Professional Documents
Culture Documents
Revision 1
January 2002
Page 1
Introduction
The following is a procedure guide recommended for use in the handling of bulk gas
measurements with the Orifice meter and chart recorder. It is designed to provide a quick
reference in carrying out bulk gas measurement using the DOF system.
The Daniel orifice fitting is still employed in many of SPDC facilities for measurement for
bulk gas released from Separators.
With the new drive to enshrine bulk gas measurement as an integral part of Production
management system it is pertinent to provide the necessary guide for the personnel involved
in the daily management and reading of the gas charts collected from the Barton/Foxboro
chart recorders.
It is hoped that the document will provide the much needed quick reference and checklist in
the process of gas volume measurement.
1.0
2.0
Page 2
The amount of deflection is governed by the magnitude of the pressure and the range
of the DP cell of the Barton/Foxboro recorder.
For fairly even trend on the chart, the reading could be estimated to a reasonable
accuracy by eyeballing.
For charts with rapid undulation however, a reliable reading can only be achieved via
the use of the Planimeter. The instrument evaluates the radius of the area traversed by
the cross-hair.
2.1
3.0
Device
Station OBGN/GP
Date
Time
VOF
Group
Ori
Third Party
23-JAN-03 06:00
NEPA
Size
Read
DP
Reading
Plan
5.75 2.353
100
60.00
Elem
Range Range
1500
100
F
57.0
.569
The fields to be populated on the EPPROMS entry screen are explained as follows:
Orifice size:
This is the diameter of the Orifice plate. If exact value is not accepted by EPPROMS,
use the closest value from the list in EPPROMS Table. To see EPPROMS list, press
<ctrl>F3 and move with <TAB> to see EPPROMS standard values. Be sure to check
PHE-OGA Oil & Gas Accounting.
Page 3
that the information to be loaded into EPPROMS corresponds to the value in place in
the field. Note that the value of the differential pressure set up across the orifice is
greatly influenced by the size of the hole relative to the pipe diameter.
Differential Factor:
This is the factor that is applied on the planimetered value. This field has been set at
2 and makes the system to double any input fed into the previous field. If it is set at 1,
then there is no need for dividing the planimeter results.
Planimeter Factor:
This should remain at the default 1 except where it is necessary to apply a multiplier
factor on the Static pressure.
Chart Range:
The linear range for the chart is 100.
Temperature:
The temperature value should be extracted as explained above and entered in degrees
Farenheit. Again the utmost must be done here to get an accurate value for the
temperature. As would be seen below in the equation for gas volume calculation, a
temperature factor is derived to correct the location value to the universal base
temperature of 600F.
Page 4
Specific Gravity:
This is the specific gravity of the gas stream passing through the orifice. This should
be derived from a proper gas composition analysis of gas sample taken from the
Separator. This parameter is very important in the final volume computation.
Obviously, with a given force applied on a gas, a lighter gas can be more easily
pushed through the orifice than a heavier one. The total volume of gas passing is
therefore directly influenced by this parameter.
4.0 Gas Volume calculation in EPPROMS
Once the required parameters as listed above have been entered into EPPROMS,
EPPROMS will compute the gas flow rate applying the AGA equation as follows:
Q = Chp
Where Q = quantity rate of flow at base conditions, cfh
h = differential pressure in inches of water at 60oF
p = absolute static pressure, psia
C = orifice flow constant which is expressed as follows:
C = (Fb)(Fr)(Y)(Fpb)(Ftb)(Ftf)(Fg)(Fpv)(Fm)(Ft)(Fa)
Where
Fb = Basic orifice factor
Fr = Reynolds number factor (viscosity)
Y = Expansion factor
Fpb = Pressure base factor
Ftb = Temperature base factor
Ftf= Flowing temperature factor
Fg = Specific gravity factor
Fpv = Supercompressibility factor
Fm = Manometer factor for mercury meter
Ft = Gauge location factor
Fa = Orifice thermal expansion factor
EPPROMS evaluates all these parameters from the basic inputs entered above.
5.0
Page 5
The meter is over-ranging and is an indication that the Plate size in the line is too
small. A bigger sized plate is needed.
Case III: Pen markings on charts too small, almost close to the zero line.
The differential pressure created in the line is too small to cause sufficient deflection
of the Pen on the chart.
The plate size is too large and should be replaced with an appropriate smaller plate.
Case IV: Incomplete cycle on the chart markings.
If the 24-hour cycle on the chart is incomplete due to fault on the meter while flow of
gas is continuing, then the reading from the chart needs to be extrapolated to 24
hours, since EPPROMS expects a 24-hr reading. The planimeter figure should be
multiplied by 24 and divided by the number of hours for which the meter was
available.
6.0 General rule for ensuring accurate gas flow measurement with DOF.
As a rule, to ensure accuracy of gas volume derivation with the DOF system, the following
potential sources of error should be monitored and addressed:
Incorrect information about the bore of the Orifice plate and the pipe (verify diameter
value stored in EPPROMS)
Eccentricity of the Orifice bore in relation to the pipe bore (i.e. not concentric)
Excessive pipe roughness
Incorrect location of differential taps in relation to the orifice plate
Accumulation of liquids in the pipe at the bottom of the plate
Changes in operating conditions
Excessive friction between the pen and chart
Leakage around the orifice plate
Non-uniform calibration of the meter (during calibration of the meter, a 4-point
calibration of linear range with pressure range is considered a standard and should be
achieved before the calibration certifcate is signed)
The list above is by no means exhaustive. Field Supervisors are expected to coordinate the
management of the bulk gas charts in the field as part of the key day to day operations
requirement. This is because, while the Orifice meter is considered as one of the most
reliable measurement systems the computed volume can only be as correct as the input
parameters.
Further update and expansion of this guide will be done as required.
Page 6