You are on page 1of 315

CSC-326

Transformer Protection IED


Technical Application Manual

CSC-326 Transformer
Protection IED
Technical Application Manual
Compiled: Jin Rui
Checked: Hou Changsong
Standardized: Li Lianchang

Inspected: Cui Chenfan

Version V1.01
Doc.Code0SF.450.085(E)
Issued Date2012.8.31

VersionV1.01
Doc. Code0SF.450.085(E)
Issued Date2012.8
Copyright owner: Beijing Sifang Automation Co., Ltd
Note: the company keeps the right to perfect the instruction. If equipment does not agree
with the instruction at anywhere, please contact our company in time. We will provide you
with corresponding service.

is registered trademark of Beijing Sifang Automation Co., Ltd.


We reserve all rights to this document, even in the event that a patent is issued and a different
commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted.
This document has been carefully checked. If the user nevertheless detects any errors, he is
asked to notify us as soon as possible.
The data contained in this manual is intended solely for the product description and is not to be
deemed to be a statement of guaranteed properties. In the interests of our customers, we
constantly seek to ensure that our products are developed to the latest technological standards as a result; it is possible that there may be some differences between the hardware/software product and this information product.
Manufacturer:
Beijing Sifang Automation Co., Ltd.
Tel: +86-10-62961515
Fax: +86-10-62981900
Internet: http://www.sf-auto.com
Add: No.9, Shangdi 4th Street, Haidian District, Beijing, P.R.C.100085

Preface
Purpose of this manual
This manual describes the functions, operation, installation, and placing into service
of device CSC-326. In particular, one will find:

Information on how to configure the device scope and a description of the device
functions and setting options;

Instructions for mounting and commissioning;

Compilation of the technical specifications;

A compilation of the most significant data for experienced users in the Appendix.

Target Audience
Protection engineers, commissioning engineers, personnel concerned with
adjustment, checking, and service of selective protective equipment, automatic and
control facilities, and personnel of electrical facilities and power plants.

Applicability of this Manual


This manual is valid for SIFANG Distance Protection IED CSC-326; firmware version
V1.00 and higher

Indication of Conformity
Additional Support
In case of further questions concerning IED CSC-326 system, please contact
SIFANG representative.

Safety information

Strictly follow the company and international safety regulations.


Working in a high voltage environment requires serious approch to
aviod human injuries and damage to equipment

Do not touch any circuitry during operation. Potentially lethal


voltages and currents are present

Avoid to touching the circuitry when covers are removed. The IED
contains electirc circuits which can be damaged if exposed to static
electricity. Lethal high voltage circuits are also exposed when covers
are removed

Using the isolated test pins when measuring signals in open circuitry.
Potentially lethal voltages and currents are present

Never connect or disconnect wire and/or connector to or from IED


during normal operation. Dangerous voltages and currents are
present. Operation may be interrupted and IED and measuring
circuitry may be damaged

Always connect the IED to protective earth regardless of the


operating conditions. Operating the IED without proper earthing may
damage both IED and measuring circuitry and may cause injuries in
case of an accident.

Do not disconnect the secondary connection of current transformer


without short-circuiting the transformers secondary winding.
Operating a current transformer with the secondary winding open will
cause a high voltage that may damage the transformer and may
cause injuries to humans.

Do not remove the screw from a powered IED or from an IED


connected to power circuitry. Potentially lethal voltages and currents
are present

Using the certified conductive bags to transport PCBs (modules).


Handling modules with a conductive wrist strap connected to
protective earth and on an antistatic surface. Electrostatic discharge
may cause damage to the module due to electronic circuits are
sensitive to this phenomenon

Do not connect live wires to the IED, internal circuitry may be


damaged

When replacing modules using a conductive wrist strap connected to


protective earth. Electrostatic discharge may damage the modules
and IED circuitry

When installing and commissioning, take care to avoid electrical


shock if accessing wiring and connection IEDs

Changing the setting value group will inevitably change the IEDs
operation. Be careful and check regulations before making the
change

Contents
Chapter 1 Introduction................................................................................................... 1
1 Overview .................................................................................................................... 2
2 Features..................................................................................................................... 3
Chapter 2 Basic protection elements ............................................................................. 9
1 Startup element .........................................................................................................10
1.1
Introduction..................................................................................................10
1.2
Sudden-change current startup element ......................................................10
1.3
Differential current startup element ..............................................................10
2 Input and output signals ............................................................................................ 11
3 Settings .....................................................................................................................13
4 Report .......................................................................................................................16
Chapter 3 Differential protection ...................................................................................17
1 Introduction ...............................................................................................................18
2 Applications...............................................................................................................18
3 Protection algorithm ..................................................................................................19
3.1
Differential and restraint current calculation .................................................20
3.2
Automatic Ratio compensation ....................................................................22
3.3
Automatic Vector group and zero sequence current compensation..............26
4 Protection principle....................................................................................................32
4.1
Instantaneous differential protection characteristic .......................................32
4.2
Treble slope percent differential protection characteristic .............................34
4.3
Selective inrush stabilization schemes .........................................................37
4.3.1
2nd harmonic stabilization ...........................................................................38
4.3.2
Fuzzy recognition of inrush based on the waveform ....................................38
4.4
Overexcitation stabilization ..........................................................................40
4.5
CT Failure supervision .................................................................................42
4.6
CT Saturation supervision............................................................................43
4.7
Differential current supervision.....................................................................44
5 Input and output signals ............................................................................................46
6 Settings .....................................................................................................................47
7 Report .......................................................................................................................50
8 Technical data ...........................................................................................................51
Chapter 4 Restricted earth fault protection ...................................................................53
1 Introduction ...............................................................................................................54
2 Applications...............................................................................................................54
3 Protection principle....................................................................................................56
3.1
Differential and restraint current calculation .................................................57
3.2
Automatic Ratio compensation ....................................................................59
3.3
Positive sequence current blocking..............................................................61
3.4
Restricted earth fault current alarm ..............................................................62
4 Input and output signals ............................................................................................63
5 Settings .....................................................................................................................64

6 Report ...................................................................................................................... 66
7 Technical data........................................................................................................... 67
Chapter 5 Overexcitation protection ............................................................................. 69
1 Introduction............................................................................................................... 70
2 Protection principle ................................................................................................... 70
2.1
Protection principle...................................................................................... 70
2.2
Voltage channel configuration ..................................................................... 76
3 Input and output signals............................................................................................ 77
4 Settings .................................................................................................................... 78
5 Report ...................................................................................................................... 79
6 Technical data........................................................................................................... 80
Chapter 6 Overcurrent protection................................................................................. 83
1 Introduction............................................................................................................... 84
2 Protection principle ................................................................................................... 84
2.1
Protection Elements .................................................................................... 84
2.2
Inrush Restraint Feature.............................................................................. 86
2.3
Direction Determination Feature.................................................................. 87
2.4
CBF initiation Feature ................................................................................. 90
3 Input and output signals............................................................................................ 91
4 Setting ...................................................................................................................... 92
5 Report ...................................................................................................................... 99
6 Technical data........................................................................................................... 99
Chapter 7 Earth fault protection ................................................................................. 101
1 Protection principle ................................................................................................. 102
1.1
Protection elements .................................................................................. 102
1.2
Inrush Restraint Feature............................................................................ 104
1.3
Direction Determination Feature................................................................ 105
1.4
CBF initiation Feature ............................................................................... 107
2 Input and output signals.......................................................................................... 108
3 Setting .................................................................................................................... 109
4 Report .................................................................................................................... 115
5 Technical data......................................................................................................... 116
Chapter 8 Neutral earth fault protection ..................................................................... 119
1 Protection principle ................................................................................................. 120
1.1
Protection Elements .................................................................................. 120
1.2
Inrush Restraint Feature............................................................................ 122
1.3
Direction Determination Feature................................................................ 122
1.4
CBF initiation Feature ............................................................................... 124
2 Input and output signals.......................................................................................... 125
3 Setting .................................................................................................................... 126
4 Report .................................................................................................................... 132
5 Technical data......................................................................................................... 133
Chapter 9 Thermal overload protection ...................................................................... 135
1 Introduction............................................................................................................. 136

2 Protection principle..................................................................................................136
3 Input and output signals ..........................................................................................138
4 Setting.....................................................................................................................138
5 Report .....................................................................................................................140
6 Technical data .........................................................................................................141
Chapter 10 Overload protection ...................................................................................143
1 Protection principle..................................................................................................144
2 Input and output signals ..........................................................................................145
3 Setting.....................................................................................................................146
4 Report .....................................................................................................................148
Chapter 11 Overvoltage protection...............................................................................149
5 Introduction .............................................................................................................150
6 Protection principle..................................................................................................150
6.1
Phase to phase overvoltage protection ......................................................150
6.2
Phase to earth overvlotage protection........................................................151
7 Logic diagram .........................................................................................................151
8 Input and output signals ..........................................................................................151
9 Setting.....................................................................................................................152
10
Report ..............................................................................................................154
11
Technical data ..................................................................................................154
Chapter 12 Circuit breaker failure protection ................................................................157
1 Introduction .............................................................................................................158
2 Protection principle..................................................................................................158
3 Logic diagram .........................................................................................................161
4 Input and output signals ..........................................................................................163
5 Setting.....................................................................................................................164
6 Report .....................................................................................................................167
7 Technical data .........................................................................................................167
Chapter 13 Dead zone protection.................................................................................169
1 Introduction .............................................................................................................170
2 Protection principle..................................................................................................170
2.1
Function description...................................................................................171
3 Logic diagram .........................................................................................................171
4 Input and output signals ..........................................................................................172
5 Setting.....................................................................................................................173
6 Report .....................................................................................................................174
7 Technical data .........................................................................................................174
Chapter 14 STUB protection ........................................................................................175
1 Introduction .............................................................................................................176
2 Protection principle..................................................................................................176
2.1
Function description...................................................................................176
3 Logic diagram .........................................................................................................177
4 Input and output signals ..........................................................................................177
5 Setting.....................................................................................................................178

6 Report .................................................................................................................... 180


7 Technical data......................................................................................................... 181
Chapter 15 Poles discordance protection .................................................................... 183
1 Introdcution............................................................................................................. 184
2 Protection principle ................................................................................................. 184
2.1
Function description .................................................................................. 184
3 Logic diagram ......................................................................................................... 185
4 Input and output signals.......................................................................................... 186
5 Setting .................................................................................................................... 187
6 Report .................................................................................................................... 188
7 Technical data......................................................................................................... 188
Chapter 16 Secondary system supervision .................................................................. 189
1 VT failure supervision function ................................................................................ 190
2 Function principle ................................................................................................... 190
3 Input and output signals.......................................................................................... 193
4 Setting .................................................................................................................... 194
5 Report .................................................................................................................... 195
6 Technical data......................................................................................................... 196
Chapter 17 External BIs to trip BOs ............................................................................. 197
1 Introduction............................................................................................................. 198
2 Function principle ................................................................................................... 198
3 BI Trigger Record ................................................................................................... 199
4 BI Switch SetGroup ................................................................................................ 200
5 BI Blk Rem Access and RELAY TEST................................................................ 200
6 BI BI_Config1~ BI_Config2 and BI TRIGGER DR1~ 10 ..................................... 201
7 Setting .................................................................................................................... 201
Chapter 18 Station communication .............................................................................. 203
1 Overview ................................................................................................................ 204
1.1
Protocol..................................................................................................... 204
1.1.1
LON communication protocol ............................................................. 204
1.1.2
IEC61850-8 communication protocol .................................................. 204
1.1.3
IEC60870-5-103 communication protocol ........................................... 205
1.2
Communication port .................................................................................. 205
1.2.1
Front communication port ................................................................... 205
1.2.2
RS485 communication ports............................................................... 205
1.2.3
Ethernet communication ports ............................................................ 205
1.3
Technical data ........................................................................................... 205
Front communication port .............................................................................................. 206
RS485 communication port ........................................................................................... 206
2 Typicalcommunication scheme ............................................................................... 208
2.1
Typical substation communication scheme................................................ 208
2.2
Typical time synchronizing scheme ........................................................... 208
Chapter 19 Hardware .................................................................................................. 211
This chapter describes the IED hardware. ..................................................................... 211

Introduction .............................................................................................................212
3.1
IED structure .............................................................................................212
3.2
IED appearance.........................................................................................212
3.3
IED module arrangement ...........................................................................213
3.4
The rear view of the protection IED............................................................213
Local human-machine interface ..............................................................................214
4.1
Human machine interface ..........................................................................214
4.2
LCD ...........................................................................................................215
4.3
Keypad ......................................................................................................215
4.4
Shortcut keys and functional keys..............................................................216
4.5
LED ...........................................................................................................217
4.6
Front communication port ..........................................................................218
Analog input module ...............................................................................................219
5.1
Introduction................................................................................................219
5.2
Terminals of Analogue Input Module (AIM) ................................................219
5.3
Technical data............................................................................................220
5.3.1
Internal current transformer.................................................................220
5.3.2
Internal voltage transformer ................................................................221
Communication module ..........................................................................................222
6.1
Introduction................................................................................................222
6.2
Substaion communication port ...................................................................222
6.2.1
RS232 communication ports ...............................................................222
6.2.2
RS485 communication ports ...............................................................222
6.2.3
Ethernet communication ports.............................................................222
6.2.4
Time synchronization port ...................................................................223
6.3
Terminals of Communication Module .........................................................223
6.4
Operating reports .......................................................................................224
6.5
Technical data............................................................................................224
6.5.1
Front communication port ...................................................................224
6.5.2
RS485 communication port .................................................................225
6.5.3
Ethernet communication port ..............................................................225
6.5.4
Time synchronization ..........................................................................226
Binary input module ................................................................................................227
7.1
Introduction................................................................................................227
7.2
Terminals of Binary Input Module (BIM) .....................................................227
7.3
Technical data............................................................................................229
Binary output module ..............................................................................................230
8.1
Introduction................................................................................................230
8.2
Terminals of Binary Output Module (BOM) .................................................230
8.2.1
Binary Output Module A ......................................................................230
8.2.2
Binary Output Module C ......................................................................233
8.3
Technical data............................................................................................234
Power supply module ..............................................................................................236
9.1
Introduction................................................................................................236

9.2
9.3

Terminals of Power Supply Module (PSM) ................................................ 236


Technical data ........................................................................................... 238
10
Techinical data ................................................................................................. 239
10.1
Basic data ................................................................................................. 239
10.1.1 Frequency .......................................................................................... 239
10.1.2 Internal current transformer ................................................................ 239
10.1.3 Internal voltage transformer ................................................................ 239
10.1.4 Auxiliary voltage ................................................................................. 239
10.1.5 Binary inputs....................................................................................... 240
10.1.6 Binary outputs .................................................................................... 240
10.2
Type tests.................................................................................................. 241
10.2.1 Product safety-related Tests ............................................................... 241
10.2.2 Electromagnetic immunity tests .......................................................... 242
10.2.3 DC voltage interruption test ................................................................ 244
10.2.4 Electromagnetic emission test ............................................................ 244
10.2.5 Mechanical tests ................................................................................. 244
10.2.6 Climatic tests ...................................................................................... 245
10.2.7 CE Certificate ..................................................................................... 246
10.3
IED design ................................................................................................ 246
Chapter 20 Appendix ................................................................................................... 247
1 General setting list .................................................................................................. 248
1.1
Function setting list ................................................................................... 248
1.2
Binary setting list ....................................................................................... 266
2 General report list ................................................................................................... 288
3 Time inverse characteristic ..................................................................................... 295
3.1
11 kinds of IEC and ANSI inverse time characteristic curves ..................... 295
3.2
User defined characteristic ........................................................................ 296
4 CT Requirement ..................................................................................................... 296
4.1
Overview ................................................................................................... 296
4.2
Current transformer classification .............................................................. 296
4.3
Abbreviations (according to IEC 60044-1, -6, as defined).......................... 297
4.4
General current transformer requirements................................................. 298
4.4.1
Protective checking current ................................................................ 298
4.4.2
CT class ............................................................................................. 299
4.4.3
Accuracy class ................................................................................... 301
4.4.4
Ratio of CT ......................................................................................... 301
4.4.5
Rated secondary current .................................................................... 301
4.4.6
Secondary burden .............................................................................. 302
4.5
Rated equivalent secondary e.m.f requirements........................................ 302
4.5.1
Transformer differential protection ...................................................... 303

Chapter 1 Introduction

Chapter 1 Introduction

About this chapter


This chapter gives an overview of SIFANG transformer protection IED.

Chapter 1 Introduction

Overview
It is selective, reliable and high speed IED (Intelligent Electronic Device)
for transformer protection with powerful capabilities to cover following
applications:
For large and medium two- or three-winding transformers, and autotransformer

Used in a wide range of voltage levels, up to 1000kV

For single or multi-breaker arrangement

Up to 7 three-phase sets of CTs input (special ordering)

Work as main protection unit only or full functions unit for the
complicated application

Communication with station automation system

The IED is able to provide all main protection functions and backup protection functions in one case, including differential protection, restricted
earth fault (REF), overexcitation, thermal overload, overcurrent, earth
fault protection, etc.
The integrated flexible logic make the IED suitable to be applied to (auto)transformers with all the possible vector groups, with/without earthing
connection inside the protected zone.
The wide application flexibility makes the IED an excellent choice for both
new installations and retrofitting of the existing stations.
.

Chapter 1 Introduction

Features

Protection and monitoring IED with extensive functional library, user


configuration possibility and expandable hardware design to meet with
users special requirements

Inter-lock between two CPU modules, avoiding mal-operation due to


internal severe fault of one module

Transformer differential protection (87T)

Treble slope percent differential protection

Automatic CT ratio matching

Automatic vector group and zero sequence current compensation

Settable 2nd harmonic restraint function for transformer inrush

Fuzzy waveform recognition restraint function for transformer


inrush

3rd or 5th harmonic restraint for overexcitation

CT saturation detection

CT secondarycircuit supervison

Differential current alarm

Restricted earth fault protection (87N)

Two slope percent REF protection

Automatic CT ratio matching

CT saturation recognition

REF differential current supervision

Positive sequence current blocking

A complete protection functions library, include:


3

Chapter 1 Introduction

Transformer differential protection (87T)

Restricted earth fault protection (87N)

Overcurrent protection (50, 51, 67)

Earth fault protection (50N, 51N, 67N)

Neutral earth fault protection (50G, 51G, 67G)

Thermal overload protection (49)

Overload protection (50OL)

Delta winding overload protection (50OL)

Overexcitation protection (24)

Overvoltage protection (59)

Circuit breaker failure protection (50BF)

Poles discordance protection (50PD)

Dead zone protection (50SH-Z)

Voltage transformer secondary circuit supervision (97FF)

Current transformer secondary circuit supervision

2 sets external trip commands (BIs BOs)

Self-supervision to all modules in the IED

Complete information recording: tripping reports, alarm reports,


startup reports and general operation reports. Any kinds of reports can
be stored up to 2000 and be memorized in case of power
disconnection

Up to three electric /optical Ethernet ports can be selected to


communicate with substation automation system by IEC61850 or
IEC60870-5-103 protocols

Up to two electric RS-485 ports can be selected to communicate with

Chapter 1 Introduction
substation automation system by IEC60870-5-103 protocol

Time synchronization via network(SNTP), pulse and IRIG-B mode

Configurable LEDs and output relays satisfied users requirement

Versatile human-machine interface

Multifunctional software tool CSmart/CSPC for setting, monitoring,


fault recording analysis, configuration, etc.

Chapter 1 Introduction
Protection functions
IEC 61850
Description

ANSI Code

Logical Node
Name

IEC 60617
graphical symbol

Differential protection
Transformer differential protection

87T

PDIF

Restricted earth fault protection

87N

PDIF

Current protection
3IINV>
Overcurrent protection

50,51,67

PTOC

3I >>
3I >>>
I0INV>

Earth fault protection

50N, 51N, 67N

PEFM

I0>>
I0>>>

Neutral earth fault protection

50G, 51G, 67G

Thermal overload protection

49

PTTR

Ith

Overload protection

50OL

PTOC

3I >OL

Delta Winding Overload Protection

50OL

U/f>

Voltage protection
Overexcitation protection

24

PVPH

Overvoltage protection

59

PTOV

3U>
3U>>

Breaker protection and control function


3I> BF
Breaker failure protection

50BF

RBRF

I0>BF
I2>BF

Dead zone protection

50SH-Z
3I< PD

Poles discordance protection

50PD

RPLD

I0>PD
I2>PD

Secondary system supervision


CT secondary circuit supervision
VT secondary circuit supervision
Other functions
2 sets external trip commands (BIs
BOs)

Chapter 1 Introduction
Monitoring functions
Description
Auxiliary contacts of circuit breaker supervision
Self-supervision
Fault recorder

Station communication
Description
Front communication port
Isolated RS232 port
Rear communication port
0-2 isolated electrical RS485 communication ports
0-3 Ethernet electrical/optical communication ports
Time synchronization port
Communication protocols
IEC 61850 protocol
IEC 60870-5-103 protocol

Digital communication network through converter

IED software tools


Functions
Reading measuring value
Reading IED report
Setting
IED testing
Disturbance recording analysis
IED configuration
Printing

Chapter 1 Introduction

Chapter 2 Basic protection elements

Chapter 2 Basic protection elements

About this chapter


This chapter describes basic protection elements including
startup elements, phase selectors and directional elements.

Chapter 2 Basic protection elements

Startup element

1.1

Introduction
Startup elements are designed to detect a faulty condition in the power
system and initiate all necessary procedures for selective clearance of
the fault. The main startup element of CSC-326 is current
sudden-change startup element(abrupt current), the backup startup
element is diffrential current startup elment.
Startup element includes:

1.2

Current sudden-change startup element(abrupt current)

differential current startup element

Sudden-change current startup element


Sudden-change current startup element is the main startup element that
can sensitively detect most of faults. Its criteria are as followings:

i I _ startup

i i (t ) 2 i (t T ) i (t 2T )
where
I_startup is a fix threshold value(IQd =0.2A when the secondary
value of CT is 1A, and IQd =1A when secondary value of CT is 5A)

1.3

Differential current startup element


I d max I _ diff startup

I d max Max I d , a, b, c

I _ diff startup 0.8I _ percent diff


where

10

Chapter 2 Basic protection elements


I_diff startup is the startup threshold of differential protection,
I_Percent Diff is a setting value, and Idis the phase differential current.

Input and output signals


Sudden-change current
startup element
IA1

Relay Startup

IB1
IC1
IA2
IB2
IC2
IA3
IB3
IC3
IA4
IB4
IC4
IA5
IB5
IC5

Figure 1 Sudden-change current startup element

11

Chapter 2 Basic protection elements

Differential current
startup element
IA1

Relay Startup

IB1
IC1
IA2
IB2
IC2
IA3
IB3
IC3
IA4
IB4
IC4
IA5
IB5
IC5

Figure 2 Differential current startup element


Table 1 Analog input list

Signal

Description

IA1

Phase A current input of 1st CT set

IB1

Phase B current input of 1st CT set

IC1

Phase C current input of 1st CT set

IA2

Phase A current input of 2nd CT set

IB2

Phase B current input of 2nd CT set

IC2

Phase C current input of 2nd CT set

IA3

Phase A current input of 3th CT set

IB3

Phase B current input of 3th CT set

IC3

Phase C current input of 3th CT set

IA4

Phase A current input of 4th CT set

IB4

Phase B current input of 4th CT set

IC4

Phase C current input of 4th CT set

IA5

Phase A current input of 5th CT set

IB5

Phase B current input of 5th CT set

12

Chapter 2 Basic protection elements

Signal

Description

IC5

Phase C current input of 5th CT set

Table 2 Binary output list

Signal

Description

Relay Startup

Relay Startup

Settings
Table 3 Settings of basic protection element

Setting

Unit

HV Wind Conn/Y

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
0

Connection for HV winding,


0:wye connection, 1:delta
connection

MV Wind Conn/Y

Connection for MV winding,


0:wye connection, 1:delta
connection

LV Wind Conn/Y

Connection for LV winding,


0:wye connection, 1:delta
connection

Vet Grp Angle

MVA

1.000

3000.

120.0

Vector Group Angle( VET


GRP ANGLE)

SN

kV

1.000

1000.

220.0

Capacity of the transformer

HV VT Ratio

MVA

1.000

9999.

2200.0

Voltage transformer(VT) Ratio in HV side

50.00

9999.

1200.0

HV CT Pri

HV side
A

1.000

5.000

1.0

HV CT Sec
HV Voltage Chan

Sel

CT Secondary(SEC) current
in HV side

Sel
MV Voltage Chan

CT Primary(PRI) current in

HV voltage channel location


MV voltage channel location
13

Chapter 2 Basic protection elements

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

50.00

9999.

Default
setting
(Ir:5A/1

Description

A)
1200.0

HV NCT Pri(REF)

Neutral CT (NCT) Primary(PRI) current in HV side


for REF

1.000

5.000

1.0

HV NCT Sec(REF)

Neutral CT (NCT) Secondary(SEC) current in HV side


for REF

50.00

9999.

1200.0

HV NCT Pri(BU)

Neutral CT (NCT) Primary(PRI) current in HV side


for backup protection

1.000

5.000

1.0

HV NCT Sec(BU)

Neutral CT (NCT) Secondary(PRI) current in HV side


for backup protection

kV

1.000

1000.

110.0

MV UN

Nominal voltage (UN) in


Middle voltage (MV)side

1.000

9999.

1100.0

MV VT Ratio

Voltage transformer(VT) Ratio in MV side

50.00

9999.

1200.0

MV CT Pri

CT Primary(PRI) current in
MV side

1.000

5.000

1.0

MV CT Sec

CT Secondary(SEC) current
in MV side

50.00

9999.

1200.0

MV NCT Pri(REF)

Neutral CT (NCT) Primary(PRI) current in MV side


for REF

1.000

5.000

1.0

MV NCT Sec(REF)

Neutral CT (NCT) Secondary(SEC) current in MV


side for REF

50.00

9999.

1200.0

MV NCT Pri(BU)

Neutral CT (NCT) Primary(PRI) current in MV side


for backup protection

1.000

5.000

1.0

MV NCT Sec(BU)

Neutral CT (NCT) Secondary(PRI) current in MV side


for backup protection

kV

1.000

1000.

10.50

LV UN

voltage (LV)side
1.000

LV VT Ratio

14

Nominal voltage (UN) in Low

9999.

105.0

Voltage transformer(VT) Ratio in LV side

Chapter 2 Basic protection elements

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

50.00

9999.

Default
setting
(Ir:5A/1
A)
3000.0

LV CT Pri

CT Primary(PRI) current in
LV side

1.000

5.000

1.0

LV CT Sec
LV Sec Inside

Description

CT Secondary(SEC) current
in LV side

1.000

5.000

Delta

1.0

CT Secondary(SEC) current in LV inside delta

9999

HV Rated Cur Pri

Rated primary current for


HV side (calculated value,
read only)

9999

HV Rated Cur Sec

Rated secondary current for


HV side (calculated value,
read only)

9999

Ratio Factor KTAH

HV ratio factor for differential protection (calculated


value, read only)

9999

Ratio Factor KTAM

MV ratio factor for differential protection (calculated


value, read only)

9999

Ratio Factor KTAL

LV ratio factor for differential


protection (calculated
value, read only)

9999

HV ratio factor, with zero-sequence current calcu-

Ratio REF KTAH

lated, for REF protection


(calculated value, read
only)
0

9999

HV ratio factor with zero-sequence current directly

Ratio REF KNH

measured, for REF protection (calculated value,


read only)
0

9999

MV ratio factor, with zero-sequence current calcu-

Ratio REF KTAM

lated, for REF protection


(calculated value, read
only)

15

Chapter 2 Basic protection elements

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

9999

Default
setting
(Ir:5A/1

Description

A)
MV ratio factor with zero-sequence current directly

Ratio REF KNM

measured, for REF protection (calculated value,


read only)

Table 4 Binary settings of basic protection

Setting

Unit

Min.

Max.

Default
setting

Description
Autotransformer not comm
on transformer

Auto Trans

1-autotransformer ;
0- not autotransformer

Two-Wind Trans

Two-winding(TWO WIND )
not three -winding
0

trans-

former (TRANS)
1-two-winding trans;
0-three-winding trans

CT Fail Detect

VT Failure Detection On/Off


1-On, 0-Off.

Report
Table 5 Event report list

Information
Relay startup

16

Description
The relay is initiated by startup elements

Chapter 3 Differential protection

Chapter 3 Differential protection

About this chapter


This chapter describes the protection principle, input and
output signals, parameter, IED report and technical data for
differential protection function.

17

Chapter 3 Differential protection

Introduction
The numerical current differential protection represents the main protection function of the IED. It provides a fast short-circuit protection for
power transformers. The protected zone is selectively limited by the CTs
at its ends. The device is able to perform this function on 2 or 3 winding
transformers in a variety of voltage levels and protected object types.

Applications
The IED provides numerical differential protection function which can be
used to protect power transformers in various configurations. For example, it is possible to use it for a two-winding transformer, three-winding
transformer as well as auto-transformer. Examples for some of applications are illustrated in the below figure.
HV

I A.1

LV

Ia.2

A
I B.1

Ib .2

I C .1

Ic .2

a
b

CSC-326

Figure 3 Application of differential protection on a two-winding Yd


transformer
I A.1

Ia.2

A
IB.1

IC .1

Ic .2

CSC-326

18

Ib .2

Chapter 3 Differential protection


Figure 4 Application of differential protection on an auto
transformer

LV

HV

I A.1

Ia.2

A
IB.1

Ib .2

IC .1

Ic .2

B
C

CSC-326

Figure 5 Application of differential protection on a two-winding Yd


transformer with earthing transformer inside the protected zone
MV
Ia.2

Ib .2

b
I A.1

Ic .2

HV

I B.1

B
I C .1

LV

Ia.3

Ib .3

b
Ic .3

CSC-326

Figure 6 Application of differential protection on a three-winding


Ydd transformer

Protection algorithm
This section describes basic principle of differential protection function.
19

Chapter 3 Differential protection


First, the case of a single phase transformer with two windings is considered. The basic principle is based on current comparison at two sides
of the protected object. Indeed, the differential protection function makes
use of the fact that a protected object carries always the same current at
its two sides in healthy operation condition. This current flows into one
side of the protected object and leaves it from the other side. A difference
in currents is an indication of a fault within this section. An example of this
condition is shown in below figure, when a fault inside the protected zone
causes a current I1prim. + I2prim. flowing in from both sides of the protected
object.

Protected Zone
I2-prim.

I1-prim.
CT-1

CT-2

Protected
Transformer

I2

I1
CSC-326

Figure 7 Basic principle of differential protection for two ends


(single phase)
For protected objects with three or more sides, the basic principle is expanded in that the total of all currents flowing into the protected object is
zero in healthy operation, whereas in case of a fault the total in-flowing
current is equal to the fault current.
When an external fault causes a heavy current to flow through the protected transformer, differences in the magnetic characteristics of the
current transformers CT-1 and CT-2 under saturation condition may
cause a significant difference in the secondary currents I1 + I2 connected
to IED. If the difference is greater than the pickup threshold, the differential protection function can trip even though no fault occurred in the protected zone. To prevent the protection function from such erroneous operation, a restraint (stabilizing) current is brought in. For differential protection IED, the restraint current is normally derived from the I1 and I2.
The next subsection goes on to demonstrate how the differential and restraint currents are calculated.

3.1
20

Differential and restraint current calculation

Chapter 3 Differential protection


The differential current Idiff and the restraining current Ires are calculated
by the following equation. The following definitions apply for each phase
of the protected object.
N

Ii
I diff

i 1

N 1
1

I i (i j )
j
(max)
res

i 1

Equation 1

Where I i is the current vector of side i, corresponding to HV, MV and LV


windings; N is total current inputs of the IED. In other words, it is number
of the protected object sides;

I j (max)

is the maximum current vector

among the N current inputs of the IED, suppose it is side j;

N 1
I i (i j )
i 1

is

the sum of the other current inputs of the IED, not including side j. Idiff is
derived from the fundamental frequency current and produces the tripping effect quantity, whereas Ires counteracts this effect. To clarify the
situation, three important operating conditions with ideal and matched
measurement qualities are examined.
(a) External fault under undisturbed conditions:
I1 flows into the protected zone, I2 leaves the protected zone, i.e. is
negative according to the definition of signs, therefore I2 = I1.
Idiff = I1 + I2 = I1 I1 = 0
Ires = 0.5| I1 - (I1) | = 0.5|2I1| = |I1|
No tripping effect (Idiff = 0); the restraint (Ires) corresponds to the external fault current flowing through the protected object.
(b) Internal fault, fed with equal currents from both sides:
The following applies I2 = I1
Idiff = I1 + I2 = I1 + I1 = 2 I1
Ires = 0.5| I1 - I1| = 0
21

Chapter 3 Differential protection


Tripping effect (Idiff) corresponds to double the fault current, and restraint
value (Ires) are equal to zero.
(c) Internal fault, fed from one side only:
The following applies when assuming I2 = 0
Idiff = I1 + I2 = I1 + 0 = I1
Ires = 0.5|I1 - I2| =0.5 |I1 - 0| = 0.5|I1|=0.5 I1
Tripping quantity (Idiff) and restraint quantity (Ires) are equal and correspond to the single-sided fault current.
The results show that the device is capable to properly discriminate internal and external faults by using the definitions proposed for differential
and restraint current. However, the device is still subjected to some influences that induce differential currents even during normal operation
condition. These influences should be compensated in appropriate
manners. The specific treatments designed to cope with these influences
includes automatic ratio compensation and automatic vector group
compensation which are explored in the next subsections.

3.2

Automatic Ratio compensation


Differential protection of power transformers represents some problems
in the application of current transformers. CTs should be matched to the
current rating of each transformer winding, so that normal current through
the power transformer is equal on the secondary side of the CT on different windings. However, because only standard CT ratios are available,
this matching may not be exact. As a result, the secondary currents of the
current transformers are not generally equal when a current flows
through the power transformer. The difference between the currents
flowing through CTs secondary circuit depends on the transformation ratio of the protected power transformer, as well as the rated currents of the
current transformers. Therefore, the currents should be matched in order
to become comparable. To do so, the input currents of the IED are converted in relation to the power transformer rated currents. This is
achieved by entering the characteristic values of the power transformer
(i.e. rated apparent power and rated voltages) and primary rated currents
of CTs into the IED by using user-entered settings. As a result, matching
to various power transformer and current transformer ratios is performed
purely mathematically inside the device. Therefore, no external matching

22

Chapter 3 Differential protection


transformer is required. In this context, the rated primary current of each
side, I1N, is calculated automatically according to below equation.

I 1N

SN
3U 1N

Equation 2
Where SN is rated apparent power of the transformer and U1N is rated
voltage of the corresponding side.
The rated secondary current of each side, I2N, is then calculated.

I 2N

I1N
nCT
Equation 3

Rated secondary current of the high voltage side is then taken as the
reference current. The currents of the other sides are automatically
matched to the rated current of the high voltage side by calculation of
correction factor KCT for MV and LV side, according to below equations,
respectively:

K CT MV

I 2 N HV
I
/n
S / 3U 1N HV nCT MV U 1N MV nCT MV
1N HV CT HV N

I 2 N MV I 1N MV / nCT MV S N / 3U 1N MV nCT HV U 1N HV nCT HV

Equation 4

K CT LV

I 2 N HV I 1N HV / nCT HV S N / 3U 1N HV nCT LV U 1N LV nCT LV

I 2 N LV
I1N LV / nCT LV
S N / 3U 1N LV nCT HV U 1N HV nCT HV

Equation 5
Where KCT-MV is the correction factor for middle voltage side and
KCT-LV is the correction factor for Low voltage side,
23

Chapter 3 Differential protection


I1N is the primary rated current of the transformer (I1N-HV for high voltage side, I1N-MV for middle voltage side and I1N-LV for low voltage
side),
I2N is the secondary rated current of the transformer (I2N-HV for high
voltage side, I2N-MV for middle voltage side, I2N-LV for low voltage
side),
nCT is CT ratio of the transformer (nCT-HV for high voltage side, nCT-MV
for middle voltage side, nCT-LV for low voltage side),
U1N is rated voltage of the transformer (U1N-HV for high voltage side,
U1N-MV for middle voltage side, U1N-LV for low voltage side).
As mentioned previously, all of the calculations are automatically performed inside the IED by its CPU. The related settings can be found
under the menu Test Menu.
Below figure shows an example of automatic ratio compensation in case
of a two-winding transformer. The primary nominal currents of the HV and
LV sides, (I1N = 402A, I2N= 1466A) are calculated from the rated apparent power of the transformer (160MVA) and the nominal voltages of
each side (230kV and 63kV). Since the nominal currents of the current
transformers deviate from the nominal currents of the power transformer
sides, the secondary current of LV side is multiplied with the factor
KCT-LV. Subsequent to this matching, equal current magnitudes are
achieved at both sides under nominal conditions of the power transformer.

SN=160MVA
U1N-HV=230kV

CTRATIO=500/1A

U1N-LV=63kV

CTRATIO=2000/1A

Figure 8 Example of automatic ratio compensation in a two-winding


transformer

24

I1N HV

160MVA
402 A
3 230

I 2 N HV

I 1N HV 402

0.804 A
nCT
500

Chapter 3 Differential protection


I1N LV

160 MVA

I 2 N LV

1466
0.733 A
2000

3 63

K CT LV

1466 A

0.804
1.097
0.733

Concerning three-winding power transformers, the windings may have


different power ratings. In order to compare secondary currents in an
appropriate manner, all currents are matched to the rated secondary
current of HV winding having highest power rating. This apparent power
is nominated as the rated apparent power of the transformer.
Below figure shows an example of a three-winding power transformer.
HV winding and MV winding are rated for 160MVA. The rated primary
and secondary currents of these windings are calculated as shown in
previous example. However, the LV winding has 25MVA rating (e.g. for
auxiliary supply). The rated current of this winding may result in 721A.
However, differential protection has to process comparable currents.
Therefore, the currents of LV winding should be referred to the rated
apparent power of the transformer, i.e. 160MVA. This results in a rated
current of 4619A. This is the base value for the LV winding, which should
be further multiplied by KCT-LV to be used in calculation process of differential protection.

160MVA

160MVA

U1N-HV=230kV

U1N-MV=63kV

CTRATIO=2000/1A

CTRATIO=500/1A
U1N-LV=20kV

25MVA
CTRATIO=2500/1A

Figure 9 Example of automatic ratio compensation in a


three-winding transformer
I1N LV

160 MVA
3 20

4619 A

I 2 N HV

I 1N LV 4619

1.848 A
nCT
2500

K CT LV

0.804
0.435
1.848

25

Chapter 3 Differential protection


If a three-winding transformer with a delta LV winding (with no CB installed) is used to supply substation LVAC loads, it may be desired that
LV current should not be integrated in differential protection. In this case,
Binary setting Diff Includes LV Cur is used to select whether LV current
should be included in differential protection calculation procedure or not.
By applying setting Diff Includes LV Cur to 0, only HV and MV currents
would be included in differential protection calculation. On the contrary,
when a three-winding transformer is equipped with three CBs in its sides,
it may be desired to include LV current in differential protection. This can
be achieved by applying setting Diff Includes LV Cur to 1 to respective
Binary setting.

3.3

Automatic Vector group and zero sequence


current compensation
Transformers have different vector groups, which cause a shift of the
phase angles between the primary and the secondary side. Without adequate correction, this phase shift would cause a false differential current.
Furthermore, the conditioning of the starpoint(s) of the power transformer
has a great impact on the resulting differential current during through fault
currents.
The IED removes this problem. To do so, all CTs at the power transformer are connected Wye (polarity markings pointing away from the
transformer). User-entered settings in the relay are then used to characterize the power transformer and allow the relay to automatically perform all necessary phase angles, and zero sequence compensation. This
section describes the procedures that perform this compensation inside
the relay and produce the required calculated quantities for transformer
differential protection. The phase angle compensation as well as zero
sequence current elimination procedure is performed by programmed
coefficient matrices which are capable to simulate the difference in phase
angle of currents flowing through transformer windings. Thus, compensation is possible for the entire commonly used transformer vector
groups. This simplifies application of the IED in various configurations, if
the setting corresponding to vector Group Angle, Vet Grp Angle, is
properly entered into the device, together with the settings for connection
type of transformer windings in each side, HV WIND CONN/Y-0 D-1,
MV WIND CONN/Y-0 D-1, LV WIND CONN/Y-0 D-1, which could be
set to 1-delta or 0-wye. The basic principle of numerical vector group and
zero-sequence compensation is shown through some examples. A
through review of all possible connection groups as well as device

26

Chapter 3 Differential protection


treatment in each case is explored in Appendix.
(1). Take example for Yy0 connection, including similar ones of Yy0
(separate or auto-connected windings), YNy0, Yyn0, YNyn0 (separate or
auto-connected windings) and so on. Below figure shows an example in
case of Yy0 connection group with no earthed starpoint. The figure
shows the windings (left) and the vector diagrams of symmetrical currents (right).
A

C
A
a

Yy0

Figure 10 Vector Group and zero sequence compensation for Yy0


transformer
The equations including the coefficient matrix are as follow:

I A
1 -1
1
0 1
I B
3
I
-1 0
C

0 I A

-1 I B
1 I C

Equation 6

I a
1 -1
1
0 1
I b
3
I
-1 0
c

0 Ia

-1 I b
1 I c

Equation 7

According to these matrices, if we deduct side 1 currents I A I B , the re27

Chapter 3 Differential protection

sulting current I A has the same direction as I A on side 2. Multiplying it

with 1 3 , matches the absolute value. The matrices describe the conversion for all three phases. Using these matrices, the elimination of zero
sequence currents are warranted regardless of starpoint earth connection.
As mentioned previously, the two above equations can be used similarly
for auto-transformers, as the auto-connected windings in auto-transformers can only be connected Y(N)y(n)0. If the starpoint is
earthed, both the auto-connected HV and LV windings are affected. The
zero sequence components in current flowing through both sides of the
transformer are then coupled because of the common starpoint. These
zero sequence components are eliminated by the application of the matrices presented in the above equations.
(2). Take example for Yd1 connection, including similar ones of Yd1 and
YNd1 without earthing transformer installed at delta side. Below figure
shows an example in case of Yd1 connection group with no earthed
starpoint.

C
A
a

Yd1

Figure 11 Vector Group compensation for Yd1 transformer


The equation including the coefficient matrix is as follows:

I A
1 0
1
-1 1
I B
3
I
0 -1
C
28

-1 I A

0 I B
1 I C

Chapter 3 Differential protection


Equation 8
If an earthing transformer/reactor is installed inside the protected zone on
delta side, the IED should be informed about it by Binary setting HV
D_side Eliminate I0, MV D_side Eliminate I0 or LV D_side Eliminate
I0. The Binary setting related to delta side with earthing connection
should be set to 1-eliminate in such condition. By taking example for
Yd1 connection with earthing transformer installed at delta side, Binary
setting LV D_side Eliminate I0 is set to 1-eliminate, and thus, device
performs a zero sequence current elimination on delta side. In this case,
the equations including the coefficient matrices are as follow:

I A
1 0
1
-1 1
I B
3
I
0 -1
C

-1 I A

0 I B
1 I C

Equation 9

I
I
a

2 1 1 a

1
. I

1
2

1
b

b
3

1 1 2
I c
I c


Equation 10
(3). Take example for Ydd3 connection, including similar ones of Ydd3
and YNdd3 without earthing transformer installed at delta sides. Below
figure shows an example in case of Ydd3 connection group with no
earthed starpoint in Wye side.

29

Chapter 3 Differential protection


A

A
c(c)

a(a)

Ydd3
C

c'

a'

b(b)

b'

Figure 12 Vector Group compensation for Ydd3 transformer


The equation including the coefficient matrix is as follows:

I A
0 1
1
-1 0
I B
3
I
1 -1
C

-1 I A

1 I B
0 I C

Equation 11

(4). Take example for Yd5 connection, including similar ones of Yd5 and
YNd5 with earthing transformer installed at delta side. Below figure
shows an example in case of Yd5 connection group with no earthed
starpoint.

C
A
c

Yd5

30

Chapter 3 Differential protection


Figure 13 Vector Group compensation for Yd5 transformer
By setting binary setting LV D_side Eliminate I0 to 1-eliminate, the
equations including the coefficient matrices are as follow:

I A
-1 1
1
0 -1
I B
3
I
1 0
C

0 I A

1 I B
-1 I C

Equation 12

I
I
a

2 1 1 a
1
. I

1
2

1
b

b
3 1 1 2

I c
I c


Equation 13
(5). Take example for Dy1 connection, including similar ones of Dy1 and
Dyn1 without earthing transformer installed at delta side. Below figure
shows an example in case of Dy1 connection group with no earthed
starpoint.

A
a

Dy1

c
b

Figure 14 Vector Group compensation for Dy1 transformer


The equation including the coefficient matrix is as follows:

31

Chapter 3 Differential protection


I a
1 -1
1
0
1
I b
3
I
-1 0
c

0 I a

-1 I b
1 I c

Equation 14

If an earthing transformer/reactor is installed inside the protected zone on


delta side, binary setting HV D_side Eliminate I0 is set to 1-eliminate,
and thus, device performs a zero sequence current elimination on delta
side. In this case, the equations including the coefficient matrices are as
follow:



I
I
A

2 1 1 A
1

I B . 1 2 1. I B
3 1 1 2

I C
I C


Equation 15

I a
1 -1
1
0
1
I b
3
I
-1 0
c

0 I a

-1 I b
1 I c

Equation 16

Subsequent to application of the magnitude, vector group and zero sequence compensation, the IED use the following calculated quantities
(per phase) to discriminate between internal and external faults: fundamental component of differential and restraint currents together with instantaneous value, 2nd and 5th harmonic contents of differential current.
The following sections go on to demonstrate the fault recognition criteria
using these derived quantities.

Protection principle

4.1

Instantaneous differential protection


characteristic

32

Chapter 3 Differential protection


An instantaneous (unrestrained) differential characteristic which entails
an overcurrent protection is provided for fast tripping on heavy internal
faults. The characteristics can be enabled or disabled by using Binary
setting Func_Inst Diff (1-on, 0-off). If setting 1-on is selected, a trip
signal is issued regardless of the magnitude of the restraining current, as
soon as the differential current rises above the threshold ID>> (setting "
I_Inst Diff "). The generated trip signal is phase selective. it means that
the device issues event reports Inst Diff Trip A, Inst Diff Trip B or Inst
Diff Trip C, when the calculated differential current in phase A, B or C
exceeds the threshold ID>> (setting " I_Inst Diff "). The purpose of this
stage of differential protection is extremely fast operation in case of high
magnitude internal fault currents. This is always the case when the short
circuit current is higher than IN/Uk%, which indicates a fault inside the
power transformer. It should be noted that the magnitude of through fault
currents are always lower than IN/Uk%, when they are supplied via
power transformer. In this equation, IN is nominal current and Uk% is
short circuit voltage of the power transformer.
The logic diagram of instantaneous differential protection is shown in
below figure.

Ia>I_Inst Diff
AND

INST DIFF TripA

AND

INST DIFF TripB

AND

INST DIFF TripC

Func_Inst Diff On

Ib>I_Inst Diff

Ib>I_Inst Diff

Figure 15 Tripping logic of the instantaneous differential protection


As mentioned previously and can be seen from the figure, the stage operates as an unrestrained protection function. In other words, it is not inhibited by any of harmonic stabilization features of the percent differential
element as well as the CT failure detection. This means that it can operate even when, for example, a considerable second harmonic is present
in the differential current, which is caused by current transformer saturation by a DC component in the fault current, and which could be interpreted by the inrush inhibit function as an inrush current.

33

Chapter 3 Differential protection


This high current stage evaluates the fundamental component of the differential current as well as the instantaneous values. Instantaneous value
processing ensures fast tripping even in case the fundamental component of the current is strongly reduced by current transformer saturation.
Fast trip area is shown in Figure 16.

4.2

Treble slope percent differential protection


characteristic
The percent differential protection uses a treble-slope dual break-point
operating characteristic with magnetizing inrush and overexcitation and
CT failure detection inhibits integrated. The treble slope characteristics
can be enabled or disabled by using Binary setting Func_Percent Diff
(1-on, 0-off). If setting 1-on is selected, the stage calculates differential
and restraint current separately in each phase to obtain operating point in
each operation condition. The derived point is then mapped into Idiff-Ires
plane to examine whether it lies in trip or block area which is defined
according to predefined operating characteristic. The operation characteristic is shown in below figure.

IDiff
Fast trip area
Differential current

I_Inst Diff

Slope 3

Trip area
Slope 2
Slope 1

block area
IRest

I_Percent Diff
I_ResPoint1 Diff

I_ResPoint2 Diff

Restraint current

Figure 16 Differential protection characteristics for transformers


In this characteristic, branch 1 represents the sensitivity threshold of the
differential protection. The setting of ID> (setting "I_Percent Diff") defines
the minimum differential current required for operation. The setting is
chosen based on the amount of differential current that might be seen
under normal operating conditions which corresponds to constant error
currents such as magnetizing currents and CT errors under no-load con34

Chapter 3 Differential protection


ditions. The setting for slope of branch 1 is applicable for restraint currents of zero to the first break-point indicated on restraint axis (setting
"I_ResPoint1 Diff"). The slope (setting Slope1_Diff) defines the ratio of
differential to restraint current above which the percent differential stage
will operate. The first break-point on restraint axis defines the end of the
slope 1 region and the start of the second branch region. This setting
should be set just above the maximum operating current level of the
transformer. This level is somewhere between the maximum
forced-cooled rated current of the transformer and the maximum emergency overload current level.
Branch 2 considers current-proportional errors which may result from
transformation errors of the main CTs or the input CTs of the relay. This
may also contain the error caused by the influence of tap changers in
power transformers with voltage control. The setting for slope of branch 2
(setting Slope2_Diff) is applicable for restraint currents of the first
break-point to the second one on restraint axis, and defines the ratio of
differential to restraint current above which the element will operate. This
slope is set to ensure sensitivity to internal faults at normal operating
current levels. The second break-point on restraint axis (setting
I_ResPoint2 Diff) defines the end of the slope 2 region and the beginning of the slope 3 region. This setting should be set to the level at which
any of the protection CTs is probable to saturate.
In the range of high through fault currents which may give rise to high
differential currents as a result of CT saturation, branch 3 is applicable to
provide additional stabilization. The setting for the slope of this branch
(setting Slope3_Diff) is applicable up to the point at which the branch
intersects the characteristic of instantaneous differential protection.
As a summary of the fault detection using operating characteristics of the
above figure, the calculated differential and restraint currents, IDiff and
IRest, are compared by the differential protection with the operating
characteristic according to the following formula ,

I res I R1

S2 ( I res I R1 ) S1 I R1 I D
I R1 I res I R 2

S3 ( I res I R 2 ) S2 ( I R 2 I R1 ) S1 I R1 I D I R 2 I res

I diff S1I res I D


I diff
I diff

Equation 17
Where S1 is the slope of the branch 1 (setting Slope1_Diff),
35

Chapter 3 Differential protection


S2 is the slope of the branch 2, (setting Slope2_Diff),
S3 is the slope of the branch 3, (setting Slope3_Diff),
ID> is the setting for the sensitivity threshold of the differential protection,
(setting I_Percent Diff),
IR1 is the setting for the first breakpoint restraint current, (setting
I_ResPoint1 Diff),
IR2 is the setting for the second breakpoint restraint current, (setting
I_ResPoint2 Diff).
If the operating point calculated from the quantities of differential and restraint current falls into the trip area, a trip signal is issued by the percent
differential protection. The issued signals are phase selective. They can
be found in event report as Per Diff Trip A, Per Diff Trip B and Per Diff
Trip C.
This stage cannot operate when there is an inrush or overexcitation stabilization or a restraint due to CT failure detection. This is illustrated in
below logic diagram.

Func_Percent Diff on

Phase-A

I diff A , I rest A
ID>

A
N
D

PER DIFF Trip A

A
N
D

PER DIFF Trip B

A
N
D

PER DIFF Trip C

PER DIFF BLK A


Phase-B

I diff B , I rest B
ID>

PER DIFF BLK B


Phase-C

I diff C , I rest C
ID>

PER DIFF BLK C

Block Diff at CT_Fail on

CT FAIL

Figure 17 Tripping logic of the percent differential protection


It should be noted that when the IED is delivered, both the instantaneous
and percent differential protection functions are switched off. Setting of
0-off is applied for Binary settings Func_Inst Diff and Func_Percent
36

Chapter 3 Differential protection


Diff. This is because the fact that these protection functions should not
be used before at least the vector group and other essential parameters
for each side is correctly set. Without these settings the equipment may
show unpredictable behavior. (E.g. tripping)

4.3

Selective inrush stabilization schemes


In power transformers, high short-time magnetizing currents may be
present during power-up (inrush currents). The inrush current can
amount to a multiple of the rated current. These currents enter the protected zone. However, it does not exit again. They thus produce differential quantities, as they seem like single-end fed fault currents. Therefore,
they should be recognized in an appropriate manner. By this way, it is
possible to prevent false operation of differential protection caused by
inrush current. This possibility is provided in the IED. Selective inrush
stabilization can be enabled or disabled by Binary setting Block Diff at
Inrush, (1-Block, 0-Not Block). If setting 1-Block is applied, the function
monitors differential current to detect an inrush condition. If the condition
is detected, it is possible to block differential protection phase-selectively.
Furthermore, alarm report entitled Diff 2har Blk is issued whenever inrush detection impose a blocking condition to differential protection. It
should be noted that the latter, is generated when any condition (2nd
harmonic, 3rd/5th harmonic, CT fail) leads to blocking of differential protection.
The IED provides two schemes to detect inrush conditions. The first
scheme is 2nd harmonic stabilization; the second scheme is fuzzy
recognition of inrush conditions based on the waveform. The two
schemes are convenient for user to be selected by the setting 2nd HAR
NOT WAVE (1-2nd harmonic on; 0-waveform on). The two implemented
algorithm work alternatively. As soon as an inrush condition is recognized
by each of them, a restraint condition is applied to the respective phase
evaluation of percent differential protection. Since the applied restraint by
2nd harmonic detection operates individually per phase, the protection is
fully operative even when the protected transformer is switched onto a
single-phase fault, whereas inrush currents may possibly be present in
one of the healthy phases. It is, however, possible to set the protection in
a way that when the 2nd harmonic recognition is fulfilled only in one single phase, not only the phase with the inrush current, but also the remaining phases of the percent differential protection are blocked. This is
achieved by cross-blocking the differential protection for a certain period
to avoid spurious tripping. The setting corresponds to T_2nd Harm
Block. Within this time, all three phases are blocked as soon as an in37

Chapter 3 Differential protection


rush current is detected in any one phase. After the timer is expired, only
the phase with inrush current content is blocked.

4.3.1

2nd harmonic stabilization


By selecting 1-Block for control-word Block Diff at Inrush and selecting1-2nd harmonic for Binary setting 2nd HAR NOT WAVE, inrush
current is recognized if the second harmonic content in the differential
current exceeds a selectable threshold (setting Ratio_2nd Harm). The
ratio between the 2nd harmonic and the fundamental frequency component is decisive to discriminate inrush conditions from the other operation
conditions. The ratio is calculated by the below equation. As soon as the
measured ratio exceeds the set thresholds, a restraint is applied to the
percent differential protection in respective phase.
I diff 2
I diff

K 2

Equation 18
Where Idiff-2 is 2nd harmonics magnitude of differential current, K2 is
the setting for 2nd harmonics ratio, Idiff- is fundamental frequency
component of differential current.

4.3.2

Fuzzy recognition of inrush based on the waveform


By selecting 1-block in control-word Block Diff at Inrush, and selecting
0-waveform on for Binary setting 2nd HAR NOT WAVE, inrush current
is detected by a fuzzy recognition method based on waveform. In this
context, differential current waveform is sampled in each phase by 2n
number of samples per cycle, each of the samples is nominated as I(k),
k=1, 2, , 2n. Then the value of X(k) is calculated according to the below
equation.

X (k )

I ( k ) I ( k n)
I ( k ) I ( k n)

, k 1,2,..., n

Equation 19
The smaller values of X(k) represent that the calculated point corre38

Chapter 3 Differential protection


sponds to fault condition with higher confidence level. Alternatively, the
larger values of X(k) gives a picture that there is large content of inrush
current in the waveform. Assume that X(k) belongs to inrush Fuzzy
class with membership function of A[X(k)]. Then, the fuzzy similarity coefficient for the n calculated values of X(k) in one cycle is defined as below equation.
n

A[ X (k )] / n
k 1

Equation 20
The derived value of N is used in the IED to assess the differential current corresponds to inrush condition or not. To do so, the value of N is
compared with a threshold K, and inrush content is recognized in the
current waveform, if N>K.
Func_Percent Diff on

I diff A 2
I diff A

I diff B 2
I diff B

I diff C 2
I diff C

2nd Harm Not Wave on

K 2

2nd Harm Not Wave on

K 2

K 2

2nd Harm Not Wave on

A
N
D

A
N
D

A
N
D

T_2nd Harm Block

T_2nd Harm Block

O
R

Block Diff at Inrush on

O
R

Block Diff at Inrush on

O
R

PER DIFF BLK A

PER DIFF BLK B

Block Diff at Inrush on

PER DIFF BLK C

T_2nd Harm Block

Figure 18 logic diagram of inrush stabilization schemes by 2nd harmonic

39

Chapter 3 Differential protection

Func_Percent Diff on

Fuzzy Inrush
Recognition in
Ph-A

Fuzzy Inrush
Recognition in
Ph-B

Fuzzy Inrush
Recognition in
Ph-C

2nd Harm Not Wave off

2nd Harm Not Wave off

2nd Harm Not Wave off

A
N
D

T_2nd Harm Block

A
N
D

T_2nd Harm Block Block Diff at Inrush on

A
N
D

T_2nd Harm Block Block Diff at Inrush on

Block Diff at Inrush on

PER DIFF BLK A

PER DIFF BLK B

PER DIFF BLK C

Figure 19 logic diagram of inrush stabilization schemes by fuzzy


recognition

4.4

Overexcitation stabilization
Apart from the second harmonic, other harmonic contents can be selected in the IED to cause stabilization of percent differential protection.
This is because the fact that unwanted differential currents caused by
transformer overexcitation may result in false tripping of the percent differential protection. Since steady state overexcitation is characterized by
odd harmonics, the 3rd or the 5th harmonic can be selected in the IED to
judge for overexcitation stabilization. If it is desired to impose a blocking
condition to percent differential protection by these harmonics, Binary
setting Block Diff at Overexcit should be set to 1-on. By applying this
setting, alarm report entitled Diff 3/5har Blk is issued whenever 3rd or
5th harmonic detection impose a blocking condition to differential protection. It should be noted that the latter, is generated when any condition
(2nd harmonic, 3rd/5th harmonic, CT fail) leads to blocking of differential
protection.
It is possible to use Binary setting Overexcitation 3rd NOT 5th to select
whether 3rd or 5th harmonic detection is utilized for detection of
overexcitation condition (1-3rd harmonic, 0-5th harmonic). Since the third
harmonic is often eliminated in delta winding of power transformers, the
fifth harmonic is more commonly used.
Similar to the 2nd harmonic stabilization, the applied restraint by 3rd or

40

Chapter 3 Differential protection


5th harmonic detection operates individually per phase. It is, however,
possible to set the protection in a way that when the 3rd or 5th harmonic
recognition is fulfilled only in one single phase, not only the phase with
the inrush current, but also the remaining phases of the percent differential protection are blocked. This is achieved by cross-blocking the differential protection for a certain period to avoid spurious tripping. The setting corresponds to T_3/5th Harm Block. Within this time, all three
phases are blocked as soon as an 3rd or 5th harmonic is detected in any
one phase. After the timer is expired, only the phase with 3rd or 5th
harmonic content is blocked.
The detection method used for 3rd or 5th harmonic is similar to those
applied for 2nd harmonic. However, setting Ratio_3/5th Harm is decisive in this case. It means that 3rd or 5th harmonic is recognized if the
ratio between third or fifth harmonic and the fundamental frequency
component of the differential current exceeds the setting threshold. The
ratio is calculated by the below equation.
I diff 3 / 5
I diff

K 3 / 5

Equation 21
Where Idiff-3/5 is 3rd/5th harmonic magnitude of differential current,
K3/5 is the setting for 3rd/5th harmonic ratio, Idiff- is fundamental
frequency component of differential current. Below figure show logic diagram of overexcitation stabilization.
Block Diff at Overexcit on

I diff A 3
I diff A
I diff A 5
I diff A
I diff B 3
I diff B
I diff B 5
I diff B
I diff C 3
I diff C
I diff C 5
I diff C

K 3 / 5
Overexcit 3rd NOT 5th on

K 3 / 5

K 3 / 5

Overexcit 3rd NOT 5

th

A
off N
D

Overexcit 3rd NOT 5th on


Overexcit 3rd NOT 5th off

K 3 / 5

K 3 / 5
K 3 / 5

A
N
D

Overexcit 3rd NOT 5th on


Overexcit 3rd NOT 5th off

A
N
D

A
N
D
T_3/5th Harm Block

A
N
D

A
N
D

T_3/5th Harm Block

O
R

PER DIFF BLK A

O
R

PER DIFF BLK B

O
R

PER DIFF BLK C

T_3/5th Harm Block

Figure 20 logic diagram of overexcitation stabilization

41

Chapter 3 Differential protection


4.5

CT Failure supervision
During steady-state operation, the CT failure supervision monitors the
transient behavior of the currents flowing through secondary circuit of
each phase and thus registers failures in the secondary circuit of the
current transformers for each side of the power transformer. The function
can be enabled or disabled by using setting CT Fail Detect (1-On, 0-Off).
If setting 1-On is applied, IED issues the alarm report Ph_A CT Fail,
Ph_B CT Fail, Ph_C CT Fail, whenever a CT failure is detected. It is
also possible to set differential protection to be blocked or not at CT failure detection through setting "Block Diff at CT_Fail" (1-Block, 0-Not
Block). By setting 1-Block, the percent differential protection is blocked
immediately in all phases. Blocking condition is cancelled as soon as the
device is again supplied with a normal current in the relevant faulty
phase(s). It should be noted that the setting "Block Diff at CT_Fail" is not
useful if the differential current is very high (more than 1.2 Ie, Ie is the
rated current of high voltage side). In other words, blocking conditions
takes place only for treble slope percent differential protection. This
means that the instantaneous differential protection will issue trip if a differential current greater than setting I_Inst Diff is present, even if " Block
Diff at CT_Fail " is set to 1-Block.
The criteria for CT failure detection are as follow:
The currents flowing through all three phases of CT secondary are normal at each side of the protected object. As a result, the differential current is near to zero. When one or two phase current of one side is decreased to less than a threshold (half of the memory current), at the
same time all three phase currents in other side(s) are normal, and differential current is more than a threshold (>0.3I_Percent Diff) at least in
one phase, the condition maybe an indication of CT failure in the mutative phase(s). CT failure detection logic is illustrated in below figure.

42

Chapter 3 Differential protection

CT Fail Detect on

Max {Idiff_A, Idiff_B, Idiff_C}>0.3I_Percent Diff


Among {IHV_A, IHV_B, IHV_C} only 1
or 2 phase current decreased
Among {IMV_A, IMV_B, IMV_C}
and {ILV_A, ILV_B, ILV_C} all
currents without changing
Among {IMV_A, IMV_B, IMV_C} only 1
or 2 phase current decreased
Among {IHV_A, IHV_B, IHV_C} and
{ILV_A, ILV_B, ILV_C} all currents
without changing
Among {ILV_A, ILV_B, ILV_C} only 1
or 2 phase current decreased
Among {IHV_A, IHV_B, IHV_C} and
{IMV_A, IMV_B, IMV_C} all currents
without changing

A
N
D
A
N
D
A
N
D

CT Fail

O
R

A
N
D

Figure 21 CT Fail detection logic

4.6

CT Saturation supervision
When Internal and external faults occurs, it is possible that transient and
steady fault currents induce the CT saturation. CT saturation may lead to
mal-operation of differential protection when an external fault occurs. In
order to avoid mal-operation of protection in such situations, CT saturation supervision element is integrated in IED.
When transient saturation of CT occurs, the 2nd harmonic content in the
corresponding phase current is dominant. Also whenever steady saturation of CT occurs, the 3rd harmonic content in the corresponding phase
current is dominant. Both 2nd and 3rd harmonic contents of all phase
currents of each side of the protected transformer are calculated to judge
whether CT saturation occurs or not. Comprehensive harmonic ratio is
calculated by below equation.
I 2
I

I 3
I

K har

43

Chapter 3 Differential protection


Equation 22
Where:
I2 is 2nd harmonic magnitude of phase current at each side,
I3 is 3rd harmonic magnitude of phase current at each side,
Khar is the setting for comprehensive harmonic ratio, fixed in the software.
If the 2nd and 3rd harmonic contents of any phase current are more than
Khar, then CT satisfies the above formulas and it is saturated. Usually
before the CT saturation status, there is a short time period in which CT
still works in its linear characteristic. By very fast CT saturation detection
of IED, it needs only 4ms before any CT saturation happening to detect
the fault which is internal or external fault. In order to distinguish saturation caused by internal faults and external faults effectively, percent differential protection based on sample values is used. If CT saturation is
induced by external fault, differential protection will be blocked. However
if CT saturation is induced by internal fault, differential protection will
send its trip signal.
The typical saturation figure of phase A CT saturation is shown in below
figure.

Figure 22 Typical phase A current transformer Saturation waveform

4.7

44

Differential current supervision

Chapter 3 Differential protection


In normal operation condition, zero differential current is assumed in
each phase. The differential current supervision monitors the differential
currents and checks its value to be less than a threshold. An alarm report
is generated as Diff Cur Alarm after 5s, if the differential current exceeds the threshold value. The alarm is an indication of miss-connection
in CT secondary windings, and therefore is released to remind user to
detect the faulty connection in secondary circuit and remove it. The function can be enabled or disabled by using setting Func_Diff Alarm (1-On,
0-Off). The fixed threshold for releasing alarm is 0.3I_Percent Diff. However, to avoid incorrect alarm indications, the threshold value is increased
to 0.1A (in 1A nominal current inputs) and to 0.3A (in A nominal current
inputs), if 0.3I_Percent Diff<0.1A. This is shown in below equations.

I D.alarm max{0.3I _ Percent Diff , 0.1A}

I D.alarm max{0.3I _ Percent Diff , 0.3 A}

if I n 1A
if I n 5 A
Equation 23

Logic of differential current supervision is shown in below figure.

Func_Diff Alarm on

Idiff_A>ID.alarm
Idiff_B>ID.alarm

O
R

A
N
D

5s

DIFF Alarm

Idiff_C>ID.alarm

Figure 23 CT Fail detection logic


DANGER: Before Differential protection is put into operation on site, polarity of current transformer must have been checked right by an energizing test of every side of the transformer or a test of simulating an external
fault of the side in primary system. Otherwise a mal-operation may occur
during an external fault.

45

Chapter 3 Differential protection

Input and output signals


Differential Protection
IA1

Diff Alarm

IB1

Diff Trip

IC1

Inst Diff A Trip

IA2

Inst Diff B Trip

IB2

Inst Diff C Trip

IC2

Per Diff A Trip

IA3

Per Diff B Trip

IB3

Per Diff C Trip

IC3

Relay Startup

IA4
IB4
IC4
IA5
IB5
IC5

Figure 24 Transformer differention protection module, with up to 15


current inputs

46

Chapter 3 Differential protection


Table 6 Analog input list

Signal

Description

IA1

Phase A current input of 1st CT set

IB1

Phase B current input of 1st CT set

IC1

Phase C current input of 1st CT set

IA2

Phase A current input of 2nd CT set

IB2

Phase B current input of 2nd CT set

IC2

Phase C current input of 2nd CT set

IA3

Phase A current input of 3th CT set

IB3

Phase B current input of 3th CT set

IC3

Phase C current input of 3th CT set

IA4

Phase A current input of 4th CT set

IB4

Phase B current input of 4th CT set

IC4

Phase C current input of 4th CT set

IA5

Phase A current input of 5th CT set

IB5

Phase B current input of 5th CT set

IC5

Phase C current input of 5th CT set

Table 7 Binary output list

Signal

Description

Diff Alarm

Differential alarm

Diff Trip

Differential trip

Inst Diff A Trip

Instantaneous differential phase A Trip

Inst Diff B Trip

Instantaneous differential phase B Trip

Inst Diff C Trip

Instantaneous differential phase C Trip

Per Diff A Trip

Percent differential phase A Trip

Per Diff B Trip

Percent differential phase B Trip

Per Diff C Trip

Percent differential phase C Trip

Relay Startup

Relay Startup

Settings
Table 8 Instruction for Vector Group Angle setting

Binary setting

values

47

Chapter 3 Differential protection


Binary setting

values
0

odd

odd

even

even

odd

odd

Y-Y-D-1

Y-D-D-1

Y-Y-Y-

D-D-D-

D-D-Y-

D-Y-Y-

/3/5/7/9/

/3/5/7/9/

2/4/6/8

2/4/6/8/

1/3/5/7

1/3/5/7

11

11

/10/12

10/12

/9/11

/9/11

HV Wind Conn/Y-0 D-1


MV Wind Conn/Y-0 D-1
(Only for three-winding transformers)
LV Wind Conn/Y-0 D-1
Vet Grp Angle

Remarks

Table 9 Settings of Differential protection

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
Instantaneous Differential

I_Inst Diff

0.5Ir

20Ir

20

I_Percent Diff

0.08Ir

4Ir

2.1

I_ResPoint1 Diff

0.1Ir

Ir

I_ResPoint2 Diff

0.1Ir

10Ir

Slope1_Diff

0.2

0.2

the 1st slope

Slope2_Diff

0.2

0.7

0.5

the 2nd slope

Slope3_Diff

0.25

0.95

0.7

the 3rd slope

Ratio_2nd Harm

0.05

0.80

0.15

2nd harmonic(HAR) ratio

Ratio_3/5th Harm

0.05

0.80

0.35

3 / 5 harmonic(HAR) ratio

(ID>>) current setting


Percentage Differential (ID>)
current setting
The 1st breakpoint restraint
current (IR1)
The 2nd breakpoint restraint
current (IR2)

rd

th

Within the delay 2

nd

har-

monic block all three phasT_2nd Harm Block

20

20

es. After the delay, then


only the local phase is
blocked.

T_3/5th Harm

48

20

20

th

Within the delay 5 har-

Chapter 3 Differential protection

Unit

Setting

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)

Block

monic block all three phases. After the delay, then


only the local phase is
blocked.

Table 10 Binary settings of Differential protection

Setting
Func_Inst Diff

Unit

Default

Min.

Max.

setting

Func_Percent Diff

Block Diff at Inrush

Description
Instantaneous differential
protection ON 1-on; 0-off.
Percentage differential protection ON 1-on; 0-off.
Inrush block differential pro-

tection
1-block; 0-not block.

2nd Harm Not

2nd harmonic (HAR) inhibit

Wave

not the fuzzy recognition


based on the wave0

form(WAVE)
1-2nd harmonic on; 0waveform on

Block Diff at
Overexcit

Overexcitation block differ0

ential protection
1-block; 0-not block.
Overexcitation stabilization
judgement

Overexcit 3rd NOT


5th

3rd or 5th harmonic (HAR)


0

inhibit on
rd

th

1-3 harmonic; 0-5 harmonic.


Differential current (DIFF)
Func_Diff Alarm

Alarming on
1-on; 0-off.

Block Diff at
CT_Fail

Block differential protection


0

when there is CT failure


1-block; 0-not block.

49

Chapter 3 Differential protection


Setting

Unit

Min.

Max.

Default
setting

Description
Eliminate calculated 3I0

HV D_side Elimi-

nate I0

when HV side winding is


connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0

MV D_side Elimi-

nate I0

when MV side winding is


connected in Delta mode
1- eliminate; 0-not eliminate
Eliminate calculated 3I0

LV D_side Elimi-

nate I0

when LV side winding is


connected in Delta mode
1- eliminate; 0-not eliminate
LV current is included in
calculation of the differential

Diff Includes LV

Cur

protection.
1- Diff Includes LV Cur;
0-Diff NOT Includes LV Cur

Report
Table 11 Event report list

Information

Description

Per Diff Trip A


Per Diff Trip B

Treble slope percent Differential protection (ID>) trip for phase A/B/C

Per Diff Trip C


Inst Diff Trip A
Inst Diff Trip B

Instantaneous Differential protection (ID>>) trip for phase A/B/C

Inst Diff Trip C

Table 12 Alarm report list

Information

Description

Ph_A Ct Fail

Phase A CT failure

Ph_B Ct Fail

Phase B CT failure

50

Chapter 3 Differential protection

Information

Description

Ph_C Ct Fail

Phase C CT failure

Diff Cur Alarm

Imbalance differential current alarm

Diff 2har Blk

Differential protection is blocked by 2

nd
rd

Diff 3/5har Blk

harmonic.
th

Differential protection is blocked by 3 or 5 harmonic.

Table 13 Operation report list

Information

Description

Func_Diff On

Differential protection is switched ON (by CW)

Func_Diff Off

Differential protection is switched OFF (by CW)

Technical data
Table 14 Differential protection technical data
Item

Range or value

Tolerance

Instantaneous differential current

0.5 Ir to 20.00 Ir

3% setting or 0.02Ir

Percentage differential current

0.08 Ir to 4.00 Ir

3% setting or 0.02Ir,

Restraint current 1

0.1 Ir to 1 Ir

3% setting or 0.02Ir

Restraint current 2

0.1 Ir to 10 Ir

3% setting or 0.02Ir

Slope 1

0.0 to 0.2

Slope 2

0.2 to 0.7

Slope 3

0.25 to 0.95

2nd harmonic restraint ratio

0.05 to 0.80 of fundamental

3rd / 5th harmonic restraint ratio


Reset ratio of restrained differential
Operating time of restraint differential
Operating time of instantaneous
differential
Reset time

0.05 to 0.80
approx. 0.7
30ms at 200% setting, and
IDifferential>2IRestraint
20ms typically at 200% setting
approx. 40ms

51

Chapter 3 Differential protection

52

Chapter 4 Restricted earth fault protection

Chapter 4 Restricted earth fault


protection

About this chapter


This chapter describes the protection principle, input and
output signals, parameter, IED report and technical data for
restricted earth fault protection function.

53

Chapter 4 Restricted earth fault protection

Introduction
The restricted earth fault protection detects earth faults in power transformers with earthed starpoint or in non-earthed power transformers with
a starpoint former (earthing transformer/reactor) installed inside the protected zone. A precondition for using this function is that a CT should be
installed in the starpoint connection, i.e. between the starpoint and earth.
The starpoint CT and the phase CTs define the limits of the protected
zone by restricted earth fault protection.

Applications
The IED provides two restricted differential protection functions which
can be used independently at various locations. For example, it is possible to use them for both windings of YNyn transformer which is earthed at
both starpoints. Further, one of them can be implemented to protect an
earthed transformer winding and the other for an earthing transformer/reactor. In case of auto-transformers, one of them is sufficient to protect the auto-windings. Examples for some of applications are illustrated
in the below figure.

I A.2

LV

HV

A
IB.2

B
IC .2

C
3I02 IA.2 IB.2 IC .2

CSC-326

3I01

Figure 25 Application of restricted earth fault protection on an


earthed transformer winding

54

Chapter 4 Restricted earth fault protection


HV

LV

Ia .2

Ib .2

Ic.2

a
b
c

3I01

Ia .2 Ib .2 Ic.2
3I02
CSC-326

Figure 26 Application of restricted earth fault protection on an


earthing transformer winding

I A.2

LV

HV

Ia .2

A
IB.2

Ib .2

B
IC .2

Ic.2

C
3I01

3I01

3I02 IA.2 IB.2 IC .2

CSC-326
Ia .2 Ib .2 Ic.2
3I02

Figure 27 Application of restricted earth fault protection on both


sides of transformer

55

Chapter 4 Restricted earth fault protection


I A.2

Ia.3

A
IB.2

Ib .3

IC .2

Ic .3

3I01

3I02 IA.2 IB.2 IC .2

CSC-326
3I03 Ia.3 Ib.3 Ic.3

Figure 28 Application of restricted earth fault protection on an


auto-transformer

Protection principle
During healthy operation condition, no starpoint current 3I01 flows
through the starpoint CT. Furthermore, the sum of the phase currents 3I02
=IA.2 + IB.2 + IC.2 is almost zero. In case of auto-transformer, both the residual currents 3I02 =IA.2 + IB.2 + IC.2 and 3I03 =IA.3 + IB.3 + IC.3 are zero. With
an earth fault inside the protected zone, a starpoint current 3I01 flows.
Moreover, depending on the earthing conditions of the power system
outside the protected zone, a further earth current may be recognized in
the residual current path of the phase CTs (3I02 and 3I03). Since all the
currents flowing into the protected zone are defined positive, the residual
current from the system (3I02 and 3I03) is more or less in phase with the
starpoint current (3I01). With an earth fault outside the protected zone, a
starpoint current 3I01 flows into the protected zone, together with equal
residual current 3I02 and 3I03 which flows toward outside of the protected
zone, through the phase CTs. Keeping in mind positive direction current
flow, which is toward the protected zone, the starpoint current is in phase
opposition with 3I02 and 3I03.
With the described situations, it may seem to be simple to discriminate an
internal fault from an external one. However, there are some difficulties to
do so. For instance, when a strong fault without earth connection occurs
outside the protected zone, a residual current may appear in the residual
current path of the phase CTs. The residual current is caused by different
degrees of saturation in phase CTs and could simulate a fault in the
protected zone. Thus, additional measures should be taken to prevent
this current to cause false tripping. To achieve this objective, the restricted earth fault protection provides a restraint quantity.

56

Chapter 4 Restricted earth fault protection


3.1

Differential and restraint current calculation


The differential current Idiff0 and the restraining current Irest0 are calculated
according to below figure.

I diff 0 3I01 3I02 3I03

I
max 3I01 , 3I02 , 3I03

rest 0

Equation 24

Idiff0 and Irest0 are compared by the restricted earth fault protection with
a dual-slope operating characteristic defined by below equation and
shown in below figure.
I diff 0 I 0 D

I diff 0 S 0 D I res0

if I res0 I 0 D / S 0 D
if I res0 I 0 D / S 0 D

Equation 25
Where I0D is the setting for sensitivity threshold of restricted earth fault
protection (setting HV 3I0_REF, MV 3I0_REF or LV 3I0_REF), and
S0D is slope of the branch (setting HV Slope_REF, MV Slope_REF or
LV Slope_REF).
This characteristic can be enabled or disabled by using Binary setting
HV Func_REF Trip, MV Func_REF Trip or LV Func_REF Trip). If
setting 1-on is selected, a trip signal is issued by restricted earth fault
protection when the operating point lies into tripping area (see below figure) and the preset time delay is expired (setting HV T_REF Trip, MV
T_REF Trip or LV T_REF Trip).
The trip logic for restricted earth fault protection is shown in below figure.

57

Chapter 4 Restricted earth fault protection


I Diff0

Trip area

Slope _ REF
3 I 0 _ REF
block area

I Res0

Figure 29 Characteristic of restricted earth fault protection

Func_REF Trip on

A
N
D

Func_REF Alarm on

Idiff0>HV 3I0_REF Alarm

A
N
D

T_REF Trip

T_REF Alarm

REF Trip

REF Alarm

Figure 30 Tripping logic of the restricted earth fault protection


To clarify the proper operation during various situations, three important
operating conditions are examined.
External fault:
3I01 enters the protected zone, whereas 3I02 leaves the protected zone,
i.e. is negative according to the definition of signs, therefore 3I02 = 3I01.
Idiff0 = |3I01 + 3I02| = |3I01 3I02|= 0
Ires0 = max {|3I01|, |3I02|} = |3I01|
No tripping quantity (Idiff0 = 0); the restraint quantity (Irest0) corresponds
to the external fault current flowing through the starpoint connection.
Internal fault, fed only from the starpoint:

58

Chapter 4 Restricted earth fault protection


In this case, 3I02=0, thus,
Idiff0 = |3I01 + 3I02| = |3I01 + 0| = |3I01|
Ires0 = max {|3I01|, |3I02|} = |3I01|
Both the tripping (Idiff0) and the restraint (Irest0) quantities correspond to
the fault current flowing through the starpoint.
Internal fault, fed from the starpoint and from the system, e.g. with equal
earth current magnitude:
Both the 3I01 and 3I02 enter the protected zone, thus having positive sign.
The condition results in 3I02 = 3I01.
Idiff0 = |3I01 + 3I02| = |3I01 + 3I02|= 2|3I01|
Ires0 = max {|3I01|, |3I02|} = |3I01|
Tripping quantity (Idiff0) corresponds to double the fault current flowing
through the starpoint connection, and restraint quantity (Irest0) is equal to
the fault current.
The results show that the device is capable to properly discriminate internal and external earth faults by using the definitions proposed for differential and restraint current. However, the device is still subjected to
some influences that induce differential currents even during normal operation condition. These influences should be compensated in appropriate manner. The specific treatments designed to cope with these influences includes automatic ratio compensation which is explored as follows.

3.2

Automatic Ratio compensation


Restricted earth fault protection represents some problems in the application of current transformers regarding to matching between phase and
starpoint CTs. The problem is originated from different ratio of phase and
starpoint CTs. The difference may result in a differential current in normal
operation condition. To remove this problem, the input currents of the
relay from starpoint CTs should be converted according to primary rated
currents of phase and starpoint CTs. In the IED, this objective is achieved
by taking a common reference value and converting all secondary currents of starpoint CTs into the same reference. The conversion is per59

Chapter 4 Restricted earth fault protection


formed by calculation of ratio compensation factor for starpoint CTs. The
compensation factors are then multiplied by the secondary current of
starpoint CTs to make them comparable with those current measured at
phase CTs. The conversion procedure is performed inside the device.
The ratio compensation factors are calculated as follow:

K Starpoint HV

nStarpoint HV
nPhase HV
Equation 26

K StarpointMV

nStarpointMV
nPhaseMV
Equation 27

K Starpoint LV

nStarpoint LV
nPhase LV
Equation 28

Where

K StarpointHV

is the ratio compensation factor for HV starpoint

CT;

K StarpointMV

is the ratio compensation for MV starpoint CT

and

K StarpointLV

is the ratio compensation for LV starpoint CT;

For auto-transformer, in addition to the common winding starpoint CT, the


measured current from phase winding of MV winding should also be
converted to the common reference current. In this context, the ratio
compensation factors are calculated as follow:

K MV

nPhase MV
nPhase HV
Equation 29

K Starpoint
60

nStarpoint
nPhase HV

Chapter 4 Restricted earth fault protection


Equation 30
Where K MV is the ratio compensation factor for MV phase CT, and

K Starpoint

is the ratio compensation factor for common winding starpoint

CT.
The reference current is selected as is shown in below figure.
Table 15 Reference side selection for REF functions
Type

HV REF

MV REF

LV REF

2 winding

HV CT

---

LV CT

3 winding

HV CT

MV CT

---

Auto-transformer

HV CT

---

---

3.3

function

Positive sequence current blocking


CT2
I A.2

LV

HV

A
IB.2

B
IC .2

C
3I02 IA.2 IB.2 IC .2

CSC-326

3I01

When an external fault causes a heavy current to flow through the protected transformer, differences in the magnetic characteristics of the
current transformer CT2 under saturation condition may cause a significant difference in the secondary currents I02 connected to IED. If the
difference is greater than the pickup threshold, the CBF protection function can trip even though no fault occurred in the protected zone. To
prevent the protection function from such erroneous operation, a restraint
(stabilizing) ratio, zero-sequence current divides positive-sequence current, is brought in.

61

Chapter 4 Restricted earth fault protection


I0
15%
I1
Where I0 is zero-sequence current, I1 is positive-sequence current.
Only when the ratio is greater than 15% can the CBF protection trip.

3.4

Restricted earth fault current alarm


In normal operation condition, zero differential current is expected for restricted earth fault protection. The Restricted earth fault current supervision monitors Idiff0 and checks its value to be less than a threshold. An
alarm report is generated as HV REF 3I0 Alarm, MV REF 3I0 Alarm or
LV REF 3I0 Alarm, after the preset time of HV T_REF Alarm, MV
T_REF Alarm or LV T_REF Alarm, if the differential current exceeds
the threshold value HV 3I0_REF, MV 3I0_REF or LV 3I0_REF. The
alarm is an indication of miss-connection in phase or starpoint CT secondary windings, and therefore is released to remind user to detect the
faulty connection in secondary circuit and remove it. The function can be
enabled or disabled by using setting HV Func_REF Alarm, MV
Func_REF Alarm or LV Func_REF Alarm, (1-On, 0-Off). The setting
range of the threshold differential current to release restricted earth fault
current alarm is on [0.08-10A]. However, to avoid incorrect alarm indications, the threshold value is increased to 0.1A (in 1A nominal current inputs) and to 0.3A (in 5A nominal current inputs), if the set value is less
than 0.1A.
DANGER: Before Restricted Earth Fault protection is put into operation on
site, polarity of neutral current transformer for REF must have been
checked right by an energizing test of every side of the transformer or a
test of simulating an external fault of the side in primary system. Otherwise
a mal-operation may occur during an external earth fault.

62

Chapter 4 Restricted earth fault protection

Input and output signals


Restricted Earth
Fault Protection
IA1

REF Alarm

IB1

REF Trip

IC1

Relay Startup

IA2
IB2
IC2
IREF

Figure 31 Restricted earth fault protection module


Table 16 Analog input list

Signal

Description

IA1

Phase A current input of CT of circuit breaker 1

IB1

Phase B current input of CT of circuit breaker 1

IC1

Phase C current input of CT of circuit breaker 1

IA2

Phase A current input of CT of circuit breaker 2

IB2

Phase B current input of CT of circuit breaker 2

IC2

Phase C current input of CT of circuit breaker 2

IREF

Neutral point current for REF

Table 17 Binary output list

Signal

Description

REF Alarm

Restricted Earth Fault alarm

REF Trip

Restricted Earth Fault trip

Relay Startup

Relay Startup

63

Chapter 4 Restricted earth fault protection

Settings

Table 18 Settings of Restricted earth fault protection for HV side of transformer

Setting

HV 3I0_REF

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

HV 3I0_REF
Alarm
HV T_REF
Alarm

(Ir:5A/1

Description

A)
2Ir

0.2

0.95

0.5

60

0.03

0.08Ir

2Ir

60

0.03

Slope_REF

Trip

setting

0.08Ir

HV

HV T_REF

Default

Current setting for HV Restricted Earth Fault protection


Slope setting for HV Restricted
Earth Fault protection
HV Restricted Earth Fault trip
time setting
HV Restricted Earth Fault alarm
current setting
HV Restricted Earth Fault alarm
time setting

Table 19 Binary settings of restricted earth fault protection for HV side of


transformer
DeSetting

Unit

Min.

Max.

fault

Description

setting
HV Restricted earth fault trip-stage

HV Func_REF

Trip

ON

1-on; 0-off.
HV Restricted earth fault

HV Func_REF

Alarm

Alarm-stage ON

1-on; 0-off.

Block HV REF

at HV CT_Fail

Block HV REF when CT failure,

1-Block;0-unblock

Table 20 Settings of Restricted earth fault protection for MV side of transformer

Setting

MV 3I0_REF

64

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.08Ir

Default
setting
(Ir:5A/1

Description

A)
2Ir

Current setting for MV Restricted Earth Fault protection

Chapter 4 Restricted earth fault protection

Unit

Setting

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

MV

Trip
MV 3I0_REF
Alarm
MV T_REF
Alarm

setting
(Ir:5A/1

Description

A)

0.2

0.95

0.5

60

0.03

0.08Ir

2Ir

60

0.03

Slope_REF
MV T_REF

Default

Slope setting for MV Restricted


Earth Fault protection
MV Restricted Earth Fault trip
time setting
MV Restricted Earth Fault alarm
current setting
MV Restricted Earth Fault alarm
time setting

Table 21 Binary settings of restricted earth fault protection for MV side of


transformer
DeSetting

Unit

Min.

Max.

fault

Description

setting
MV Func_REF

Trip

MV Restricted earth fault trip-stage

ON 1-on; 0-off.
MV Restricted earth fault

MV Func_REF

Alarm

Alarm-stage ON

1-on; 0-off.

Block MV REF

at MV CT_Fail

Block MV REF when CT failure,

1-Block;0-unblock

Table 22 Settings of restricted earth fault protection for LV side of transformer

Setting

LV 3I0_REF

Unit

LV 3I0_REF
Alarm

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)

0.08Ir

2Ir

0.2

0.95

0.5

60

0.03

0.08Ir

2Ir

LV Slope_REF

LV T_REF Trip

Min.

Current setting for LV Restricted


Earth Fault protection
Slope setting for LV Restricted
Earth Fault protection
LV Restricted Earth Fault trip
time setting
LV Restricted Earth Fault alarm
current setting

65

Chapter 4 Restricted earth fault protection

Unit

Setting

LV T_REF

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Alarm

Default
setting

Description

(Ir:5A/1
A)

60

LV Restricted Earth Fault alarm

0.03

time setting

Table 23 Binary settings of restricted earth fault protection for LV side of


transformer
DeSetting

Unit

Min.

Max.

fault

Description

setting
LV Func_REF
Trip
LV Func_REF
Alarm

LV Restricted earth fault trip-stage


ON 1-on; 0-off.
LV Restricted earth fault

Alarm-stage ON
1-on; 0-off.

Block LV REF at
LV CT_Fail

Block LV REF when CT failure,


1-Block;0-unblock

Report
Table 24 Event report list

Information

Description

HV REF Trip

HV Restricted Earth fault (REF) protection trip

MV REF Trip

MV Restricted Earth fault (REF) protection trip

LV REF Trip

LV Restricted Earth fault (REF) protection trip

Table 25 Alarm report list

Information

Description

HV REF 3I0 Alarm

HV Restricted Earth fault (REF) protection trip

MV REF 3I0 Alarm

MV Restricted Earth fault (REF) protection trip

LV REF 3I0 Alarm

LV Restricted Earth fault (REF) protection trip

66

Chapter 4 Restricted earth fault protection


Table 26 Operation report list

Information

Description

HV Func_REF On

HV REF protection is switched ON (by CW)

HV Func_REF Off

HV REF protection is switched OFF (by CW)

MV Func_REF On

MV REF protection is switched ON (by CW)

MV Func_REF Off

MV REF protection is switched OFF (by CW)

LV Func_REF On

LV REF protection is switched ON (by CW)

LV Func_REF Off

LV REF protection is switched OFF (by CW)

Technical data
Table 27 Restricted earth fault protection technical data
Item

Rang or Value

Differential current

0.08 Ir to 2.00 Ir

Slope

0.2 to 0.95
0.00 to 60.00s, step 0.01s

Tolerance
3% setting or 0.02Ir

1% setting or +40ms, at 200%

Time delay
operating setting
Reset ratio

Approx. 0.7, at tripping

Operating time

30ms, at 200% setting

Reset time

approx. 40ms

67

Chapter 4 Restricted earth fault protection

68

Chapter 5 Overexcitation protection

Chapter 5 Overexcitation protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for
overexciation protection function.

69

Chapter 5 Overexcitation protection

Introduction
The overexcitation protection is used to detect impermissible overexcitation
conditions which can endanger power transformers. An increase in transformer flux beyond the rated values leads to saturation of the iron core and to
large eddy current losses which cause impermissible temperature rise in
transformer core.

Protection principle

2.1

Protection principle
The overexcitation condition may occur in power plant transformers when a
load center is disconnected from the system, and the voltage regulator does
not operate sufficiently fast to control the associated voltage rise. Similarly,
the overexcitation condition may occur as result of a decrease in frequency,
e.g. in island system. To protect the power transformer in such conditions, the
overexcitation protection function should pick up when the permissible limit of
flux is exceeded in the transformer core. To do so, the overexcitation protection function measures the voltage/frequency (U/f) ratio which is proportional
to the flux density B in transformer core, and puts it in relation to the nominal
flux density BN. The decision is then made based on the calculated ratio as is
shown in below equation.

U f
B

BN U N f

Equation 31
Where N is the ratio of volt/hertz calculated by the device.
U and f are the measured voltage and frequency, and UN and fN are the rated
voltage and frequency (50Hz or 60Hz) of the device. While the rated frequency is fixed to 50Hz or 60Hz in software, device is informed about rated
voltage by setting Reference Voltage which corresponds to nominal
phase-neutral voltage of the protected transformer when is transferred to
70

Chapter 5 Overexcitation protection


secondary value, using the turn ratio of voltage transformer. Thus, the use of
the overexcitation protection presumes that measured voltage is connected to
the device. Calculation of voltage/hertz ratio above is performed based on the
maximum voltage of the three phase-neutral or phase-phase voltages. Binary
setting V/F Voltage(0-VPP,1-VPN) determines whether phase-to-phase
voltage or phase-neutral voltage should be used for overexcitation protection,
by setting 0-VPP or 1-VPN, respectively.
It should be mentioned that the overexcitation protection can operate properly,
only if frequency is in range of 0.5 - 1.3 times the rated frequency and voltage
is greater than 0.7 times the rated voltage. If frequency or voltage is out of the
specified range, an alarm report U or F EXCEED is generated by the device,
after a fixed time delay of 150ms, and the overexcitation protection is blocked.
The logic is shown in below figure.

V<0.7Un
f<0.5fn or
f>1.3fn

O
R

150ms

U or F EXCEED

Figure 32 Condition for generating U or F EXCEED alarm


The overexcitation protection includes two definite characteristics (alarm and
trip) and one thermal characteristic. The latter characteristic provides an approximate replica of the temperature rise caused by overexcitation in the
protected object. The definite alarm stage can be enabled or disabled by using Binary setting Func_Overexcit Alarm Def on. Similarly, the definite trip
stage can be enabled or disabled by using Binary setting Func_Overexcit
Trip Def on. Furthermore, the thermal characteristic can be set by Binary
setting Func_Overexcit Trip Inv on. It should be mentioned that the
overexcitation protection can be applied at HV, MV or LV side of the protected
transformer. However, it is not recommended to apply the function on the
transformer side with variable winding turns such as the transformer side with
an installed tap changer. To enable the protection on a given side, setting of
HV Func_Overexcit on, MV Func_Overexcit on and LV Func_Overexcit
on should be applied to corresponding Binary settings. However, these settings should be applied to 1 only on one side at the same time. If any two of
HV Func_Overexcit, MV Func_Overexcit and HV Func_Overexcit are set
to 1 at the same time, alarm report Setting Err will be given by the device.
All the three available stages of the overexcitation protection use
phase-to-phase voltage or phase-neutral voltage of the corresponding side in
their calculations, based on the setting applied at Binary setting V/F Volt71

Chapter 5 Overexcitation protection


age(0-VPP,1-VPN).
If the definite alarm stage is enabled in one side, and the calculated volt/hertz
ration exceeds the threshold defined by setting Func_Overexcit Alarm Def,
an alarm report Def V/F Alarm is generated by the device, after the time
delay T_Definite Alarm elapsed. The logic for the definite alarm stage of
overexcitation protection is shown in below figure when it is applied to HV
side. The logic is the same when the protection function is applied to other
sides.

HV Func_Overexcit on

Func_Overexcit Alarm Def on

A
N
D

NU AB_ Hv, f DEF Alarm V / F

NUBC_ Hv, f DEF Alarm V / F

O
R

NUAC_ Hv, f DEF Alarm V / F


A
N
D

V/F Voltage(0-VPP,1-VPN) on

O
R

DEF V/F Alarm

A
N
D

NUA_ Hv , f DEF Alarm V / F


NUB_ Hv , f DEF Alarm V / F

HV T_REF Alarm

O
R

NUC_Hv , f DEF AlarmV / F

U or F EXCEED

Figure 33 Logic of the definite alarm stage for overexcitation protection


Similarly, if the definite trip stage is enabled in one side, and the calculated
volt/hertz ration exceeds the threshold defined by setting V/F_Definite Trip,
an event report Def V/F Trip is generated by the device, subsequent to the
72

Chapter 5 Overexcitation protection


expiration of time delay T_Definite Trip. Tripping Logic of the definite trip
stage of overexcitation protection is shown in below figure.

HV Func_Overexcit on

Func_Overexcit Trip Def on

A
N
D

NUAB_ Hv , f DEF Trip V / F


`

NUBC_ Hv , f DEF Trip V / F

O
R

N U AC _ Hv , f DEF Trip V / F
A
N
D

V/F Voltage(0-VPP,1-VPN) on

O
R

DEF V/F Trip

A
N
D

N U A_ Hv , f DEF Trip V / F

N U B _ Hv , f DEF Trip V / F

T_Definite Trip

O
R

N UC _ Hv , f DEF Trip V / F

U or F EXCEED

Figure 34 Tripping logic of the definite trip stage for overexcitation protection
If thermal characteristic is set to 1-on in one of transformer sides, it uses the
measured voltage and frequency of the corresponding side (depending on the
setting applied at Binary setting V/F Voltage (0-VPP,1-VPN)), together with
ten points derived from the manufacturer data. The points correspond to the
desired tripping times for a given volt/hertz ratios. Intermediate values are
determined by performing linear interpolation by the device. The ratios range
from N=1.05 to N=1.50. They are entered into the device by settings
73

Chapter 5 Overexcitation protection


T1_Inverse V/F=1.05, T2_Inverse V/F=1.10, T3_Inverse V/F=1.15,
T4_Inverse V/F=1.20, T5_Inverse V/F=1.25, T6_Inverse V/F=1.30,
T7_Inverse V/F=1.35, T8_Inverse V/F=1.40, T9_Inverse V/F=1.45 and
T10_Inverse V/F=1.50. The device uses these points to form an inverse
characteristic such as those shown in below figure.

u/f
1.50
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05

T10 T9 T8 T7 T6 T5 T4

T3

T2

T1

t(s)

Figure 35 Thermal overexcitation characteristic


As can be seen from the above figure, N=1.05 works as a pickup threshold for
thermal stage. The thermal replica is implemented in IED by a counter which
is incremented from 0% to 100%, as soon as the calculated voltage/hertz ratio of exceeds the pickup threshold (N=1.05). If the counter reaches to 100%
corresponding to expiration of trip time delay according to the trip characteristic, the event report Inv V/F Trip is given. The trip signal is cancelled as
soon as the calculated voltage/hertz ratio falls below the pickup threshold
(N=1.05). However, the counter is decremented to zero according to cool
down time of the transformer (the time by which the thermal replica counter
reaches from 100% to 0%). The cool down time is informed to the device by
setting T_Cool Down.
Tripping Logic of the inverse thermal trip stage of overexcitation protection is
shown in below figure.

74

Chapter 5 Overexcitation protection

HV Func_Overexcit on
A
N
D

Func_Overexcit Trip Inv on

u/f

N (U AB HV , f )

1.50
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05

T10T9 T8 T7 T6 T5 T4 T3 T2

T1 t(s)

u/f

N (U BC HV , f )

O
R

1.50
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05

T10T9 T8 T7 T6 T5 T4 T3 T2

T1 t(s)

T10T9 T8 T7 T6 T5 T4 T3 T2

T1 t(s)

u/f

N (U AC HV , f )

1.50
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05

A
N
D

V/F Voltage(0-VPP,1-VPN) on

O
R

u/f

N (U A HV , f )

5
1.
0
4
1.
45
1.
0
3
1.
3
5
1.
0
2
1.2
1.5
0
1
1.
1
5
1.
0
1.
5

T10T9 T8 T7 T6 T5 T4 T3 T2

Inv V/F Trip

A
N
D

T1 t(s)

u/f

N (U B HV , f )

5
1.
0
4
1.
45
1.
0
3
1.
3
5
1.
0
2
1.2
1.5
0
1
1.
1
5
1.
0
1.
5

O
R
T10T9 T8 T7 T6 T5 T4 T3 T2

T1 t(s)

T10T9 T8 T7 T6 T5 T4 T3 T2

T1 t(s)

u/f

N (U C HV , f )

5
1.
0
4
1.
45
1.
0
3
1.
3
5
1.
0
2
1.2
1.5
0
1
1.
1
5
1.
0
1.
5

U or F EXCEED

Figure 36 Tripping logic of the thermal trip stage for overexcitation protection
NOTE: If it is possible for a given transformers to operate continuously under
75

Chapter 5 Overexcitation protection


the condition of N=1.05, corresponding time delay setting (T1_Inverse
V/F=1.05) should be set to 9999s. The same approach can be taken when, for
example, it is permissible for a transformer to operate continuously under the
condition N=1.10, N=1.15 and so on. It means that the thermal characteristic is
compound of 10 points at most, and it maybe contains less than 10 points. The
thermal characteristic would be disabled if all the delay time settings are set to
9999s.

2.2

Voltage channel configuration


UA/B/C voltage input channel of 1st Analog input module (hereinafter is
refered as AIM) is provided with the high accurate frequency measurement
hardware circuit. In order to offer the high performance overexcitation function
for HV, MV or LV side, the applied voltage input of HV side, MV side or LV
side must be connected with the UA/B/C voltage input channel of 1st Analog
input module (AIM1).
Only one of HV overexcitation, MV overexcitation or LV overexcitation functions could be enabled for one transformer, so settings of HV Voltage Chan
Sel and MV Voltage Chan Sel under Comm Para submenu are used to
select the voltage channel.
For example of HV side; the setting HV Voltage Chan Sel can be set as 1, 2
and 3 which means voltage channels are connected to the corresponding
analog input module (see below table).
Table 28 Voltage channel selection setting
Voltage Chan Sel

Voltage input channels, connected with external


volage inputs

UA/B/C voltage input channel of AIM1, which channels can


provide the frequency measurement hardware circuit.

UA/B/C voltage input channel of AIM2

UA/B/C voltage input channel of AIM3

If Binary setting HV Func_Overexcit is set 1 and HV Voltage Chan Sel is


set 2 or 3 (not 1), alarm report Setting Err will be given by the device. If Binary setting MV Func_Overexcit is set 1 and MV Voltage Chan Sel is set 2
or 3 (not 1), alarm report Setting Err will be given by the device. If LV
76

Chapter 5 Overexcitation protection


Func_Overexcit, anyone of HV Voltage Chan Sel and MV Voltage Chan
Sel is set 1, alarm report Setting Err will be given by the device.

Input and output signals


Overexcitation
Protection
UA

Def V/F Alarm

UB

Def V/F Trip

UC

Inv V/F Trip


Relay Startup

Figure 37 Overexcitation protection module


Table 29 Analog input list

Signal

Description

UA

Phase A voltage input

UB

Phase B voltage input

UC

Phase C voltage input

Table 30 Binary output list

Signal

Def V/F Alarm


Def V/F Trip
Inv V/F Trip
Relay Startup

Description
Overexcitation protection(V/F) alarm with
definite (DEF) time characteristic
Overexcitation protection(V/F) tripping (Trip)
with definite (DEF) time characteristic
Overexcitation protection(V/F) tripping (Trip)
with inverse(IVR) time characteristic
Relay Startup

77

Chapter 5 Overexcitation protection

Settings
Table 31 Settings of overexcitation protection

Setting

Reference Voltage

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

40

130

57.3

1.5

1.1

0.1

9999

10

1.5

1.2

0.1

9999

0.1

9999

10

0.1

9999

90

0.1

9999

80

0.1

9999

70

0.1

9999

60

0.1

9999

50

0.1

9999

45

0.1

9999

40

0.1

9999

35

0.1

9999

30

0.1

9999

25

Unit

V/F_Definite
Alarm
T_Definite Alarm

V/F_Definite
Trip
T_Definite Trip
T1_Inverse
V/F=1.05
T2_Inverse
V/F=1.10
T3_Inverse
V/F=1.15
T4_Inverse
V/F=1.20
T5_Inverse
V/F=1.25
T6_Inverse
V/F=1.30
T7_Inverse
V/F=1.35
T8_Inverse
V/F=1.40
T9_Inverse
V/F=1.45
T10_Inverse
V/F=1.50
T_Cool Down

78

Default

Min.

setting
(Ir:5A/1

Description

A)
Nominal phase voltage in HV
side
Alarming setting of volt/hertz
Timer setting for volt/hertz
alarming stage
Tripping setting of definite
volt/hertz stage
Timer setting for definite
volt/hertz stage
Timer setting for
volt/hertz=1.05
Timer setting for
volt/hertz=1.10
Timer setting for
volt/hertz=1.15
Timer setting for
volt/hertz=1.20
Timer setting for
volt/hertz=1.25
Timer setting for
volt/hertz=1.30
Timer setting for
volt/hertz=1.35
Timer setting for
volt/hertz=1.40
Timer setting for
volt/hertz=1.45
Timer setting for
volt/hertz=1.50
Cool down time delay for
overexcitation protection

Chapter 5 Overexcitation protection


Table 32 Binary settings of overexcitation protection
DeSetting

Unit

Min.

Max.

fault
set-

Description

ting
HV Func_Overexcit

MV Func_Overexcit

LV Func_Overexcit

Func_Overexcit
Alarm Def

HV Overexcitation (V/F) on
1-on; 0-off.
MV Overexcitation (V/F) on
1-on; 0-off.
LV Overexcitation (V/F) on
1-on; 0-off.
Definite Overexcitation (V/F)

Alarming on
1-on; 0-off.

Func_Overexcit Trip
Def

Definite (DEF)Overexcitation
0

(V/F) on
1-on; 0-off.

Func_Overexcit Trip
Inv

Inverse (IVR)Overexcitation
0

(V/F) on
1-on; 0-off.
Overexcitation protection uses

V/F Voltage(0-VPP,1-VPN)

phase-to-phase voltage (VPP)


or phase-to-earth voltage (VPN)
0-VPP; 1-VPN.

Report
Table 33 Event report list

Information

Description

Def V/F Trip

Overexcitation protection(V/F) tripping (Trip) with definite (DEF)

Inv V/F Trip

and inverse(IVR) time characteristic

Table 34 Alarm report list

Information

Description

Def V/F Alarm

Overexcitation alarm
79

Chapter 5 Overexcitation protection

Information

Description
Voltage or frequency is out of the permissible range

V or F Exceed

(25-65Hertz, >0.7 Un)

Table 35 Operation report list

Information

Description

Func_Overexc On

Overexcitation protection is switched ON (by CW)

Func_Overexc Off

Overexcitation protection is switched OFF (by CW)

Technical data
Table 36 Overexcitation protection technical data
Item

Rang or Value

Tolerance

Reference voltage UN

40 to 130V,

3 % setting or 1 V

Inverse time characteristic


Ratio:

1.00 to 1.50

2.5% of the setting or 0.01

Time delay
Pair of Values for characteristic
of V/f
Reset time,

0.1s to 9999s
1.05 /1.10 /1.15 /1.20 /1.25 /1.30
/1.35 /1.40 /1.45 /1.50
Approx. 70ms

5% setting or 70ms

Reset ratio

0.96

5% setting or 70ms

Definite time characteristic

80

Time delay T

0.1s to 9999s

Reset time,

Approx. 70ms

Reset ratio

0.96

5% setting or 70ms, at 200%


operating setting

Chapter 5 Overexcitation protection

81

Chapter 5 Overexcitation protection

82

Chapter 6 Overcurrent protection

Chapter 6 Overcurrent protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for overcurrent
protection function.

83

Chapter 6 Overcurrent protection

Introduction
The non-directional overcurrent elements can be applied as backup protection functions for transformer as well as power system protection in networks
with radial nature and those which are supplied from a single source. The
directional overcurrent protection can also be applied in systems where protection coordination depends on both the magnitude of the fault current and
the direction of power flow to the fault location, for instance in case of parallel transformers supplied from a single source.

Protection principle

2.1

Protection Elements
Each voltage side of the protected transformer is provided with three overcurrent protection elements from which two elements operate as definite
overcurrent stages and the other one operates with inverse time-current
characteristic. All the elements can operate in conjunction with the integrated
inrush restraint and directional functions.
Various stages of the elements are independent from each other and can be
combined as desired. They can be enabled or disabled in each side using
dedicated Binary settings. These Binary settings include HV Func_OC1,
HV Func_OC2 and HV Func_OC Inv, for HV side overcurrent protection,
MV Func_OC1, MV Func_OC2 and MV Func_OC Inv, for MV side
overcurrent protection, LV Func_OC1, LV Func_OC2 and LV Func_OC
Inv, for LV side overcurrent protection. For example by applying setting
1-on to HV Func_OC1, respective stage of overcurrent protection would
be enabled in HV side.
Individual pickup value for each definite stage can be defined by setting HV
I_OC1 and HV I_OC2 for HV side, MV I_OC1 and MV I_OC2 for MV
side, LV I_OC1 and LV I_OC2 for LV side. By applying these settings, each
phase current is compared separately with the setting value for each stage. If
the respective value is exceeded, a trip time delay timer is started. The condition for start of the delay timer is expressed mathematically by below equation, in which a, b and c represent three phases.
I I set ( a, b, c )

Equation 32
The timer is set to count up to a user-defined time delay. The time delay can
be set for each definite stage individually through settings HV T_OC1 and
84

Chapter 6 Overcurrent protection


HV T_OC2 for HV side, MV T_OC1 and MV T_OC2 for MV side, LV
T_OC1 and LV T_OC2 for LV side. After the user-defined time delays have
been elapsed, a trip signal is issued if the inrush restraint feature is applied
and no inrush current is detected or if inrush restraint is disabled. However,
the overcurrent protection would be blocked and therefore, no tripping takes
place if the inrush restraint feature is enabled and an inrush condition exists.
Further, an alarm report is issued as HV Inrush Blk BU, MV Inrush Blk BU
or LV Inrush Blk BU indicating that a blocking condition is imposed to overcurrent element by inrush condition detection.
The pickup value for the inverse time-current stage can be defined by setting
HV I_OC Inv, MV I_OC Inv and LV I_OC Inv for HV, MV and LV sides,
respectively. Each phase current is separately compared with corresponding
setting value. If a current exceeds 1.1 times the setting value, corresponding
stage picks up. If an inverse time-current stage picks up, the tripping time is
calculated from the actual fault current flowing, using the selected tripping
curve. Maximum tripping time is limited to 100s.
The time delay of time-inverse characteristic is calculated based on the type
of the characteristic, the magnitude of the current and a time multiplier. For
the time-inverse characteristic, both ANSI and IEC based standard curves are
available and any user-defined characteristic can be defined using the following equation:

A _ OC Inv

t K _ OC Inv
B _ OC Inv
P _ OC Inv
I

-1
I S

Where I is the fault current;


Is is the current setting;
A_OC Inv: Time factor for inverse time stage
B_OC Inv: Time delay for inverse time stage
P_OC Inv: index for inverse time stage
K_OC Inv: Time multiplier Inrush restraint feature
(For detailed time inverse characteristic, refer to Appendix Time inverse
characteristic)
As mentioned previously, selection among the curves can be carried out by
settings HV Func_OC Inv, MV Func_OC Inv and LV Func_OC Inv for HV,
MV and LV sides, respectively. Furthermore, the time multiplier K_OC Inv can
be set by user to coordinate the integrated inverse time-current characteristic
of the device with other overcurrent relays installed for power system protection. This can be performed by settings HV K_OC Inv, MV K_OC Inv and
85

Chapter 6 Overcurrent protection


LV K_OC Inv in case of HV, MV and LV overcurrent elements, respectively.
By applying pickup current and time multiplier settings, the device calculates
the tripping time from the measured current in each phase separately, based
on the selected inverse curve. Once the calculated time has been elapsed, a
trip signal is issued provided that no inrush current is detected or inrush restraint is disabled. If the inrush restraint feature is enabled and an inrush
condition exists, the overcurrent protection would be blocked and therefore no
tripping takes place. However, an alarm report is generated as HV Inrush Blk
BU, MV Inrush Blk BU or LV Inrush Blk BU, indicating the blocking condition which is imposed to overcurrent element by detection of inrush condition.
The trip signals and corresponding event reports are available separately for
each stage. These include HV OC1 Trip, HV OC2 Trip and HV OC Inv
Trip for HV side, MV OC1 Trip, MV OC2 Trip and MV OC Inv Trip for MV
side, LV OC1 Trip, LV OC2 Trip and LV OC Inv Trip for LV side overcurrent elements.

2.2

Inrush Restraint Feature


The transformer overcurrent protection may detect large magnetizing inrush
currents flowing when transformer is energized. The inrush current may be
several times of the nominal current, and may last from several tens of milliseconds to several seconds. Inrush current comprises second harmonic as
well as considerable fundamental component. So it may affect the overcurrent protection which operates based on the fundamental component of the
measured current. Inrush blocking unit in overcurrent function is provided for
this purpose. It is possible to apply the inrush restraint feature separately to
each definite stage and inverse time-current stage of overcurrent element by
using Binary settings HV OC1 Inrush Block, HV OC2 Inrush Block and HV
OC Inv Inrush Block on for HV side, MV OC1 Inrush Block, MV OC2 Inrush
Block and MV OC Inv Inrush Block for MV side, LV OC1 Inrush Block, LV
OC2 Inrush Block and LV OC Inv Inrush Block for LV side. By applying setting 1-on to each of the mentioned Binary settings, no trip command would
be possible by corresponding stage, if an inrush condition is detected.
Since Inrush current contains a relatively large second harmonic component
which is nearly absent during a fault current, the inrush restraint feature operates based on the evaluation of the second harmonic content which is
present in the measured current. The inrush condition is recognized if the ratio of second harmonic current to fundamental component exceeds the setting values HV Ratio_I2/I1, MV Ratio_I2/I1 or LV Ratio_I2/I1 in each
phase. The setting is applicable to both the definite stages of overcurrent
protection element as well as the inverse time-current stage for each voltage
side of the protected transformer. As soon as the measured ratio exceeds the
set threshold, a restraint is applied to those stages for which corresponding
setting is applied to make them blocked in inrush condition detection (HV
OC1 Inrush Block, HV OC2 Inrush Block and HV OC Inv Inrush Block
for HV side, MV OC1 Inrush Block, MV OC2 Inrush Block and MV OC Inv
Inrush Block for MV side, LV OC1 Inrush Block, LV OC2 Inrush Block
and LV OC Inv Inrush Block for LV side.).

86

Chapter 6 Overcurrent protection


Since the applied restraint by second harmonic detection operates individually per phase, the protection is fully operative even when the protected
transformer is switched onto a single-phase fault, whereas inrush currents
may possibly be present in one of the healthy phases. It is, however, possible
to set the protection in a way that when the second harmonic recognition is
fulfilled only in one single phase, not only the phase with the inrush current,
but also the remaining phases of the overcurrent protection are blocked. This
is achieved by cross-blocking the overcurrent protection for a certain period to
avoid spurious tripping. The setting corresponds to HV T2h_Cross_Blk, MV
T2h_Cross_Blk, LV T2h_Cross_Blk. Within this time, the overcurrent protection in all three phases is blocked as soon as an inrush current is detected
in any one phase. After the timer is expired, the overcurrent protection is
blocked only in the phase with inrush current content. To put it more simply,
cross blocking is reset if there is no more inrush in any phase, or the cross
blocking time interval is elapsed. It should be noted that inrush currents
flowing in the earth/ground path will not cross-block tripping by the phase
elements.
Furthermore, if the fundamental component of phase current exceeds the
upper limit value HV Imax_2H_UnBlk, MV Imax_2H_UnBlk or LV
Imax_2H_UnBlk, the inrush restraint will no longer be effective in respective
side, since a high-current fault is assumed in this case. The setting can be
applied for each overcurrent element in each side of the protected transformer.

2.3

Direction Determination Feature


The integrated directional function can be applied to each stage of overcurrent element via dedicated Binary settings. These Binary settings include HV
OC1 Direction, HV OC2 Direction and HV OC Inv Direction for HV side
overcurrent stages, MV OC1 Direction, MV OC2 Direction and MV OC Inv
Direction for MV side overcurrent stages and LV OC1 Direction, LV OC2
Direction and LV OC Inv Direction for LV side overcurrent stages. Furthermore, the directional orientation can be set individually for each stage of
the overcurrent elements in various sides of the protected transformer. This
can be performed by using Binary settings HV OC1 Dir To Sys, HV OC2 Dir
To Sys and HV OC Inv Dir To Sys for HV side, MV OC1 Dir To Sys, MV
OC2 Dir To Sys and MV OC Inv Dir To Sys for MV side, LV OC1 Dir To Sys,
LV OC2 Dir To Sys and LV OC Inv Dir To Sys for LV side. The possible
settings for these Binary settings comprise 0-toward transformer and
1-toward system.
Basically, the direction determination is performed by determining the phase
angle between the fault current and a reference voltage. The direction of a
phase-directional element is detected by means of a cross-polarized voltage.
It means that the fault current of the corresponding phase is used together
with the healthy phase-to-phase voltage to determine direction of fault current.
This takes effect to all three phases. Below figure shows the assignment of
the measured values for the determination of fault direction for various types
of pickups in phase overcurrent elements.
NOTE: The direction mentioned above is based on that the positive polarity is
87

Chapter 6 Overcurrent protection


at the side of the busbar and the negative polarity is at the side the transformer.
Table 37 Voltage and current measurement used for direction determination
Phase

Current

Voltage

Ia

U bc

Ib

U ca

Ic

U ab

As can be seen, the healthy voltages are used in direction determination. This
allows for a correct direction determination even if the fault voltage has collapsed entirely because of a single-phase short-line fault. With three-phase
short-line faults, memory voltage values are used to clearly determine the
direction if the measurement voltages are not sufficient. The directional element of each side uses the voltage on itself side.
In a single-phase fault, the cross-polarized voltage (reference voltage) is 90
out of phase with the fault voltage. With phase-to-phase faults, the position of
the reference voltage changes up to 30, depending on the degree of collapse
in the fault voltages. In order to satisfy different network conditions and applications, the reference voltage can be rotated by an adjustable angle. For
each side of the protected transformer, the directional angle can be set independently. The settings include HV Angle_OC, HV Angle_OC and LV
Angle_OC, for HV, MV and LV sides, respectively.
Forward

90

IA

Bisector
Angle_Range
OC
Angle_OC

0
U BC_Ref

-IA

Figure 38 Overcurrent protection directional characteristic


where:
Angle_OC: The settable characteristic angle
88

Chapter 6 Overcurrent protection


Angle_Range OC: 85
During direction decision by directional function, a VT Fail condition (a short
circuit or broken wire in the voltage transformer's secondary circuit or operation of the voltage transformer fuse) may result in false or undesired tripping
by directional overcurrent elements. In such a situation, it is possible to select
operation status of the directional overcurrent protection elements in each
side by using a number of control worlds to block the overcurrent protection
elements or keep them in operational state with no direction decision (block
direction decision). The corresponding Binary settings include Block HV OC
at HV VT_FAIL, Block MV OC at MV VT_FAIL and Block LV OC at LV
VT_FAIL, for HV, MV and LV sides, respectively. When the Binary settings
are set as 0 to select HV OC1 Direction, corresponding overcurrent protection elements will not judge direction at the local side VT failure. When they
set as 1 to select Block OC at VT Fail, no operation is possible by the
overcurrent protection elements. It is noted that the Binary settings affect all
the stages of corresponding overcurrent elements at each side. For instance,
by applying setting 0- HV OC1 Direction, all the three stages of the overcurrent element will remain operative without direction determination in case
of any fault in secondary circuit of HV side voltage transformer. On the other
hand, setting 1- Blk HV OC at HV VT_Fail makes them blocked.
The logic for Definite and Inverse time IDMTL overcurrent protection is shown
in below figure.
HV Func_OC on

DIR Positive
VT failure

A
N
D

Direct OK at VT FAIL

O
R

Direction Unit OK

A
N
D

HV Func_OC1 (2) on

I>HV I_OC1 (2)

A
N
D

HV T_OC1(2)

OC 1 2Trip

Direction Unit OK
Inrush BLK OC

Direction Unit
OK

HV Func_OC Inv on

Inverse Curve>
Direction Unit
OK

A
N
D

OC Inv Trip

Inrush BLK OC

89

Chapter 6 Overcurrent protection


Figure 39 Tripping logic for overcurrent protection

2.4

CBF initiation Feature


It is possible to set whether the overcurrent protection elements can initiate
the integrated CBF protection or not. The available choices depend on the
voltage side of the power transformer at which overcurrent protection is applied. In this context, HV side overcurrent protection element always initiates
HV side CBF function with no additional setting. However, it is possible to
select whether it can initiate MV and LV CBF protection functions via Binary
settings HV OC Initiate LV CBF and HV OC Initiate MV CBF, respectively.
MV side overcurrent protection element always initiates MV side CBF function
with no additional setting. However, it is possible to select whether it can initiate HV side CBF protection function via Binary setting MV OC Initiate HV1
CBF.
LV side overcurrent protection element always initiates LV side CBF function
with no additional setting. However, it is possible to select whether it can initiate HV side CBF protection function via Binary setting LV OC Initiate HV1
CBF.
More detail information about the initiation conditions and related Binary settings can be found as below.

90

Chapter 6 Overcurrent protection

Input and output signals


Overcurrent
Protection
IA1

OC1 Trip

IB1

OC2 Trip

IC1

OC Inv Trip

IA2

Relay Startup

IB2
IC2
UA
UB
UC

Figure 40 Overcurrent protection module

Table 38 Analog input list

Signal

Description

IA1

Phase A current input of CT of circuit breaker 1

IB1

Phase B current input of CT of circuit breaker 1

IC1

Phase C current input of CT of circuit breaker 1

IA2

Phase A current input of CT of circuit breaker 2

IB2

Phase B current input of CT of circuit breaker 2

IC2

Phase C current input of CT of circuit breaker 2

UA

Phase A voltage input

UB

Phase B voltage input

UC

Phase C voltage input

91

Chapter 6 Overcurrent protection


Table 39 Binary output list

Signal

Description

OC1 Trip

Overcurrent stage 1 trip

OC2 Trip

Overcurrent stage 2 trip

OC Inv Trip

Overcurrent inverse stage trip

Relay Startup

Relay Startup

Setting
Table 40 Settings of overcurrent protection for HV side of transformer

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
HV overcurrent (O/C) current

HV I_OC1

0.05Ir

20Ir

HV T_OC1

60

60

HV I_OC2

0.05Ir

20Ir

HV T_OC2

60

60

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

setting for Stage 1


Time setting for HV OC, Stage
1
HV overcurrent (O/C) current
setting for Stage 2
Time setting for HV OC, Stage
2

HV
Curve_OC
Inv

HV I_OC Inv

HV K_OC Inv
HV A_OC Inv

200

0.14

Ref to IEC and ANSI Curves

HV B_OC Inv

60

Ref to IEC and ANSI Curves

10

0.02

Ref to IEC and ANSI Curves

90

45

HV P_OC Inv
HV Angle_OC

Blk

92

ahead of current.
st

The maximum 1 -harmonic

HV
Imax_2H_Un

The angle setting for voltage

0.25Ir

20Ir

current setting to remove the


inrush block, in HV O/C pro-

Chapter 6 Overcurrent protection


tection
Inrush 2
HV Ra-

0.07

tio_I2/I1

0.5

0.2

nd

harmonic ratio set-

ting for blocking HV O/C protection


Inrush 2

HV
T2h_Cross_B

60

20

lk

nd

harmonic

cross-block time for HV O/C


protection

Table 41 Binary settings of overcurrent protection for HV side of transformer


DeSetting

Unit

Min.

Max.

fault
set-

Description

ting
st

HV Func_OC1

The 1 stage of HV OC (OC_1)


0

protection is switched ON
1-on; 0-off.

HV OC1 Direction

Direction (DIR) detection of HV OC


0

Stage 1 is switched ON
1-on; 0-off.

HV OC1 Dir To

Direction unit of HV OC Stage 1

Sys
0

points to system
0 - point to the protected transformer
1- point to system

HV OC1 Inrush
Block

Inrush 2
0

nd

harmonic detection HV

OC Stage 1 is switched ON
1-on; 0-off.
nd

HV Func_OC2

The 2 stage of HV OC (OC_2)


0

protection is switched ON
1-on; 0-off.

HV OC2 Direction

Direction (DIR) detection of HV OC


0

Stage 2 is switched ON
1-on; 0-off.

HV OC2 Dir To

Direction unit of HV OC Stage 2

Sys
0

points to system
0 - point to the protected transformer
1- point to system

HV OC2 Inrush
Block

Inrush 2
0

nd

harmonic detection HV

OC Stage 2 is switched ON
1-on; 0-off.

93

Chapter 6 Overcurrent protection


HV Func_OC

The IDMTL inverse time stage of HV

Inv

OC protection is switched ON
1-on; 0-off.

HV OC Inv Di-

Direction (DIR) detection of HV OC

rection

IDMTL inverse time is switched ON


1-on; 0-off.

HV OC Inv Dir

Direction unit of HV OC IDMTL in-

To Sys
0

verse time points to system

0 - point to the protected transformer


1- point to system

HV OC Inv In-

Inrush 2

rush Block
0

nd

harmonic detection HV

OC IDMTL inverse time is switched

ON
1-on; 0-off.

Block HV OC at

Select to block HV OC protection or

HV VT_Fail

exit direction unit, when HV VT fails

0- HV Direct OK at HV VT Fail
1- Blk HV OC at HV VT Fail

HV OC Initiate

HV OC protection initiate LV side

LV CBF

CBF
0 - initiate, 1 not initiate

HV OC Initiate

HV OC protection initiate MV side

MV CBF

CBF
0 - initiate, 1 not initiate

Table 42 Settings of overcurrent protection for MV side of transformer

Setting

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

0.05Ir

20Ir

MV T_OC1

60

60

MV I_OC2

0.05Ir

20Ir

MV T_OC2

60

60

12

Curve_OC

Description

A)

MV I_OC1

MV

94

Unit

Min.

MV overcurrent (O/C) current


setting for Stage 1
Time setting for MV OC, Stage
1
MV overcurrent (O/C) current
setting for Stage 2
Time setting for MV OC, Stage
2
Ref to IEC and ANSI Curves

Chapter 6 Overcurrent protection


Inv

MV I_OC Inv

MV K_OC Inv

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

MV A_OC Inv

200

0.14

Ref to IEC and ANSI Curves

MV B_OC Inv

60

Ref to IEC and ANSI Curves

10

0.02

Ref to IEC and ANSI Curves

90

45

MV P_OC Inv
MV Angle_OC

The angle setting for voltage


ahead of current.
st

The maximum 1 -harmonic


MV
Imax_2H_Un

0.25Ir

20Ir

Blk

current setting to remove the


inrush block, in MV O/C protection
Inrush 2

MV Ra-

0.07

tio_I2/I1

0.2

0.5

nd

harmonic ratio set-

ting for blocking MV O/C protection


Inrush 2

MV
T2h_Cross_B

20

60

lk

nd

harmonic

cross-block time for MV O/C


protection

Table 43 Binary settings of overcurrent protection for MV side of transformer


DeSetting

Unit

Min.

Max.

fault
set-

Description

ting
st

MV Func_OC1

The 1 stage of MV OC (OC_1)


0

protection is switched ON
1-on; 0-off.

MV OC1 Direction

Direction (DIR) detection of MV OC


0

Stage 1 is switched ON
1-on; 0-off.

MV OC1 Dir To

Direction unit of MV OC Stage 1

Sys
0

points to system
0 - point to the protected transformer
1- point to system

MV OC1 Inrush
Block

Inrush 2
0

nd

harmonic detection MV

OC Stage 1 is switched ON
1-on; 0-off.

95

Chapter 6 Overcurrent protection


nd

MV Func_OC2

The 2 stage of MV OC (OC_2)


0

protection is switched ON
1-on; 0-off.

MV OC2 Direc-

Direction (DIR) detection of MV OC

tion

Stage 2 is switched ON
1-on; 0-off.

MV OC2 Dir To

Direction unit of MV OC Stage 2

Sys
0

points to system

0 - point to the protected transformer


1- point to system

MV OC2 Inrush

Inrush 2

Block

nd

harmonic detection MV

OC Stage 2 is switched ON
1-on; 0-off.

MV Func_OC

The IDMTL inverse time stage of MV

Inv

OC protection is switched ON
1-on; 0-off.

MV OC Inv

Direction (DIR) detection of MV OC

Direction

IDMTL inverse time is switched ON


1-on; 0-off.

MV OC Inv Dir

Direction unit of MV OC IDMTL in-

To Sys
0

verse time points to system

0 - point to the protected transformer


1- point to system

MV OC Inv

Inrush 2

Inrush Block
0

nd

harmonic detection MV

OC IDMTL inverse time is switched

ON
1-on; 0-off.

Block MV OC

Select to block MV OC protection or

at MV VT_Fail

exit direction unit, when MV VT fails

0- MV Direct OK at MV VT Fail
1- Blk MV OC at MV VT Fail

MV OC Initiate

MV OC protection initiate HV1 side

HV1 CBF

CBF
0 - initiate, 1 not initiate

Table 44 Settings of overcurrent protection for LV side of transformer

Setting

96

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1
A)

Description

Chapter 6 Overcurrent protection


LV overcurrent (O/C) current

LV I_OC1

0.05Ir

20Ir

LV T_OC1

60

60

LV I_OC2

0.05Ir

20Ir

LV T_OC2

60

60

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

setting for Stage 1


Time setting for LV OC, Stage
1
LV overcurrent (O/C) current
setting for Stage 2
Time setting for LV OC, Stage
2

MV
Curve_OC
Inv

LV I_OC Inv

LV K_OC Inv
LV A_OC Inv

200

0.14

Ref to IEC and ANSI Curves

LV B_OC Inv

60

Ref to IEC and ANSI Curves

LV P_OC Inv

10

0.02

Ref to IEC and ANSI Curves

LV Angle_OC

90

45

The angle setting for voltage


ahead of current.
st

The maximum 1 -harmonic


LV
Imax_2H_Un

0.25Ir

20Ir

Blk

current setting to remove the


inrush block, in LV O/C protection
Inrush 2

LV Ra-

0.07

tio_I2/I1

0.2

0.5

nd

harmonic ratio set-

ting for blocking LV O/C protection


Inrush 2

LV
T2h_Cross_B

20

60

lk

nd

harmonic

cross-block time for LV O/C


protection

Table 45 Binary settings of overcurrent protection for LV side of transformer


DeSetting

Unit

Min.

Max.

fault
set-

Description

ting
st

LV Func_OC1

The 1 stage of LV OC (OC_1) pro0

tection is switched ON
1-on; 0-off.

LV OC1 Direc-

Direction (DIR) detection of LV OC


97

Chapter 6 Overcurrent protection


tion

Stage 1 is switched ON
1-on; 0-off.

LV OC1 Dir To

Direction unit of LV OC Stage 1

Sys
0

points to system
0 - point to the protected transformer
1- point to system

LV OC1 Inrush
Block

Inrush 2
0

nd

harmonic detection LV

OC Stage 1 is switched ON
1-on; 0-off.
nd

LV Func_OC2

The 2 stage of LV OC (OC_2)


0

protection is switched ON
1-on; 0-off.

LV OC2 Direction

Direction (DIR) detection of LV OC


0

Stage 2 is switched ON
1-on; 0-off.

LV OC2 Dir To

Direction unit of LV OC Stage 2

Sys
0

points to system
0 - point to the protected transformer
1- point to system

LV OC2 Inrush
Block

Inrush 2
0

nd

harmonic detection LV

OC Stage 2 is switched ON
1-on; 0-off.

LV Func_OC
Inv

The IDMTL inverse time stage of LV


0

OC protection is switched ON
1-on; 0-off.

LV OC Inv Direction

Direction (DIR) detection of LV OC


0

IDMTL inverse time is switched ON


1-on; 0-off.

LV OC Inv Dir

Direction unit of LV OC IDMTL in-

To Sys
0

verse time points to system


0 - point to the protected transformer
1- point to system

LV OC Inv In-

Inrush 2

rush Block
0

nd

harmonic detection LV

OC IDMTL inverse time is switched


ON
1-on; 0-off.

Block LV OC at
LV VT_Fail

Select to block LV OC protection or


0

exit direction unit, when LV VT fails


0- LV Direct OK at LV VT Fail
1- Blk LV OC at LV VT Fail

98

Chapter 6 Overcurrent protection


LV OC Initiate

LV OC protection initiate HV1 side

HV1 CBF

CBF
0 - initiate, 1 not initiate

Report
Table 46 Event report list

Information

Description

HV OC Inv Trip

Inverse time stage of HV overcurrent protection trip

HV OC1 Trip

HV overcurrent stage 1 trip

HV OC2 Trip

HV overcurrent stage 2 trip

MV OC Inv Trip

Inverse time stage of MV overcurrent protection trip

MV OC1 Trip

MV overcurrent stage 1 trip

MV OC2 Trip

MV overcurrent stage 2 trip

LV OC Inv Trip

Inverse time stage of LV overcurrent protection trip

LV OC1 Trip

LV overcurrent stage 1 trip

LV OC2 Trip

LV overcurrent stage 2 trip

Table 47 Operation report list

Information

Description

HV Func_OC On

Overcurrent protection of HV side is switched ON (by CW)

HV Func_OC Off

Overcurrent protection of HV side is switched OFF (by CW)

MV Func_OC On

Overcurrent protection of MV side is switched ON (by CW)

MV Func_OC Off

Overcurrent protection of MV side is switched OFF (by CW)

LV Func_OC On

Overcurrent protection of LV side is switched ON (by CW)

LV Func_OC Off

Overcurrent protection of LV side is switched OFF (by CW)

Technical data
Table 48 Overcurrent protection technical data
Item

Rang or Value

Tolerance

Definite time characteristics


Current

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

99

Chapter 6 Overcurrent protection


Time delay

0.00 to 60.00s, step 0.01s

Reset time

approx. 40ms

Reset ratio

Approx. 0.95 at I/In 0.5

1% setting or +40ms, at 200%


operating setting

Inverse time characteristics


Current

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

IEC standard

Normal inverse;

5% setting + 40ms, at 2

Very inverse;

<I/ISETTING < 20, in accordance

Extremely inverse;

with IEC60255-151

Long inverse
ANSI

Inverse;

5% setting + 40ms, at 2

Short inverse;

<I/ISETTING < 20, in accord-

Long inverse;

ance with ANSI/IEEE C37.112,

Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
5% setting + 40ms, at 2

user-defined characteristic

<I/ISETTING < 20, in accordance

T=

with IEC60255-151
Time factor of inverse time, A

0.005 to 200.0s, step 0.001s

Delay of inverse time, B

0.000 to 60.00s, step 0.01s

Index of inverse time, P

0.005 to 10.00, step 0.005

set time Multiplier for step n: k

0.05 to 999.0, step 0.01

Minimum operating time

20ms

Maximum operating time

100s

Reset mode

instantaneous

Reset time

approx. 40ms,
Directional element

Operating area range

170

Characteristic angle

0to 90, step 1

100

3, at phase to phase voltage >1V

Chapter 7 Earth fault protection

Chapter 7 Earth fault protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for earth fault
protection function.

101

Chapter 7 Earth fault protection

Protection principle

1.1

Protection elements
Each voltage side of the protected transformer is provided with three earth
fault protection elements from which two elements operate as definite earth
fault stages and the other one operates with inverse time-current characteristic. All the elements can operate in conjunction with the integrated inrush restraint and directional functions.
Various stages of each element are independent from each other and can be
combined as desired. They can be enabled or disabled in each side using
dedicated Binary settings. These Binary settings include HV Func_EF1, HV
Func_EF2 and HV Func_EF Inv on, for HV side earth fault protection, MV
Func_EF1, MV Func_EF2 and MV Func_EF Inv, for MV side earth fault
protection, LV Func_EF1, LV Func_EF2 and LV Func_EF Inv, for LV side
earth fault protection. For example by applying setting 1-on to HV
Func_EF1, respective stage of earth fault protection would be enabled in HV
side.
Individual pickup value for each definite stage can be defined by setting HV
3I0_EF1 and HV 3I0_EF2 for HV side, MV 3I0_EF1 and MV 3I0_EF2 for
MV side, LV 3I0_EF1 and LV 3I0_EF2 for LV side. By applying these settings, each earth current (quantity 3I0) calculated from the three phase currents is compared separately with the setting value for each stage. If the respective value is exceeded, a trip time delay timer is started. The condition for
start of the delay timer is expressed mathematically:

3I 0 3I 0set
Equation 33
The timer is set to count up to a user-defined time delay. The time delay can
be set for each definite stage individually through settings HV T_EF1 and
HV T_EF2 for HV side, MV T_EF1 and MV T_EF2 for MV side, LV
T_EF1 and LV T_EF2 for LV side. After the user-defined time delay has
been elapsed, a trip signal is issued if the inrush restraint feature is applied
and no inrush current is detected or inrush restraint is disabled. The earth
fault protection would be blocked and therefore, no tripping takes place if the
inrush restraint feature is enabled and an inrush condition exists. However, an
alarm report is issued nominated as HV EF1 Inrush Block, HV EF2 Inrush
Block or HV EF Inv Inrush Block, indicating the blocking condition of earth
fault element caused by inrush condition detection.
Pickup value for the inverse time-current stage can be set by setting HV
3I0_EF Inv, MV 3I0_EF Inv and LV 3I0_EF Inv for HV, MV and LV sides,
respectively. Each earth current (quantity 3I0) calculated from the three phase
102

Chapter 7 Earth fault protection


currents is separately compared with corresponding setting value. If a current
exceeds 1.1 times the setting value, corresponding stage picks up. When an
inverse time-current stage picks up, the tripping time is calculated from the
calculated quantity 3I0, using the selected tripping curve. Maximum tripping
time is limited to 100s.
The time delay of time-inverse characteristic is calculated based on the type
of the characteristic, the magnitude of the current and a time multiplier. For
the time-inverse characteristic, both ANSI and IEC based standard curves are
available and any user-defined characteristic can be defined using the following equation:

A _ EF Inv

t K _ EF Inv
B _ EF Inv
HP _ EF Inv
I

-1
I S

Equation 34
Where I is the calculated earth fault current;
Is is the current setting;
A_EF Inv: Time factor for inverse time stage
B_EF Inv: Time delay for inverse time stage
P_EF Inv: index for inverse time stage
K_EF Inv: Time multiplier
By applying the desired setting values, the device calculates the tripping time
from the zero sequence current. Once the calculated time elapsed, report EF
Inv Trip will be issued.
As mentioned previously, selection among the curves can be carried out by
settings HV Curve_EF Inv, MV Curve_EF Inv and LV Curve_EF Inv for
HV, MV and LV sides, respectively. Furthermore, the time multiplier K_EF Inv
can be applied by user to coordinate the integrated inverse time-current
characteristic of the device with other earth fault relays installed for power
system protection. This can be performed by settings HV K_EF Inv, MV
K_EF Inv and LV K_EF Inv in case of HV, MV and LV earth fault elements.
By applying pickup current and time multiplier settings, the device determines
the tripping time from the calculated earth current, based on the selected inverse curve. Once the calculated time has been elapsed, a trip signal is issued provided that no inrush current is detected or inrush restraint is disabled.
If the inrush restraint feature is enabled and an inrush condition exists the
earth fault protection would be blocked and therefore no tripping takes place.
103

Chapter 7 Earth fault protection


However, an alarm report is issued designated as HV Inrush Blk BU, MV
Inrush Blk BU or LV Inrush Blk BU, indicating the blocking condition of
overcurrent element caused by inrush condition detection.
The trip signals and corresponding event reports are available separately for
each stage. They include HV EF_1 Trip, HV EF_2 Trip and HV IDMTL EF
Trip for HV side, MV EF_1 Trip, MV EF_2 Trip and MV IDMTL EF Trip for
MV side, LV EF_1 Trip, LV EF_1 Trip and LV IDMTL EF Trip for LV side
earth fault elements.

1.2

Inrush Restraint Feature


The transformer earth fault protection may detect large magnetizing inrush
currents flowing when transformer is energized. The inrush current may be
several times of the nominal current, and may last from several tens of milliseconds to several seconds.
Inrush current comprises second harmonic as well as a considerable fundamental component. So, it may affect earth fault protection which operates
based on the fundamental component of the measured current. Inrush
blocking unit in earth fault function is provided for this purpose.
It is possible to apply the inrush restraint feature separately to each definite
stage and inverse time-current stage of earth fault element by using Binary
settings HV EF1 Inrush Block, HV EF2 Inrush Block and HV EF Inv Inrush
Block for HV side, MV EF1 Inrush Block, MV EF2 Inrush Block and MV
EF Inv Inrush Block for MV side, LV EF1 Inrush Block, LV EF2 Inrush
Block and LV EF Inv Inrush Block on for LV side. By applying setting 1-on
to each of the mentioned Binary settings, no trip command would be possible
by corresponding stage, if an inrush condition is detected.
Since the inrush current contains a relatively large second harmonic component which is nearly absent during a fault current, the inrush restraint operates based on the evaluation of the second harmonic content which is present
in the phase currents. The inrush condition is recognized if the ratio of second
harmonic current to the fundamental component exceeds the setting value
HV Ratio_I2/I1_EF, MV Ratio_I2/I1_EF or LV Ratio_I2/I1_EF in each
phase current. The setting is applicable to both the definite stages of earth
fault protection element as well as the inverse time-current stage. As soon as
the measured ratio exceeds the set threshold, a restraint is applied to those
stages for which corresponding setting is applied to make them blocked in
inrush condition detection (HV EF1 Inrush Block, HV EF2 Inrush Block and
HV EF Inv Inrush Block on for HV side, MV EF1 Inrush Block, MV EF2
Inrush Block and MV EF Inv Inrush Block for MV side, LV EF_1 Inrush
Detect ON, LV EF1 Inrush Block, LV EF2 Inrush Block and LV EF Inv
Inrush Block for LV side).
Furthermore, if the fundamental component of each phase current exceeds
the upper limit value HV Ratio_I2/I1, MV Ratio_I2/I1 or LV Ratio_I2/I1,
the inrush restraint will no longer effective in respective side, since a
high-current fault is assumed in this case.

104

Chapter 7 Earth fault protection


1.3

Direction Determination Feature


The integrated directional function can be applied to each stage of earth fault
elements via Binary settings. The Binary settings include HV EF1 Direction,
HV EF2 Direction and HV EF Inv Direction on for HV side earth fault
stages, MV EF1 Direction, MV EF2 Direction and MV EF Inv Direction for
MV side earth fault stages and LV EF1 Direction, LV EF2 Direction and LV
EF Inv Direction for LV side earth fault stages.
Furthermore, the directional orientation can be set individually for each stage
of earth fault elements in various sides of the protected transformer. This can
be performed by Binary settings HV EF1 Dir To Sys, HV EF2 Dir To Sys
and HV EF Inv Dir To Sys for HV side, MV EF1 Dir To Sys, MV EF2 Dir To
Sys and MV EF Inv Dir To Sys for MV side, LV EF1 Dir To Sys, LV EF2
Dir To Sys and LV EF Inv Dir To Sys for LV side. The possible settings for
these Binary setting comprise 0-toward transformer and 1-toward system.
Basically, the direction determination is performed by comparing the zero
sequence system quantities. In the current path, 3I0 current is calculated from
the sum of the three phase currents. In the voltage path, the device calculates
the zero sequence voltage 3V0 from the sum of the three phase voltages.
Contrary to the directional phase elements, which work with the un-faulted
voltage as reference voltage, the fault voltage itself is the reference voltage
for the directional ground element. Depending on the connection of the voltage transformer, this is the voltage 3V0 or VN. The directional element at
each side operates with the residual/ neutral voltage of the same side.
In order to satisfy different network conditions and applications, the reference
voltage can be rotated by an adjustable angle. For each side of the protected
transformer, the directional angle can be set independently. The settings include HV Angle_EF, MV Angle_EF and LV Angle_EF, for HV, MV and LV
sides, respectively. It should be noted that the settings affect all the directional
stages of the corresponding earth fault element.
NOTE: The direction mentioned above is based on that the positive polarities of
three phases CT.

The voltage used by directional element is calculated by

three phase voltage. Details are shown as below.

Below figure shows an example of direction determination for a fault in phase


A. As can be seen from the figure, fault current 3I0 lags from fault voltage Va.
Accordingly, fault current -3I0 lags residual sequence voltage 3U0 by this
angle. The reference voltage 3U0 is rotated to be as close as possible to -3I0
current. Furthermore, the forward area is depicted in the figure.

105

Chapter 7 Earth fault protection

3I 0

90

0
3U 0_Ref
Angle_EF
Angle_Range
EF

Forward

-3 I 0

Bisector

Figure 41 Characteristic of zero sequence directional element


where:
Angle_EF: The settable characteristic angle
Angle_Range EF: 80
During direction decision by directional function, a VT Fail condition (a short
circuit or broken wire in the voltage transformer's secondary system or an
operation of the voltage transformer fuse) may result in false or undesired
tripping by directional earth fault elements. In such a situation, it is possible to
select operation status of the directional earth fault protection elements in
each side by using a number of Binary settings to block the earth fault protection elements or keep them in operational state with no direction decision
(block direction decision). The Binary settings are designated as Block HV
EF at HV VT_Fail, Block MV EF at HV VT_Fail and Block LV EF at HV
VT_Fail, for HV, MV and LV sides, respectively. When the Binary settings are
set as 0 to select Direct OK at VT Fail, corresponding earth fault protection
elements will not judge direction at the local side VT failure. When they set as
1 to select Block EF at VT Fail, no operation is possible by the earth fault
protection elements. It is noted that the Binary settings affect all the stages of
corresponding earth fault elements at each side. For instance, by applying
setting Block HV EF at HV VT_Fail off, all the three stages of the earth fault
element will remain operative without direction determination in case of any
fault in secondary circuit of HV side voltage transformer. On the other hand,
setting Block HV EF at HV VT_Fail on makes them blocked.
It is possible to block earth fault protection elements in each side of the protected transformer if a CT fail is detected in the same side. This can be performed by Binary settings Block HV EF at HV CT_Fail, Blk MV EF at MV
CT_FAIL and Blk LV EF at LV CT FAIL in each voltage side. If setting 1 is
applied to these Binary settings, any CT fail detection in a given side of the
power transformer would bring blocking condition to all stages of the earth
106

Chapter 7 Earth fault protection


fault element which is applied in the same side.
The logic for definite and inverse time IDMTL earth fault protection is shown in
below figure.
HV EF Direction

DIR Positive
VT failure
Direct OK at VT FAIL

A
N
D

O
R

E/F Direction Unit OK

A
N
D

HV Func_EF1 (2) on

3I0>HV 3I0_EF1(2)

A
N
D

HV T_EF1(2)

E/F Trip

Direction Unit OK
Inrush BLK EF
HV Func_EF1 (2) on
HV Func_EF Inv on

Inverse Curve>

A
N
D

IDMTL E/F Trip

E/F Direction OK
Inrush BLK EF

Figure 42 Tripping logic for earth fault protection

1.4

CBF initiation Feature


It is possible to set whether the earth fault protection elements can initiate the
integrated CBF protection or not. The available choices depend on the voltage side of the power transformer at which earth fault protection is applied. In
this context, HV side earth fault protection element always initiates HV side
CBF function with no additional setting. However, it is possible to select
whether it can initiate MV and LV CBF protection functions via Binary settings
HV EF Initiate LV CBF and HV EF Initiate MV CBF on, respectively.
MV side earth fault protection element always initiates MV side CBF function
with no additional setting. However, it is possible to select whether it can initiate HV side CBF protection function via Binary setting MV EF Initiate HV1
CBF on.
More detail information about the initiation conditions and related Binary settings can be found in below table.

107

Chapter 7 Earth fault protection

Input and output signals


Earth Fault
Protection
IA1

EF1 Trip

IB1

EF2 Trip

IC1

EF Inv Trip

IA2

Relay Startup

IB2
IC2
UA
UB
UC

Figure 43 Earth fault protection module


Table 49 Analog input list

Signal

Description

IA1

Phase A current input of CT of circuit breaker 1

IB1

Phase B current input of CT of circuit breaker 1

IC1

Phase C current input of CT of circuit breaker 1

IA2

Phase A current input of CT of circuit breaker 2

IB2

Phase B current input of CT of circuit breaker 2

IC2

Phase C current input of CT of circuit breaker 2

UA

Phase A voltage input of VT of related winding of transformer

UB

Phase B voltage input of VT of related winding of transformer

UC

Phase C voltage input of VT of related winding of transformer

Table 50 Binary output list

Signal

Description

EF1 Trip

Earth Fault stage 1 trip

EF2 Trip

Earth Fault stage 2 trip

EF Inv Trip

Earth Fault inverse stage trip

108

Chapter 7 Earth fault protection

Signal

Description

Relay Startup

Relay Startup

Setting
Table 51 Settings of earth fault protection for HV side of transformer

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
HV earth fault (E/F) protection

HV 3I0_EF1

0.05Ir

20Ir

HV T_EF1

60

60

HV 3I0_EF2

0.05Ir

20Ir

HV T_EF2

60

60

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

1.2

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

200

0.14

Ref to IEC and ANSI Curves

60

Ref to IEC and ANSI Curves

10

0.02

Ref to IEC and ANSI Curves

90

45

current setting for Stage 1


Time setting for HV E/F, Stage 1
HV earth fault (E/F) current setting for Stage 2
Time setting for HV E/F, Stage 2

HV
Curve_EF
Inv
HV 3I0_EF
Inv

HV K_EF
Inv
HV A_EF
Inv
HV B_EF
Inv
HV P_EF
Inv
HV Angle_EF

ahead of current.
st

The maximum 1 -harmonic cur-

HV
Imax_2H_U

The angle setting for voltage

0.25Ir

20Ir

nBlk_EF

rent setting to remove the inrush


block, in HV EF protection
st

The maximum 1 -harmonic curHV Ratio_I2/I1_EF

0.07

0.5

0.2

rent setting to remove the inrush


block, in HV EF protection

109

Chapter 7 Earth fault protection


Table 52 Binary settings of earth fault protection for HV side of transformer
DeSetting

Unit

Min.

Max.

fault
set-

Description

ting
st

The 1 stage of HV earth fault


HV Func_EF1

(EF_1) protection is switched ON


1-on; 0-off.
Direction (DIR) detection of HV EF

HV EF1 Direction

Stage 1 is switched ON
1-on; 0-off.
Direction unit of HV EF Stage 1

HV EF1 Dir To
Sys

points to system
0 - point to the protected transformer
1- point to system
Inrush 2

HV EF1 Inrush
Block

nd

harmonic detection HV

EF Stage 1 is switched ON
1-on; 0-off.
nd

The 2 stage of HV earth fault


HV Func_EF2

(EF_2) protection is switched ON


1-on; 0-off.
Direction (DIR) detection of HV EF

HV EF2 Direction

Stage 2 is switched ON
1-on; 0-off.
Direction unit of HV EF Stage 2

HV EF2 Dir To
Sys

points to system
0 - point to the protected transformer
1- point to system
Inrush 2

HV EF2 Inrush
Block

nd

harmonic detection HV

EF Stage 2 is switched ON
1-on; 0-off.
The IDMTL inverse time stage of HV

HV Func_EF Inv

EF protection is switched ON
1-on; 0-off.
Direction (DIR) detection of HV EF

HV EF Inv Direction

IDMTL inverse time is switched ON


1-on; 0-off.

HV EF Inv Dir To
Sys

110

Direction unit of HV EF IDMTL inverse time points to system

Chapter 7 Earth fault protection


0 - point to the protected transformer
1- point to system
Inrush 2
HV EF Inv Inrush

Block

nd

harmonic detection HV

EF IDMTL inverse time is switched


ON
1-on; 0-off.
Select to block HV EF protection or

Block HV EF at

HV VT_Fail

exit direction unit, when HV VT fails


0 - HV Direct OK at HV VT Fail
1 - Blk HV EF at HV VT Fail
Block HV EF when there is HV CT

Block HV EF at

HV CT_Fail

failure
1-Block; 0-NOT block
HV EF protection initiate LV side

HV EF Initiate LV

CBF

CBF
0 - initiate, 1 not initiate
HV EF protection initiate MV side

HV EF Initiate

MV CBF

CBF
0 - initiate, 1 not initiate

Table 53 Settings of earth fault protection for MV side of transformer

Setting

MV
3I0_EF1
MV T_EF1
MV
3I0_EF2
MV T_EF2

Default

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.05Ir

20Ir

60

60

0.05Ir

20Ir

60

60

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

200

0.14

Ref to IEC and ANSI Curves

Unit

setting
(Ir:5A/1

Description

A)
MV earth fault (E/F) protection
current setting for Stage 1
Time setting for MV E/F, Stage 1
MV earth fault (E/F) current setting for Stage 2
Time setting for MV E/F, Stage 2

MV
Curve_EF
Inv
MV 3I0_EF
Inv

MV K_EF
Inv
MV A_EF
Inv

111

Chapter 7 Earth fault protection


MV B_EF
Inv

MV P_EF
Inv
MV Angle_EF

60

Ref to IEC and ANSI Curves

10

0.02

Ref to IEC and ANSI Curves

90

45

The angle setting for voltage


ahead of current.
st

The maximum 1 -harmonic cur-

MV
Imax_2H_U

0.25Ir

20Ir

nBlk_EF

rent setting to remove the inrush


block, in MV E/F protection

MV Ra-

0.07

tio_I2/I1_EF

0.5

0.2

Inrush 2

nd

harmonic ratio setting

for blocking MV E/F protection

Table 54 Binary settings of earth fault protection for MV side of transformer


DeSetting

Unit

Min.

Max.

fault
set-

Description

ting
st

The 1 stage of MV earth fault


MV Func_EF1

(EF_1) protection is switched ON


1-on; 0-off.
Direction (DIR) detection of MV EF

MV EF1 Direction

Stage 1 is switched ON
1-on; 0-off.
Direction unit of MV EF Stage 1

MV EF1 Dir To
Sys

points to system
0 - point to the protected transformer
1- point to system
Inrush 2

MV EF1 Inrush
Block

nd

harmonic detection MV

EF Stage 1 is switched ON
1-on; 0-off.
nd

The 2 stage of MV earth fault


MV Func_EF2

(EF_2) protection is switched ON


1-on; 0-off.
Direction (DIR) detection of MV EF

MV EF2 Direction

Stage 2 is switched ON
1-on; 0-off.
Direction unit of MV EF Stage 2

MV EF2 Dir To
Sys

points to system
0 - point to the protected transformer
1- point to system

112

Chapter 7 Earth fault protection


Inrush 2
MV EF2 Inrush

Block

nd

harmonic detection MV

EF Stage 2 is switched ON
1-on; 0-off.
The IDMTL inverse time stage of MV

MV Func_EF Inv

EF protection is switched ON
1-on; 0-off.
Direction (DIR) detection of MV EF

MV EF Inv Direc-

tion

IDMTL inverse time is switched ON


1-on; 0-off.
Direction unit of MV EF IDMTL in-

MV EF Inv Dir To

Sys

verse time points to system


0 - point to the protected transformer
1- point to system
Inrush 2

MV EF Inv Inrush

Block

nd

harmonic detection MV

EF IDMTL inverse time is switched


ON
1-on; 0-off.
Select to block MV EF protection or

Block MV EF at

MV VT_Fail

exit direction unit, when MV VT fails


0 - MV Direct OK at MV VT Fail
1 - Blk MV EF at MV VT Fail
Block MV EF when there is MV CT

Block MV EF at

MV CT_Fail

failure
1-Block; 0-NOT block
MV EF protection initiate HV1 side

MV EF Initiate

HV CBF

CBF
0 - initiate, 1 not initiate

Table 55 Settings of earth fault protection for LV side of transformer

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)

LV 3I0_EF1

0.05Ir

20Ir

LV T_EF1

60

60

LV 3I0_EF2

0.05Ir

20Ir

LV T_EF2

60

60

LV earth fault (E/F) protection


current setting for Stage 1
Time setting for LV E/F, Stage 1
LV earth fault (E/F) current setting
for Stage 2
Time setting for LV E/F, Stage 2

113

Chapter 7 Earth fault protection


LV
Curve_EF

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

Inv
LV 3I0_EF
Inv

LV K_EF Inv
LV A_EF Inv

200

0.14

Ref to IEC and ANSI Curves

LV B_EF Inv

60

Ref to IEC and ANSI Curves

10

0.02

Ref to IEC and ANSI Curves

90

45

LV P_EF Inv
LV Angle_EF

The angle setting for voltage


ahead of current.
st

The maximum 1 -harmonic cur-

LV
Imax_2H_U

0.25Ir

20Ir

rent setting to remove the inrush

nBlk_EF

block, in LV E/F protection

LV Ra-

Inrush 2

0.07

tio_I2/I1_EF

0.5

0.2

nd

harmonic ratio setting

for blocking LV E/F protection

Table 56 Binary settings of earth fault protection for LV side of transformer


DeSetting

Unit

Min.

Max.

fault
set-

Description

ting
st

The 1 stage of LV earth fault


LV Func_EF1

(EF_1) protection is switched ON


1-on; 0-off.
Direction (DIR) detection of LV EF

LV EF1 Direction

Stage 1 is switched ON
1-on; 0-off.
Direction unit of LV EF Stage 1

LV EF1 Dir To
Sys

points to system
0 - point to the protected transformer
1- point to system
Inrush 2

LV EF1 Inrush
Block

nd

harmonic detection LV EF

Stage 1 is switched ON
1-on; 0-off.
nd

The 2 stage of LV earth fault


LV Func_EF2

(EF_2) protection is switched ON


1-on; 0-off.

114

Chapter 7 Earth fault protection


Direction (DIR) detection of LV EF
LV EF2 Direction

Stage 2 is switched ON
1-on; 0-off.
Direction unit of LV EF Stage 2

LV EF2 Dir To
Sys

points to system
0 - point to the protected transformer
1- point to system
Inrush 2

LV EF2 Inrush
Block

nd

harmonic detection LV EF

Stage 2 is switched ON
1-on; 0-off.
The IDMTL inverse time stage of LV

LV Func_EF Inv

EF protection is switched ON
1-on; 0-off.
Direction (DIR) detection of LV EF

LV EF Inv Direction

IDMTL inverse time is switched ON


1-on; 0-off.
Direction unit of LV EF IDMTL in-

LV EF Inv Dir To
Sys

verse time points to system


0 - point to the protected transformer
1- point to system
Inrush 2

LV EF Inv Inrush
Block

nd

harmonic detection LV EF

IDMTL inverse time is switched ON


1-on; 0-off.
Select to block LV EF protection or

Block LV EF at
LV VT_Fail

exit direction unit, when LV VT fails


0 - LV Direct OK at LV VT Fail
1 - Blk LV EF at LV VT Fail

Block LV EF at
LV CT_Fail

Block LV EF when there is LV CT


0

failure
1-Block; 0-NOT block
LV EF protection initiate HV1 side

LV EF Initiate HV
CBF

CBF
0 - initiate, 1 not initiate

Report
Table 57 Event report list

Information

Description

115

Chapter 7 Earth fault protection

Information

Description

HV EF Inv Trip

Inverse time stage of HV earth fault protection trip

HV EF1 Trip

HV earth fault stage 1 trip

HV EF2 Trip

HV earth fault stage 2 trip

MV EF Inv Trip

Inverse time stage of MV earth fault protection trip

MV EF1 Trip

MV earth fault stage 1 trip

MV EF2 Trip

MV earth fault stage 2 trip

LV EF Inv Trip

Inverse time stage of LV earth fault protection trip

LV EF1 Trip

LV earth fault stage 1 trip

LV EF2 Trip

LV earth fault stage 2 trip

Table 58 Operation report list

Information

Description

HV Func_EF On

Earth fault protection of HV side is switched ON (by CW)

HV Func_EF Off

Earth fault protection of HV side is switched OFF (by CW)

MV Func_EF On

Earth fault protection of MV side is switched ON (by CW)

MV Func_EF Off

Earth fault protection of MV side is switched OFF (by CW)

LV Func_EF On

Earth fault protection of LV side is switched ON (by CW)

LV Func_EF Off

Earth fault protection of LV side is switched OFF (by CW)

Technical data
Table 59 Earth fault protection technical data
Item

Rang or value

Tolerance

Definite time characteristic


Current

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

Time delay

0.00 to 60.00s, step 0.01s

1% setting or +40ms, at 200%


operating setting

Reset time

approx. 40ms

Reset ratio

Approx. 0.95 at I/Ir 0.5


Inverse time characteristics

Current

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

IEC standard

Normal inverse;

IEC60255-151

Very inverse;

5% setting + 40ms, at 2

Extremely inverse;

<I/ISETTING < 20

116

Chapter 7 Earth fault protection


Long inverse
ANSI

Inverse;

ANSI/IEEE C37.112,

Short inverse;

5% setting + 40ms, at 2

Long inverse;

<I/ISETTING < 20

Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse
IEC60255-151

user-defined characteristic

5% setting + 40ms, at 2

T=

<I/ISETTING < 20
Time factor of inverse time, A

0.005 to 200.0s, step


0.001s

Delay of inverse time, B

0.000 to 60.00s, step 0.01s

Index of inverse time, P

0.005 to 10.00, step 0.005

set time Multiplier for step n: k

0.05 to 999.0, step 0.01

Minimum operating time

20ms

Maximum operating time

100s

Reset mode

instantaneous

Reset time

approx. 40ms
Directional element

Operating area range of zero


sequence directional element
Characteristic angle
Operating area range of negative
sequence directional element
Characteristic angle

160

3, at 3U01V

0to 90, step 1


160

3, at 3U22V

50to 90, step 1

117

Chapter 7 Earth fault protection

118

Chapter 8 Neutral earth fault protection

Chapter 8 Neutral earth fault


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for neutral earth
fault protection function.

119

Chapter 8 Neutral earth fault protection

Protection principle

1.1

Protection Elements
Each voltage side of the protected transformer is provided with three neutral
earth fault protection elements from which two elements operate as definite
earth fault stages and the other one operates with inverse time-current characteristic. All the elements can operate in conjunction with the integrated inrush restraint and directional functions.
Various stages of each element are independent from each other and can be
combined as desired. They can be enabled or disabled in each side using
dedicated Binary settings. These Binary settings include HV Func_Neu OC1,
HV Func_Neu OC2 and HV Func_Neu OC Inv, for HV side earth fault
protection, MV Func_Neu OC1, MV Func_Neu OC2 and MV Func_Neu
OC Inv, for MV side earth fault protection, LV Func_Neu OC1, LV
Func_Neu OC2 and LV Func_Neu OC Inv, for LV side earth fault protection.
For example by applying setting 1-on to HV Func_Neu OC1, respective
stage of neutral earth fault protection would be enabled in HV side.
Individual pickup value for each definite stage can be defined by setting HV
3I0_Neutral OC1 and HV 3I0_Neutral OC2 for HV side, MV 3I0_Neutral
OC1 and MV 3I0_Neutral OC2 for MV side, LV 3I0_Neutral OC1 and LV
3I0_Neutral OC2 for LV side. By applying these settings, each neutral current
(quantity IN) measured from the installed neutral CT is compared separately
with the setting value for each stage. If the respective value is exceeded, a
trip time delay timer is started. The condition for start of the delay timer is expressed mathematically:

I N I N _ set
Equation 35
The timer is set to count up to a user-defined time delay. The time delay can
be set for each definite stage individually through settings HV T_Neutral
OC1 and HV T_Neutral OC2 for HV side, MV T_Neutral OC1 and MV
T_Neutral OC2 for MV side, LV T_Neutral OC1 and LV T_Neutral OC2
for LV side. After the user-defined time delay has been elapsed, a trip signal is
issued if the inrush restraint feature is applied and no inrush current is detected or inrush restraint is disabled. The neutral earth fault protection would
be blocked and therefore, no tripping takes place if the inrush restraint feature
is enabled and an inrush condition exists. However, an alarm report is issued
nominated as HV Inrush Blk BU, MV Inrush Blk BU or LV Inrush Blk BU,
indicating the blocking condition of neutral earth fault element caused by inrush condition detection.
Pickup value for the inverse time-current stage can be set by setting HV
3I0_NOC Inv, MV 3I0_NOC Inv and LV 3I0_NOC Inv for HV, MV and LV
sides, respectively. Each neutral current (quantity IN) measured by installed
neutral CT is separately compared with corresponding setting value. If a current exceeds 1.1 times the setting value, corresponding stage picks up. When
120

Chapter 8 Neutral earth fault protection


an inverse time-current stage picks up, the tripping time is calculated from the
measured quantity IN, using the selected tripping curve. Maximum tripping
time is limited to 100s.
For Time-inverse characteristic, the pickup value can be defined by setting
3I0_NOC Inv. The measured zero sequence current is compared with corresponding setting value. If it exceeds the setting, related signal will be reported and the tripping time is calculated according to the pre-defined characteristic. The tripping curve can be set as IEC or ANSI standard curves or
any user-defined characteristic by following tripping time equation.

A _ NOC Inv

t K _ NOC Inv
B _ NOC Inv
P _ NOC Inv
I

-1
I S

Equation 36
Where I is the calculated neutral current;
Is is the current setting;
where:
A_NOC Inv: Time factor for inverse time stage
B_ NOC Inv: Time delay for inverse time stage
P_ NOC Inv: index for inverse time stage
K_ NOC Inv: Time multiplier
As mentioned previously, selection between the curves can be carried out by
settings HV Curve_NOC Inv, MV Curve_NOC Inv and LV Curve_NOC
Inv for HV, MV and LV sides, respectively. Furthermore, the time multiplier
K_NOC Inv can be applied by user to coordinate the integrated inverse
time-current characteristic of the device with other relays installed for power
system protection. This can be performed by settings HV K_NOC Inv, MV
K_NOC Inv and LV K_NOC Inv in case of HV, MV and LV neutral earth fault
elements.
By applying pickup current and time multiplier settings, the device determines
the tripping time from the measured neutral current, based on the selected
inverse curve. Once the calculated time has been elapsed, a trip signal is
issued provided that no inrush current is detected or inrush restraint is disabled. If the inrush restraint feature is enabled and an inrush condition exists,
the neutral earth fault protection would be blocked and therefore no tripping
takes place. However, alarm report of HV Inrush Blk BU, MV Inrush Blk BU
or LV Inrush Blk BU is issued, indicating the blocking condition of neutral
earth fault element caused by inrush condition detection.
The trip signals and corresponding event reports are available separately for
each stage. They include HV Neu OC_1 Trip, HV Neu OC_2 Trip and HV
Neu OC IDMTL for HV side, MV Neu OC_1 Trip, MV Neu OC_2 Trip and
MV Neu OC IDMTL for MV side, LV Neu OC_1 Trip, LV Neu OC_1 Trip
121

Chapter 8 Neutral earth fault protection


and LV Neu OC IDMTL for LV side neutral earth fault elements.

1.2

Inrush Restraint Feature


The transformer neutral earth fault protection may detect large magnetizing
inrush currents flowing when transformer is energized. The inrush current
may be several times of the nominal current, and may last from several tens
of milliseconds to several seconds.
Inrush current comprises second harmonic as well as a considerable fundamental component. So, it may affect neutral earth fault protection which operates based on the fundamental component of the measured current. Inrush
blocking unit in neutral earth fault function is provided for this purpose.
It is possible to apply the inrush restraint feature separately to each definite
stage and inverse time-current stage of earth fault element by using Binary
settings HV Neu OC1 Inrush Block, HV Neu OC2 Inrush Block and HV
Neu OC Inv Inrush Block on for HV side, MV Neu OC1 Inrush Block, MV
Neu OC2 Inrush Block and MV Neu OC Inv Inrush Block on for MV side,
LV Neu OC1 Inrush Block, LV Neu OC2 Inrush Block and LV Neu OC Inv
Inrush Block on for LV side. By applying setting 1-on to each of the mentioned Binary settings, no trip command would be possible by corresponding
stage, if an inrush condition is detected.
Since the inrush current contains a relatively large second harmonic component which is nearly absent during a fault current, the inrush restraint operates based on the evaluation of the second harmonic content which is present
in the measured neutral current (quantity IN), or in the phase currents, based
on setting. The inrush condition is recognized if the ratio of second harmonic
current to the fundamental component exceeds the setting value HV Ratio_I2/I1_NOC, MV Ratio_I2/I1_NOC or LV Ratio_I2/I1_NOC in the
measured neutral current. The setting is applicable to both the definite stages
of neutral earth fault protection element as well as the inverse time-current
stage. As soon as the measured ratio exceeds the set threshold, a restraint is
applied to those stages for which corresponding setting is applied to make
them blocked in inrush condition detection (HV Neu OC1 Inrush Block, HV
Neu OC2 Inrush Block and HV Neu OC Inv Inrush Block for HV side, MV
Neu OC1 Inrush Block, MV Neu OC2 Inrush Block and MV Neu OC Inv
Inrush Block for MV side, LV Neu OC1 Inrush Block, LV Neu OC2 Inrush
Block and LV Neu OC Inv Inrush Block for LV side).
Furthermore, if the fundamental component of the measured neutral current
exceeds the upper limit value HV Imax_2H_UnBlk_NOC, MV
Imax_2H_UnBlk_NOC or LV Imax_2H_UnBlk_NOC, the inrush restraint
will no longer effective in respective side, since a high-current fault is assumed in this case.

1.3

Direction Determination Feature


The integrated directional function can be applied to each stage of neutral
earth fault elements via Binary settings. The Binary settings include HV Neu
OC1 Direction, HV Neu OC2 Direction and HV Neu OC Inv Direction on
for HV side earth fault stages, MV Neu OC1 Direction, MV Neu OC2 Direction and MV Neu OC Inv Direction for MV side earth fault stages and LV

122

Chapter 8 Neutral earth fault protection


Neu OC1 Direction, LV Neu OC2 Direction and LV Neu OC Inv Direction
for LV side earth fault stages.
Furthermore, the directional orientation can be set individually for each stage
of neutral earth fault elements in various sides of the protected transformer.
This can be performed by Binary settings HV Neu OC1 Dir To Sys, HV Neu
OC2 Dir To Sys and HV Neu OC Inv Dir To Sys for HV side, MV Neu OC1
Dir To Sys, MV Neu OC2 Dir To Sys and MV Neu OC Inv Dir To Sys for
MV side, LV Neu OC1 Dir To Sys, LV Neu OC2 Dir To Sys and LV Neu OC
Inv Dir To Sys for LV side. The possible settings for these Binary setting
comprise 0-toward transformer and 1-toward system.
Basically, the direction determination is performed by comparing the zero
sequence system quantities. In the current path, 3I0 current is measured from
the neutral CT installed at the transformer starpoint. In the voltage path, the
device calculates the zero sequence voltage 3V0 from the sum of the three
phase voltages. Contrary to the directional phase elements, which work with
the un-faulted voltage as reference voltage, in this application, the fault voltage itself is the reference voltage. Depending on the connection of the voltage transformer, this is the voltage 3V0 or VN. The directional element at
each side operates with the residual/ neutral voltage of the same side.
In order to satisfy different network conditions and applications, the reference
voltage can be rotated by an adjustable angle. For each side of the protected
transformer, the directional angle can be set independently. The settings include HV Angle_NOC, MV Angle_NOC and LV Angle_NOC, for HV, MV
and LV sides, respectively. It should be noted that the settings affect all the
directional stages of the corresponding neutral earth fault element.

3I 0

90

0
3U 0_Ref
Angle_EF
Angle_Range
EF

Forward

-3 I 0

Bisector

Figure 44 Neutral directional element characteristic


where:
Angle_OC: The settable characteristic angle
Angle_Range OC: 80

123

Chapter 8 Neutral earth fault protection


During direction decision by directional function, a VT Fail condition (a short
circuit or broken wire in the voltage transformer's secondary system or an
operation of the voltage transformer fuse) may result in false or undesired
tripping by directional neutral earth fault elements. In such a situation, it is
possible to select operation status of the directional neutral earth fault protection elements in each side by using a number of Binary settings to block
the neutral earth fault protection elements or keep them in operational state
with no direction decision (block direction decision). The Binary settings are
designated as Block HV NOC at HV VT_Fail, Block MV NOC at HV
VT_Fail and Block LV NOC at HV VT_Fail, for HV, MV and LV sides, respectively. When the Binary settings are set as 0 to select Direct OK at VT
Fail, corresponding neutral earth fault protection elements will not judge direction at the local side VT failure. When they set as 1 to select Blk NEU OC
at VT Fail, no operation is possible by the neutral earth fault protection elements. It is noted that the Binary settings affect all the stages of corresponding neutral earth fault elements at each side. For instance, by applying setting
Block HV NOC at HV VT_Fail off, all the three stages of the neutral earth
fault element will remain operative without direction determination in case of
any fault in secondary circuit of HV side voltage transformer. On the other
hand, setting Block HV NOC at HV VT_Fail on makes them blocked.
The logic for definite and inverse time IDMTL neutral earth fault protection is
shown in below figure.
Func_Neu OC1 2 on

Dir_Forward

And
Or

NEF Direction Unit OK

VT failure
Direct OK at VT FAIL

And

Func_Neu OC1 2 on

3I0 > 3I0_Neutral OC1 2


1)
NEF Direction Unit OK

And

Neutral EF Trip

Inrush BLK NEF

Func_Neu OC Inv on

3I0>3I0_NOC Inv
NEF Direction Unit OK

And

NEF Inv Trip

Inrush BLK NOC


1) t: T_Neutral OC1(2)

Figure 45 Tripping logic for neutral earth fault protection

1.4
124

CBF initiation Feature

Chapter 8 Neutral earth fault protection


It is possible to set whether the neutral earth fault protection elements can initiate the integrated CBF protection or not. The available choices depend on
the voltage side of the power transformer at which neutral earth fault protection is applied. In this context, HV side neutral earth fault protection element
always initiates HV side CBF function with no additional setting. However, it is
possible to select whether it can initiate MV and LV CBF protection functions
via Binary settings HV Neu OC Init LV CBF and HV Neu OC Init MV CBF,
respectively.
MV side neutral earth fault protection element always initiates MV side CBF
function with no additional setting.

Input and output signals


Neutral Earth
Fault Protection
INBK

NEF1 Trip

UA

NEF2 Trip

UB

NEF Inv Trip

UC

Relay Startup

Figure 46 Neutral earth fault protection module


Table 60 Analog output list
Signal

Description

INBK
UA
UB
UC

Neutral current input of HV side, MV side, or LV side of transformer


Phase A voltage input of HV side, MV side, or LV side of transformer
Phase B voltage input of HV side, MV side, or LV side of transformer
Phase C voltage input of HV side, MV side, or LV side of transformer

Table 61 Binary output list


Signal

Description

NOC1 Trip
NOC2 Trip
NOC Inv Trip
Relay Startup

Neutral Earth Fault stage 1 trip


Neutral Earth Fault stage 2 trip
Neutral Earth Fault inverse stage trip
Relay Startup

125

Chapter 8 Neutral earth fault protection

Setting
Table 62 Settings of neutral earth fault protection for HV side of transformer

Setting

c
HV
T_Neutral
OC1
HV
3I0_Neutral
OC2
HV
T_Neutral
OC2
HV
Curve_NOC
Inv
HV 3I0_NOC
Inv

Unit

Min.
(Ir:5A/1
A)

Max.
(Ir:5A/1
A)

Default
setting
(Ir:5A/1
A)

0.05Ir

20Ir

HV neutral over-current (NOC)


protection current setting for Stage
1

60

60

Time setting for HV NOC, Stage


1

0.05Ir

20Ir

HV neutral over-current (NOC)


protection current setting for Stage
2

60

60

Time setting for HV NOC, Stage


1

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

HV K_NOC
Inv

Description

HV A_NOC
Inv

200

0.14

Ref to IEC and ANSI Curves

HV B_NOC
Inv

60

Ref to IEC and ANSI Curves

10

0.02

Ref to IEC and ANSI Curves

90

45

The angle setting for voltage


ahead of current.
The maximum 1 -harmonic
current setting to remove the
inrush block, in HV NOC protection

HV P_NOC
Inv
HV Angle_NOC

st

HV
Imax_2H_Un
Blk_NOC

0.25Ir

20Ir

0.07

0.5

0.2

HV Ratio_I2/I1_NO
C

nd

Inrush 2 harmonic ratio setting


for blocking HV NOC protection

Table 63 Binary settings of neutral earth fault protection for HV side of transformer

Setting

126

Unit

Min.

Max.

Default
setting

Description

Chapter 8 Neutral earth fault protection

HV Func_Neu
OC1

HV Neu OC1 Direction

HV Neu OC1 Dir


To Sys

HV Neu OC1 Inrush Block

HV Func_Neu
OC2

HV Neu OC2 Direction

HV Neu OC2 Dir


To Sys

HV Neu OC2 Inrush Block

HV Func_Neu OC
Inv

HV Neu OC Inv
Direction

HV Neu OC Inv Dir


To Sys

The 1st stage of HV neutral OC


(OC_1) protection is switched
ON
1-on; 0-off.
Direction (DIR) detection of HV
neutral OC Stage 1 is switched
ON
1-on; 0-off.
Direction unit of HV neutral OC
Stage 1 points to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
HV neutral OC Stage 1 is
switched ON
1-on; 0-off.
The 2nd stage of HV neutral OC
(OC_2) protection is switched
ON
1-on; 0-off.
Direction (DIR) detection of HV
neutral OC Stage 2 is switched
ON
1-on; 0-off.
Direction unit of HV neutral OC
Stage 2 points to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
HV neutral OC Stage 2 is
switched ON
1-on; 0-off.
The IDMTL inverse time stage
of HV neutral OC protection is
switched ON
1-on; 0-off.
Direction (DIR) detection of HV
neutral OC IDMTL inverse time
stage is switched ON
1-on; 0-off.
Direction unit of HV neutral OC
IDMTL inverse time stage points
to system
0 - point to the protected transformer
1- point to system

127

Chapter 8 Neutral earth fault protection

HV Neu OC Inv
Inrush Block

Block HV NOC at
HV VT_Fail

HV Neu OC Init
MV CBF

Inrush 2nd harmonic detection


HV neutral OC IDMTL inverse
time stage is switched ON
1-on; 0-off.
Select to block HV neutral OC
protection or exit direction unit,
when HV VT fails
0 - HV Direct OK at HV VT Fail
1 - Blk HV NOC at HV VT Fail

HV neutral OC protection initiate LV side CBF


0 - initiate, 1 not initiate

Table 64 Settings of neutral earth fault protection for MV side of transformer

Setting
MV
3I0_Neutral
OC1
MV
T_Neutral
OC1
MV
3I0_Neutral
OC2
MV
T_Neutral
OC2
MV
Curve_NOC
Inv
MV
3I0_NOC Inv

Unit

Min.
(Ir:5A/1
A)

Max.
(Ir:5A/1
A)

Default
setting
(Ir:5A/1
A)

0.05Ir

20Ir

MV neutral over-current (NOC)


protection current setting for
Stage 1

60

60

Time setting for MV NOC, Stage


1

0.05Ir

20Ir

MV neutral over-current (NOC)


protection current setting for
Stage 2

60

60

Time setting for MV NOC, Stage


1

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

MV K_NOC
Inv

Description

MV A_NOC
Inv

200

0.14

Ref to IEC and ANSI Curves

MV B_NOC
Inv

60

Ref to IEC and ANSI Curves

10

0.02

Ref to IEC and ANSI Curves

90

45

The angle setting for voltage


ahead of current.

The maximum 1 -harmonic


current setting to remove the
inrush block, in MV NOC protection

MV P_NOC
Inv
MV Angle_NOC

st

MV
Imax_2H_Un
Blk_NOC

128

0.25Ir

20Ir

Chapter 8 Neutral earth fault protection


MV Ratio_I2/I1_NO
C

nd

0.07

0.5

0.2

Inrush 2 harmonic ratio setting


for blocking MV NOC protection

Table 65 Binary settings of neutral earth fault protection for MV side of transformer

Setting

Unit

Min.

Max.

Default
setting

MV Func_Neu
OC1

MV Neu OC1 Direction

MV Neu OC1 Dir


To Sys

MV Neu OC1 Inrush Block

MV Func_Neu
OC2

MV Neu OC2 Direction

MV Neu OC2 Dir


To Sys

MV Neu OC2 Inrush Block

MV Func_Neu OC
Inv

MV Neu OC Inv
Direction

Description

The 1st stage of MV neutral OC


(OC_1) protection is switched
ON
1-on; 0-off.
Direction (DIR) detection of MV
neutral OC Stage 1 is switched
ON
1-on; 0-off.
Direction unit of MV neutral OC
Stage 1 points to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
MV neutral OC Stage 1 is
switched ON
1-on; 0-off.
The 2nd stage of MV neutral OC
(OC_2) protection is switched
ON
1-on; 0-off.
Direction (DIR) detection of MV
neutral OC Stage 2 is switched
ON
1-on; 0-off.
Direction unit of MV neutral OC
Stage 2 points to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
MV neutral OC Stage 2 is
switched ON
1-on; 0-off.
The IDMTL inverse time stage
of MV neutral OC protection is
switched ON
1-on; 0-off.
Direction (DIR) detection of MV
neutral OC IDMTL inverse time
129

Chapter 8 Neutral earth fault protection

MV Neu OC Inv
Dir To Sys

MV Neu OC Inv
Inrush Block

Block MV NOC at
MV VT_Fail

MV Neu OC Init
MV CBF

stage is switched ON
1-on; 0-off.
Direction unit of MV neutral OC
IDMTL inverse time stage points
to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
MV neutral OC IDMTL inverse
time stage is switched ON
1-on; 0-off.
Select to block MV neutral OC
protection or exit direction unit,
when MV VT fails
0 - MV Direct OK at MV VT Fail
1 - Blk MV NOC at MV VT Fail

MV neutral OC protection initiate LV side CBF


0 - initiate, 1 not initiate

Table 66 Settings of neutral earth fault protection for LV side of transformer

Unit

Min.
(Ir:5A/1
A)

Max.
(Ir:5A/1
A)

Default
setting
(Ir:5A/1
A)

LV
3I0_Neutral
OC1

0.05Ir

20Ir

LV neutral over-current (NOC)


protection current setting for
Stage 1

LV T_Neutral
OC1

60

60

Time setting for LV NOC, Stage 1

Setting

Description

LV
3I0_Neutral
OC2

0.05Ir

20Ir

LV neutral over-current (NOC)


protection current setting for
Stage 2

LV T_Neutral
OC2

60

60

Time setting for LV NOC, Stage 1

12

Ref to IEC and ANSI Curves

0.05Ir

20Ir

Ref to IEC and ANSI Curves

0.05

999

Ref to IEC and ANSI Curves

LV
Curve_NOC
Inv
LV 3I0_NOC
Inv

LV K_NOC
Inv
LV A_NOC
Inv

200

0.14

Ref to IEC and ANSI Curves

LV B_NOC
Inv

60

Ref to IEC and ANSI Curves

130

Chapter 8 Neutral earth fault protection

LV P_NOC
Inv
LV Angle_NOC

10

0.02

Ref to IEC and ANSI Curves

90

45

The angle setting for voltage


ahead of current.
st

LV
Imax_2H_Un
Blk_NOC

0.25Ir

20Ir

The maximum 1 -harmonic


current setting to remove the
inrush block, in LV NOC protection

0.07

0.5

0.2

Inrush 2 harmonic ratio setting


for blocking LV NOC protection

LV Ratio_I2/I1_NO
C

nd

Table 67 Binary settings of neutral earth fault protection for LV side of transformer

Setting

Unit

Min.

Max.

Default
setting

LV Func_Neu OC1

LV Neu OC1 Direction

LV Neu OC1 Dir


To Sys

LV Neu OC1 Inrush Block

LV Func_Neu OC2

LV Neu OC2 Direction

LV Neu OC2 Dir


To Sys

LV Neu OC2 Inrush Block

Description

The 1st stage of LV neutral OC


(OC_1) protection is switched
ON
1-on; 0-off.
Direction (DIR) detection of LV
neutral OC Stage 1 is switched
ON
1-on; 0-off.
Direction unit of LV neutral OC
Stage 1 points to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
LV neutral OC Stage 1 is
switched ON
1-on; 0-off.
The 2nd stage of LV neutral OC
(OC_2) protection is switched
ON
1-on; 0-off.
Direction (DIR) detection of LV
neutral OC Stage 2 is switched
ON
1-on; 0-off.
Direction unit of LV neutral OC
Stage 2 points to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
LV neutral OC Stage 2 is
131

Chapter 8 Neutral earth fault protection

LV Func_Neu OC
Inv

LV Neu OC Inv
Direction

LV Neu OC Inv Dir


To Sys

LV Neu OC Inv
Inrush Block

Block LV NOC at
LV VT_Fail

LV Neu OC Init LV
CBF

switched ON
1-on; 0-off.
The IDMTL inverse time stage
of LV neutral OC protection is
switched ON
1-on; 0-off.
Direction (DIR) detection of LV
neutral OC IDMTL inverse time
stage is switched ON
1-on; 0-off.
Direction unit of LV neutral OC
IDMTL inverse time stage points
to system
0 - point to the protected transformer
1- point to system
Inrush 2nd harmonic detection
LV neutral OC IDMTL inverse
time stage is switched ON
1-on; 0-off.
Select to block LV neutral OC
protection or exit direction unit,
when LV VT fails
0 - LV Direct OK at LV VT Fail
1 - Blk LV NOC at LV VT Fail

LV neutral OC protection initiate


LV side CBF
0 - initiate, 1 not initiate

Report
Table 68 Event report list
Information

Description

HV NOC Inv Trip

Inverse time stage of neutral OC protection trip

HV NOC1 Trip

HV neutral OC stage 1 trip

HV NOC2 Trip

HV neutral OC stage 2 trip

MV EF Inv Trip

Inverse time stage of MV neutral OC protection trip

MV EF1 Trip

MV neutral OC stage 1 trip

MV EF2 Trip

MV neutral OC stage 2 trip

LV EF Inv Trip

Inverse time stage of LV neutral OC protection trip

LV EF1 Trip

LV neutral OC stage 1 trip

LV EF2 Trip

LV neutral OC stage 2 trip

132

Chapter 8 Neutral earth fault protection


Table 69 Operation report list
Information

Description

HV Func_NOC On

NOC protection of HV side is switched ON (by CW)

HV Func_NOC Off

NOC protection of HV side is switched OFF (by CW)

MV Func_NOC On

NOC protection of MV side is switched ON (by CW)

MV Func_NOC Off

NOC protection of MV side is switched OFF (by CW)

LV Func_NOC On

NOC protection of LV side is switched ON (by CW)

LV Func_NOC Off

NOC protection of LV side is switched OFF (by CW)

Technical data
Table 70 Neutral earth fault protection technical data
Item

Rang or value

Tolerance

Definite time characteristic


Current

0.08 Ir to 20.00 Ir

Time delay

0.00 to 60.00s, step 0.01s

Reset time

approx. 40ms

Reset ratio

Approx. 0.95 at I/Ir 0.5


Inverse time characteristics

Current
IEC standard

0.08 Ir to 20.00 Ir

ANSI

user-defined characteristic

Time factor of inverse time, A

Normal inverse;
Very inverse;
Extremely inverse;
Long inverse
Inverse;
Short inverse;
Long inverse;
Moderately inverse;
Very inverse;
Extremely inverse;
Definite inverse

3% setting or 0.02Ir
1% setting or +40ms, at 200%
operating setting

3% setting or 0.02Ir
5% setting + 40ms, at 2
<I/ISETTING < 20, in accordance with
IEC60255-151
5% setting + 40ms, at 2
<I/ISETTING < 20, in accordance
with ANSI/IEEE C37.112,

5% setting + 40ms, at 2
<I/ISETTING < 20, in accordance with
IEC60255-151

T=

Delay of inverse time, B

0.005 to 200.0s, step


0.001s
0.000 to 60.00s, step 0.01s

Index of inverse time, P

0.005 to 10.00, step 0.005

set time Multiplier for step n: k

0.05 to 999.0, step 0.01

Minimum operating time

20ms

Maximum operating time

100s

Reset mode

instantaneous

Reset time

approx. 40ms
Directional element

Operating area range

160

3, at 3U01V

133

Chapter 8 Neutral earth fault protection


Characteristic angle

0to 90, step 1

Operating area range

160

Characteristic angle

0to 90, step 1

134

3, at 3U22V

Chapter 9 Thermal overload protection

Chapter 9 Thermal overload


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for thermal
overload protection function.

135

Chapter 9 Thermal overload protection

Introduction
The insulating material surrounding the transformer windings ages rapidly if
the temperature exceeds the design limit value. Furthermore, by using less
and less metal per MVA of transformed power, the designed limit value is
reduced in modern power transformers. Hence, it represents an essential
requirement to provide thermal protection to supplement the winding temperature device. The thermal overload protection estimates winding temperature
and therefore prevents damage to transformer caused by thermal overloading.

Protection principle
The thermal overload protection includes two stages (alarm and trip). They
work by using an approximate replica of the temperature rise in the protected
object caused by overload. The thermal replica is implemented based on
thermal models (Cold / Hot Curve) of IEC60255-8 Std., without ambient
temperature influence.
Both of the alarm and trip stages can be enabled or disabled by using Binary
setting HV Func_Thermal OvLd, MV Func_Thermal OvLd or LV
Func_Thermal OvLd on. The thermal overload protection can be assigned to
any desired side (HV, MV or LV) of the protected object. However, for transformers with tap changer, it is recommended to use the function on the
non-regulated side. To enable the protection on each side, setting of 1-on
should be applied to corresponding Binary setting.
Both of the thermal overload stages can use cold curve or hot curve in their
calculations, based on the setting applied at Binary setting HV Cold Curve,
MV Cold Curve or LV Cold Curve. If the protection is enabled in one side,
and the measured current in each phase of the protected transformer in corresponding side exceeds the threshold defined by setting HV I_Therm OL
Alarm, MV I_Therm OL Alarm or LV I_Therm OL Alarm, a counter is incremented from 0% to 100%. When the counter is accumulated to its alarm
setting which correspond to the expiration of alarm time delay according to
the selected cold/hot characteristic, the alarm report HV Load Alarm, MV
Load Alarm or LV Load Alarm is given to allow a preventive load reduction.
The alarm signal is cancelled as soon as the measured phase current falls
below the threshold defined by setting HV I_Therm OL Alarm, MV I_Therm
OL Alarm or LV I_Therm OL Alarm. However, the counter is decremented to
zero according to cool down time of the transformer (the time by which the
thermal replica counter reaches from 100% to 0%). The cool down time is
informed to the device by setting HV T_Const Cool Down, MV T_Const
Cool Down and LV T_Const Cool Down.
Similarly, if the measured current in each phase of the protected transformer
in corresponding side exceeds the threshold defined by setting HV I_Therm
OL Trip, MV I_Therm OL Trip or LV I_Therm OL Trip, a counter is incremented from 0% to 100%. If the counter reaches to 100% corresponding to
expiration of trip time delay according to the selected cold/hot characteristic,
the event report HV THERM Trip, MV THERM Trip or LV THERM Trip is

136

Chapter 9 Thermal overload protection


given. The alarm signal is cancelled as soon as the measured phase current
falls below the threshold defined by setting HV I_Therm OL Trip, MV
I_Therm OL Trip or LV I_Therm OL Trip. However, the counter is decremented to zero according to cool down time of the transformer which is entered into the device by setting HV T_Const Cool Down, MV T_Const Cool
Down and LV T_Const Cool Down.
The cold and hot curves used in each thermal overload stages, is based on
thermal curves defined in IEC 60255-8 Std.
The curves provide an operating current/time characteristic that corresponds
to the current overload characteristic of the transformer windings. The formulas corresponding to cold and hot curve is denoted by (1-46) and (1-47),
respectively. The cold curve provides no memory regarding to previous
thermal condition of the transformer, whereas, by using the hot curve, the
protection function is able to represent a memorized thermal profile of the
protected transformer.
2
I ph

t ln 2
2
I ph I

Equation 37
2
I ph
I P2
t ln 2
2
I ph I

Equation 38
Where,
t is alarm/trip time of thermal overload protection function in seconds,
is thermal time constant of heating for the power transformer, in seconds. It
is usually provided by the manufacturer. The device is informed about it by
settings HV T_Const Therm, MV T_Const Therm and H\LV T_Const
Therm.
Iph is the current flowing through corresponding side of the transformer, in
each phase. It means that the calculation is performed separately for each
phase, based on fundamental component measurement and also includes
the effect of harmonic contents up to 7th harmonic. Thus, the minimum calculated alarm/ trip time is decisive for evaluation of the thresholds.
I is the setting for alarm and trip stages of the thermal overload protection, in
rms. It should be set considering the maximum permissible thermal continuous overload current of the transformer windings and insulations. The setting
is applied by using HV I_Therm OL Alarm and HV I_Therm OL Trip for HV
side, MV I_Therm OL Alarm and HV I_Therm OL Trip for MV side, and
H\LV I_Therm OL Alarm and HV I_Therm OL Trip for LV side of the power
transformer.
IP is the prior current to overload, assuming sufficient time to reach
137

Chapter 9 Thermal overload protection


steady-state temperature.
NOTE: When Binary setting xx Curve/Hot Curve is set to 0, and fundamental
current is less than the settings, and the heat accumulation is cleared and set
as 0 automatically.

Input and output signals


Thermal Overload
Protection
IA1

Therm OL Trip

IB1

Therm OL Alarm

IC1

Relay Startup

IA2
IB2
IC2

Figure 47 Thermal overload protection module


Table 71 Analog input list
Signal

Description

IA1
IB1
IC1
IA2
IB2
IC2

Phase A current input of CT of circuit breaker 1


Phase B current input of CT of circuit breaker 1
Phase C current input of CT of circuit breaker 1
Phase A current input of CT of circuit breaker 2
Phase B current input of CT of circuit breaker 2
Phase C current input of CT of circuit breaker 2

Table 72 Binary output list


Signal

Description

Therm OL Trip
Therm OL Alarm
Relay Startup

Thermal overload trip


Thermal overload alarm
Relay Startup

Setting
Table 73 Settings of thermal overload protection for HV side of transformer
Setting

138

Unit

Min.
(Ir:5A/

Max.
(Ir:5A/

Default
setting

Description

Chapter 9 Thermal overload protection

HV I_Therm OL Trip

1A)

1A)

(Ir:5A/
1A)

0.1Ir

5Ir

Setting for HV-side thermal


overload trip-stage current
Setting for HV-side thermal
overload alarm-stage current

HV I_Therm OL Alarm

0.1Ir

5Ir

HV T_Const Therm

9999

10

Time const for HV-side


thermal overload protection

HV T_Const Cool
Down

9999

10

Cool down time delay for


HV-side thermal overload

Table 74 Binary settings of thermal overload protection for HV side of transformer

Min.

Max.

Default
setting

HV Func_Thermal
OvLd

HV Cold Curve

HV Thermal Init LV
CBF

HV Thermal Init MV
CBF

Setting

Unit

Description

Thermal overload in HV
side is switched on
0 - OFF, 1 - ON
HV side using hot/cold
curve type
0 Hot curve, 1 Cold
curve
HV thermal overload protection initiate LV side CBF
0 - initiate, 1 not initiate
HV thermal overload protection initiate MV side
CBF
0 - initiate, 1 not initiate

Table 75 Settings of thermal overload protection for MV side of transformer

Unit

Min.
(Ir:5A/
1A)

Max.
(Ir:5A/
1A)

Default
setting
(Ir:5A/
1A)

MV I_Therm OL Trip

0.1Ir

5Ir

MV I_Therm OL
Alarm

0.1Ir

5Ir

MV T_Const Therm

9999

10

MV T_Const Cool
Down

9999

10

Setting

Description
Setting for MV-side thermal
overload trip-stage current
Setting for MV-side thermal
overload alarm-stage current
Time const for MV-side
thermal overload protection
Cool down time delay for
MV-side thermal overload

139

Chapter 9 Thermal overload protection


Table 76 Binary settings of thermal overload protection for MV side of transformer

Min.

Max.

Default
setting

MV Func_Thermal
OvLd

MV Cold Curve

MV Thermal Init HV1


CBF

Setting

Unit

Description

Thermal overload in MV
side is switched on
0 - OFF, 1 - ON
MV side using hot/cold
curve type
0 Hot curve, 1 Cold
curve
MV thermal overload protection initiate HV side
CBF
0 - initiate, 1 not initiate

Report
Table 77 Event report list
Information

Description

HV Therm OL Trip

HV Thermal (TEM) Overload(OVLD) tripping (Trip)

MV Therm OL Trip

MV Thermal (TEM) Overload(OVLD) tripping (Trip)

Table 78 Alarm report list


Information

Description

HV Therm OL Alm

HV Thermal overload Alarm

MV Therm OL Alm

MV Thermal overload Alarm

Table 79 Operation report list


Information

Description

HV Func_Therm On

HV thermal overload protection is switched ON (by CW)

HV Func_Therm Off

HV thermal overload protection is switched OFF (by CW)

MV Func_Therm On

MV thermal overload protection is switched ON (by CW)

MV Func_Therm Off

MV thermal overload protection is switched OFF (by CW)

140

Chapter 9 Thermal overload protection

Technical data
Table 80 Thermal overload protection technical data
Item

Rang or Value

Current

0.1 Ir to 5.00 Ir

Thermal heating time constant

1 to 9999 s

Thermal cooling time constant

1 to 9999 s

Tolerance
3% setting or 0.02Ir

IEC cold curve

I eq2
t ln 2
2
I eq I

IEC 602558,
5% setting or +40ms

IEC hot curve

2
I eq
I P2
t ln 2
2
I eq I

IEC 602558,
5% setting or +40ms

141

Chapter 9 Thermal overload protection

142

Chapter 10 Overload protection

Chapter 10 Overload protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for overload
protection function.

143

Chapter 10 Overload protection

Protection principle
Overload protection is equipped for each voltage side and LV delta winding.
The function is to protect all sides of windings of transformer continuous
overload currents.
HV or MV or LV overload protection only comprises a definite time alarm
stage.
HV Func_OverLoad on

Max(IA,IB,IC)>HV
I_OverLoad

HV T_OverLoad

A
N
D

Load Alarm

Figure 48 The logic for HV overload protection


The LV winding overload includes one alarm and two definite time tripping
stages, namely low-setting tripping stage and high-setting tripping stage. The
two tripping stage can be set respective to initiate each side CBF or not
The logic for overload protection is shown in below figure.
LW Func_OvLd Alarm on

Max(IA,IB,IC)> I_OverLoad

&

T_OverLo
ad

&

LW T_OvLd
Low Trip

&

LW T_OvLd High
Trip

LW Load Alarm

LW Func_OvLd Low Trip on

Max(IA,IB,IC)> LW I_OvLd
Low Trip

LW Load Low_Stg

LW Func_OvLd High Trip on

Max(IA,IB,IC)>LW I_OvLd
High Trip

LW Load High_Stg

Figure 49 The logic for LV winding overload protection

144

Chapter 10 Overload protection

Input and output signals


Overload Protection
IA1

Overload Alarm

IB1

Relay Startup

IC1
IA2
IB2
IC2

Figure 50 Overload protection module for HV, MV, or LV side of


transformer
Delta Winding
Overload Protection
IA

Overload high set trip

IB

Overload low set trip

IC

Overload Alarm
Relay Startup

Figure 51 Overload protection module for LV delta winding of


transformer
Table 81 Analog input list
Signal

Description

IA1
IB1
IC1
IA2
IB2
IC2

Phase A current input of CT of circuit breaker 1


Phase B current input of CT of circuit breaker 1
Phase C current input of CT of circuit breaker 1
Phase A current input of CT of circuit breaker 2
Phase B current input of CT of circuit breaker 2
Phase C current input of CT of circuit breaker 2

Table 82 Binary output list


Signal

Description

Overload Alarm

Overload Alarm

Relay Startup

Relay Startup

145

Chapter 10 Overload protection

Setting
Table 83 Setting of overload protection for HV side of transformer

Unit

Min.
(Ir:5A/
1A)

Max.
(Ir:5A/
1A)

Default
setting
(Ir:5A/
1A)

HV I_OverLoad

0.1Ir

4Ir

HV T_OverLoad

0.1

3600

10

Setting

Description

Overcurrent Setting of overload


Time setting for overload

Table 84 Binary settings of overload protection for HV side of transformer

Setting

Unit

Min.

Max.

Default
setting

HV Func_OverLoad

Description
Overload (LOAD) protection in
HV side is switched ON
1-on; 0-off.

Table 85 Setting of overload protection for MV side of transformer

Unit

Min.
(Ir:5A/
1A)

Max.
(Ir:5A/
1A)

Default
setting
(Ir:5A/
1A)

MV I_OverLoad

0.1Ir

4Ir

MV T_OverLoad

0.1

3600

10

Setting

Description

Overcurrent Setting of overload


Time setting for overload

Table 86 Binary settings of overload protection for MV side of transformer

Setting

Unit

Min.

Max.

Default
setting

MV Func_OverLoad

Description
Overload (LOAD)in MV side
on

Table 87 Setting of overload protection for LV side of transformer

Setting

LV I_OverLoad

146

Unit

Min.
(Ir:5A/
1A)

Max.
(Ir:5A/
1A)

Default
setting
(Ir:5A/
1A)

0.1Ir

4Ir

Description

Overcurrent Setting of overload

Chapter 10 Overload protection


LV T_OverLoad

0.1

Time setting for overload

10

3600

Table 88 Binary settings of overload protection for LV side of transformer

Setting

Unit

LV Func_OverLoad

Min.

Max.

Default
setting

Description

Overload (LOAD)in LV side on

Table 89 Setting of overload protection for LV delta winding of transformer

Setting

Unit

Min.
(Ir:5A/
1A)

Max.
(Ir:5A/
1A)

Default
setting
(Ir:5A/
1A)

Description

LW I_OvLd Alarm

0.1Ir

4Ir

20

Alarm current setting of LV delta


winding overload protection

LW T_OvLd Alarm

0.1

3600

10

Alarm time setting of LV delta


winding overload protection

0.1Ir

4Ir

20

Low stage tripping current setting

0.1

3600

10

Low stage tripping time setting

0.1Ir

4Ir

20

High stage tripping current setting

0.1

3600

10

High stage tripping time setting

LW I_OvLd Low
Trip
LW T_OvLd Low
Trip
LW I_OvLd High
Trip
LW T_OvLd High
Trip

Table 90 Binary settings of overload protection for LV delta winding of transformer

Setting

Unit

Min.

Max.

Default
setting

LW Func_OvLd
Alarm

LW Func_OvLd Low
Trip

LW Func_OvLd High
Trip

Low Trip Init HV1 CBF

Description
Alarm stage of LV delta winding (LWIND) overload (LOAD)
protection is switched ON.
1-on; 0-off.
Low-setting trip stage of LV
delta winding overload protection is switched ON.
1-on; 0-off.
High-setting trip stage of LV
delta winding overload protection is switched ON.
1-on; 0-off.
Low-setting trip stage of LV
delta winding overload protection initiate HV1 side CBF
0 - initiate, 1 not initiate

147

Chapter 10 Overload protection

High Trip Init HV1 CBF

Low Trip Init MV CBF

High Trip Init MV CBF

High-setting trip stage of LV


delta winding overload protection initiate HV1 side CBF
0 - initiate, 1 not initiate
Low-setting trip stage of LV
delta winding overload protection initiate MV side CBF
0 - initiate, 1 not initiate
High-setting trip stage of LV
delta winding overload protection initiate MV side CBF
- initiate, 1 not initiate

Report
Table 91 Event report list
Information

Description

LW Load Low_Stg

LV delta winding (LWIND) overload (LOAD) protection low setting


trip
LV delta winding (LWIND) overload (LOAD) protection high setting
trip

LW Load High_Stg

Table 92 Alarm report list


Information

Description

HV Load Alarm

HV overload Alarm

MV Load Alarm

MV overload Alarm

LV Load Alarm

LV overload Alarm

Table 93 Operation report list


Information

Description

HV Func_OL On

HV overload protection is switched ON (by CW)

HV Func_OL Off

HV overload protection is switched OFF (by CW)

MV Func_OL On

MV overload protection is switched ON (by CW)

MV Func_OL Off

MV overload protection is switched OFF (by CW)

LV Func_OL On

LV overload protection is switched ON (by CW)

LV Func_OL Off

LV overload protection is switched OFF (by CW)

148

Chapter 11 Overvoltage protection

Chapter 11 Overvoltage protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data used for overvoltage protection.

149

Chapter 11 Overvoltage protection

Introduction
Voltage protection has the function to protect electrical equipment against
overvoltage condition. Abnormally high voltages often occur e.g. in low
loaded, long distance transmission lines, in islanded systems when generator
voltage regulation fails, or after full load shutdown of a generator from the
system. Even if compensation reactors are used to avoid line overvoltage by
compensation of the line capacitance and thus reduction of the overvoltage,
the overvoltage will endanger the insulation if the reactors fail (e.g. fault
clearance). The line must be disconnected within very short time.
The protection provides the following features:

Two definite time stages

Each stage can be set to alarm or trip

Measuring voltage between phase-earth voltage and phase-phase (selectable)

Settable dropout ratio

Protection principle

6.1

Phase to phase overvoltage protection


All the three phase voltages are measured continuously, and compared with
the corresponding setting value. If a phase voltage exceeds the set thresholds, HV U_OV1 or HV U_OV2 for HV said, MV U_OV1 or MV U_OV2
for MV said, after expiry of the time delays, HV T_OV1 or HV T_OV2, and
MV T_OV1 or MV T_OV2, the protection IED will issue alarm signal or trip
command according to the users requirement.
There are two stages included in overvoltage protection, each stage can be
set to alarm or trip separately in binary setting, and the time delay for each
stage can be individually set. Thus, the alarming or tripping can be
time-coordinated based on how severe the voltage increase, e.g. in case of
high overvoltage, the trip command will be issued with a short time delay,
whereas for the less severe overvoltage, trip or alarm signal can be issued
with a longer time delay.

150

Chapter 11 Overvoltage protection


Additionaly, the dropout ratio of the overvoltage protection can be set in setting Dropout_OV. Therefore, the trip command of overvoltage is reset if the
measured voltage comes bellow the ratio value mentioned in this setting.

6.2

Phase to earth overvlotage protection


The phase to earth overvoltage protection operates just like the phase to
phase protection except that it detects phase to earth voltages.

Logic diagram
Ua>HV U_OV1
Ub>HV U_OV1

O
R

HV OV Chk PE on

Uc>HV U_OV1
HV OV1 Trip on

Trip
Uab>HV U_OV1
Ubc>HV U_OV1

O
R

HV OV Chk PE off

O
R

HV T_OV1
HV OV1 Trip off

Uca>HV U_OV1

Alarm

Figure 52 Logic diagram for overvoltage protection

Input and output signals


Overvoltage Protection
UA

OV1 Trip

UB

OV2 Trip

UC

OV1 Alarm
OV2 Alarm
Relay Startup

Figure 53 Oervoltage protection module


Table 94 Analog input list

Signal

Description

151

Chapter 11 Overvoltage protection

Signal

Description

UA

Phase A voltage input

UB

Phase B voltage input

UC

Phase C voltage input

Table 95 Binary output list

Signal

Description

OV1 Trip

OV stage 1trip

OV2 Trip

OV stage 2trip

OV1 Alarm

OV stage 1 alarm

OV2 Alarm

OV stage 2 alarm

Relay Startup

Relay Startup

Setting

Table 96 Function setting list for overvoltage protection for HV side of transformer

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1
A)

HV U_OV1

40

200

200

HV T_OV1

60

60

HV U_OV2

40

200

200

HV T_OV2

60

60

0.9

0.99

0.95

HV Dropout_OV

Description

HV voltage setting for stage 1


of overvoltage protection
HV time setting for stage 1 of
overvoltage protection
HV voltage setting for stage 2
of overvoltage protection
HV time setting for stage 2 of
overvoltage protection
HV dropout ratio for overvoltage protection

Table 97 Binary setting list for overvoltage protection for HV side of transformer

Setting
HV Func_OV1

152

Unit

Min.

Max.

Default
setting
0

Description
HV overvoltage stage 1 enabled

Chapter 11 Overvoltage protection


Setting

Unit

Min.

Max.

Default
setting

Description
or disabled

HV Func_OV2
HV Func_OV2
HV OV2 Trip

HV overvoltage stage 1 trip or


alarm
HV overvoltage stage 2 enabled
or disabled
HV overvoltage stage 2 trip or
alarm

HV OV Chk PE

HV phase to phase voltage or


0

phase to earth measured for


overvoltage protection

Table 98 Function setting list for overvoltage protection for MV side of transformer

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1
A)

MV U_OV1

40

200

200

MV T_OV1

60

60

MV U_OV2

40

200

200

MV T_OV2

60

60

0.9

0.99

0.95

MV Dropout_OV

Description

MV voltage setting for stage 1


of overvoltage protection
MV time setting for stage 1 of
overvoltage protection
MV voltage setting for stage 2
of overvoltage protection
MV time setting for stage 2 of
overvoltage protection
MV dropout ratio for overvoltage protection

Table 99 Binary setting list for overvoltage protection for MV side of transformer

Setting
MV Func_OV1
MV Func_OV2
MV Func_OV2
MV OV2 Trip
MV OV Chk PE

Unit

Default

Min.

Max.

setting

Description
MV overvoltage stage 1 enabled
or disabled
MV overvoltage stage 1 trip or
alarm
MV overvoltage stage 2 enabled
or disabled
MV overvoltage stage 2 trip or
alarm
MV phase to phase voltage or
phase to earth measured for
153

Chapter 11 Overvoltage protection


Setting

Unit

Min.

Max.

Default
setting

Description
overvoltage protection

10

Report
Table 100 Event report list

Information

Description

HV OV1 Trip

HV overvoltage stage 1 trip

HV OV2 Trip

HV overvoltage stage 2 trip

MV OV1 Trip

MV overvoltage stage 1 trip

MV OV2 Trip

MV overvoltage stage 2 trip

Table 101 Alarm report list

Information

Description

HV OV1 Alarm

HV overvoltage stage 1 alarm

HV OV2 Alarm

HV overvoltage stage 2 alarm

MV OV1 Alarm

MV overvoltage stage 1 alarm

MV OV2 Alarm

MV overvoltage stage 2 alarm

Table 102 Operation report list


Description of event

comment

HV Func_OV On

HV overvoltage protection is switched ON (by CW)

HV Func_OV Off

HV overvoltage protection is switched OFF (by CW)

MV Func_OV On

MV overvoltage protection is switched ON (by CW)

MV Func_OV Off

MV overvoltage protection is switched OFF (by CW)

11

Technical data
Table 103 Technical data for overvoltage protection
Item

Voltage connection

Rang or Value
Phase-to-phase voltages or
phase-to-earth voltages

154

Tolerance
3 % setting or 1 V

Chapter 11 Overvoltage protection


Phase to earth voltage

40 to 100 V, step 1 V

3 % setting or 1 V

Phase to phase voltage

80 to 200 V, step 1 V

3 % setting or 1 V

Reset ratio

0.90 to 0.99, step 0.01

3 % setting

Time delay

0.00 to 60.00 s, step 0.01s

1 % setting or +50 ms, at


120% energizing setting

Reset time

<40ms

155

Chapter 11 Overvoltage protection

156

Chapter 12 Circuit breaker failure protection

Chapter 12 Circuit breaker failure


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for circuit
breaker failure protection function.

157

Chapter 12 Circuit breaker failure protection

Introduction
The circuit breaker failure (CBF) protection function monitors proper tripping
of the relevant circuit breaker. There are two separate CBF protection integrated in the IED. They are dedicated to HV and MV sides of the protected
transformer.

Protection principle
Normally, the circuit breaker should be tripped and therefore interrupt the fault
current whenever a short circuit protection function issues a trip command.
The circuit breaker failure protection provides rapid back-up fault clearance,
in the event of circuit breaker malfunction to respond to a trip command. This
feature can be enabled or disabled at each side of the protected transformer
via Binary settings HV1 CBF ON, MV CBF ON. If setting 1-On is applied
at these Binary settings, respective CBF protection will be switched on. In this
case, by operation of a protection function, and subsequent CBF initiation by
respective protection function, a report nominated as HV1 CBF INIT or MV
CBF INIT is generated by the IED. Furthermore, CBF initiation causes a
programmed timer to run toward a preset time delay limit. This time delay is
set by user under the settings HV1 T1_CBF or MV1 T1_CBF. If the circuit
breaker has not been opened after expiration of the preset time limit, the circuit breaker failure protection issues a command to trip circuit breaker (e.g.
via a second trip coil). Furthermore, event report of HV1 CBF T1 or MV
CBF T1is generated by the device. If the circuit breaker doesnt respond to
the repeated trip command, until another preset delay time which is set at
HV1 T2_CBF or MV1 T2_CBF, the protection issues a trip command to
isolate the fault by tripping other surrounding backup circuit breakers (e.g. the
other CBs connected to the same bus section as the faulty CB). Furthermore,
event report of HV1 CBF T2 or MV CBF T2 is generated in this case.
Initiation of CBF protection can be carried out by both the internal and external protection functions. If it is desired to initiate the CBF protection by means
of external protection functions, they should be marshaled to Binary input (BI)
of HV1 CBF EXT. INT or MV CBF EXT. INT for HV or MV CBF protection
respectively. Internal protection functions can initiate the CBF protection integrated in IED (HV and/or MV CBF), according to the mapping shown in
below table.

158

Chapter 12 Circuit breaker failure protection


Table 104 Internal functions mapping to initiate CBF protection
CBF

PROTECTION FUNCTIONS

INITIATION

HV1

MV

Percent Differential Protection Trip [IDIFF>]

High-Set Differential Protection Trip [IDIFF>>]

HV Restricted Earth Fault Protection Trip

MV Restricted Earth Fault Protection Trip

LV Restricted Earth Fault Protection Trip

Overexcitation Protection INV Trip

Overexcitation Protection DEF Trip [U/f >>]

HV Thermal Overload Protection Trip

CW
[0/1]

CW
[0/1]

MV Thermal Overload Protection Trip

CW
[0/1]

LV Thermal Overload Protection Trip

CW
[0/1]

HV Overcurrent Protection Trip [INV / DEF (Stage-1,2)]

CW
[0/1]

CW
[0/1]

MV Overcurrent Protection Trip [INV / DEF


(Stage-1,2)]

CW
[0/1]

LV Overcurrent Protection Trip [INV / DEF (Stage-1,2)]

CW
[0/1]

HV Earth Fault Protection Trip [INV / DEF (Stage-1,2)]

CW
[0/1]

CW
[0/1]

MV Earth Fault Protection Trip [INV / DEF (Stage-1,2)]

CW
[0/1]

LV Earth Fault Protection Trip [INV / DEF (Stage-1,2)]

CW
[0/1]

HV Neutral Current Protection Trip [INV / DEF


(Stage-1,2)]

CW
[0/1]

CW
[0/1]

MV Neutral Current Protection Trip [INV / DEF


(Stage-1,2)]

CW
[0/1]

LV Neutral Current Protection Trip [INV / DEF


(Stage-1,2)]

CW
[0/1]

Overload Protection for LV Winding Low-Stage Trip


(Inside Delta)

CW
[0/1]

CW
[0/1]

159

Chapter 12 Circuit breaker failure protection


Over Load Protection for LV Winding
(Inside Delta)

High-Stage Trip

CW
[0/1]

CW
[0/1]

DI1 Trip

CW
[0/1]

CW
[0/1]

CW
[0/1]

DI2 Trip

CW
[0/1]

CW
[0/1]

CW
[0/1]

In above table,
:means that the protection function working at a given side of the protected
transformer always initiate the CBF protection applied in specified side of the
power transformer. As can be seen, differential, restricted earth fault and
overexcitation protection functions initiate CBF protection in each side of
protected transformer with no additional settings.
The statement CW [0/1] means that the protection function can initiate CBF
protection according to the setting which is applied at respective Binary setting. The setting includes 1: Initiate the CBF and 0: Dont initiate the CBF.
Related Binary settings are available for specific functions which include
thermal overload, overcurrent, earth fault and neutral earth fault protections.
Furthermore, the dash sign means that it is not possible to initiate CBF protection of respective side by operation of a protection function working at a
given side of the protected transformer.
There are two criteria for breaker failure detection: the first one is to check
whether the actual current flow effectively disappeared after a tripping command had been issued. The second one is to evaluate the circuit breaker
auxiliary contact status. Since circuit breaker is supposed to be open when
current disappears from the circuit, the first criterion (current monitoring) is
the most reliable means for relay to be informed about proper operation of
circuit breaker. Therefore, current monitoring is applied to detect circuit
breaker failure condition. In this context, the monitored current of each phase
is compared with the pre-defined setting. The settings are applied at HV1
I_CBF OC or MV I_CBF OC, for HV or MV CBF protection.
Furthermore, it is possible to implement current checking in case of zero-sequence and negative-sequence currents via Binary setting HV1 3I0/3I2
Check On, MV1 3I0/3I2 Check On. If setting 1-On is applied at these Binary settings, zero-sequence and negative-sequence currents are calculated
and

compared with user-defined settings. Corresponding

settings include HV 3I0_CBF ZS and MV 3I0_CBF ZS for zero-sequence


current, and HV 3I2_CBF NS and MV 3I2_CBF NS for negative-sequence
current.
160

Chapter 12 Circuit breaker failure protection


For protection functions where the tripping criterion is not dependent on current, current flow is not a suitable criterion for proper operation of the breaker.
In this case, the position of the circuit breaker auxiliary contact should be
used to determine if the circuit breaker properly operated. It is possible to
evaluate the circuit breaker operation from its auxiliary contact status. To do
so, Binary settings HV1 CB Status Check On or MV CB Status Check On
should be set to 1-On to integrate circuit breaker auxiliary contacts into CBF
function..
It should be noted that evaluation of circuit breaker auxiliary contacts is carried out in CBF function only when the current flow monitoring has not picked
up. Once the current flow criterion has picked up during the running time of
CBF timers, the circuit breaker is assumed to be open as soon as the current
disappears, even if the associated auxiliary contacts dont indicate that the
circuit breaker has opened. This gives preference to the more reliable current
criterion and avoids over functioning due to a defect e.g. in the auxiliary contact mechanism or circuit.

Logic diagram
BI_HV1 CB EXT.INT
Inter 3Ph Init CBF

O
R

Init HV CBF

Figure 54 Internal and external initiation

161

Chapter 12 Circuit breaker failure protection


Ia > HV1 I_CBF
OC

HV 3I0/3I2 Check Off

3I0 > HV1


3I0_CBF ZS
3I2 > HV1
3I2_CBF NS
Ib >HV1 I_CBF OC

O
R

A
N
D

O
R

HV 3I0/3I2 Check On

Ic > HV1 I_CBF


OC
Ib >HV1 I_CBF
OC

HV 3I0/3I2 Check Off

3I0 > HV1


3I0_CBF ZS
3I2 > HV1
3I2_CBF NS
Ic > HV1 I_CBF
OC

A
N
D

O
R

HV 3I0/3I2 Check On

O
R

Ia >HV1 I_CBF OC
Ic >HV1 I_CBF
OC

HV 3I0/3I2 Check Off

3I0 > HV1


3I0_CBF ZS
3I2 > HV1
3I2_CBF NS
Ib > HV1 I_CBF
OC

A
N
D

O
R

HV 3I0/3I2 Check On

O
R

Ia > HV1 I_CBF


OC

O
R

Curr. Crit.

Figure 55 Circuit breaker auxiliary contact evaluation

BI_HV1 CB Open A

A
N
D

BI_HV1 CB Open B
BI_HV1 CB Open C
Init HV CBF
CBF Curr. Crit. 3P

O
R

A
N
D
A
N
D

Figure 56 The logic for CB close

162

CB is closed

Chapter 12 Circuit breaker failure protection


CB is closed
CB Status Check On

Curr. crit.

O
R

A
N
D

Func_CBF on
T1_CBF

CBF stg1

T2_CBF

CBF stg2

Init HV CBF

Figure 57 The logic for CBF protection

Input and output signals


Circuit Breaker
Failure Proteciton
IA

CBF Stage 1 Trip

IB

CBF Stage 2 Trip

IC

Relay Startup

CB Pole A Open
CB Pole B Open
CB Pole C Open
EXT. INT CBF

Figure 58 Circuit breaker protection module


Table 105 Analog input list

Signal

Description

IA

Phase A current input

IB

Phase B current input

IC

Phase C current input

Table 106 Binary intput list

Signal

Description

CB Pole A Open

Circuit breaker(CB) pole A is open

163

Chapter 12 Circuit breaker failure protection

Signal

Description

CB Pole B Open

Circuit breaker(CB) pole A is open

CB Pole COpen

Circuit breaker(CB) pole A is open

EXT.INT CBF

initiate the CBF protection by external protection

Table 107 Binary output list

Signal

Description

CBF Stage1 Trip

CBF protection stage 1 trip

CBF Stage2 Trip

CBF protection stage 1 trip

Relay Startup

Relay Startup

Setting
Table 108 Settings of CBF protection for HV side of transformer

Setting

HV I_CBF
OC

Unit

Min.

Max.

(Ir:5A/1A)

(Ir:5A/1A)

Default
setting
(Ir:5A/1A)
Phase current setting value for

0.05Ir

20Ir

Negative sequence (NS) curA

0.05Ir

20Ir

NS

Zero sequence (ZS) current


A

0.05Ir

20Ir

ZS

setting

3I 0 value for HV1

CBF protection

HV T1_CBF

32

10

HV T2_CBF

0.1

32

10

164

rent setting 3I 2 value for HV


CBF protection

HV
3I0_CBF

HVcircuit breaker failure (CBF)


protection

HV
3I2_CBF

Description

Time setting value of Stage 1,


for HV CBF protection
Time setting value of Stage 2,
for HV CBF protection

Chapter 12 Circuit breaker failure protection


Table 109 Binary settings of CBF protection for HV side of transformer
DeSetting

Unit

Min.

Max.

fault

Description

setting
HV Circuit breaker failure (CBF)
HV Func_CBF

protection is switched ON
1-on; 0-off.
HV CBF protection detect nega-

HV 3I0/3I2 Check

On

tive or zero sequence current


3I0 or 3I2.
1-Detect; 0- Not Detect
HV CBF protection detect HV1

HV CB Status

Check On

CB status
1-Detect; 0- Not Detect

Table 110 Settings of CBF protection for MV side of transformer

Setting
MVI_CBF
OC

Unit

Min.

Max.

(Ir:5A/1A)

(Ir:5A/1A)

0.05Ir

20Ir

Default
setting

Description

(Ir:5A/1A)

Phase current setting value for


MV CBF protection
Negative sequence (NS) cur-

MV
3I2_CBF

0.05Ir

20Ir

NS

rent setting 3I 2 value for MV


CBF protection
Zero sequence (ZS) current

MV
3I0_CBF

0.05Ir

20Ir

ZS

setting

3I 0 value for MV CBF

protection

MV T1_CBF

32

10

MV T2_CBF

0.1

32

10

Time setting value of Stage 1,


for MV CBF protection
Time setting value of Stage 2,
for MV CBF protection

Table 111 Binary settings of CBF protection for MV side of transformer


DeSetting

Unit

Min.

Max.

fault

Description

setting

165

Chapter 12 Circuit breaker failure protection


MV Circuit breaker failure (CBF)
MV Func_CBF

protection is switched ON
1-on; 0-off.
MV CBF protection detect nega-

MV 3I0/3I2 Check

On

tive or zero sequence current


3I0 or 3I2.
1-Detect; 0- Not Detect
MV CBF protection detect MV

MV CB Status

Check On

CB status
1-Detect; 0- Not Detect

Table 112 Settings of CBF protection for LV side of transformer

Setting

Unit

LV I_CBF
OC

Min.

Max.

(Ir:5A/1A)

(Ir:5A/1A)

0.05Ir

20Ir

Default
setting

Description

(Ir:5A/1A)

Phase current setting value for


LV CBF protection
Negative sequence (NS) cur-

LV 3I2_CBF
NS

0.05Ir

20Ir

rent setting 3I 2 value for LV


CBF protection
Zero sequence (ZS) current

LV 3I0_CBF
ZS

0.05Ir

20Ir

setting

3I 0 value for LV CBF

protection
LV T1_CBF

32

10

LV T2_CBF

0.1

32

10

Time setting value of Stage 1,


for LV CBF protection
Time setting value of Stage 2,
for LV CBF protection

Table 113 Binary settings of CBF protection for LV side of transformer


DeSetting

Unit

Min.

Max.

fault

Description

setting
LV Circuit breaker failure (CBF)
LV Func_CBF

protection is switched ON
1-on; 0-off.

LV 3I0/3I2 Check
On

166

LV CBF protection detect nega0

tive or zero sequence current


3I0 or 3I2.

Chapter 12 Circuit breaker failure protection


1-Detect; 0- Not Detect

LV CB Status
Check On

LV CBF protection detect LV CB


0

status

1-Detect; 0- Not Detect

Report
Table 114 Event report list

Information

Description

HV CBF1 Trip

HV circuit breaker failure protection stage 1 trip

HV CBF2 Trip

HV circuit breaker failure protection stage 2 trip

HV CBF Init

Internal or external initiate HV circuit breaker failure protection

MV CBF1 Trip

MV circuit breaker failure protection stage 1 trip

MV CBF2 Trip

MV circuit breaker failure protection stage 2 trip

MV CBF Init

Internal or external initiate MV circuit breaker failure protection

LV CBF1 Trip

LV circuit breaker failure protection stage 1 trip

LV CBF2 Trip

LV circuit breaker failure protection stage 2 trip

LV CBF Init

Internal or external initiate LV circuit breaker failure protection

Table 115 Alarm report list


Description of event

comment

HV Func_CBF On

HV circuit breaker failure protection is switched ON (by CW)

HV Func_CBF Off

HV circuit breaker failure protection is switched OFF (by CW)

MV Func_CBF On

MV circuit breaker failure protection is switched ON (by CW)

MV Func_CBF Off

MV circuit breaker failure protection is switched OFF (by CW)

LV Func_CBF On

LV circuit breaker failure protection is switched ON (by CW)

LV Func_CBF Off

LV circuit breaker failure protection is switched OFF (by CW)

Technical data
Item
phase current

Rang or Value

Tolerance

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

0.00s to 32.00 s, step 0.01s

1% setting or +25 ms, at

Negative sequence current


zero sequence current
Time delay of stage 1

167

Chapter 12 Circuit breaker failure protection


Time delay of stage 2

0.00s to 32.00 s, step 0.01s

Reset ratio

>0.95

Reset time

< 25ms

168

200% energizing setting

Chapter 13 Dead zone protection

Chapter 13 Dead zone protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data used for dead
zone (short zone) protection function.

169

Chapter 13 Dead zone protection

Introduction
The IED provides this protection function to protect dead zone, namely the
area between circuit breaker and CT in the case that CB is open. Therefore,
by occurrence of a fault in dead zone, the short circuit current is measured by
protection relay while CB auxiliary contacts indicate the CB is open.

Internal/ external initiation

Self-adaptive for bus side CT or line side CT

When one bus side CT of feeder is applied, once a fault occurs in the dead
zone, the IED trips the relevant busbar zone. Tripping logic is illustrated in
below figure.

Protection principle
In the case of feeders with bus side CTs, once a fault occurs in the dead zone,
the IED trips the relevant busbar zone CBs. Tripping concept is illustrated in
the below figure.

trip

Trip

Bus1

Bus1

IFAULT

IFAULT
T1
Ln

Ln

L1

L1

Bus2

T1

Bus3

Bus3
Legend:

Legend:

170

Opened CB

Opened CB

Closed CB

Closed CB

Bus2

Chapter 13 Dead zone protection


Figure 59 Tripping logic for applying bus side CT and for applying line side CT

2.1

Function description

Internal/external initiation

Self-adaptive for bus side CT or line side CT. For bus side CTs, the dead

zone protection will select to trip breakers on other lines connected to the
same busbar. For line side CTs, the dead zone protection will select trip opposite side breakers on the same line.

Logic diagram
Func_HV CBF
On

Init HV CBF

A
N
D

CBF.Curr. Crit.
BI_HV PhA CB Open
BI_HV PhB CB Open
BI_HV PhC CB Open

A
N
D

Func_Dead Zone On
T_Dead Zone

Dead Zone Trip

A
N
D

BI_HV 3Ph CB Close

Figure 60 Dead zone protection logic

171

Chapter 13 Dead zone protection

Input and output signals


Dear Zone
Protection
IA

DZ Trip

IB

Relay Startup

IC
CB Pole A Open
CB Pole B Open
CB Pole C Open
CB 3 Poles Close

Figure 61 Dead zone protection module


Table 116 Analog input list

Signal

Description

IA

Phase A current input

IB

Phase B current input

IC

Phase C current input

Table 117 Binary input list

Signal

Description

CB Pole A Open

Circuit breaker(CB) pole A is open

CB Pole B Open

Circuit breaker(CB) pole B is open

CB Pole C Open

Circuit breaker(CB) pole C is open

CB 3 Poles Close

3 poles of circuit breaker(CB) is close

Table 118 Binary output list

Signal

Description

DZ Trip

dead zone protection trip

Relay Startup

Relay Startup

172

Chapter 13 Dead zone protection

Setting
Table 119 Dead zone protection function setting list for HV side of transformer

Setting

Unit

HV T_Dead Zone

Min.

Max.

(Ir:5A/1A

(Ir:5A/1A

32

Default
setting
(Ir:5A/1A

Description

)
10

Time delay setting for HV


dead zone protection

Table 120 Dead zone protection binary setting list for HV side of transformer

Setting

Uni

Min

Max

Default set-

ting

Description
Dead zone protection is switched

HV Func_Dead

Zone

ON
1-on; 0-off.

Table 121 Dead zone protection function setting list for MV side of transformer

Setting

Unit

MV T_Dead Zone

Min.

Max.

(Ir:5A/1A

(Ir:5A/1A

32

Default
setting
(Ir:5A/1A

Description

)
10

Time delay setting for MV


dead zone protection

Table 122 Dead zone protection binary setting list for MV side of transformer

Setting

Uni

Min

Max

Default set-

ting

Description
Dead zone protection is switched

MV Func_Dead

Zone

ON
1-on; 0-off.

Table 123 Dead zone protection function setting list for LV side of transformer

Setting

LV T_Dead Zone

Unit

Min.

Max.

(Ir:5A/1A

(Ir:5A/1A

32

Default
setting
(Ir:5A/1A

Description

)
10

Time delay setting for LV

173

Chapter 13 Dead zone protection


dead zone protection

Table 124 Dead zone protection binary setting list for LV side of transformer

Setting

Uni

Min

Max

Default set-

ting

LV Func_Dead
Zone

Description
Dead zone protection is switched ON
1-on; 0-off.

Report
Table 125 Event report list
Information

Description

HV Dead Zone

HV Dead zone trip

MV Dead Zone

MV Dead zone trip

LV Dead Zone

LV Dead zone trip

Table 126 Operation report list


Information

Description

HV Func_DZ On

HV DZ function on

HV Func_DZ Off

HV DZ function off

MV Func_DZ On

MV DZ function on

MV Func_DZ Off

MV DZ function off

LV Func_DZ On

LV DZ function on

LV Func_DZ Off

LV DZ function off

Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
Item

Rang or Value

Tolerance

Current

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

Time delay

0.00s to 32.00s, step 0.01s

1% setting or +40 ms, at


200% energizing setting

Reset ratio

174

>0.95

Chapter 14 STUB protection

Chapter 14 STUB protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data used for STUB
protection function.

175

Chapter 14 STUB protection

Introduction
The STUB protection protects the zone between the CTs and the open
disconnector. The STUB protection is enabled when the open position of the
disconnector is informed to the IED through connected binary input. The
function supports one definite stage with the logic shown inbelow figure.

Protection principle

2.1

Function description

Busbar A
CT1-1
CB1
CT1-2

Fault

Feeder1

Feeder 1 Disconnector
CT3-1
CB3
CT3-2
Feeder2
Feeder 2 Disconnector
CT2-1
CB2
CT2-2
Busbar B

Figure 62 STUB fault at circuit breaker arrangement


If IED detects short circuit current flowing while the line disconnector is open,
STUB fault is detected for the short circuit in the area between the current
transformers and the line disconnector. Here, the summation of CT1 and CT3
presents the short circuit current.

176

Chapter 14 STUB protection


The STUB protection is an overcurrent protection which is only in service if
the status of the line disconnector indicates the open condition. The binary
input must therefore be informed via an auxiliary contact of the disconnector.
In the case of a closed line disconnector, the STUB protection is out of service. The STUB protection stage provides one definite time overcurrent stage
with settable delay time. This protection function can be enabled or disabled
via the binary setting Func_STUB. Corresponding current setting value can
be inserted in I_STUB setting. The IED generate trip command whenever
the time setting T_STUB is elapsed.

Logic diagram
Ia>I_STUB
Ib>I_STUB

O
R

Ic>I_STUB
Func_STUB

Output Disconnector Open

A
N
D

T_STUB

Permanent trip

Figure 63 Logic diagram for STUB protection

Input and output signals

STUB Protection
IA1

STUB Trip

IB1

Relay Startup

IC1
IA2
IB2
IC2

Figure 64 STUB protection module

177

Chapter 14 STUB protection


Table 127 Analog input list

Signal

Description

IA1

Phase A current input of CT of circuit breaker 1

IB1

Phase B current input of CT of circuit breaker 1

IC1

Phase C current input of CT of circuit breaker 1

IA2

Phase A current input of CT of circuit breaker 2

IB2

Phase B current input of CT of circuit breaker 2

IC2

Phase C current input of CT of circuit breaker 2

Table 128 Binary input list

Signal

Description
Transformer output feeder disconnector is

Output disconnector open

open, to enable the STUB protection

Table 129 Binary output list

Signal

Description

STUB Trip

STUB Trip

Relay Startup

Relay Startup

Setting
Table 130 Setting value list for STUB protection for HV side of transformer

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1
A)

HV I_STUB

0.05Ir

20Ir

100

HV T_STUB

60

60

178

Description

current threshold of STUB protection


delay time of STUB protection

Chapter 14 STUB protection


Table 131 Binary setting list for STUB protection for HV side of transformer

Setting

Unit

HV Func_STUB

Min.

Max.

Default
setting
0

HV STUB Init LV

Description
Enable or disable STUB
protection
STUB protection initiate

CBF

LV side CBF
0 - initiate, 1 not initiate

HV STUB Init MV

STUB protection initiate

CBF

HV side CBF
0 - initiate, 1 not initiate

Table 132 Setting value list for STUB protection for MV side of transformer

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)

MV I_STUB

0.05Ir

20Ir

100

MV T_STUB

60

60

current threshold of STUB protection


delay time of STUB protection

Table 133 Binary setting list for STUB protection for MV side of transformer

Setting

Unit

MV Func_STUB

Min.

Max.

Default
setting
0

MV STUB Init LV

Description
Enable or disable STUB
protection
STUB protection initiate

CBF

LV side CBF
0 - initiate, 1 not initiate

MV STUB Init MV

STUB protection initiate

CBF

MV side CBF
0 - initiate, 1 not initiate

Table 134 Setting value list for STUB protection for LV side of transformer

Setting

LV I_STUB

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.05Ir

20Ir

Default
setting
(Ir:5A/1

Description

A)
100

current threshold of STUB protec179

Chapter 14 STUB protection

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
tion

LV T_STUB

60

60

delay time of STUB protection

Table 135 Binary setting list for STUB protection for LV side of transformer

Setting

Unit

LV Func_STUB

Min.

Max.

Default
setting
0

LV STUB Init LV

Description
Enable or disable STUB
protection
STUB protection initiate

CBF

LV side CBF
0 - initiate, 1 not initiate

LV STUB Init MV

STUB protection initiate

CBF

LV side CBF
0 - initiate, 1 not initiate

Report
Table 136 Event report list

Information

Description

HV STUB Trip

HV STUB protection trip

MV STUB Trip

MV STUB protection trip

LV STUB Trip

LV STUB protection trip

Table 137 Operation report list


Information

Description

HV Func_STUB On

HV STUB function on

HV Func_STUB Off

HV STUB function Off

MV Func_STUB On

MV STUB function on

MV Func_STUB Off

MV STUB function Off

LV Func_STUB On

LV STUB function on

LV Func_STUB Off

LV STUB function Off

180

Chapter 14 STUB protection

Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
Table 138 Technical data for STUB protection
Item

Rang or Value

Tolerance

Current

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

Time delay

0.00s to 60.00s, step 0.01s

1% setting or +40 ms, at


200% energizing setting

Reset ratio

>0.95

181

Chapter 14 STUB protection

182

Chapter 15 Poles discordance protection

Chapter 15 Poles discordance


protection

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for poles discordance protection.

183

Chapter 15 Poles discordance protection

Introdcution
Under normal operating condition, all three poles of the circuit breaker must
be closed or open at the same time. The phase separated operating circuit
breakers can be in different positions (close-open) due to electrical or mechanical failures. This can cause negative and zero sequence currents which
gives thermal stress on rotating machines and can cause unwanted operation
of zero sequence or negative sequence current functions.
Single pole opening of the circuit breaker is permitted only in the short period
related to single pole dead times, otherwise the breaker is tripped three pole
to resolve the problem. If the problem still remains, the remote end can be
intertripped via circuit breaker failure protection function to clear the unsymmetrical load situation.
The pole discordance function operates based on information from auxiliary
contacts of the circuit breaker for the three phases with additional criteria from
unsymmetrical phase current.

Protection principle

2.1

Function description
The CB position signals are connected to IED via binary input in order to
monitor the CB status. Poles discordance condition is established when binary setting HV Func_PD for HV said, or MV Func_PD for MV said is set
to 1/on, and at least one pole is open and at the same time not all three
poles are closed. The auxiliary contacts of the circuit breakers are checked
with corresponding phase currents for plausibility check. Error alarm CB Err
Blk PD is reported after 5 sec whenever CB auxiliary contacts indicate that
one pole is open but at the same time current is flowing through the pole.
Additionally the function can be informed via binary setting HV PD Chk
3I0/3I2 and MV PD Chk 3I0/3I2for additionaly zero and negative sequence
current as well as current criteria involved in CBF protection. Pole discordance can be detected when current is not flowing through all three poles.
When current is flowing through all three poles, all three poles must be closed
even if the breaker auxiliary contacts indicate a different status.

184

Chapter 15 Poles discordance protection

Logic diagram

BI_CB Open A

Ia > 0.06Ir

BI_CB Open B

Ib > 0.06Ir
BI_CB Open C

Ic > 0.06Ir

BI_CB Open A
BI_CB Open B
BI_CB Open C

BI_CB Open A

Ia < 0.06Ir

BI_CB Open B

Ib < 0.06Ir
BI_CB Open C

Ic< 0.06Ir

3I2 > 3I2_PD


3I0 >3I0_PD
CBF Curr. Crit. A
CBF Curr. Crit. B
CBF Curr. Crit. C

A
N
D
A
N
D

O
R

A
N
D

A
N
D

5s

CB Err Blk PD

A
N
D
A
N
D
A
N
D

Func_PD On

A
N
D

O
R

T_PD

PD Trip

A
N
D
O
R
A
N
D

A
N
D

PD Chk 3I0/3I2 on
PD Chk 3I0/3I2 off

Figure 65 Logic diagram for poles discordance protection

185

Chapter 15 Poles discordance protection

Input and output signals


Pole Discordance
Protection
IA

PD Trip

IB

Relay Startup

IC

INBK
CB Pole A Open
CB Pole B Open
CB Pole C Open

Figure 66 Poles discordance protection module


Table 139 Analog input list
Signal

Description

IA
IB
IC
INBK

Phase A current input


Phase B current input
Phase C current input
Neutral current input

Table 140 Binary input list


Signal

Description

CB Pole A Open
CB Pole B Open
CB Pole C Open

Circuit breaker(CB) pole A is open


Circuit breaker(CB) pole B is open
Circuit breaker(CB) pole C is open

Table 141 Binary output list


Signal

Description

PD Trip
Relay Startup

PD Trip
Relay Startup

186

Chapter 15 Poles discordance protection

Setting
Table 142 Function setting list for poles discordance protection for HV side of
tranformer

Setting

Default
setting

Unit

Min.

Max.

Description

HV 3I0_PD

0.05Ir

20Ir

zero sequence current threshold of


pole discordance protection

HV 3I2_PD

0.05Ir

20Ir

negative sequence current threshold of pole discordance protection

HV T_PD

60

delay time of pole discordance


protection

10

Table 143 Binary setting list for poles discordance protection for HV side of
tranformer
Min.

Max.

Default
setting

MV Func_PD

MV PD Chk
3I0/3I2

Setting

Unit

Description
Enable or disable MV poles
discordance protection
Enable or disable 3I0/3I2
criteria

Table 144 Function setting list for poles discordance protection for MV side of
tranformer

Setting

Default
setting

Unit

Min.

Max.

Description

MV 3I0_PD

0.05Ir

20Ir

zero sequence current threshold of


pole discordance protection

MV 3I2_PD

0.05Ir

20Ir

negative sequence current threshold of pole discordance protection

MV T_PD

60

delay time of pole discordance


protection

10

Table 145 Binary setting list for poles discordance protection for MV side of
tranformer
Min.

Max.

Default
setting

MV Func_PD

MV PD Chk
3I0/3I2

Setting

Unit

Description
Enable or disable MV poles
discordance protection
Enable or disable 3I0/3I2
criteria

187

Chapter 15 Poles discordance protection

Report
Table 146 Event report list
Information

Description

HV PD Trip
MV PD Trip

HV poles discordance protection trip


MV poles discordance protection trip

Table 147 Alarm report list


Information

Description

CB Err Blk PD

Circuit breaker error block poles discordance protection

Table 148 Operation report list


Information
HV Func_PD On
HV Func_PD Off
MV Func_PD On
MV Func_PD Off

Description
HV poles discordance function on
HV poles discordance function off
MV poles discordance function on
MV poles discordance function off

Technical data
NOTE:
Ir: CT rated secondary current, 1A or 5A;
Table 149 Technical data for pole discordance
Item

Rang or Value

Tolerance

Current

0.08 Ir to 20.00 Ir

3% setting or 0.02Ir

Time delay

0.00s to 60.00s, step 0.01s

1% setting or +40 ms, at


200% energizing setting

Reset ratio

>0.95

188

Chapter 16 Secondary system supervision

Chapter 16 Secondary system


supervision

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for secondary
system supervision function.

189

Chapter 16 Secondary system supervision

VT failure supervision function


In the event of a measured voltage failure due to a broken conductor or a
short circuit fault in the secondary circuit of voltage transformer, those protection functions which work based on voltage criteria may mistakenly see a
voltage of zero. VT failure supervision function is provided to inform those
functions about a voltage failure.

Function principle
VT failure supervision function can be enabled or disabled in each side
through Binary setting HV VT Fail Detect, MV VT Fail Detect and LV VT
Fail Detect. By applying setting 1-On to these Binary settings, respective
VT failure supervision function would monitor the voltage transformer circuit
of corresponding side. Each VT failure supervision function is able to detect
single-phase broken, two-phase broken or three-phase broken faults in respective voltage transformer. There are three main criteria for VT failure detection; from them the first one is dedicated to detect three-phase broken
faults. The second and third one is dedicated to detect single or two-phase
broken faults in solid earthed and isolated/resistance earthed systems, respectively. A precondition to meet these three criteria is that the relay should
not be picked up and the calculated zero sequence and negative sequence
currents should be less than setting of HV I_VT Fail, MV I_VT Fail or LV
I_VT Fail. These criteria are as follows:
The calculated zero sequence voltage 3U0 as well as maximum of three
phase-to-earth voltages of respective side of the protected transformer are
less than the setting of HV Upe_VT Fail, MV Upe_VT Fail or LV Upe_VT
Fail and at the same time, maximum of three phase currents of respective
side is higher than setting of HV I_VT Fail, MV I_VT Fail or LV I_VT Fail.
This condition may correspond to three phase broken fault in secondary circuit of the voltage transformer in respective side of the protected transformer.
The calculated zero sequence voltage 3U0 of respective side of the protected
transformer is more than the setting of HV Upe_VT Fail, MV Upe_VT Fail
or LV Upe_VT Fail. This condition may correspond to single or two-phase
broken fault in secondary circuit of the voltage transformer in respective side
of the protected transformer, if the system starpoint is solidly earthed.
The calculated zero sequence voltage 3U0 of respective side of the protected
transformer is more than the setting of HV Upe_VT Fail, MV Upe_VT Fail
or LV Upe_VT Fail, and at the same time, the difference between the maximum and minimum phase-to-phase voltages of respective side is more than
the setting of HV Upp_VT Fail, MV Upp_VT Fail or LV Upp_VT Fail. This
condition may correspond to single or two-phase broken fault in secondary
circuit of the voltage transformer in respective side of the protected transformer, if the system starpoint is isolated or resistance earthed.

In addition to the mentioned conditions, the device has the capability to be


190

Chapter 16 Secondary system supervision


informed about the VT MCB failure through its binary inputs. These inputs include HV MCB FAIL BI, MV MCB FAIL BI and LV MCB FAIL BI. In this
context, VT fail is detected in corresponding side, if the respective binary inputs are active.
If VT failure supervision detects a failure in voltage transformer secondary
circuit, either by means of the above mentioned criteria or reception of a VT
MCB fail indication, all the protection functions which operate based on direction determination would be blocked in corresponding side of the protected
transformer, depending on the setting. Furthermore, an alarm report of HV
VT Fail, MV VT Fail or LV VT Fail, is issued after 10s delay time. The
blocking condition would be removed if one of the following conditions is met
within the 10s delay time.
Minimum phase voltage of corresponding side of the protected transformer
becomes more than setting of HV Upe_VT Normal, MV Upe_VT Normal or
LV Upe_VT Normal for 500ms.
Minimum phase voltage of corresponding side becomes more than setting of
HV Upe_VT Normal, MV Upe_VT Normal or LV Upe_VT Normal and at
the same time, the calculated zero sequence and negative sequence current
of corresponding side becomes more than the setting of HV 3I02_VT Fail,
MV 3I02_VT Fail or LV 3I02_VT Fail.
Subsequent to reporting VT fail alarm, the blocking condition of respective
protection functions would be removed if the minimum phase voltage of corresponding side becomes more than the setting of HV Upe_VT Normal, MV
Upe_VT Normal or LV Upe_VT Normal for a duration more than 10s.
Below figure shows logic diagram of VT failure supervision as it is implemented in the IED.

191

Chapter 16 Secondary system supervision

Max(Ia,Ib,Ic)>I_ VT Fail

A
N
D

Max{Ua,Ub,Uc}<Upe_VT Fail

3U0 < Upe_VT Fail-1

Solid Earth on

O
R

3U0 >= Upe_VT Fail-1)

Solid Earth off

A
N
D

A
N
D

Max{Uab,Ubc,Uca}Min{Uab,Ubc,Uca}>
Upp_VT Fail

A
N
D

Relay Pickup

O
R

BI MCB Fail

A
N
D

VT Fail
Detected

HV VT Fail Detect on

VT Fail Detected

Min{Ua,Ub,Uc}>Upe_VT Normal

3I0>3I02_VT Fail or
3I2>3I02_VT Fail

min{Ua,Ub,Uc}>Upe_VT Normal

A
N
D

A
N
D

500ms
A
N
D
A
N
D

O
R

A
N
D

No VT Fail

10s

Figure 67 Logic of VT Failure supervision

192

10s

Alarm report

Chapter 16 Secondary system supervision

Input and output signals


VT Secondary
Circuit Supervision
IA1

VT Failure

IB1

Relay Startup

IC1
IA2
IB2
IC2
UA
UB
UC
V3P MCB Fail

Figure 68 VT Failure supervision module


Table 150 Analog input list
Signal

Description

IA1

Phase A current input of CT of circuit breaker


1
Phase B current input of CT of circuit breaker
1
Phase C current input of CT of circuit breaker
1
Phase A current input of CT of circuit breaker
2
Phase B current input of CT of circuit breaker
2
Phase C current input of CT of circuit breaker
2
Phase A voltage input
Phase B voltage input
Phase C voltage input

IB1
IC1
IA2
IB2
IC2
UA
UB
UC

Table 151 Binary input list


Signal

Description

V3P MCB Fail

VT failure informed by BI

193

Chapter 16 Secondary system supervision


Table 152 Binary output list
Signal

Description

VT Failure
Relay Startup

VT Failure

Relay Startup

Setting
Table 153 Settings of VT failure supervision for HV side of transformer
Default
setting

Setting Title

Unit

HV I_VT Fail

0.05Ir

0.2Ir

0.05

HV 3I02_ VT Fail

0.05Ir

0.2Ir

0.5

HV Upe_VT Fail

20

HV Upp_VT Fail

10

30

16

HV Upe_VT
Normal

40

65

40

Min.

Max.

Comment
Minimum Current of VT failure
for HV side
Minimum zero or negative Current of HV VT fail
Maximum phase to earth voltage
of HV VT fail
Maximum phase to phase voltage of HV VT fail
Minimum phase to phase voltage of HV VT normal

Table 154 Binary settings of VT failure supervision for HV side of transformer


Default

Min.

Max.

HV VT FAIL Detect

HV Solid Earth

Setting Title

Unit

Comment
HV VT Failure Detection
On/Off
1-On, 0-Off.
HV Earthing mode:
1: Solid earthed system ;
0: isolated system or resistance earthed.

Table 155 Settings of VT failure supervision for MV side of transformer


Default
setting

Setting Title

Unit

MV I_VT Fail

0.05Ir

0.2Ir

0.05

MV 3I02_VT Fail

0.05Ir

0.2Ir

0.5

MV Upe_VT Fail

20

MV Upp_VT Fail

10

30

16

MV Upe_VT
Normal

40

65

40

194

Min.

Max.

Comment
Minimum Current of VT failure
for MV side
Minimum zero or negative Current of MV VT fail
Maximum phase to earth voltage
of MV VT fail
Maximum phase to phase voltage of MV VT fail
Minimum phase to phase voltage of MV VT normal

Chapter 16 Secondary system supervision


Table 156 Binary settings of VT failure supervision for MV side of transformer
Setting Title

Unit

MV VT FAIL Detect

MV Solid Earth

Default

Min.

Max.

MV VT Failure Detection
On/Off
1-On, 0-Off.

MV Earthing mode:
1: Solid earthed system ;
0: isolated system or resistance earthed.

Comment

Table 157 Settings of VT failure supervision for LV side of transformer


Default
setting

Setting Title

Unit

LV I_VT Fail

0.05Ir

0.2Ir

0.05

LV 3I02_VT Fail

0.05Ir

0.2Ir

0.5

LV Upe_VT Fail

20

LV Upp_VT Fail

10

30

16

LV Upe_VT
Normal

40

65

40

Min.

Max.

Comment
Minimum Current of VT failure
for LV side
Minimum zero or negative Current of LV VT fail
Maximum phase to earth voltage
of LV VT fail
Maximum phase to phase voltage of LV VT fail
Minimum phase to phase voltage of LV VT normal

Table 158 Binary settings of VT failure supervision for LV side of transformer


Default

Min.

Max.

LV VT FAIL Detect

LV Solid Earth

Setting Title

Unit

Comment
LV VT Failure Detection On/Off
1-On, 0-Off.
LV Earthing mode:
1: Solid earthed system ;
0: isolated system or resistance earthed.

Report
Table 159 Alarm report list
Information

Description

HV VT Fail
MV VT Fail
LV VT Fail

HV VT Fail alarm
MV VT Fail alarm
LV VT Fail alarm

Table 160 Operation report list


Information
HV Func_VT On
HV Func_VT Off
MV Func_VT On

Description
HV VT failure supervision function on
HV VT failure supervision function off
MV VT failure supervision function on
195

Chapter 16 Secondary system supervision


Information
MV Func_VT Off
LV Func_VT On
LV Func_VT Off

Description
MV VT failure supervision function off
LV VT failure supervision function on
LV VT failure supervision function off

Technical data
Item
Minimum current
Minimum zero or negative sequence current
Maximum phase to earth voltage
Maximum phase to phase voltage
Normal phase to earth voltage

196

Range or value
0.08Ir to 0.20Ir, step 0.01A
0.08Ir to 0.20Ir, step 0.01A

Tolerances
3% setting or 0.02Ir
5% setting or 0.02Ir

7.0V to 20.0V, step 0.01V


10.0V to 30.0V, step 0.01V

3% setting or 1 V
3% setting or 1 V

40.0V to 65.0V, step 0.01V

3% setting or 1 V

Chapter 17 External Bis to trip BOs

Chapter 17 External BIs to trip BOs

About this chapter


This chapter describes the protection principle, input and output
signals, parameter, IED report and technical data for external BIs
to trip BOs function.

197

Chapter 17 External Bis to trip BOs

Introduction
Two special binary inputs (BI_Config1, BI_Config2) are provided which can
be used to activate respective binary outputs (BO1 and BO2), according to
the setting applied at Binary settings BI1 Enable BO1 and BI2 Enable BO2.
By applying setting 1-enable to these Binary settings, BO1 will be activated
if BI1 is energized. Similarly, BO2 will be activated if BI2 is energized. Furthermore, 7th LED in front plate of the device would be lighted when BO1 or
BO2 is activated.

Function principle
The external BIs can be used in conjunction with the mechanical protections
of the protected transformer (such as Buchholz, Winding temperature, and so
on). In this context, trip commands of the main and backup mechanical protections can be marshaled to BI1 and BI2, respectively. By doing so, the
output trip commands would be provided at BO1 and BO2 respectively.
Since the trip command of mechanical protection has latched nature, two
operating modes are provided for the Bos activation. The operating modes
include direct and pulse tripping modes. In direct tripping mode, each BO
contact is active as long as respective BI is energized, and after BI disappearance 20ms the BO contacts are deactivated. Whereas in pulse tripping
mode, by each up-edge of BI, respective BO contacts remain active during a
settable pulse time, and after the settable time, the BO contacts are inactive.
The tripping modes can be selected for the BOs by Binary settings BO1
Pulse Tripping and BO2 Pulse Tripping. Pulse tripping mode would be
possible if setting 1-Pulse Tripping is applied to the Binary settings. Similarly,
setting 0-Direct Tripping activates direct tripping mode for respective BOs.
The logic is shown in below figure.

BI Enable BO on

A
N
D
BO Pulse Tripping

BIx up edge

Pulse Tripping Time


1

A
N
D

1
0

0
BI trip BO

A
N
D

198

A
N
D

0
BI trip BO

Chapter 17 External Bis to trip BOs


Figure 69 Logic of external BIs to trip BOs
Furthermore, it is possible to set BIs to initiate CBF protection in HV, MV or LV
sides of protected transformer via a number of Binary settings. The Binary
settings include BI1 Init HV CBF, BI1 Init MV CBF and BI1 Init LV CBF on
for the first BI. Similarly, Binary settings BI2 Init HV CBF, BI2 Init MV CBF
and BI2 Init LV CBF correspond to the second BI.

BI Trigger Record
In the IED, it is possible for Binary inputs (BIs) to trigger disturbance record
(DR). The exceptions are Switch SetGroup, Blk Rem Access, Relay Test
and Reset. In this context, each Binary input can be set independently
whether it can trigger DR or not. Further, it is possible to set whether BI triggers DR in its up or down edge. Example logic of BI HV CB Open Status
triggering DR is given in below figure. The same logic is applied for the other
BIs.
BI HV1 CB Open A
Change from 1to 0

Equipment parameter
HV1 CB OPEN STATUS DOWN = 1

A
N
D

O
R

BI HV1 CB OPEN STATUS ENABLE


=1

BI HV1 CB Open Status


Change from 0to 1
Equipment parameter
HV1 CB OPEN STATUS DOWN = 0
(meaning UP edge)

Trigger
Record

A
N
D

Figure 70 Logic of BI trigger record

199

Chapter 17 External Bis to trip BOs

BI Switch SetGroup
BI Switch SetGroup is used to switch setting group of the device. Both BI
SetGrp Switchand Normal Set Switch are selected by making change in the
content of special Binary setting BI SetGrp Switch which can be set under
Common Para submenu. When the Binary setting is set to 1, BI setting
group switch mode is applied, on the contrary, Normal setting group switch
mode (shortcut key or operate through the menu) is applied. For BI SetGrp
Switch mode, When BI Switch SetGroup is deactivated, the content of Binary setting BI SetGrp Switch is set to 0 and it means that no switching in
setting groups is desired. In this case, Group 1 is applied to the device. When
the BI is activated, the content of Binary setting BI SetGrp Switch is set to 1
and it means that BI SetGrp Switch mode is applied. Thus, the current setting-value would automatically be switched to Group 2. For the other switch
mode, whether the BI is activated or not, setting group change is valid for
shortcut key or operate through the menu.

BI Blk Rem Access and RELAY


TEST
There are two methods to block remote access to the device, BI Blk Rem
Access or making change in the content of special Binary setting NOT Blk
Remote Access which can be set under Common Para submenu.
When BI Blk Rem Access is activated, or the content of Binary setting NOT
Blk Remote Access is set to 0, SCADA remote access is blocked to the device and therefore, only local operation is permitted.
When BI Blk Rem Access is deactivated, and the content of Binary setting
NOT Blk Remote Access is set to 1, both SCADA commands and local operation can be executed by the device.
Similarly, there are two methods to select test or normal operating mode of
the device, BI Relay Test or making change in the content of special Binary
setting Relay Test Mode which can be set under Common Para submenu.
When BI Relay Test is activated, or the content of Binary setting Relay Test
Mode is set to 1, the relay is in test mode.
When BI Relay Test is deactivated, and the content of Binary setting Relay
Test Mode is set to 0, the relay is in normal operation mode

200

Chapter 17 External Bis to trip BOs

BI BI_Config1~ BI_Config2 and BI


TRIGGER DR1~ 10

Both BI_Config1~ BI_Config2 and BI Trigger DR1~ BI Trigger DR10 are


binary inputs which can be recorded. BI_Config1~ BI_Config2 can operate to
binary output X10 and X11. The names of these BIs can be modified by
CSPC tools according to actual situation.

Setting
Table 161 Setting of external BIs to trip BOs

Setting

T_Pulse
Tripping

Unit

Default

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.2

setting
(Ir:5A/1

Description

A)
5

delay time of STUB protection

Table 162 Binary settings of external DIs to trip DOs

Setting Title

Setting

Default

options

setting

Comment
st

BI1 Enable
BO1

To select whether the 1 binary input (BI1) trip


1/0

st

the 1 binary output (BO1) or not.


1-enable, 0-disable
To select BO1 tripping in pulse mode or in direct

BO1 Pulse
Tripping

1/0

mode
0- BO1 Direct Tripping, without delay
1- BO1 Pulse Tripping, with preset delay time

BI2 Enable
BO2

To select whether the 2


1/0

the 2

nd

nd

binary input (BI2) trip

binary output (BO2) or not.

1-enable, 0-disable
To select BO2 tripping in pulse mode or in direct

BO2 Pulse
Tripping

1/0

mode
0- BO2 Direct Tripping, without delay
1- BO2 Pulse Tripping, with preset delay time

BI1 Init HV
CBF
BI1 Init MV
CBF

1/0

1/0

whether BI1 initiate HV side CBF or not


0 - initiate, 1 not initiate
whether BI1 initiate MV side CBF or not
201

Chapter 17 External Bis to trip BOs


Setting Title

Setting

Default

options

setting

Comment
0 - initiate, 1 not initiate

BI1 Init LV
CBF
BI2 Init HV
CBF
BI2 Init MV
CBF
BI2 Init LV
CBF

202

1/0

1/0

1/0

1/0

whether BI1 initiate LV side CBF or not


0 - initiate, 1 not initiate
whether BI2 initiate HV side CBF or not
0 - initiate, 1 not initiate
whether BI2 initiate MV side CBF or not
0 - initiate, 1 not initiate
whether BI2 initiate LV side CBF or not
0 - initiate, 1 not initiate

Chapter 18 Station communication

Chapter 18 Station communication

About this chapter


This chapter describes the communication possibilities in a
SA-system.

203

Chapter 18 Station communication

Overview
Each IED is provided with a communication interface, enabling it to connect to
one or many substation level systems or equipment.
The following communication protocols are available:

LON communication protocol

IEC 61850-8-1 communication protocol

60870-5-103 communication protocol

The IED is able to connect to one or more substation level systems or


equipments simultaneously, through the communication ports and supported
protocols.

1.1

Protocol

1.1.1

LON communication protocol


The LON protocol is specified in the LonTalkProtocol Specification Version 3
from Echelon Corporation. This protocol is designed for communication in
control networks and is a peer-to-peer protocol where all the devices connected to the network can communicate with each other directly.

1.1.2

IEC61850-8 communication protocol


IEC 61850-8-1 allows two or more intelligent electronic devices (IEDs) from
one or several vendors to exchange information and to use it in the performance of their functions and for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC
61850-8-1 standard, allows the IEDs to communicate state and control information amongst themselves, using a publish-subscribe mechanism. That
is, upon detecting an event, the IED(s) use a multi-cast transmission to notify
those devices that have registered to receive the data. An IED can, by publishing a GOOSE message, report its status. It can also request a control action to be directed at any device in the network.

204

Chapter 18 Station communication


1.1.3

IEC60870-5-103 communication protocol


The IEC 60870-5-103 communication protocol is mainly used when a protection IED communicates with a third party control or monitoring system. This
system must have software that can interpret the IEC 60870-5-103 communication messages.
The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit
serial communication exchanging information with a control system. In IEC
terminology a primary station is a master and a secondary station is a slave.
The communication is based on a point-to-point principle. The master must
have software that can interpret the IEC 60870-5-103 communication messages. For detailed information about IEC 60870-5-103, refer to the
IEC60870 standard part 5: Transmission protocols, and to the section 103:
Companion standard for the informative interface of protection equipment.

1.2

Communication port

1.2.1

Front communication port


There is a serial RS232 port on the front plate of all IEDs. Through this port,
the IED can be connected to the personal computer for setting, testing, and
configuration using the dedicated Sifang software tool.

1.2.2

RS485 communication ports


Up to 2 isolated electrical RS485 communication ports are provided to connect with substation automation system. These two ports can work in parallel
for IEC60870-5-103.

1.2.3

Ethernet communication ports


Up to 3 electrical or optical Ethernet communication ports are provided to
connect with substation automation system. These two out of three ports can
work in parallel for protocol, IEC61850 or IEC60870-5-103.

1.3

Technical data

205

Chapter 18 Station communication


Front communication port
Item

Data

Number

Connection

Isolated, RS232; front panel


9-pin subminiature connector, for CSmart

Communication speed

9600 baud

Max. length of communication cable

15 m

RS485 communication port


Item

Data

Number

0~2

Connection

2-wire connector
Rear port in communication module

Max. length of communication cable

1.0 km

IEC 60870-5-103 protocol


Communication speed

Factory setting 9600 baud


Min. 1200 baud, Max. 19200 baud

Ethernet communication port


Item

Data
Electrical communication port

Number

0~3

Connection

RJ45 connector
Rear port in communication module

Max. length of communication cable

100m

IEC 61850 protocol


Communication speed

100 Mbit/s

IEC 60870-5-103 protocol


Communication speed

100 Mbit/s
Optical communication port ( optional )

Number

0~3

Connection

SC connector
Rear port in communication module

206

Chapter 18 Station communication


Item

Data

Optical cable type

Multi-mode

Max. length of communication cable

2.0km

IEC 61850 protocol


Communication speed

100 Mbit/s

IEC 60870-5-103 protocol


Communication speed

100 Mbit/s

Time synchronization
Item

Data

Mode

Pulse mode

IRIG-B signal format

IRIG-B000

Connection

2-wire connector
Rear port in communication module

Voltage levels

differential input

207

Chapter 18 Station communication

2 Typicalcommunication scheme
2.1

Typical substation communication scheme


Server or
Work Station 1

Work Station 3

Server or
Work Station 2

Switch

Work Station 4

Net 1: IEC61850/IEC103,Ethernet Port A

Switch

Net 2: IEC61850/IEC103,Ethernet Port B

Switch

Switch

Switch

Gateway
or
converter

Switch

Gateway
or
converter

Net 4: IEC103, RS485 Port B


Net 3: IEC103, RS485 Port A

Figure 71 Connection example for multi-networks of station automation system

2.2

Typical time synchronizing scheme


All IEDs feature a permanently integrated electrical time synchronization port.
It can be used to feed timing telegrams in IRIG-B or pulse format into the
IEDs via time synchronization receivers. The IED can adapt the second or
minute pulse in the pulse mode automatically.
Meanwhile, SNTP network time synchronization can be applied.
Below figure illustrates the optional time synchronization modes.

208

Chapter 18 Station communication

SNTP

Ethernet port

IRIG-B

IRIG-B port

Pulse

Binary input

Figure 72 Time synchronizing modes

209

Chapter 18 Station communication

210

Chapter 19 Hardware

Chapter 19 Hardware

About this chapter


This chapter describes the IED hardware.

211

Chapter 19 Hardware

Introduction

3.1

IED structure
The enclosure for equipment is 19 inches in width and 4U in height according
to IEC 60297-3.

The equipment is flush mounting with panel cutout and cabinet.

Connection terminals to other system on the rear.

The front panel of equipment is aluminium alloy by founding in integer

and overturn downwards. LCD, LED and setting keys are mounted on the
panel. There is a serial interface on the panel suitable for connecting to PC.

Draw-out modules for serviceability are fixed by lock component.

The modules can be combined through the bus on the rear board. Both

the equipment and the other system can be combined through the rear interfaces.

3.2

IED appearance

Figure 73 Protection IED front view


212

Chapter 19 Hardware

3.3

IED module arrangement

X1

X2

X3

X4

X5

X6

AIM

AIM

AIM

AIM

COM

BIM

X7

X8

X9

X10

X11

X12

BOM1 BOM2 BOM3 BOM4

X13
PSM
Power supply module

Spare slot

Binary output module 4

Binary output module 3

Binary output module 2

Binary output module 1

Spare slot

Binary input module

Communication mod-

ule

Spare slot

Analogue Input module

Analogue Input module

Analogue Input module

Figure 74 Module arrangement front view, when open the front panel

3.4

The rear view of the protection IED

Test port

X13
PSM

X12

For BIM and BOM

X11

X10

X9

X8

Ethernet ports

X7

X6

X5
COM

X3
AIM

X2
AIM

X1
AIM

Figure 75 Rear view of the protection IED

213

Chapter 19 Hardware

Local human-machine interface


Setting operation and interrogation of numerical protection systems can be
carried out via the integrated membrane keyboard and display panel located
on the front plate. All the necessary operating parameters can be entered and
all the information can be read out from here,e.g. display, main menu, debugging menu. Operation is, additionally, possible via interface socket by
means of a personal computer or similar.

4.1

Human machine interface


Front panel adopts little arc streamline and beelines sculpt, and function keys
for MMI are reasonably distributed in faceplate. Panel layout are shown as
below figures.

214

Chapter 19 Hardware

4
CSC-326

Figure 76 Front panel layout for 8 LEDs

4
CSC-326

Figure 77 Front panel layout for 20 LEDs

4.2

LCD
The member of keyboard and display panel is externally arranged similar to a
pocked calculator.

4.3

Keypad
The keypad is used to monitor and operate the IED. The keypad has the
215

Chapter 19 Hardware
same look and feel in all IEDs in the CSC series. LCD screens and other
details may differ but the way the keys function is identical. The keys used to
operate the IED are described below.
Table 163 function of keys of the keypad
Key
SET

function
SET key:
Enters main menu or sub-menu, and confirms the setting changes

QUIT

QUIT key:

Navigates backward the upper menu.

Cancels current operation and navigates backward the upper


menu.

Returns normal rolling display mode

Locks and unlocks current display in the normal scrolling display


mode; (the locked display mode is indicated by a key type icon
on the upright corner of LCD.)

Right arrow key:

Moves right in menu.

Left arrow key:

Moves left in menu.

Up arrow key:

Moves up in menu

Page up between screens

Increases value of setting.

Down arrow key

Moves down in menu

Page down between screens

Decreases the value of setting.

RESET key:

RESET

4.4

Reset LEDs

Return to normal scrolling display mode directly

Shortcut keys and functional keys


The shortcut keys and functional keys are below the LCD on the front panel. These
keys are designated to execute the frequent menu operations for users convenience.
The keys used to operate the IED are described below.

Table 164 function of Shortcut keys and functional keys


Key
216

function

Chapter 19 Hardware
F1

Reserved

F2
F3

Reserved

F4

Reserved

Plus key:

Reserved

Switch next setting group forward as active setting group meaning


the number of setting group plus one.
_

Minus key
Switch next setting group backward as active setting group , meaning the number of setting group subtracted one.

4.5

LED
The definitions of the LEDs are fixed and descrbed below.
Table 165 Definition of 8 LEDs

No

LED

Color

Description
Steady lighting: Operation normally

Run

Green
Flashing: IED startup
Steady lighting: Alarm II, meaning abnormal situation,
only the faulty function is out of service. Power supply
for tripping output is not blocked.

Alarm

Red
Flashing: Alarm I, meaning severe internal fault, all
protections are out of service. And power supply for
tripping outputs is blocked as well.

The definitions of the LEDs are fixed and described below for 20 LEDs.
Table 166 Definition of 20 LEDs
No

LED

Color

Description
Steady lighting: Operation normally

Run

Green
Flashing: IED startup

11

Alarm

Red

Steady lighting: Alarm II, meaning abnormal situation,


only the faulty function is out of service. Power supply

217

Chapter 19 Hardware
No

LED

Color

Description
for tripping output is not blocked.
Flashing: Alarm I, meaning severe internal fault, all
protections are out of service. And power supply for
tripping outputs is blocked as well.

The other LEDs which are not described above can be configured.

4.6

Front communication port


There is a serial RS232 port on the front plate of all the IEDs. Through this
port, the IED can be connected to the personal computer for setting, testing,
and configuration using the dedicated Sifang software tool.

218

Chapter 19 Hardware

Analog input module

5.1

Introduction
The analogue input module is used to galvanically separate and transform the
secondary currents and voltages generated by the measuring transformers.
There are two types of current transformer: Rated current 5A with linearity
range 50mA150A and rated current 1A with linearity range 100mA30A
(please indicate clearly when order the product).

5.2

Terminals of Analogue Input Module (AIM)


b

b01

a01

b02

a02

b03

a03

b04

a04

b05

a05

b06

a06

b07

a07

b08

a08

b09

a09

b10

a10

b11

a11

b12

a12

Figure 78 Terminals arrangement of AIM E

Table 167 Description of terminals of AIM E


Terminal

Analogue

Remark

219

Chapter 19 Hardware
Input
a01

IA

b01

IA

a02

IB

b02

IB

a03

IC

b03

IC

a04

IN

b04

IN

a05

INM

b05

INM

a06

Null

b06

Null

a07

Null

b07

Null

a08

Null

b08

Null

a09

Null

b09

Null

a10

U4

b10

U4

a11

UB

Star point

b11

UC

Star point

a12

UA

Star point

b12

UN

5.3

Technical data

5.3.1

Internal current transformer


Item

Rated current Ir

Star point

Star point

Star point

Star point

Star point

Star point

Star point

Star point

Star point

Standard

IEC 60255-1

Data
1 or 5 A

Nominal current range

0.05 Ir to 30 Ir

Nominal current range of sensitive

0.005 to 1 A

220

Chapter 19 Hardware
CT
0.1 VA at Ir = 1 A;

Power consumption (per phase)

0.5 VA at Ir = 5 A
0.5 VA for sensitive CT

IEC 60255-1

100 Ir for 1 s

IEC 60255-27

4 Ir continuous

Thermal overload capability for

IEC 60255-27

100 A for 1 s

sensitive CT

DL/T 478-2001

3 A continuous

Thermal overload capability

5.3.2

Internal voltage transformer


Item

Rated voltage Vr (ph-ph)

Standard

IEC 60255-1

Nominal range (ph-e)


Power consumption at Vr = 110 V

Data
100 V /110 V
0.4 V to 120 V

IEC 60255-27

0.1 VA per phase

DL/T 478-2001
Thermal overload capability

IEC 60255-27

2 Vr, for 10s

(phase-neutral voltage)

DL/T 478-2001

1.5 Vr, continuous

221

Chapter 19 Hardware

Communication module

6.1

Introduction
The communication module performs communication between the internal
protection system and external equipments such as HMI, engineering workstation, substation automation system, RTU, etc., to transmit remote metering,
remote signaling, SOE, event reports and record data.
Up to 3 channels isolated electrical or optical Ethernet ports and up to 2
channels RS485 serial communication ports can be provided in communication module to meet the communication demands of different substation automation system and RTU at the same time.
The time synchronization port is equipped, which can work in pulse mode or
IRIG-B mode. SNTP mode can be applied through communication port.
In addition, a series printer port is also reserved.

6.2

Substaion communication port

6.2.1

RS232 communication ports


There is a serial RS232 port on the front plate of all the IEDs. Through this
port, the IED can be connected to the personal computer for setting, testing,
and configuration using the dedicated Sifang software tool.

6.2.2

RS485 communication ports


Up to 2 isolated electrical RS485 communication ports are provided to connect with substation automation system. These two ports can work in parallel
for IEC60870-5-103.

6.2.3

Ethernet communication ports


Up to 3 electrical or optical Ethernet communication ports are provided to
connect with substation automation system. Two out of these three ports can

222

Chapter 19 Hardware
work in parallel for protocol, IEC61850 or IEC60870-5-103.

6.2.4

Time synchronization port


All IEDs feature a permanently integrated electrical time synchronization port.
It can be used to feed timing telegrams in IRIG-B or pulse format into the
IEDs via time synchronization receivers. The IED can adapt the second or
minute pulse in the pulse mode automatically.
Meanwhile, SNTP network time synchronization can also be applied.

6.3

Terminals of Communication Module


01
02

Ethernet port A

03
04
05
06
07

Ethernet port B

08
09
10
11

Ethernet port C

12
13
14
15
16

Figure 79 Terminals arrangement of COM


Table 168 Definition of terminals of COM
Terminal

Definition

01

Null

02

Null

03

Null

04

Null

223

Chapter 19 Hardware
05

Optional RS485 port - 2B

06

Optional RS485 port - 2A

07

Optional RS485 port - 1B

08

Optional RS485 port - 1A

09

Time synchronization

10

Time synchronization GND

11

Null

12

Null

13

Null

14

Null

15

Null

16

Null

Ethernet
Port A

Optional optical fiber or RJ45


port for station automation system

Ethernet
Port B

Optional optical fiber or RJ45


port for station automation system

Ethernet
Port C

Optional optical fiber or RJ45


port for station automation system

6.4

Operating reports
Information

Description

DI Comm Fail

DI communication error

DO Comm Fail

DO communication error

6.5

Technical data

6.5.1

Front communication port


Item

Data

Number

Connection

Isolated, RS232; front panel,


9-pin subminiature connector, for software tools

224

Chapter 19 Hardware
Communication speed

9600 baud

Max. length of communication cable

15 m

6.5.2

RS485 communication port


Item

Data

Number

0 to 2

Connection

2-wire connector
Rear port in communication module

Max. length of communication cable

1.0 km

Test voltage

500 V AC against earth

For IEC 60870-5-103 protocol


Communication speed

Factory setting 9600 baud,


Min. 1200 baud, Max. 19200 baud

6.5.3

Ethernet communication port


Item

Data
Electrical communication port

Number

0 to 3

Connection

RJ45 connector
Rear port in communication module

Max. length of communication cable

100m

For IEC 61850 protocol


Communication speed

100 Mbit/s

For IEC 60870-5-103 protocol


Communication speed

100 Mbit/s
Optical communication port ( optional )

Number

0 to 2

Connection

SC connector
Rear port in communication module

Optical cable type

Multi-mode

Max. length of communication cable

2.0km

IEC 61850 protocol


Communication speed

100 Mbit/s

IEC 60870-5-103 protocol


Communication speed

100 Mbit/s

225

Chapter 19 Hardware
6.5.4

Time synchronization
Item

Data

Mode

Pulse mode

IRIG-B signal format

IRIG-B000

Connection

2-wire connector
Rear port in communication module

Voltage levels

226

differential input

Chapter 19 Hardware

Binary input module

7.1

Introduction
The binary input module is used to connect the input signals and alarm signals such as the auxiliary contacts of the circuit breaker (CB), etc.
The negative terminal of power supply for BI module, 220V or 110V, should
be connected to the terminal.

7.2

Terminals of Binary Input Module (BIM)


c

c02

a02

c04

a04

c06

a06

c08

a08

c10

a10

c12

a12

c14

a14

c16

a16

c18

a18

c20

a20

c22

a22

c24

a24

c26

a26

c28

a28

c30

a30

c32

DC -

DC -

a32

Figure 80: Terminals arrangement of BIM A

227

Chapter 19 Hardware
Table 169 Definition of terminals of BIM A

228

Terminal

Definition

Remark

a02

BI1

BI group 1

c02

BI2

BI group 2

a04

BI3

BI group 1

c04

BI4

BI group 2

a06

BI5

BI group 1

c06

BI6

BI group 2

a08

BI7

BI group 1

c08

BI8

BI group 2

a10

BI9

BI group 1

c10

BI10

BI group 2

a12

BI11

BI group 1

c12

BI12

BI group 2

a14

BI13

BI group 1

c14

BI14

BI group 2

a16

BI15

BI group 1

c16

BI16

BI group 2

a18

BI17

BI group 1

c18

BI18

BI group 2

a20

BI19

BI group 1

c20

BI20

BI group 2

a22

BI21

BI group 1

c22

BI22

BI group 2

a24

BI23

BI group 1

c24

BI24

BI group 2

a26

BI25

BI group 1

c26

BI26

BI group 2

a28

BI27

BI group 1

c28

BI28

BI group 2

a30

BI29

BI group 1

c30

BI30

BI group 2

a32

DC - Input

Common terminal of BI group 1

c32

DC - Input

Common terminal of BI group 2

Chapter 19 Hardware
7.3

Technical data
Item

Input voltage range

Standard
IEC60255-1

Data
110/125 V DC
220/250 V DC

Threshold1: guarantee oper-

IEC60255-1

ation
Threshold2: uncertain opera-

77V, for 110V/125V DC


IEC60255-1

tion
Response time/reset time

154V, for 220/250V DC

132V, for 220/250V DC;


66V, for 110V/125V DC

IEC60255-1

Software provides de-bounce


time

Power consumption, energized

IEC60255-1

Max. 0.2 W/input, 24V DC


Max. 0.5 W/input, 110V DC
Max. 1 W/input, 220V DC

229

Chapter 19 Hardware

Binary output module

8.1

Introduction
The binary output modules mainly provide tripping output contacts, initiating
output contacts and signaling output contacts. All the tripping output relays
have contacts with a high switching capacity and are blocked by protection
startup elements.
Each output relay can be configured to satisfy the demands of users.

8.2

Terminals of Binary Output Module (BOM)

8.2.1

Binary Output Module A


The module provides 16 output relays for tripping or initiating, with total 16
contacts.

230

Chapter 19 Hardware
R
1

R
3

R
5

R
7

R
9

R
11

R
13

R
15

c02

a02

c04

a04

c06

a06

c08

a08

c10

a10

c12

a12

c14

a14

c16

a16

c18

a18

c20

a20

c22

a22

c24

a24

c26

a26

c28

a28

c30

a30

c32

a32

R
2

R
4

R
6

R
8

R
10

R
12

R
14

R
16

Figure 81 Terminals arrangement of BOM A

231

Chapter 19 Hardware
Table 170 Definition of terminals of BOM A

232

Terminal

Definition

Related relay

a02

Trip contact 1-0

Output relay 1

c02

Trip contact 1-1

Output relay 1

a04

Trip contact 2-0

Output relay 2

c04

Trip contact 2-1

Output relay 2

a06

Trip contact 3-0

Output relay 3

c06

Trip contact 3-1

Output relay 3

a08

Trip contact 4-0

Output relay 4

c08

Trip contact 4-1

Output relay 4

a10

Trip contact 5-0

Output relay 5

c10

Trip contact 5-1

Output relay 5

a12

Trip contact 6-0

Output relay 6

c12

Trip contact 6-1

Output relay 6

a14

Trip contact 7-0

Output relay 7

c14

Trip contact 7-1

Output relay 7

a16

Trip contact 8-0

Output relay 8

c16

Trip contact 8-1

Output relay 8

a18

Trip contact 9-0

Output relay 9

c18

Trip contact 9-1

Output relay 9

a20

Trip contact 10-0

Output relay 10

c20

Trip contact 10-1

Output relay 10

a22

Trip contact 11-0

Output relay 11

c22

Trip contact 11-1

Output relay 11

a24

Trip contact 12-0

Output relay 12

c24

Trip contact 12-1

Output relay 12

a26

Trip contact 13-0

Output relay 13

c26

Trip contact 13-1

Output relay 13

a28

Trip contact 14-0

Output relay 14

c28

Trip contact 14-1

Output relay 14

a30

Trip contact 15-0

Output relay 15

c30

Trip contact 15-1

Output relay 15

a32

Trip contact 16-0

Output relay 16

c32

Trip contact 16-1

Output relay 16

Chapter 19 Hardware
Binary Output Module C

8.2.2

The module provides 16 output relays for signal, with total 19 contacts.
R
4

R
5

R
1

R
2

R
3

R
6

R
7

c02

a02

c04

a04

c06

a06

c08

a08

c10

a10

c12

a12

c14

a14

c16

a16

c18

a18

c20

a20

c22

a22

c24

a24

c26

a26

c28

a28

c30

a30

c32

a32

R
8

R
9

R
10

R
11

R
12

R
13

R
14

R
15

R
16

Figure 82 Terminals arrangement of BOM C


Table 171 Definition of terminals of BOM C
Terminal

Definition

a02

Signal 1-0, Common terminal of signal contact group 1

c02

Signal 2-0, Common terminal of signal contact group 2

Related relay

233

Chapter 19 Hardware

8.3

a04

Signal contact 1-1

Output relay 1

c04

Signal contact 2-1

Output relay 1

a06

Signal contact 1-2

Output relay 2

c06

Signal contact 2-2

Output relay 2

a08

Signal contact 1-3

Output relay 3

c08

Signal contact 2-3

Output relay 3

a10

Signal 3-0, Common terminal of signal contact group 3

c10

Signal 4-0, Common terminal of signal contact group 4

a12

Signal contact 3-1

Output relay 4

c12

Signal contact 4-1

Output relay 7

a14

Signal contact 3-2

Output relay 5

c14

Signal contact 4-2

Output relay 6

a16

Signal contact 5-0

Output relay 8

c16

Signal contact 5-1

Output relay 8

a18

Signal contact 6-0

Output relay 9

c18

Signal contact 6-1

Output relay 9

a20

Signal contact 7-0

Output relay 10

c20

Signal contact 7-1

Output relay 10

a22

Signal contact 8-0

Output relay 11

c22

Signal contact 8-1

Output relay 11

a24

Signal contact 9-0

Output relay 12

c24

Signal contact 9-1

Output relay 12

a26

Signal contact 10-0

Output relay 13

c26

Signal contact 10-1

Output relay 13

a28

Signal contact 11-0

Output relay 14

c28

Signal contact 11-1

Output relay 14

a30

Signal contact 12-0

Output relay 15

c30

Signal contact 12-1

Output relay 15

a32

Signal contact 13-0

Output relay 16

c32

Signal contact 13-1

Output relay 16

Technical data
Item

234

Standard

Data

Chapter 19 Hardware
Item

Standard

Data

Max. system voltage

IEC60255-1

250V DC/AC

Current carrying capacity

IEC60255-1

5 A continuous,
42A1s ON, 9s OFF

Making capacity

IEC60255-1

1100 W(DC) at inductive load


with L/R>40 ms
1000 VA(AC)

Breaking capacity

IEC60255-1

1000 cycles
DC220V, 0.15A t=L/R40 ms
DC110V, 0.30A t=L/R40 ms

Unloaded mechanical endur-

IEC60255-1

ance
Specification state verification

50,000,000 cycles (3 Hz
switching frequency)

IEC60255-1

UL/CSATV

IEC60255-23
IEC61810-1
Contact circuit resistance

IEC60255-1

measurement

IEC60255-23

30m

IEC61810-1
Open Contact insulation test

IEC60255-1

(AC Dielectric strength)

IEC60255-27

Maximum temperature of parts

IEC60255-1

AC1000V 1min

55

and materials

235

Chapter 19 Hardware

Power supply module

9.1

Introduction
The power supply module is used to provide the correct internal voltages and
full isolation between the terminal and the battery system. Its power input is
DC 220V or 110V (according to the order code), and its outputs are five
groups of power supply.
(1) 24V two groups provided:
nary inputs of the CPU module
(2) 12V:

Power for inputs of the corresponding bi-

Power for A/D

(3) + 5V: Power for all micro-chips

9.2

Terminals of Power Supply Module (PSM)


c
c02
c04

a
DC 24V +
OUTPUTS

a08

c08
DC 24V OUTPUTS

a10

c12

a12

c14

a14

c16

a16

c18

a18

c20
c22

AUX.DC +
INPUT

c24
c26
c28

236

a04
a06

c06

c10

a02

a20
a22
a24

AUX. DC INPUT

a26
a28

c30

a30

c32

a32

Chapter 19 Hardware
Figure 83 Terminals arrangement of PSM
Table 172 Definition of terminals of PSM
Terminal

Definition

a02

AUX.DC 24V+ output 1

c02

AUX.DC 24V+ output 2

a04

AUX.DC 24V+ output 3

c04

AUX.DC 24V+ output 4

a06

Isolated terminal, not wired

c06

Isolated terminal, not wired

a08

AUX.DC 24V- output 1

c08

AUX.DC 24V- output 2

a10

AUX.DC 24V- output 3

c10

AUX.DC 24V- output 4

a12

AUX.DC 24V- output 5

c12

AUX.DC 24V- output 6

a14

Alarm contact A1, for AUX.DC power input failure

c14

Alarm contact A0, for AUX.DC power input failure

a16

Alarm contact B1, for AUX.DC power input failure

c16

Alarm contact B0, for AUX.DC power input failure

a18

Isolated terminal, not wired

c18

Isolated terminal, not wired

a20

AUX. power input 1, DC +

c20

AUX. power input 2, DC +

a22

AUX. power input 3, DC +

c22

AUX. power input 4, DC +

a24

Isolated terminal, not wired

c24

Isolated terminal, not wired

a26

AUX. power input 1, DC -

c26

AUX. power input 2, DC -

a28

AUX. power input 3, DC -

c28

AUX. power input 4, DC -

a30

Isolated terminal, not wired

c30

Isolated terminal, not wired

a32

Terminal for earthing

237

Chapter 19 Hardware
c32

9.3

Terminal for earthing

Technical data
Item

Data

Rated auxiliary voltage Vaux

110~250V DC

Permissible tolerance

%20 Uaux
Power consumption

Normal operation

30 W

Tripping condition

50 W

238

Chapter 19 Hardware

10

Techinical data

10.1

Basic data

10.1.1

Frequency
Item

Data

System rated frequency

10.1.2

50 Hz or 60Hz

Internal current transformer


Item

Data

Rated current Ir

1 or 5 A

Nominal current range

(0.05 20)x Ir

Power consumption (per phase)

0.1 VA at Ir = 1 A;
0.5 VA at Ir = 5 A

Thermal overload capability

100 x Ir for 1 s
4 x Ir continuous

10.1.3

Internal voltage transformer


Item

Data

Rated voltage Vr (ph-ph)

100-120

Nominal range (ph-e)

0.4 V to 120 V

Power consumption at Vr = 110 V

0.1 VA per phase

Thermal overload capability (phase-neutral

2Vr, for 10s

voltage)

1.5Vr, continuous

10.1.4

Auxiliary voltage
Item

Standard

Data

Rated auxiliary voltage Vaux

IEC60255-1

110 to 250V DC

Permissible tolerance

IEC60255-1

%20 Uaux

239

Chapter 19 Hardware
Item

Standard

Power consumption at quies-

Data

IEC60255-1

50 W

IEC60255-1

60 W

IEC60255-1

T 10 ms/I 25 A

cent state
Power consumption at maximum load
Inrush Current

10.1.5

Binary inputs
Item

Input voltage range

Standard
IEC60255-1

Data
110/125 V DC
220/250 V DC

Threshold1: guarantee oper-

IEC60255-1

ation

154V, for 220/250V DC


77V, for 110V/125V DC

Threshold2: uncertain opera-

IEC60255-1

tion

132V, for 220/250V DC;


66V, for 110V/125V DC

Response time/reset time

IEC60255-1

Software provides de-bounce


time

Power consumption, ener-

IEC60255-1

gized

Max. 0.2 W/input, 24V DC


Max. 0.5 W/input, 110V DC
Max. 1 W/input, 220V DC

10.1.6

Binary outputs
Item

Standard

Data

Max. system voltage

IEC60255-1

250V DC/AC

Current carrying capacity

IEC60255-1

5 A continuous,
42A1s ON, 9s OFF

Making capacity

IEC60255-1

1100 W(DC) at inductive load


with L/R>40 ms
1000 VA(AC)

Breaking capacity

IEC60255-1

1000 cycles
DC220V, 0.15A t=L/R40 ms
DC110V, 0.30A t=L/R40 ms

Unloaded mechanical endur-

IEC60255-1

ance
Specification state verification

switching frequency)
IEC60255-1
IEC60255-23

240

50,000,000 cycles (3 Hz

UL/CSATV

Chapter 19 Hardware
Item

Standard

Data

IEC61810-1

Contact circuit resistance

IEC60255-1

measurement

IEC60255-23

30m

IEC61810-1
Open Contact insulation test

IEC60255-1

(AC Dielectric strength)

IEC60255-27

Maximum temperature of parts

IEC60255-1

AC1000V 1min

55

and materials

10.2

Type tests

10.2.1

Product safety-related Tests


Item

Standard

Data

Over voltage category

IEC60255-27

Category III

Pollution degree

IEC60255-27

Degree 2

Insulation

IEC60255-27

Basic insulation

Degree of protection (IP)

IEC60255-27

Front plate: IP40

IEC 60529

Rear, side, top and bottom: IP


30

Power frequency high voltage

IEC 60255-5

2KV, 50Hz

withstand test

ANSI C37.90

2.8kV DC

GB/T 15145-2001

between the following circuits:

DL/T 478-2001

auxiliary power supply


CT / VT inputs
binary inputs
binary outputs
case earth
500V, 50Hz
between the following circuits:
Communication ports to
case earth
time synchronization terminals to case earth

Impulse voltage test

IEC60255-5
IEC 60255-27

5kV (1.2/50s, 0.5J)


if Ui63V
241

Chapter 19 Hardware
Item

Standard

Data

ANSI C37.90

1kV if Ui<63V

GB/T 15145-2001

Tested between the following

DL/T 478-2001

circuits:
auxiliary power supply
CT / VT inputs
binary inputs
binary outputs
case earth
Note: Ui: Rated voltage

Insulation resistance

100 M at 500 VDC

IEC60255-5
IEC 60255-27
ANSI C37.90
GB/T 15145-2001
DL/T 478-2001

Protective bonding resistance

IEC60255-27

0.1

Fire withstand/flammability

IEC60255-27

Class V2

10.2.2

Electromagnetic immunity tests


Item

1 MHz burst immunity test

Standard

Data

IEC60255-22-1

class III

IEC60255-26

2.5 kV CM ; 1 kV DM

IEC61000-4-18

Tested on the following circuits:

ANSI/IEEE C37.90.1

auxiliary power supply


CT / VT inputs
binary inputs
binary outputs
1 kV CM ; 0 kV DM
Tested on the following circuits:
communication ports

Electrostatic discharge

IEC 60255-22-2

Level 4

IEC 61000-4-2

8 kV contact discharge;
15 kV air gap discharge;
both polarities; 150 pF; Ri = 330

Radiated electromagnetic field


disturbance test

IEC 60255-22-3

frequency sweep:
80 MHz 1 GHz; 1.4 GHz 2.7 GHz
spot frequencies:

242

Chapter 19 Hardware
Item

Standard

Data
80 MHz; 160 MHz; 380 MHz;
450 MHz; 900 MHz; 1850 MHz;
2150 MHz
10 V/m
AM, 80%, 1 kHz

Radiated electromagnetic field

IEC 60255-22-3

disturbance test

pulse-modulated
10 V/m, 900 MHz; repetition rate
200 Hz, on duration 50 %

Electric fast transient/burst im-

IEC 60255-22-4,

class A, 4KV

munity test

IEC 61000-4-4

Tested on the following circuits:

ANSI/IEEE C37.90.1

auxiliary power supply


CT / VT inputs
binary inputs
binary outputs
class A, 2KV
Tested on the following circuits:
communication ports

Surge immunity test

IEC 60255-22-5

4.0kV L-E

IEC 61000-4-5

2.0kV L-L
Tested on the following circuits:
auxiliary power supply
CT / VT inputs
binary inputs
binary outputs
2.0kV L-E
Tested on the following circuits:
communication ports

Conduct immunity test

IEC 60255-22-6

frequency sweep: 150 kHz 80

IEC 61000-4-6

MHz
spot frequencies: 27 MHz and
68 MHz
10 V
AM, 80%, 1 kHz

Power frequency immunity test

IEC60255-22-7

Class A
300 V CM
150 V DM

Power frequency magnetic field

IEC 61000-4-8

test
100 kHz burst immunity test

level 4
30 A/m cont. / 300 A/m 1 s to 3 s

IEC61000-4-18

2.5 kV CM ; 1 kV DM
243

Chapter 19 Hardware
Item

Standard

Data
Tested on the following circuits:
auxiliary power supply
CT / VT inputs
binary inputs
binary outputs
1 kV CM ; 0 kV DM
Tested on the following circuits:
communication ports

10.2.3

DC voltage interruption test


Item

DC voltage dips

Standard
IEC 60255-11

Data
100% reduction 80 ms
60% reduction 200 ms
30% reduction 500 ms

DC voltage interruptions

IEC 60255-11

100% reduction 5 s

DC voltage ripple

IEC 60255-11

15%, twice rated frequency

DC voltage gradual shutdown

IEC 60255-11

60 s shut down ramp

/start-up

5 min power off


60 s start-up ramp

DC voltage reverse polarity

10.2.4

IEC 60255-11

1 min

Electromagnetic emission test


Item

Radiated emission

Conducted emission

Standard

Data

IEC60255-25

30MHz to 1GHz ( IT device may

CISPR22

up to 5 GHz)

IEC60255-25

0.15MHz to 30MHz

CISPR22

10.2.5

Mechanical tests
Item

Sinusoidal Vibration response


test

Standard
IEC60255-21-1

Data
class 1
10 Hz to 60 Hz: 0.075 mm
60 Hz to 150 Hz: 1 g

244

Chapter 19 Hardware
Item

Standard

Data
1 sweep cycle in each axis
Relay energized

Sinusoidal Vibration endur-

IEC60255-21-1

ance test

class 1
10 Hz to 150 Hz: 1 g
20 sweep cycle in each axis
Relay non-energized

Shock response test

IEC60255-21-2

class 1
5 g, 11 ms duration
3 shocks in both directions of 3
axes
Relay energized

Shock withstand test

IEC60255-21-2

class 1
15 g, 11 ms duration
3 shocks in both directions of 3
axes
Relay non-energized

Bump test

IEC60255-21-2

class 1
10 g, 16 ms duration
1000 shocks in both directions of
3 axes
Relay non-energized

Seismic test

IEC60255-21-3

class 1
X-axis 1 Hz to 8/9 Hz: 7.5 mm
X-axis 8/9 Hz to 35 Hz :2 g
Y-axis 1 Hz to 8/9 Hz: 3.75 mm
Y-axis 8/9 Hz to 35 Hz :1 g
1 sweep cycle in each axis,
Relay energized

10.2.6

Climatic tests
Item

Cold test - Operation

Standard
IEC60255-27

Data
-10C, 16 hours, rated load

IEC60068-2-1
Cold test Storage

IEC60255-27

-25C, 16 hours

IEC60068-2-1
Dry heat test Operation

[IEC60255-27

+55C, 16 hours, rated load

IEC60068-2-2

245

Chapter 19 Hardware
Item

Standard

Dry heat test Storage

IEC60255-27

Data
+70C, 16 hours

IEC60068-2-2
Change of temperature
Damp heat static test
Damp heat cyclic test

10.2.7

IEC60255-27

Test Nb, figure 2, 5 cycles

IEC60068-2-14

-10C / +55C

IEC60255-27

+40C, 93% r.h. 10 days, rated

IEC60068-2-78

load

IEC60255-27

+55C, 93% r.h. 6 cycles, rated

IEC60068-2-30

load

CE Certificate
Item

EN 61000-6-2 and EN61000-6-4 (EMC

EMC Directive

Council Directive 2004/108/EC)

Low voltage directive

10.3

Data

EN 60255-27 (Low-voltage directive 2006/95


EC).

IED design
Item

Data

Case size

4U19inch

Weight

8kg

246

Chapter 20 Appendix

Chapter 20 Appendix

247

Chapter 20 Appendix

General setting list

1.1

Function setting list

Setting

Unit

HV Wind Conn/Y

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
0

Connection for HV winding,


0:wye connection, 1:delta
connection

MV Wind Conn/Y

Connection for MV winding,


0:wye connection, 1:delta
connection

LV Wind Conn/Y

Connection for LV winding,


0:wye connection, 1:delta
connection

Vet Grp Angle

MVA

1.000

3000.

120.0

Vector Group Angle( VET


GRP ANGLE)

SN

kV

1.000

1000.

220.0

Capacity of the transformer

HV VT Ratio

MVA

1.000

9999.

2200.0

Voltage transformer(VT) Ratio in HV side

50.00

9999.

1200.0

HV CT Pri

CT Primary(PRI) current in
HV side

1.000

5.000

1.0

HV CT Sec

CT Secondary(SEC) current
in HV side

HV Voltage Chan

Sel
MV Voltage Chan
Sel

HV voltage channel location


MV voltage channel location

50.00

9999.

1200.0

HV NCT Pri(REF)

Neutral CT (NCT) Primary(PRI) current in HV side


for REF

1.000

5.000

1.0

HV NCT Sec(REF)

Neutral CT (NCT) Secondary(SEC) current in HV side


for REF

HV NCT Pri(BU)

248

50.00

9999.

1200.0

Neutral CT (NCT) Prima-

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
ry(PRI) current in HV side
for backup protection

1.000

5.000

1.0

HV NCT Sec(BU)

Neutral CT (NCT) Secondary(PRI) current in HV side


for backup protection

kV

1.000

1000.

110.0

MV UN

Nominal voltage (UN) in


Middle voltage (MV)side

1.000

9999.

1100.0

MV VT Ratio

Voltage transformer(VT) Ratio in MV side

50.00

9999.

1200.0

MV CT Pri

CT Primary(PRI) current in
MV side

1.000

5.000

1.0

MV CT Sec

CT Secondary(SEC) current
in MV side

50.00

9999.

1200.0

MV NCT Pri(REF)

Neutral CT (NCT) Primary(PRI) current in MV side


for REF

1.000

5.000

1.0

MV NCT Sec(REF)

Neutral CT (NCT) Secondary(SEC) current in MV


side for REF

50.00

9999.

1200.0

MV NCT Pri(BU)

Neutral CT (NCT) Primary(PRI) current in MV side


for backup protection

1.000

5.000

1.0

MV NCT Sec(BU)

Neutral CT (NCT) Secondary(PRI) current in MV side


for backup protection

kV

1.000

1000.

10.50

LV UN

voltage (LV)side
1.000

9999.

105.0

LV VT Ratio
A

50.00

9999.

3000.0

CT Primary(PRI) current in
LV side

1.000

5.000

1.0

LV CT Sec

CT Secondary(SEC) current
in LV side

1.000

5.000

Delta
HV Rated Cur Pri

Voltage transformer(VT) Ratio in LV side

LV CT Pri

LV Sec Inside

Nominal voltage (UN) in Low

1.0

CT Secondary(SEC) current in LV inside delta

9999

Rated primary current for


249

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
HV side (calculated value,
read only)

9999

Rated secondary current for

HV Rated Cur Sec

HV side (calculated value,


read only)
0

9999

HV ratio factor for differen-

Ratio Factor KTAH

tial protection (calculated


value, read only)
0

9999

MV ratio factor for differen-

Ratio Factor KTAM

tial protection (calculated


value, read only)
0

9999

LV ratio factor for differential

Ratio Factor KTAL

protection (calculated
value, read only)
0

9999

HV ratio factor, with zero-sequence current calcu-

Ratio REF KTAH

lated, for REF protection


(calculated value, read
only)
0

9999

HV ratio factor with zero-sequence current directly

Ratio REF KNH

measured, for REF protection (calculated value,


read only)
0

9999

MV ratio factor, with zero-sequence current calcu-

Ratio REF KTAM

lated, for REF protection


(calculated value, read
only)
0

9999

MV ratio factor with zero-sequence current directly

Ratio REF KNM

measured, for REF protection (calculated value,


read only)
A

I_Inst Diff

250

0.5Ir

20Ir

20

Instantaneous Differential
(ID>>) current setting

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.08Ir

4Ir

Default
setting
(Ir:5A/1

Description

A)
2.1

I_Percent Diff

Percentage Differential
(ID>) current setting

0.1Ir

Ir

I_ResPoint1 Diff

The 1st breakpoint restraint


current (IR1)

0.1Ir

10Ir

I_ResPoint2 Diff

The 2nd breakpoint restraint current (IR2)

Slope1_Diff

0.2

0.2

the 1st slope

Slope2_Diff

0.2

0.7

0.5

the 2nd slope

Slope3_Diff

0.25

0.95

0.7

the 3rd slope

Ratio_2nd Harm

0.05

0.80

0.15

2nd harmonic(HAR) ratio

0.05

0.80

0.35

3rd / 5th harmonic(HAR)

Ratio_3/5th Harm

ratio
s

20

20

Within the delay 2nd harmonic block all three phas-

T_2nd Harm Block

es. After the delay, then


only the local phase is
blocked.
s

20

20

Within the delay 5th harmonic block all three phas-

T_3/5th Harm

es. After the delay, then

Block

only the local phase is


blocked.
A

0.08Ir

2Ir

HV 3I0_REF

Current setting for HV Restricted Earth Fault protection

0.2

0.95

0.5

HV Slope_REF

Slope setting for HV Restricted Earth Fault protection

60

0.03

HV T_REF Trip

trip time setting


A

0.08Ir

2Ir

HV 3I0_REF Alarm

HV Restricted Earth Fault


alarm current setting

60

0.03

HV T_REF Alarm
MV 3I0_REF

HV Restricted Earth Fault

HV Restricted Earth Fault


alarm time setting

0.08Ir

2Ir

Current setting for MV Re-

251

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
stricted Earth Fault protection

0.2

0.95

0.5

MV Slope_REF

Slope setting for MV Restricted Earth Fault protection

60

0.03

MV T_REF Trip
MV 3I0_REF

MV Restricted Earth Fault


trip time setting

0.08Ir

2Ir

Alarm

MV Restricted Earth Fault


alarm current setting

60

0.03

MV T_REF Alarm

MV Restricted Earth Fault


alarm time setting

0.08Ir

2Ir

LV 3I0_REF

Current setting for LV Restricted Earth Fault protection

0.2

0.95

0.5

LV Slope_REF

Slope setting for LV Restricted Earth Fault protection

60

0.03

LV T_REF Trip

trip time setting


A

0.08Ir

2Ir

LV 3I0_REF Alarm
s

60

0.03

40

130

57.3

Nominal phase voltage in


HV side

1.5

1.1

V/F_Definite Alarm

Alarming setting of
volt/hertz

0.1

9999

10

T_Definite Alarm

Timer setting for volt/hertz


alarming stage

1.5

1.2

V/F_Definite Trip

Tripping setting of definite


volt/hertz stage

0.1

9999

T_Definite Trip

Timer setting for definite


volt/hertz stage

0.1

9999

10

V/F=1.05

252

LV Restricted Earth Fault


alarm time setting

Reference Voltage

T2_Inverse

LV Restricted Earth Fault


alarm current setting

LV T_REF Alarm

T1_Inverse

LV Restricted Earth Fault

Timer setting for


volt/hertz=1.05

0.1

9999

90

Timer setting for

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1
A)

V/F=1.10
T3_Inverse

volt/hertz=1.10
s

0.1

9999

80

V/F=1.15
T4_Inverse

0.1

9999

70

0.1

9999

60

0.1

9999

50

0.1

9999

45

0.1

9999

40

Timer setting for


volt/hertz=1.40

0.1

9999

35

V/F=1.45
T10_Inverse

Timer setting for


volt/hertz=1.35

V/F=1.40
T9_Inverse

Timer setting for


volt/hertz=1.30

V/F=1.35
T8_Inverse

Timer setting for


volt/hertz=1.25

V/F=1.30
T7_Inverse

Timer setting for


volt/hertz=1.20

V/F=1.25
T6_Inverse

Timer setting for


volt/hertz=1.15

V/F=1.20
T5_Inverse

Description

Timer setting for


volt/hertz=1.45

0.1

9999

30

V/F=1.50

Timer setting for


volt/hertz=1.50

0.1

9999

25

T_Cool Down

Cool down time delay for


overexcitation protection

0.05Ir

20Ir

HV I_OC1

HV overcurrent (O/C) current setting for Stage 1

60

60

HV T_OC1

Time setting for HV OC,


Stage 1

0.05Ir

20Ir

HV I_OC2

HV overcurrent (O/C) current setting for Stage 2

60

60

HV T_OC2

Time setting for HV OC,


Stage 2

HV Curve_OC Inv

12

Ref to IEC and ANSI


Curves

0.05Ir

20Ir

HV I_OC Inv

Curves
0.05

999

HV K_OC Inv

Ref to IEC and ANSI


Curves

s
HV A_OC Inv

Ref to IEC and ANSI

200

0.14

Ref to IEC and ANSI


Curves

253

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

60

Default
setting
(Ir:5A/1

Description

A)
0

HV B_OC Inv

Ref to IEC and ANSI


Curves

10

0.02

HV P_OC Inv

Ref to IEC and ANSI


Curves

90

45

HV Angle_OC

The angle setting for voltage ahead of current.

0.25Ir

20Ir

The maximum 1st

HV

-harmonic current setting to

Imax_2H_UnBlk

remove the inrush block, in


HV O/C protection
0.07

0.5

0.2

HV Ratio_I2/I1

Inrush 2nd harmonic ratio


setting for blocking HV O/C
protection

60

20

HV T2h_Cross_Blk

Inrush 2nd harmonic


cross-block time for HV O/C
protection

0.05Ir

20Ir

MV I_OC1

MV overcurrent (O/C) current setting for Stage 1

60

60

MV T_OC1

Time setting for MV OC,


Stage 1

0.05Ir

20Ir

MV I_OC2

MV overcurrent (O/C) current setting for Stage 2

60

60

MV T_OC2

Time setting for MV OC,


Stage 2

MV Curve_OC Inv

12

Ref to IEC and ANSI


Curves

0.05Ir

20Ir

MV I_OC Inv

Curves
0.05

999

MV K_OC Inv
s

200

0.14

Ref to IEC and ANSI


Curves

60

MV B_OC Inv

Ref to IEC and ANSI


Curves

254

Ref to IEC and ANSI


Curves

MV A_OC Inv

MV P_OC Inv

Ref to IEC and ANSI

10

0.02

Ref to IEC and ANSI


Curves

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

90

Default
setting
(Ir:5A/1

Description

A)
45

MV Angle_OC

The angle setting for voltage ahead of current.

0.25Ir

20Ir

The maximum 1st

MV

-harmonic current setting to

Imax_2H_UnBlk

remove the inrush block, in


MV O/C protection
0.07

0.5

0.2

MV Ratio_I2/I1

Inrush 2nd harmonic ratio


setting for blocking MV O/C
protection

60

20

MV

Inrush 2nd harmonic


cross-block time for MV O/C

T2h_Cross_Blk

protection
A

0.05Ir

20Ir

LV I_OC1

LV overcurrent (O/C) current setting for Stage 1

60

60

LV T_OC1

Time setting for LV OC,


Stage 1

0.05Ir

20Ir

LV I_OC2

LV overcurrent (O/C) current setting for Stage 2

60

60

LV T_OC2

Time setting for LV OC,


Stage 2

MV Curve_OC Inv

12

Ref to IEC and ANSI


Curves

0.05Ir

20Ir

LV I_OC Inv

Curves
0.05

999

LV K_OC Inv
s

200

0.14

Ref to IEC and ANSI


Curves

60

LV B_OC Inv

Ref to IEC and ANSI


Curves

10

0.02

LV P_OC Inv

Ref to IEC and ANSI


Curves

90

45

LV Angle_OC

Imax_2H_UnBlk

Ref to IEC and ANSI


Curves

LV A_OC Inv

LV

Ref to IEC and ANSI

The angle setting for voltage ahead of current.

0.25Ir

20Ir

The maximum 1st


-harmonic current setting to
255

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
remove the inrush block, in
LV O/C protection

0.07

0.5

0.2

LV Ratio_I2/I1

Inrush 2nd harmonic ratio


setting for blocking LV O/C
protection

60

20

LV T2h_Cross_Blk

Inrush 2nd harmonic


cross-block time for LV O/C
protection

0.05Ir

20Ir

HV 3I0_EF1

HV earth fault (E/F) protection current setting for Stage


1

60

60

HV T_EF1

Time setting for HV E/F,


Stage 1

0.05Ir

20Ir

HV 3I0_EF2

HV earth fault (E/F) current


setting for Stage 2

60

60

HV T_EF2

Time setting for HV E/F,


Stage 2

12

HV Curve_EF Inv

Ref to IEC and ANSI


Curves

0.05Ir

20Ir

1.2

HV 3I0_EF Inv

Ref to IEC and ANSI


Curves

0.05

999

HV K_EF Inv

Ref to IEC and ANSI


Curves

200

0.14

HV A_EF Inv

Ref to IEC and ANSI


Curves

60

HV B_EF Inv

Ref to IEC and ANSI


Curves

10

0.02

HV P_EF Inv

Ref to IEC and ANSI


Curves

90

45

HV Angle_EF

The angle setting for voltage ahead of current.

0.25Ir

20Ir

HV

The maximum 1st


-harmonic current setting to

Imax_2H_UnBlk_E

remove the inrush block, in

HV EF protection
HV Ratio_I2/I1_EF
256

0.07

0.5

0.2

The maximum 1st

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
-harmonic current setting to
remove the inrush block, in
HV EF protection

0.05Ir

20Ir

MV 3I0_EF1

MV earth fault (E/F) protection current setting for Stage


1

60

60

MV T_EF1

Time setting for MV E/F,


Stage 1

0.05Ir

20Ir

MV 3I0_EF2

MV earth fault (E/F) current


setting for Stage 2

60

60

MV T_EF2

Time setting for MV E/F,


Stage 2

12

MV Curve_EF Inv

Ref to IEC and ANSI


Curves

0.05Ir

20Ir

MV 3I0_EF Inv

Ref to IEC and ANSI


Curves

0.05

999

MV K_EF Inv

Ref to IEC and ANSI


Curves

200

0.14

MV A_EF Inv

Ref to IEC and ANSI


Curves

60

MV B_EF Inv

Ref to IEC and ANSI


Curves

10

0.02

MV P_EF Inv

Ref to IEC and ANSI


Curves

90

45

MV Angle_EF

The angle setting for voltage ahead of current.

0.25Ir

20Ir

MV

The maximum 1st


-harmonic current setting to

Imax_2H_UnBlk_E

remove the inrush block, in

MV E/F protection
0.07

0.5

0.2

MV Ratio_I2/I1_EF

Inrush 2nd harmonic ratio


setting for blocking MV E/F
protection

A
LV 3I0_EF1

0.05Ir

20Ir

LV earth fault (E/F) protection current setting for Stage


1
257

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

60

Default
setting
(Ir:5A/1

Description

A)
60

LV T_EF1

Time setting for LV E/F,


Stage 1

0.05Ir

20Ir

LV 3I0_EF2

LV earth fault (E/F) current


setting for Stage 2

60

60

LV T_EF2

Time setting for LV E/F,


Stage 2

12

LV Curve_EF Inv

Ref to IEC and ANSI


Curves

0.05Ir

20Ir

LV 3I0_EF Inv

Ref to IEC and ANSI


Curves

0.05

999

LV K_EF Inv

Ref to IEC and ANSI


Curves

200

0.14

LV A_EF Inv

Ref to IEC and ANSI


Curves

60

LV B_EF Inv

Ref to IEC and ANSI


Curves

10

0.02

LV P_EF Inv

Ref to IEC and ANSI


Curves

90

45

LV Angle_EF

The angle setting for voltage ahead of current.

0.25Ir

20Ir

LV

The maximum 1st


-harmonic current setting to

Imax_2H_UnBlk_E

remove the inrush block, in

LV E/F protection
0.07

0.5

0.2

LV Ratio_I2/I1_EF

Inrush 2nd harmonic ratio


setting for blocking LV E/F
protection

0.05Ir

20Ir

HV 3I0_Neutral

HV neutral over-current
(NOC) protection current

OC1

setting for Stage 1


s

60

60

HV T_Neutral OC1

Time setting for HV NOC,


Stage 1

0.05Ir

20Ir

HV 3I0_Neutral

HV neutral over-current
(NOC) protection current

OC2

setting for Stage 2


HV T_Neutral OC2
258

60

60

Time setting for HV NOC,

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
Stage 1

HV Curve_NOC

12

Inv

Ref to IEC and ANSI


Curves

0.05Ir

20Ir

HV 3I0_NOC Inv

Ref to IEC and ANSI


Curves

0.05

999

HV K_NOC Inv

Ref to IEC and ANSI


Curves

200

0.14

HV A_NOC Inv

Ref to IEC and ANSI


Curves

60

HV B_NOC Inv

Ref to IEC and ANSI


Curves

10

0.02

HV P_NOC Inv

Ref to IEC and ANSI


Curves

90

45

HV Angle_NOC

The angle setting for voltage ahead of current.

0.25Ir

20Ir

HV

The maximum 1st


-harmonic current setting to

Imax_2H_UnBlk_

remove the inrush block, in

NOC

HV NOC protection
0.07

0.5

0.2

HV Ra-

Inrush 2nd harmonic ratio


setting for blocking HV NOC

tio_I2/I1_NOC

protection
A

0.05Ir

20Ir

MV 3I0_Neutral

MV neutral over-current
(NOC) protection current

OC1

setting for Stage 1


s

60

60

MV T_Neutral OC1

Time setting for MV NOC,


Stage 1

0.05Ir

20Ir

MV 3I0_Neutral

MV neutral over-current
(NOC) protection current

OC2

setting for Stage 2


s

60

60

MV T_Neutral OC2

Stage 1
1

MV Curve_NOC

12

Inv

Ref to IEC and ANSI


Curves

A
MV 3I0_NOC Inv

Time setting for MV NOC,

0.05Ir

20Ir

Ref to IEC and ANSI


Curves
259

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.05

999

Default
setting
(Ir:5A/1

Description

A)
1

MV K_NOC Inv

Ref to IEC and ANSI


Curves

200

0.14

MV A_NOC Inv

Ref to IEC and ANSI


Curves

60

MV B_NOC Inv

Ref to IEC and ANSI


Curves

10

0.02

MV P_NOC Inv

Ref to IEC and ANSI


Curves

90

45

MV Angle_NOC

The angle setting for voltage ahead of current.

0.25Ir

20Ir

MV

The maximum 1st


-harmonic current setting to

Imax_2H_UnBlk_

remove the inrush block, in

NOC

MV NOC protection
0.07

0.5

0.2

MV Ra-

Inrush 2nd harmonic ratio


setting for blocking MV

tio_I2/I1_NOC

NOC protection
A

0.05Ir

20Ir

LV 3I0_Neutral

LV neutral over-current
(NOC) protection current

OC1

setting for Stage 1


s

60

60

LV T_Neutral OC1

Time setting for LV NOC,


Stage 1

0.05Ir

20Ir

LV 3I0_Neutral

LV neutral over-current
(NOC) protection current

OC2

setting for Stage 2


s

60

60

LV T_Neutral OC2

Stage 1
1

12

LV Curve_NOC Inv
A

0.05Ir

20Ir

Ref to IEC and ANSI


Curves

0.05

999

LV K_NOC Inv

Ref to IEC and ANSI


Curves

200

0.14

LV A_NOC Inv

260

Ref to IEC and ANSI


Curves

LV 3I0_NOC Inv

LV B_NOC Inv

Time setting for LV NOC,

Ref to IEC and ANSI


Curves

60

Ref to IEC and ANSI

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
Curves

10

0.02

LV P_NOC Inv

Ref to IEC and ANSI


Curves

90

45

LV Angle_NOC

The angle setting for voltage ahead of current.

0.25Ir

20Ir

LV

The maximum 1st


-harmonic current setting to

Imax_2H_UnBlk_

remove the inrush block, in

NOC

LV NOC protection
0.07

0.5

0.2

LV Ra-

Inrush 2nd harmonic ratio


setting for blocking LV NOC

tio_I2/I1_NOC

protection
HV I_Therm OL

0.1Ir

5Ir

Trip

Setting for HV-side thermal


overload trip-stage current

0.1Ir

5Ir

HV I_Therm OL

Setting for HV-side thermal


overload alarm-stage cur-

Alarm

rent
HV T_Const

9999

10

Therm
HV T_Const Cool

thermal overload protection


s

9999

10

Down
MV I_Therm OL

Time const for HV-side

Cool down time delay for


HV-side thermal overload

0.1Ir

5Ir

Trip

Setting for MV-side thermal


overload trip-stage current

0.1Ir

5Ir

MV I_Therm OL

Setting for MV-side thermal


overload alarm-stage cur-

Alarm

rent
MV T_Const

9999

10

Therm
MV T_Const Cool

thermal overload protection


s

9999

10

Down
A

MV I_OverLoad

Cool down time delay for


MV-side thermal overload

0.1Ir

4Ir

HV I_OverLoad
HV T_OverLoad

Time const for MV-side

Overcurrent Setting of
overload

0.1

3600

10

Time setting for overload

0.1Ir

4Ir

Overcurrent Setting of
overload

261

Chapter 20 Appendix

Setting

MV T_OverLoad

Default

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.1

3600

10

Time setting for overload

0.1Ir

4Ir

Overcurrent Setting of

Unit

setting
(Ir:5A/1
A)

LV I_OverLoad
LV T_OverLoad

Description

overload
s

0.1

3600

10

Time setting for overload

0.1Ir

4Ir

20

Alarm current setting of LV

LW I_OvLd Alarm

delta winding overload protection


s

0.1

3600

10

LW T_OvLd Alarm

Alarm time setting of LV


delta winding overload protection

LW I_OvLd Low

0.1Ir

4Ir

20

Trip
LW T_OvLd Low

setting
s

0.1

3600

10

Trip
LW I_OvLd High

0.1Ir

4Ir

20

0.1

3600

10

High stage tripping time


setting

40

200

200

HV U_OV1

HV voltage setting for stage


1 of overvoltage protection

60

60

HV T_OV1

HV time setting for stage 1


of overvoltage protection

40

200

200

HV U_OV2

HV voltage setting for stage


2 of overvoltage protection

60

60

HV T_OV2

HV time setting for stage 2


of overvoltage protection

0.9

0.99

0.95

HV Dropout_OV

HV dropout ratio for overvoltage protection

40

200

200

MV U_OV1

MV voltage setting for stage


1 of overvoltage protection

60

60

MV T_OV1

MV time setting for stage 1


of overvoltage protection

40

200

200

MV U_OV2

MV voltage setting for stage


2 of overvoltage protection

262

High stage tripping current


setting

Trip

MV T_OV2

Low stage tripping time setting

Trip
LW T_OvLd High

Low stage tripping current

60

60

MV time setting for stage 2


of overvoltage protection

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.9

0.99

Default
setting
(Ir:5A/1

Description

A)
0.95

MV Dropout_OV

MV dropout ratio for overvoltage protection

0.05Ir

20Ir

HV I_CBF OC

Phase current setting value


for HVcircuit breaker failure
(CBF)

0.05Ir

20Ir

protection

Negative sequence (NS)


current setting 3I 2 value

HV 3I2_CBF NS

for HV CBF protection


A

0.05Ir

20Ir

HV 3I0_CBF ZS

Zero sequence (ZS) current


setting

3I 0

value for HV1

CBF protection
s

32

10

HV T1_CBF

Time setting value of Stage


1, for HV CBF protection

0.1

32

10

HV T2_CBF

Time setting value of Stage


2, for HV CBF protection

0.05Ir

20Ir

MVI_CBF OC

Phase current setting value


for MV CBF protection

0.05Ir

20Ir

Negative sequence (NS)


current setting 3I 2 value

MV 3I2_CBF NS

for MV CBF protection


A

0.05Ir

20Ir

MV 3I0_CBF ZS

Zero sequence (ZS) current


setting

3I 0

value for MV

CBF protection
s

32

10

MV T1_CBF

1, for MV CBF protection


s

0.1

32

10

MV T2_CBF

Time setting value of Stage


2, for MV CBF protection

0.05Ir

20Ir

LV I_CBF OC

Phase current setting value


for LV CBF protection

A
LV 3I2_CBF NS

Time setting value of Stage

0.05Ir

20Ir

Negative sequence (NS)


current setting 3I 2 value
for LV CBF protection
263

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.05Ir

20Ir

Default
setting
(Ir:5A/1

Description

A)
5

LV 3I0_CBF ZS

Zero sequence (ZS) current


setting

3I 0

value for LV

CBF protection
s

32

10

LV T1_CBF

1, for LV CBF protection


s

0.1

32

10

LV T2_CBF
HV T_Dead Zone

Time setting value of Stage

Time setting value of Stage


2, for LV CBF protection

32

10

Time delay setting for HV


dead zone protection

MV T_Dead Zone

32

10

Time delay setting for MV


dead zone protection

LV T_Dead Zone

32

10

Time delay setting for LV


dead zone protection

0.05Ir

20Ir

100

HV I_STUB

current threshold of STUB


protection

60

60

HV T_STUB

delay time of STUB protection

0.05Ir

20Ir

100

MV I_STUB

current threshold of STUB


protection

60

60

MV T_STUB

delay time of STUB protection

0.05Ir

20Ir

100

LV I_STUB

current threshold of STUB


protection

60

60

LV T_STUB

delay time of STUB protection

0.05Ir

20Ir

HV 3I0_PD

zero sequence current


threshold of pole discordance protection

0.05Ir

20Ir

HV 3I2_PD

negative sequence current


threshold of pole discordance protection

60

10

HV T_PD

ance protection
A

MV 3I0_PD

264

delay time of pole discord-

0.05Ir

20Ir

zero sequence current


threshold of pole discord-

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

Default
setting
(Ir:5A/1

Description

A)
ance protection

0.05Ir

20Ir

MV 3I2_PD

negative sequence current


threshold of pole discordance protection

60

10

MV T_PD

ance protection
A

0.05Ir

0.2Ir

0.05

HV I_VT Fail
A

0.05Ir

0.2Ir

0.5

20

10

30

16

Maximum phase to phase


voltage of HV VT fail

40

65

40

mal

Minimum phase to phase


voltage of HV VT normal

0.05Ir

0.2Ir

0.05

MV I_VT Fail

Minimum Current of VT
failure for MV side

0.05Ir

0.2Ir

0.5

MV 3I02_VT Fail

Minimum zero or negative


Current of MV VT fail

20

MV Upe_VT Fail

Maximum phase to earth


voltage of MV VT fail

10

30

16

MV Upp_VT Fail

Maximum phase to phase


voltage of MV VT fail

40

65

40

mal

Minimum phase to phase


voltage of MV VT normal

0.05Ir

0.2Ir

0.05

LV I_VT Fail

Minimum Current of VT
failure for LV side

0.05Ir

0.2Ir

0.5

LV 3I02_VT Fail

Minimum zero or negative


Current of LV VT fail

20

LV Upe_VT Fail

Maximum phase to earth


voltage of LV VT fail

10

30

16

LV Upp_VT Fail

mal

Maximum phase to earth


voltage of HV VT fail

HV Upp_VT Fail

LV Upe_VT Nor-

Minimum zero or negative


Current of HV VT fail

HV Upe_VT Fail

MV Upe_VT Nor-

Minimum Current of VT
failure for HV side

HV 3I02_ VT Fail

HV Upe_VT Nor-

delay time of pole discord-

Maximum phase to phase


voltage of LV VT fail

40

65

40

Minimum phase to phase


voltage of LV VT normal
265

Chapter 20 Appendix

Setting

Unit

Min.

Max.

(Ir:5A/1

(Ir:5A/1

A)

A)

0.2

Default
setting
(Ir:5A/1
A)
5

T_Pulse Tripping

1.2

Description

delay time of STUB protection

Binary setting list


Setting

Unit

Min.

Max.

Default
setting

Description
Autotransformer not comm
on transformer

Auto Trans

1-autotransformer ;
0- not autotransformer

Two-Wind Trans

Two-winding(TWO WIND )
not three -winding
0

trans-

former (TRANS)
1-two-winding trans;
0-three-winding trans

CT Fail Detect
Setting
Func_Inst Diff
Func_Percent Diff

Unit

Min.

Max.

Default
setting

Block Diff at Inrush

VT Failure Detection On/Off


1-On, 0-Off.
Description
Instantaneous differential
protection ON 1-on; 0-off.
Percentage differential protection ON 1-on; 0-off.
Inrush block differential protection
1-block; 0-not block.

2nd Harm Not

2nd harmonic (HAR) inhibit

Wave

not the fuzzy recognition


0

based on the waveform(WAVE)


1-2nd harmonic on; 0waveform on

Block Diff at
Overexcit

Overexcitation block differ0

ential protection
1-block; 0-not block.

Overexcit 3rd NOT


5th
266

Overexcitation stabilization
judgement

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
3rd or 5th harmonic (HAR)
inhibit on
1-3rd harmonic; 0-5th harmonic.

Func_Diff Alarm

Differential current (DIFF)


0

Alarming on
1-on; 0-off.

Block Diff at
CT_Fail

Block differential protection


0

when there is CT failure


1-block; 0-not block.

HV D_side Eliminate I0

Eliminate calculated 3I0


0

when HV side winding is


connected in Delta mode
1- eliminate; 0-not eliminate

MV D_side Eliminate I0

Eliminate calculated 3I0


0

when MV side winding is


connected in Delta mode
1- eliminate; 0-not eliminate

LV D_side Eliminate I0

Eliminate calculated 3I0


0

when LV side winding is


connected in Delta mode
1- eliminate; 0-not eliminate

Diff Includes LV

LV current is included in

Cur

calculation of the differential


0

protection.
1- Diff Includes LV Cur;
0-Diff NOT Includes LV Cur

HV Func_REF Trip

HV Restricted earth fault


0

trip-stage ON
1-on; 0-off.

HV Func_REF
Alarm

HV Restricted earth fault


0

Alarm-stage ON
1-on; 0-off.

Block HV REF at
HV CT_Fail

Block HV REF when CT


0

failure,
1-Block;0-unblock

MV Func_REF Trip

MV Func_REF
Alarm

MV Restricted earth fault


trip-stage ON 1-on; 0-off.
MV Restricted earth fault

Alarm-stage ON
1-on; 0-off.

267

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Block MV REF at
MV CT_Fail

Description
Block MV REF when CT

failure,
1-Block;0-unblock

LV Func_REF Trip

LV Func_REF
Alarm

LV Restricted earth fault


trip-stage ON 1-on; 0-off.
LV Restricted earth fault

Alarm-stage ON
1-on; 0-off.

Block LV REF at
LV CT_Fail

Block LV REF when CT fail0

ure,
1-Block;0-unblock

HV
Func_Overexcit
MV
Func_Overexcit
LV Func_Overexcit

Func_Overexcit
Alarm Def

HV Overexcitation (V/F) on
1-on; 0-off.
MV Overexcitation (V/F) on
1-on; 0-off.
LV Overexcitation (V/F) on
1-on; 0-off.
Definite Overexcitation (V/F)

Alarming on
1-on; 0-off.

Func_Overexcit
Trip Def

Definite (DEF)Overexcitation
0

(V/F) on
1-on; 0-off.

Func_Overexcit
Trip Inv

Inverse (IVR)Overexcitation
0

(V/F) on
1-on; 0-off.

V/F Volt-

Overexcitation protection

age(0-VPP,1-VPN)

uses phase-to-phase volt0

age (VPP) or phase-to-earth


voltage (VPN)
0-VPP; 1-VPN.

HV Func_OC1

The 1st stage of HV OC


0

(OC_1) protection is
switched ON
1-on; 0-off.

HV OC1 Direction

Direction (DIR) detection of


0

HV OC Stage 1 is switched
ON
1-on; 0-off.

HV OC1 Dir To Sys

268

Direction unit of HV OC
Stage 1 points to system

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
0 - point to the protected
transformer
1- point to system

HV OC1 Inrush
Block

Inrush 2nd harmonic detec0

tion HV OC Stage 1 is
switched ON
1-on; 0-off.

HV Func_OC2

The 2nd stage of HV OC


0

(OC_2) protection is
switched ON
1-on; 0-off.

HV OC2 Direction

Direction (DIR) detection of


0

HV OC Stage 2 is switched
ON
1-on; 0-off.

HV OC2 Dir To Sys

Direction unit of HV OC
Stage 2 points to system
0

0 - point to the protected


transformer
1- point to system

HV OC2 Inrush
Block

Inrush 2nd harmonic detec0

tion HV OC Stage 2 is
switched ON
1-on; 0-off.

HV Func_OC Inv

The IDMTL inverse time


0

stage of HV OC protection is
switched ON
1-on; 0-off.

HV OC Inv Direction

Direction (DIR) detection of


0

HV OC IDMTL inverse time


is switched ON
1-on; 0-off.

HV OC Inv Dir To

Direction unit of HV OC

Sys

IDMTL inverse time points to


0

system
0 - point to the protected
transformer
1- point to system

HV OC Inv Inrush
Block

Inrush 2nd harmonic detec0

tion HV OC IDMTL inverse


time is switched ON

269

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
1-on; 0-off.

Block HV OC at

Select to block HV OC pro-

HV VT_Fail

tection or exit direction unit,


0

when HV VT fails
0- HV Direct OK at HV VT
Fail
1- Blk HV OC at HV VT Fail

HV OC Initiate LV
CBF

HV OC protection initiate LV
0

side CBF
0 - initiate, 1 not initiate

HV OC Initiate MV
CBF

HV OC protection initiate MV
0

side CBF
0 - initiate, 1 not initiate

MV Func_OC1

The 1st stage of MV OC


0

(OC_1) protection is
switched ON
1-on; 0-off.

MV OC1 Direction

Direction (DIR) detection of


0

MV OC Stage 1 is switched
ON
1-on; 0-off.

MV OC1 Dir To

Direction unit of MV OC

Sys

Stage 1 points to system


0

0 - point to the protected


transformer
1- point to system

MV OC1 Inrush
Block

Inrush 2nd harmonic detec0

tion MV OC Stage 1 is
switched ON
1-on; 0-off.

MV Func_OC2

The 2nd stage of MV OC


0

(OC_2) protection is
switched ON
1-on; 0-off.

MV OC2 Direction

Direction (DIR) detection of


0

MV OC Stage 2 is switched
ON
1-on; 0-off.

MV OC2 Dir To
Sys

Direction unit of MV OC
0

Stage 2 points to system


0 - point to the protected

270

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
transformer
1- point to system

MV OC2 Inrush
Block

Inrush 2nd harmonic detec0

tion MV OC Stage 2 is
switched ON
1-on; 0-off.

MV Func_OC Inv

The IDMTL inverse time


0

stage of MV OC protection is
switched ON
1-on; 0-off.

MV OC Inv Direction

Direction (DIR) detection of


0

MV OC IDMTL inverse time


is switched ON
1-on; 0-off.

MV OC Inv Dir To

Direction unit of MV OC

Sys

IDMTL inverse time points to


0

system
0 - point to the protected
transformer
1- point to system

MV OC Inv Inrush
Block

Inrush 2nd harmonic detec0

tion MV OC IDMTL inverse


time is switched ON
1-on; 0-off.

Block MV OC at

Select to block MV OC pro-

MV VT_Fail

tection or exit direction unit,


0

when MV VT fails
0- MV Direct OK at MV VT
Fail
1- Blk MV OC at MV VT Fail

MV OC Initiate
HV1 CBF

MV OC protection initiate
0

HV1 side CBF


0 - initiate, 1 not initiate

LV Func_OC1

The 1st stage of LV OC


0

(OC_1) protection is
switched ON
1-on; 0-off.

LV OC1 Direction

Direction (DIR) detection of


0

LV OC Stage 1 is switched
ON
1-on; 0-off.

271

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

LV OC1 Dir To Sys

Description
Direction unit of LV OC
Stage 1 points to system

0 - point to the protected


transformer
1- point to system

LV OC1 Inrush
Block

Inrush 2nd harmonic detec0

tion LV OC Stage 1 is
switched ON
1-on; 0-off.

LV Func_OC2

The 2nd stage of LV OC


0

(OC_2) protection is
switched ON
1-on; 0-off.

LV OC2 Direction

Direction (DIR) detection of


0

LV OC Stage 2 is switched
ON
1-on; 0-off.

LV OC2 Dir To Sys

Direction unit of LV OC
Stage 2 points to system
0

0 - point to the protected


transformer
1- point to system

LV OC2 Inrush
Block

Inrush 2nd harmonic detec0

tion LV OC Stage 2 is
switched ON
1-on; 0-off.

LV Func_OC Inv

The IDMTL inverse time


0

stage of LV OC protection is
switched ON
1-on; 0-off.

LV OC Inv Direction

Direction (DIR) detection of


0

LV OC IDMTL inverse time is


switched ON
1-on; 0-off.

LV OC Inv Dir To

Direction unit of LV OC

Sys

IDMTL inverse time points to


0

system
0 - point to the protected
transformer
1- point to system

LV OC Inv Inrush

272

Inrush 2nd harmonic detec-

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Block

Description
tion LV OC IDMTL inverse
time is switched ON
1-on; 0-off.

Block LV OC at LV

Select to block LV OC pro-

VT_Fail

tection or exit direction unit,


0

when LV VT fails
0- LV Direct OK at LV VT Fail
1- Blk LV OC at LV VT Fail

LV OC Initiate HV1
CBF

LV OC protection initiate
0

HV1 side CBF


0 - initiate, 1 not initiate

HV Func_EF1

The 1st stage of HV earth


0

fault (EF_1) protection is


switched ON
1-on; 0-off.

HV EF1 Direction

Direction (DIR) detection of


0

HV EF Stage 1 is switched
ON
1-on; 0-off.

HV EF1 Dir To Sys

Direction unit of HV EF
Stage 1 points to system
0

0 - point to the protected


transformer
1- point to system

HV EF1 Inrush
Block

Inrush 2nd harmonic detec0

tion HV EF Stage 1 is
switched ON
1-on; 0-off.

HV Func_EF2

The 2nd stage of HV earth


0

fault (EF_2) protection is


switched ON
1-on; 0-off.

HV EF2 Direction

Direction (DIR) detection of


0

HV EF Stage 2 is switched
ON
1-on; 0-off.

HV EF2 Dir To Sys

Direction unit of HV EF
Stage 2 points to system
0

0 - point to the protected


transformer
1- point to system

273

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

HV EF2 Inrush
Block

Description
Inrush 2nd harmonic detec-

tion HV EF Stage 2 is
switched ON
1-on; 0-off.

HV Func_EF Inv

The IDMTL inverse time


0

stage of HV EF protection is
switched ON
1-on; 0-off.

HV EF Inv Direction

Direction (DIR) detection of


0

HV EF IDMTL inverse time is


switched ON
1-on; 0-off.

HV EF Inv Dir To

Direction unit of HV EF

Sys

IDMTL inverse time points to


0

system
0 - point to the protected
transformer
1- point to system

HV EF Inv Inrush
Block

Inrush 2nd harmonic detec0

tion HV EF IDMTL inverse


time is switched ON
1-on; 0-off.

Block HV EF at HV

Select to block HV EF pro-

VT_Fail

tection or exit direction unit,


0

when HV VT fails
0 - HV Direct OK at HV VT
Fail
1 - Blk HV EF at HV VT Fail

Block HV EF at HV
CT_Fail

Block HV EF when there is


0

HV CT failure
1-Block; 0-NOT block

HV EF Initiate LV
CBF

HV EF protection initiate LV
0

side CBF
0 - initiate, 1 not initiate

HV EF Initiate MV
CBF

HV EF protection initiate MV
0

side CBF
0 - initiate, 1 not initiate

MV Func_EF1

The 1st stage of MV earth


0

fault (EF_1) protection is


switched ON
1-on; 0-off.

274

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

MV EF1 Direction

Description
Direction (DIR) detection of

MV EF Stage 1 is switched
ON
1-on; 0-off.

MV EF1 Dir To Sys

Direction unit of MV EF
Stage 1 points to system
0

0 - point to the protected


transformer
1- point to system

MV EF1 Inrush
Block

Inrush 2nd harmonic detec0

tion MV EF Stage 1 is
switched ON
1-on; 0-off.

MV Func_EF2

The 2nd stage of MV earth


0

fault (EF_2) protection is


switched ON
1-on; 0-off.

MV EF2 Direction

Direction (DIR) detection of


0

MV EF Stage 2 is switched
ON
1-on; 0-off.

MV EF2 Dir To Sys

Direction unit of MV EF
Stage 2 points to system
0

0 - point to the protected


transformer
1- point to system

MV EF2 Inrush
Block

Inrush 2nd harmonic detec0

tion MV EF Stage 2 is
switched ON
1-on; 0-off.

MV Func_EF Inv

The IDMTL inverse time


0

stage of MV EF protection is
switched ON
1-on; 0-off.

MV EF Inv Direction

Direction (DIR) detection of


0

MV EF IDMTL inverse time


is switched ON
1-on; 0-off.

MV EF Inv Dir To
Sys

Direction unit of MV EF
0

IDMTL inverse time points to


system

275

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
0 - point to the protected
transformer
1- point to system

MV EF Inv Inrush
Block

Inrush 2nd harmonic detec0

tion MV EF IDMTL inverse


time is switched ON
1-on; 0-off.

Block MV EF at

Select to block MV EF pro-

MV VT_Fail

tection or exit direction unit,


0

when MV VT fails
0 - MV Direct OK at MV VT
Fail
1 - Blk MV EF at MV VT Fail

Block MV EF at
MV CT_Fail

Block MV EF when there is


0

MV CT failure
1-Block; 0-NOT block

MV EF Initiate HV
CBF

MV EF protection initiate
0

HV1 side CBF


0 - initiate, 1 not initiate

LV Func_EF1

The 1st stage of LV earth


0

fault (EF_1) protection is


switched ON
1-on; 0-off.

LV EF1 Direction

Direction (DIR) detection of


0

LV EF Stage 1 is switched
ON
1-on; 0-off.

LV EF1 Dir To Sys

Direction unit of LV EF Stage


1 points to system
0

0 - point to the protected


transformer
1- point to system

LV EF1 Inrush
Block

Inrush 2nd harmonic detec0

tion LV EF Stage 1 is
switched ON
1-on; 0-off.

LV Func_EF2

The 2nd stage of LV earth


0

fault (EF_2) protection is


switched ON
1-on; 0-off.

LV EF2 Direction

276

Direction (DIR) detection of

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
LV EF Stage 2 is switched
ON
1-on; 0-off.

LV EF2 Dir To Sys

Direction unit of LV EF Stage


2 points to system
0

0 - point to the protected


transformer
1- point to system

LV EF2 Inrush
Block

Inrush 2nd harmonic detec0

tion LV EF Stage 2 is
switched ON
1-on; 0-off.

LV Func_EF Inv

The IDMTL inverse time


0

stage of LV EF protection is
switched ON
1-on; 0-off.

LV EF Inv Direction

Direction (DIR) detection of


0

LV EF IDMTL inverse time is


switched ON
1-on; 0-off.

LV EF Inv Dir To

Direction unit of LV EF

Sys

IDMTL inverse time points to


0

system
0 - point to the protected
transformer
1- point to system

LV EF Inv Inrush
Block

Inrush 2nd harmonic detec0

tion LV EF IDMTL inverse


time is switched ON
1-on; 0-off.

Block LV EF at LV

Select to block LV EF pro-

VT_Fail

tection or exit direction unit,


0

when LV VT fails
0 - LV Direct OK at LV VT
Fail
1 - Blk LV EF at LV VT Fail

Block LV EF at LV
CT_Fail

Block LV EF when there is


0

LV CT failure
1-Block; 0-NOT block

LV EF Initiate HV
CBF

LV EF protection initiate HV1


side CBF

277

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
0 - initiate, 1 not initiate

HV Func_Neu
OC1

The 1st stage of HV neutral


0

OC (OC_1) protection is
switched ON
1-on; 0-off.

HV Neu OC1 Direction

Direction (DIR) detection of


0

HV neutral OC Stage 1 is
switched ON
1-on; 0-off.

HV Neu OC1 Dir

Direction unit of HV neutral

To Sys

OC Stage 1 points to system


0

0 - point to the protected


transformer
1- point to system

HV Neu OC1 Inrush Block

Inrush 2nd harmonic detec0

tion HV neutral OC Stage 1


is switched ON
1-on; 0-off.

HV Func_Neu
OC2

The 2nd stage of HV neutral


0

OC (OC_2) protection is
switched ON
1-on; 0-off.

HV Neu OC2 Direction

Direction (DIR) detection of


0

HV neutral OC Stage 2 is
switched ON
1-on; 0-off.

HV Neu OC2 Dir

Direction unit of HV neutral

To Sys

OC Stage 2 points to system


0

0 - point to the protected


transformer
1- point to system

HV Neu OC2 Inrush Block

Inrush 2nd harmonic detec0

tion HV neutral OC Stage 2


is switched ON
1-on; 0-off.

HV Func_Neu OC
Inv

The IDMTL inverse time


0

stage of HV neutral OC protection is switched ON


1-on; 0-off.

HV Neu OC Inv
Direction
278

Direction (DIR) detection of


HV neutral OC IDMTL in-

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
verse time stage is switched
ON
1-on; 0-off.

HV Neu OC Inv Dir

Direction unit of HV neutral

To Sys

OC IDMTL inverse time


0

stage points to system


0 - point to the protected
transformer
1- point to system

HV Neu OC Inv

Inrush 2nd harmonic detec-

Inrush Block

tion HV neutral OC IDMTL


0

inverse time stage is


switched ON
1-on; 0-off.

Block HV NOC at

Select to block HV neutral

HV VT_Fail

OC protection or exit direction unit, when HV VT fails


0

0 - HV Direct OK at HV VT
Fail
1 - Blk HV NOC at HV VT
Fail

HV Neu OC Init
MV CBF

HV neutral OC protection
0

initiate LV side CBF


0 - initiate, 1 not initiate

MV Func_Neu
OC1

The 1st stage of MV neutral


0

OC (OC_1) protection is
switched ON
1-on; 0-off.

MV Neu OC1 Direction

Direction (DIR) detection of


0

MV neutral OC Stage 1 is
switched ON
1-on; 0-off.

MV Neu OC1 Dir

Direction unit of MV neutral

To Sys

OC Stage 1 points to system


0

0 - point to the protected


transformer
1- point to system

MV Neu OC1 Inrush Block

Inrush 2nd harmonic detec0

tion MV neutral OC Stage 1


is switched ON
1-on; 0-off.

279

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

MV Func_Neu
OC2

Description
The 2nd stage of MV neutral

OC (OC_2) protection is
switched ON
1-on; 0-off.

MV Neu OC2 Direction

Direction (DIR) detection of


0

MV neutral OC Stage 2 is
switched ON
1-on; 0-off.

MV Neu OC2 Dir

Direction unit of MV neutral

To Sys

OC Stage 2 points to system


0

0 - point to the protected


transformer
1- point to system

MV Neu OC2 Inrush Block

Inrush 2nd harmonic detec0

tion MV neutral OC Stage 2


is switched ON
1-on; 0-off.

MV Func_Neu OC
Inv

The IDMTL inverse time


0

stage of MV neutral OC
protection is switched ON
1-on; 0-off.

MV Neu OC Inv

Direction (DIR) detection of

Direction

MV neutral OC IDMTL in0

verse time stage is switched


ON
1-on; 0-off.

MV Neu OC Inv Dir

Direction unit of MV neutral

To Sys

OC IDMTL inverse time


0

stage points to system


0 - point to the protected
transformer
1- point to system

MV Neu OC Inv

Inrush 2nd harmonic detec-

Inrush Block

tion MV neutral OC IDMTL


0

inverse time stage is


switched ON
1-on; 0-off.

Block MV NOC at
MV VT_Fail

Select to block MV neutral


0

OC protection or exit direction unit, when MV VT fails


0 - MV Direct OK at MV VT

280

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
Fail
1 - Blk MV NOC at MV VT
Fail

MV Neu OC Init
MV CBF

MV neutral OC protection
0

initiate LV side CBF


0 - initiate, 1 not initiate

LV Func_Neu OC1

The 1st stage of LV neutral


0

OC (OC_1) protection is
switched ON
1-on; 0-off.

LV Neu OC1 Direction

Direction (DIR) detection of


0

LV neutral OC Stage 1 is
switched ON
1-on; 0-off.

LV Neu OC1 Dir To

Direction unit of LV neutral

Sys

OC Stage 1 points to system


0

0 - point to the protected


transformer
1- point to system

LV Neu OC1 Inrush Block

Inrush 2nd harmonic detec0

tion LV neutral OC Stage 1 is


switched ON
1-on; 0-off.

LV Func_Neu OC2

The 2nd stage of LV neutral


0

OC (OC_2) protection is
switched ON
1-on; 0-off.

LV Neu OC2 Direction

Direction (DIR) detection of


0

LV neutral OC Stage 2 is
switched ON
1-on; 0-off.

LV Neu OC2 Dir To

Direction unit of LV neutral

Sys

OC Stage 2 points to system


0

0 - point to the protected


transformer
1- point to system

LV Neu OC2 Inrush Block

Inrush 2nd harmonic detec0

tion LV neutral OC Stage 2 is


switched ON
1-on; 0-off.

LV Func_Neu OC

The IDMTL inverse time


281

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Inv

Description
stage of LV neutral OC protection is switched ON
1-on; 0-off.

LV Neu OC Inv

Direction (DIR) detection of

Direction

LV neutral OC IDMTL in0

verse time stage is switched


ON
1-on; 0-off.

LV Neu OC Inv Dir

Direction unit of LV neutral

To Sys

OC IDMTL inverse time


0

stage points to system


0 - point to the protected
transformer
1- point to system

LV Neu OC Inv

Inrush 2nd harmonic detec-

Inrush Block

tion LV neutral OC IDMTL


0

inverse time stage is


switched ON
1-on; 0-off.

Block LV NOC at

Select to block LV neutral

LV VT_Fail

OC protection or exit direc0

tion unit, when LV VT fails


0 - LV Direct OK at LV VT
Fail
1 - Blk LV NOC at LV VT Fail

LV Neu OC Init LV
CBF

LV neutral OC protection
0

initiate LV side CBF


0 - initiate, 1 not initiate

HV Func_Thermal
OvLd

Thermal overload in HV side


0

is switched on
0 - OFF, 1 - ON

HV Cold Curve

HV side using hot/cold curve


0

type
0 Hot curve, 1 Cold curve

HV Thermal Init LV
CBF

HV thermal overload protec0

tion initiate LV side CBF


0 - initiate, 1 not initiate

HV Thermal Init
MV CBF

HV thermal overload protec0

tion initiate MV side CBF


0 - initiate, 1 not initiate

MV Func_Thermal

282

Thermal overload in MV side

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

OvLd

Description
is switched on
0 - OFF, 1 - ON

MV Cold Curve

MV side using hot/cold curve


0

type
0 Hot curve, 1 Cold curve

MV Thermal Init
HV1 CBF

MV thermal overload protec0

tion initiate HV side CBF


0 - initiate, 1 not initiate

HV
Func_OverLoad

Overload (LOAD) protection


0

in HV side is switched ON
1-on; 0-off.

MV
Func_OverLoad
LV
Func_OverLoad

LW Func_OvLd

Overload (LOAD)in MV side


on
Overload (LOAD)in LV side
on
Alarm stage of LV delta

Alarm

winding (LWIND) overload


0

(LOAD) protection is
switched ON.
1-on; 0-off.

LW Func_OvLd
Low Trip

Low-setting trip stage of LV


0

delta winding overload protection is switched ON.


1-on; 0-off.

LW Func_OvLd
High Trip

High-setting trip stage of LV


0

delta winding overload protection is switched ON.


1-on; 0-off.

Low Trip Init HV1


CBF

Low-setting trip stage of LV


0

delta winding overload protection initiate HV1 side CBF


0 - initiate, 1 not initiate

High Trip Init HV1


CBF

High-setting trip stage of LV


0

delta winding overload protection initiate HV1 side CBF


0 - initiate, 1 not initiate

Low Trip Init MV


CBF

Low-setting trip stage of LV


0

delta winding overload protection initiate MV side CBF


0 - initiate, 1 not initiate

283

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

High Trip Init MV


CBF

Description
High-setting trip stage of LV

delta winding overload protection initiate MV side CBF


- initiate, 1 not initiate

HV Func_OV1
HV Func_OV2
HV Func_OV2
HV OV2 Trip

HV OV Chk PE

HV overvoltage stage 1 enabled or disabled


HV overvoltage stage 1 trip
or alarm
HV overvoltage stage 2 enabled or disabled
HV overvoltage stage 2 trip
or alarm
HV phase to phase voltage
or phase to earth measured
for overvoltage protection

MV Func_OV1
MV Func_OV2
MV Func_OV2
MV OV2 Trip

MV OV Chk PE

MV overvoltage stage 1 enabled or disabled


MV overvoltage stage 1 trip
or alarm
MV overvoltage stage 2 enabled or disabled
MV overvoltage stage 2 trip
or alarm
MV phase to phase voltage

or phase to earth measured


for overvoltage protection

HV Func_CBF

HV Circuit breaker failure


0

(CBF) protection is switched


ON
1-on; 0-off.

HV 3I0/3I2 Check
On

HV CBF protection detect


0

negative or zero sequence


current 3I0 or 3I2.
1-Detect; 0- Not Detect

HV CB Status
Check On

HV CBF protection detect


0

HV1 CB status
1-Detect; 0- Not Detect

MV Func_CBF

MV Circuit breaker failure


0

(CBF) protection is switched


ON
1-on; 0-off.

284

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

MV 3I0/3I2 Check
On

Description
MV CBF protection detect

negative or zero sequence


current 3I0 or 3I2.
1-Detect; 0- Not Detect

MV CB Status
Check On

MV CBF protection detect


0

MV CB status
1-Detect; 0- Not Detect

LV Func_CBF

LV Circuit breaker failure


0

(CBF) protection is switched


ON
1-on; 0-off.

LV 3I0/3I2 Check
On

LV CBF protection detect


0

negative or zero sequence


current 3I0 or 3I2.
1-Detect; 0- Not Detect

LV CB Status
Check On

LV CBF protection detect LV


0

CB status
1-Detect; 0- Not Detect

HV Func_Dead
Zone

Dead zone protection is


0

switched ON
1-on; 0-off.

MV Func_Dead
Zone

Dead zone protection is


0

switched ON
1-on; 0-off.

LV Func_Dead
Zone

Dead zone protection is


0

switched ON
1-on; 0-off.

HV Func_STUB

HV STUB Init LV
CBF

Enable or disable STUB


protection
STUB protection initiate LV

side CBF
0 - initiate, 1 not initiate

HV STUB Init MV
CBF

STUB protection initiate HV


0

side CBF
0 - initiate, 1 not initiate

MV Func_STUB

MV STUB Init LV
CBF

Enable or disable STUB


protection
STUB protection initiate LV

side CBF
0 - initiate, 1 not initiate

285

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

MV STUB Init MV
CBF

Description
STUB protection initiate MV

side CBF
0 - initiate, 1 not initiate

LV Func_STUB

LV STUB Init LV
CBF

Enable or disable STUB


protection
STUB protection initiate LV

side CBF
0 - initiate, 1 not initiate

LV STUB Init MV
CBF

STUB protection initiate LV


0

side CBF
0 - initiate, 1 not initiate

MV Func_PD
MV PD Chk 3I0/3I2
MV Func_PD
MV PD Chk 3I0/3I2

HV VT FAIL Detect

Enable or disable MV poles


discordance protection
Enable or disable 3I0/3I2
criteria
Enable or disable MV poles
discordance protection
Enable or disable 3I0/3I2
criteria
HV VT Failure Detection

On/Off
1-On, 0-Off.

HV Solid Earth

HV Earthing mode:
0

1: Solid earthed system ;


0: isolated system or resistance earthed.

MV VT FAIL Detect

MV VT Failure Detection
0

On/Off
1-On, 0-Off.

MV Solid Earth

MV Earthing mode:
0

1: Solid earthed system ;


0: isolated system or resistance earthed.

LV VT FAIL Detect

LV VT Failure Detection
0

On/Off
1-On, 0-Off.

LV Solid Earth

LV Earthing mode:
0

1: Solid earthed system ;


0: isolated system or resistance earthed.

286

Chapter 20 Appendix
Setting

Unit

Min.

Max.

Default
setting

Description
To select whether the 1

BI1 Enable BO1

st

binary input (BI1) trip the 1

st

binary output (BO1) or not.


1-enable, 0-disable
To select BO1 tripping in
pulse mode or in direct mode

BO1 Pulse Tripping

0- BO1 Direct Tripping,


without delay
1- BO1 Pulse Tripping, with
preset delay time
To select whether the 2

BI2 Enable BO2

nd

binary input (BI2) trip the 2

nd

binary output (BO2) or not.


1-enable, 0-disable
To select BO2 tripping in
pulse mode or in direct mode

BO2 Pulse Tripping

0- BO2 Direct Tripping,


without delay
1- BO2 Pulse Tripping, with
preset delay time
whether BI1 initiate HV side

BI1 Init HV CBF

CBF or not
0 - initiate, 1 not initiate
whether BI1 initiate MV side

BI1 Init MV CBF

CBF or not
0 - initiate, 1 not initiate
whether BI1 initiate LV side

BI1 Init LV CBF

CBF or not
0 - initiate, 1 not initiate
whether BI2 initiate HV side

BI2 Init HV CBF

CBF or not
0 - initiate, 1 not initiate
whether BI2 initiate MV side

BI2 Init MV CBF

CBF or not
0 - initiate, 1 not initiate
whether BI2 initiate LV side

BI2 Init LV CBF

CBF or not
0 - initiate, 1 not initiate

287

Chapter 20 Appendix

2 General report list


Table 173 event report list

Information
Relay startup

Description
The relay is initiated by startup elements

Per Diff Trip A


Per Diff Trip B

Treble slope percent Differential protection (ID>) trip for phase A/B/C

Per Diff Trip C


Inst Diff Trip A
Inst Diff Trip B

Instantaneous Differential protection (ID>>) trip for phase A/B/C

Inst Diff Trip C


HV REF Trip

HV Restricted Earth fault (REF) protection trip

MV REF Trip

MV Restricted Earth fault (REF) protection trip

LV REF Trip

LV Restricted Earth fault (REF) protection trip

Def V/F Trip

Overexcitation protection(V/F) tripping (Trip) with definite (DEF) and

Inv V/F Trip

inverse(IVR) time characteristic

HV OC Inv Trip

Inverse time stage of HV overcurrent protection trip

HV OC1 Trip

HV overcurrent stage 1 trip

HV OC2 Trip

HV overcurrent stage 2 trip

MV OC Inv Trip

Inverse time stage of MV overcurrent protection trip

MV OC1 Trip

MV overcurrent stage 1 trip

MV OC2 Trip

MV overcurrent stage 2 trip

LV OC Inv Trip

Inverse time stage of LV overcurrent protection trip

LV OC1 Trip

LV overcurrent stage 1 trip

LV OC2 Trip

LV overcurrent stage 2 trip

HV EF Inv Trip

Inverse time stage of HV earth fault protection trip

HV EF1 Trip

HV earth fault stage 1 trip

HV EF2 Trip

HV earth fault stage 2 trip

MV EF Inv Trip

Inverse time stage of MV earth fault protection trip

MV EF1 Trip

MV earth fault stage 1 trip

MV EF2 Trip

MV earth fault stage 2 trip

288

Chapter 20 Appendix

Information

Description

LV EF Inv Trip

Inverse time stage of LV earth fault protection trip

LV EF1 Trip

LV earth fault stage 1 trip

LV EF2 Trip

LV earth fault stage 2 trip

HV NOC Inv Trip

Inverse time stage of neutral OC protection trip

HV NOC1 Trip

HV neutral OC stage 1 trip

HV NOC2 Trip

HV neutral OC stage 2 trip

MV EF Inv Trip

Inverse time stage of MV neutral OC protection trip

MV EF1 Trip

MV neutral OC stage 1 trip

MV EF2 Trip

MV neutral OC stage 2 trip

LV EF Inv Trip

Inverse time stage of LV neutral OC protection trip

LV EF1 Trip

LV neutral OC stage 1 trip

LV EF2 Trip

LV neutral OC stage 2 trip

HV Therm OL Trip

HV Thermal (TEM) Overload(OVLD) tripping (Trip)

MV Therm OL Trip

MV Thermal (TEM) Overload(OVLD) tripping (Trip)

HV OV1 Trip

HV overvoltage stage 1 trip

HV OV2 Trip

HV overvoltage stage 2 trip

MV OV1 Trip

MV overvoltage stage 1 trip

MV OV2 Trip

MV overvoltage stage 2 trip

HV CBF1 Trip

HV circuit breaker failure protection stage 1 trip

HV CBF2 Trip

HV circuit breaker failure protection stage 2 trip

HV CBF Init

Internal or external initiate HV circuit breaker failure protection

MV CBF1 Trip

MV circuit breaker failure protection stage 1 trip

MV CBF2 Trip

MV circuit breaker failure protection stage 2 trip

MV CBF Init

Internal or external initiate MV circuit breaker failure protection

LV CBF1 Trip

LV circuit breaker failure protection stage 1 trip

LV CBF2 Trip

LV circuit breaker failure protection stage 2 trip

LV CBF Init

Internal or external initiate LV circuit breaker failure protection

HV Dead Zone

HV Dead zone trip

MV Dead Zone

MV Dead zone trip

LV Dead Zone

LV Dead zone trip

HV STUB Trip

HV STUB protection trip

289

Chapter 20 Appendix

Information

Description

MV STUB Trip

MV STUB protection trip

LV STUB Trip

LV STUB protection trip

HV PD Trip

HV poles discordance protection trip

MV PD Trip

MV poles discordance protection trip

HV VT Fail

HV VT Fail alarm

MV VT Fail

MV VT Fail alarm

LV VT Fail

LV VT Fail alarm

Table 174 Alarm report list


No

Abbr. (LCD Display)

Description

Battery Off

Battery off

BI Breakdown

Binary input breakdown

BI Check Err

Binary input checking is error

BI Comm Fail

Binary input communication fail

BI Config Err

Binary input configuration is error

BI EEPROM Err

The EEPROM of binary input is error

BI Input Err

Binary input error

BI_CBF Err

Binary input error of CBF

BO Breakdown

Binary output breakdown

BO Comm Fail

Binary output communication fail

BO EEPROM Err

The EEPROM of binary output is error

BO No Response

No response of binary output

BOConfig Err

Binary output configuration is error

CB Err Blk PD

CB auxiliary contacts indicate that one


pole is open but at the same time current is
flowing through the pole.

CB Open A Err

Binary input error of CB Open A

CB Open B Err

Binary input error of CB Open B

3
4
5
6

10
11
12
13
14

15
16

290

Chapter 20 Appendix
17

CB Open C Err

Binary input error of CB Open C

18

CB Status Err

CB Status Error

19

Def V/F Alarm

Def V/F Alarm

Diff 2har Blk

Inrush detection impose a blocking condition to differential protection

Diff 3/5har Blk

3rd or 5th harmonic detection impose a


blocking condition to differential protection

Diff Cur Alarm

Differential current exceeds the threshold


value

EquipPara Err

Equipment parameter is error

FLASH Check Err

FLASH checking is error

H BI MCB VT Fail

Binary input error of VT fail of MCB

H BI_V3P_MCB Err

Binary input error of three phase MCB

HV 3U0 Alarm

HV 3U0 Alarm

HV BLK VOL REGU

Block tap changer control of transformer

HV Inrush Blk BU

a blocking condition is imposed to backup


protection by inrush condition detection

HV Load Alarm

HV Load Alarm

HV OV1 Alarm

Stage 1 of overvoltage protection alarm

HV OV2 Alarm

Stage 2 of overvoltage protection alarm

HV REF 3I0 Alarm

HV REF 3I0 Alarm

HV Therm OL Alm

HV Thermal Overload Alarm

HV VT Fail

HV VT Fail

20

21

22

23
24
25
26
27
28
29

30
31
32
33
34
35
36

HV1 I2 Alarm
37
HV2 I2 Alarm
38
39
40

Negative-sequence current exceeds a threshold


Negative-sequence current exceeds a threshold

L BI MCB VT Fail

Binary input error of VT fail of MCB

L BI_V3P_MCB Err

Binary input error of three phase MCB

LV 3U0 Alarm

LV 3U0 Alarm

291

Chapter 20 Appendix
41
LV I2 Alarm

Negative-sequence current exceeds a threshold

42
LV Inrush Blk BU

a blocking condition is imposed to backup


protection by inrush condition detection

43

LV Load Alarm

LV Load Alarm

44

LV REF 3I0 Alarm

LV REF 3I0 Alarm

45

LV Therm OL Alm

LV Thermal Overload Alarm

46

LV VT Fail

LV VT Fail

47

LW Load Alarm

LW Load Alarm

M BI MCB VT Fail

Binary input error of VT fail of MCB

M BI_V3P_MCB Err

Binary input error of three phase MCB

MV 3U0 Alarm

MV 3U0 Alarm

MV BLK VOL REGU

Block tap changer control of transformer

48
49
50
51
52

MV I2 Alarm

Negative-sequence current exceeds a threshold

53

54
55
56
57
58

a blocking condition is imposed to backup


protection by inrush condition detection

MV Load Alarm

MV Load Alarm

MV OV1 Alarm

Stage 1 of overvoltage protection alarm

MV OV2 Alarm

Stage 2 of overvoltage protection alarm

MV REF 3I0 Alarm

MV REF 3I0 Alarm

MV Therm OL Alm

MV Thermal Overload Alarm

59

MV VT Fail

MV VT Fail

60

NO/NC Discord

NO/NC discord

61

Ph_A CT Fail

Phase A CT Fail

62

Ph_B CT Fail

Phase B CT Fail

63

Ph_C CT Fail

Phase C CT Fail

64

ROM Verify Err

ROM verifying is error

65

Sampling Err

Sampling is error

66

Set Group Err

Setting group is error

67

Setting Err

Setting value is error

68

Soft Version Err

Soft version is error

69

SRAM Check Err

SRAM checking is error

Sys Config Err

System configuration is error

70

292

MV Inrush Blk BU

Chapter 20 Appendix
71

Test BO Un_reset

Do not reset after testing binary output

72

Voltage or frequency is out of the permissible

V or F Exceed

range

Table 175 operation report list

No

Information

Description

Func_Diff On

Differential protection is switched ON (by CW)

Func_Diff Off

Differential protection is switched OFF (by CW)

HV Func_REF On

HV REF protection is switched ON (by CW)

HV Func_REF Off

HV REF protection is switched OFF (by CW)

MV Func_REF On

MV REF protection is switched ON (by CW)

MV Func_REF Off

MV REF protection is switched OFF (by CW)

LV Func_REF On

LV REF protection is switched ON (by CW)

LV Func_REF Off

LV REF protection is switched OFF (by CW)

Func_Overexc On

Overexcitation protection is switched ON (by CW)

10

Func_Overexc Off

Overexcitation protection is switched OFF (by CW)

11
12
13
14
15
16
17
18
19
20
21

HV Func_OC On
HV Func_OC Off
MV Func_OC On
MV Func_OC Off
LV Func_OC On
LV Func_OC Off
HV Func_EF On
HV Func_EF Off
MV Func_EF On
MV Func_EF Off
LV Func_EF On

Overcurrent protection of HV side is switched ON


(by CW)
Overcurrent protection of HV side is switched OFF
(by CW)
Overcurrent protection of MV side is switched ON
(by CW)
Overcurrent protection of MV side is switched OFF
(by CW)
Overcurrent protection of LV side is switched ON (by
CW)
Overcurrent protection of LV side is switched OFF
(by CW)
Earth fault protection of HV side is switched ON (by
CW)
Earth fault protection of HV side is switched OFF (by
CW)
Earth fault protection of MV side is switched ON (by
CW)
Earth fault protection of MV side is switched OFF
(by CW)
Earth fault protection of LV side is switched ON (by
CW)

293

Chapter 20 Appendix

No
22

LV Func_EF Off

Description
Earth fault protection of LV side is switched OFF (by
CW)

23

HV Func_NOC On

NOC protection of HV side is switched ON (by CW)

24

HV Func_NOC Off

NOC protection of HV side is switched OFF (by CW)

25

MV Func_NOC On

NOC protection of MV side is switched ON (by CW)

26

MV Func_NOC Off

NOC protection of MV side is switched OFF (by CW)

27

LV Func_NOC On

NOC protection of LV side is switched ON (by CW)

28

LV Func_NOC Off

NOC protection of LV side is switched OFF (by CW)

29
30
31
32

294

Information

HV Func_Therm On
HV Func_Therm Off
MV Func_Therm On
MV Func_Therm Off

HV thermal overload protection is switched ON (by


CW)
HV thermal overload protection is switched OFF (by
CW)
MV thermal overload protection is switched ON (by
CW)
MV thermal overload protection is switched OFF (by
CW)

33

HV Func_OL On

HV overload protection is switched ON (by CW)

34

HV Func_OL Off

HV overload protection is switched OFF (by CW)

35

MV Func_OL On

MV overload protection is switched ON (by CW)

36

MV Func_OL Off

MV overload protection is switched OFF (by CW)

37

LV Func_OL On

LV overload protection is switched ON (by CW)

38

LV Func_OL Off

LV overload protection is switched OFF (by CW)

39

HV Func_OV On

HV overvoltage protection is switched ON (by CW)

40

HV Func_OV Off

HV overvoltage protection is switched OFF (by CW)

41

MV Func_OV On

MV overvoltage protection is switched ON (by CW)

42

MV Func_OV Off

MV overvoltage protection is switched OFF (by CW)

43

HV Func_DZ On

HV DZ function on

44

HV Func_DZ Off

HV DZ function off

45

MV Func_DZ On

MV DZ function on

46

MV Func_DZ Off

MV DZ function off

47

LV Func_DZ On

LV DZ function on

48

LV Func_DZ Off

LV DZ function off

49

HV Func_STUB On

HV STUB function on

50

HV Func_STUB Off

HV STUB function Off

51

MV Func_STUB On

MV STUB function on

52

MV Func_STUB Off

MV STUB function Off

53

LV Func_STUB On

LV STUB function on

54

LV Func_STUB Off

LV STUB function Off

Chapter 20 Appendix

No

Information

Description

55

HV Func_PD On

HV poles discordance function on

56

HV Func_PD Off

HV poles discordance function off

57

MV Func_PD On

MV poles discordance function on

58

MV Func_PD Off

MV poles discordance function off

59

HV Func_VT On

HV VT failure supervision function on

60

HV Func_VT Off

HV VT failure supervision function off

61

MV Func_VT On

MV VT failure supervision function on

62

MV Func_VT Off

MV VT failure supervision function off

63

LV Func_VT On

LV VT failure supervision function on

64

LV Func_VT Off

LV VT failure supervision function off

Time inverse characteristic

3.1

11 kinds of IEC and ANSI inverse time


characteristic curves
In the setting, if the curve number is set for inverse time characteristic, which
is corresponding to the characteristic curve in the following tabel. Both IEC
and ANSI based standard curves are available.
Table 176 11 kinds of IEC and ANSI inverse time characteristic

Curves No.

IDMTL Curves

Parameter A

Parameter P

Parameter B

IEC INV.

0.14

0.02

IEC VERY INV.

13.5

1.0

IEC EXTERMELY INV.

80.0

2.0

IEC LONG INV.

120.0

1.0

ANSI INV.

8.9341

2.0938

0.17966

ANSI SHORT INV.

0.2663

1.2969

0.03393

ANSI LONG INV.

5.6143

2.18592

ANSI MODERATELY

0.0103

0.02

0.0228
295

Chapter 20 Appendix
INV.

3.2

ANSI VERY INV.

3.922

2.0

0.0982

10

ANSI EXTERMELY INV.

5.64

2.0

0.02434

11

ANSI DEFINITE INV.

0.4797

1.5625

0.21359

User defined characteristic


For the inverse time characteristic, also can be set as user defined
characteristic if the setting is set to 12.

Equation 39

where:
A: Time factor for inverse time stage
B: Delay time for inverse time stage
P: index for inverse time stage
K: Set time multiplier for step n

CT Requirement

4.1

Overview
In practice, the conventional magnetic- core current transformer (hereinafter
as referred CT) is not able to transform the current signal accurately in whole
fault period of all possible faults because of manufactured cost and installation space limited. CT Saturation will cause distortion of the current signal
and can result in a failure to operate or cause unwanted operations of some
functions. Although more and more protection IEDs have been designed to
permit CT saturation with maintained correct operation, the performance of
protection IED is still depended on the correct selection of CT.

4.2

Current transformer classification


The conventional CTs are usually manufactured in accordance with the
standard, IEC 60044, ANSI / IEEE C57.13, ANSI / IEEE C37.110 or other

296

Chapter 20 Appendix
comparable standards, which CTs are specified in different protection class.
Currently, the CT for protection are classified according to functional performance as follows:
Class P CT
Accuracy limit defined by composite error with steady symmetric primary
current. No limit for remanent flux.
Class PR CT
CT with limited remanence factor for which, in some cased, a value of the
secondary loop time constant and/or a limiting value of the winding resistance may also be specified.
Class PX CT
Low leakage reactance for which knowledge of the transformer secondary excitation characteristic, secondary winding resistance, secondary
burden resistance and turns ratio is sufficient to assess its performance
in relation to the protective relay system with which it is to be used.
Class TPS CT
Low leakage flux current transient transformer for which performance is
defined by the secondary excitation characteristics and turns ratio error
limits. No limit for remanent flux
Class TPX CT
Accuracy limit defined by peak instantaneous error during specified transient duty cycle. No limit for remanent flux.
Class TPY CT
Accuracy limit defined by peak instantaneous error during specified transient duty cycle. Remanent flux not to exceed 10% of the saturation flux..
Class TPZ CT
Accuracy limit defined by peak instantaneous alternating current component error during single energization with maximum d.c. offset at
specified secondary loop time constant. No requirements for d.c. component error limit. Remanent flux to be practically negligible.
TPE class CT (TPE represents transient protection and electronic type
CT)

4.3

Abbreviations (according to IEC 60044-1, -6, as


defined)
297

Chapter 20 Appendix
Abbrev.

Description

Esl

Rated secondary limiting e.m.f

Eal

Rated equivalent limiting secondary e.m.f

Ek

Rated knee point e.m.f

Uk

Knee point voltage (r.m.s.)

Kalf

Accuracy limit factor

Kssc

Rated symmetrical short-circuit current factor

Kssc

Effective symmetrical short-circuit current factor

Kssc

based on different Ipcf

Kpcf

Protective checking factor

Ks

Specified transient factor

Kx

Dimensioning factor

Ktd

Transient dimensioning factor

Ipn

Rated primary current

Isn

Rated secondary current

Ipsc

Rated primary short-circuit current

Ipcf

protective checking current

Isscmax

Maximum symmetrical short-circuit current

Rct

Secondary winding d.c. resistance at 75 C /


167 F (or other specified temperature)

Rb

Rated resistive burden

Rb

= Rlead + Rrelay = actual connected resistive


burden

Rs

Total resistance of the secondary circuit, inclusive of the secondary winding resistance corrected to 75, unless otherwise specified, and
inclusive of all external burden connected.

Rlead

Wire loop resistance

Zbn

Rated relay burden

Zb

Actual relay burden

Tp

Specified primary time constant

Ts

Secondary loop time constant

4.4

General current transformer requirements

4.4.1

Protective checking current


The current error of CT should be within the accuracy limit required at specified fault current.
To verify the CT accuracy performance, Ipcf, primary protective checking
current, should be chose properly and carefully.

298

Chapter 20 Appendix
For different protections, Ipcf is the selected fault current in proper fault position of the corresponding fault, which will flow through the verified CT.
To guarantee the reliability of protection relay, Ipcf should be the maximum
fault current at internal fault. E.g. maximum primary three phase short-circuit
fault current or single phase earth fault current depended on system sequence impedance, in different positions.
Moreover, to guarantee the security of protection relay, Ipcf should be the
maximum fault current at external fault.
Last but not least, Ipcf calculation should be based on the future possible
system power capacity
Kpcf, protective checking factor, is always used to verified the CT performance

To reduce the influence of transient state, Kalf, Accuracy limit factor of CT,
should be larger than the following requirement

Ks, Specified transient factor, should be decided based on actual operation


state and operation experiences by user.

4.4.2

CT class
The selected CT should guarantee that the error is within the required accuracy limit at steady symmetric short circuit current. The influence of short
circuit current DC component and remanence should be considered, based
on extent of system transient influence, protection function characteristic,
consequence of transient saturation and actual operating experience. To fulfill the requirement on a specified time to saturation, the rated equivalent
secondary e.m.f of CTs must higher than the required maximum equivalent
secondary e.m.f that is calculated based on actual application.
For the CTs applied to transmission line protection, transformer differential
protection with 330kV voltage level and above, and 300MW and above gen299

Chapter 20 Appendix
erator-transformer set differential protection, the power system time constant
is so large that the CT is easy to saturate severely due to system transient
state. To prevent the CT from saturation at actual duty cycle, TP class CT is
preferred.
For TPS class CT, Eal (rated equivalent secondary limiting e.m.f) is generally
determined as follows:

Where
Ks: Specified transient factor
Kssc: Rated symmetrical short-circuit current factor
For TPX, TPY and TPZ class CT, Eal (rated equivalent secondary limiting
e.m.f) is generally determined as follows:

Where
Ktd: Rated transient dimensioning factor
Considering at short circuit current with 100% offset
For C-t-O duty cycle,

t: duration of one duty cycle;


For C-t-O-tfr-C-t-O duty cycle,

t: duration of first duty cycle;


t: duration of second duty cycle;
tfr: duration between two duty cycle;
For the CTs applied to 110 - 220kV voltage level transmission line protection,
110 - 220kV voltage level transformer differential protection, 100-200MW
generator-transformer set differential protection, and large capacity motor
differential protection, the influence of system transient state to CT is so less
that the CT selection is based on system steady fault state mainly, and leave
300

Chapter 20 Appendix
proper margin to tolerate the negative effect of possible transient state.
Therefore, P, PR, PX class CT can be always applied.
For P class and PR class CT, Esl (the rated secondary limited e.m.f) is generally determined as follows:

Kalf: Accuracy limit factor


For PX class CT, Ek (rated knee point e.m.f) is generally determined as follows:

Kx: Demensioning factor


For the CTs applied to protection for110kV voltage level and below system,
the CT should be selected based on system steady fault state condition. P
class CT is always applied.

4.4.3

Accuracy class
The CT accuracy class should guarantee that the protection relay applied is
able to operate correctly even at a very sensitive setting, e.g. for a sensitive
residual overcurrent protection. Generally, the current transformer should
have an accuracy class, which have an current error at rated primary current,
that is less than 1% (e.g. class 5P).
If current transformers with less accuracy are used it is advisable to check
the actual unwanted residual current during the commissioning.

4.4.4

Ratio of CT
The current transformer ratio is mainly selected based on power system data
like e.g. maximum load. However, it should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to
be detected with the selected CT ratio. The minimum operating current is
different for different functions and settable normally. So each function
should be checked separately.

4.4.5

Rated secondary current


There are 2 standard rated secondary currents, 1A or 5A. Generally, 1 A
301

Chapter 20 Appendix
should be preferred, particularly in HV and EHV stations, to reduce the burden of the CT secondary circuit. Because 5A rated CTs, i.e. I2R is 25x compared to only 1x for a 1A CT. However, in some cases to reduce the CT
secondary circuit open voltage, 5A can be applied.

4.4.6

Secondary burden
Too high flux will result in CT saturation. The secondary e.m.f is directly
proportional to linked flux. To feed rated secondary current, CT need to
generate enough secondary e.m.f to feed the secondary burden. Consequently, Higher secondary burden, need Higher secondary e.m.f, and then
closer to saturation. So the actual secondary burden Rb must be less than
the rated secondary burden Rb of applied CT, presented
Rb > Rb
The CT actual secondary burden Rb consists of wiring loop resistance
Rlead and the actual relay burdens Zb in whole secondary circuit, which is
calculated by following equation
Rb = Rlead + Zb
The rated relay burden, Zbn, is calculated as below:

Where
Sr: the burden of IED current input channel per phase, in VA;
For earth faults, the loop includes both phase and neutral wire, normally
twice the resistance of the single secondary wire. For three-phase faults the
neutral current is zero and it is just necessary to consider the resistance up to
the point where the phase wires are connected to the common neutral wire.
The most common practice is to use four wires secondary cables so it normally is sufficient to consider just a single secondary wire for the three-phase
case.
In isolated or high impedance earthed systems the phase-to-earth fault is not
the considered dimensioning case and therefore the resistance of the single
secondary wire always can be used in the calculation, for this case.

4.5

Rated equivalent secondary e.m.f requirements


To guarantee correct operation, the current transformers (CTs) must be able
to correctly reproduce the current for a minimum time before the CT will
begin to saturate.

302

Chapter 20 Appendix
4.5.1

Transformer differential protection


It is recommended that the CT of each side could be same class and with
same characteristic to guarantee the protection sensitivity.
For the CTs applied to 330kV voltage level and above step-down transformer,
TPY class CT is preferred for each side.
For the CTs of high voltage side and middle voltage side, Eal should be verified at external fault C-O-C-O duty cycle.
For the CT of low voltage side in delta connection, Eal should be verified at
external three phase short circuit fault C-O duty cycle.
Eal must meet the requirement based on following equations:

Where
Ktd: Recommended transient dimensioning factor for verification, 3
recommended
For 220kV voltage level and below transformer differential protection, P
Class, PR class and PX class is able to be used. Because the system time
constant is less relatively, and then DC component is less, the probability of
CT saturation due to through fault current at external fault is reduced more
and more.
For P Class, PR class CT, Esl can be verified as below:

Where
Ks: Specified transient factor, 2 recommended
For PX class CT, Ek can be verified as below:

Where
Ks: Specified transient factor, 2 recommended

303

You might also like