.0 s - Limit
5122 Relay 59 OFF delay 5.0 s - Horn
999.9 s

5130 Relay 61

Alarm Option M12 Function selections:


5131 Relay 61 Function Alarm
Horn - Alarm
0.0 s - Limit
5132 Relay 61 OFF delay 5.0 s - Horn
999.9 s

5140 Relay 63

Alarm Option M12 Function selections:


5141 Relay 63 Function Alarm
Horn - Alarm
0.0 s - Limit
5142 Relay 63 OFF delay 5.0 s - Horn
999.9 s

5150 Relay 65

Alarm Designer’s Normally used for


5151 Relay 65 Function Alarm
Horn Reference governor UP command
Handbook (menu 2600).
Function selections:
0.0 s - Alarm
5152 Relay 65 OFF delay 5.0 s
999.9 s - Limit
- Horn

5160 Relay 67

Alarm Designer’s Normally used for


5161 Relay 67 Function Alarm
Horn Reference governor DOWN
Handbook command (menu
2600).
0.0 s Function selections:
5162 Relay 67 OFF delay 0.0 s - Alarm
999.9 s
- Limit
- Horn

5170 Relay 69

Alarm Designer’s Normally used for AVR


5171 Relay 69 Function Alarm
Horn Reference UP command (menu

DEIF A/S Page 93 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Handbook 2720).
Function selections:
0.0 s
5172 Relay 69 OFF delay 5.0 s - Alarm
999.9 s
- Limit
- Horn

5180 Relay 71

Alarm Designer’s Normally used for AVR


5181 Relay 71 Function Alarm
Horn Reference DOWN command
Handbook (menu 2720).
Function selections:
0.0 s - Alarm
5182 Relay 71 OFF delay 5.0 s
999.9 s - Limit
- Horn

5190 Relay 90

Alarm Option Function selections:


5191 Relay 90 Function Limit Alarm M14.6: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5192 Relay 90 OFF delay 5.0 s #6
999.9 s

5200 Relay 92

Alarm Option Function selections:


5201 Relay 92 Function Limit Alarm M14.6: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5202 Relay 92 OFF delay 5.0 s #6
999.9 s

5210 Relay 94

Alarm Option Function selections:


5211 Relay 94 Function Limit Alarm M14.6: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5212 Relay 94 OFF delay 5.0 s #6
999.9 s

5220 Relay 96

Alarm Option Function selections:


5221 Relay 96 Function Limit Alarm M14.6: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5222 Relay 96 OFF delay 5.0 s #6
999.9 s

5230 Relay 126

Alarm Option Function selections:


5231 Relay 126 Function Limit Alarm M14.8: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5232 Relay 126 OFF delay 5.0 s #8
999.9 s

5240 Relay 128

Alarm Option Function selections:


5241 Relay 128 Function Limit Alarm M14.8: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5242 Relay 128 OFF delay 5.0 s #8
999.9 s

DEIF A/S Page 94 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

5250 Relay 130

Alarm Option Function selections:


5251 Relay 130 Function Limit Alarm M14.8: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5252 Relay 130 OFF delay 5.0 s #8
999.9 s

5260 Relay 132

Alarm Option Function selections:


5261 Relay 132 Function Limit Alarm M14.8: - Alarm
Horn 4 x relay - Limit
0.0 s output, slot - Horn
5262 Relay 132 OFF delay 5.0 s #8
999.9 s

5270 Transistor output setup

Designer’s The transistor outputs


Reference on terminals 21 and 22
Relay
5271 Transistor 20 T20 Relay Handbook can be configured as
kWh
relay outputs or pulse
signals. If ‘Relay’ is
selected, the relays 20
and 21 will be
available.
Relay If set to ‘Relay’,
5272 Transistor 21 T21 Relay external relays are
kVArh
needed due to limited
current output. Max. 10
mA.

DEIF A/S Page 95 of 137


AGC-3 Alarm and Parameter List

Analogue output limits

No. Setting Min. Factory Notes Ref. Description


setting
Max.

5720 PWM 68 limits

0% Option: For Caterpillar engines.


5721 PWM 68 limits Min. 10%
50% PWM
50% output
5722 PWM 68 limits Max. 90% (EF5)
100

5780 Aout 66 limits

-25/0 mA Option: Min range and factory


5781 AOut 66 limits Min. -20/0 mA
10 mA 2x setting value is option
analogue dependent.
10 mA outputs
5782 AOut 66 limits Max. 20 mA
25 mA (E1/E2)

5790 Aout 71 limits

-25/0 mA Option: Min range and factory


5791 AOut 71 limits Min. -20/0 mA
10 mA 2x setting value is option
analogue dependent.
10 mA outputs
5792 AOut 71 limits Max. 20 mA
25 mA (E1/E2)

5800 Aout 91 limits

0 mA Option: Min range and factory


5801 AOut 91 limits Min. 0 mA
10 mA 2x setting value is option
analogue dependent.
10 mA outputs
5802 AOut 91 limits Max. 20 mA
25 mA (F1)

5810 Aout 95 limits

0 mA Option: Min range and factory


5811 AOut 95 limits Min. 0 mA
10 mA 2x setting value is option
analogue dependent.
10 mA outputs
5812 AOut 95 limits Max. 20 mA
25 mA (F1)

DEIF A/S Page 96 of 137


AGC-3 Alarm and Parameter List

Transducer outputs

No. Setting Min. Factory Notes Ref. Description


setting
Max.

5820 P output 1

Disabled Option:
5821 P output 1 Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5822 P output 1 Output B Option- Disabled or EF2)
dep.
0-20 mA
5823 P output 1 Type 4-20 mA
4-20 mA
0 kW
5824 P output 1 Max. value 20000 500 kW
kW
-9999 kW
5825 P output 1 Min. value 20000 0 kW
kW

5830 P output 2

Disabled Option:
5831 P output 2 Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5832 P output 2 Output B Option- Disabled or EF2)
dep.
0-20 mA
5833 P output 2 Type 4-20 mA
4-20 mA
0 kW
5834 P output 2 Max. value 20000 500 kW
kW
-9999 kW
5835 P output 2 Min. value 20000 0 kW
kW

5840 P output 3

Disabled Option:
5841 P output 3 Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5842 P output 3 Output B Option- Disabled or EF2)
dep.
0-20 mA
5843 P output 3 Type 4-20 mA
4-20 mA
0 kW
5844 P output 3 Max. value 20000 500 kW
kW
-9999 kW
5845 P output 3 Min. value 20000 0 kW
kW

5850 S output

Disabled Option:
5851 S output Output A Option- Disabled Analogue
dep. outputs

DEIF A/S Page 97 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Disabled (E2 or F1
5852 S output Output B Option- Disabled or EF2)
dep.
0-20 mA
5853 S output Type 4-20 mA
4-20 mA
0 kVA
5854 S output Max. value 20000 600 kVA
kVA
-9999
kVA
5855 S output Min. value 0 kVA
20000
kVA

5860 Q output

Disabled Option:
5861 Q output Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5862 Q output Output B Option- Disabled or EF2)
dep.
0-20 mA
5863 Q output Type 4-20 mA
4-20 mA
0 kVAr
5864 Q output Max. value 16000 400 kVAr
kVAr
8000 kVA
5865 Q output Min. value 16000 0 kVAr
kVA

5870 PF output

Disabled Option: Positive value means


5871 PF output Output A Option- Disabled Analogue inductive.
dep. outputs Negative value means
Disabled (E2 or F1 capacitive.
5872 PF output Output B Option- Disabled or EF2)
dep.
0-20 mA
5873 PF output Type 4-20 mA
4-20 mA
0.5
5874 PF output Max. value 0.80
0.99
-0.99
5875 PF output Min. value -0.80
-0.50

5880 f output

Disabled Option:
5881 F output Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5882 F output Output B Option- Disabled or EF2)
dep.
0-20 mA
5883 F output Type 4-20 mA
4-20 mA
0.0 Hz
5884 F output Max. value 55.0 Hz
70.0 Hz
0.0 Hz
5885 F output Min. value 45.0 Hz
70.0 Hz

DEIF A/S Page 98 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

5890 U output

Disabled Option: The voltage output


5891 U output Output A Option- Disabled Analogue represents L1-L2 voltage.
dep. outputs
Disabled (E2 or F1
5892 U output Output B Option- Disabled or EF2)
dep.
0-20 mA
5893 U output Type 4-20 mA
4-20 mA
0V
5894 U output Max. value 500 V
28000 V
0V
5895 U output Min. value 0V
28000 V

5900 I output

Disabled Option: The current output


Disabled
5901 I output Output A Option- Analogue represents L1 current.
dep. outputs
Disabled (E2 or F1
Disabled or EF2)
5902 I output Output B Option-
dep.
0-20 mA
5903 I output Type 4-20 mA
4-20 mA
0A
5904 I output Max. value 1000 A
9000 A
0A
5905 I output Min. value 0A
9000 A

5910 U BB output

Disabled Option: The voltage output


5911 U BB output Output A Option- Disabled Analogue represents L1-L2 voltage.
dep. outputs
Disabled (E2 or F1
5912 U BB output Output B Option- Disabled or EF2)
dep.
0-20 mA
5913 U BB output Type 4-20 mA
4-20 mA
0V
5914 U BB output Max. value 500 V
28000 V
0V
5915 U BB output Min. value 0V
28000 V

5920 f BB output

Disabled Option:
5921 F BB output Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5922 F BB output Output B Option- Disabled or EF2)
dep.
0-20 mA
5923 F BB output Type 4-20 mA
4-20 mA
0.0 Hz
5924 F BB output Max. value 55.0 Hz
70.0 Hz

DEIF A/S Page 99 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0.0 Hz
5925 F BB output Min. value 45.0 Hz
70.0 Hz

5930 Multi-input 102

Disabled Option:
5931 Multi-input 102 Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5932 Multi-input 102 Output B Option- Disabled or EF2)
dep.
0-20 mA
5933 Multi-input 102 Type 4-20 mA
4-20 mA
0
5934 Multi-input 102 Max. value 500
28000
0
5935 Multi-input 102 Min. value 0
28000

5940 Multi-input 105

Disabled Option:
Disabled
5941 Multi-input 105 Output A Option- Analogue
dep. outputs
Disabled (E2 or F1
Disabled or EF2)
5942 Multi-input 105 Output B Option-
dep.
0-20 mA
5943 Multi-input 105 Type 4-20 mA
4-20 mA
0
5944 Multi-input 105 Max. value 500
28000
0
5945 Multi-input 105 Min. value 0
28000

5950 Multi-input 108

Disabled Option: .
5951 Multi-input 108 Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5952 Multi-input 108 Output B Option- Disabled or EF2)
dep.
0-20 mA
5953 Multi-input 108 Type 4-20 mA
4-20 mA
0
5954 Multi-input 108 Max. value 500
28000
0
5955 Multi-input 108 Min. value 0
28000

5960 P total consumed

Disabled Option:
5961 P total consumed Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5962 P total consumed Output B Option- Disabled or EF2)
dep.
0-20 mA
5963 P total consumed Type 4-20 mA
4-20 mA

DEIF A/S Page 100 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0 kW
5964 P total consumed Max. value 20000 500 kW
kW
-9999 kW
5965 P total consumed Min. value 20000 0 kW
kW

5970 P total available

Disabled Option:
5971 P total available Output A Option- Disabled Analogue
dep. outputs
Disabled (E2 or F1
5972 P total available Output B Option- Disabled or EF2)
dep.
0-20 mA
5973 P total available Type 4-20 mA
4-20 mA
0 kW
5974 P total available Max. value 20000 500 kW
kW
-9999 kW
5975 P total available Min. value 20000 0 kW
kW

Regulator output selection

These menus are used to select which analogue output to use for governor/AVR
(option D) control.

No. Setting Available Factory Notes Ref. Description


settings setting

5980 Governor output

Option:
Disabled Analogue
5981 Governor output Output A AO66 Disabled governor
AO71 output
(E1/EF)

5990 AVR output

Option:
Analogue
Disabled
AVR
5991 AVR output Output A AO66 Disabled
output
AO71
(E1/EF
and D1)

DEIF A/S Page 101 of 137


AGC-3 Alarm and Parameter List

System

These menus include parameters for the system setup

General setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6000 Nominal settings 1

48.0 Hz Designer’s The selection of nominal


6001 Nom. settings Frequency 50.0 Hz
62.0 Hz Reference settings to be used is set
10 kW Handbook in 6006. A binary input or
6002 Nom. settings Power 480 kW selection in M-Logic can
20000 kW
also be used.
0A
6003 Nom. settings Current 867 A
9000 A
100 V
6004 Nom. settings Voltage 400 V
25000 V
100 RPM
6005 Nom. settings RPM 1500 RPM
4000 RPM
1
6006 Nom. settings Set 1
4

6010 Nominal settings 2

48.0 Hz Designer’s
6011 Nom. Settings 2 Frequency 50.0 Hz
62.0 Hz Reference
10 kW Handbook
6012 Nom. Settings 2 Power 230 kW
20000 kW
0A
6013 Nom. Settings 2 Current 345 A
9000 A
100 V
6014 Nom. Settings 2 Voltage 480 V
25000 V
100 RPM
6015 Nom. Settings 2 RPM 1500 RPM
4000 RPM

6020 Nominal settings 3

48.0 Hz Designer’s
6021 Nom. Settings 3 Frequency 60.0 Hz
62.0 Hz Reference
10 kW Handbook
6022 Nom. Settings 3 Power 230 kW
20000 kW
0A
6023 Nom. Settings 3 Current 345 A
9000 A
100 V
6024 Nom. Settings 3 Voltage 480 V
25000 V
100 RPM
6025 Nom. Settings 3 RPM 1800 RPM
4000 RPM

6010 Nominal settings 4

48.0 Hz Designer’s
6031 Nom. Settings 4 Frequency 60.0 Hz
62.0 Hz Reference
10 kW Handbook
6032 Nom. Settings 4 Power 230 kW
20000 kW

DEIF A/S Page 102 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

0A
6033 Nom. Settings 4 Current 345 A
9000 A
100 V
6034 Nom. Settings 4 Voltage 480 V
25000 V
100 RPM
6035 Nom. Settings 4 RPM 1800 RPM
4000 RPM

6040 Gen/Mains/busbar A transformer

G/M/BA 100 V Designer’s If no voltage transformer


6041 U primary 400 V
transformer 25000 V Reference is present, the primary
G/M/BA U 100 V Handbook and secondary side
6042 400 V values are set to
transformer secondary 690 V
generator nominal value.
G/M/BA 5A
6043 I primary 1000 A
transformer 9000 A
G/M/BA 1A
6044 I secondary 5A
transformer 5A

6050 Busbar settings

100 V Designer’s If no voltage transformer


6041 BB transformer U primary 400 V
25000 V Reference is present, the primary
Handbook and secondary side
U 100 V values are set to
6042 BB transformer 400 V generator nominal value.
secondary 690 V

6070 Gen-set Mode

Designer’s Possible selections are:


Reference -Island
Handbook -Auto Mains Failure
-Peak Shaving
-Fixed power
Island
-Mains power export
6071 Gen-set mode Power
-Load takeover
management
-Power management
(option G5)
-Remote maintenance
-Plant management
(option G7)

6080 Language

Designer’s The master language is


English Reference English. Additionally 11
6081 Language Language 1- English Handbook different languages can
11 be configured with the
PC utility software.

DEIF A/S Page 103 of 137


AGC-3 Alarm and Parameter List

Counters and timers

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6090 Date and time

2001 Designer’s Used to set up the clock


6091 Date and time Year 2008
2100 Reference in the AGC.
1 Handbook
6092 Date and time Month 1
12
1
6093 Date and time Date 1
31
1
6094 Date and time Week day 1
7
0
6095 Date and time Hour 3
23
0
6096 Date and time Minute 5
59

6100 Counters

Running 0 hr Designer’s Setting 6105 resets the


6101 Counters 0 hr
hour 999 hr Reference kWh counter to 0. It
Running, th. 0 th. hrs Handbook automatically reverts to
6102 Counters 0 th. hrs OFF after being set ON.
hours 999 th. hrs
GB/TB/BTB 0
6103 Counters 0
operations 20000
MB 0
6104 Counters 0
operations 20000
OFF
6105 Counters kWh OFF
ON
Start 0
6106 Counters 0
attempts 20000

6110 Service timer 1

OFF Designer’s The timer is reset by


6111 Service timer 1 Enable ON
ON Reference enabling menu 6116. The
Running 0 hrs Handbook menu automatically goes
6112 Service timer 1 500 hrs OFF.
hours 9000 hrs
1 days
6113 Service timer 1 Days 365 days
1000 days
F2
6114 Service timer 1 Fail class F1…F7
(warning)
Not used
6115 Service timer 1 Output A Not used
Option-dep.
OFF
6116 Service timer 1 Reset OFF
ON

6120 Service timer 2

OFF Designer’s The timer is reset by


6121 Service timer 2 Enable ON
ON Reference enabling menu 6126. The
Running 0 hrs Handbook menu automatically goes
6122 Service timer 2 500 hrs OFF.
hours 9000 hrs
1 days
6123 Service timer 2 Days 365 days
1000 days

DEIF A/S Page 104 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

F2
6124 Service timer 2 Fail class F1…F8
(warning)
Relay Not used
6125 Service timer 2 Not used
output A Option-dep.
OFF
6126 Service timer 2 Reset OFF
ON

Alarm horn

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6130 Alarm horn

Designer’s If the setting is adjusted


Reference to 0 s, the horn relay will
0.0 sec
6131 Alarm horn ON time 0.0 sec Handbook be activated
990.0 sec
continuously until the
alarm is acknowledged.

Run coil setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6150 Run coil setup

Designer’s
1.0 sec
6151 Run coil setup ON time 1.0 sec Reference
600.0 sec
Handbook
Designer’s
Pulse
6152 Run coil setup Type Pulse Reference
Continuous
Handbook

DEIF A/S Page 105 of 137


AGC-3 Alarm and Parameter List

Running, start and stop

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6160 Run status

0.0 s Designer’s If a relay output is used,


6161 Run status Delay 5.0 s
300.0 s Reference the relay in question must
Relay Not used Handbook be set to ‘limit’.
6162 Run status Not used
output A Option-dep.
Relay Not used
6163 Run status Not used
output B Option-dep.
OFF
6164 Run status Enable OFF
ON

6170 Running detection

0 teeth Designer’s If menu 6171 is set to 0,


6171 Running detect. No of Teeth 0 teeth
500 teeth Reference the magnetic pickup input
Digital in Handbook is not active.
6172 Running detect. Type Frequency
Multi-input
Available running
Running 0 RPM detection types:
6173 Running detect. 1000 RPM
RPM 4000 RPM - Digital input
Remove 1 RPM - Magnetic pickup
6174 Running detect. 400 RPM
starter 2000 RPM - Frequency
- EIC (Engine
communication)
- Multi-input 102
- Multi-input 105
Pressure 0.0 bar - Multi-input 106
6175 Running detect. 0.0 bar
level 15.0 bar
If menu 6175 is set to
0.0, the oil pressure
running detection is
OFF.

6180 Starter

Start 0.0 s Designer’s Menu 6185 and 6186


6181 Starter 5.0 s
prepare 600.0 s Reference relate to using oil
0.0 s Handbook pressure as running
6182 Starter Ext. prepare 0.0 s feedback.
600.0 s
If menu 6186 is set to 0.0
Start ON 1.0 s the oil pressure running
6183 Starter 5.0 s
time 180.0 s feedback is disregarded.
Start OFF 1.0 s
6184 Starter 5.0 s
time 99.0 s
Multi-input
102 Multi-input
6185 Starter Input type
Multi-input 102
108
0.0 bar
6186 Starter Setpoint 0.0 bar
300.0 bar

6190 Start attempts

Designer’s Number of start attempts.


1
6181 Start attempts Setpoint 3 Reference
10
Handbook

6200 Shutdown override

DEIF A/S Page 106 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Shutdown 1 Designer’s Shutdown override turns


6201 Attempts 7
override 10 Reference all shutdowns into
Shutdown Cooling 0s Handbook warnings. Only exception
6202 240 s is overspeed and
override down 9900 s
emergency stop.
Shutdown OFF
6203 Enable OFF
override ON

6210 STOP

Cooling 0.0 s Designer’s The extended stop timer


6211 STOP 240.0 s
down 9900.0 s Reference starts when the running
Handbook feedback disappears.
Extended 1.0 s During the delay time it is
6212 STOP 5.0 s not possible to start the
stop 99.0 s
engine.
Multi-input
Multi-input
6213 STOP TYPE 102
102
M-logic
0 dec.
6214 STOP Setpoint 0 dec.
482 dec.

6220 Hz/V OK

Designer’s The voltage and


Reference frequency have to be
1.0 s
6221 HZ/V OK Delay 5.0 s Handbook continuously within the
99.0 s
limits before the breaker
can be closed.

Breaker control

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6230 Gen/Mains/Tie/Bus tie Breaker control

GB/MB/TB/BTB 0.0 s Designer’s Menu 6212 is for


6211 Close delay 2.0 s
control 30.0 s Reference compact breakers (need
GB/MB/TB/BTB 0.0 s Handbook to charge spring before
6212 Load time 0.0 s closing).
control 30.0 s

DEIF A/S Page 107 of 137


AGC-3 Alarm and Parameter List

Power derate

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6260 Power derate

Multi-inp. 102 Multi-inp. Designer’s The derate function


6261 Power derate Input
M-logic 102 Reference lowers the max power of
0 units Handbook the generator set based
6262 Power derate Start derate 16 units on e.g. water
20000 units
temperature.
Derate 0.1 %/unit Input:
6263 Power derate 5.0 %/unit
slope 100.0 %/unit - Multi-input 102
OFF - Multi-input 105
6264 Power derate Proportional OFF
ON - Multi-input 108
- M-logic
OFF
6265 Power derate Enable OFF - EIC
ON
0.0 %
6266 Power derate Limit 80.0 %
100.0 %

Idle start

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6290 Idle start

0.0 min Designer’s


6291 Idle start Start timer 300.0 min
999.0 min Reference
OFF Handbook
6292 Idle start Enable start OFF
ON
0.0 min
6293 Idle start Stop timer 300.0 min
999.0 min
OFF
6294 Idle start Enable stop OFF
ON
Relay Not used
6295 Idle start Not used
output A Option-dep.
OFF
6296 Idle start Enable OFF
ON

DEIF A/S Page 108 of 137


AGC-3 Alarm and Parameter List

Engine heater

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6320 Engine heater

20 deg. Designer’s Heater function for


6321 Engine heater Setpoint 40 deg.
250 deg. Reference standstill.
Relay Not used Handbook Type:
6322 Engine heater Not used - Multi-input 102
output A Option-dep.
- Multi-input 105
Multi-inp 102 Multi-inp - Multi-input 108
6323 Engine heater Type
Multi-inp. 108 102 - EIC
1 deg.
6324 Engine heater Hysteresis 3 deg.
70 deg.
OFF
6325 Engine heater Enable OFF
ON

Analogue load sharing lines output

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6380 Load share out

Option G3 Adjustment of the


1.0 V Analogue analogue load sharing
6381 Load share out Setpoint 4.0 V
5.0 V load line max. value.
sharing

6390 Load share type

Option G3 Selection between select-


Analogue able load sharing line
Adjustable
6391 Load share type Setpoint load max. value (setting 6381)
Selco T4800
sharing or adaptation to Selco
T4800 load sharing line.

DEIF A/S Page 109 of 137


AGC-3 Alarm and Parameter List

Master clock

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6400 Master clock

0h Designer’s Compensation for


6401 Master clock Start hour 8h
23 h Reference frequency variation
0h Handbook related clock time in the
6402 Master clock Stop hour 8h system.
23 h
1s
6403 Master clock Difference 20 s
999 s
Compen- 0.1 Hz
6404 Master clock 0.1 Hz
sation 1.0 Hz
OFF
6405 Master clock Enable OFF
ON

Cooling ventilation

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6460 Max. ventilation

20 deg. Designer’s
6461 Max ventilation Setpoint 90 deg.
250 deg. Reference
Relay Not used Handbook
6462 Max ventilation Not used
output A Option dep
1 deg.
6463 Max ventilation Hysteresis 5 deg.
70 deg.
OFF
6464 Max ventilation Enable OFF
ON

Summer/winter time

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6490 Summer/winter time

Designer’s The summer/winter time


OFF
6491 Sum/win time Enable OFF Reference change follows the
ON
Handbook mainland Europe rules.

DEIF A/S Page 110 of 137


AGC-3 Alarm and Parameter List

Fuel transfer pump logic

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6550 Fuel pump logic

Setpoint 0% Designer’s Type:


6291 Fuel pump logic 20 %
start 100 % Reference - Multi-input 102
Setpoint 0% Handbook - Multi-input 105
6292 Fuel pump logic 80 % - Multi-input 108
stop 100 %
Fill check 0.1 s
6293 Fuel pump logic 60.0 s
time 300.0 s
Relay Not used
6294 Fuel pump logic Not used
output A Option-dep.
Multi-inp 102 Multi-inp
6295 Fuel pump logic Type
Multi-inp 108 102
Warning
6296 Fuel pump logic Fail class F1…F7
(F2)

Alarm jump

No. Setting Min. Factory Notes Ref. Description


setting
Max.

6900 Alarm jump

Designer’s Selection of jump to


Reference alarm list view on the
OFF
6901 Alarm jump Enable ON Handbook display if an alarm
ON
appears (ON), or stay at
present view (OFF).

DEIF A/S Page 111 of 137


AGC-3 Alarm and Parameter List

Mains setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7000 Mains power


-20000 kW Designer’s
7001 Mains power Day 750 kW
20000 kW Reference
-20000 kW Handbook
7002 Mains power Night 1000 kW
20000 kW
Transducer 0 kW
7003 Mains power 0 kW
max 20000 kW
Transducer -20000 kW
7004 Mains power 0 kW
min 0 kW

7010 Daytime period


0h Designer’s The period outside the
7011 Daytime period Start hour 8h
23 h Reference daytime period is defined
0 min Handbook as the night period.
7012 Daytime period Start minute 0 min
59 min
0h
7013 Daytime period Stop hour 16 h
23 h
0 min
7014 Daytime period Stop period 0 min
59 min

7020 Start generator


5% Designer’s The setpoint refers to the
7021 Start generator Setpoint 80%
100% Reference menu 7000 mains power
0.0 s Handbook setting.
7022 Start generator Delay 10.0 s
990.0 s
Minimum 0%
7023 Start generator 5%
load 100%

7030 Stop generator


0% Designer’s The setpoint refers to the
7031 Stop generator Setpoint 60%
80% Reference menu 7000 mains power
0.0 s Handbook setting.
7032 Stop generator Delay 30.0 s
990.0 s

DEIF A/S Page 112 of 137


AGC-3 Alarm and Parameter List

Test

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7040 Test running

1% Designer’s Available test types:


7041 Test Setpoint 80%
100% Reference - Simple (engine run only)
0.0 min Handbook - Load (parallel to mains)
7042 Test Test time 999.0 5.0 min - Full (disconnects mains)
min
Semi-
7043 Test Return mode auto Auto
Auto
Simple
7044 Test Test type Simple
Full

Controller settings

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7050 Fixed power settings

Fixed power 0% Designer’s Parallel with mains settings.


7051 Power 100 %
settings 100 % Reference
Fixed power 0.60 Handbook
7052 Power factor 0.90
settings 1.00
Fixed power Inductive
7053 Power factor Inductive
settings Capacitive

DEIF A/S Page 113 of 137


AGC-3 Alarm and Parameter List

Mains failure

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7060 U Mains Failure

0.5 s Designer’s Menus 7063 and 7064 relate


7061 U Mains failure Fail. delay 5.0 s
990.0 s Reference to nominal settings.
10 s Handbook Menu 7066 refers to the
7062 U Mains failure MSB OK delay 60 s mean value of the measured
9900 s
voltage.
80%
7063 U Mains failure U< 90%
100%
100%
7064 U Mains failure U> 110%
120%
Start
eng. + Start
Mains fail.
7065 U Mains failure open MB eng. +
control
Start open MB
eng.
2%
7066 U Mains failure U unbalance 100%
100%

7070 f Mains Failure

0.5 s Designer’s Menus 7073 and 7074 relate


7071 f Mains failure Fail. delay 5.0 s
990.0 s Reference to nominal settings.
Mains OK 10 s Handbook
7072 f Mains failure 60 s
delay 9900 s
80.0%
7073 f Mains failure f< 95.0%
100.0%
100.0%
7074 f Mains failure f> 105.0%
120.0%

7080 MB control

OFF Designer’s
7081 MB control Mode Shift OFF
ON Reference
MB close 0.0 s Handbook
7082 MB control 0.5 s
delay 30.0 s
OFF
7083 MB control Back sync. OFF
ON
OFF
7084 MB control Sync to Mains ON
ON
0.0s
7085 MB control Load time 0.0 s
30.0 s

DEIF A/S Page 114 of 137


AGC-3 Alarm and Parameter List

Y1(X1) droop curve

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7120 Y1(x1) Deadband

0.00 % Designer’s
7121 Y1(x1) Deadband Deadband low 0.40 %
99.99 % Reference
Deadband 0.00 % Handbook
7122 Y1(x1) Deadband 0.50 %
high 99.99 %
0.00 %
7123 Y1(x1) Deadband Hysterese low 0.50 %
99.99 %
0.00 %
7124 Y1(x1) Deadband Hysterese high 0.50 %
99.99 %

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7130 P(x1) Slope

0 kW Designer’s
7131 P(x1) Slope MIN 200 kW
20000 kW Reference
0 kW Handbook
7132 P(x1) Slope MAX 480 kW
20000 kW
-20000 kW
7133 P(x1) Slope Slope low 50 kW
20000 kW
-20000 kW
7134 P(x1) Slope Slope high -50 kW
20000 kW

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7140 Droop curve 1

P(x1) Designer’s
7141 Droop curve 1 P(x1) P(x1)
P(x1) Reference
f Handbook
7142 Droop curve 1 X1 f
f
OFF
7143 Droop curve 1 Enable OFF
ON

DEIF A/S Page 115 of 137


AGC-3 Alarm and Parameter List

Y2(X2) droop curve

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7150 Y2(x2) Deadband

0.00 % Option D1
7151 Y2(x2) Deadband Deadband low 2.00 %
99.99 %
Deadband 0.00 %
7152 Y2(x2) Deadband 2.00 %
high 99.99 %
0.00 %
7153 Y2(x2) Deadband Hysterese low 2.10 %
99.99 %
0.00 %
7154 Y2(x2) Deadband Hysterese high 2.10 %
99.99 %

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7160 Q(x2) Slope

0 kVAr Option D1
7161 Q(x2) Slope MIN 20000 200 kVAr
kVAr
0 kVAr
7162 Q(x2) Slope MAX 20000 480 kVAr
kVAr
-20000
kVAr
7163 Q(x2) Slope Slope low 50 kVAr
20000
kVAr
-20000
kVAr
7164 Q(x2) Slope Slope high -50 kVAr
20000
kVAr

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7170 PF(x2) Slope

0.60 Option D1
7171 PF(x2) Slope MIN 0.80 PF
1.00
Inductive
7172 PF(x2) Slope I/C Inductive
Capacitive
0.60
7173 PF(x2) Slope MAX 1.00 PF
1.00
Inductive
7174 PF(x2) Slope I/C Inductive
Capacitive
- 1.00
7175 PF(x2) Slope Slope low -0.05 PF
1.00
-1.00
7176 PF(x2) Slope Slope high 0.05 PF
1.00

DEIF A/S Page 116 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7180 Droop curve 2

PF(x2) Option D1
7141 Droop curve 2 PF(x2) PF(x2)
Q(x2)
U
7122 Droop curve 2 X2 U
P
OFF
7123 Droop curve 2 Enable OFF
ON

DEIF A/S Page 117 of 137


AGC-3 Alarm and Parameter List

External communication

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7500 Communication control

OFF Option H2 These settings must be


7501 Comm. control Power OFF
ON or H3: ON if commands are to
OFF Modbus or be sent over the
7502 Comm. control Frequency OFF Profibus Modbus
ON
communication. This
OFF will overrule external
7503 Comm. control Voltage OFF
ON and internal settings.
OFF Voltage, power factor
7504 Comm. control PF OFF
ON and reactive power
control requires AVR
Reactive OFF
7505 Comm. control OFF control (option D1).
power ON

7510 External communication

Option H2 The mode ASCII is


Ext. 1 or H3: used for modem
7511 ID 1
communication 247 Modbus or communication (ASCII:
Profibus 7 data bit, RTU: 8 data
Ext. 9600 Option H2: bit).
7512 Baud rate 9600
communication 19200 Modbus
Ext. RTU Option H2:
7513 Mode RTU
communication ASCII Modbus

Power management internal communication

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7530 Internal communication ID

Designer’s
1
7531 Int. comm. ID ID 1 Reference
16
Handbook

DEIF A/S Page 118 of 137


AGC-3 Alarm and Parameter List

Engine interface communication

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7560 Engine I/F

OFF Option: The setting affects the


Engine QSX15 Cummins displayed data, but not
7561 Engine I/F OFF
type QSK23/45/60/78 Modbus the Modbus data (option
QST30 (H6) H2).
OFF Option: MTU MDEC is only
DDEC J1939/MTU available in option H5.
EMR ADEC/
JDEC MTU Please choose MDEC
Iveco MDEC 2000/4000 M.303 when
Perkins (H5) M.201 or M.304 is
Caterpillar required.
Volvo Penta J1939
EMS (H7) Menu 7562 is only
Engine Volvo Penta available when MTU
7561 Engine I/F OFF
type EMS 2 ADEC is selected as
Scania EMS engine type.
Scania EMS S6
MDEC Menu 7563 is for
2000/4000 M.302 enabling the EIC
MDEC commands transmission.
2000/4000 M.303
MTU ADEC Menu 7564: When set to
Cummins “on”, up to 19 extra views
Generic J1939 (of 3 lines) are added to
0 the 15 original V1 views
7562 CANopen ID Node ID 6 (of 3 lines). These extra
16
views are displaying all
OFF the present engine com.
7563 EIC Controls Enable ON
ON values broadcasted on
this CAN communication
OFF
7564 EIC Auto view Enable OFF when this function is set
ON
to “on”.

DEIF A/S Page 119 of 137


AGC-3 Alarm and Parameter List

External I/O communication setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7950 KL320x config

7951 KL320x config Module 1 Option: Selection for analogue


7952 KL320x config Module 2 External I/O modules.
Pt100 modules The selections for KL
7953 KL320x config Module 3 (2/3-wire) (H8) 3202/3204 cannot be
10- changed.
1200 Ω After changing module
7954 KL320x config Module 4 (2-wire) type, the parameter list in
the PC USW must be
uploaded again.

7970 CAN 1

OFF Option: This menu is only


7971 CAN 1 Type OFF
Beckhoff External I/O activated if option H8.2 is
50k modules activated.
7972 CAN 1 Baud 125k 125k (H8) After changing type, the
250k parameter list in the PC
USW must be uploaded
1 to again.
7973 CAN 1 ID 1
64 Menu 7974 is for re-
establishing
NO
7974 CAN 1 Reset NO communication after a
YES
fault/disconnection.

7980 CAN 2

OFF Option: This menu is only


7981 CAN 2 Type OFF
Beckhoff External I/O activated if option H8.8 is
50k modules activated.
7982 CAN 2 Baud 125k 125k (H8) After changing type, the
250k parameter list in the PC
USW must be uploaded
1 to again.
7983 CAN 2 ID 1
64 Menu 7984 is for re-
establishing
NO
7984 CAN 2 Reset NO communication after a
YES
fault/disconnection.

DEIF A/S Page 120 of 137


AGC-3 Alarm and Parameter List

Event printer

No. Setting Min. Factory Notes Ref. Description


setting
Max.

7990 Event printer


Enable this when the printer
OFF
7991 Event printer Enable OFF is connected to the service
ON
port.
Enable this if additional data
OFF have to be printed for every
7992 Event printer Print add data OFF
ON event; additional data such as
power, voltage etc.
This counter is the number of
events that will be printed with
1
7993 Event printer Event records 5 additional data, when the
150
digital input ‘Print event log’ is
activated.
Log types:
Log type Event Event
7994 Event printer Event
select Battery Alarm
Battery
Time interval between the
0 min automatic status prints. If
7995 Event printer Auto status 0 min
990 min auto status is set to 0, the
auto print is disabled.

DEIF A/S Page 121 of 137


AGC-3 Alarm and Parameter List

Power management setup

No. Setting Min. Factory Notes Ref. Description


setting
Max.

8000 Load dependent start

1 kW Designer’s
8001 Load dep. start P setpoint 100 kW
20000 kW Reference
1 kVA Handbook
8002 Load dep. start S setpoint 100 kVA
20000 kVA
1%
8003 Load dep. start % setpoint 90 %
100 %
0.0 s
8004 Load dep. start Delay 10.0 s
990.0 s
0 kW
8005 Load dep. Start Min. load 20 kW
20000 kW

8010 Load dependent stop

0 kW Designer’s
8011 Load dep. stop P setpoint 200 kW
20000 kW Reference
1 kVA Handbook
8012 Load dep. stop S setpoint 200 kVA
20000 kVA
1%
8013 Load dep. stop % setpoint 70 %
100 %
5.0 s
8014 Load dep. stop Delay 30.0 s
990.0 s
Blocked
ON Blocked
8015 Load dep. stop Select
Blocked ON
OFF

8020 PM config

Remote Designer’s Remote and local decide if


8021 PM config Enable Remote
Local Reference the start/stop command of
Handbook the plant is given Remote
(digital input) or Local (from
the display).
Update is used to define if
Update all the change of a running
Update
8022 PM config Update Local mode will affect all AGCs
all
update connected on the power
management CAN line or
only the local unit where the
running mode is changed.

8030 Priority selection

Option G4 Priorities available:


and G5 - Manual absolute
Manual
- Running hours absolute
8031 Priority select. Priority Fuel Manual
- Fuel optimisation
optimise
- Manual relative
- Running hours relative

8080 Priority (1-5)

1 Option G4 Menu 8086 is only available


8081 Priority 1 ID 1
16 and G5 if “Manual” is selected in

DEIF A/S Page 122 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

1 menu 8031. Menu 8086


8082 Priority 2 ID 2
16 resets itself to OFF
1 automatically, once the new
8083 Priority 3 ID 3 settings have been
16
transmitted.
1
8084 Priority 4 ID 4
16
1
8085 Priority 5 ID 5
16
Transmit new ON
8086 Tx OFF
priority OFF

8090 Priority (6-11)

1 Option G4
8091 Priority 6 ID 6
16 and G5
1
8092 Priority 7 ID 7
16
1
8093 Priority 8 ID 8
16
1
8094 Priority 9 ID 9
16
1
8095 Priority 10 ID 10
16
1
8096 Priority 11 ID 11
16

8100 Priority (12-16)

1 Option G4
8101 Priority 12 ID 12
16 and G5
1
8102 Priority 13 ID 13
16
1
8103 Priority 14 ID 14
16
1
8104 Priority 15 ID 15
16
1
8105 Priority 16 ID 16
16

8110 Running hours

1 hrs Designer’s
8111 Running hours Set timer 175 hrs
20000 hrs Reference
Absolute Handbook
8112 Running hours Type Absolute
Relative
OFF
8113 Running hours Reset
ON

8120 Ground relay

Not used Designer’s


8121 Ground relay Output A Not used
Option-dep. Reference
Not used Handbook
8122 Ground relay Output B Not used
Option-dep.
Off
8123 Ground relay Enable Off
On

8140 Stop non-connected DGs

DEIF A/S Page 123 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Option:
Power
10.0 s
8141 Stop non-con. DGs Delay 60.0 s manage-
600.0 s
ment
(G5)

8170 Fuel optimise

30% Option:
8171 Fuel optimise Setpoint 80%
100% Power
Swap 10 kW manage-
8172 Fuel optimise 200 kW ment
setpoint 20000 kW
(G5)
0.0 s
8173 Fuel optimise Delay 10.0 s
999.0 s
1 hrs
8174 Fuel optimise Hours 175 hrs
20000 hrs
OFF
8175 Fuel optimise Enable hour OFF
ON

8180 Mains config.

OFF Option: Only available in AGC mains


8181 Mb failure start Enable OFF
ON Power unit.
OFF manage- Auto switch selections:
8182 Parallel Enable OFF ment -OFF
ON
(G5) -Static section
OFF -Dynamic section-
8183 No break transfer Enable OFF
ON -All sections
OFF
8184 Auto switch Select OFF
All sections
Run all
mains Run one
8185 Run type Select
Run one mains
mains
17
8186 Run type ID to run 17
32

8190 Tie breaker

TB open 0 kW Option: Only available in AGC mains


8171 Tie breaker 50 kW
point 20000 kW Power unit.
Power 1 kW manage-
8172 Tie breaker 50 kW ment
Capacity 20000 kW
(G5)
P. cap. 5.0 s
8173 Tie breaker 30.0 s
Overrule 999.9 s
P cap. OFF
8174 Tie breaker OFF
Overrule ON
0.0 s
8175 Tie breaker Load time 0.0 s
30.0 s

8200 Heavy consumer 1

10 kVA Option: Only available in AGC DG


8201 Heavy consumer 1 Req. value 500 kVA
9999 kVA Power units.
10 kW manage-
8202 Heavy consumer 1 Nom. power 400 kW ment (G5)
9999 kW
Fixed load
Fixed
8203 Heavy consumer 1 Load type Variable
load
load

DEIF A/S Page 124 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

8210 Heavy consumer 2

10 kVA Option: Only available in AGC DG


8211 Heavy consumer 2 Req. value 500 kVA
9999 kVA Power units.
10 kW manage-
8212 Heavy consumer 2 Nom. power 400 kW ment (G5)
9999 kW
Fixed load
Fixed
8213 Heavy consumer 2 Load type Variable
load
load

8220 Available power 1

10 kW Option: The setting can be used for


8221 Avail. power 1 Setpoint 1000 kW
20000 kW Power conditional connection of
1.0 s manage- load groups.
8222 Avail. power 1 Delay 10.0 s ment The relay(s) used must be
999.9 s
(G5) set to “Limit” mode.
Relay Not used
8223 Avail. power 1 Not used
output A Option-dep.
Relay Not used
8224 Avail. power 1 Not used
output B Option-dep.
OFF
8225 Avail. power 1 Enable OFF
ON

8230 Available power 2

10 kW Option: The setting can be used for


8231 Avail. power 2 Setpoint 1000 kW
20000 kW Power conditional connection of
2.0 s manage- load groups.
8232 Avail. power 2 Delay 10.0 s ment The relay(s) used must be
999.9 s
(G5) set to “Limit” mode.
Relay Not used
8233 Avail. power 2 Not used
output A Option-dep.
Relay Not used
8234 Avail. power 2 Not used
output B Option-dep.
OFF
8235 Avail. power 2 Enable OFF
ON

8240 Available power 3

10 kW Option: The setting can be used for


8241 Avail. power 3 Setpoint 1000 kW
20000 kW Power conditional connection of
3.0 s manage- load groups.
8242 Avail. power 3 Delay 10.0 s ment The relay(s) used must be
999.9 s
(G5) set to “Limit” mode.
Relay Not used
8243 Avail. power 3 Not used
output A Option-dep.
Relay Not used
8244 Avail. power 3 Not used
output B Option-dep.
OFF
8245 Avail. power 3 Enable OFF
ON

8250 Available power 4

10 kW Option: The setting can be used for


8251 Avail. power 4 Setpoint 1000 kW
20000 kW Power conditional connection of
4.0 s manage- load groups.
8252 Avail. power 4 Delay 10.0 s ment The relay(s) used must be
999.9 s
(G5) set to “Limit” mode.
Relay Not used
8253 Avail. power 4 Not used
output A Option-dep.

DEIF A/S Page 125 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Relay Not used


8254 Avail. power 4 Not used
output B Option-dep.
OFF
8255 Avail. power 4 Enable OFF
ON

8260 Available power 5

10 kW Option: The setting can be used for


8261 Avail. power 5 Setpoint 1000 kW
20000 kW Power conditional connection of
5.0 s manage- load groups.
8262 Avail. power 5 Delay 10.0 s ment The relay(s) used must be
999.9 s
(G5) set to “Limit” mode.
Relay Not used
8263 Avail. power 5 Not used
output A Option-dep.
Relay Not used
8264 Avail. power 5 Not used
output B Option-dep.
OFF
8265 Avail. power 5 Enable OFF
ON

8270 TB power

Transducer 0 kW Option: AGC mains only: If the TB


8271 TB power 0 kW
max. 20000 kW Power needs to be deloaded before
manage- opening, a power transducer
Transducer -20000 kW ment must be connected to multi-
8272 TB power 0 kW
min. 0 kW (G5) input 105.

8280 Asymmetric load sharing

1% Option: Please refer to the option


8281 Asymmetric LS Setpoint 95%
100% Power G4/G5 manual.
manage-
OFF ment
8282 Asymmetric LS Enable OFF
ON (G5)

8880 Load dependent start/stop calc.

kW Option: These settings are used to


8881 Start/stop calc. S1 kVA Power decide how the load
% manage- dependent start and stop
ment commands in the power
Value (G5) management system should
8882 Start/stop calc. S2
Percentage be calculated.

8920 Secured mode

Secured Option: Multi-start setpoint 1 and 2:


Secured
mode OFF Power - Auto calculation
8921 Secured mode Sec mode
Secured manage- - 1 DG
OFF
mode ON ment - 2 DG
Auto cal- (G5) - 3 DG
culation Auto cal- - 4 DG
8922 Multi-start setpoint 1 Setpoint 1 - 5 DG
Start 16 culation
DG - 6 DG
- 7 DG
Minimum - 8 DG
8923 Multi-start setpoint 1 Run 1 number 1 - 9 DG
run. 1-16 - 10 DG
8924 Multi-start config. Select - 11 DG
- 12 DG
Auto cal-
- 13 DG
culation Start 16
8925 Multi-start setpoint 2 Setpoint 2 - 14 DG
Start 16 DG
- 15 DG
DG

DEIF A/S Page 126 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

- 16 DG

Minimum number of running


Minimum
DGs: 1-16 DGs.
8926 Multi-start setpoint 2 Run 2 number 1
run. 1-16
Multi-start configuration:
Selects between setpoint 1
and 2.

8930 Heavy consumer 1 variable load

Multi-in 102 Multi-in Type:


8931 HC 1 VAR load Type
Multi-in 108 102 - Multi-input 102
Setpoint 0 mA - Multi-input 105
8932 HC 1 VAR load 0 mA - Multi-input 108
min. 10 mA
Setpoint 10 mA The function is only avail-
8933 HC 1 VAR load 20 mA
max. 20 mA able in AGC DG units.

8940 Heavy consumer 2 variable load

Multi-in 102 Multi-in Type:


8941 HC 2 VAR load Type
Multi-in 108 105 - Multi-input 102
Setpoint 0 mA - Multi-input 105
8942 HC 2 VAR load 0 mA - Multi-input 108
min. 10 mA
Setpoint 10 mA The function is only avail-
8943 HC 2 VAR load 20 mA
max. 20 mA able in AGC DG units.

DEIF A/S Page 127 of 137


AGC-3 Alarm and Parameter List

Jump menus
A number of menus can only be entered using the jump menu:

9000 Software version


Information about the actual software downloaded to the unit. Please check this before
contacting DEIF regarding service and support matters.

9010 Display character test


Shows a test print of the character set in the display.

9020 Service port


The service port can be set up to use the ASCII communication. The ASCII communication is
used when the utility software is connected through a modem.

Selection ‘0’ must be used for cable connection between the AGC and the PC.
Selection ‘1’ must be used for modem connection between the AGC and the PC.

9070 M4 SW version
Information about the software version in the engine I/F PCB placed in slot #8.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

9100 Application

Designer’s This setting is only


Reference accessible using the ‘JUMP’
Handbook button on the display.
DG unit Available selections:
9100 Application Application DG unit
BTB unit - DG unit (diesel generator)
- Mains unit (mains
connection)
- BTB unit (bus tie breaker)

Warning: The unit will return to factory settings if the parameter is changed!

No. Setting Min. Factory Notes Ref. Description


setting
Max.

911x Password

0 Designer’s It is recommended to
9116 User password Setting 2000
32000 Reference change the password levels
0 Handbook of the user, service and
9117 Service password YYYYY setting 2001 master password, if access
32000
to parameter settings must
0 be restricted.
9118 Master password XXXXX setting 2002
32000

DEIF A/S Page 128 of 137


AGC-3 Alarm and Parameter List

9120 Service menu


The service menu can only be entered using the ‘JUMP’ push-button. This menu is used in
service situations.

In the alarm selection you can see all the alarm timers and their remaining time if they are
counting.

The input and output selections show the present status of the inputs and outputs. E.g. mode
inputs, relay outputs and load sharing lines.

No. Setting Description

912x Service menu

Service menu Timers Shows remaining alarm delay time


Service menu Digital inputs Shows digital input status
Service menu Digital outputs Shows digital output status
Service menu Miscellaneous Shows misc. information

9130 AC config.
This menu is used to choose between the different AC measurement systems.

No. Setting Description

9130 AC config.

3 phase L1L2L3 (1)


2 phase L1L3 (2)
9130 AC config. Setting
2 phase L1L2 (3)
1 phase L1 (4)

9140 Angle compensation BB/G


This menu is used to compensate the transformer phase angle when the generator and busbar
measurements are made on each side of a transformer.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

9140 Angle comp. BB/G

Designer’s
-45.0 deg.
9140 Angle comp. BB/G Angle 0.0 Reference
45.0 deg.
Handbook

No. Setting Description

9150 Backlight dim

9150 Backlight dim Sets the light intensity for the display.

DEIF A/S Page 129 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

9160 User defined application

Designer’s The 4 different applications


Appl 1 (1) Appl. 1 Reference available make it possible to
9160 Application
Appl 4 (4) (1) Handbook shift between different plant
types.

9170 Internal CAN protocol


This menu is used to make it possible to interface to AGC units using application SW version
3.20.x or earlier.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

9170 Internal CAN protocol

Designer’s
Protocol 1 Protocol
9170 Application Application Reference
Protocol 2 1
Handbook

9180 Quick setup (AGC mains)


This menu makes it possible to set up the power management application without using the
‘Application configuration’ tool in the PC utility software.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

9180 Quick setup

OFF When using this menu, it will


9181 Quick setup Mode Setup stand-alone OFF not be possible to design
Setup plant applications with AGC bus
OFF tie units.
CAN A
9182 Quick setup CAN CAN A
CAN B
CAN A+B
Pulse
No breaker
9183 Quick setup MB Ext/Ats Pulse
Continuous
Compact
Pulse
No breaker
9184 Quick setup TB Pulse
Continuous
Compact
Normally Open
9185 Quick setup NX NO
Normally Closed

DEIF A/S Page 130 of 137


AGC-3 Alarm and Parameter List

9190 Application broadcast


This menu makes it possible to broadcast an application between all AGC units connected on
the CAN A or CAN B line.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

9190 Application broadcast

OFF
Application Broadcast
9191 Enable OFF
broadcast Broadcast +
activate
Application 1
Application Application 2
9192 Application Application 1
broadcast Application 3
Application 4

DEIF A/S Page 131 of 137


AGC-3 Alarm and Parameter List

Command timers

There are 8 identical command timers in the unit, but only command timer 1 is
shown here.

The setup of the command timers can only be accessed through the
“Parameters” in the PC utility software version 3.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

10000 Start/stop command 1

Start Designer’s
10001 Start/stop cmd. 1 Setpoint Start
Stop Reference
ON Handbook
10002 Start/stop cmd. 1 Enable OFF
OFF

10010 Cmd. 1 day(s)

Designer’s Possible selections:


Reference MO
Handbook TU
WE
MO
MO-TU- TH
MO-TU-
WE-TH- FR
10011 Cmd. 1 days Setpoint WE-TH-
FR-SA- SA
FR-SA-
SU SU
SU
MO-TU-WE-TH
MO-TU-WE-TH-FR
SA-SU
MO-TU-WE-TH-FR-SA-SU

10020 Cmd. 1 hour

Designer’s
0
10021 Cmd. 1 hour Setpoint 10 Reference
23
Handbook

10030 Cmd. 1 min

Designer’s
0
10031 Cmd. 1 min Setpoint 0 Reference
59
Handbook

The activation/deactivation of the command timers must be accessed from the


M-logic user interface in the PC utility software version 3.

DEIF A/S Page 132 of 137


AGC-3 Alarm and Parameter List

GSM settings

GSM settings are only accessible in the utility software.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

10320 GSM Pin code

Designer’s
GSM Pin 0 Reference
Function 1933
code 9999 Handbook

10330 Telephone no. 1

Designer’s
0 Reference
10330 Telephone 1 Function 12345678903
99999999999 Handbook

Menus similar to menu 10330 are available for telephone no.’s 2-5 with the
menu numbers 10340-10370.

Passwords

Password settings are only accessible in the utility software.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

10390 Password language page

Designer’s Selections are:


Reference - None
None
10390 Passw. lang. page None Handbook - Master
Customer
- Service
- Customer

10400 Password log page

Designer’s Selections are:


Reference - None
None Handbook - Master
10400 Passw. log page None
Customer - Service
- Customer

10410 Password control page

Designer’s Selections are:


Reference - None
None Handbook - Master
10410 Passw. control page None
Customer - Service
- Customer

DEIF A/S Page 133 of 137


AGC-3 Alarm and Parameter List

VDO 102

VDO 102 settings are only accessible in the utility software.

No. Setting Min. Factory Notes Ref. Description


setting
Max.

10460 VDO 1 type

Designer’s Selections are:


Reference -Sensor type 1
Sensor type 1 Sensor type
10460 VDO 1 type Handbook -Sensor type 2
Configurable 1
-Sensor type 3
-Configurable

10470 VDO 1 input setpoint 1

Designer’s Configurable VDO


0 Ohm Reference curve.
10470 VDO 1 inp. setp. 1 10 Ohm
480 Ohm Handbook

10480 VDO 1 output setpoint 1

Designer’s Configurable VDO


-49 Reference curve.
10480 VDO 1 outp. setp. 1 40
482 Handbook

10490 VDO 1 input setpoint 2

Designer’s Configurable VDO


0 Ohm Reference curve.
10480 VDO 1 inp. setp. 2 44.9 Ohm
480 Ohm Handbook

10500 VDO 1 output setpoint 2

Designer’s Configurable VDO


-49 Reference curve.
10500 VDO 1 outp. setp. 2 50
482 Handbook

10510 VDO 1 input setpoint 3

Designer’s Configurable VDO


0 Ohm Reference curve.
10510 VDO 1 inp. setp. 3 81 Ohm
480 Ohm Handbook

10520 VDO 1 output setpoint 3

Designer’s Configurable VDO


-49 Reference curve.
10520 VDO 1 outp. setp. 3 60
482 Handbook

10530 VDO 1 input setpoint 4

Designer’s Configurable VDO


0 Ohm Reference curve.
10530 VDO 1 inp. setp. 4 134.7 Ohm
480 Ohm Handbook

10540 VDO 1 output setpoint 4

DEIF A/S Page 134 of 137


AGC-3 Alarm and Parameter List

No. Setting Min. Factory Notes Ref. Description


setting
Max.

Designer’s Configurable VDO


-49 Reference curve.
10540 VDO 1 outp. setp. 4 80
482 Handbook

10550 VDO 1 input setpoint 5

Designer’s Configurable VDO


0 Ohm Reference curve.
10550 VDO 1 inp. setp. 5 184 Ohm
480 Ohm Handbook

10560 VDO 1 output setpoint 5

Designer’s Configurable VDO


-49 Reference curve.
10560 VDO 1 outp. setp. 5 100
482 Handbook

10570 VDO 1 input setpoint 6

Designer’s Configurable VDO


0 Ohm Reference curve.
10570 VDO 1 inp. setp. 6 200 Ohm
480 Ohm Handbook

10580 VDO 1 output setpoint 6

Designer’s Configurable VDO


-49 Reference curve.
10580 VDO 1 outp. setp. 6 110
482 Handbook

10590 VDO 1 input setpoint 7

Designer’s Configurable VDO


0 Ohm Reference curve.
10590 VDO 1 inp. setp. 7 210 Ohm
480 Ohm Handbook

10600 VDO 1 output setpoint 7

Designer’s Configurable VDO


-49 Reference curve.
10600 VDO 1 outp. setp. 7 115
482 Handbook

10610 VDO 1 input setpoint 8

Designer’s Configurable VDO


0 Ohm Reference curve.
10610 VDO 1 inp. setp. 8 220 Ohm
480 Ohm Handbook

10620 VDO 1 output setpoint 8

Designer’s Configurable VDO


-49 Reference curve.
10620 VDO 1 outp. setp. 8 120
482 Handbook

DEIF A/S Page 135 of 137


AGC-3 Alarm and Parameter List

VDO 105

VDO 105 settings are only accessible in the utility software.

Settings 10630-10790 equal the settings for VDO 102 (10460-10620).

VDO 108

VDO 108 settings are only accessible in the utility software.

Settings 10800-10960 equal the settings for VDO 102 (10460-10620).

Multi-input selections

No. Setting Min. Factory Notes Ref. Description


setting
Max.

10970 Engineering units

Bar/Celsius
10970 Engineering units Bar/Celsius
Psi/Fahrenheit

10980 Multi-input configuration 102


Possible selections:
4-20 mA
0-40 V DC
Pt100
4-20 mA
10980 Multi-inp.comf. 102 0-40 V DC Pt1000
Binary
VDO oil pressure
VDO water temp
VDO fuel level
Binary

10990 Multi-input configuration 105


Possible selections:
4-20 mA
0-40 V DC
Pt100
4-20 mA
10990 Multi-inp.comf. 105 0-40 V DC Pt1000
Binary
VDO oil pressure
VDO water temp
VDO fuel level
Binary

11000 Multi-input configurable 108


Possible selections:
4-20 mA
0-40 V DC
Pt100
4-20 mA
11000 Multi-inp.comf. 108 0-40 V DC Pt1000
Binary
VDO oil pressure
VDO water temp
VDO fuel level
Binary

DEIF A/S Page 136 of 137


AGC-3 Alarm and Parameter List

External digital outputs

No. Setting Min. Factory Notes Ref. Description


setting
Max.

12790 Ext. dig. out 1

Alarm Option:
Ext. dig. out 1 Function Alarm
Limit External
I/O
0.0 s modules
Ext. dig. out 1 OFF delay 5.0 s
999.9 s (H8)

The same for settings 12800-12940.

External module status

No. Setting Min. Notes Ref. Description


Max.

Option: This is a number read in


External I/O the external module and
-32768
12950 Ext module 0 STATUS modules (H8) displayed in the USW only.
+32767
Please refer to option H8
description for details.

The same for settings 12951-12983 (external modules 1 to 33).

DEIF A/S reserves the right to change any of the above.

DEIF A/S Page 137 of 137