Professional Documents
Culture Documents
Continued on page 20
September 2003
Designers Guide
Continued from page 18
have the proper amount of water circulating through it. There are valves sold
specifically for this purpose with calibrated markings on the valve handle.
Alternately, a throttling valve, such as a
globe valve, can be used for balancing.
However, a gate valve or ball valve does
not work well for balancing, as they do
not easily control low flow rates.
Second, hot water circulation must not
have inverted traps in the piping. The reason for this is the fact that air is released
from solution at an increasing rate with
temperature. Consequently, hot water
piping tends to become air-bound more
readily than cold water. If a hot water circulation leg becomes air-bound it can
disrupt the flow and prevent circulation.
One means of avoiding air in circulation
piping is to run the circulation loop on the
level below the top floor of plumbing fixtures. This allows trapped air to be
released from the fixtures when they are
used. If this approach is not possible,
high points in the circulation loop can be
vented with automatic air vent valves
(AVV).
Pump Flow Rate
The pump in a hot water circulation
system must be capable of moving water
through the system nearly as fast as it
cools down. The rate at which the water
cools is a function of the thickness of
insulation and the temperature differential. Table 1 indicates standard BTU loss
values for hot water piping with 1" fiberglass insulation and a 50-degree temperature differential (120-degree water in a
70-degree environment). These numbers
are fairly standard, but would have to be
modified for accuracy if a different insulation thickness or water temperature
were used.
Table 1
Pipe Size
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
4"
BTUH/ft
6
7
8
9
10
11
13
15
18
September 2003
Figure 1
Pump Head
Lastly, the pump head needs to be calculated. The pump must be capable of
overcoming the friction through the furthest part of the system. To determine
this, the friction loss associated with the
circulated flow rate through the furthest
riser or loop must be calculated. This calculation can be tedious for a large sysPlumbing Engineer
Table 2
Size
3/4"
3/4"
3/4"
3/4"
3/4"
1"
1"
1-1/4"
1-1/2"
1-1/2"
gpm
1
2
3
4
5
2
5
3
4
5
loss/100'
0.46
1.5
3.2
5.1
7.6
0.46
2.5
0.35
0.23
0.42
tem. Done properly, it must include friction losses for each portion of the system
where the flow increases due to accumulation of each circulated loop. In our
example, the pressure loss through the
furthest loop would look like that which
is presented in Table 2.
Therefore, the minimum pump head
required is about 17' to circulate through
the furthest riser (on the left). Once it can
overcome this friction it will have sufficient pressure to circulate through the
other risers. Remember, you do not need
to include the friction through all of the
risers, only the furthest loop. Note that
friction factors were taken from a standard friction chart for
copper pipe. Also note
that hot water circulation pumps should be of
either bronze or stainless steel construction.
OtherConsiderations
Keep in mind that hot
water circulation is not
as exact a science as the
calculations
would
imply. It is no simple
task to balance a system
with exactly 1 gpm
flowing through each
riser. For this reason, it
is a good idea to put a
little fat into the circulation pump. As
illustrated in Table 2, I would probably
double the flow rate of the pump to
allow for errors in balancing the system.
There is nothing more frustrating than a
hot water circulation system that balances on paper but not in the field.
Nobody will thank you for saving them
1/25th of a horsepower on the circula-
length
100
50
50
50
50
100
200
200
200
200
Total
0.46
0.75
1.6
2.6
3.8
0.46
5
0.7
0.46
0.84
Total: 16.67