GT3A
GT3A
Switches & Pilot Lights
Key features:
4 selectable operation modes on each model
External start, reset, and gate inputs
Panel mount or socket mount
Large variety of timing functions
Power and output status indicating LEDs
Signaling Lights
Specifications
GT3A-1
GT3A-2
Operation
GT3A-3
Multi-mode
Time Range
Contact Ratings
Voltage Tolerance
Error
10% maximum
Reset Time
60msec maximum
Insulation Resistance
100MW minimum
Between power and output terminals: 2,000V AC, 1 minute
Between contacts of different poles: 2,000V AC, 1 minute
Between contacts of the same pole: 750V AC, 1 minute
Dielectric Strength
Delayed SPDT +
instantaneous SPDT
Delayed DPDT
Delayed DPDT
10.8VA
(200V AC, 60Hz)
13.5VA
(200V AC, 60Hz)
14.4VA
(200V AC, 60Hz)
12VDC/1W
24VDC/0.7W
24VAC/1.2VA
12VDC/1.1W
24VDC/0.6W
24VAC/1.3VA
12VDC/0.8W
24VDC/0.6W
24VAC/1.3VA
Shock Resistance
73g
79g
80g
Terminal Blocks
Vibration Resistance
Contactors
Delayed SPDT
Mechanical Life
Weight (approximate)
Timers
Setting Error
Electrical LIfe
Rated Voltage
Power Consumption
(approximate)
GT3A-4,-5,-6
Operating Temperature
10 to +50C
Operating Humidity
45 to 85% RH
Storage Temperature
30 to +80C
Housing Color
Circuit Breakers
Breakers
Circuit
Gray
843
Timers
Signaling Lights
GT3A
Part Numbers
GT3A-1, -2, -3
Mode Of
Operation
Time Range
Output
Contact
Delayed SPDT
0.1 seconds
to 180 hours
Delayed SPDT +
Instantaneous SPDT
Delayed DPDT
11-Pin
GT3A-1AF20
GT3A-1EAF20
GT3A-2AF20
GT3A-2EAF20
GT3A-2D12
GT3A-2ED12
GT3A-2AD24
GT3A-2EAD24
GT3A-3AF20
GT3A-3EAF20
GT3A-3D12
GT3A-3ED12
GT3A-3AD24
GT3A-3EAD24
1. For wiring schematics and timing diagrams for GT3A-1, -2, -3, see pages page 845 and page 846 respectively.
2. For more details about time ranges, see instructions on page page 850.
3. For socket and accessory part numbers, see page 860.
Mode of
Operation
A: ON-Delay 2
B: Cycle 2
C: Signal ON/OFF-Delay 1
D: Signal OFF-Delay 1
A: Interval 2
B: One-Shot Cycle
C: Signal ON/OFF-Delay 2
D: Signal OFF-Delay 2
A: One-Shot
B: One-Shot ON-Delay
C: One-Shot 2
D: Signal ON/OFF-Delay 3
4.
5.
6.
7.
8.
Time Range
Output
0.1 seconds
to 180 hours
For wiring schematics and timing diagrams GT3A-4,-5,-6, see pages 832, 833, and 833 respectively.
For more details about time ranges, see instructions on page 850.
A (11-pin) and B (11-pin) differ in the way inputs are wired.
For socket and accessory part numbers, see page 860.
For the timing diagrams overview, see page 832.
Circuit Breakers
844
Contact
Input
Terminal Blocks
Contactors
Timers
GT3A-4, -5, -6
www.IDEC.com
Delayed
DPDT
Start
Reset
Gate
B (11-pin)
GT3A-4AF20
GT3A-4EAF20
GT3A-4D12
GT3A-4ED12
GT3A-4AD24
GT3A-4EAD24
GT3A-5AF20
GT3A-5EAF20
GT3A-5AD24
GT3A-5EAD24
GT3A-6AF20
GT3A-6EAF20
GT3A-6AD24
GT3A-6EAD24
Timers
GT3A
Switches & Pilot Lights
Timing Diagrams/Schematics
GT3A-1 Timing Diagrams
Delayed SPDT
Operation
Mode
Selection
MODE
Item
Set Time
Power
Delayed
Contact
Terminal Number
Signaling Lights
ON-Delay 1
Operation
T
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
(NC)
(NO)
POWER
Indicator
Interval 1
MODE
Item
Set Time
Power
Delayed
Contact
Terminal Number
OUT
Operation
T
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
(NC)
(NO)
POWER
Indicator
OUT
MODE
Item
Set Time
Power
Delayed
Contact
Terminal Number
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
Timers
Cycle 1
(OFF first)
Operation
T
(NC)
(NO)
POWER
Indicator
OUT
MODE
Item
Set Time
Power
Delayed
Contact
Terminal Number
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
Contactors
Cycle 3
(ON first)
Operation
(NC)
(NO)
POWER
Indicator
OUT
Terminal Blocks
Circuit Breakers
845
Timers
Signaling Lights
GT3A
Operation
Mode
Selection
Operation
Mode
Selection
ON-Delay 1
MODE
Item
Set Time
Power
Delayed
Contact
Instantaneous
Contact
Terminal Number
Operation
T
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
(NC)
1-4
(NC)
1-3
(NO)
ON-Delay 1
MODE
(NO)
Item
Set Time
Power
Delayed
Contact
Terminal Number
Operation
T
2 - 7 (8p)
2 - 10 (11p)
1 -4, 5 - 8 (8p)
(NC)
1 -4, 8 - 11 (11p)
1 -3, 6 - 8 (8p)
(NO)
1 -3, 9 - 11 (11p)
POWER
Indicator
OUT
POWER
Indicator
OUT
Interval 1
MODE
Item
Set Time
Power
Delayed
Contact
Instantaneous
Contact
Interval 1
Terminal Number
Operation
T
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
(NC)
1-4
(NC)
1-3
(NO)
OUT
Cycle 1
(OFF first)
MODE
MODE
Contactors
Power
Delayed
Contact
Instantaneous
Contact
Terminal Number
Item
Set Time
Power
Delayed
Contact
Operation
T
Terminal Number
(NC)
1-4
(NC)
1-3
(NO)
(NO)
Cycle 3
(ON first)
MODE
Item
Set Time
Power
Delayed
Contact
2 - 7 (8p)
2 - 10 (11p)
1 -4, 5 - 8 (8p)
(NC)
1 -4, 8 - 11 (11p)
1 -3, 6 - 8 (8p)
(NO)
1 -3, 9 - 11 (11p)
POWER
Terminal Blocks
Delayed
Contact
Instantaneous
Contact
Terminal Number
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
(NC)
1-4
(NC)
1-3
(NO)
OUT
Operation
T
(NO)
POWER
Indicator
OUT
Circuit Breakers
846
Terminal Number
Indicator
MODE
OUT
OUT
Power
POWER
Indicator
Item
Set Time
Operation
T
2 - 7 (8p)
2 - 10 (11p)
1 -4, 5 - 8 (8p)
(NC)
1 -4, 8 - 11 (11p)
1 -3, 6 - 8 (8p)
(NO)
1 -3, 9 - 11 (11p)
Indicator
2 - 7 (8p)
2 - 10 (11p)
5 - 8 (8p)
8 - 11 (11p)
6 - 8 (8p)
9 - 11 (11p)
POWER
Cycle 3
(ON first)
Operation
T
POWER
OUT
Item
Set Time
Delayed
Contact
Terminal Number
2 - 7 (8p)
2 - 10 (11p)
1 -4, 5 - 8 (8p)
(NC)
1 -4, 8 - 11 (11p)
1 -3, 6 - 8 (8p)
(NO)
1 -3, 9 - 11 (11p)
Indicator
Indicator
Cycle 1
(OFF first)
Power
(NO)
POWER
Timers
MODE
Item
Set Time
www.IDEC.com
Operation
Timers
GT3A
Switches & Pilot Lights
Operation
Mode Selection
ON-Delay 2
MODE
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Start
Input
Operation
2 - 10 POWER
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
(NC)
Terminal Number
Signaling Lights
Item
Power
(NO)
POWER
Indicator
OUT
Set Time
Item
Power
Cycle 2
Terminal Number
T"
Operation
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
Timers
Input
T'
2 - 10 POWER
Start
MODE
Ta
(NC)
(NO)
POWER
Indicator
OUT
Set Time
Item
Signal ON/OFF-Delay 1
MODE
Ta
Terminal Number
T"
T"
Operation
2 - 10 POWER
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Start
Input
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
Contactors
Power
ON or L
ON or L
ON or L
(NC)
(NO)
POWER
Indicator
Item
Power
Signal OFF-Delay 1
MODE
Ta
Ta
Terminal Number
T"
Ta
Operation
2 - 10 POWER
Start
Input
Terminal Blocks
OUT
Set Time
Reset
Gate
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
2 - 5 (A)
Delayed
Contact
ON or L
ON or L
(NC)
(NO)
Circuit Breakers
1-4
8 - 11
1-3
9 - 11
ON or L
POWER
Indicator
OUT
Set Time
Ta
Ta
847
Timers
Operation
Mode Selection
Signaling Lights
GT3A
Item
Power
Interval 2
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Start
MODE
Terminal Number
Input
Operation
2 - 10 POWER
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
(NC)
(NO)
POWER
Indicator
OUT
Set Time
Item
Power
One-Shot Cycle
Timers
MODE
T'
Terminal Number
T"
Operation
2 - 10 POWER
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Start
Input
Ta
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
(NC)
(NO)
POWER
Indicator
OUT
Set Time
Contactors
Item
Power
Signal ON/OFF-Delay 2
MODE
Ta
Terminal Number
T'
T"
Operation
2 - 10 POWER
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Start
Input
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
(NC)
(NO)
POWER
Terminal Blocks
Indicator
OUT
Set Time
Item
Power
Signal OFF-Delay 2
MODE
Circuit Breakers
Ta
Terminal Number
Ta
Ta
T'
T"
Operation
2 - 10 POWER
Start
Input
Reset
Gate
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
(NC)
(NO)
POWER
Indicator
OUT
Set Time
Ta
Ta
848
www.IDEC.com
T'
T"
Ta
Timers
GT3A
Switches & Pilot Lights
Operation
Mode Selection
One-Shot 1
MODE
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Start
Input
Operation
2 - 10 POWER
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
(NC)
Terminal Number
Signaling Lights
Item
Power
(NO)
POWER
Indicator
OUT
Set Time
Ta
Item
Power
One-Shot ON-Delay
MODE
Ta
T'
Terminal Number
T"
Operation
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
ON or L
ON or L
ON or L
Timers
2 - 10 POWER
Start
Input
Ta
(NC)
(NO)
POWER
Indicator
OUT
Set Time
Item
One-Shot 2
MODE
T'
Terminal Number
T"
Operation
2 - 10 POWER
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
Start
Input
Ta
Reset
Gate
2 - 5 (A)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
Contactors
Power
ON or L
ON or L
ON or L
(NC)
(NO)
POWER
Indicator
Item
Power
Signal ON/OFF-Delay 3
MODE
T'
Terminal Number
T"
Operation
2 - 10 POWER
Start
Input
Ta
Terminal Blocks
OUT
Set Time
Reset
Gate
2 - 6 (A)
5 - 7 (B)
2 - 7 (A)
6 - 7 (B)
2 - 5 (A)
Delayed
Contact
ON or L
ON or L
(NC)
(NO)
Circuit Breakers
1-4
8 - 11
1-3
9 - 11
ON or L
POWER
Indicator
OUT
Set Time
Ta
T'
T"
Ta
Ta
849
Timers
GT3A
Switches & Pilot Lights
Signaling Lights
m Setting Knob
Step 1.
Circuit Breakers
Terminal Blocks
Contactors
Timers
k Dial Selector
0-1, 0-3, 0-6, 0-18
Step 2.
Step 3.
Set the precise period of time desired by using the m Setting Knob.
850
Selection
j Operation Mode Selector
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
Selection
k Dial Selector
l Time Range Selector
0-1
0-3
1S
0-6
0-18
0-1
0-3
10S
0-6
0-18
0-1
0-3
10M
0-6
0-18
0-1
0-3
10H
0-6
0-18
Selection
www.IDEC.com
Remarks
Remarks
Timers
GT3F
Switches & Pilot Lights
Signaling Lights
Specifications
GT3F-1
Operation
GT3F-2
True power OFF-delay
Time Range
Rated Voltage
Contact Rating
Contact Form
SPDT
DPDT
1 second
AF20: 100 to 240V AC
AD24: 21.6 to 26.4VDC, 20.4 to 26.4VAC
0.2%, 10 msec
Voltage Error
0.2%, 10 msec
Temperature Error
0.2%, 10 msec
Setting Error
10% maximum
Insulation Resistance
Timers
Repeat Error
100MW minimum
Power Consumption
Electrical Life
Vibration Resistance
Operating Temperature
10 to +50C
Storage Temperature
30 to +80C
Operating Humidity
45 to 85% RH
Weight (approximate)
Terminal Blocks
Shock Resistance
Contactors
Dielectric Strength
Mechanical Life
77g
79g
Circuit Breakers
1. An inrush current flows during the minimum power application time. AF20: approximate 0.4A,
AD24: approximate 1.2A
2. GT3F does not read the preset time range shown on the knob after power is turned off. Note that minimizing
the preset time, by turning the knob to zero, does not shorten the delay time after power is removed.
851
Timers
GT3F
Signaling Lights
True-Power
OFF-delay
Rated
Voltage Code
Time Range
AF20: 100 to
240VAC (50/60Hz)
AD24: 24V AC/DC
Output
Contact
Optional Input
Delayed SPDT
Reset
Delayed DPDT
None (8p)
Reset (11p)
8-Pin
GT3F-1AF20
GT3F-1EAF20
GT3F-1AD24
GT3F-1EAD24
GT3F-2AF20
GT3F-2EAF20
GT3F-2AD24
GT3F-2EAD24
Optional reset input resets the contact to the OFF state before time out.
Timing Diagrams/Schematics
GT3F-1 Timing Diagrams
GT3F-1 (8-pin)
Item
Terminal Number
2 - 7 (8p)
2 - 10 (11p)
1 - 4 (8p)
ON or L
6 - 7 (11p)
Power
Reset
Input
Delayed
Contact
Indicator
5 - 8 (8p)
1 - 4 (11p)
(NC)
6 - 8 (8p)
1 - 3 (11p)
(NO)
Operation
POWER
Set Time
Tr
T = Set time
Ta = Shorter than set time
Ts = 1 Second
Tr = Minimum Power Application Time
GT3F-1: 1 Second
Ta
Ts
Circuit Breakers
852
Terminal Blocks
Contactors
GT3F-1E (11-pin)
Delayed SPDT Output, with Reset Input
www.IDEC.com
11-Pin
Timers
GT3F
GT3F-2 (8-pin)
m n
Reset
j q
POWER
Item
8-Pin Type
Terminal Number
(NC)
(NO)
11-Pin Type
POWER
T
Terminal Number
Tr
Operation
2 - 10
6 - 7 (11p)
1-4
8 - 11
1-3
9 - 11
Delayed
Contact
Indicator
1-4
5-8
1-3
6-8
Power
Reset
Input
POWER
Operation
Set Time
Item
POWER
2-7
Delayed
Contact
Indicator
no p
q
m
r
l
s
k
(-)
(+)
j
Reset
o
p (+)
Power
no p
q
m
r
l
s
k
(-)
(+)
j
Signaling Lights
l
(-) k
(Transistor Input)
ON or L
(NC)
(NO)
POWER
Tr
Ta
Ts
Timers
Set Time
When power is applied, the NO contact closes. When power is removed, the timing period begins. When time has elapsed, the NO contact opens. Optional reset
input will return contacts to original state before time elapses.
Contactors
T = Set time
Ta = Shorter than set time
Ts = 1 Second
Tr = Minimum Power Application Time
GT3F-1: 1 Second
Terminal Number
Reset
Input
Set Time
Operation
2 - 10
6 - 7 (11p)
Delayed
Contact
Indicator
Terminal Blocks
Item
Power
ON or L
1-4
8 - 11
(NC)
1-3
9 - 11
(NO)
POWER
T
Ta
Ts
Circuit Breakers
Tr
853
Timers
GT3F
Switches & Pilot Lights
POWER Indicator
l Setting Knob
Signaling Lights
j Dial Selector
0-1, 0-3, 0-6, 0-18, 0-60
Select a time
rangethat
contains the
desired period
of time.
Desired Operation
Selection
j Dial Selector
0.1s to 1s
0 to 1
0.1s to 3s
0 to 3
0.1s to 6s
0 to 6
0.1s to 10s
0 to 1
0.3s to 30
0 to 3
0.6s to 60
0 to 6
1.8s to 180s
0 to 18
6s to 600s
0 to 60
Remarks
Step 2
Timers
Step 1
Remarks
Setting Examples:
1. When the Setting Knob l is set at 2.5, with Dial Selector j 0 to 3 and Time
Range Selector k 1S selected, then the set time is 2.5 seconds.
Circuit Breakers
Terminal Blocks
Contactors
854
www.IDEC.com
Timers
GT3F
Switches & Pilot Lights
GT3 Series
Timer
Input
Contact or Transistor
[correct]
Input
Terminal
Input
Terminal
2
10
Power
Power
10
Signaling Lights
10
Input
Terminal
Input
Terminal
10
In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
GT3 Series
Timer
Input
Terminal
Insulating Transformer
On the GT3F timers, connect the input signals to terminal No.1 and 4 only on the 8-pin type; connect the input signals to terminal No. 6 and 7 only on the 11-pin type.
Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
Circuit
Rectifier
Circuit
Power
Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for input wiring.
Timers
The GT3F, consisting of a high-impedance circuit, may not be reset due to the influence of an inductive voltage or residual voltage caused by a leakage current. If not
reset, connect an RC filter or bleeder resistor between power terminals so that the voltage between power terminals can be reduced to less than 15% of the rated
voltage.
Contactors
Terminal Blocks
Circuit Breakers
855
Timers
Signaling Lights
GT3W
General Specifications
Contact Ratings
Operation System
960VA/120W
Operation Type
Multi-Mode
Allowable Voltage
250V AC/150V DC
Time Range
Allowable Current
5A
Pollution Degree
2 (IE60664-1)
III (IE60664-1)
Maximum permissible
operating frequency
Terminal Blocks
Contactors
Timers
Voltage Tolerance
100-240V AC(50/60Hz)
AD24
24V AC(50/60Hz)/24V DC
D12
12V DC
AF20
85-264V AC(50/60Hz)
AD24
20.4-26.4V AC(50/60Hz)/21.6-26.4V DC
D12
10.8-13.2V DC
Rated Voltage x10% minimum
-10 to +50C (without freezing)
Atmospheric Pressure
Reset Time
60msec maximum
Repeat Error
0.2%, 10msec*
Voltage Error
0.2%, 10msec*
Temperature Error
0.6%, 10msec*
Setting Error
10% maximum
Insulation Resistance
Dielectric Strength
Vibration Resistance
Shock Resistance
Power Consumption
(Approx.)
2.3VA
200V AC/60Hz
4.6VA
AD24 (AC/DC)
1.8VA/0.9W
Mounting Position
Free
Dimensions
40Hx 36W x 70 mm
Weight (Approx.)
72g
* For the value of the error against a preset time, whichever the largest applies.
856
www.IDEC.com
100V AC/60Hz
Rated Load
Degree of Protection
Circuit Breakers
1/8HP, 240V AC
AF20
Electrical
Mechanical
Timers
GT3W
Switches & Pilot Lights
Output
Contact
Time Range*
Rated Voltage
100 to 240V AC
(50/60Hz)
3A, 240V AC
5A, 120V AC/30V DC
(Resistive Load)
Delayed
SPDT
+
Delayed
SPDT
1: 0.1sec - 6 hours
*(See Time Range Settings for details.)
8 pin
GT3W-A11AF20N
11 pin
GT3W-A11EAF20N
8 pin
GT3W-A11AD24N
11 pin
GT3W-A11EAD24N
8 pin
GT3W-A11D12N
11 pin
GT3W-A11ED12N
24V AC/DC
Signaling Lights
A: Sequential Start
B: On-delay with course and fine
C: Recycler and instaneous
D: Recycler outputs (OFF Start)
E: Recycler outputs (ON Start)
F: Interval ON
G: Interval ON Delay
H: Sequential
Interval
Pin Configuration
12V DC
GT3W-A33AF20N
8 pin
24V AC/DC
100 to 240V AC
(50/60Hz)
GT3W-A33AD24N
1S
10S
Time Range
0.1 sec - 1 sec
1S
Scale
Time Range
0.1 sec - 3 sec
1M
10M
15 sec - 10 min
1H
3 min - 3 hours
1S
1S
10S
1 sec - 60 sec
1M
6 sec - 6 min
1H
0-6
10M
1 min - 60 min
1H
6 min - 6 hours
10H
0-3
3 sec - 3 min
36 sec - 30 min
0 - 30
36min - 30 hours
Contactors
1M
0-1
Timers
Time Range
Selector
Terminal Blocks
Circuit Breakers
857
Timers
GT3W
Operation Chart
Power
2-7
Delayed
Contact
Ry2
Indicator
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Description
ON after T1
ON after T1 + T2
OUT1
OUT2
Contactors
Timers
Set Time
T1
Delayed
Contact
Ry2
Indicator
ON after T1 + T2
OUT1
Delayed
Contact
Ry2
Indicator
Set Time
T1
Item
Terminal
No.
2-7
Delayed
Contact
Ry1
Delayed
Contact
Ry2
Indicator
Operation
Description
Instantaneous ON
OFF during T1
ON during T2
OUT1
2-7
Delayed
Contact
Ry1
Delayed
Contact
Ry2
Indicator
Terminal
No.
Power
2-7
Delayed
Contact
Ry1
Delayed
Contact
Ry2
Indicator
Operation
Description
T2
Operation
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Description
ON during T1
ON after T1 + T2
OUT1
OFF during T1
ON during T2
OFF during T1
ON during T2
OUT1
T1
Item
Terminal
No.
Power
2-7
Delayed
Contact
Ry1
Delayed
Contact
Ry2
Indicator
OUT2
T2
Operation
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
ON after T1,
during T2
OUT2
T1
T2
www.IDEC.com
Description
ON during T1 + T2
OUT1
Set Time
Circuit Breakers
858
ON after T1,
during T2
T1
Set Time
T2
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Set Time
ON during T1
OUT2
T1
Terminal
No.
Description
OUT1
Item
OUT2
Item
Operation
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Set Time
T2
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Power
T2
OUT2
OUT2
Power
ON during T1
OFF during T2
T1
Delayed
Contact
Ry1
ON after T1 + T2
ON during T1
OFF during T2
OUT2
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Description
Description
OUT1
2-7
Operation
Operation
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Power
Set Time
Terminal Blocks
Delayed
Contact
Ry1
2-7
Power
Indicator
2-7
Terminal
No.
Terminal
No.
Delayed
Contact
Ry2
Item
Power
Item
Item
Delayed
Contact
Ry1
Operation Chart
Terminal
No.
Set Time
T2
F: Interval ON
Delayed
Contact
Ry1
Operation
Mode
E: Recycler outputs (ON Start)
Item
Terminal
No.
G: Interval ON Delay
A: Sequential Start
Mode
H: Sequential Interval
Signaling Lights
Timing Diagrams/Schematics
T1
T2
Timers
GT3W
T2 Setting Knob
Caution
All Electronic Timer modules are manufactured under IDECs rigorous quality
control system, but users must add a backup or fail safe provision to the
control system when using the Electronic Timer in applications where heavy
damage or personal injury may occur should the Electronic Timer fail.
Caution notices are used where inattention might cause personal injury or damage to equipment.
Timers
Make sure that the operating conditions are as described in the specifications. If you are uncertain about the specifications, contact IDEC in advance.
Safety Precautions
Signaling Lights
T1 Setting Knob
Use an IEC60127-approved fuse and circuit breaker on the power and output
line outside the Electronic Timer.
Warning
Warning notices are used to emphasize that improper operation may cause sever
personal injury or death.
Turn power off to the Electronic timer before starting installation, removal,
Wiring, maintenance, and inspection on the Electronic Timer.
Failure to turn power off may cause electrical shocks or fire hazard.
Emergency stop and interlocking circuits must be configured outside the
Electronic timer. If such a circuit is configured inside the Electronic Timer,
failure of the Electronic timer may cause malfunction of the control system, or
an accident.
Terminal Blocks
Circuit Breakers
859
Timers
GT3 Series
Accessories
DIN Rail Mounting Accessories
DIN Rail/Surface Mount Sockets and Hold-Down Springs
DIN Rail Mount Socket
Appearance
Part No.
GT3A-1, 2, 3 (8-pin)
GT3F-1, 2 (8-pin)
GT3W (8-pin)
SR2P-05
GT3A-1, 2, 3 (11-pin)
GT3A-4, 5, 6
GT3F-1, 2 (11-pin)
GT3W (11-pin)
SR3P-05
Appearance
Part No.
SFA-203
GT3A-1, 2, 3 (8-pin)
GT3F-1, 2 (8-pin)
GT3W (8-pin)
SR2P-05C
GT3A-1, 2, 3 (11-pin)
GT3A-4, 5, 6
GT3F-1, 2 (11-pin)
GT3W (11-pin)
SR3P-05C
GT3A-1, 2, 3 (8-pin)
GT3F-1, 2 (8-pin)
GT3W (8-pin)
SR2P-06
Timers
Signaling Lights
Style
Terminal Blocks
Contactors
SFA-202
GT3A-1, 2, 3 (11-pin)
GT3A-4, 5, 6
GT3F-1, 2 (11-pin)
GT3W (11-pin)
SR3P-06
BNDN1000
Hold-down Spring
SFA-402
Circuit Breakers
Insert
Socket SR2P-05
Socket SR2P-06
860
www.IDEC.com
8-pin Socket
SR2P-51
Timers
Appearance
Applicable HD Springs
Use with Timers
GT3A- (8-pin)
GT3W- (8-pin)
GT3F- (8-pin)
Part No.
Appearance
Part No.
SR2P-51
Signaling Lights
SFA-402
GT3A- (11-pin)
GT3W- (11-pin)
GT3F- (11-pin)
SR3P-51
Appearance
Part No.
RTB-G01
SR6P-M08G
SR6P-M11G
SR6P-S08
SR6P-S11
Timers
Accessory
Contactors
Terminal Blocks
Circuit Breakers
861
Timers
GT3 Series
Timer
Input
Contact or Transistor
[correct]
Input
Terminal
Signaling Lights
Input
Terminal
2
10
Power
Power
Input
Terminal
Input
Terminal
2
10
10
10
In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
GT3 Series
Timer
Input
Terminal
Circuit
Insulating Transformer
Connect the input signal terminals of the GT3A timers to Terminal No.2 only. Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
5, 6, and 7
Input Terminal
RY
10
Power
Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for
input wiring.
Circuit Breakers
Terminal Blocks
Contactors
Timers
Rectifier
Circuit
Power
862
www.IDEC.com
Timers
Gate Input
Start Input
Reset Input
9
2
10
1
11
Power
Signaling Lights
For transistor input, use transistors with the following specifications; VCE = 40V, VCES = 1V or less, IC = 50 mA or more, and ICBO = 50A or less. The resistance
should be less than 1k when the transistor is on. When the output transistor switches on, a signal is input to the timer.
6
Gate Input
Start Input
Reset Input
9
2
10
1
11
Power
Gate Input
Start Input
Reset Input
9
2
10
1
11
Power
Timers
Reset Input
Gate Input
No-voltage contact inputs and NPN open collector transistor inputs are applicable.
24V DC, 1mA maximum
Contactors
Start Input
Terminal Blocks
Circuit Breakers
863
Timers
Dimensions
36.0
70.0
N40.0
5.6
Unit: mm
60
40
36
64.2
Holddown
spring
(SFA-202)
DIN Rail
18
13
22
36
52
33
40
27
101.5 maximum
Contactors
Hold-down
Spring (SFA-203)
36
64.2
16.5
20
13
Timers
1.7
31.7
60
1.7
95 maximum
Holddown
spring
(SFA-202)
28.5
42.5
1.7
48
Terminal Blocks
95 maximum
31.7
40
11
61.2
Circuit Breakers
48
864
www.IDEC.com
64.2
13
DIN Rail
18
22
Signaling Lights
Timers
45
Tolerance: +0.5 to 0
N: No. of timers mounted
3.5 max.
4
5.6 min.
3.6 min.
30.4
44.6
6.9 max.
11 7
9 10
3.5 max.
Signaling Lights
44.6
45
45
34
45
Single
Mounting
5.8 min.
3.6 min.
6.9 max.
7
80.5
30.5
9.8 3
92
7
8.5 4
865
Timers
General Instructions for All Timer Series
Load Current
With inductive, capacitive, and incandescent lamp loads, inrush current more
than 10 times the rated current may cause welded contacts and other undesired
effects. The inrush current and steady-state current must be taken into consideration when specifying a timer.
Excessive vibration or shocks can cause the output contacts to bounce, the
timer should be used only within the operating extremes for vibration and shock
resistance. In applications with significant vibration or shock, use of hold down
springs or clips is recommended to secure a timer to its socket.
Contact Protection
Time Setting
The time range is calibrated at its maximum time scale; so it is desirable to use
the timer at a setting as close to its maximum time scale as possible. For a more
accurate time delay, adjust the control knob by measuring the operating time
with a watch before application.
Input Contacts
Use the timer within the operating temperature and operating humidity ranges
and prevent freezing or condensation. After the timer has been stored below
its operating temperature, leave the timer at room temperature for a sufficient
period of time to allow it to return to operating temperatures before use.
Use mechanical contact switch or relay to supply power to the timer. When
driving the timer with a solid-state output device (such as a two-wire proximity
switch, photoelectric switch, or solid-state relay), malfunction may be caused by
leakage current from the solid-state device. Since AC types comprise a capacitive load, the SSR dielectric strength should be two or more times the power
voltage when switching the timer power using an SSR.
Environment
Avoid contact between the timer and sulfurous or ammonia gases, organic solvents (alcohol, benzine, thinner, etc.), strong alkaline substances, or strong acids.
Do not use the timer in an environment where such substances are prevalent. Do
not allow water to run or splash on the timer.
Timers
Signaling Lights
General Instructions
Contactors
Voltage Error
= Tv - Tr x 100%
Tr
= Tt - T20 x 100%
T20
Setting Error
Circuit Breakers
Terminal Blocks
880
www.IDEC.com