Professional Documents
Culture Documents
2. System
description
SPACE 3000
Service Manual
3.
2.1 Overview
2.2 Functions
2.3 Components
2.4 Terminal
2.5
2.6
Delivery settings
4. Troubleshooting
8
9
Repairs
5. Periodical
inspections
6. Connecting
accessories
Settings
7.
10
4.3
11
4.4 Repairs
12
4.5
13
5.1 Service
14
5.2
15
16
6.2 Settings
17
6.3
18
6.4
19
SPACE information
20
2000-12-20
2000-12-20
PREF
ACE
PREFACE
This service manual describes the microprocessor
controlled electronic safety system, which is used to
control the various functions on a HIAB crane.
The information in this manual is divided into seven
different main sections. Some of the sections are
divided into subsections.
The new structure of the binder will make it easier for
you, the service engineer in the HIAB organisation, to
find the information you are looking for.
If for example a customer wants to have a winch
mounted on his crane, all information regarding electrical connection and changing of settings will be found
under section 6.1 Connecting accessories.
If you want to learn more about how the system works
all information regarding function and components will
be found under section 2 System description.
We hope that you will like the improved layout of the
manual.
If there is something regarding the information or
structure in the manual that you think could be improved please let us know. Your information will be of
great value to us and will be used when updating the
manual.
HIAB AB,
Product support dept.,
Technical documentation
2000-12-20
SAFETY REGULA
TIONS
REGULATIONS
Read this for your safety
The HIAB Cargo Handling Equipment can be hazardous if it is not operated correctly. Make sure you read
and understand the general safety information given in
this chapter.
The equipment must be operated in accordance with
the instructions given in the relevant Operators
Manual. Using the equipment in any other way or for
any other purpose is prohibited.
Warnings, cautions, notes and tips are given in this
manual. Their meanings are as follows:
WARNING
A Warning is given where wrong action could result in
death or injury to the operator and nearby personnel.
Warnings must always be adhered to, and given
precedence over written and verbal instructions as well
as Cautions.
CAUTION
A Caution is given where wrong action could result in
damage to the equipment. Cautions must always be
adhered to, and given precedence over Notes, and
written and verbal instructions.
NOTE!
A note emphasises an important piece of information or
an instruction.
Warnings and Cautions that apply to the general
operation of the HIAB Cargo Handling
Equipment are given in the relevant Operators Manual.
TIP!
Tip to make work easy to carry out.
Excluded personnel
Untrained personnel must not operate or carry out
repairs to the Cargo Handling Equipment.
2000-12-20
Maintenance manual
7.2.4.1
7.2.4.2
7.2.4.3
2000-12-20
2000-12-20
2000-12-20
2000-12-20
2.1 Overview
2.1 Overview
Contents
General......................................................................................... 3
SPACE ......................................................................................... 4
CAN-Communication ......................................................... 4
Standard box (SPACE box) ................................................ 4
User interface .................................................................... 5
Column box ........................................................................ 5
Sensors ............................................................................. 5
Indicators ........................................................................... 5
Dump valve ........................................................................ 6
Signalling components ....................................................... 6
Function ....................................................................................... 7
SPACE Operating Principles ............................................. 7
Switch on ................................................................ 7
Beginning Operation ............................................... 8
During Operation .................................................... 8
SPACE, system overview .................................................. 9
2000-12-20
2.1 Overview
2000-12-20
2.1 Overview
GENERAL
SPACE 3000 is a microprocessor controlled electronic
safety system used to control the various functions on
a HIAB crane (Fig. 1).
SPACE stands for:
S = Speed
P = Payload
A = Accessories
C = Certificate
E = Electronics
SPACE 3000 contains a microprocessor that is the
system's "brain". On the crane there are various
sensors and indicators which send signals to the
microprocessor regarding the crane's load, position
and movements.
This then decides how the crane can be operated and
stops or reduces unpermitted movements and speeds.
SPACE 3000
1070-328
ADC
Fig. 1
2000-12-20
2.1 Overview
SP
ACE
SPACE
(Fig. 2)
A CL/DUO system consists of e.g.:
1
1
User interface
Empty box
Column box
Pressure sensors
4
Indicators
Dump valve
Spool sensors.
5
ADC
SPACE 3000
MSC valve
The modules are connected in a star-shaped pattern
with the Standard box in its centre.
1070-327
CAN-Communication
The Standard box, the User interfaces and other
components such as Cabin warning are with 7-wire
shielded cables. The modules use a CAN-bus for
communication. It was developed for the automotive
industry with high demands on reliability and suppression of disturbances. The CAN-bus uses two wires, but
will still function if one of them is interrupted or shorted
to a permanent voltage.
1. Tilt indicators
2. Pressure sensors
3. Column box
4. Slewing sector indicators
5. Standard box
6. Dump valve
7. Spool sensors
Fig. 2
Standard box
The Standard box is the heart of the system. The
microprocessor monitors crane operation.
Main power supply is connected to the Standard box.
2000-12-20
2.1 Overview
User interface
(Fig. 3)
The User interface is the communication centre of the
SPACE 3000. It gives information about the system
and is also where the user controls the system.
The User interface is located on the Standard box and
on an empty box. It can also be located on an
Extended box (if present). Maximum four User
interfaces can be fitted on a crane.
SPACE 3000
1070-316
Column box
ADC
Fig. 3
Indicators
An indicator gives an on/off signal, which correspond to
e.g. the position of outer boom.
The inner boom and outer boom indicators (option on
certain cranes) give the position of the inner boom and
outer boom. The slewing sector indicators (option on
certain cranes) give information of slewing position of
the crane.
Sensors
A sensor gives an analogue signal, which correspond
to e.g. the pressure in the inner boom cylinder.
The pressure sensors register the pressures in the
inner boom and outer boom cylinders.
The spool sensors gives information of the position of
the spools.
2000-12-20
2.1 Overview
Dump valve
(Fig. 4)
The dump valve controls the oil flow:
When active, oil goes to the control valve
When inactive, i.e. without power, this flow stops and
all crane functions stop.
Signalling components
Fig. 4
2000-12-20
2.1 Overview
FUNCTION
SP
ACE Operating
SPACE
Principles
The purpose of this section is to give a brief overview of
the basic principles employed in the operation of the
SPACE system. It is not intended to be an accurate
description of a particular system, but a familiarisation
section for the engineer who has not worked with
SPACE before or one who has maybe not been in
contact with a full SPACE system for sometime.
Switch on
(Fig. 5)
SPACE is switched on by pressing the ON/OFF button
on the User interface.
If the button is pressed for more then 2 s when system
is switched on the lamp test is activated, as long as
the button is pressed all red LEDs light, when
released all red LEDs continue to light for 3 s then all
green LEDs light for 3 s.
ADC
10
70
-3
31
SPACE 3000
Fig. 5
2000-12-20
2.1 Overview
Beginning operation
(Fig. 6)
When operation begins with the movement of a control
valve lever, the spool sensor for the relevant spool
sends a signal to the Standard box. A signal is then
sent from the Standard box to the dump valve which
will open, allowing oil to enter the valve and the
hydraulic function to begin.
SPACE 3000
1070-325
ADC
Fig. 6
During operation
100%
90%
1070-314
(Fig. 7)
Whilst the crane is operating SPACE monitors signals
sent from the spool sensors, tilt indicators and pressure sensors. In the event of any of the signals moving
outside the pre-determined parameters set in SPACE,
a warning is given that the crane has reached 90% of
it's capacity the red LEDs 1-3 on the User interface
will flash. If operation continues to increase the loading
of the crane the signal to the dump valve will be
switched off and crane operation will cease. The red
LEDs 1-4 will be lit constantly. SPACE will now wait
for an operation command that will reduce the loading
on the crane and operation will restart automatically.
SPACE will not accept any command that will increase the loading of the crane once OLP has been
activated.
Fig. 7
2000-12-20
2.1 Overview
SP
ACE, system overview
SPACE,
This table shows the possible connections between
the four different crane types and control systems,
valves and remote controls.
Control System
Crane type
V50
V50 RD
CL
SPACE 3000
SPACE
DUO
SPACE 3000
SPACE
PRO
HI PRO
2000-12-20
V91
V91 CD 5000
SPACE 3000
SPACE 5000
2.2 Functions
2.2 Functions
Contents
General......................................................................................... 3
Functions ..................................................................................... 4
Overload protection (OLP) ................................................. 4
OLP Basic crane .................................................... 4
OLP Winch ............................................................. 5
OLP Manual extensions .......................................... 5
OLP Disconnection ................................................ 5
Automatic Duty Control (ADC) ................................ 6
Manual Speed Control (MSC) ................................. 6
Automatic Dumping of Oil (ADO) ............................ 7
Stability ............................................................................... 8
Slewing Sector ........................................................ 8
Fixed platform ......................................................... 9
Cabin warning ......................................................... 9
Automatic damping on slewing (ADS) .................... 9
2000-12-20
2.2 Functions
2000-12-20
2.2 Functions
GENERAL
This section contains functions that SPACE 3000 is
equipped with as a standard for the majority of cranes.
This section also describes a number of functions that
can be obtained with the accessories supplied by
HIAB and options that are only program possibilities in
SPACE 3000. HIAB has no standard solutions how to
apply sensors e.g.
Please contact HIAB for information of supply sources
of these components.
2000-12-20
2.2 Functions
FUNCTIONS
Overload protection (OLP)
OLP Basic crane
100%
90%
1070-314
Fig. 1
Fig. 2
2000-12-20
2.2 Functions
OLP Winch
When winch reaches 90% of permitted load the winch
LED on the User interface starts flashing. At 100%
load OLP cuts in, stopping load increasing movements. The LED has a steady red light until the
overload situation is over.
When the wire is almost completely unwound (three
turns left on drum) winch lowering is stopped. Operator
has to winch in to reverse situation.
ADC
-3
31
SPACE 3000
70
Fig. 4
10
OLP Disconnection
Fig. 5
2000-12-20
2.2 Functions
ADC
ADC
SPACE 3000
1070-335
(Fig. 6)
Automatic Duty Control (ADC) is a patent pending
function in SPACE 3000/5000.
The purpose of ADC is that the crane knows in which
type of lifting mode it is.
SPACE will automatically calculate the maximum
lifting capacity in each lifting mode so that the crane
will be used in an optimised way without any risk of
overloading the crane structure.
ADC is sensed by the spool sensor on the sixth lever
or if function winch is used.
If sixth lever or winch is used ADC will automatically be
chosen again after 60 seconds inactivity in these
functions.
ADC is automatically chosen at start up, which is
indicated by a LED on the user interface.
ADC increases the lifting capacity without any
reduction in lifting speed. In winch mode the lifting
capacity is increased.
Fig. 6
1070
-337
Fig. 7
2000-12-20
2.2 Functions
2000-12-20
2.2 Functions
Stability
Slewing Sector
When the truck has insufficient stability in a certain
sector, e. g. in front of the cabin indicators can be
fitted defining this sector (Fig. 8). The system is
programmed to allow only reduced load in the indicated sector. For load sensing inner boom cylinder
pressure is used.
1070-043
Fig. 8
NOTE!
For information how to set parameters
when using a special slewing sector
sector,, see
section 6.2 Settings.
2000-12-20
2.2 Functions
Fixed platform
(Fig. 9)
Fixed platform is known in some countries as Stand up
platform.
It is possible to connect this function to SPACE. It will
prevent the operator from slewing the boom into the
fixed platform or themselves.
Slewing sector, inner boom and outer boom angle
indicators are used to define permitted lifting areas
when operating the crane from fixed platform.
Fig. 9
Cabin warning
Signal in the cabin (normally a lamp) is possible if one
of following conditions is fulfilled:
the system is ON and the stop button is pulled out
the system is ON and tilt indicator indicates "UP"
the system is OFF and the tilt indicator indicated
"UP" when powering off (provided there is current to
the lamp kit).
Even if the truck battery has been disconnected when
the inner boom was positioned to high the system will
remember that and the lamp in the cabin will light up
when the driver start the truck again.
2000-12-20
10
2.2 Functions
2000-12-20
2.3 Components
2.3 Components
Contents
General......................................................................................... 3
Boxes and sensors ...................................................................... 4
Connection plinths ............................................................. 4
Grease ............................................................................... 4
Bar code signs ................................................................... 4
Connection diagram ........................................................... 5
CL/DUO crane ........................................................ 5
PRO crane ............................................................. 6
Standard box ...................................................................... 7
Function .................................................................. 7
Connection plinths .................................................. 8
Jumpers ................................................................ 10
User interface ................................................................... 11
Function ................................................................. 11
Buttons .................................................................. 11
Indicator LEDs ..................................................... 12
Connection plinths ................................................ 14
Jumpers ................................................................ 15
Column box ...................................................................... 16
Function ................................................................ 16
Connection plinths ................................................ 16
Extended box ................................................................... 18
Function ................................................................ 18
Connection plinths ................................................ 19
Operation ................................................................................... 20
Jumper settings ............................................................... 20
Channels and connection plinths ..................................... 21
Slewing sector indicators ................................................. 22
Function ................................................................ 22
2000-12-20
2.3 Components
2000-12-20
2.3 Components
GENERAL
This section contains components that SPACE 3000
is equipped with as a standard and also describes a
number of accessories supplied by HIAB for the
majority of cranes.
2000-12-20
2.3 Components
Connection plinths
The connection boxes in SPACE 3000 consist of a
case with several cable inlets and a cover that is
mounted with screws. Under the cover there are
different types of connection plinths depending on the
box type.
The connections are marked with e.g. P2.1, P2.2,
P2.3 in pictures and wiring diagrams (Fig 1).
P2 is the connection plinth.
.1 is plinth number 1 which normally is the first from
left seen from the cable side.
Grease
Fig. 1
2000-12-20
2.3 Components
Connection diagram
The connection diagrams is show example of a CL/
DUO crane (Fig. 3) and a PRO crane (Fig. 4).
Below the diagrams are component lists.
CL/DUO crane
Fig. 3
2000-12-20
2.3 Components
PRO crane
4
6
5
2
8
1
23
22
24
25
21
10
26
24 V 11
17
16
12
1070-321
20
19
15
14
13
18
Fig. 4
2000-12-20
2.3 Components
Standard box
Function
(Fig. 5)
The Standard box is the central unit of the system. It
supplies power to all the other units in the system. It
consists of two parts, a connection terminal board and
a display.
The Standard box distributes power to all the other
modules of the system. Nominal supply is 24 V DC,
but the system will be fully operational between
16V32V.
Fig. 5
2000-12-20
2.3 Components
Connection plinths
(Fig. 5)
Plinth
Description
P1
P3
P1.1
Ground
P3.1
Ground
P1.2
24 V
P3.2
24 V
P1.3
P3.3
Data out
P1.4
P3.4
Data in
P1.5
P1.6
P4
P2
P4.1
Ground
P2.1
Ground
P4.2
24 V
P2.2
24 V
P4.3
P2.3
P2.4
Fig. 5
2000-12-20
P5
P8
To horn
P5.1
Ground
P8.1
Ground
P5.2
24 V
P8.2
24 V ( 2 A)
P5.3
P9
To dump valve
P9.1
Ground
P9.2
24V
P10
Power in
P10.1
Ground to truck
P10.2
P5.4
P5.5
P5.6
P5.7
P5.8
P5.9
P6
P6.1
Ground
P6.2
24 V
P6.3
P6.4
P6.5
P6.6
P7
P7.1
Ground
P7.2
24 V
P7.3
CAN +
P7.4
CAN -
P7.5
P7.6
Emergency stop in
P7.7
On/off
2000-12-20
2.3 Components
NOTE!
Only plinth P10 shows the 24 V supply from
truck.
All other plinths show lower voltage
depending on a filtering unit between them
and P10.
2.3 Components
Jumpers
(Fig. 6)
In the Standard box the jumpers are located in the
lower centre of the box. There is one row with five
jumpers.
Fig. 6
10
2000-12-20
2.3 Components
User interface
Function
(Fig. 7)
The User interface is the communication centre of the
SPACE 3000. It gives information about the system
and is also where the user controls the system.
The User interface is mounted on the Standard box
and the extended box (if present). It can also be
mounted on an Empty box. Maximum four User
interfaces can be fitted on a crane.
Buttons
(Fig. 7)
1. Power On
Enables power to SPACE. If button is pressed for
more then 2 s when system is on the LED test is
activated, as long as the button is pressed all red
LED`s light, when released all red LED`s continue to
light for 3 s then all green LED`s light for 3 s.
Fig. 7
2. Release
Enables power to:
- OLP release if crane has OLP
- Dump valve/valves if not OLP, if Extended box
present also dump valve 2 (switched off after 10
minutes and when a crane function is used
dump valve 2 is always switched off).
3. Emergency stop
In danger the emergency stop button is pressed.
Power to the dump valve is cut and the crane stops.
The emergency stop button is to be turned
clockwise to reset.
4. Horn
Enables power to the horn if present.
5. Manual extension
Enables power to manual extension logic.
2000-12-20
11
2.3 Components
Indicator LEDs
4
5
6
10
ADC
1070-339
(Fig. 8)
The display consists of eight LED`s which indicates
button positions, errors, stability sector, winch etc.
For detailed information, see table below.
SPACE 3000
9 8
7
1. Power On, green
2. Stab sector, green
3. Service/error, green/red
4. Inner boom pressure, green/red
5. Winch, red
6. ADC, green
7. Manual extension, green
8. Release, red
9. Release, green
10. Outer boom pressure, green/red
Fig. 8
12
2000-12-20
2.3 Components
LED
State
Meaning
On
Flash
System is on.
An emergency stop button is depressed, dump power to
space is interrupted or no jumper is strapped in user
interface.
On
3. Service
Error
Green, on
Red, on
Red, flashing
Green LED 1 on
50 - 69 % of OLP pressure
70 - 89 % of OLP pressure
5. Winch, red
Flashing
On
Flashing fast
90 % of OLP pressure
100 % of OLP pressure
The outer boom is over a given angle when the system is
switched off.
6. ADC, green
On
8. Release, red
On
Flashing
OLP.
Release button pushed and allowed to run crane
(OLP case).
9. Release, green
On
Green LED 1 on
50 - 69 % of OLP pressure
70 - 89 % of OLP pressure
2000-12-20
13
2.3 Components
Connection plinths
(Fig. 9)
Plinth
Description
P1
P1.1
Ground
P1.2
24 V
P1.3
CAN +
P1.4
CAN -
P1.5
P1.6
Emergency stop in
P1.7
On/off
P2
P2.1
Ground
P2.2
24 V
P2.3
CAN +
P2.4
CAN -
P2.5
P2.6
Emergency stop in
P2.7
On/off
Fig. 9
14
2000-12-20
2.3 Components
Jumpers
(Fig. 10)
The jumpers are located in the higher right side of the
User interface. There is one row with five jumpers.
Fig. 10
2000-12-20
15
2.3 Components
Column box
Function
(Fig. 11)
This connection box is fitted to the crane column. All
the signals from the pressure sensors and indicators
(max. 7) on the boom system are collected in the box.
The Column box is connected to the SPACE box using
a 9-conductor cable.
Connection plinths
(Fig. 11)
P1
To Standard box
P1.1
Ground
P1.2
24 V
P1.3
P1.4
P1.5
P1.6
P1.7
P1.8
P1.9
Fig. 11
16
2000-12-20
P2
P2.1
Ground
P2.2
24 V to winch indicators
P2.3
2.3 Components
P4
P4.1
P4.2
P4.3
P2.4
Ground
P4.4
P2.5
P4.5
P4.6
P4.7
P4.8
P2.6
NOTE!
Outer boom fixed platform angle indicator
should be connected to P2.46 if no hydraulic extension in indicator is present in
system. If hydraulic extension in indicator is
present, outer boom fixed platform angle
indicator should be connected to P3.46
instead.
P3
P3.1
Ground
P3.2
P3.3
P3.4
Ground
P3.5
P3.6
NOTE!
P3.3 and P3.5 are connected in series.
2000-12-20
17
2.3 Components
Extended box
Function
(Fig. 12)
The Extended box is present if Space 3000 is
equipped with MSC, ADS or external dump.
There is a digit indicator (A) in the box which display a
number if an error should occur in the system and the
number of errors. To interpret these numbers there is
an error list.
Example: The digit 4 and a dot, followed by 03 without
a dot indicates that there are four errors and the
lowest number of these is no. 03.
If there are no errors the number 0 flashes.
There is a row with five jumpers in the Extended box.
NOTE
The jumpers are only for internal use and
should under no circumstances be
strapped.
Fig.12
18
2000-12-20
2.3 Components
Connection plinths
P1
To ADS valve
P7
P1.1
P7.1
Ground
P1.2
24 V (1 A)
P7.2
24 V
P7.3
CAN +
P2
P7.4
CAN -
P2.1
24 V
P7.5
P2.2
P7.6
Emergency stop in
P3
P3.1
24 V
P8
P3.2
P8.1
Ground
P8.2
24 V (2 A)
P9
P9.1
Ground
P9.2
24 V (2 A)
P10
P10.1
Ground
P10.2
24 V
P10.3
P1
1
P11
P11.1
Ground
P11.2
24 V
P4
P4.1
Ground
P4.2
24 V
P4.3
P5
P5.1
Ground
P5.2
24 V
P5.3
P5.4
P6
P6.1
Ground
P6.2
24 V
P6.3
CAN +
P6.4
CAN -
P6.5
P6.6
Emergency stop in
2000-12-20
19
2.3 Components
OPERA
TION
OPERATION
Jumper settings
The Standard box and the different User interfaces
must be configured in the correct way otherwise the
system will not function.
Fig.13
Fig.14
20
2000-12-20
2.3 Components
C 13
C 20
C 12
C 11
C 10
C 19
C9
C8
C 14
C 15
C 21 C 22
A
C5
C4
C3
C2
C1
C0
C 17 C 6
C7
1070-332
C 18
Fig.15
2000-12-20
21
2.3 Components
NOTE!
For information and settings, see section
Connecting accessories 6.1.
Spool sensor
1070
-342
(Fig. 17)
The spool sensors give information of the position of
the spools. There are two different spool sensors, one
for two spools and one for four spools. The sensors are
fitted directly on the valves.
NOTE!
For information and settings, see section
Settings 6.2.
22
Fig.17
2000-12-20
2.3 Components
Winch box
Function
The winch can be positioned on the loader body, inner
boom, outer boom, outer end of the crane, jib or the
outer end of the jib. OLP-logic is dependent on where
the winch is positioned.
The winch can have four indicators connected to a
special Winch box (Fig. 18) according to:
WTOP
WEND
WLOAD
WDIS
Fig. 18
2000-12-20
23
2.3 Components
Logic operation
The 2-tonne winch has a torque indicator, WLOAD (1)
and a switch for three turns remaining WEND (2) as
standard (Fig. 19).
Winches can also be equipped with a WTOP indicator
(hook near the boom) and a WDIS indicator (cable fully
wound in).
If the indicator WLOAD is active it is not possible to
wind the winch in.
If the indicator WTOP is active it is only possible to
wind the winch out.
If the indicator WEND is active it is only possible to
wind the winch in.
If the indicator WDIS is active you can only operate the
winch by pressing the emergency override button. This
will allow you to run the winch for about 20 seconds.
Press the button again to continue. Waiting time does
not apply as it does with normal override operation.
Normally the winch is controlled from the 5th valve
function. If the winch is to be controlled from another
function, parameter changes are demanded.
Fig. 19
NOTE!
For information and settings, see section 6.1
Connecting accessories.
Plug
If you disconnect the winch and instead connect a tool
to the winchs valve function you must connect a plug
in the contact on the cable which runs between the
SPACE system and the winch box. This plug tells
SPACE that the winch is disconnected and that the
function should be regarded as a tool (Fig. 20).
Fig. 20
24
2000-12-20
2.3 Components
Connection plinths
(Fig. 21)
To Column box
P1
P1.1
Ground
P1.2
24 V
P1.3
24 V
Px.3
Fig. 21
2000-12-20
25
26
2.3 Components
2000-12-20
2.4 Terminal
2.4 Terminal
Contents
Handheld PC ................................................................................ 3
Equipment needed for HIAB terminal ................................. 4
New Users .............................................................. 4
HP95/200 Users ..................................................... 4
Things to be aware of when using a handheld PC ............. 5
Battery Power ......................................................... 5
Time Bug ................................................................ 5
Memory Cards ........................................................ 5
Installation of HIAB Windows CE terminal programs ......... 6
What is needed? ..................................................... 6
Installation ............................................................... 6
Windows CE terminal functions ................................................... 7
Login .................................................................................. 7
Main menu ......................................................................... 7
Init ...................................................................................... 7
Init System Overview .............................................. 8
Init Auto ................................................................... 8
Init Type .................................................................. 11
Init Levers .............................................................. 11
Calibrate ................................................................ 11
Variables .......................................................................... 12
Detailed ................................................................. 13
User Interface ....................................................... 13
Extended ............................................................... 14
Errors ............................................................................... 15
Error Counters ...................................................... 15
Parameters ...................................................................... 16
Change Par Value ................................................. 16
2000-12-20
2.4 Terminal
File ................................................................................... 16
Counters .......................................................................... 17
Service log ............................................................ 17
Reset Counters .................................................... 17
Dos terminal ............................................................................... 18
General ............................................................................ 18
Init Auto ................................................................. 18
Variable list ....................................................................... 22
Variables ..................................................................................... 22
OLP ................................................................................. 24
MSC ................................................................................. 24
Analogue inputs................................................................ 25
Levers .............................................................................. 25
Pressure sensors ............................................................ 26
Digital inputs .................................................................... 26
Stability ............................................................................. 28
Various ............................................................................. 28
Timers ........................................................................................ 29
Timer list .......................................................................... 29
Parameters ................................................................................ 30
Parameter list .................................................................. 30
OLP ................................................................................. 32
MSC ................................................................................. 33
Pressure sensors ............................................................ 33
Digital inputs .................................................................... 34
Stability ............................................................................. 35
Service ............................................................................. 36
Various ............................................................................. 37
2000-12-20
2.4 Terminal
HANDHELD PC
A Handheld PC is a small computer that has Windows
CE as its operating system.
The Handheld PCs has a lot of advantages:
1. Easy to use. If you know Windows, then you are
already familiar with Windows CE.
2. Cheaper than a Laptop.
3. Communication with a PC through serial cable.
Files can be copied to the PC and stored there.
Update of the HIAB terminal program versions will
be easier.
Fig. 1
2000-12-20
2.4 Terminal
Handheld System
Handheld PC. Currently we support only Hewlett
Packard HP 680/690. Do not buy anything else but
these computers, since the programs depend very
much on the hardware of the Handheld PC,
especially the processor.
Handheld Interface 370 9426 from HIAB. Includes
Interface, diskette with Windows CE programs and
instructions.
HP95/200 Users
HIAB will continue to update the DOS programs to
work with the latest versions of Space boxes.
HP Interfaces 361 0888 and 367 3103 will remain as
spare parts.
2000-12-20
2.4 Terminal
Things to be aware of
when using a handheld PC
Battery Power
The Handheld PC does not get any power whatsoever
from the SPACE system, so it needs to have fully
charged batteries at all time.
The Handhelds have a feature that turns off the power
after between 15 minutes when on battery power. The
battery of a HP 690 lasts for 7-8 hours of continuous
use. If the battery is fully charged when starting a job
the battery power should not be a problem.
Charge the battery for the Handheld PC at all times
when it is not used, because if the battery is drained
all information is lost on the Handheld PC, and the
terminal programs must be reinstalled.
Battery is drained even if the Handheld PCs power is
switched off.
Fig. 2
Time Bug
Currently there is a time bug in Windows CE, when the
date is asked for in the programs the returned date
from Windows CE is incorrect.
Symptom:
S3000 CE.exe will not start due to an illegal year.
Wrong year in the file headers from files saved using
the HIAB terminal programs.
Solution:
Chose a city within USA when selecting Home City,
this cures the time problem. But set the date and time
to your date and time.
Memory Cards
HIAB will not sell memory cards for Handheld
systems. This is because the programs come on a PC
Diskette.
Handheld systems support the RAM cards that were
used for HP 95/200. An even better and cheaper
memory card is CompactFlash cards which have a
much higher storage capacity than RAM cards.
It is a good idea to put a backup of the terminal
programs onto a CompactFlash card so you dont
need to reinstall the HIAB terminal programs if the
battery is completely drained. Do also remember to
take backups of Crane.dat and Crane.s3d.
2000-12-20
2.4 Terminal
Installation of HIAB
Windows CE terminal
programs
What is needed?
A PC with Windows 95 or later.
A Handheld PC recommended from HIAB.
Installation programs. This comes with the Handheld
Interface as a PC Diskette.
Installation
This installation assumes that the program to install is
Space CE. Use the same procedure for the other
terminal programs.
1. Establish a connection between the PC and the
Handheld PC. Refer to the Handheld PC
manufacturers users guide for information regarding
this.
2. Insert the diskette labeled Handheld Installation
into the PC.
3. Copy Space CE.exe to a temporary folder on the
PCs hard drive.
4. Start the Space CE.exe that is now on the hard
drive. This will extract the installation files.
5. Start the newly extracted Setup.exe. Follow the
instructions on the screen.
6. When asked Install using default directory, answer
Yes.
7. Wait for the files to be installed on the Handheld
PC, this takes some time without any indication on
the screen, so be patient.
8. Ignore the error message saying that Space CE
was not installed successfully, remove it using add/
remove programs. This error message is wrong,
the installation is successful.
9. Space CE is now installed in the HIAB folder.
2000-12-20
2.4 Terminal
WINDOWS CE
TERMINAL FUNCTIONS
Login
(Fig. 3)
Type in your User ID and Password then
click on button OK.
Main menu
(Fig. 4)
At the top is the program version of the
Space 3000, and the program serial
number.
Below that, there is the crane serial
number and further down we have the
Crane Type.
Top right is your Access level, and below
is your Display level.
From access level Service its possible
to chose diplay level Diagnostic.
Fig. 3
Fig. 4
Init
(Fig. 5)
Here are all the Init Menus:
System Overview, Auto, Type, Levers and
Prog SerNo.
Fig. 5
2000-12-20
2.4 Terminal
Init Auto
Fig. 6
Sub menu 1
Slew Sector 1
Sector Type:
Platf 1 Low
Cap (%)
Slew Sector 2
Sector Type:
Cap (%)
Yes
No
OLP
60
Winch
60
ADS
Yes
No
Ext In Indicator
Yes
Manual Extension
Cap (%)
50
75
No
Pressure Settings (bar)
Height Warn
Yes
No
Cancel
IB
+2%
265
OB
+1%
273
OK
1070-365
Fig. 7
No sector:
No slewing sector sensor is present in
system.
OLP:
Is used when the crane has a stability
sector.
Stop:
Stops the crane when entering the
slewing sector.
2000-12-20
Slew Sector 1
Sector Type:
Platf 0 Low:
No tilt indicators for the Fixed Platform.
Platf 1 Low
Cap (%)
Slew Sector 2
Sector Type:
Cap (%)
Yes
No
OLP
60
Winch
60
ADS
Yes
No
Platf 1 Low:
One tilt indicator on the inner boom.
Platf 2 Low:
Tilt indicators for the Fixed Platform on
both inner and outer boom. The
indicators are not connected in series.
Ext In Indicator
Yes
Manual Extension
Cap (%)
50
75
No
Pressure Settings (bar)
Height Warn
Yes
No
Cancel
IB
+2%
265
OB
+1%
273
OK
1070-365
2.4 Terminal
Fig. 7
Platf 2S Low:
Tilt indicators connected in series for the
Fixed Platform on both inner and outer
boom.
This setting is only used when both
platform indicators are connected to
plinth P3 in Column box.
Cap (%):
Only used if the sector is set as OLP,
and sets the capacity of the inner boom
pressure when crane is in the slew
sector.
Winch
(Fig. 7)
Yes & No. Tells SPACE 3000 if Winch is
mounted or not.
Ext In Indicator
(Fig. 7)
Yes & No. Tells SPACE 3000 if a
hydraulic extension in indicator is
mounted or not.
ADS
(Fig. 7)
Yes & No. Tells SPACE 3000 if ADS is
mounted or not.
2000-12-20
Slew Sector 1
Sector Type:
Platf 1 Low
Cap (%)
Slew Sector 2
Sector Type:
Cap (%)
Yes
No
OLP
60
Winch
60
ADS
Yes
No
Ext In Indicator
Yes
Manual Extension
Cap (%)
50
75
No
Pressure Settings (bar)
Height Warn
Yes
No
Cancel
IB
+2%
265
OB
+1%
273
OK
1070-365
Height Warn
(Fig. 7)
If the crane has a tilt indicator on the
inner boom this option will be set to Yes,
whether you have a Height Warning kit or
not. The program checks if the crane is
equipped with an M-Link, which needs an
inner boom tilt indicator. Which means
that if you have selected the correct
Crane Type in InitType, then the program
will not remove the inner boom setting if
you selected No and have an M-Link.
2.4 Terminal
Fig. 7
Manual Extension
(Fig. 7)
Sets the capacity when Manual
extension is selected on the User
Interface. The first value (should be the
lowest value) is used when the hydraulic
extensions are fully in or if no ext_in
sensor is connected and the second
value (higher) when the hydraulic
extensions are out.
10
2000-12-20
2.4 Terminal
Init Type
Sub menu 1
(Fig. 8)
Sets parameters for the selected crane
type. Click select to set the parameters.
Button File is only used if more than one
Crane.dat file is used
.
Fig. 8
Init Levers
Sub menu 1
(Fig. 9)
This menu can be used for three things;
Firstly to check if the calibration of the
levers was good or not. Move the lever on
the valve and see that the sliders on the
screen will move appropriately. Secondly
you can also see if the correct function is
connected to this lever, the name of the
function is above the slider. Third, see if
the correct functions are used for this
crane. The Terminal checks parameter
lev_ad_chan to see what functions are
used, and then only shows those functions on the screen. To calibrate the
levers press button Calibrate.
Fig. 9
Calibrate
Sub menu 2
(Fig. 10)
Follow the instructions on the screen
when calibrating the levers. To skip a
Tool lever press button Skip Lever. To
abort calibration press Back. You dont
have to press any key during calibration
just follow the commands on the screen.
As opposed from the DOS version where
you have to press Enter after every
command.
2000-12-20
Fig. 10
11
2.4 Terminal
Variables
(Fig. 11)
This display is called the Summary display.
Here you can read off several variables simultaneously.
Here you can do a lot of troubleshooting by viewing the information from the variables.
Slew
Inner Boom
Outer Boom
Extension
Winch
Tool 1
Tool 2
Tool 3
Pressure
Lim
%
26
104
109
0
100
0
MPa
t0 l0 e0 d0
Lev %
0
-43
0
100
0
0
0
0
0
0
Max +
100
0
0
100
100
100
100
100
100
100
Max 0
50
50
100
100
100
100
100
100
100
Tilt
up
Sect
-1,0
down
Platform
in
up
down
off
Extended
Detailed
User Interface
Back
Fig. 11
1 Winch
2 Pressure MPa Shows current working pressure in inner and outer boom in MPa (ib_p_mom and ob_p_mom).
%
Shows current working pressure in inner and outer boom in % of maximum pressure (ib_p_filt
and ob_p_filt).
Lim Shows maximum permitted working pressure in inner and outer boom in %.
The value is normally 100 but can be higher if ADC and/or MSC is activated. If manual
extension or an OLP slewing sector indicator is activated the value is lower than 100.
(ib_olp_lim and ob_olp_lim).
3 Lev %
4 Max +
Max -
Shows maximum permitted spool stroke in % of full stroke for each function and
direction. 0 means that the movement is stopped (max_speed_p and max_speed_n).
5 Tilt
12
2000-12-20
6 Sect
2.4 Terminal
Sect shows one sector value if only one slewing sector is set for this crane, otherwise it will show
both sector values. (stab_sects)
7 Platform Platform is the indicators for the Fixed Platform. From the top of this box and down we have:
In or Out of the Fixed Platform slewing sector.
Inner boom Fixed Platform tilt indicator up or down.
Outer boom Fixed Platform titl indicator up or down.
On, if there is a person on the Fixed Platform, otherwise Off.
(stand_ib_low, stand_ob_low and stand_on)
Detailed
Sub menu 1
(Fig. 12)
Select variable class and then select
variable. The variable value will now be
shown in the variable value box.
Fig. 12
User Interface
Sub menu 1
(Fig. 13)
Translates the variable cov_stat file to
plain text. Here you can see the status
of the User Interfaces of the system.
Only the UIs that are connected are
shown. The status is shown with simple
Yes/No answers.
Fig. 13
2000-12-20
13
2.4 Terminal
Extended
Sub menu 1
(Fig. 14)
Translates the variable ext_stat file to
plain text. Here you can see the status
of the Space 3000 Extended box, if one
is connected to the system. The following text strings can be shown:
- Input from Extended Slewing Sector
positive
- Input from Extended Slewing Sector
negative
Fig. 14
14
2000-12-20
2.4 Terminal
Errors
(Fig. 15)
Shows current Errors in Space. The
errors are continuously updated from
Space. Button Clear Errors is used to
tell Space to clear the errors manually. If
the error still persists then it is not
cleared, otherwise it is cleared. Most
errors are cleared when the reason for
the error disappears.
Button Error Count will take you to error
counters.
Fig. 15
Error Counters
Sub menu 1
(Fig. 16)
Shows a count of all errors in this Space
box since it was produced. Press button
Reset to reset the right column of the
error counters. This can be used to
check what kind of errors that have
occurred since the last time the crane
was in a workshop.
Fig. 16
2000-12-20
15
2.4 Terminal
Parameters
(Fig. 17)
This is where you can check and set
parameter values. Select parameter
class and then a Parameter. When a
parameter is selected its value will be
shown in the Parameter Value box. To
change a parameter click button
Change Par Value or double click on
the parameter name.
Fig. 17
Fig. 18
File
(Fig. 19)
Load, loads a coded parameter file (.sav)
that was saved with the Save button.
Save As Text saves parameters,
counters, diary and error counters to a
file as text. This file can be opened later
with any text editor (Word, Notepad
etc.). Save As Code saves all data from
this Space box to a coded file. This file
cannot be viewed with a text editor. The
purpose of this coded file is to get a
complete picture of what this crane has
been doing and its settings. Can only be
viewed by certain personnel at HIAB.
16
Fig. 19
2000-12-20
2.4 Terminal
Counters
(Fig. 20)
Shows counter and timer values. This
menu is continuously updated from
Space, so if a timer has a new value it is
automatically updated.
Fig. 20
Service log
Sub menu 1
(Fig. 21)
In access level Diagnostic it is possible
to view the Service log by clicking on
Yes.
This question will not appear in access
level Service.
23:31
40
1950:12
986:45
56:52
14:23
Back
1070-367
Service
Fig. 21
Reset Counters
Sub menu 2
(Fig. 22)
Click on Yes to reset Service counters.
NOTE!
For more information about
timer and counter settings, see
section 5.1 Service.
23:31
40
1950:12
986:45
56:52
14:23
Back
1070-366
Service
Fig. 22
2000-12-20
17
2.4 Terminal
DOS TERMINAL
General
This section only describes the Init Auto menu in DOS.
The Init Auto menu is the menu that differs most from
Windows CE.
For more information about the DOS terminal and the
different menus, see SPACE service manual.
Init Auto
Sub menu 1
Navigation in menu:
%, & = Move between parameters.
ENTER = Change between values.
Inner or Outer Boom Pressure Limits
Sets ib_p_lim_corr and ob_p_lim_corr.
The display shows inner and outer boom
pressure. Type correction values if needed
and press ENTER to update values.
Slewing Sectors
(Fig. 23)
Here you set which slewing sectors that are
present in the system. It is possible to have
two slewing sectors.
You can choose from:
- NO
- OLP
- STOP
- PLATF0
- PLATF1
- PLATF2
- PLATF2S
Fig. 23
18
2000-12-20
2.4 Terminal
NO:
No slewing sector sensor is present in system.
OLP:
Is used when the crane has a stability sector. If OLP is
chosen the capacity (%) of the inner boom pressure
when crane is in the slewing sector should be set in
line below OLP.
STOP:
Stops the crane when entering the slewing sector.
PLATF is for Fixed Platform and the number tells how
many tilt indicators are used for the Fixed Platform.
PLATF0:
No tilt indicators for the Fixed Platform.
PLATF1:
One tilt indicator on the inner boom.
PLATF2:
Tilt indicators for the Fixed Platform on both inner and
outer boom. The indicators are not connected in
series.
PLATF2S:
Series connected tilt indicators for the Fixed Platform
on both inner and outer boom.
This setting is only used when both platform indicators
are connected to plinth P3 in Column box.
2000-12-20
19
2.4 Terminal
Winch
(Fig. 24)
YES & NO. Tells SPACE 3000 if a winch
is mounted or not.
Fig. 24
ADS
(Fig. 24)
YES & NO. Tells SPACE 3000 if ADS is
mounted or not.
20
2000-12-20
2.4 Terminal
Fig. 25
Fig. 26
2000-12-20
21
2.4 Terminal
VARIABLES
Variable list
S=Service
D=Diagnostic
NOTE!
Display
Variable name
Description of variables
?b_olp_lim
OLP
olp_rel_w_ctr
These variables show the present OLP activating pressure for the inner or
outer boom (in % of the working pressure ib_p_lim and ob_p_lim).
This variable shows the number of seconds that remains until the OLP
release mode can be activated again.
MSC
D
D
D
?b_msc_on
mm_active
mm_off_?cnt
anin
st_anin
These variables contain the raw data from the analogue inputs.
A value of 0 corresponds to a input voltage of 0 V or a current of 0 mA.
The full scale value is 255 and corresponds to a input voltage of +5 V or
current of 22.7 mA.
This is a special version of the analogue inputs variable. This variable
contains all the Standard Box physical analogue inputs.
Levers
lever
This variable shows the lever position [%]. Should correspond to the
amount of oil that flows trough the valve.
Pressures
sensors
?b_p_filt
?b_p_mom
?b_tilt
These variables show the actual state of the inner or outer boom tilt
indicator (0 = down, 1 = up, -1 = not connected).
digin
This variable shows the state of the eight voltage supervision signals.
ext_in_inp
This variable shows the actual state of the crane hydraulic extensions in
input.
(0 = extension in, 1 = extension out, -1 = not in use)
Digital inputs
Analogue
inputs
Class
22
2000-12-20
Various
Stability
Digital inputs
Class
2.4 Terminal
Display
Variable name
Description of variables
lo_load_inp
This variable shows the actual state of the crane capacity reducing input
(0 = off, 1 = on, -1 = not connected).
man_ext_sel
stand_?b_low
These variables show the actual state of the stand platforms inner or
outer boom too low indicator
(0 = low, 1 = high, -1 = not connected).
stand_on
This variable shows the actual state of the person on platform indicator
(0 = off, 1 = on, -1 = not connected).
voltin
This variable shows the state of the eight digital input pins.
wdis
This variable shows the actual state of the winch disabled signal
(0 = off, 1 = on, -1 = not connected).
wend
This variable shows the actual state of the winch 3 coils left indicator
(0 = off, 1 = on, -1 = not connected).
wload
This variable shows the actual state of the winch overload indicator
(0 = off, 1 = on, -1 = not connected).
wtop
This variable shows the actual state of the winch top position indicator
(0 = off, 1 = on, -1 = not connected).
stab_?
These variables show the current status of the slewing sector indicators
(negative and positive for three different sectors).
stab_sect
This variable shows the combined (worst case) status of the slewing
sectors.
stab_sects
apo_ctr
This variable shows the time (minutes) left to the Automatic Power Off.
max_speed_?
These variables show the actual maximum permitted speed [%] for each
function in both directions (negative and positive).
2000-12-20
23
2.4 Terminal
OLP
ib_olp_lim
ob_olp_lim
display: S
These variables show the present OLP activating pressure for the inner or outer boom (in % of
the working pressure ib_p_lim and ob_p_lim).
This value is normally 100, but changes according to MSC status, Multi -Mode, stability
conditions and so on.
olp_rel_w_ctr
display: S
This variable shows the number of seconds that remains until the OLP release mode can be
activated again.
MSC
ib_msc_on
ob_msc_on
display: D
These variables show if the MSC is active or not.
mm_active
display: D
This variable shows in which Multi Mode the crane currently is.
The modes are:
0
Tool Mode (Basic capacity)
1
Hook Mode (mm_?b_olp_add[0] capacity used, typically +10%)
2
Winch Mode (mm_?b_olp_add[1] capacity used, typically +5%)
mm_off_lcnt
mm_off_tcnt
display: D
These variables show how many lifts (mm_off_lcnt) or how many seconds (mm_off_tcnt)
remain until the Multi Mode returns to hook mode.
24
2000-12-20
2.4 Terminal
Analogue inputs
anin
display: S
These variables contain the raw data from the analogue inputs.
A value of 0 corresponds to a input voltage of 0 V or a current of 0 mA.
The full scale value is 255 and corresponds to a input voltage of +5 V or current of 22.7 mA.
st_anin
display: D
This is a special version of the analogue inputs variable. This variable contains all the
Standard Box physical analogue inputs (not even channel number related).
Levers
lever
display: D
This variable shows the lever position [%]. Should correspond to the amount of oil that flows
through the valve.
2000-12-20
25
2.4 Terminal
Pressure sensors
ib_p_filt
ob_p_filt
display: S
These variables show the filtrated relative pressure [%].
?b_p_mom
display: S
This variable shows the actual momentan pressure in bars.
Digital inputs
ib_tilt
ob_tilt
display: S
These variables show the actual state of the inner or outer boom tilt indicator
(0 = down, 1 = up, -1 = not connected).
digin
display: D
This variable shows the state of the eight voltage supervision signals:
Bit
0
1
2
3
4
5
6
7
Dec
1
2
4
8
16
32
64
128
Name
DIGIN_0
DIGIN_1
DIGIN_2
DIGIN_3
STRAP_0
STRAP_1
STRAP_2
STRAP_3
Terminal
P5:9
P4:3
P6:5
P6:6
P11:5
P11:4
P11:3
P11:2
ext_in_inp
display: S
This variable shows the actual state of the crane hydraulic extensions in input
(0 = extension in, 1 = extension out, -1 = not in use)
lo_load_inp
display: S
This variable shows the actual state of the crane capacity reducing input
(0 = off, 1 = on, -1 = not connected).
man_ext_sel
display: S
This variable shows whether manual extensions are selected or not (selected with the manual
extension switch on the User Interface).
If a Hydraulic extension in indicator is connected, this variable can also get the value 2 which
means that manual extension are selected, but the crane extensions are out (ext_in_inp = 0)
which means use the higher man_ext_load[1].
26
2000-12-20
stand_ib_low
stand_ob_low
2.4 Terminal
display: D
These variables show the actual state of the stand platforms inner or outer boom too low
indicator
(0 = low, 1 = high, -1 = not connected).
stand_on
display: D
This variable shows the actual state of the person on platform indicator
(0 = off, 1 = on, -1 = not connected).
voltin
display: D
This variable shows the state of the eight digital input pins:
Bit
Dec
Name Terminal
0
1
1
2
VBHORN
V24TERM
2
3
4
5
6
7
4
8
16
32
64
128
Used for
wdis
display: S
This variable shows the actual state of the winch disabled signal
(0 = off, 1 = on, -1 = not connected).
(wdis is activated when the inputs for both wend and wtop are activated at the same time).
wend
display: S
This variable shows the actual state of the winch 3 coils left indicator
(0 = off, 1 = on, -1 = not connected).
wload
display: S
This variable shows the actual state of the winch overload indicator
(0 = off, 1 = on, -1 = not connected).
wtop
display: S
This variable shows the actual state of the winch top position indicator
(0 = off, 1 = on, -1 = not connected).
2000-12-20
27
2.4 Terminal
Stability
stab_n
stab_p
display: S
These variables show the current status of the slewing sector indicators (negative
and positive for three different sectors).
stab_sect
display: S
This variable shows the combined (worst case) status of the slewing sectors. A zero
means that the crane is not in any sector. -1 means that the crane has entered a restricted
sector in the negative direction and +1 that the sector is entered in the positive direction. 2
means that the entering direction is unknown or that two conflicting sectors are active.
stab_sects
display: S
This variable shows the status of the slewing sectors. A zero means that the crane is
out of the restricted sector. -1 means that the sector has been entered in the negative
direction and +1 that the sector is entered in the positive direction. 2 means that the entering
direction is unknown (indicator error or conflict with the valve position)
Various
apo_ctr
max_speed_n
max_speed_p
28
display: D
This variable shows the time (minutes) left to the Automatic Power Off.
display: D
These variables show the actual maximum permitted speed [%] for each function in both
directions (negative resp positive). These values reflects the status of the MSC, the different
OLPs and the LO_SPEED errors.
2000-12-20
2.4 Terminal
TIMERS
Timer list
NOTE!
In this manual all timers are written in plain
style.
S=Service
D=Diagnostic
Diplay
Timer name
Description of timer
dump_time
This timer counts how many minutes the dump valve output has been on.
ib_OLP_ctr
ob_OLP_ctr
These timers counts how many times an inner boom or outer boom OLPsituation has occurred in the system.
ib_prewarn_ctr
This timer counts how many times the inner boom pre-warning pressure
level has been reached.
lift_ctr
This timer counts how many lifts have been done with the crane.
man_ext_ctr
This timer counts how many time the Manual Extension or lo_load logic
is activated.
man_ext_time
This timer counts how many minutes the crane has been used with
Manual Extensions selected at the User interface or with the lo_load_inp
active.
OLP_rel_ctr
This timer counts how many times the OLP release function has been
used.
srvc_lifts_left
This timer counts down how many lifts are left until the next service.
srvc_tot_time_left
This timer counts how many tot_time minutes are left until the next
service.
srvc_use_time_left
This timer counts how many use_time minutes are left until the next
service.
stab_OLP_ctr
This timer counts how many times an inner boom OLP situation has
occurred because of some slewing sector limitation.
tot_time
This timer counts how many minutes the power has been on to the
Standard box.
use_time
This timer counts how many minutes the crane has been used (lever not
centred and oil not dumped).
wi_OLP_ctr
This timer counts how many times the winch overload indicator (wload)
has been activated.
2000-12-20
29
30
on platform
indicator
P1.5
P5.6
Ext-P10.3
extra sensor
C3
C18
tilt
indicator (ib)
B3
C10
spool sensor 3
A3
C2
P1.6
P5.5
not currently
used
C4
tilt
indicator (ob)
B4
C11
spool sensor 4
A4
C3
P2.3
P5.4
not currently
used
C5
pressure
sensor (ob)
B5
C12
spool sensor 5
A5
C4
P2.4
P5.3
240
240
not currently
used
C6
pressure
sensor (ib)
B6
C13
spool sensor 6
A6
C5
Ext-P5.3
P6.3
B8
C15
P6.4
A8
C7 Ext-P5.4
spool sensor 8
16
0
240
255
not currently
used
C7
16
0
240
255
not currently
used
C8
B7
C14
spool sensor 7
A7
C6
Note: On program versions 1.1---1.22 values may be displayed in boxes C4 and C6. Ignore these values they have no relevance to anin [19].
hydraulic
extension in
indicator
Ext-P4.3
C2
C17
C1
C16
P5.9
Winch indicators
P5.7
Second tilt
indicator (ib)
platform logic
P5.8
B2
C9
P1.4
B1
C8
A2
C1
spool sensor 2
P1.3
spool sensor 1
A1
C0
Analogue inputs
2000-12-20
2000-12-20
2.4 Terminal
31
2.4 Terminal
PARAMETERS
Parameter list
Access
Display
S=Service
D=Diagnostic
mlink_mode
olp_lim
This parameter sets the default OLP limit pressure for inner and
outer boom OLP systems
prew_horn_on
This parameter sets how many times the horn should beep
when the crane load reaches the pre-warning level.
prew_horn_time
w_top_?
msc_act_mode
msc_rel_mode
?b_p_lim_corr
stop_tool_?_load
ext_in_chan
ib_tilt_chan
This parameter sets the channel number for the inner boom tilt
indicator.
lo_load_inp_chan
Parameter name
Digital inputs
Pressure
sensors
MSC
OLP
Class
32
NOTE!
Description of parameters
2000-12-20
Display
Stability
Digital inputs
Class
lo_load_inp_load
The inner boom capacity is limited to this value [%] when the
lo_load_inp_chan is set and the lo_load_inp variable is off.
man_ext_load
The inner boom capacity is limited to this value [%] when the
manual extension mode is selected on User interface.
stand_?b_low_chan
These parameters set the channel number for the inner and
outer boom tilt indicators for the fixed platform.
stand_on_chan
stab_?_chan
These parameters set the channel number for the two slewing
sector indicators negative or positive side.
stab_olp
This parameter sets the level (in %) to which the inner boom
OLP pressure limit will reduce when the slewing is inside an
OLP_SECT restriction sector.
stab_sect_type
Parameter name
Description of parameters
Service
0 OLP_SECT
2 STND_SECT
Various
2.4 Terminal
Access
srvc_lifts
srvc_tot_hours
srvc_use_hours
ads_mode
apo_time
dump_time
password
2000-12-20
33
2.4 Terminal
OLP
mlink_mode
olp_lim
prew_horn_on
access: D
display: D
limits: 0..255
default: 22
These parameters contains a bit pattern that describes which functions will be stopped in the
negative (w_top_n) or positive (w_top_p) directions when the winch top switch indicator is
activated.
34
2000-12-20
2.4 Terminal
MSC
msc_act_mode
msc_rel_mode
1: Non-limiting
2: Zero-pos.
The MSC is activated only when all levers are centred. This means that
when the crane load increases, you will first get an OLP at the crane
nominal capacity (100%). When you center the levers, the MSC will be
activated (also limiting the valve spool strokes) and the crane capacity will
increase with ??_msc_olp_add %.
Pressure sensors
ib_p_lim_corr
ob_p_lim_corr
2000-12-20
35
2.4 Terminal
Digital inputs
ext_in_chan
access: D
display: D limits: -1..24
default: -1
This parameter sets the channel number (usually 19) for the crane hydraulic extension in
indicator (used to give a higher manual extension load when the crane extensions are out).
ib_tilt_chan
access: S
display: S limits: -1..18
default: -1
This parameter sets the channel number for the inner boom tilt indicator.
lo_load_inp_chan
access: D
display: D limits: -1..24
default: -1
This parameter is a digital input with which the crane capacity can be reduced.
lo_load_inp_load
access: D
display: D limits: 0..100
default: 50
The inner boom capacity is limited to this value [%] when the lo_load_inp_chan is set
(? 1) and the lo_load_inp variable is off (? 1).
man_ext_load
access: D
display: D limits: 0..100
default: 50, 75
The inner boom capacity is limited to this value [%] when the manual extension mode is
selected on User interface. The first value (should be lower) is used when the crane
hydraulic extensions are in (ext_in_inp = 1) or no ext_in indicator is connected
(ext_in_chan = -1) and the second value (higher) when the crane extensions are out
(ext_in_inp = 0).
stand_ib_low_chan access: D
display: D limits :-1..24
default: -1
stand_ob_low_chan
These parameters set the channel number for the inner or outer boom angle indicators for
the stand platform.
stand_on_chan
36
access: D
display: D limits: -1..24
default: -1
This parameter sets the channel number for the person on platform indicator.
2000-12-20
2.4 Terminal
Stability
stab_n_chan
stab_p_chan
access: D
display: D
limits: -1..24
These parameters set the channel number for the two slewing sector indicators, negative
or positive side.
stab_olp
stab_sect_type
2000-12-20
37
2.4 Terminal
Service
srvc_lifts
srvc_tot_hours
srvc_use_hours
38
2000-12-20
2.4 Terminal
Various
ads_mode
apo_time
dump_time
password
2000-12-20
39
40
2.4 Terminal
2000-12-20
3 Delivery settings
3 Delivery settings
Contents
Connection of a 24 V power supply to SPACE 3000 .................... 3
Connection of a oil cooler................................................................3
Initiation of the system ................................................................. 4
Load and Stability tests ................................................................ 5
Adjustments for load and stability testing ........................... 5
Raising the OLP limit ......................................................... 5
Windows CE terminal ............................................. 6
DOS terminal .......................................................... 7
2000-12-20
3 Delivery settings
2000-12-20
3 Delivery settings
CONNECTION OF A
24 V POWER SUPPLY
All new cranes are supplied with an 8-metre power
supply cable connected to the SPACE 3000 standard
box.
Connect this cable to a 15 A power output provided by
the truck manufacturer.
If the cable needs to be replaced with a longer cable
the minimum cable area is 2.25 mm.
CONNECTION OF A OIL
COOLER
With SPACE 3000 it is not possible to connect an oil
cooler to the control system power supply as a MPCB
box is not used.
The oil cooler power supply must be connected
directly to the truck electrical system using a suitable
fused 15amp-connection point. All connections at the
oil cooler are made at the factory and the connection
cable is attached to the crane for transport.
Before starting the crane, make sure that the transport
protection plate is removed from the oil cooler. It is
secured by 4 plastic ties. Rapid Overheating of the oil
will occur if this plate is not removed.
2000-12-20
3 Delivery settings
INITIATION OF THE
SYSTEM
All the basic settings in SPACE 3000 are made at the
factory and no further adjustments are necessary.
NOTE!
If accessories have been fitted to the crane
during installation refer to section 6.1
Connecting accessories for connection and
setting details.
2000-12-20
3 Delivery settings
2000-12-20
3 Delivery settings
Windows CE terminal
1. Connect a HP Jornada terminal to
SPACE.
2. Type User Name and Password, click
on OK and the Main menu is displayed.
3. Select Parameters from Main menu.
4. Select OLP in the Class window.
5. Select Olp_lim in the Parameter
window (Fig. 1).
6. Click on Change Par Value.
7. Type in 130, click on OK and the
display returns to previous display
(Fig. 2).
Fig. 1
olp_lim
150
Service
50
1070-382
130
Fig. 2
2000-12-20
3 Delivery settings
DOS terminal
1. Connect a HP 95 terminal or a 200
model of Handheld PC to SPACE.
SPACE-3000 v1.20/Nov 20 2000/n:125
olp_horn_time
prew_horn_on
SELECT
1070-383
Min: 50
Max: 150
1070-384
Fig. 4
2000-12-20
3 Delivery settings
2000-12-20
2000-12-20
2000-12-20
GENERAL
1070-340
2000-12-20
Troubleshooting
organization
Check especially:
connectors for bad contact, contact resistance and
oxidation
cables to sensors, indicators and boxes for damage.
4. No error is found
Select COUNT/Error Count. Reset error counter in
right column by selecting RESET/Reset
RESET/Reset.
Ask the customer to come back if the error symptom
occurs again.
2000-12-20
Fig. 1
2000-12-20
2000-12-20
4.2 Troubleshooting
4.2 Troubleshooting
Contents
How to use troubleshooting .......................................................... 4
E0: Supply voltage to Standard box too low ................................. 6
E1: Voltage feed to sensors too low ............................................. 8
E2: Voltage feed to dump valve too low ...................................... 12
E3: Emergency button pushed in ............................................... 14
E4: Error in dump valve circuit ................................................... 18
E5: Error in emergency chain .................................................... 20
E6: Supply voltage to Column box too low ................................. 24
E7: Supply voltage to terminal too low ........................................ 36
E8: Supply voltage to CAN-bus too low ...................................... 38
E9: Voltage feed to horn too low ................................................. 44
E10: Extended box error ............................................................ 46
E11, E20, E27, E28, E29, E30: Internal error ............................. 50
E12, E13, E14, E15: Spool sensor signal too low or to high ...... 52
E16, E17: Spool sensor signal too low or too high ..................... 54
E18, E19: Spool sensor signal too low or too high ..................... 56
E20: Inner boom fixed platform angle indicator,
signal too low or too high .................................................... 58
E21: Winch box, signal too low or too high ................................ 62
E22: Inner boom tilt indicator, signal too low or too high ............. 66
E23: Outer boom tilt indicator, signal too low or too high............ 70
E23: Outer boom tilt indicator, signal too low or too high............ 72
E24: Outer boom pressure sensor, signal too low or too high ... 74
E25: Inner boom pressure sensor, signal too low or too high .... 78
E31: Slewing sector 1, faulty signal ........................................... 82
E32: Slewing sector 2, faulty signal ........................................... 84
E33: Slewing sector 3, faulty signal ........................................... 86
E34: Winch, indicator error ........................................................ 88
2000-12-20
4.2 Troubleshooting
2000-12-20
2000-12-20
4.2 Troubleshooting
4.2 Troubleshooting
Condition:
E3 is set when the Standard box records that there is no voltage on connection P7.6 in Standard box.
Error reasons:
- Stop button pushed in
- Emergency stop chain is broken or shorted to ground
- Defective User interface
- Contact resistance in connections
4
Make sure that stop buttons are
not pushed in
8
6
7
9
User interface 1
Disconnect wire from P2.5.
Test for min. 15,0 V between P2.5
and P2.6
Connect wire to P2.5
User interface 2
Disconnect wire/strapping from
P2.5
Test for min. 15,0 V between P2.5
and P2.6.
Connect wire/strapping to P2.5
10
Finish
2000-12-20
4.2 Troubleshooting
Description of troubleshooting
charts
1. Error code headline
Gives information about error code number, component and signal status
2. Condition
Gives information under which conditions that
SPACE sets an error code.
3. Error reasons
Gives information about possible error reasons. The
most likely is placed first.
4. Rectangle
A rectangle gives information about what to check,
disconnect, measure etc.
5. C
ircle with a number
Circle
A picture on the opposite page with the same
number shows exactly where to measure in boxes
etc.
6. Thick arrow
A thick arrow shows the flow if measuring values etc.
are correct in the square.
Some troubleshootings will be continued on next
page.
7. Broken line arrow
A broken line arrow shows the flow if measuring
values etc. are incorrect in the square.
8. Rectangle with rounded corners
A rectangle with rounded corners gives information
about what action that has to be taken.
9. Thin arrow
A thin arrow shows the flow when an action has been
taken and the error is corrected.
10. H
exagon
Hexagon
The hexagon is the end of the troubleshooting.
Check crane according to 6 Final check of crane in
section 4.1 Troubleshooting organization.
2000-12-20
4.2 Troubleshooting
Standard box
Test for min. 16,0 V between
P10.1 and P10.2
Standard box
Remove fuse.
Test for min. 16,0 V in fuse holder
Replace fuse
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P10.1
P10.2
2000-12-20
4.2 Troubleshooting
E1: V
oltage feed to sensors too low
Voltage
Condition:
E1 is set when the Standard box records that voltage to sensors (connection P1, P2, P4 or P6 ) is below 15,0 V.
Error reasons:
- Voltage wire to a sensor shorted to ground
- Defective spool sensor
- Defective indicator on control platform
- Defective slewing sector indicator
Standard box
Disconnect wire from P1.2.
Clear errors.
Check if E1 is still active.
Connect wire to P1.2
Standard box
Disconnect wire from P2.2.
Clear errors
Check if E1 is still active.
Connect wire to P2.2
E2 is not active
Replace spool sensor no.
1-4 (P1)
E2 is not active
Replace spool sensor no.
5-6 (P2)
Finish
2000-12-20
4.2 Troubleshooting
Location
1
P2.2
P1.2
2000-12-20
4.2 Troubleshooting
E1: V
oltage feed to sensors too low
Voltage
Standard box
Disconnect wire from P4.2.
Clear errors
Check if E1 is still active.
Connect wire to P4.2
E1 is not active.
Disconnect control platform
sensor.
Clear errors.
Check if E1 is still active.
Replace cable if E1 is active.
Replace sensor if E1 is not
active
E1 is not active.
Replace defective slewing
sector sensor.
Replace cable between
Standard box P6 and slewing
sensors if E1 is still active
when all slewing sectors are
disconnected
Finish
10
2000-12-20
4.2 Troubleshooting
Location
3
4
P4.2
2000-12-20
11
4.2 Troubleshooting
E2: V
oltage feed to dump valve too low
Voltage
Condition:
E2 is set when the Standard box records that voltage to dump valve is below 15,0 V.
Error reasons:
- Voltage wire to dump valve shorted to ground
- Contact resistance in connections
- Defective dump valve
E2 is not active.
Replace dump valve.
E2 is active.
Check if P9.2 in Standard box is
shorted to ground.
Replace cable to dump valve if
no eror is found
Finish
12
2000-12-20
4.2 Troubleshooting
Location
1
P 9.2
2000-12-20
13
4.2 Troubleshooting
User interface 1
Disconnect wire from P2.5.
Test for min. 15,0 V between P2.5
and P2.6
Connect wire to P2.5
User interface 2
Disconnect wire/strapping from
P2.5
Test for min. 15,0 V between P2.5
and P2.6.
Connect wire/strapping to P2.5
14
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P2.6
P2.6
P2.5
2000-12-20
P2.5
15
4.2 Troubleshooting
Finish
16
2000-12-20
4.2 Troubleshooting
Location
3
4
P2.6
P7.6
P2.5
P7.5
2000-12-20
17
4.2 Troubleshooting
Resistance is incorrect.
Replace dump valve
Standard box
Disconnect wire from P9.2.
Measure resistance between the
wire and P9.1
Should be 20-100 .
Connect wire to P9.2.
Resistance is incorrect.
Replace cable to dump valve
Finish
18
2000-12-20
4.2 Troubleshooting
Location
1
2
9.2
P9.1
2000-12-20
19
4.2 Troubleshooting
User interface 1
Push in the emergency stop.
Disconnect wire from P2.6.
Test for max. 1,0 V between P1.1
and P1.6
Connect wire to P2.6.
Pull out the emergency stop
User interface 2
Push in the emergency stop.
Disconnect wire/strapping from
P2.6
Test for max. 1,0 V between P1.1
and P1.6.
Connect wire/strapping to P2.6.
Pull out the emergency stop
20
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P2.6
2000-12-20
P1.6
P1.1
P2.6
P1.6
P1.1
21
4.2 Troubleshooting
Finish
22
2000-12-20
4.2 Troubleshooting
Location
3
4
P2.6
P1.6
P1.1
P7.6
P7.5
2000-12-20
23
4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
Clear errors.
Check if E6 is still active.
Connect wire to P1.2
E6 is active.
Check if P5.2 in Standard box is
shorted to ground.
Replace cable to Column box if
no error is found
Column box
Disconnect wire from P4.1.
Clear errors.
Check if E6 is still active.
Connect wire to P4.1
E6 is not active.
Disconnect pressure sensor,
inner boom.
Clear errors.
Check if E6 is still active.
Replace cable if E6 is active.
Replace sensor if E6 is not
active
24
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P1.2
P4.1
2000-12-20
25
4.2 Troubleshooting
Column box
Disconnect wire from P4.3.
Clear errors
Check if E6 is still active.
Connect wire to P4.3
E6 is not active.
Disconnect pressure sensor,
outer boom.
Clear errors.
Check if E6 is still active.
Replace cable if E6 is active.
Replace sensor if E6 is not
active
Column box
Disconnect wire from P4.5.
Clear errors.
Check if E6 is still active.
Connect wire to P4.5
E6 is not active.
Disconnect tilt indicator, outer
boom.
Clear errors.
Check if E6 is still active.
Replace cable if E6 is active.
Replace indicator if E6 is not
active
26
Finish
2000-12-20
4.2 Troubleshooting
Location
3
4
P4.3
2000-12-20
P4.5
27
4.2 Troubleshooting
Column box
Disconnect wire from P4.7.
Clear errors.
Check if E6 is still active.
Connect wire to P4.7
28
E6 is not active.
Disconnect tilt indicator, inner
boom.
Clear errors.
Check if E6 is still active.
Replace cable if E6 is active.
Replace tilt indicator if E6 is
not active
Finish
2000-12-20
4.2 Troubleshooting
Location
Location
5
P4.7
2000-12-20
29
4.2 Troubleshooting
Column box
Disconnect wire from P2.2.
Clear errors.
Check if E6 is still active.
Connect wire to P2.2
E6 is not active.
Disconnect wire from P1.2 in
winch box.
Clear errors.
Check if E6 is still active.
Connect wire to P1.2
E6 is still active.
Replace cable betwen winch
box and Column box
E6 is not active.
Disconnect voltage supply
from P2.2 and winch indicators
one by one form P2.2, 3.2, 4.2
and 5.2 in winch box.
Clear errors before
disconnecting next indicator.
Check if E6 is still active.
E6 is not active.
Error cables to (Rotzler)
connection box, connection box or
indicator.
Troubleshoot according to
Crane Info 15.
E6 is still active.
Replace winch box
Finish
30
2000-12-20
4.2 Troubleshooting
Location
Location
6
P2.2
2000-12-20
31
4.2 Troubleshooting
Column box
Disconnect wire from P2.5.
Clear errors.
Check if E6 is still active.
Connect wire to P2.5
Column box
Disconnect wire from P3.2.
Clear errors.
Check if E6 is still active.
Connect wire to P3.2
32
E6 is not active.
Disconnect outer boom fixed
platform angle indicator.
Clear errors.
Check if E6 is still active.
Replace cable if E6 is active.
Replace indicator if E6 is not
active
E6 is not active.
Disconnect inner boom fixed
platform angle indicator.
Clear errors.
Check if E6 is still active.
Replace cable if E6 is active.
Replace indicator if E6 is not
active
Finish
2000-12-20
4.2 Troubleshooting
Location
Location
7
P3.2
P2.5
2000-12-20
33
4.2 Troubleshooting
Column box
Disconnect wire from P3.5.
Clear errors.
Check if E6 is still active.
Connect wire to P3.5
E6 is not active.
Disconnect hydraulic extension
in indicator..
Clear errors.
Check if E6 is still active.
Replace cable if E6 is active.
Replace indicator if E6 is not
active
Finish
34
2000-12-20
4.2 Troubleshooting
Location
Location
9
P3.5
2000-12-20
35
4.2 Troubleshooting
Disconnect terminal/handheld
computer.
Switch system off and on again
Check if E7 is still active by
looking at the display in standard
box
E7 is active.
Check that wires connected to
P3 are properly fixed and that
there is no dirt in terminal
connector.
Replace cable if no error is
found
Connect terminal/handheld
computer.
Switch system off and on again
Check if E7 is still active by
looking at the display in standard
box
E7 is active.
Error is in terminal/handheld
computer, interface or in
connection cables.
Finish
36
2000-12-20
2000-12-20
4.2 Troubleshooting
37
4.2 Troubleshooting
Standard box
Disconnect wire from P7.3 and
P7.4.
Clear errors.
Check if E8 is still active.
Connect wires to P7.3 and P7.4
E8 is active.
Replace Standard box
User interface 1
Disconnect wire from P1.3 and
P1.4.
Clear errors.
Check if E8 is still active.
Connect wires to P1.3 and P1.4
E8 is active.
Replace cable to Standard box
User interface 1
Disconnect wire from P2.3 and
P2.4.
Clear errors.
Check if E8 is still active.
Connect wires to P2.3 and P2.4
E8 is active.
Replace User interface 1
38
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P1.4
P7.4
P1.3
P7.3
3
P2.4
P2.3
2000-12-20
39
4.2 Troubleshooting
User interface 2
Disconnect wire from P1.3 and
P1.4.
Clear errors.
Check if E8 is still active.
Connect wires to P1.3 and P1.4
E8 is active.
Replace cable to User interface
1
User interface 2
Disconnect wire from P2.3 and
P2.4.
Clear errors.
Check if E8 is still active.
Connect wires to P2.3 and P2.4
E8 is active.
Replace User interface 2
E8 is active.
Replace cable to User interface
2
40
Finish
2000-12-20
4.2 Troubleshooting
Location
4
5
P1.4
P2.4
P1.3
P2.3
6
P1.4
P1.3
2000-12-20
41
4.2 Troubleshooting
E8 is active.
Replace User interface 3
E8 is active.
Replace cable to User interface.
E8 is not active.
Replace Extended box
Finish
42
2000-12-20
4.2 Troubleshooting
Location
7
8
P2.4
P6.3
P2.3
P6.4
2000-12-20
43
4.2 Troubleshooting
E9: V
oltage feed to horn too low
Voltage
Condition:
E9 is set when the Standard box records that voltage to horn is below 15,0 V.
Error reasons:
- Voltage cable to horn shorted to ground
- Vehicle battery voltage too low
- Defective horn
Standard box
Test for min. 16,0 V between
P10.1 and P10.2
E9 is not active.
Replace horn.
Disconnect horn.
Check if E9 is active.
Connect horn.
E9 is active.
Check if P8.2 in Standard box is
shorted to ground.
Replace cable to horn if no error
is found
Finish
44
2000-12-20
4.2 Troubleshooting
Location
1
2
P10.1
P8.2
P10.2
2000-12-20
45
4.2 Troubleshooting
No.
Set parameters correctly
Extended box
Check that wires connected to P6
are properly fixed
User interface 2
Check that wires connected to P2
are properly fixed
46
Finish
2000-12-20
4.2 Troubleshooting
Location
1
P6
P2
2000-12-20
47
4.2 Troubleshooting
Resistance is incorrect.
Replace cable between
Extended box and User
interface 2.
Resistance is correct.
Replace Extended box
Finish
48
2000-12-20
2000-12-20
4.2 Troubleshooting
49
4.2 Troubleshooting
E1
1, E20, E27, E28, E29, E30: Internal error
E11,
Condition:
E11, E20, E27, E28, E29 or E30 is set when the Standard box records an internal problem in processor or
programme.
Error reason:
- Error in processor or programme
Clear errors.
Run system
Finish
50
2000-12-20
2000-12-20
4.2 Troubleshooting
51
4.2 Troubleshooting
Standard box
Check that wires connected to
P1.1, 1.2, 1.3, 1.4, 1.5 and 1.6 are
properly fixed
Clear errors.
Run system
Finish
52
2000-12-20
4.2 Troubleshooting
Location
1
P1.6
P1.5
P1.4
P1.3
P1.2
P1.1
2000-12-20
53
4.2 Troubleshooting
Standard box
Check that wires connected to
P2.1, 2.2, 2.3 and 2.4 are properly
fixed
Clear errors.
Run system
Finish
54
2000-12-20
4.2 Troubleshooting
Location
1
P2.4
P2.3
P2.2
P2.1
2000-12-20
55
4.2 Troubleshooting
Extended box
Check that wires connected to
P5.1, 5.2, 5.3 and 5.4 are properly
fixed
Clear errors.
Run system
Finish
56
2000-12-20
4.2 Troubleshooting
Location
1
P5.2
P5.1
P5.4
P5.3
2000-12-20
57
4.2 Troubleshooting
Check if E6 is set
E6 is set.
Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P3.2.
Test for min. 14,5 V between
P3.2 and P3.3.
Connect cable to P3.2
58
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P3.3
P3.2
2000-12-20
59
4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
Test for min. 14,5 V between
the wire and P1.8.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
Test for min. 14,5 V between
P5.2 and P5.8.
Connect wire to P5.2
Finish
60
2000-12-20
4.2 Troubleshooting
Location
3
4
P1.2
P5.2
P5.8
P1.8
2000-12-20
61
4.2 Troubleshooting
Check if E6 is set
E6 is set.
Check voltage supply to
Column box according to E6
Winch box
Disconnect wire from P1.2.
Test for min. 14,5 V between
the wire and P1.3.
Connect wire to P1.2
Column box
Disconnect wire from P2.2
Test for min. 14,5 V between
P2.2 and 2.3.
Connect wire to P2.2
62
Finish
2000-12-20
4.2 Troubleshooting
Location
Location
1
1.2
P2.3
P2.2
P1.3
2000-12-20
63
4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
Test for min. 14,5 V between
the wire and P1.7.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
Test for min. 14,5 V between
P5.2 and P5.7.
Connect wire to P5.2
Finish
64
2000-12-20
4.2 Troubleshooting
Location
Location
3
4
P5.2
1.2
P5.7
P1.7
2000-12-20
65
4.2 Troubleshooting
Check if E6 is set
E6 is set.
Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.7.
Test for min. 14,5 V between
P4.7 and 4.8.
Connect wire to P4.7
66
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P4.8
P4.7
2000-12-20
67
4.2 Troubleshooting
Column box
Disconnect cable from P1.2.
Test for min. 14,5 V between
the wire and P1.6.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
Test for min. 14,5 V between
P5.2 and P5.6.
Connect wire to P5.2
Finish
68
2000-12-20
4.2 Troubleshooting
Location
3
1.2
4
P5.2
P5.8
P1.8
2000-12-20
69
4.2 Troubleshooting
Check if E6 is set
E6 is set.
Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.5.
Test for min. 14,5 V between
P4.5 and P4.6.
Connect wire to P4.5
70
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P4.6
P4.5
2000-12-20
71
4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
Test for min. 14,5 V between
the wire and P1.5.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
Test for min. 14,5 V between
P5.2 and P5.5.
Connect wire to P5.2
Finish
72
2000-12-20
4.2 Troubleshooting
Location
3
1.2
4
P5.2
P1.5
P5.5
2000-12-20
73
4.2 Troubleshooting
Check if E6 is set
E6 is set.
Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.3.
Test for min. 14,5 V between
P4.3 and P4.4.
Connect wire to P4.3
74
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P4.3
P4.4
2000-12-20
75
4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
Test for min. 14,5 V between
the wire and P1.4.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
Test for min. 14,5 V between
P5.2 and P5.4.
Connect wire to P5.2
Finish
76
2000-12-20
4.2 Troubleshooting
Location
3
1.2
4
P5.2
P1.4
P5.4
2000-12-20
77
4.2 Troubleshooting
Check if E6 is set
E6 is set.
Check voltage supply to Column
box according to E6
Column box
Disconnect wire from P4.1.
Test for min. 14,5 V between
P4.1 and P4.2.
Connect wire to P4.1
78
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2
P4.1
P4.2
2000-12-20
79
4.2 Troubleshooting
Column box
Disconnect wire from P1.2.
Test for min. 14,5 V between
the wire and P1.3.
Connect wire to P1.2
Standard box
Disconnect wire from P5.2.
Test for min. 14,5 V between
P5.2 and P5.3.
Connect wire to P5.2
Finish
80
2000-12-20
4.2 Troubleshooting
Location
3
4
1.2
P5.2
P1.3
P5.3
2000-12-20
81
4.2 Troubleshooting
Standard box
Check that wires connected to
P6.1, 6.2, 6.3 and 6.4 are properly
fixed
Clear errors.
Run system
Finish
82
2000-12-20
4.2 Troubleshooting
Location
1
P6.2
P6.1
2000-12-20
P6.4
P6.3
83
4.2 Troubleshooting
Standard box
Check that wires connected to
P6.1, 6.2, 6.5 and 6.6 are properly
fixed
Clear errors.
Run system
Finish
84
2000-12-20
4.2 Troubleshooting
Location
1
P6.2
P6.1
2000-12-20
P6.6
P6.5
85
4.2 Troubleshooting
Extended box
Check that wires to slewing
sensors are properly fixed
Clear errors.
Run system
Finish
86
2000-12-20
2000-12-20
4.2 Troubleshooting
87
4.2 Troubleshooting
Winch box
Disconnect not indicator
activated indicator
from P3.3 or P4.3
Check if E34 is still active.
Connect indicator
Winch box
Disconnect wire from P1.3
Check if E34 is still active
Connect wire to P1.3
Finish
88
2000-12-20
4.2 Troubleshooting
Location
Location
1
P1.3
P3.3
2000-12-20
P4.3
89
4.2 Troubleshooting
E35 is active.
If message is
Checksum" the error may
appear if voltage to standard
box is broken during setting of
a parameter.
Try again to initialise the same
parameters as when the error
occured
E35 is active.
Read error message on
terminal, at top of main menu.
Initialize system if message is
Uninitialized
E35 is active.
Change current parameter if
message is Out of range.
Turn system off and on again.
Clear errors.
Run system.
Replace Standard box if E35
is still active
Finish
90
2000-12-20
2000-12-20
4.2 Troubleshooting
91
4.2 Troubleshooting
Finish
92
2000-12-20
2000-12-20
4.2 Troubleshooting
93
4.2 Troubleshooting
Finish
94
2000-12-20
2000-12-20
4.2 Troubleshooting
95
4.2 Troubleshooting
Finish
96
2000-12-20
2000-12-20
4.2 Troubleshooting
97
4.2 Troubleshooting
Check if E0 is set
E0 is set
Troubleshoot according to E0
98
Finish
2000-12-20
2000-12-20
4.2 Troubleshooting
99
4.2 Troubleshooting
User interface 1
Disconnect P2.2
Wait min 15 sec.
Test for min. 12,0 V between P1.1
and P1.2
User interface 1
Test for min. 12,0 V between
P2.1 and P2.2.
Connect P2.2
User interface 1
Push in emergency stop.
Disconnect wire from P2.5.
Test for max. 1,0 V between P2.1
and P2.5
Connect wire to P2.5.
Pull out emergency stop
100
Finish
2000-12-20
4.2 Troubleshooting
Location
1
P2.2
P1.1
P1.2
P2.1
P2.2
P2.1
P2.5
2000-12-20
101
4.2 Troubleshooting
Resistance is incorrect.
Replace cable between User
interface 1 and Standard box
Resistance is correct.
Replace User interface 1
Finish
102
2000-12-20
2000-12-20
4.2 Troubleshooting
103
4.2 Troubleshooting
E0 or E39 is set
Troubleshoot according to E0 or
E39.
rface 2.
Identify User interface
Check if jumper B2 is strapped
104
Finish
2000-12-20
2000-12-20
4.2 Troubleshooting
105
4.2 Troubleshooting
User interface 2
Disconnect P2.2
Wait min 15 sec.
Test for min. 12,0 V between P1.1
and P1.2
User interface 2
Test for min. 12,0 V between
P2.1 and P2.2.
Connect P2.2
User interface 2
Push in emergency stop.
Disconnect wire from P2.5.
Test for max. 1,0 V between P2.1
and P2.5
Connect wire to P2.5.
Pull out emergency stop
106
Finish
2000-12-20
4.2 Troubleshooting
Location
1
P2.2
P1.1
P1.2
P2.1
P2.2
P2.1
P2.5
2000-12-20
107
4.2 Troubleshooting
Resistance is incorrect.
Replace cable between user
interface 1 and 2
Resistance is correct.
Replace User interface 2
Finish
108
2000-12-20
2000-12-20
4.2 Troubleshooting
109
4.2 Troubleshooting
Standard box
Should it be three User interfaces
in the system?
110
Finish
2000-12-20
2000-12-20
4.2 Troubleshooting
111
4.2 Troubleshooting
User interface 3
Disconnect P2.2
Wait min 15 sec.
Test for min. 12,0 V between P1.1
and P1.2
User interface 3
Test for min. 12,0 V between
P2.1 and P2.2.
Connect P2.2
User interface 3
Push in emergency stop.
Disconnect wire from P2.5.
Test for max. 1,0 V between P2.1
and P2.5
Connect wire to P2.5.
Pull out emergency stop
112
Finish
2000-12-20
4.2 Troubleshooting
Location
1
P2.2
P1.1
P1.2
P2.1
P2.2
P2.1
P2.5
2000-12-20
113
4.2 Troubleshooting
Resistance is incorrect.
Replace cable between user
interface 2 and 3
Resistance is correct.
Replace User interface 3
Finish
114
2000-12-20
2000-12-20
4.2 Troubleshooting
115
4.2 Troubleshooting
Standard box
Should it be four User interfaces in
the system?
116
Finish
2000-12-20
2000-12-20
4.2 Troubleshooting
117
4.2 Troubleshooting
User interface 4
Disconnect P2.2
Wait min 15 sec.
Test for min. 12,0 V between P1.1
and P1.2
User interface 4
Test for min. 12,0 V between
P2.1 and P2.2.
Connect P2.2
User interface 4
Push in emergency stop.
Disconnect wire from P2.5.
Test for max. 1,0 V between P2.1
and P2.5
Connect wire to P2.5.
Pull out emergency stop
118
Finish
2000-12-20
4.2 Troubleshooting
Location
1
P2.2
P1.1
P1.2
P2.1
P2.2
P2.1
P2.5
2000-12-20
119
4.2 Troubleshooting
Resistance is incorrect.
Replace cable between user
interface 3 and 4
Resistance is correct.
Replace User interface 4
Finish
120
2000-12-20
2000-12-20
4.2 Troubleshooting
121
4.2 Troubleshooting
E10 is set.
Check error in Extended box
according to E10
No.
Set parameters correctly
122
Resistance is incorrect.
Replace ADS valve
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2000-12-20
123
4.2 Troubleshooting
Extended box
Disconnect wire from P1.2
Measure resistance between the
wire and P1.1
Should be 20-100 .
Connect wire to P1.2
Resistance is incorrect.
Replace ADS valve
Finish
124
2000-12-20
4.2 Troubleshooting
Location
2
1.2
P1.1
2000-12-20
125
4.2 Troubleshooting
E10 is set.
Check error in Extended box
according to E10
No.
Set parameters correctly
126
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2000-12-20
127
4.2 Troubleshooting
Extended box
Disconnect wire from P2.1.
Test for min. 14,5 V between
P2.1 and P2.2.
Connect wire to P2.1
Finish
128
2000-12-20
4.2 Troubleshooting
Location
2
P2.2
P2.1
2000-12-20
129
4.2 Troubleshooting
E10 is set.
Check error in Extended box
according to E10
No.
Set parameters correctly
130
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2000-12-20
131
4.2 Troubleshooting
Extended box
Disconnect wire from P3.1.
Test for min. 14,5 V between
P3.1 and P3.2.
Connect wire to P3.1
Finish
132
2000-12-20
4.2 Troubleshooting
Location
2
P3.2
P3.1
2000-12-20
133
4.2 Troubleshooting
E10 is set.
Check error in Extended box
according to E10
No.
Set parameters correctly
Resistance is incorrect.
Replace MSC valve
134
Finish
2000-12-20
4.2 Troubleshooting
Location
1
2000-12-20
135
4.2 Troubleshooting
Extended box
Disconnect wire from P9.2.
Measure resistance between the
wire and P9.1
Should be 20-100 .
Connect wire to P9.2.
Resistance is incorrect.
Replace cable to MSC valve
Finish
136
2000-12-20
4.2 Troubleshooting
Location
2
9.2
2000-12-20
P9.1
137
4.2 Troubleshooting
Resistance is incorrect.
Replace dump 2 valve
Extended box
Disconnect wire from P8.2.
Measure resistance between the
wire and P8.1
Should be 20-100 .
Connect wire to P8.2.
Resistance is incorrect.
Replace cable to dump 2 valve
Finish
138
2000-12-20
4.2 Troubleshooting
Location
1
8.2
2000-12-20
P8.1
139
4.2 Troubleshooting
140
E0 or E35 is active
Troubleshoot according to E0 or
E35
Finish
2000-12-20
4.2 Troubleshooting
Terminal is connected.
Disconnect terminal.
Turn off system and start
again.
Clear errors.
Check if E48 is still active.
Replace Standard box if E48 is
active.
Check terminal communication
if E48 is not active
Clear errors.
Run system
Finish
2000-12-20
141
4.2 Troubleshooting
E49: Service
Condition:
E49 is set when the Standard box records that one of the service counters (total time, use time or number of lifts)
is full.
Error reasons:
-
Finish
142
2000-12-20
4.4 Repairs
4.4 Repairs
Contents
Replacing Standard box ............................................................... 3
Settings, Windows CE terminal ......................................... 5
Settings, DOS terminal ...................................................... 6
2000-12-20
4.4 Repairs
2000-12-20
4.4 Repairs
REPLACING
ST
ANDARD BOX
STANDARD
1. Unscrew the 4-socket head screws in the front of
the User interface. It is not necessary to completely
remove these screws they are designed to be
retained in the cover, only unscrew until no further
resistance is felt.
2. Carefully remove the User interface. It maybe
necessary to ease the User interface from the
Standard box by placing a screwdriver in the joint
between the two components. Take care not to
damage this joint, it is part of the water protection
seal.
NOTE!
Do not allow the User interface to hang on
wires, always support it while the wiring is
connected.
3. Disconnect all connections from plinth P7 in the
Standard box.
4. Disconnect all connections from plinth P2 on the
User Interface and place in a safe area.
5. Mark up cables in Standard box. Disconnect all
connections to Standard box plinths.
6. Release all clips from cable inlets and carefully
withdraw cables.
7. Remove the 4-socket head mounting screws from
rear of the mounting plate and lift the Standard box
away.
2000-12-20
4.4 Repairs
2000-12-20
4.4 Repairs
Settings, Windows
CE terminal
1. Connect a HP Jornada terminal to
SPACE.
2. Type User Name and Password, click
on OK and the Main menu is
displayed.
3. If you have only a Service level
password select Diagnostic in the
display box.
4. Select Init from Main menu.
5. Select Type in Parameter Initialization
screen.
6. Highlight the crane class and type you
require and click on Select (fig. 1).
The required channels and parameters
are now set. Select Back
ack.
7. Select Levers in Parameter
Initialization screen.
8. Select Calibrate and follow screen
instructions (fig. 2).
9. Make any adjustments to the basic
settings by selecting Init followed by
Auto (fig. 3). Settings for winch etc.
can be made here.
NOTE!
Fig. 1
Sector Type:
Platf 1 Low
Cap (%)
Slew Sector 2
Sector Type:
Cap (%)
Yes
No
OLP
60
Winch
60
ADS
Yes
No
Ext In Indicator
Yes
Manual Extension
Cap (%)
50
75
No
Pressure Settings (bar)
Height Warn
Yes
No
Cancel
IB
+2%
265
OB
+1%
273
OK
1070-365
Slew Sector 1
Fig. 3
2000-12-20
4.4 Repairs
2000-12-20
5.1 Service
5.1 Service
Contents
Service requirements ................................................................... 3
General checks .................................................................. 3
OLP check ......................................................................... 4
Stickers / manuals ............................................................. 4
Functional test ................................................................... 4
Resetting counters, Windows CE terminal ........................ 5
Resetting counters, DOS terminal ..................................... 6
2000-12-20
5.1 Service
2000-12-20
5.1 Service
SERVICE
REQUIREMENTS
General checks
Check all cables for wear, damage, corrosion or
tightness
Check all sensors, indicators and connectors for wear,
damage or corrosion
- pressure sensor, inner boom cylinder
- pressure sensor, outer boom cylinder
- tilt indicator, inner boom
- tilt indicator, outer boom
- fixed platform angle indicators
- slewing sector indicators
- spool sensors
- Cannon connector, winch
- etc.
Check all boxes and cable connections for damage or
corrosion
- Standard box
- Extended box
- Empty box
- Column box
- Winch box
- Cable reel box
- etc.
2000-12-20
5.1 Service
OLP check
Check the function of OLP by moving the first and
second boom cylinders to end position.
Stickers / manuals
Check that Operators manual and Service manuals
are with truck.
Check that warning plates, load plates, symbol plates
etc. are unbroken.
For information about type and numbers of stickers
see Operators manual.
Functional test
Check:
- operation of all User interface buttons and warning
LEDs
- crane movements to/from folded/unfolded position
and end positions
By means of a HP terminal, check for any error
messages in F6 - ERRS
ERRS.
Reset after corrective measures.
2000-12-20
5.1 Service
Resetting counters,
Windows CE terminal
After completing all service operations as
per the HIAB service documentation, it is
necessary to reset the counters in
SPACE 3000.
1. Connect a HP Jornada terminal to
SPACE.
2. Type User Name and Password, click
on OK and the Main menu is
displayed.
3. Select Counters from Main menu.
4. Select Service from counters menu.
6. Click on Back
Back.
23:31
40
1950:12
986:45
56:52
14:23
Service
7. Disconnect terminal.
Back
1070-366
Fig. 1
2000-12-20
5.1 Service
Resetting counters,
DOS terminal
After completing all service operations as per the HIAB
service documentation, it is necessary to reset the
counters in SPACE 3000.
1. Connect a HP 95 terminal or a 200 model of
Handheld PC to SPACE.
2. Type User Name and press ENTER
ENTER. Type
Password, press ENTER and the Main menu is
displayed.
3. Press F9 - COUNT from Main menu.
4. Press F8 - SERVICE from count menu.
5. Enter the letter Y at the flashing cursor, press
ENTER
ENTER.
6. Disconnect terminal.
2000-12-20
2000-10-31
2000-10-31
CONNECTING A WINCH
General
NOTE!
The following instructions relate only to the
electrical connections and adjustments to
SP
ACE 3000 that are required when
SPACE
connecting a winch. For all other
information you must refer to Crane Info 15
or the relevant winch manufacturers
installation instructions.
Fig. 1
2000-10-31
Settings, Windows
CE terminal
Automatic Parameter Initialization
Sector Type:
Platf 1 Low
Cap (%)
Slew Sector 2
Sector Type:
Yes
No
OLP
60
Winch
60
Cap (%)
ADS
Yes
No
Ext In Indicator
Yes
50
75
IB
+2%
265
OB
+1%
273
Cancel
OK
Fig. 2
Cap (%)
No
Manual Extension
1070-365
Slew Sector 1
OK
Ready
Slew Sector 1
Sector Type:
Platf 1 Low
Cap (%)
The
set
Ext In Indicator
Winch were successfully
Slew Sector
2 parameters
Sector Type:
OLP
60
Cap (%)
60
Yes
Yes
No
No
ADS
Yes
No
Manual Extension
Cap (%)
50
75
Height Warn
Yes
No
Cancel
IB
+2%
265
OB
+1%
273
OK
1070-369
Fig. 3
8. Select Levers.
9. Select Calibrate (Fig. 4) and follow
the on screen instructions.
10. When calibration is completed click
on OK in message box (Fig. 5) and
check functions
11. Click on Back twice to return to main
menu.
Fig. 4
Fig. 5
2000-10-31
2000-10-31
CONNECTING A FIXED
PLATFORM
NOTE!
These instructions do not include mounting
details for the mechanical components of a
fixed platform.
Description
When a crane is fitted with a fixed platform, it is
necessary to stop crane operation when there is a
possibility the operator may be struck by the boom
assembly.
To facilitate this HIAB have introduced logic into
SPACE 3000 system that will not permit the crane to
operate in the area over the platform.
The logic for the fixed platform is controlled by:
an indicator mounted under the platform to inform
SPACE if an operator is on the platform
indicators mounted at the base of the column
indicating the slew position
additional angle indicators that can be mounted on
both the inner and outer booms to provide the means
to stop the crane depending on boom position, in
addition to the slewing position.
2000-10-31
Function
Number
Type
On platform indicator
Normally closed
Normally open
Normally open
Normally open
2000-10-31
Connection of indicators to
Column box
The inner and outer boom indicators should be connected to the Column box.
The connection in the Column box has to be done in
two different ways depending on if a hydraulic extension in indicator is mounted or not.
Connection if no hydraulic
extension in indicator is
present
If no hydraulic extension in indicator is mounted, the
fixed platform indicators should be connected to the
Column box as shown in fig. 6, which is the most
common connection.
P3
65
Plinth Description
P2.4-6
P2.4
Ground (brown)
P2.5
24 V (red)
P2.6
P3.1-3
P3.1
Ground (brown)
P3.2
24 V (red)
P3.3
321
6
5
4
P4
P2
1
P1
1070-374
NOTE!
A jumper must always be fitted between
plinth P3.5 and P3.6.
Fig. 6
2000-10-31
Connection if a hydraulic
extension in indicator is
present
If a hydraulic extension in indicator is mounted, the
fixed platform indicators should be connected to the
Column box as shown in fig. 7.
The hydraulic extension in indicator has to be
connected to plinth P2.4-6.
If an outer boom angle indicator is used it has to be
connected to P3.4-6 instead.
P3
Plinth Description
P2.4-6
P3.1-3
P3.1
Ground (brown)
P3.2
24 V (red)
P3.3
P3.4-6
P3.4
Ground (brown)
P3.5
24 V (red)
P3.6
NOTE!
654321
1
P2
P4
1
1
P1
1070-375
Fig. 7
2000-10-31
Connection of indicators to
Standard box
(Fig. 8)
The On platform indicator and slewing sector indicators
should to be connected to the Standard box.
NOTE!
Only connections for On platform indicator
and slewing sector indicators used for fixed
platform are illustrated. All other component connections have been removed for
clarity.
NOTE!
Ensure that there is a jumper placed in the
User interface 3 between plinth P2.5 and
P2.6.
5
1.
2.
3.
4.
5.
6.
7.
8.
1070-373
User interface 2
User interface 1
User interface 3
Empty box (placed on platform)
Slewing sector indicators
On platform indicator
Standard box
Extended box or Empty box (placed on tank side)
Fig. 8
10
2000-10-31
(Fig. 9)
P4
On platform indicator
P4.1
Ground (brown)
P4.2
24 V (red)
P4.3
P6.1-4
P6.1
Ground (brown)
P6.2
24 V (red)
P6.3
P6.4
1070-378
Plinth Description
Fig. 9
Position
2000-10-31
11
Inner boom
fixed platform
angle indicator
Outer boom
fixed platform
angle indicator
Slewing
sector
indicators
On
platform
indicator
Platf 0
Platf 1
Platf 2
Platf 2S
Hydraulic
extension
in indicator
12
2000-10-31
Platf 0 Low:
No tilt indicators fitted to the boom
system.
Slew Sector 1
Sector Type:
Platf 1 Low
Cap (%)
Slew Sector 2
Sector Type:
Yes
No
OLP
60
Winch
60
Cap (%)
ADS
Yes
No
Ext In Indicator
Yes
Manual Extension
Cap (%)
50
75
No
Pressure Settings (bar)
Height Warn
Yes
No
IB
+2%
265
OB
+1%
273
Cancel
OK
1070-365
Fig. 10
Platf 1 Low:
One tilt indicator fitted on the inner
boom.
Platf 2 Low:
Tilt indicators fitted to both inner and
outer booms with the inner boom
indicator connected to plinth P3 and
outer boom indicator connected to plinth
P2.
Platf 2S Low:
Tilt indicators fitted to both inner and
outer boom and both connected to plinth
P3 in the column box.
OK
Ready
Slew Sector 1
Sector Type:
Platf 1 Low
Cap (%)
The
set
Ext In Indicator
Winch were successfully
Slew Sector
2 parameters
Sector Type:
OLP
60
Cap (%)
60
Yes
Yes
No
No
ADS
Yes
No
Manual Extension
Cap (%)
50
75
IB
+2%
265
OB
+1%
273
OK
1070-369
9. Disconnect terminal.
Fig. 11
2000-10-31
13
14
2000-10-31
2000-10-31
15
CONNECTING ADS
General
NOTE!
NOTE!
NOTE!
When replacing an Empty box with
Extended box, ensure that there is a jumper
placed in the Extended box between plinth
P7.5 and P7.6.
1070-376
4
1. User interface 2
2. User interface 1
3. Standard box
4. Pressure sensor ADS
5. Valve ADS
6. Extended box
Fig. 12
16
2000-10-31
Settings, Windows
CE terminal
1. Connect a suitable terminal to SPACE
and enter the main menu.
2. Type User Name and Password, click
on OK and the Main menu is
displayed.
3. Select Init from Main menu.
Platf 1 Low
Cap (%)
60
Yes
60
Cap (%)
ADS
Yes
No
Ext In Indicator
Yes
Manual Extension
Cap (%)
50
75
No
Pressure Settings (bar)
Height Warn
Yes
No
IB
+2%
265
OB
+1%
273
Cancel
OK
Fig. 13
OK
Ready
Slew Sector 1
8. Disconnect terminal.
Winch
No
OLP
Sector Type:
Sector Type:
Platf 1 Low
Cap (%)
The
set
Ext In Indicator
Winch were successfully
Slew Sector
2 parameters
Sector Type:
OLP
60
Cap (%)
60
Yes
Yes
No
No
ADS
Yes
No
Manual Extension
Cap (%)
50
75
IB
+2%
265
OB
+1%
273
OK
1070-369
Sector Type:
Slew Sector 2
1070-365
Slew Sector 1
Fig. 14
2000-10-31
17
18
2000-10-31
CONNECTING A
HYDRAULIC
EXTENSION IN
INDICATOR
Description
The hydraulic extension in indicator makes it possible
to control the lifting capacity of a crane when using
manual extensions. By using a signal from a suitable
indicator mounted approximately at the centre position
along the length of the outer boom, SPACE 3000
reduces the inner boom lifting capacity to pre-set limits
depending on the position of the hydraulic extension.
The logic for this facility is activated when the manual
extension button is pressed on the User interface.
NOTE!
HIAB do not supply any indicator kit for this
function.
2000-10-31
19
Connection of indicator to
Column box
A normally open type proximity switch must be used
as the indicator for this function.
It should be connected to plinth P2.4-6 in Column box
as shown in fig. 15.
P3
NOTE!
6
5
4
P4
Plinth Description
Hydraulic extension in indicator
P2.4
Ground (blue)
P2.5
24 V (brown)
P2.6
1
P1
1070-377
P2.4-6
P2
Fig. 15
20
2000-10-31
Settings, Windows
CE terminal
1. Connect a HP Jornada terminal to
SPACE.
2. Type User Name and Password, click
on OK and the Main menu is
displayed.
3. Select Init from Main menu.
4. Select Auto in Automatic Parameter
Initialization screen.
Automatic Parameter Initialization
Sector Type:
Platf 1 Low
Cap (%)
Slew Sector 2
Sector Type:
60
Cap (%)
ADS
Yes
No
Manual Extension
Cap (%)
50
75
No
Pressure Settings (bar)
Height Warn
Yes
No
IB
+2%
265
OB
+1%
273
OK
Fig. 16
OK
Ready
Slew Sector 1
Sector Type:
Platf 1 Low
Cap (%)
The
set
Ext In Indicator
Winch were successfully
Slew Sector
2 parameters
Sector Type:
OLP
60
Cap (%)
60
Yes
Yes
No
No
ADS
Yes
No
Manual Extension
Cap (%)
50
75
Ext In Indicator
Yes
Cancel
Yes
No
OLP
60
Winch
1070-365
Slew Sector 1
IB
+2%
265
OB
+1%
273
OK
1070-369
Fig. 17
2000-10-31
21
22
2000-10-31
6.2 Settings
6.2 Settings
Contents
Settings introduction ..................................................................... 3
Operating systems ............................................................ 3
Conventions used .............................................................. 4
Setting ADC function .................................................................... 5
Windows CE terminal ........................................................ 5
DOS terminal ..................................................................... 7
Setting MSC function .................................................................... 8
Windows CE terminal ........................................................ 8
DOS terminal ................................................................... 10
2000-12-20
6.2 Settings
2000-12-20
6.2 Settings
SETTINGS
INTRODUCTION
We understand that not all service engineers work with
our products everyday, and this can make it difficult to
remember exactly which display to use or which
button to press when presented with a specific task,
when using one of the terminal units that are available.
With the introduction also of the new Windows CE
based programs the choices and options have
increased.
The purpose of this section is to provide the service
engineer with a step by step guide, to making changes
to the basic settings of the SPACE 3000 system.
Following the introduction of the new HP Jornada range
of handheld PC's into the list of suitable terminal units,
for use with the SPACE control systems, we have
provided instructions for both types of operating
systems now available.
Operating systems
Desktop and laptop PC's in conjunction with the PC
interface use the DOS based program.
HP 95 and 200 handheld PC's use the DOS based
programs.
HP 680/690 and 720 handheld PC's use the Windows
CE based program.
2000-12-20
6.2 Settings
Conventions used
(Fig. 1) Throughout the instructions you
will find different types of text used, the
meanings are listed below, please take a
few minutes to read these it will help you
to understand the instructions more
clearly.
All windows within the main display are
discussed in plain text (1).
1
Parameter
Parameter Value
1070-372
Fig. 1
2000-12-20
6.2 Settings
SETTING ADC
FUNCTION
When a new SPACE 3000 Standard box
is supplied as a spare part, only the
Classic crane program is present. If you
have a DUO or PRO crane, you must
enable the logic in SPACE. To carry out
this operation it is necessary for your
service responsible to obtain a special
password from product support
department at HIAB AB.
Windows CE
terminal
1. Connect a HP Jornada terminal to
SPACE.
2. Type User Name and Password, click
on OK and the Main menu is
displayed.
3. If you have only a Service level
password select Diagnostic in the
display box.
4. Select Parameters from Main menu.
5. Select Various In the Class window.
6. Select password In the Parameter
window (Fig. 2).
Parameter
Parameter Value
2000-12-20
1070-371
alue
7. Click on Change Par V
Value
alue.
Fig. 2
6.2 Settings
2000-12-20
6.2 Settings
DOS terminal
1. Connect a HP 95 terminal or a 200 model of
Handheld PC to SPACE.
2. Type User Name and press ENTER
ENTER. Type
Password, press ENTER and the Main menu is
displayed.
3. If you have only a Service level password highlight
with the cursor bar Diagnostic
Diagnostic.
ARS from Main menu.
4. Press F3 - P
PARS
5. Highlight Various using the arrow keys and press
ENTER
ENTER.
6. Highlight password using the arrow keys and
press ENTER
ENTER.
7. In the New Value window type in the special
password obtained from HIAB AB.
8. Press ENTER and then F10 - EXIT and the display
will return to the previous screen.
9. Select ADC using the arrow keys and press
ENTER
ENTER.
10. Highlight multi_mode using the arrow keys and
press ENTER.
11. Type 1 under New Value, press ENTER and the
display returns to previous display.
12. Press F10 - EXIT twice and the display returns to
the Main menu window and the ADC function is
now active.
13. Disconnect terminal.
14. Carry out full crane function test.
2000-12-20
6.2 Settings
SETTING MSC
FUNCTION
When a new SPACE 3000 Standard box
is supplied as a spare part, only the
Classic crane program is present. If you
have a crane fitted with the MSC function,
you must enable the logic in SPACE. To
carry out this operation it is necessary for
your service responsible to obtain a
special password from product support at
HIAB AB.
Windows CE
terminal
1. Connect a HP Jornada terminal to
SPACE.
2. Type User Name and Password, click
on OK and the Main menu is
displayed.
3. If you have only a Service level
password select Diagnostic in the
display box.
4. Select Parameters from Main menu.
5. Select Various In the Class window.
6. Select password In the Parameter
window (Fig. 4).
Parameter
Parameter Value
1070-371
Fig. 4
2000-12-20
6.2 Settings
2000-12-20
Fig. 5
6.2 Settings
DOS terminal
1. Connect a HP 95 terminal or a 200 model of
Handheld PC to SPACE.
2. Type User Name and press ENTER
ENTER. Type
Password, press ENTER and the Main menu is
displayed.
3. If you have only a Service level password highlight
with the cursor bar Diagnostic
Diagnostic.
ARS from Main menu.
4. Press F3 - P
PARS
5. Highlight Various using the arrow keys and press
ENTER
ENTER.
6. Highlight password using the arrow keys and press
ENTER
ENTER.
7. In the New Value window type in the special
password obtained from HIAB AB.
8. Press ENTER and then F10 - EXIT and the display
will return to the previous screen.
9. Select MSC using the arrow keys and press
ENTER
ENTER.
10. Highlight msc_mode using arrow keys and press
ENTER
ENTER.
11. Type 1 under New Value, press ENTER and the
display returns to previous display.
12. Press F10 - EXIT twice and the display returns to
the Main menu window and the MSC function is
now active.
13. Disconnect terminal.
14. Carry out full crane function test.
10
2000-12-20
2000-10-31