You are on page 1of 334

6 F 2 S 0 7 5 8

INSTRUCTION MANUAL
DIRECTIONAL OVERCURRENT PROTECTION RELAY
GRD140

TOSHIBA Corporation 2004


All Rights Reserved.

( Ver.0.9)

6 F 2 S 0 7 5 8

Safety Precautions
Before using this product, please read this chapter carefully.
This chapter describes the safety precautions recommended when using the GRD140. Before
installing and using the equipment, this chapter must be thoroughly read and understood.

Explanation of symbols used


Signal words such as DANGER, WARNING, and two kinds of CAUTION, will be followed by
important safety information that must be carefully reviewed.

DANGER

Indicates an imminently hazardous situation which will result in death or


serious injury if you do not follow the instructions.

WARNING

Indicates a potentially hazardous situation which could result in death or


serious injury if you do not follow the instructions.

CAUTION
CAUTION

Indicates a potentially hazardous situation which if not avoided, may result in


minor injury or moderate injury.
Indicates a potentially hazardous situation which if not avoided, may result in
property damage.

6 F 2 S 0 7 5 8
DANGER

Current transformer circuit

Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.

WARNING

Exposed terminals

Do not touch the terminals of this equipment while the power is on, as the high voltage generated
is dangerous.

Residual voltage

Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes approximately 30 seconds for the voltage to discharge.

Fiber optic

When connecting this equipment via an optical fiber, do not look directly at the optical signal.

CAUTION

Earth

The earthing terminal of the equipment must be securely earthed.

CAUTION

Operating environment

The equipment must only used within the range of ambient temperature, humidity and dust
detailed in the specification and in an environment free of abnormal vibration.

Ratings

Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.

Printed circuit board

Do not attach and remove printed circuit boards when the DC power to the equipment is on, as this
may cause the equipment to malfunction.

External circuit

When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.

Connection cable

Carefully handle the connection cable without applying excessive force.

6 F 2 S 0 7 5 8

Modification

Do not modify this equipment, as this may cause the equipment to malfunction.

Disposal

This product does not contain expendable supplies nor parts that can be recycled. When disposing
of this equipment, do so in a safe manner according to local regulations as an industrial waste. If
any points are unclear, please contact our sales representatives.

Plastics material

This product contains the following plastics material.


- ABS, Polycarbonate, Acrylic resins

(SJ/T11364-2006)

/
The Mark and Information are applicable for People's Republic of China only.

6 F 2 S 0 7 5 8

Contents
Safety Precautions

1.

Introduction

2.

Application Notes

10

2.1

10
10
17
21
45
47
50
53
56
59
61
61
64
67
70
72
74
76
76
77
79

2.2

2.3
2.4
2.5

3.

Overcurrent and Undercurrent Protection


2.1.1 Non-directional Overcurrent Protection
2.1.2 Directional Overcurrent Protection
2.1.3 Scheme Logic
2.1.4 Phase Undercurrent Protection
2.1.5 Thermal Overload Protection
2.1.6 Broken Conductor Protection
2.1.7 Breaker Failure Protection
2.1.8 Cold Load Protection
2.1.9 CT Requirements
Overvoltage and Undervoltage Protection
2.2.1 Phase Overvoltage Protection
2.2.2 Phase Undervoltage Protection
2.2.3 Zero Phase Sequence Overvoltage Protection
2.2.4 Negative Phase Sequence Overvoltage Protection
Frequency Protection
Trip and Alarm Signal Output
Autoreclose
2.5.1 Scheme Logic
2.5.2 Sequence Coordination
2.5.3 Setting

Technical Description

82

3.1

82
82
86
86
86
90
91
91
91
92
93
94
95
96
97
98

3.2

3.3

Hardware Description
3.1.1 Outline of Hardware Modules
Input and Output Signals
3.2.1 AC Input Signals
3.2.2 Binary Input, Output Signals
3.2.3 Binary Output Signals
Automatic Supervision
3.3.1 Basic Concept of Supervision
3.3.2 Relay Monitoring
3.3.3 CT Failure Supervision
3.3.4 VT Failure Supervision
3.3.5 Trip Circuit Supervision
3.3.6 Circuit Breaker Monitoring
3.3.7 Failure Alarms
3.3.8 Trip Blocking
3.3.9 Setting

6 F 2 S 0 7 5 8
3.4

3.5
3.6

4.

109

4.1

109
109
111
112
112
115
118
123
129
130
175
178
178
179
179

4.3
4.4
4.5
4.6

6.

99
99
100
101
103
106
106
106
107
107
108

User Interface

4.2

5.

Recording Function
3.4.1 Fault Recording
3.4.2 Event Recording
3.4.3 Disturbance Recording
Metering Function
Fault locator
3.6.1 Application
3.6.2 Distance to Fault Calculation
3.6.3 Starting Calculation
3.6.4 Displaying Location
3.6.5 Setting
Outline of User Interface
4.1.1 Front Panel
4.1.2 Communication Ports
Operation of the User Interface
4.2.1 LCD and LED Displays
4.2.2 Relay Menu
4.2.3 Displaying Records
4.2.4 Displaying the Status
4.2.5 Viewing the Settings
4.2.6 Changing the Settings
4.2.7 Testing
Personal Computer Interface
Relay Setting and Monitoring System
IEC 60870-5-103 Interface
Clock Function

Installation

181

5.1
5.2
5.3
5.4
5.5

Receipt of Relays
Relay Mounting
Electrostatic Discharge
Handling Precautions
External Connections

181
181
181
181
182

Commissioning and Maintenance

183

6.1
6.2

183
184
184
184
185
186
186
186
187
188

6.3
6.4

Outline of Commissioning Tests


Cautions
6.2.1 Safety Precautions
6.2.2 Cautions on Tests
Preparations
Hardware Tests
6.4.1 User Interfaces
6.4.2 Binary Input Circuit
6.4.3 Binary Output Circuit
6.4.4 AC Input Circuits

6 F 2 S 0 7 5 8
6.5

6.6

6.7

7.

Function Test
6.5.1 Measuring Element
6.5.2 Protection Scheme
6.5.3 Metering and Recording
Conjunctive Tests
6.6.1 On Load Test
6.6.2 Tripping and Reclosing Circuit Test
Maintenance
6.7.1 Regular Testing
6.7.2 Failure Tracing and Repair
6.7.3 Replacing Failed Relay Unit
6.7.4 Resumption of Service
6.7.5 Storage

Putting Relay into Service

190
190
201
201
202
202
203
205
205
205
206
207
207
208

6 F 2 S 0 7 5 8
Appendix A Programmable Reset Characteristics and Implementation of Thermal
Model to IEC60255-8

209

Appendix B Directional Earth Fault Protection and Power System Earthing

213

Appendix C Signal List

219

Appendix D Event Record Items

227

Appendix E Details of Relay Menu and LCD & Button Operation

231

Appendix F Case Outline

247

Appendix G Typical External Connection

249

Appendix H Relay Setting Sheet

257

Appendix I

273

Commissioning Test Sheet (sample)

Appendix J Return Repair Form

277

Appendix K Technical Data

281

Appendix L Symbols Used in Scheme Logic

289

Appendix M IEC60870-5-103: Interoperability

293

Appendix N Modbus: Interoperability

303

Appendix O Inverse Time Characteristics

323

Appendix P Ordering

329

The data given in this manual are subject to change without notice. (Ver.0.9)

6 F 2 S 0 7 5 8

1. Introduction
GRD140 series relays provide four stage non-directional and directional overcurrent protection
for distribution networks, and back-up protection for transmission and distribution networks.
The GRD140 series has three models and provides the following protection schemes in all models.
Directional overcurrent protection and directional zero phase sequence overcurrent
protection for earth fault with definite time or inverse time characteristics
Instantaneous directional overcurrent protection and instantaneous directional zero phase
sequence overcurrent protection for earth fault
Model 110 provides directional earth fault protection and directional sensitive earth fault
protection.
Models 400 and 430 provide three-phase directional phase fault protection and directional earth
fault protection. In Model 400, phase fault element and earth fault element are applied to the same
CT. In Model 430, the phase fault element and the earth fault element are applied to the different
CTs respectively, and the earth fault element is applied to the independent CT such as Core
balance CT etc. (See Appendix G.)
Models 420 provides three-phase directional phase fault protection, and directional earth and
sensitive earth fault protection.
All models include multiple, high accuracy, overcurrent protection elements (for phase and/or
earth fault) with inverse time and definite time delay functions. All phase, earth and sensitive earth
fault overcurrent elements can be independently subject to directional control.
In addition, GRD140 provides multi-shot, three phase auto-reclose, with independent sequences
for phase fault, and earth fault and sensitive earth fault. Auto-reclosing can also be triggered by
external protection devices.
Other protection functions are available according to model type, including thermal protection to
IEC60255-8, negative sequence overcurrent protection, under/overvoltage and
under/overfrequency protections. See Table 1.1.1 for details of the protection functions available
in each model.
All models provide continuous monitoring of internal circuits and of software. External circuits
are also monitored, by trip circuit supervision, CT and VT supervision, and CB condition
monitoring features.
A user-friendly HMI is provided through a backlit LCD, programmable LEDs, keypad and
menu-based operating system. PC access is also provided, either for local connection via a
front-mounted RS232 port, or for remote connection via a rear-mounted RS485 or fibre optic port.
The communication system allows the user to read and modify the relay settings, and to access
data gathered by the relays metering and recording functions.
Data available either via the relay HMI or communications ports includes the following functions.
The GRD140 series provides the following functions for all models.
Metering
Fault recording
Event recording
Disturbance recording (available via communications ports)

6 F 2 S 0 7 5 8
Table 1.1.1 shows the members of the GRD140 series and identifies the functions to be provided
by each member.
Table 1.1.1 Series Members and Functions
Model Number

GRD140 110

Directional Phase Fault O/C OC1 OC4 (67/50P, 67/51P)


Directional Earth Fault O/C EF1 EF4 (67/50N, 67/51N)

Directional Sensitive Earth Fault SEF1 SEF4(67/50N, 67/51N)

400

420

430(*)

Phase Undercurrent UC1, UC2 (37P)

Thermal Overload THM (49)

Directional Negative Phase Sequence Overcurrent NOC1, NOC2 (67/46)

Phase Overvoltage OV1, OV2 (59)

Phase Undervoltage UV1, UV2 (27)

Negative Phase Sequence Overvoltage NOV1, NOV2 (47)

Under/Overfrequency FRQ1 FRQ4 (81U/81O)

Broken Conductor BCD

Circuit Breaker Fail CBF (50BF)

Cold Load Protection

Fault Locator

CT Supervision

VT Supervision

Zero Phase Sequence Overvoltage ZOV1, ZOV2 (59N)

Auto-reclose (79)

Trip circuit supervision

Self supervision

CB State Monitoring

Trip Counter Alarm

Iy

Alarm

CB Operate Time Alarm

Four settings groups

Metering

Fault records

Event records

Disturbance records

IEC60870-5-103 Communication

Modbus Communication

(*): Input aux. CT for EF is different from that of Model 400.


Available functions above are depends on the scheme switch [APPL-CT] or [APPL-VT] setting in
models 400, 430 and 420.

CAUTION:
Do not change the APPL setting under service condition of the relay.

6 F 2 S 0 7 5 8

2. Application Notes
2.1

Overcurrent and Undercurrent Protection


2.1.1

Non-directional Overcurrent Protection


GRD140 provides distribution network protection with four-stage phase fault and earth fault
overcurrent elements OC1 to OC4, EF1 to EF4, sensitive earth fault elements SEF1 to SEF4, and
two-stage negative sequence overcurrent elements NOC1 and NOC2 which can be enabled or
disabled by scheme switch setting. The OC1, EF1 and SEF1 elements have selective inverse time
and definite time characteristics. The protection of local and downstream terminals is coordinated
with the current setting, time setting, or both.
The characteristic of overcurrent elements are as follows:

Stage 4

Stage 1

Note: NOC provides two stage overcurrent elements.

Figure 2.1.1

Characteristic of Overcurrent Elements

2.1.1.1 Inverse Time Overcurrent Protection


In a system for which the fault current is practically determined by the fault location, without
being substantially affected by changes in the power source impedance, it is advantageous to use
inverse definite minimum time (IDMT) overcurrent protection. This protection provides
reasonably fast tripping, even at a terminal close to the power source where the most severe faults
can occur.
Where ZS (the impedance between the relay and the power source) is small compared with that of
the protected section ZL, there is an appreciable difference between the current for a fault at the far
end of the section (ES/(ZS+ZL), ES: source voltage), and the current for a fault at the near end
(ES/ZS). When operating time is inversely proportional to the current, the relay operates faster for
a fault at the end of the section nearer the power source, and the operating time ratio for a fault at
the near end to the far end is ZS/(ZS + ZL).
The resultant time-distance characteristics are shown in Figure 2.1.2 for radial networks with
several feeder sections. With the same selective time coordination margin TC as the download
section, the operating time can be further reduced by using a more inverse characteristic.

10

6 F 2 S 0 7 5 8
Operate time

TC

TC

Figure 2.1.2 Time-distance Characteristics of Inverse Time Protection

The inverse time overcurrent protection elements have the IDMT characteristics defined by
equation (1):

+ c
t = TMS
a

I Is 1

( )

(1)

where:
t = operating time for constant current I (seconds),
I = energising current (amps),
Is = overcurrent setting (amps),
TMS = time multiplier setting,
k, a, c = constants defining curve.
Nine curve types are available as defined in Table 2.1.1. They are illustrated in Figure 2.1.3.
Any one curve can be selected for each IDMT element by scheme switch [MC].
Table 2.1.1 Specification of IDMT Curves
Curve Type (IEC 60255-151)

Curve Description

tr

IEC Normal Inverse (NI)

0.14

0.02

IEC Very Inverse (VI)

13.5

IEC Extremely Inverse (EI)

80

UK Long Time Inverse (LTI)

120

IEEE Moderately Inverse (MI)

0.0515

0.02

0.114

4.85

IEEE Very Inverse (VI)

19.61

0.491

21.6

IEEE Extremely Inverse (EI)

28.2

0.1217

29.1

US CO8 Inverse

5.95

0.18

5.95

US CO2 Short Time Inverse

0.02394

0.02

0.01694

2.261

Note: tr, b are used to define the reset characteristic. Refer to equation (2).

In addition to above nine curve types, GRD140 can provide a user configurable IDMT curve. If
required, set the scheme switch [MC] to CON and set the curve defining constants k, a, c.

11

6 F 2 S 0 7 5 8
The following table shows the setting ranges of the curve defining constants.
Curve defining constants

Range

Step

0.000 30.000

0.001

0.00 5.00

0.01

0.000 5.000

0.001

tr(kr)

0.000 30.000

0.001

0.00 5.00

0.01

IEC/UK Inverse Curves


(Time Multiplier = 1)

IEEE/US Inverse Curves


(Time Multiplier = 1)

1000

100

100

Operating Time (s)

Operating Time (s)

10

10
LTI
NI
1

MI
VI

VI

CO2
CO8

EI

EI
0.1

0.1
1

10

100

10

100

Current (Multiple of Setting)

Current (Multiple of Setting)

Figure 2.1.3

IDMT Characteristics

Programmable Reset Characteristics


OC1, EF1 and SEF1 have a programmable reset feature: instantaneous, definite time delayed, or
dependent time delayed reset. (Refer to Appendix A for a more detailed description.)
Instantaneous resetting is normally applied in multi-shot auto-reclosing schemes, to ensure correct
grading between relays at various points in the scheme.
The inverse reset characteristic is particularly useful for providing correct coordination with an
upstream induction disc type overcurrent relay.
The definite time delayed reset characteristic may be used to provide faster clearance of
intermittent (pecking or flashing) fault conditions.

12

6 F 2 S 0 7 5 8
Definite time reset
The definite time resetting characteristic is applied to the IEC/IEEE/US operating characteristics.
If definite time resetting is selected, and the delay period is set to instantaneous, then no
intentional delay is added. As soon as the energising current falls below the reset threshold, the
element returns to its reset condition.
If the delay period is set to some value in seconds, then an intentional delay is added to the reset
period. If the energising current exceeds the setting for a transient period without causing tripping,
then resetting is delayed for a user-definable period. When the energising current falls below the
reset threshold, the integral state (the point towards operation that it has travelled) of the timing
function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.
Dependent time reset
The dependent time resetting characteristic is complied with IEC 60255-151 depending time reset
characteristic, and is defined by the following equation:

tr

t = RTMS
b
I
1 I S

(2)

where:
t = time required for the element to reset fully after complete operation (seconds),
I = energising current (amps),
Is = overcurrent setting (amps),
tr(kr) = time required to reset fully after complete operation when the energising current is
zero (see Table 2.1.1),
RTMS = reset time multiplier setting.
b = constants defining curve.
Figure 2.1.4 illustrates the dependent time reset characteristics.

13

6 F 2 S 0 7 5 8

IEEE Reset Curves


(Time Multiplier = 1)
1000.00

Time (s)

100.00

EI
VI
10.00
CO8
MI
CO2

1.00
0.1
1
Current (Multiple of Setting)

Figure 2.1.4

Dependent Time Reset Characteristics

2.1.1.2 Definite Time Overcurrent Protection


In a system in which the fault current does not vary a great deal in relation to the position of the
fault, that is, the impedance between the relay and the power source is large, the advantages of the
IDMT characteristics are not fully utilised. In this case, definite time overcurrent protection is
applied. The operating time can be constant irrespective of the magnitude of the fault current.
The definite time overcurrent protection consists of instantaneous overcurrent measuring elements
and delayed pick-up timers started by the elements, and provides selective protection with graded
setting of the delayed pick-up timers. Thus, the constant time coordination with the downstream
section can be maintained as shown in Figure 2.1.5. As is clear in the figure, the nearer to the
power source a section is, the greater the delay in the tripping time of the section. This is
undesirable particularly where there are many sections in the series.
Operate time

TC
TC

Figure 2.1.5 Definite Time Overcurrent Protection

14

6 F 2 S 0 7 5 8
2.1.1.3 Instantaneous Overcurrent Protection
In conjunction with inverse time overcurrent protection, additional overcurrent elements provide
instantaneous or definite time overcurrent protection.
OC1 to OC4 and EF1 to EF4 are phase fault and earth fault protection elements, respectively. Each
element is programmable for instantaneous or definite time delayed operation. (In case of
instantaneous operation, the delayed pick-up timer is set to 0.00.) The phase fault elements operate
on a phase segregated basis, although tripping is for three phase only.
Selective Instantaneous Overcurrent Protection
When they are applied to radial networks with several feeder sections where ZL (impedance of the
protected line) is large enough compared with ZS (the impedance between the relay and the power
source), and the magnitude of the fault current for a local end fault is much greater (3 times or
more, or (ZL+ZS)/ZS3, for example) than that for a remote end fault under the condition that ZS
is maximum, the pick-up current can be set sufficiently high so that the operating zone of the
elements do not reach the remote end of the feeder, and thus instantaneous and selective protection
can be applied.
This high-set overcurrent protection is applicable and effective particularly for feeders near the
power source where the setting is feasible, but the longest tripping times would otherwise have to
be accepted.
As long as the associated inverse time overcurrent protection is correctly coordinated, the
instantaneous protection does not require setting coordination with the downstream section.
Figure 2.1.6 shows operating times for instantaneous overcurrent protection in conjunction with
inverse time overcurrent protection. The shaded area shows the reduction in operating time by
applying the instantaneous overcurrent protection. The instantaneous protection zone decreases as
ZS increases.
Operate time

TC

TC

Figure 2.1.6 Conjunction of Inverse and Instantaneous Overcurrent Protection

The current setting is set 1.3 to 1.5 times higher than the probable maximum fault current in the
event of a fault at the remote end. The maximum fault current for elements OC1 to OC4 is
obtained in case of three-phase faults, while the maximum fault current for elements EF1 to EF4 is
obtained in the event of single phase earth faults.
2.1.1.4 Staged Definite Time Overcurrent Protection
When applying inverse time overcurrent protection for a feeder system as shown in Figure 2.1.7,
well coordinated protection with the fuses in branch circuit faults and high-speed protection for
the feeder faults can be provided by adding staged definite time overcurrent protection with
time-graded OC2 and OC3 or EF2 and EF3 elements.

15

6 F 2 S 0 7 5 8
Fuse

GRD140

Figure 2.1.7

Feeder Protection Coordinated with Fuses

Configuring the inverse time element OC1 (and EF1) and time graded elements OC2 and OC3 (or
EF2 and EF3) as shown in Figure 2.1.8, the characteristic of overcurrent protection can be
improved to coordinate with the fuse characteristic.
Time (s)

OC1
OC2

OC3

Fuse

Current (amps)

Figure 2.1.8

Staged Definite Time Protection

16

6 F 2 S 0 7 5 8
2.1.2

Directional Overcurrent Protection


In a system including parallel feeder circuits, ring main circuits or sources at both line terminals,
the fault current at the relay location can flow in either direction. In such a case, directional control
should be added to overcurrent elements.
GRD140 provides directional control for phase fault and earth fault overcurrent elements OC1 to
OC4, EF1 to EF4, SEF1 to SEF4, NOC1 and NOC2 which can be enabled or disabled by scheme
switch setting. The directional characteristic can be selected to Forward or Reverse or Non
by scheme switch setting [-DIR]. The OC1, EF1 and SEF1 elements have selective inverse
time and definite time characteristics.

2.1.2.1 Application of Directional Overcurrent Protection


Parallel Feeder Circuits
If non-directional protection were applied to the circuit shown in Figure 2.1.9, then a fault at F
would result in both feeders being tripped at points A and B, and total loss of supply to the load.
Directional relays can be applied to look back into the feeder, thereby ensuring that only the faulty
feeder is disconnected. The relays at A and B would normally be set to operate at 50% of the full
load current of the circuit, via their inverse time elements OC1 and EF1, with a directional
characteristic looking in the direction shown by the arrows.
The various overcurrent elements of GRD140 are independently programmable for directional
operation. Therefore, elements OC2 and EF2 could be set for non-directional operation to provide
time-delayed back-up protection for the load.
A

GRD140

Load

GRD140

Non-directional

Directional
B

GRD140

GRD140

Non-directional

Figure 2.1.9

Directional

Application of GRD140 to Parallel Feeders

Ring Main Circuits


A ring main circuit is commonly protected by directional overcurrent relays, since current may
flow in either direction past the relaying points. The normal grading procedure is applied
separately in both the clockwise and anti-clockwise directions. Conventionally, two directional
relays would be required at each load connection point, one for each direction.
A simple system is illustrated in Figure 2.1.10 showing definite time grading, although inverse
time can also be applied. Non-directional relays are applied at the in-feeds to the ring. All other
protections are directional relays. It can be seen that a fault at F is cleared by tripping at A in 1.0s
and at B in 0.4s.
Alternatively, since GRD140 provides multiple, independent bi-directional overcurrent stages, a
scheme could be implemented in which a single relay can perform the necessary protection
functions in both directions at each load connection point. Each GRD140 overcurrent element can
be programmed with different settings for forward and reverse direction, thus allowing correct
grading to be achieved in both the clockwise and anti-clockwise directions.

17

6 F 2 S 0 7 5 8

0.4s

GRD140

1.0s

GRD140

GRD140

GRD140

0.1s

0.7s

GRD140
1.3s
Non-directional

GRD140

0.4s

GRD140

1.0s

GRD140

GRD140

0.1s

GRD140

1.3s
Non-directional

Figure 2.1.10

0.7s

Protection of a Ring Main Circuit

Power Systems with Sources at both Line Terminals


In power systems with sources at both line terminals as shown in Figure 2.1.11, the fault current
flows in from both terminals.

G1

G2
F2

Figure 2.1.11

F1

Protection of a power system with sources at both line terminals

The protection is performed by setting the directional element at points 1, 2 and 3 which operates
only when the fault current (F1: solid lines) flows in from source G1 and at points a, b and c which
operates only when the fault current (F2: dotted lines) flows in from source G2, with grading provided
by time delays.

18

6 F 2 S 0 7 5 8
2.1.2.2 Directional Characteristics
Figure 2.1.12 illustrates the directional characteristic, with the forward operate zone shaded. The
reverse zone is simply a mirror image of the forward zone. The forward operate zone or reverse
operate zone is selectable by the scheme switch [OC-DIR], [EF-DIR], [SE-DIR] and [NC-DIR].
As shown in Figure 2.1.13, each directional characteristic is composed of forward directional
characteristic, reverse directional characteristic and overcurrent thresholds.
Boundary of Operation
(leading)

CA + 90

Boundary of Operation
CA + 90

+87.5 (leading)

CA + 60

CA + 60

CA + 30

CA + 30

10 x Is

10 x Is
5 x Is

5 x Is

CA - 180

CA - 180

CA

Reverse
Operate
Zone

Forward
Operate
Zone

CA

Reverse
Operate
Zone

CA - 30

Forward
Operate
Zone

CA - 60

CA - 60
CA - 90

CA - 90

Boundary of Operation
(lagging)

Boundary of Operation
- 87.5 (lagging)

CA: Characteristic angle

CA: Characteristic angle

(a) Characteristic of OC, EF and NOC

Figure 2.1.12

Reverse

CA - 30

(b) Characteristic of SEF

Directional Operate Characteristic

Directional (Forward)
(0 setting -95)

Stage
4
3
2
1

&

1-4
Forward

&

1-4
Reverse

+: lead angle
0

: lag angle

Vpol

Directional (Reverse)
(95 setting > 0)

Overcurrent (1-4 stage)


Forward
I

(Note) NOC provides stage 1 and 2 only.

: Characteristic angle

Figure 2.1.13

Directional element

Polarising signals of directional elements are shown in Figure 2.1.14. Polarisation for directional
phase overcurrent element OC is achieved by the 90 quadrature method, whereby each currents
phase angle is compared with the phase to phase voltage between the other two phases. Since the
voltage inputs to the relay will normally be connected phase to neutral, the polarising phase to
phase voltages are derived internally. The polarizing negative sequence voltage is also derived
internally. The polarizing zero sequence voltage is derived from a residual voltage or internally
depending on the model. Direction is determined in each case by measuring the phase angle of the
current with respect to a suitable polarising quantity. Table 2.1.2 summarises the current inputs
and their respective polarising signals. For details of the relationship between directional earth
fault protection and power system earthing, see Appendix B.

19

6 F 2 S 0 7 5 8
Ve

V2

Vbc90
Va

Va

Va

Ia

Vc

Vbc

I2

Vb

Vc

Vc

Vb

Vb

a2Vb

aVc

Ve

V2

Figure 2.1.14

Relationship between Current Input and Polarising signal

Table 2.1.2

Directional polarising signals

Directional element

Current Input

Polarising Signal

OC-A

Ia

Vbc90 (*)

OC-B

Ib

Vca90 (*)

OC-C

Ic

Vab90 (*)

EF

Ie

-Ve

SEF

Ise

-Ve

NOC

I2

-V2

Note (*): The quadrature voltages used for polarization the phase fault elements are automatically
phase-shifted by +90, such that they are in phase with the faulted phase voltage under
normal conditions. Therefore the faulted phase current will normally lag its polarizing
voltage under fault conditions and should be set with a negative characteristic angle. Refer to
section 2.1.3.3 for guidance on choice of settings.

In the event of a close up three phase fault, all three polarising signals will collapse below the
minimum threshold. Voltage memory provides a temporary polarising signal in these
circumstances. GRD140 maintains the polarising signal for a short period by reconstructing the
pre-fault voltages and judges the fault direction. After the voltage memory has disappeared, the
direction judgement is effective while the fault current flows as shown in Figure 2.1.15.
Phase difference calculation
|V||I|cos() 0

Amplitude calculation
|l|OCset

&

1
F/F
1

&

Amplitude calculation
|Vpol|Vset
(Note) OCset: Current setting
Vset : Voltage setting. In the case of OC and NOC, Vset = 1V fixed.

Figure 2.1.15

Direction Judgement after Disappearance of Voltage Memory

20

OC
NOC
EF
SEF

6 F 2 S 0 7 5 8
To cover applications where a 2:1:1 current distribution(*) may be experienced, it is possible to
programme the directional phase fault protection such that a trip output will only be given if two or
more phases detect fault current in the same operate zone.
Note (*): Only one-phase is in heavy load condition.

2.1.3

Scheme Logic

2.1.3.1 Phase overcurrent protection


Figures 2.1.16 to 2.1.19 show the scheme logic of the non-directional and directional phase
overcurrent protection OC1 to OC4.
Note:

For the symbols used in the scheme logic, see Appendix L.

The directional control characteristic can be selected to Forward (FWD) or Reverse (REV) or
Non by scheme switch setting [OC-DIR] (not shown in Figures 2.1.16 to 2.1.19).
The OC1 protection provides selective definite time or inverse time characteristic as shown in
Figure 2.1.16. The definite time protection is selected by setting [MOC1] to DT and trip signal
OC1 TRIP is given through the delayed pick-up timer TOC1. The inverse time protection is
selected by setting [MOC1] to any one of IEC, IEEE, US or CON and then setting
[MOC1C] according to the required IDMT characteristic, and trip signal OC1 TRIP is given.
Figure 2.1.17 to Figure 2.1.19 show the scheme logic of the definite time phase overcurrent
protection OC2 to OC4. The OC2 to OC4 give trip and alarm signals OC2 TRIP, OC3 TRIP and
OC4 ALARM through the delayed pick-up timers TOC2 to TOC4 respectively.
The trip mode of OC1 TRIP to OC4 ALARM can be selected by setting [OCTP] to 3POR(any
one of 3 phases) or 2OUTOF3(2 out of 3 phases) gate. When the 2OUTOF3 selected, the trip
signal is not issued during a single-phase fault. The switch [OCTP] is common for OC1 to OC4
protection.
The OC1 to OC4 protection provide the delayed trip control function (instantaneous trip or
delayed trip) according to the trip shot number for a fault such as a reclose-on-to-fault in
multi-shot reclosing (see Section 2.5.). If a permanent fault occurs, the following tripping (Trip)
and reclose initiating (ARC) is executed:
Trip (1st) ARC (1st) Trip (2nd) ARC (2nd) Trip (3rd) ARC (3rd) Trip (4th)
ARC (4th) Trip (5th) ARC (5th) Trip (6th)
Each tripping is selected by setting [OC-TP] to any one of Inst(instantaneous trip),
Set(delayed trip by TOC and [MOC1] setting) or Off(blocked).
Note:

Though the delayed trip control logic is not shown in Figures 2.1.17 to 2.1.19, the OC2, OC3
and OC4 also provide the same logic.

The OC1HS (high speed) element is used for blocked overcurrent protection. See Section 2.1.3.6.
GRD140 incorporates a VT failure supervision function (VTFS). (See Section 3.3.4.) When the
VTFS detects a VT failure, it can alarm and block the OC1 to OC4 protection by the scheme
switch [VTF OC1-BLK] to [VTF OC4-BLK] respectively.
The OC1 to OC4 protection can be disabled by the scheme switches [OC1EN] to [OC4EN] or the
binary input signals OC1 BLOCK to OC4 BLOCK respectively.

21

6 F 2 S 0 7 5 8
TOC1

&

&

&

&

&

&

OC1 B
C

OC1-A TRIP

OC1-B TRIP
OC1-C TRIP

0.00 - 300.00s

&

OC1
B
(INST)
C

&

1
&

&

&

&
&
[OCTP]

[OC1-EN]
+ "ON"

OC1 ON

3POR
2OUTOF3

Delayed trip control:

"US"

SHOT NUM1

"DT"

From Figure 2.5.1.

&

"CON"

OC1-INST

SHOT NUM6

"3POR"
"2OUTOF3"

"IEEE"

OC1 BLOCK by BI

&

[MOC1]
"IEC"

&

&

&

OC1-INST

OC1 TRIP

&

&

Non VTF
[VTF OC1-BLK]
+ "OFF"

1
[OC1-TP1]
+

OC1-A HS

OC1HS B

OC1-B HS

OC1 ON

"Inst"
"Set"
"OFF"

[OC1-TP6]
+

Figure 2.1.16

&

OC1-C HS

OC1 OFF

"Inst"
"Set"
"OFF"

&

OC1 Phase Fault Overcurrent Protection


TOC2

&

OC2 B

&

&

[OC2-EN]
+ "ON"

OC2-A TRIP

OC2-B TRIP

OC2-C TRIP

1
0.00 - 300.00s

OC2 TRIP

OC2 ON
OC2 BLOCK by BI

&

&

Non VTF
[VTF OC2-BLK]
+ "OFF"

&

&
&

&

[OCTP]
+

Figure 2.1.17

"3POR"
"2OUTOF3"

OC2 Phase Fault Overcurrent Protection

22

&

&

&

OC2-INST

3POR
2OUTOF3

6 F 2 S 0 7 5 8
TOC3

&

OC3 B

&

&

[OC3-EN]
+ "ON"

OC3-A TRIP

OC3-B TRIP

OC3-C TRIP

1
0.00 - 300.00s

OC3 TRIP

OC3 ON
OC3 BLOCK by BI

&

&

Non VTF

&

&

[VTF OC3-BLK]
+ "OFF"

&

&

[OCTP]
+

Figure 2.1.18

&

&

&

OC3-INST

"3POR"

3POR
2OUTOF3

"2OUTOF3"

OC3 Definite Time Phase Overcurrent Protection


TOC4

&

OC4 B

&

&

[OC4-EN]
+ "ON"

OC4-A ALARM

OC4-B ALARM

OC4-C ALARM

1
0.00 - 300.00s

OC4 ALARM

OC4 ON
OC4 BLOCK by BI

&

&

Non VTF

&

&

[VTF OC4-BLK]
+ "OFF"

&

&

[OCTP]
+

Figure 2.1.19

&

&

&

OC4-INST

"3POR"
"2OUTOF3"

3POR
2OUTOF3

OC4 Definite Time Phase Overcurrent Protection

2.1.3.2 Earth fault protection


Figure 2.1.20 to Figure 2.1.23 show the scheme logic of the non-directional and directional earth
fault protection EF1 to EF4.
The directional control characteristic can be selected to FWD or REV or Non by scheme
switch setting [EF-DIR] (not shown in Figures 2.1.20 to 2.1.23).
The EF1 protection provides selective definite time or inverse time characteristic as shown in
Figure 2.1.20. The definite time protection is selected by setting [MEF1] to DT, and the trip
signal EF1 TRIP is given through the delayed pick-up timer TEF1. The inverse time protection is
selected by setting [MEF1] to any one of IEC, IEEE, US or CON and then setting
[MEF1C] according to the required IDMT characteristic, and the trip signal EF1 TRIP is given.
Figure 2.1.21 to Figure 2.1.23 show the scheme logic of the definite time earth fault protection
EF2 to EF4. The EF2 to EF4 give trip and alarm signals EF2 TRIP, EF3 TRIP and EF4 ALARM

23

6 F 2 S 0 7 5 8
through the delayed pick-up timers TEF2, TEF3 and TEF4 respectively.
The EF1 to EF4 protection provide the delayed trip control function (instantaneous trip or delayed
trip) according to the trip shot number for a fault such as a reclose-on-to-fault in multi-shot
reclosing (see Section 2.5). If a permanent fault occurs, the following tripping (Trip) and reclose
initiating (ARC) is executed:
Trip (1st) ARC (1st) Trip (2nd) ARC (2nd) Trip (3rd) ARC (3rd) Trip (4th)
ARC (4th) Trip (5th) ARC (5th) Trip (6th)
Each tripping is selected by setting [EF-TP] to any one of Inst(instantaneous trip),
Set(delayed trip by TEF and [MEF1] setting) or Off(blocked).
Note:

Though the delayed trip control logic is not shown in Figures 2.1.21 to 2.1.23, the EF2, EF3
and EF4 also provide the same logic.

EF1HS (high speed) element is used for blocked overcurrent protection. See Section 2.1.3.6.
GRD140 incorporates a VT failure supervision function (VTFS) and a CT failure supervision
function (CTFS). When the VTFS or CTFS detects a VT failure or a CT failure, it can alarm and
block the EF1 to EF4 protection by the scheme switch [VTF EF1-BLK] to [VTF EF4-BLK] or
[CTF EF1-BLK] to [CTF EF4-BLK] respectively.
The EF1 to EF4 protection can be disabled by the scheme switches [EF1EN] to [EF4EN] or the
binary input signals EF1 BLOCK to EF4 BLOCK respectively.
EF1-REV

EF1

&

&

EF1 TRIP

0.00 - 300.00s

EF1
(INST)
EF1-INST

&

&

EF1-CR

CURREV-EF1

TEF1

&
&
1

[MEF1]
+

"IEC"

[EF2-EN]
+ "OFF"

"IEEE"

EF1 Permission by BI

EF1 ON
Delayed trip control:

"US"

SHOT NUM1

"CON"

Non VTF
[VTF EF1-BLK]
+ "OFF"

From Figure 2.5.1.

SHOT NUM6

&

1
[EF1-TP1]
+

Non CTF
[CTF EF1-BLK]
+ "OFF"

EF1HS

"DT"
EF1 BLOCK by BI

[EF1-EN]
+ "ON"

EF1 HS
[EF1-TP6]
+

Figure 2.1.20

&

&

"Inst"
"Set"
"OFF"

"Inst"
"Set"
"OFF"

EF1 OFF

&

&

EF1 Earth Fault Protection

24

EF1-INST

EF1 ON

6 F 2 S 0 7 5 8
EF2-REV

EF2

&
[EF2-EN]
+ "OFF"

EF2-CR

CURREV-EF2

TEF2

&

EF2 TRIP

&

0.00 - 300.00s

EF2 ON

&

EF2-INST

EF2 BLOCK by BI

&

Non VTF
[VTF EF2-BLK]
+ "OFF"

EF2 Permission by BI

[EF2-EN]
+ "ON"

Non CTF
[CTF EF2-BLK]
+

"OFF"

Figure 2.1.21

EF2 Earth Fault Protection

EF3-REV

EF3

&
[EF3-EN]
+ "OFF"

EF3-CR

CURREV-EF3

TEF3

&

EF3 TRIP

&

0.00 - 300.00s

EF3 ON

&

EF3-INST
EF3 BLOCK by BI

&

Non VTF
[VTF EF3-BLK]
+ "OFF"

EF3 Permission by BI

Non CTF
[CTF EF3-BLK]
+

[EF3-EN]
+ "ON"

"OFF"

Figure 2.1.22

EF3 Definite Time Earth Fault Protection


EF4-REV

EF4

&
[EF4-EN]
+ "OFF"

EF4-CR

CURREV-EF4

TEF4

&

&

0.00 - 300.00s

EF4 ON

&

EF4-INST
EF4 BLOCK by BI

Non VTF
[VTF EF4-BLK]
+ "OFF"

&
EF4 Permission by BI

[EF4-EN]
+ "ON"

Non CTF
[CTF EF4-BLK]
+

"OFF"

Figure 2.1.23

EF4 Definite Time Earth Fault Protection

25

EF4 ALARM

6 F 2 S 0 7 5 8
Earth fault command protection
GRD140 can provide the command protection. These protections require two stage EF elements,
one is for tripping and the other is for blocking or for current reverse detection.
Current reverse detection logic is provided with all stages EF1 to EF4 for command protection as
shown in Figure 2.1.24. In response to power system faults on parallel lines, sequential opening of
the circuit breaker may cause a fault current reversal on healthy lines. This logic is provided to
prevent false operation in the worst case. When EF reverse zone operates and EF-REV outputs
for 20ms or more, then even if the EF forward zone subsequently operates, CURREV-EF
becomes 0 to block tripping of the local terminal relay or transmission of the trip permission
signal, for a time set by the TREBK setting.
The stage used for current reverse detection should be selected by the scheme switch [CURREV].
The selected stage should have scheme switch [EF-DIR] set to REV.
TREBK

EF1-REV
EF2-REV
EF3-REV
EF4-REV

&

&

&

&

&

&

&

&

0.02 s

t
1

0.00 - 10.00s

[EF1-DIR] "REV"
+

[EF1-DIR] "FWD"
+

[EF2-DIR] "REV"
+

[EF2-DIR] "FWD"
+

[EF3-DIR] "REV"
+
[EF4-DIR]
"REV"
+
CURREV
+

&

CURREV-EF1

&

CURREV-EF2

&

CURREV-EF3

&

CURREV-EF4

[EF3-DIR] "FWD"
+

"1"
"2"
"3"
"4"

[EF4-DIR] "FWD"
+

Figure 2.1.24

Current Reverse Detection

2.1.3.3 Setting for OC and EF protection


The table shows the setting elements necessary for the phase overcurrent and earth fault protection
and their setting ranges.
Element

Range

Step

Default

Remarks

OCCT

1 - 20000

400

CT ratio setting for OC (*2)

OC

95 95

45

OC characteristic angle

OC1

0.1 25.0 A
(0.02 5.00 A)(*1)

0.1 A
(0.01 A)

5.0 A
(1.00 A)

OC1 threshold setting

TOC1

0.00 300.00 s

0.01 s

1.00 s

OC1 definite time setting. Required if


[MOC1] = DT.

TOC1M

0.010 1.500

0.001

1.000

OC1 time multiplier setting. Required if


[MOC1] = IEC, IEEE or US.

TOC1R

0.0 300.0 s

0.1 s

0.0 s

OC1 definite time delayed reset. Required if


[OC1R] = DEF.

TOC1RM

0.010 1.500

0.001

1.000

OC1 dependent time delayed reset time


multiplier. Required if [OC1R] = DEP.

OC2

0.1 25.0 A
(0.02 5.00 A)

0.1 A
(0.01 A)

5.0 A
(1.00 A)

OC2 threshold setting

TOC2

0.00 300.00 s

0.01 s

1.00 s

OC2 definite time setting.

OC3

0.1 250.0 A
(0.02 50.00 A)

0.1 A
(0.01 A)

50.0 A
(10.00 A)

OC3 threshold setting

26

6 F 2 S 0 7 5 8
Element

Range

Step

Default

Remarks

TOC3

0.00 300.0 s

0.01 s

1.00 s

OC3 definite time setting

OC4

0.1 250.0 A
(0.02 50.00 A)

0.1 A
(0.01 A)

100.0 A
(20.00 A)

OC4 threshold setting

TOC4

0.0 300.0 s

0.01 s

1.00 s

OC4 definite time setting

EFCT

1 - 20000

400

CT ratio setting for EF (*2)

EF

95 95

45

EF characteristic angle

EFV

0.5 100.0 V

0.1 V

3.0 V

EF ZPS voltage level

EF1

0.1 25.0 A
(0.02 5.00 A)

0.1 A
(0.01 A)

1.5 A
(0.30 A)

EF1 threshold setting

TEF1

0.00 300.00 s

0.01 s

1.00 s

EF1 definite time setting. Required if [MEF1]


= DT.

TEF1M

0.010 1.500

0.001

1.000

EF1 time multiplier setting. Required if


[MEF1] = IEC, IEEE or US.

TEF1R

0.0 300.0 s

0.1 s

0.0 s

EF1 definite time delayed reset. Required if


[EF1R] = DEF.

TEF1RM

0.010 1.500

0.001

1.000

EF1 dependent time delayed reset time


multiplier. Required if [EF1R] = DEP.

EF2

0.1 25.0 A
(0.02 5.00 A)

0.1 A
(0.01 A)

15.0 A
(3.00 A)

EF2 threshold setting for Models 110, 400


and 420

0.1 25.0 A
(0.02 5.00 A)

0.1 A
(0.01 A)

5.00 A
(1.00 A)

EF2 threshold setting for Model 430

TEF2

0.00 300.00 s

0.01 s

1.00 s

EF2 definite time setting.

EF3

0.1 250.0 A
(0.02 50.00 A)

0.1 A
(0.01 A)

25.0 A
(5.00 A)

EF3 threshold setting for Models 110, 400


and 420

0.1 40.0 A
(0.02 8.00 A)

0.1 A
(0.01 A)

15.0 A
(3.00 A)

EF3 threshold setting for Model 430

TEF3

0.00 300.00 s

0.01 s

1.00 s

EF3 definite time setting

EF4

0.1 250.0 A
(0.02 50.00 A)

0.1 A
(0.01 A)

50.0 A
(10.00 A)

EF4 threshold setting for Models 110, 400


and 420

0.1 40.0 A
(0.02 8.00 A)

0.1 A
(0.01 A)

30.0 A
(6.00 A)

EF4 threshold setting for Model 430

TEF4

0.00 300.00 s

0.01 s

1.00 s

EF4 definite time setting

TREBK

0.00 10.00 s

0.01 s

0.10

Current reverse blocking time

[OC1EN]

Off / On

On

OC1 Enable

[OC1-DIR]

FWD/REV/NON

FWD

OC1 directional characteristic

[MOC1]

DT/IEC/IEEE/US/C

DT

OC1 time characteristic

[MOC1C]
MOC1C-IEC
MOC1C-IEEE
MOC1C-US

OC1 inverse curve type.


NI / VI / EI / LTI
MI / VI / EI
CO2 / CO8

NI
MI
CO2

Required if [MOC1] = IEC.


Required if [MOC1] = IEEE.
Required if [MOC1] = US.

[OC1R]

DEF / DEP

DEF

OC1 reset characteristic. Required if


[MOC1] = IEEE or US.

[VTF-OC1BLK]

Off / On

Off

VTF block enable

[OC2EN]

Off / On

Off

OC2 Enable

[OC2-DIR]

FWD/REV/NON

FWD

OC2 directional characteristic

27

6 F 2 S 0 7 5 8
Element

Range

[VTF-OC2BLK]

Step

Default

Remarks

Off / On

Off

VTF block enable

[OC3EN]

Off / On

Off

OC3 Enable

[OC3-DIR]

FWD/REV/NON

FWD

OC3 directional characteristic

[VTF-OC3BLK]

Off / On

Off

VTF block enable

[OC4EN]

Off / On

Off

OC4 Enable

[OC4-DIR]

FWD/REV/NON

FWD

OC4 directional characteristic

[VTF-OC4BLK]

Off / On

Off

VTF block enable

[OCTP]

3POR / 2OUTOF3

3POR

OC trip mode

[EF1EN]

Off / On / POP

On

EF1 Enable

[EF1-DIR]

FWD/REV/NON

FWD

EF1 directional characteristic

[MEF1]

DT/IEC/IEEE/US/C

DT

EF1 time characteristic

[MEF1C]

EF1 inverse curve type.

MEF1C-IEC
MEF1C-IEEE
MEF1C-US

NI / VI / EI / LTI
MI / VI / EI
CO2 / CO8

NI
MI
CO2

Required if [MEF1] = IEC.


Required if [MEF1] = IEEE.
Required if [MEF1] = US.

[EF1R]

DEF / DEP

DEF

EF1 reset characteristic. Required if [MEF1]


= IEEE or US.

[VTF-EF1BLK]

Off / On

Off

VTF block enable

[CTF-EF1BLK]

Off / On

Off

CTF block enable

[EF2EN]

Off / On / POP

Off

EF2 Enable

[EF2-DIR]

FWD/REV/NON

FWD

EF2 directional characteristic

[VTF-EF2BLK]

Off / On

Off

VTF block enable

[CTF-EF2BLK]

Off / On

Off

CTF block enable

[EF3EN]

Off / On / POP

Off

EF3 Enable

[EF3-DIR]

FWD/REV/NON

FWD

EF3 directional characteristic

[VTF-EF3BLK]

Off / On

Off

VTF block enable

[CTF-EF3BLK]

Off / On

Off

CTF block enable

[EF4EN]

Off / On / POP

Off

EF4 Enable

[EF4-DIR]

FWD/REV/NON

FWD

EF4 directional characteristic

[VTF-EF4BLK]

Off / On

Off

VTF block enable

[CTF-EF4BLK]

Off / On

Off

CTF block enable

CURREV

Off / 1 / 2 / 3 / 4

Off

Current reverse detection

(*1) Current values shown in the parenthesis are in the case of a 1 A rating. Other current values are
in the case of a 5 A rating.
(*2) In Model 420, the settings of OCCT and EFCT are set to the same value.

[Setting Example of Command Protection]


The followings show a setting example of command protection when the EF1 is applied for
forward fault detection and the EF2 is applied for reverse fault detection.
(1) POP (Permissive overreach protection)
(a) Setting of EF element
EF1:

--- depends on power system condition

TEF1:

--- for time delay trip

28

6 F 2 S 0 7 5 8
EF1EN:

POP

EF1-DIR:

FWR

EF2:

TEF2:

0.00s

EF2EN:

POP

EF2-DIR:

REV

--- depends on power system condition

CURREV: 2
(b) Setting of BO (Binary Output)
The signal EF1-CR (No.285) is assigned to BOn. --- carrier signal send BO
(c) Setting of BI (Binary Input)
The EF1 protection permission is assigned to BIn. --- carrier signal receive BI
BIn SNS: Norm
(2) BOP (Blocking overreach protection)
(a) Setting of EF element
EF1:

--- depends on power system condition

TEF1:

--- for time delay trip

EF1EN:

POP

EF1-DIR:

FWR

EF2:

TEF2:

0.30s (minimum) --- coordination time for blocking carrier signal receiving

EF2EN:

POP

EF2-DIR:

REV

--- depends on power system condition

CURREV: 2
(b) Setting of BO (Binary Output)
The signal EF2-CR (No.286) is assigned to BOn. --- carrier signal send BO
(c) Setting of BI (Binary Input)
The EF1 protection permission is assigned to BIn. --- carrier signal receive BI
BIn SNS: Inv
[Time Overcurrent Protection Setting]
(1) Settings for Inverse Time Overcurrent Protection
Current setting
In Figure 2.1.25, the current setting at terminal A is set lower than the minimum fault current in the
event of a fault at remote end F1. Furthermore, when also considering backup protection for a fault
on the next feeder section, it is set lower than the minimum fault current in the event of a fault at
remote end F3.
To calculate the minimum fault current, phase-to-phase faults are assumed for the phase
overcurrent element, and phase to earth faults for residual overcurrent element, assuming the

29

6 F 2 S 0 7 5 8
probable maximum source impedance. When considering the fault at F3, the remote end of the
next section is assumed to be open.
The higher the current setting, the more effective the inverse characteristic. On the other hand, the
lower the setting, the more dependable the operation. The setting is normally 1 to 1.5 times or less
of the minimum fault current.
For grading of the current settings, the terminal furthest from the power source is set to the lowest
value and the terminals closer to the power source are set to a higher value.
The minimum setting of the phase overcurrent element is restricted so as not to operate for the
maximum load current, and that of the residual overcurrent element is restricted so as to not
operate on false zero-sequence current caused by an unbalance in the load current, errors in the
current transformer circuits, or zero-sequence mutual coupling of parallel lines.
A

F1

Figure 2.1.25

F2

F3

Current Settings in Radial Feeder

Time setting
Time setting is performed to provide selectivity in relation to the relays on adjacent feeders.
Consider the minimum source impedance when the current flowing through the relay reaches a
maximum. In Figure 2.1.25, in the event of a fault at F2, the operating time is set so that terminal A
may operate by time grading Tc behind terminal B. The current flowing in the relays may
sometimes be greater when the remote end of the adjacent line is open. At this time, time
coordination must also be kept.
The reason why the operating time is set when the fault current reaches a maximum is that if time
coordination is obtained for a large fault current, then time coordination can also be obtained for
the small fault current as long as relays with the same operating characteristic are used for each
terminal.
The grading margin Tc of terminal A and terminal B is given by the following expression for a
fault at point F2 in Figure 2.1.25.
T c = T1 + T2 + Tm
where,

T1: circuit breaker clearance time at B


T2: relay reset time at A
Tm: time margin

(2) Settings of Definite Time Overcurrent Protection


Current setting
The current setting is set lower than the minimum fault current in the event of a fault at the remote
end of the protected feeder section. Furthermore, when also considering backup protection for a
fault in a next feeder section, it is set lower than the minimum fault current, in the event of a fault
at the remote end of the next feeder section.
Identical current values can be set for terminals, but graded settings are better than identical
settings, in order to provide a margin for current sensitivity. The farther from the power source the
terminal is located, the higher the sensitivity (i.e. the lower setting) that is required.
The minimum setting of the phase overcurrent element is restricted so as not to operate for the

30

6 F 2 S 0 7 5 8
maximum load current, and that of the residual overcurrent element is restricted so as to not
operate on false zero-sequence current caused by an unbalance in the load current, errors in the
current transformer circuits, or zero-sequence mutual coupling of parallel lines. Taking the
selection of instantaneous operation into consideration, the settings must be high enough not to
operate for large motor starting currents or transformer inrush currents.
Time setting
When setting the delayed pick-up timers, the time grading margin Tc is obtained in the same way
as explained in Settings for Inverse Time Overcurrent Protection.
(3) Directional Characteristic Angle Setting
OC Characteristic Angle
The quadrature voltages used for polarization of the phase fault directional elements are
automatically phase-shifted in GRD140 by +90, such that they are in phase with the
corresponding phase voltages under normal conditions. Under fault conditions, the faulted phase
current will lag its phase voltage (and hence its polarising voltage) by an angle dependent on the
system X/R ratio. Therefore, it is necessary to apply a negative characteristic angle to the phase
fault directional elements in order to obtain maximum sensitivity.
The characteristic angle is determined by the [OC] setting. The actual value chosen will depend
on the application, but recommended settings for the majority of typical applications are as
follows:
-60, for protection of plain feeders, or applications with an earthing point behind the relay
location.
-45, for protection of transformer feeders, or applications with an earthing point in front of the relay
location.

EF Characteristic Angle
When determining the characteristic angle for directional earth fault protection, the method of
system earthing must be considered. In solidly earthed systems, the earth fault current tends to lag
the faulted phase voltage (and hence the inverted residual voltage used for polarising) by a
considerable angle, due to the reactance of the source. In resistance earthed systems the angle will
be much smaller.
Commonly applied settings are as follows:
-60, for protection of solidly earthed transmission systems.
-45, for protection of solidly earthed distribution systems.
0 or -15, for protection of resistance earthed systems.
Further guidance on application of directional earth fault protection is given in appendix B.
2.1.3.4 Sensitive Earth Fault Protection
The sensitive earth fault (SEF) protection is applied for distribution systems earthed through high
impedance, where very low levels of fault current are expected in earth faults. Furthermore, the
SEF elements of GRD140 are also applicable to the standby earth fault protection and the high
impedance restricted earth fault protection of transformers.
GRD140 provides directional earth fault protection with more sensitive settings for use in
applications where the fault current magnitude may be very low. A 4-stage directional overcurrent
function is provided, with the first stage programmable for inverse time or definite time operation.
The second, third and fourth stages provide definite time operation.

31

6 F 2 S 0 7 5 8
The sensitive earth fault element includes a digital filter which rejects all harmonics other than the
fundamental power system frequency.
The sensitive earth fault quantity is measured directly, using a dedicated core balance earth fault
CT.
This input can also be used in transformer restricted earth fault applications, by the use of external
metrosils (varistors) and setting resistors.
The directional sensitive earth fault elements can be configured for directional operation in the
same way as the standard earth fault pole, by polarising against the residual voltage. An additional
restraint on operation can be provided by a Residual Power element RP, for use in protection of
power systems which utilise resonant (Petersen coil) earthing methods.
The SEF elements provide 20 times more sensitive setting ranges (10 mA to 1 A in 5A rating) than
the regular earth fault protection.
Since very low levels of current setting may be applied, there is a danger of unwanted operation
due to harmonics of the power system frequency, which can appear as residual current. Therefore
the SEF elements operate only on the fundamental component, rejecting all higher harmonics.
The SEF protection is provided in Model 110 and 420 series which have a dedicated earth fault
input circuit.
The element SEF1 provides inverse time or definite time selective two-stage overcurrent
protection. Stage 2 of the two-stage overcurrent protection is used only for the standby earth fault
protection. The SEF2 to SEF4 provide definite time overcurrent protection.
When SEF employs IEEE or USA inverse time characteristics, two reset modes are available:
definite time or dependent time resetting. If the IEC inverse time characteristic is employed,
definite time resetting is provided. For other characteristics, refer to Section 2.1.1.1.
In applications of SEF protection, it must be ensured that any erroneous zero-phase current is
sufficiently low compared to the fault current, so that a highly sensitive setting is available.
The erroneous current may be caused with load current due to unbalanced configuration of the
distribution lines, or mutual coupling from adjacent lines. The value of the erroneous current
during normal conditions can be acquired on the metering screen of the relay front panel.
The earth fault current for SEF may be fed from a core balance CT, but if it is derived from three
phase CTs, the erroneous current may be caused also by the CT error in phase faults. Transient
false functioning may be prevented by a relatively long time delay.
Standby earth fault protection
The SEF is energised from a CT connected in the power transformer low voltage neutral, and the
standby earth fault protection trips the transformer to backup the low voltage feeder protection,
and ensures that the neutral earthing resistor is not loaded beyond its rating. Stage 1 trips the
transformer low voltage circuit breaker, then stage 2 trips the high voltage circuit breaker(s) with a
time delay after stage 1 operates.
The time graded tripping is valid for transformers connected to a ring bus, banked transformers
and feeder transformers.
Restricted earth fault protection
The SEF elements can be applied in a high impedance restricted earth fault scheme (REF), for
protection of a star-connected transformer winding whose neutral is earthed directly or through
impedance.
As shown in Figure 2.1.26, the differential current between the residual current derived from the
three-phase feeder currents and the neutral current in the neutral conductor is introduced into the

32

6 F 2 S 0 7 5 8
SEF elements. Two external components, a stabilising resistor and a varistor, are connected as
shown in the figure. The former increases the overall impedance of the relay circuit and stabilises
the differential voltage, and the latter suppresses any overvoltage in the differential circuit.
F
Power
Transformer

Varistor

GRD140
SEF input

Stabilising
Resistor

Figure 2.1.26

High Impedance REF

Scheme Logic
Figure 2.1.27 to 2.1.30 show the scheme logic of directional sensitive earth fault protection. The
directional control characteristic can be selected to FWD or REV or Non by scheme switch
setting [SE-DIR].
Figure 2.1.27 shows the scheme logic of directional sensitive earth fault protection SEF1 with
inverse time or definite time selective two-stage overcurrent protection. The definite time
protection is selected by setting [MSE1] to DT. The element SEF1 is enabled for sensitive earth
fault protection and stage 1 trip signal SEF1 TRIP is given through the delayed pick-up timer
TSE1. The inverse time protection is selected by setting [MSE1] to either IEC, IEEE, US or
CON and then setting [MEF1C] according to the required IDMT characteristic. The element
SEF1 is enabled and stage 1 trip signal SEF1 TRIP is given.
Both protections provide stage 2 trip signal SEF1-S2 through a delayed pick-up timer TSE12.
When the standby earth fault protection is applied by introducing earth current from the
transformer low voltage neutral circuit, stage 1 trip signals are used to trip the transformer low
voltage circuit breaker. If SEF1 continues operating after stage 1 has operated, the stage 2 trip
signal can be used to trip the transformer high voltage circuit breaker(s).
SEF1HS (high speed) element is used for blocked overcurrent protection. See Section 2.1.3.6.
Figure 2.1.28 to Figure 2.1.30 show the scheme logic of the definite time sensitive earth fault
protection SEF2 to SEF4. SEF2 to SEF4 give trip and alarm signals SEF2 TRIP, SEF3 TRIP and
SEF4 ALARM through delayed pick-up timers TSE2, TSE3 and TSE4 respectively.
The SEF1 to SEF4 protection provide the delayed trip control function (instantaneous trip or
delayed trip) according to the trip shot number for a fault such as a reclose-on-to-fault in
multi-shot reclosing (see Section 2.5). If a permanent fault occurs, the following tripping (Trip)
and reclose initiating (ARC) is executed:
Trip (1st) ARC (1st) Trip (2nd) ARC (2nd) Trip (3rd) ARC (3rd) Trip (4th)
ARC (4th) Trip (5th) ARC (5th) Trip (6th)
Each tripping is selected by setting [SE-TP] to any one of Inst(instantaneous trip),
Set(delayed trip by TSE and [MSE1] setting) or Off(blocked).

33

6 F 2 S 0 7 5 8
Note:

Though the delayed trip control logic is not shown in Figures 2.1.28 to 2.1.30, the SEF2,
SEF3 and SEF4 also provide the same logic.

The SEF1 to SEF4 protections can be disabled by the scheme switches [SE1EN] to [SE4EN] or
binary input signals SEF1 BLOCK to SEF4 BLOCK. The SEF1 stage 2 trip of standby earth fault
protection can be disabled by the scheme switch [SE1S2].
SEF1

SEF1
INST

&

SEF1-INST

& 0.00 - 300.00s

[SE1EN]
+
"ON"

SEF1-S1
TRIP

&

[MSE1]
+

TSE1
0
t

&

&

[SE1S2]

"IEC"
+

"IEEE"

TSE12
0
t

&

"ON"

SEF1-S2
TRIP

0.00 - 300.00s

"US"

&

Non VTF

"DT"

RPF
RPR
[RPEN]
+

SEF1 BLOCK by BI

"CON"

&

&

&

&

VTF SE1-BLK
+ "OFF"

SEF1 ON

Delayed trip control:


SHOT NUM1

"ON"
"OFF"

[SE1 DIR] "REV"


"NON"
+

&

From
Figure 2.5.1.

"FWD"

[SE1-TP1]
+

[SE1-TP6]
+

Figure 2.1.27

&
SE1 OFF

"Inst"
"Set"
"OFF"

&

"Inst"
"Set"
"OFF"

&

RPR
[RPEN]
+

TSE2
0
t

&

[SE2EN]
+
"ON"

[SE2 DIR]
+

&

&

&

&

"ON"

1
SEF2 BLOCK by BI
VTF SE2-BLK
+ "OFF"

"FWD"
"REV"
"NON"

Figure 2.1.28

&

Non VTF

"OFF"

SEF1 ON

&

0.00 - 300.00s

RPF

SEF1 Sensitive Earth Fault Protection Scheme Logic

SEF2

SEF2-INST

SEF1-INST

SHOT NUM6

SEF1 HS

SEF1HS

&
SEF2 ON

SEF2 Sensitive Earth Fault Protection Scheme Logic

34

SEF2 TRIP

6 F 2 S 0 7 5 8
SEF3

&

TSE3
0
t

&

0.00 - 300.00s

[SE3EN]
+
"ON"

SEF3-INST

RPF
RPR
[RPEN]
+
[SE3 DIR]
+

&

&

&

&

1
SEF3 BLOCK by BI

&

Non VTF

"OFF"

VTF SE3-BLK
+ "OFF"

"FWD"
"REV"
"NON"

SEF3 ON

SEF3 Sensitive Earth Fault Protection Scheme Logic

SEF4

&

TSE4
0
t

&

0.00 - 300.00s

[SE4EN]
+
"ON"

SEF4-INST

RPF
RPR
[RPEN]
+
[SE4 DIR]
+

&

&

&

&

SEF4 ALARM

&

1
SEF4 BLOCK by BI

"ON"

&

Non VTF

"OFF"

VTF SE4-BLK
+ "OFF"

"FWD"
"REV"
"NON"

Figure 2.1.30

SEF3 TRIP

&

"ON"

Figure 2.1.29

SEF4 ON

SEF4 Sensitive Definite Earth Fault Protection Scheme Logic

Setting
The table below shows the setting elements necessary for the sensitive earth fault protection and
their setting ranges.
Element

Range

Step

Default

Remarks

SEFCT

1 - 20000

400

CT ratio setting for SEF

SE

95 95

SEF characteristic angle

SEV

0.5 100.0

0.1 V

3.0V

SEF ZPS voltage level

SE1

0.01 1.00 A
(0.002 0.200 A)(*)

0.01 A
(0.001 A)

0.05 A
(0.010 A)

SEF1 threshold setting

0.002 0.200 A

0.001 A

0.020 A

SEF1 threshold setting for Model


GRD140-420A-3-

TSE1M

0.010 1.500

0.001

1.000

SEF1 inverse time multiplier setting.


Required if [MSE1] = IEC, IEEE or US.

TSE1

0.00 300.00 s

0.01 s

1.00 s

SEF1 definite time setting. Required if


[MSE1] = DT.

TSE1R

0.0 300.0 s

0.1 s

0.0 s

SEF1 definite time delayed reset. Required


if [MSE1] = IEC or [SE1R] = DEF.

TSE1RM

0.010 1.500

0.001

1.000

SEF1 dependent time delayed reset time


multiplier. Required if [SE1R] = DEP.

35

6 F 2 S 0 7 5 8
Element

Range

Step

Default

Remarks

TSE12

0.00 300.00 s

0.01 s

1.00 s

SEF1 stage 2 definite time setting

SE2

0.01 1.00 A
(0.002 0.200 A)(*)

0.01 A
(0.001 A)

0.05 A
(0.010 A)

SEF2 threshold setting

0.002 0.200 A

0.001 A

0.020 A

SEF1 threshold setting for Model


GRD140-420A-3-

TSE2

0.00 300.00 s

0.01 s

1.00 s

SEF2 definite time setting.

SE3

0.01 1.00 A
(0.002 0.200 A)(*)

0.01 A
(0.001 A)

0.05 A
(0.010 A)

SEF3 threshold setting

0.002 0.200 A

0.001 A

0.020 A

SEF1 threshold setting for Model


GRD140-420A-3-

TSE3

0.00 300.00 s

0.01 s

1.00 s

SEF3 definite time setting.

SE4

0.01 1.00 A
(0.002 0.200 A)(*)

0.01 A
(0.001 A)

0.05 A
(0.010 A)

SEF4 threshold setting

0.002 0.200 A

0.001 A

0.020 A

SEF1 threshold setting for Model


GRD140-420A-3-

TSE4

0.00 300.00 s

0.01 s

1.00 s

SEF4 definite time setting.

RP

0.00 100.00 W
(0.00 20.00 W)(*)

0.01 W
(0.01 W)

0.00 W
(0.00 W)

Residual power sensitivity

0.00 20.00 W

0.01 W

0.00 W

Residual power sensitivity for Model


GRD140-420A-3-

[SE1EN]

Off / On

Off

SEF1 Enable

[SE1-DIR]

FWD / REV / NON

FWD

SEF1 directional characteristic

[MSE1]

DT/IEC/IEEE/US/CON

DT

SEF1 characteristic

[MSE1C]
MSE1C-IEC
MSE1C-IEEE
MSE1C-US

SEF1 inverse curve type.


NI / VI / EI / LTI
MI / VI / EI
CO2 / CO8

NI
MI
CO2

Required if [MSE1] = IEC.


Required if [MSE1] = IEEE.
Required if [MSE1] = US.

[SE1R]

DEF / DEP

DEF

SEF1 reset characteristic. Required if


[MSE1] = IEEE or US.

[SE1S2]

Off / On

Off

SEF1 stage 2 timer enable

[VTF-SE1BLK]

Off / On

Off

VTF block enable

[SE2EN]

Off / On

Off

SEF2 Enable

[SE2-DIR]

FWD / REV /NON

FWD

SEF2 directional characteristic

[VTF-SE2BLK]

Off / On

Off

VTF block enable

[SE3EN]

Off / On

Off

SEF3 Enable

[SE3-DIR]

FWD / REV / NON

FWD

SEF3 directional characteristic

[VTF-SE3BLK]

Off / On

Off

VTF block enable

[SE4EN]

Off / On

Off

SEF4 Enable

[SE4-DIR]

FWD / REV / NON

FWD

SEF4 directional characteristic

[VTF-SE4BLK]

Off / On

Off

VTF block enable

[RPEN]

Off / On

Off

Residual power block enable

(*) Current values shown in parenthesis are in the case of a 1 A rating. Other current values are in the
case of a 5 A rating.

SEF
SEF is set smaller than the available earth fault current and larger than the erroneous zero-phase

36

6 F 2 S 0 7 5 8
current. The erroneous zero-phase current exists under normal conditions due to the unbalanced
feeder configuration. The zero-phase current is normally fed from a core balance CT on the feeder,
but if it is derived from three phase CTs, the erroneous current may be caused also by the CT error
in phase faults.
The erroneous steady state zero-phase current can be acquired on the metering screen of the relay
front panel.
Directional SEF
Directional SEF protection is commonly applied to unearthed systems, and to systems earthed by
an inductance (Peterson Coil). Refer to appendix B for application guidance.
High impedance REF protection
CT saturation under through fault conditions results in voltage appearing across the relay circuit.
The voltage setting of the relay circuit must be arranged such that it is greater than the maximum
voltage that can occur under through fault conditions. The worst case is considered whereby one
CT of the balancing group becomes completely saturated, while the others maintain linear
operation. The excitation impedance of the saturated CT is considered to approximate a
short-circuit.
Saturated CT

Healthy CT
Transformer
Circuit
IF

Varistor

ZM0
RCT
VS

RS

Figure 2.1.31

Stabilising
Resistor

GRD140

RL

Maximum Voltage under Through Fault Condition

The voltage across the relay circuit under these conditions is given by the equation:
VS = IF(RCT + RL)
where:
VS = critical setting voltage (rms)
IF = maximum prospective secondary through fault current (rms)
RCT = CT secondary winding resistance
RL = Lead resistance (total resistance of the loop from the saturated CT to the relaying
point)
A series stabilising resistor is used to raise the voltage setting of the relay circuit to VS. No safety
margin is needed since the extreme assumption of unbalanced CT saturation does not occur in
practice. The series resistor value, RS, is selected as follows:
RS = VS / IS
IS is the current setting (in secondary amps) applied to the GRD140 relay. However, the actual
fault setting of the scheme includes the total current flowing in all parallel paths. That is to say that
the actual primary current for operation, after being referred to the secondary circuit, is the sum of
the relay operating current, the current flowing in the varistor, and the excitation current of all the
parallel connected CTs at the setting voltage. In practice, the varistor current is normally small

37

6 F 2 S 0 7 5 8
enough that it can be neglected. Hence:
IS IP / N 4Imag
where:
IS = setting applied to GRD140 relay (secondary amps)
IP = minimum primary current for operation (earth fault sensitivity)
N = CT ratio
Imag = CT magnetising (excitation) current at voltage VS
More sensitive settings for IS allow for greater coverage of the transformer winding, but they also
require larger values of RS to ensure stability, and the increased impedance of the differential
circuit can result in high voltages being developed during internal faults. The peak voltage, Vpk,
developed may be approximated by the equation:
Vpk = 2 2 Vk ( I F R S Vk )
where:
Vk = CT knee point voltage
IF = maximum prospective secondary current for an internal fault
When a Metrosil is used for the varistor, it should be selected with the following characteristics:
V = CI
where:
V = instantaneous voltage
I = instantaneous current
= constant, normally in the range 0.20 - 0.25
C = constant.
The C value defines the characteristics of the metrosil, and should be chosen according to the
following requirements:
1. The current through the metrosil at the relay voltage setting should be as low as possible,
preferably less than 30mA for a 1Amp CT and less than 100mA for a 5Amp CT.
2. The voltage at the maximum secondary current should be limited, preferably to 1500Vrms.
Restricted earth fault schemes should be applied with high accuracy CTs whose knee point voltage
Vk is chosen according to the equation:
Vk 2VS
where VS is the differential stability voltage setting for the scheme.
2.1.3.5 Negative Sequence Overcurrent Protection
The negative sequence overcurrent protection (NOC) is used to detect asymmetrical faults
(phase-to-phase and phase-to-earth faults) with high sensitivity in conjunction with phase
overcurrent protection and residual overcurrent protection. It also used to detect load unbalance
conditions.
Phase overcurrent protection must be set to lower sensitivity when the load current is large but
NOC sensitivity is not affected by magnitude of the load current, except in the case of erroneous
negative sequence current due to the unbalanced configuration of the distribution lines.

38

6 F 2 S 0 7 5 8
For some earth faults, only a small zero sequence current is fed while the negative sequence
current is comparatively larger. This is probable when the fault occurs at the remote end with a
small reverse zero sequence impedance and most of the zero sequence current flows to the remote
end.
In these cases, NOC backs up the phase overcurrent and residual overcurrent protection. The NOC
also protects the rotor of a rotating machine from over heating by detecting a load unbalance.
Unbalanced voltage supply to a rotating machine due to a phase loss can lead to increases in the
negative sequence current and in machine heating.
GRD140 provides the directional negative sequence overcurrent protection with definite time
characteristics.
Two independent elements NOC1 and NOC2 are provided for tripping and alarming. These
elements can be directionalised by polarising against the negative sequence voltage.
The NOC protection is enabled when three-phase current is introduced and the scheme switch
[APPL-CT] is set to 3P.
Scheme Logic
Figure 2.1.32 and 2.1.33 show the scheme logic of directional negative sequence overcurrent
protection NOC1 and NOC2. The directional control characteristic can be selected to Forward
or Reverse or Non by scheme switch setting [NC1-DIR] and [NC2-DIR] (not shown in
Figures 2.1.32 and 2.1.33).
In Figures 2.1.32 and 2.1.33, the NOC1 and NOC2 gives a trip signal NOC1 TRIP and an alarm
signal NOC2 ALARM through delayed pick-up timers TNC1 and TNC2.
When the VTFS or CTFS detects a VT failure or a CT failure, it can alarm and block the NC1 and
NC2 protection by the scheme switch [VTF NC1-BLK] and [VTF NC2-BLK] or [CTF NC1-BLK]
and [CTF NC2-BLK] respectively.
The NC1 and NC2 protection can be disabled by the scheme switches [NC1EN], [NC2EN] and
[APPL-CT] or the binary input signals NC1 BLOCK and NC2 BLOCK respectively.
The scheme switch [APPL-CT] is available in which three-phase overcurrent protection can be
selected. The NOC protection is enabled when three-phase current is introduced and [APPL-CT]
is set to 3P.
TNC1

NOC1

&

&

[NC1EN]
+

NOC1 TRIP

0.00 - 300.00s

"ON"

NOC1 BLOCK by BI

Non VTF
VTF NC1-BLK
+ "OFF"

&

Non CTF
CTF NC1-BLK
+

1
"OFF"

Figure 2.1.32

Negative Sequence Overcurrent Protection NOC1 Scheme Logic

39

6 F 2 S 0 7 5 8
TNC2

NOC2

&

&

[NC2EN]
+

NOC2 ALARM

0.00 - 300.00s

"ON"

NOC2 BLOCK by BI

&

Non VTF
VTF NC2-BLK
+ "OFF"

Non CTF
CTF NC2-BLK
+

1
"OFF"

Figure 2.1.33

Negative Sequence Overcurrent Protection NOC2 Scheme Logic

Setting
The table below shows the setting elements necessary for the NOC protection and their setting
ranges.
Element

Range

Step

Default

Remarks

NC

95 95

45

NOC characteristic angle

NCV

0.5 25.0 V

0.1 V

3.0 V

NOC NPS voltage level

NC1

0.5 10.0 A
(0.10 2.00 A)(*)

0.1 A
(0.01 A)

2.0 A
(0.40 A)

NOC1 threshold setting.

TNC1

0.00 300.00 s

0.01 s

1.00 s

NOC1 definite time setting. Required if [MNC1] = DT.

TNC1M

0.010 1.500

0.001

1.000

NOC1 time multiplier setting. Required if [MNC1] =


IEC, IEEE or US.

TNC1R

0.0 300.0 s

0.1 s

0.0 s

NOC1 definite time delayed reset. Required if [NC1R]


= DEF.

TNC1RM

0.010 1.500

0.001

1.000

NC1 dependent time delayed reset time multiplier.


Required if [NC1R] = DEP.

NC2

0.5 - 10.0 A
(0.10 2.00 A)

0.1 A
(0.01 A)

1.0 A
(0.20 A)

NOC2 threshold setting.

TNC2

0.00 300.00 s

0.01 s

1.00 s

NOC2 definite time setting

[NC1EN]

Off / On

Off

NOC1 Enable

[MNC1C]

NOC1 inverse curve type.

MNC1C-IEC
MNC1C-IEEE
MNC1C-US

NI / VI / EI / LTI
MI / VI / EI
CO2 / CO8

NI
MI
CO2

Required if [MNC1] = IEC.


Required if [MNC1] = IEEE.
Required if [MNC1] = US.

[NC1R]

DEF / DEP

DEF

NOC1 reset characteristic. Required if [MNC1] = IEEE


or US.

[CTF-NC1BLK]

Off / On

Off

CTF block enable for NOC1

[VTF-NC1BLK]

Off / On

Off

VTF block enable for NOC1

[NC2EN]

Off / On

Off

NOC2 Enable

[CTF-NC2BLK]

Off / On

Off

CTF block enable for NOC2

[VTF-NC2BLK]

Off / On

Off

VTF block enable for NOC2

[APPL-CT]

3P / 2P / 1P

3P

Three-phase current input

(*) Current values shown in the parenthesis are in the case of a 1 A rating. Other current
values are in the case of a 5 A rating.

40

6 F 2 S 0 7 5 8
Sensitive setting of NOC1 and NOC2 thresholds is restricted by the negative phase sequence
current normally present on the system. The negative phase sequence current is measured in the
relay continuously and displayed on the metering screen of the relay front panel along with the
maximum value. It is recommended to check the display at the commissioning stage and to set
NOC1 and NOC2 to 130 to 150% of the maximum value displayed.
The delay time setting TNC1 and TNC2 is added to the inherent delay of the measuring elements
NOC1 and NOC2. The minimum operating time of the NOC elements is around 200ms.
Under fault conditions, the negative sequence current lags the negative sequence voltage by an
angle dependent on the negative sequence source impedance of the system. This should be
accounted for by setting the NOC characteristic angle setting [NC] when the negative sequence
protection is used in directional mode. Typical settings are as follows:
60 for transmission systems
+45 for distribution systems

41

6 F 2 S 0 7 5 8
2.1.3.6 Application of Protection Inhibits
All GRD140 protection elements can be blocked by a binary input signal. This feature is useful in
a number of applications.
Blocked Overcurrent Protection
Conventional time-graded definite time overcurrent protection can lead to excessive fault
clearance times being experienced for faults closest to the source. The implementation of a
blocked overcurrent scheme can eliminate the need for grading margins and thereby greatly
reduce fault clearance times. Such schemes are suited to radial feeder circuits, particularly where
substations are close together and pilot cables can be economically run between switchboards.
Figure 2.1.34 shows the operation of the scheme.
Instantaneous phase fault and earth fault pick-up signals OC1HS, EF1HS and SEF1HS of OC1,
EF1 and SEF1 elements are allocated to any of the binary output relays and used as a blocking
signal. OC2, EF2 and SEF2 protections are set with a short delay time. (For pick-up signals, refer
to Figure 2.1.16, 2.1.20 and 2.1.27.)
For a fault at F as shown, each relay sends the blocking signal to its upstream neighbor. The signal
is input as a binary input signal OC2 BLOCK, EF2 BLOCK and SEF2 BLOCK at the receiving
end, and blocks the OC2, EF2 and SEF2 protection. Minimum protection delays of 50ms are
recommended for the OC2, EF2 and SEF2 protection, to ensure that the blocking signal has time
to arrive before protection operation.
Inverse time graded operation with elements OC1, EF1 and SEF1 are available with the scheme
switch [MOC1], [MEF1] and [MSE1] setting, thus providing back-up protection in the event of a
failure of the blocked scheme.
F
Trip
GRD140

GRD140

GRD140
OC2/EF2/SEF2

OC2/EF2/SEF2
High
Speed
Block

OCHS/EFHS/
SEFHS

Figure 2.1.34

OC2/EF2/SEF2
High
Speed
Block

OCHS/EFHS/
SEFHS

Blocked Overcurrent Protection

42

6 F 2 S 0 7 5 8
Blocked Busbar Protection
Non-directional overcurrent protection can be applied to provide a busbar zone scheme for a
simple radial system where a substation has only one source, as illustrated in Figure 2.1.35.
For a fault on an outgoing feeder F1, the feeder protection sends a hardwired blocking signal to
inhibit operation of the incomer, the signal OCHS, EFHS and SEFHS being generated by the
instantaneous phase fault, and earth fault pick-up outputs of OC1, EF1 and SEF1 allocated to any
of the binary output relays. Meanwhile, the feeder is tripped by the OC1, EF1 and SEF1 elements,
programmed with inverse time or definite time delays and set to grade with downstream
protections.
The incomer protection is programmed to trip via its instantaneous elements OC2, EF2 and SEF2
set with short definite time delay settings (minimum 50ms), thus providing rapid isolation for
faults in the busbar zone F2.
At the incomer, inverse time graded operation with elements OC1, EF1 and SEF1 are available
with the scheme switch [MOC1], [MEF1] and [MSE1] setting, thus providing back-up protection
in the event of failure of the blocked scheme.
GRD140 integrated circuit breaker failure protection can be used to provide additional back-trips
from the feeder protection to the incomer, and from the incomer to the HV side of the power
transformer, in the event of the first trip failing to clear the earth fault.
In the case of more complex systems where the substation has two incomers, or where power can
flow into the substation from the feeders, then directional protection must be applied.

GRD140

Delayed Back-up Trip

OC1/EF1/SEF1
High Speed Block to Incomer for Feeder Fault

OC2/ EF2/SEF2
Fast Trip

F2
Feeder Trip

Feeder Trip

Feeder Trip

GRD140

GRD140

GRD140

OC1/EF1/SEF1

OC1/EF1/SEF1

OC1/EF1/SEF1

OCHS/EFHS/
SEFHS

OCHS/EFHS/
SEFHS

OCHS/EFHS/
SEFHS

F1

Figure 2.1.35

Blocked Busbar Protection Scheme 1

Figure 2.1.36 shows one half of a two-incomer station. A directional overcurrent relay protects the
incomer, with non-directional overcurrent units on the feeders.

43

6 F 2 S 0 7 5 8

GRD140
Directional
(IDMTL)
OC1/EF1/SEF1

Delayed Back-up Trip


Trip Bus Section and Bus Coupler

(50ms)
OC2/EF2/SEF2
(250ms)
OC3/EF3/SEF3

High Speed Block

Trip Incomer

Bus Section

Bus Coupler

Feeder Trip

GRD140
Non-directional

Feeder Trip

GRD140
Non-directional

OC1/EF1/SEF1

OC1/EF1/SEF1

OCHS/EFHS/
SEFHS

OCHS/EFHS/
SEFHS

Figure 2.1.36

Blocked Busbar Protection Scheme 2

For a fault on an outgoing feeder, the non-directional feeder protection sends a hardwired blocking
signal to inhibit operation of both incomers, the signal OCHS, EFHS and SEFHS being generated
by the instantaneous phase fault and earth fault pick-up outputs. Meanwhile, the feeder is tripped
by the OC1, EF1 and SEF1 elements, programmed with inverse time delays and set to grade with
downstream protections.
The incomer protection is programmed for directional operation such that it will only trip for
faults on the busbar side of its CTs. Hence, although a fault on the HV side may be back-fed from
the busbars, the relay does not trip.
For a fault in the busbar zone, the GRD140 is programmed to trip the bus section and bus coupler
circuit breakers via its instantaneous elements OC2, EF2 and SEF2 set with short definite time
delay settings (minimum 50ms). This first stage trip maintains operation of half the substation in
the event of a busbar fault or incomer fault in the other half.
If the first stage trip fails to clear the fault, a second stage trip is given to the local incomer circuit
breaker via instantaneous elements OC3, EF3 and SEF3 after a longer delay, thus isolating a fault
on the local busbar.
GRD140 integrated circuit breaker fail protection can be used to provide additional back-trips
from the feeder protection to the incomer, and from the incomer to the HV side of the power
transformer, in the event of the main trip failing to clear the fault.
A further development of this scheme might see directional relays being applied directly to the bus
section and bus coupler circuit breakers, to speed up operation of the scheme.
This scheme assumes that a busbar fault cannot be fed from the outgoing feeder circuits. In the
case of an interconnected system, where a remote power source may provide a back-feed into the
substation, directional relays must also be applied to protect the feeders.

44

6 F 2 S 0 7 5 8
2.1.4

Phase Undercurrent Protection


The phase undercurrent protection is used to detect a decrease in current caused by a loss of load,
typically motor load. Two stage undercurrent protection UC1 and UC2 are available.
The undercurrent element operates for current falling through the threshold level. But the
operation is blocked when the current falls below 4 % of CT secondary rating to discriminate the
loss of load from the feeder tripping by other protection. Figure 2.4.37 shows the undercurrent
element characteristic.
Setting value
Operating zone
0.04In
0

|I| UC1 setting

|I| UC2 setting

&

UC1

&

UC2

|I| 0.04In
In: rated current

Figure 2.1.37

Undercurrent Element Characteristic

Each phase has two independent undercurrent elements for tripping and alarming. The elements
are programmable for instantaneous or definite time delayed operation.
The undercurrent element operates on per phase basis, although tripping and alarming is threephase only.
Scheme Logic
Figure 2.1.38 shows the scheme logic of the phase undercurrent protection.
The undercurrent elements UC1 and UC2 output UC1 TRIP and UC2 ALARM through delayed
pick-up timers TUC1 and TUC2.
This protection can be disabled by the scheme switch [UC1EN] and [UC2EN] or binary input
signals UC1 BLOCK and UC2 BLOCK.
Further, this protection can be blocked when CT failure (CTF) is detected.

45

6 F 2 S 0 7 5 8

&

UC1 B

&

&

&

&

&

&

&

&

&

&

&

UC2 B

&

&

&

&

&

&

I
0.04In B
C

UC1-A TRIP
UC1-B TRIP
UC1-C TRIP

TUC2
0

UC1 TRIP

UC2-A ALARM
UC2-B ALARM
UC2-C ALARM

0.00 - 300.00s

[UC2EN]

"ON"

TUC1
0

0.00 - 300.00s

[UC1EN]
+

UC2 ALARM

"ON"

NON CTF
+

[CTF-UC1BLK]

&

&

UC1 BLOCK

"OFF"

[CTF UC2BLK]
"OFF"

In : Rated current

UC2 BLOCK

Figure 2.1.38

Undercurrent Protection Scheme Logic

Setting
The table below shows the setting elements necessary for the undercurrent protection and their
setting ranges.
Element

Range

Step

Default

Remarks

UC1

0.5 10.0 A
(0.10 2.00 A)(*)

0.1 A
(0.01 A)

1.0 A
(0.20 A)

UC1 threshold setting

TUC1

0.00 300.00 s

0.01 s

1.00 s

UC1 definite time setting

UC2

0.5 10.0 A
(0.10 2.00 A)

0.1 A
(0.01 A)

2.0 A
(0.40 A)

UC2 threshold setting

TUC2

0.00 300.00 s

0.01 s

1.00 s

UC2 definite time setting

[UC1EN]

Off / On

Off

UC1 Enable

[UC2EN]

Off / On

Off

UC2 Enable

[CTF-UC1BLK]

Off / On

Off

UC1 CTF block

[CTF-UC2BLK]

Off / On

Off

UC2 CTF block

(*) Current values shown in parenthesis are in the case of a 1 A rating. Other current values are in
the case of a 5 A rating.

46

6 F 2 S 0 7 5 8
2.1.5

Thermal Overload Protection


The temperature of electrical plant rises according to an I2t function and the thermal overload
protection in GRD140 provides a good protection against damage caused by sustained
overloading. The protection simulates the changing thermal state in the plant using a thermal
model.
The thermal state of the electrical system can be shown by equation (1).
=

t
I2
1 e 100%
2

I AOL

(1)

where:
= thermal state of the system as a percentage of allowable thermal capacity,
I = applied load current,
IAOL = allowable overload current of the system,
= thermal time constant of the system.
The thermal state 0% represents the cold state and 100% represents the thermal limit, which is the
point at which no further temperature rise can be safely tolerated and the system should be
disconnected. The thermal limit for any given system is fixed by the thermal setting IAOL. The relay
gives a trip output when = 100%.
The thermal overload protection measures the largest of the three phase currents and operates
according to the characteristics defined in IEC60255-8. (Refer to Appendix A for the
implementation of the thermal model for IEC60255-8.)
Time to trip depends not only on the level of overload, but also on the level of load current prior to
the overload - that is, on whether the overload was applied from cold or from hot.
Independent thresholds for trip and alarm are available.
The characteristic of the thermal overload element is defined by equation (2) and equation (3) for
cold and hot. The cold curve is a special case of the hot curve where prior load current Ip is
zero, catering to the situation where a cold system is switched on to an immediate overload.

I2
t =Ln 2 2
I I AOL

(2)

I2 I 2
t =Ln 2 2P
I I AOL

(3)

where:
t = time to trip for constant overload current I (seconds)
I = overload current (largest phase current) (amps)
IAOL = allowable overload current (amps)
IP = previous load current (amps)
= thermal time constant (seconds)
Ln = natural logarithm
Figure 2.1.39 illustrates the IEC60255-8 curves for a range of time constant settings. The left-hand
chart shows the cold condition where an overload has been switched onto a previously un-loaded
system. The right-hand chart shows the hot condition where an overload is switched onto a

47

6 F 2 S 0 7 5 8
system that has previously been loaded to 90% of its capacity.
Thermal Curves (Cold Curve no prior load)

Thermal Curves (Hot Curve 90% prior load)

1000

1000

100

10

100
50

Operate Time (minutes)

Operate Time (minutes)

100

10

100

0.1

50

20

0.1

10

20
10
5
2
1

0.01

5
2

0.01

10

Overload Current (Multiple of IAOL)

Figure 2.1.39

0.001
1

10

Overload Current (Multiple of


IAOL)

Thermal Curves

Scheme Logic
Figure 2.1.40 shows the scheme logic of the thermal overload protection.
The thermal overload element THM has independent thresholds for alarm and trip, and outputs
alarm signal THM ALARM and trip signal THM TRIP. The alarming threshold level is set as a
percentage of the tripping threshold.
The alarming and tripping can be disabled by the scheme switches [THMAEN] and [THMEN]
respectively or binary input signals THMA BLOCK and THM BLOCK.
A

&

&

THM

&
&

THM ALARM

THM TRIP

[THMAEN]
+

"ON"
[THMEN]

"ON"
THMA BLOCK

THM BLOCK

Figure 2.1.40

Thermal Overload Protection Scheme Logic

48

6 F 2 S 0 7 5 8
Setting
The table below shows the setting elements necessary for the thermal overload protection and their
setting ranges.
Element

Range

Step

Default

Remarks

THM

2.0 10.0 A
(0.40 2.00 A)(*)

0.1 A
(0.01 A)

5.0 A
(1.00 A)

Thermal overload setting.


(THM = IAOL: allowable overload current)

THMIP

0.0 5.0 A
(0.00 1.00 A)(*)

0.1 A
(0.01 A)

0.0 A
(0.00 A)

Previous load current

TTHM

0.5 - 100.0 min

0.1 min

10.0 min

Thermal time constant

THMA

50 99 %

1%

80 %

Thermal alarm setting.


(Percentage of THM setting.)

[THMEN]

Off / On

Off

Thermal OL enable

[THMAEN]

Off / On

Off

Thermal alarm enable

(*) Current values shown in the parenthesis are in the case of a 1 A rating. Other current
values are in the case of a 5 A rating.

Note: THMIP sets a minimum level of previous load current to be used by the thermal
element, and is only active when testing ([THMRST] = ON).

49

6 F 2 S 0 7 5 8
2.1.6

Broken Conductor Protection


Series faults or open circuit faults which do not accompany any earth faults or phase faults are
caused by broken conductors, breaker contact failure, operation of fuses, or false operation of
single-phase switchgear.
Figure 2.1.41 shows the sequence network connection diagram in the case of a single-phase series
fault assuming that the positive, negative and zero sequence impedance of the left and right side
system of the fault location is in the ratio of k1 to (1 k1), k2 to (1 k2) and k0 to (1 k0).
Single-phase series fault

E1A

E1B

1 k1

k1
k1Z1

I1F

I1F

(1-k1)Z1

E1A

E1B

Positive phase sequence


k2Z2

I2F

I2F

(1-k2)Z2

I0F

(1-k0)Z0

Negative phase sequence


k0Z0

I0F

Zero phase sequence

I1F

k2Z2

(1-k2)Z2

K0Z0

(1-k0)Z0

k1Z1

I1F
(1-k1)Z1

E1A

E1B

I1F

Z2

Z1
Z0
E1A

E1B

Figure 2.1.41 Equivalent Circuit for a Single-phase Series Fault

Positive phase sequence current I1F, negative phase sequence current I2F and zero phase sequence

50

6 F 2 S 0 7 5 8
current I0F at fault location in an single-phase series fault are given by:
I1F + I2F + I0F =0

(1)

Z2FI2F Z0FI0F = 0

(2)

E1A E1B = Z1FI1F Z2FI2F

(3)

where,
E1A, E1B: power source voltage
Z1: positive sequence impedance
Z2: negative sequence impedance
Z0: zero sequence impedance
From the equations (1), (2) and (3), the following equations are derived.
Z 2 + Z0
I1F = Z Z + Z Z + Z Z (E1A E1B)
1 2
1 0
2 0
Z0
I2F = Z Z + Z Z + Z Z (E1A E1B)
1 2
1 0
2 0
Z2
I0F = Z Z + Z Z + Z Z (E1A E1B)
1 2
1 0
2 0
The magnitude of the fault current depends on the overall system impedance, difference in phase
angle and magnitude between the power source voltages behind both ends.
Broken conductor protection element BCD detects series faults by measuring the ratio of negative
to positive phase sequence currents (I2F / I1F). This ratio is given with negative and zero sequence
impedance of the system:
Z0
I2F |I2F|
I1F = |I1F| = Z2 + Z0
The ratio is higher than 0.5 in a system when the zero sequence impedance is larger than the
negative sequence impedance. It will approach 1.0 in a high-impedance earthed or a one-end
earthed system.
The characteristic of BCD element is shown in Figure 2.1.42 to obtain the stable operation.
I2
|I2|/|I1| BCD
setting
|I1| 0.04In
|I2| 0.01In
0.01In
0

I1

0.04In

Figure 2.1.42

In: rated current

BCD Element Characteristic

51

&

BCD

6 F 2 S 0 7 5 8
Scheme Logic
Figure 2.1.43 shows the scheme logic of the broken conductor protection. BCD element outputs
trip signals BCD TRIP through a delayed pick-up timer TBCD.
The tripping can be disabled by the scheme switch [BCDEN], [APPL] or binary input signal BCD
BLOCK. The scheme switch [APPL-CT] is available in Model 400 and 420 in which three-phase
or two-phase phase overcurrent protection can be selected. The broken conductor protection is
enabled when three-phase current is introduced and [APPL-CT] is set to 3P in those models.
BCD

&

BCD TRIP

0.00 - 300.00s

[BCDEN]
+

TBCD
0
t

"ON"
[APPL]

"3P"

BCD BLOCK

Figure 2.1.43 Broken Conductor Protection Scheme Logic

Settings
The table below shows the setting elements necessary for the broken conductor protection and
their setting ranges.
Element

Range

Step

Default

Remarks

BCD

0.10 1.00

0.01

0.20

I2 / I1

TBCD

0.00 300.00s

0.01s

0.00 s

BCD definite time setting

[BCDEN]

Off / On

Off

BCD Enable

[APPL-CT]

3P / 2P / 1P

3P

Three-phase current input. Only


required in Model 400 and 420.

Minimum setting of the BC threshold is restricted by the negative phase sequence current
normally present on the system. The ratio I2 / I1 of the system is measured in the relay continuously
and displayed on the metering screen of the relay front panel, along with the maximum value of
the last 15 minutes I21 max. It is recommended to check the display at the commissioning stage.
The BCD setting should be 130 to 150% of I2 / I1 displayed.
Note: It must be noted that I2 / I1 is displayed only when the positive phase sequence current
(or load current ) in the secondary circuit is larger than 2 % of the rated secondary circuit
current.

TBCD should be set to more than 1 cycle to prevent unwanted operation caused by a transient
operation such as CB closing.

52

6 F 2 S 0 7 5 8
2.1.7

Breaker Failure Protection


When fault clearance fails due to a breaker failure, the breaker failure protection (BFP) clears the
fault by backtripping adjacent circuit breakers.
If the current continues to flow even after a trip command is output, the BFP judges it as a breaker
failure. The existence of the current is detected by an overcurrent element CBF provided for each
phase. For high-speed operation of the BFP, a high-speed reset overcurrent element (less than
20ms) is used. The CBF element resets when the current falls below 80% of the operating value as
shown in Figure 2.1.44.
Pick-up
Drop-off

Drop-off/Pick-up=0.8

Figure 2.1.44

CBF element Characteristic

In order to prevent the BFP from starting by accident during maintenance work and testing, and
thus tripping adjacent breakers, the BFP has the optional function of retripping the original
breaker. To make sure that the breaker has actually failed, a trip command is made to the original
breaker again before tripping the adjacent breakers to prevent unnecessary tripping of the adjacent
breakers following the erroneous start-up of the BFP. It is possible to choose not to use retripping
at all, or use retripping with trip command plus delayed pick-up timer, or retripping with trip
command plus overcurrent detection plus delayed pick-up timer.
An overcurrent element and delayed pick-up timer are provided for each phase which also operate
correctly during the breaker failure routine in the event of an evolving fault.
Scheme logic
The BFP initiation is performed on per-phase basis. Figure 2.1.45 shows the scheme logic for the
BFP. The BFP is started by per-phase base trip signals EXT TRIP-APH to EXT TRIP-CPH or
three-phase base trip signal EXT TRIP-3PH by binary inputs. These trip signals must
continuously exist as long as the fault is present.
The backtripping signal to the adjacent breakers CBF TRIP is output if the overcurrent element
CBF operates continuously for the setting time of the delayed pick-up timer TBTC after initiation.
Tripping of adjacent breakers can be blocked with the scheme switch [BTC].
There are two kinds of modes of the retrip signal to the original breaker CBF RETRIP, the mode in
which retrip is controlled by the overcurrent element CBF, and the direct trip mode in which retrip
is not controlled. The retrip mode together with the trip block can be selected with the scheme
switch [RTC]. In the scheme switch [RTC], DIR is the direct trip mode, and OC is the trip
mode controlled by the overcurrent element CBF.
Figure 2.1.46 shows a sequence diagram for the BFP when a retrip and backup trip are used. If the
circuit breaker trips normally, the CBF is reset before timer TRTC or TBTC is picked up and the
BFP is reset. As TRTC and TBTC start at the same time, the setting value of TBTC should include
that of TRTC.
If the CBF continues to operate, a retrip command is given to the original breaker after the setting
time of TRTC. Unless the breaker fails, the CBF is reset by retrip. TBTC does not time-out and the
BFP is reset. This sequence of events may happen if the BFP is initiated by mistake and

53

6 F 2 S 0 7 5 8
unnecessary tripping of the original breaker is unavoidable.
If the original breaker fails, retrip has no effect and the CBF continues operating and the TBTC
finally picks up. A trip command CBF TRIP is given to the adjacent breakers and the BFP is
completed.
The BFP protection can be disabled by the scheme switches [BTC] and [RTC] or the binary input
signal CBF BLOCK.
[BTC]
+

"ON"

CBF TRIP

TBTC

&

CBF B
&

&

0.00 - 300.00s

CBF TRIP-A
CBF TRIP-B
CBF TRIP-C

CBF RETRIP

TRTC

&

&

&

0.00 - 300.00s

EXT TRIP-APH

&

EXT TRIP-BPH

&

EXT TRIP-CPH

&

EXT TRIP-3PH

[RTC]
+

"OC"
"DIR"
[APPL-CT]

+
CBF BLOCK

"3P"

&

Figure 2.1.45

Breaker Failure Protection Scheme Logic

54

CBF RETRIP-A
CBF RETRIP-B
CBF RETRIP-C

6 F 2 S 0 7 5 8
Fault

Start CBFP

Trip

Adjacent
breakers Closed

Open

TRIP
Retrip

Normal trip
Original
breakers Closed

Open
Tcb

OCBF

Open
Tcb

Toc
TBF1

Toc

TRTC
CBF
RETRIP
TBF2
TBTC

CBF
TRIP

Figure 2.1.46

Sequence Diagram

Setting
The setting elements necessary for the breaker failure protection and their setting ranges are as
follows:
Element

Range

Step

Default

Remarks

CBF

0.5 10.0 A

0.1 A

2.5 A

Overcurrent setting

(0.10 - 2.00 A)(*)

(0.01 A)

(0.50 A)

TRTC

0.00 300.00 s

0.01 s

0.40 s

Retrip time setting

TBTC

0.00 300.00 s

0.01 s

0.50 s

Back trip time setting

[RTC]

Off / DIR / OC

Off

Retrip control

[BTC]

Off / On

Off

Back trip control

(*) Current values shown in the parentheses are in the case of 1 A rating. Other
current values are in the case of 5 A rating.

The overcurrent element CBF checks that the circuit breaker has opened and that the current has
disappeared. Therefore, since it is allowed to respond to load current, it can be set to 10 to 200% of
the rated current.
The settings of TRTC and TBTC are determined by the opening time of the original circuit breaker
(Tcb in Figure 2.1.46) and the reset time of the overcurrent element (Toc in Figure 2.1.46). The
timer setting example when using retrip can be obtained as follows.
Setting of TRTC = Breaker opening time + CBF reset time + Margin
= 40ms + 10ms + 20ms
= 70ms
Setting of TBTC = TCBF1 + Output relay operating time + Breaker opening time +
CBF reset time + Margin
= 70ms + 10ms + 40ms + 10ms + 10ms
= 140ms
If retrip is not used, the setting of the TBTC can be the same as the setting of the TRTC.

55

6 F 2 S 0 7 5 8
2.1.8

Cold Load Protection


GRD140 provides cold load protection to prevent incorrect operation from a magnetising inrush
current during transformer energisation.
In normal operation, the load current on the distribution line is smaller than the sum of the rated
loads connected to the line. But it amounts to several times the maximum load current for a
moment when all of the loads are energised at once after a long interruption, and decreases to 1.5
times normal peak load after three or four seconds.
To protect those lines with overcurrent element, it is necessary to use settings to discriminate the
inrush current in cold load restoration and the fault current.
This function modifies the overcurrent protection settings for a period after closing on to the type
of load that takes a high level of load on energisation. This is achieved by a Cold Load Setting, in
which the user can program alternative setting. Normally the user will choose higher current
settings within this setting.
A state transition diagram and its scheme logic are shown in Figure 2.1.47 and Figure 2.1.48 for
the cold load protection. Note that the scheme requires the use of two binary inputs assigned by
PLC function, one each for CB OPEN and CB CLOSED.
Under normal conditions, where the circuit breaker has been closed for some time, the scheme is in
STATE 0, and the normal default setting is applied to the overcurrent protection.
If the circuit breaker opens then the scheme moves to STATE 1 and runs the Cold Load Enable
timer TCLE. If the breaker closes again while the timer is running, then STATE 0 is re-entered.
Alternatively, if TCLE expires then the load is considered cold and the scheme moves to STATE
2, and stays there until the breaker closes, upon which it goes to STATE 3.
In STATE 2 and STATE 3, the Cold Load Setting is applied.
In STATE 3 the Cold Load Reset timer TCLR runs. If the circuit breaker re-opens while the timer
is running then the scheme returns to STATE 2. Alternatively, if TCLR expires then it goes to
STATE 0, the load is considered warm and normal settings can again be applied.
Accelerated reset of the cold load protection is also possible. In STATE 3, the phase currents are
monitored by overcurrent element ICLDO and if all phase currents drop below the ICLDO
threshold for longer than the cold load drop off time (TCLDO) then the scheme automatically
reverts to STATE 0. The accelerated reset function can be enabled with the scheme switch
[CLDOEN] setting.
Cold load protection can be disabled by setting [CLEN] to Off.
To test the cold load protection function, the switch [CLPTST] is provided to set the STATE 0 or
STATE 3 condition forcibly.

56

6 F 2 S 0 7 5 8

STATE 0
CB status: Closed
Settings Group: Normal
Monitor CB status

CB opens

CB closes
within
T CLE time

STATE 1
CB status: Open
Settings Group: Normal
Run T CLE timer
Monitor CB status

T CLE timer
expires

STATE 3

CB closes

STATE 2

CB status: Closed
Settings Group: Cold Load

CB status: Open
Settings Group: Cold Load
Monitor CB status

Figure 2.1.47

IL<ICLDO for
T CLDO time

T CLR timer
expires

Run T CLR timer


Monitor CB status
Monitor load current IL

CB opens within
CLR time

State Transition Diagram for Cold Load Protection

STATE 0

Change to
STATE 1

&
TCLE

STATE 1

&

Change to
STATE 2

Change to
STATE 0

0.0 - 10000.0s

&
STATE 2
STATE 3

&
TCLR

[CLEN]
+

Change to
STATE 3

&

"OFF"

&

0.0 - 10000.0s

CB CONT OPN
CB CONT CLS

CB CLOSE

CB OPEN

[CLPTST] "S0"

TCLDO

ICLDO B

&

0.00 - 100.00s

C
[CLDOEN]
+

"ON"

Figure 2.1.48

Scheme Logic for Cold Load Protection

57

"S3"

6 F 2 S 0 7 5 8
Setting
The setting elements necessary for the cold load protection and their setting ranges are as follows:
Element

Range

Step

Default

Remarks

ICLDO

0.5 10.0 A
(0.10 - 2.00 A)(*)

0.1 A
(0.01 A)

2.5 A
(0.50 A)

Cold load drop-off threshold setting

TCLE

0-10000 s

1s

100 s

Cold load enable timer

TCLR

0-10000 s

1s

100 s

Cold load reset timer

TCLDO

0.00-100.00 s

0.01 s

0.00 s

Cold load drop-off timer

[CLEN]

Off / On

Off

Cold load protection enable

[CLDOEN]

Off / On

Off

Cold load drop-off enable

(*) Current values shown in the parentheses are in the case of a 1 A rating. Other current values
are in the case of a 5 A rating.

Further, other element settings (OC1 to OC4, EF1 to EF4, SEF1 to SEF4, NOC1, NOC2 and
BCD) are required for the cold load protection.

58

6 F 2 S 0 7 5 8
2.1.9

CT Requirements

2.1.9.1 Phase Fault and Earth Fault Protection


Protection class current transformers are normally specified in the form shown below. The CT
transforms primary current within the specified accuracy limit, for primary current up to the
overcurrent factor, when connected to a secondary circuit of the given burden.

5 P 20 : 10VA
Accuracy
Limit (%)

Overcurrent
Factor

Maximum Burden
(at rated current)

Accuracy limit : Typically 5 or 10%. In applications where current grading is to be applied and
small grading steps are desirable, then a 5% CT can assist in achieving the necessary accuracy. In
less onerous applications, a limit of 10% may be acceptable.
Overcurrent factor : The multiple of the CT rating up to which the accuracy limit is claimed,
typically 10 or 20 times. A value of 20 should be specified where maximum fault current is high
and accurate inverse time grading is required. In applications where fault current is relatively low,
or where inverse time grading is not used, then an overcurrent factor of 10 may be adequate.
Maximum burden : The total burden calculated at rated secondary current of all equipment
connected to the CT secondary, including relay input burden, lead burden, and taking the CTs
own secondary resistance into account. GRD140 has an extremely low AC current burden,
typically less than 0.1VA for a 1A phase input, allowing relatively low burden CTs to be applied.
Relay burden does not vary with settings.
If a burden lower than the maximum specified is connected, then the practical overcurrent factor
may be scaled accordingly. For the example given above, at a rated current of 1A, the maximum
value of CT secondary resistance plus secondary circuit resistance (RCT + R2) should be 10. If
a lower value of, say, (RCT + R2) = 5 is applied, then the practical overcurrent factor may be
increased by a factor of two, that is, to 40A.
In summary, the example given of a 5P20 CT of suitable rated burden will meet most applications
of high fault current and tight grading margins. Many less severe applications may be served by
5P10 or 10P10 transformers.
2.1.9.2

Minimum Knee Point Voltage

An alternative method of specifying a CT is to calculate the minimum knee point voltage,


according to the secondary current which will flow during fault conditions:
Vk If (RCT + R2)
where:
Vk = knee point voltage
If = maximum secondary fault current
RCT = resistance of CT secondary winding
R2 = secondary circuit resistance, including lead resistance.
When using this method, it should be noted that it is often not necessary to transform the
maximum fault current accurately. The knee point should be chosen with consideration of the
settings to be applied and the likely effect of any saturation on protection performance. Further,

59

6 F 2 S 0 7 5 8
care should be taken when determining R2, as this is dependent on the method used to connect the
CTs (E.g. residual connection, core balanced CT connection, etc).
2.1.9.3 Sensitive Earth Fault Protection
A core balance CT should be applied, with a minimum knee point calculated as described above.
2.1.9.4 Restricted Earth Fault Protection
High accuracy CTs should be selected with a knee point voltage Vk chosen according to the
equation:
Vk 2 Vs
where Vs is the differential stability voltage setting for the scheme.

60

6 F 2 S 0 7 5 8

2.2

Overvoltage and Undervoltage Protection


2.2.1

Phase Overvoltage Protection


GRD140 provides two independent phase overvoltage elements with programmable
dropoff/pickup(DO/PU) ratio. OV1 is programmable for inverse time (IDMT) or definite time
(DT) operation. OV2 has definite time characteristic only.
Figure 2.2.1 shows the characteristic of overvoltage elements.

Pickup
Dropoff

Figure 2.2.1

Characteristic of Overvoltage Elements

The overvoltage protection element OV1 has the IDMT characteristic defined by equation (1):

t = TMS

V Vs 1

( )

(1)

where:
t = operating time for constant voltage V (seconds),
V = energising voltage (V),
Vs = overvoltage setting (V),
TMS = time multiplier setting.
The IDMT characteristic is illustrated in Figure 2.2.2.
The OV2 element is used for definite time overvoltage protection.
Definite time reset
The definite time resetting characteristic is applied to the OV1 element when the inverse time
delay is used.
If definite time resetting is selected, and the delay period is set to instantaneous, then no
intentional delay is added. As soon as the energising voltage falls below the reset threshold, the
element returns to its reset condition.
If the delay period is set to some value in seconds, then an intentional delay is added to the reset
period. If the energising voltage exceeds the setting for a transient period without causing tripping,
then resetting is delayed for a user-definable period. When the energising voltage falls below the
reset threshold, the integral state (the point towards operation that it has travelled) of the timing
function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.
Both OV1 and OV2 have a programmable dropoff/pickup(DO/PU) ratio.

61

6 F 2 S 0 7 5 8

Overvoltage Inverse Time


Curves
1000.000

Operating Time (secs)

100.000

10.000

TMS = 10
TMS = 5

TMS = 2
1.000

TMS = 1

0.100
1

1.5

2.5

Applied Voltage (x Vs)

Figure 2.2.2

IDMT Characteristic

Scheme Logic
Figure 2.2.3 shows the scheme logic of the OV1 overvoltage protection with selective definite
time or inverse time characteristic.
The definite time protection is enabled by setting [OV1EN] to DT, and trip signal OV1 TRIP is
given through the delayed pick-up timer TOV1. The inverse time protection is enabled by setting
[OV1EN] to IDMT, and trip signal OV1 TRIP is given.
The OV1 protection can be disabled by the scheme switch [OV1EN] or the binary input signal
OV1 BLOCK.
Figure 2.2.4 shows the scheme logic of the OV2 protection with definite time characteristic. The
OV2 gives the signal OV2-ALARM through delayed pick-up timer TOV2.
The OV2-ALARM signal can be blocked by incorporated scheme switch [OV2EN] and the binary
input signal OV2 BLOCK.

62

6 F 2 S 0 7 5 8

TOV1

A
OV1 B
C

&

&

&

&

&

&

OV1-B TRIP

OV1-C TRIP

0.00 - 300.00s

[OV1EN] "DT"

OV1-A TRIP

1
&

"IDMT"
OV1 BLOCK

OV1 TRIP

&

&

Figure 2.2.3

OV1 Overvoltage Protection

TOV2
0

&

&

&

&

[OV2EN]

&

&

OV2-A ALARM

OV2 B

OV2-C ALARM

0.00 - 300.00s

"On"
OV2 BLOCK

OV2-B ALARM

Figure 2.2.4

OV2 ALARM

OV2 Overvoltage Protection

Note: When APPL-VT=2PP setting, A=A-B phase, B=B-C phase, and C=None.

Setting
The table shows the setting elements necessary for the overvoltage protection and their setting
ranges.
Element

Range

Step

Default

Remarks

OV1

10.0 200.0 V

0.1 V

120.0 V

OV1 threshold setting

TOV1M

0.05 100.00

0.01

1.00

OV1 time multiplier setting. Required if [OV1EN] = IDMT.

TOV1

0.00 300.00 s

0.01 s

1.00 s

OV1 definite time setting. Required if [OV1EN] = DT.

TOV1R

0.0 300.0 s

0.1 s

0.0 s

OV1 definite time delayed reset.

OV1DPR

10 98 %

1%

95 %

OV1 DO/PU ratio setting.

OV2

10.0 200.0 V

0.1 V

140.0 V

OV2 threshold setting.

TOV2

0.00 300.00 s

0.01 s

1.00 s

OV2 definite time setting.

OV2DPR

10 - 98 %

1%

95 %

OV2 DO/PU ratio setting.

[OV1EN]

Off / DT / IDMT

Off

OV1 Enable

[OV2EN]

Off / On

Off

OV2 Enable

63

6 F 2 S 0 7 5 8
2.2.2

Phase Undervoltage Protection


GRD140 provides two independent phase undervoltage elements. UV1 programmable for inverse
time (IDMT) or definite time (DT) operation. UV2 has definite time characteristic only.
Figure 2.2.5 shows the characteristic of the undervoltage elements.

Figure 2.2.5

Characteristic of Undervoltage Elements

The undervoltage protection element UV1 has an IDMT characteristic defined by equation (2):

t = TMS
1 V Vs

( )

(2)

where:
t = operating time for constant voltage V (seconds),
V = energising voltage (V),
Vs = undervoltage setting (V),
TMS = time multiplier setting.
The IDMT characteristic is illustrated in Figure 2.2.6.
The UV2 element is used for definite time undervoltage protection.
Definite time reset
The definite time resetting characteristic is applied to the UV1 element when the inverse time
delay is used.
If definite time resetting is selected, and the delay period is set to instantaneous, then no
intentional delay is added. As soon as the energising voltage rises above the reset threshold, the
element returns to its reset condition.
If the delay period is set to some value in seconds, then an intentional delay is added to the reset
period. If the energising voltage is below the undercurrent setting for a transient period without
causing tripping, then resetting is delayed for a user-definable period. When the energising
voltage rises above the reset threshold, the integral state (the point towards operation that it has
travelled) of the timing function (IDMT) is held for that period.
This does not apply following a trip operation, in which case resetting is always instantaneous.

64

6 F 2 S 0 7 5 8

Undervoltage Inverse Time


Curves
1000.000

Operating Time (secs)

100.000

TMS = 10
10.000
TMS = 5

TMS = 2

TMS = 1
1.000
0

0.2

0.4

0.6

0.8

Applied Voltage (x Vs)

Figure 2.2.6

IDMT Characteristic

Scheme Logic
Figure 2.2.7 shows the scheme logic of the UV1 undervoltage protection with selective definite
time or inverse time characteristic.
The definite time protection is selected by setting [UV1EN] to DT, and trip signal UV1 TRIP is
given through the delayed pick-up timer TUV1. The inverse time protection is selected by setting
[UV1EN] to IDMT, and trip signal UV1 TRIP is given.
The UV1 protection can be disabled by the scheme switch [UV1EN] or binary input signal UV1
BLOCK.
Figure 2.2.8 shows the scheme logic of the UV2 protection with definite time characteristic. The
UV2 gives the signal UV2-ALARM through delayed pick-up timer TUV2.
The UV2-ALARM can be blocked by incorporated scheme switch [UV2EN] and the binary input
signal UV2 BLOCK.
In addition, there is a user programmable voltage threshold VBLK. If all measured phase voltages
drop below this setting, then both UV1 and UV2 are prevented from operating. This function can
be blocked by the scheme switch [VBLKEN]. The [VBLKEN] should be set to OFF (not used)
when the UV elements are used as fault detectors, and set to ON (used) when used for load
shedding.
Note: The VBLK must be set lower than any other UV setting values.

Further, these protection can be blocked when VT failure (VTF) is detected.

65

6 F 2 S 0 7 5 8
A
UV1

&

&

TUV1
0

&

&

UVBLK
[VBLKEN]
+
"ON"
[UVTST]
+
"OFF"

&

&

&

[UV1EN]

"DT"

0.00 - 300.00s

NON
UVBLK

UV1-C TRIP

&

UV1 TRIP

"IDMT"

&

[VTF UV1-BLK]

&
&

"OFF"

UV1 BLOCK

UV1-B TRIP

NON VTF
+

UV1-A TRIP

Figure 2.2.7

UV1 Undervoltage Protection


TUV2

&

&

&

&

[UV2EN]

&

&

UV2-A ALARM

UV2 B

"ON"

UV2-C ALARM

0.00 - 300.00s

NON BLK

NON VTF

[VTF UV2-BLK]
+

UV2-B ALARM

UV2 ALARM

&

"OFF"

UV2 BLOCK

Figure 2.2.8

UV2 Undervoltage Protection

Note: When APPL-VT=2PP setting, A=A-B phase, B=B-C phase, and C=None.

Setting
The table shows the setting elements necessary for the undervoltage protection and their setting
ranges.
Element

Range

Step

Default

Remarks

UV1

5.0 130.0 V

0.1 V

60.0 V

UV1 threshold setting

TUV1M

0.05 100.00

0.01

1.00

UVI time multiplier setting. Required if [UV1EN] = IDMT.

TUV1

0.00 300.00 s

0.01 s

1.00 s

UV1 definite time setting. Required if [UV1EN] = DT.

TUV1R

0.0 300.0 s

0.1 s

0.0 s

UV1 definite time delayed reset.

UV2

5.0 130.0 V

0.1 V

40.0 V

UV2 threshold setting.

TUV2

0.00 300.00 s

0.01 s

1.00 s

UV2 definite time setting.

VBLK

5.0 - 20.0 V

0.1 V

10.0 V

Undervoltage block threshold setting.

[UV1EN]

Off / DT / IDMT

DT

UV1 Enable

[VTF UV1BLK]

Off / On

Off

UV1 VTF block

[VBLKEN]

Off / On

Off

UV block Enable

[UV2EN]

Off / On

Off

UV2 Enable

[VTF UV2BLK]

Off / On

Off

UV2 VTF block

66

6 F 2 S 0 7 5 8
2.2.3

Zero Phase Sequence Overvoltage Protection


The zero phase sequence overvoltage protection (ZOV) is applied to earth fault detection on
unearthed, resistance-earthed system or on ac generators.
The ZOV is available for the following models and their [APPL-VT] settings:
Model

110

[APPL-VT] setting

3PN

3PV

9(1)

9(2)

9(1)

ZOV

400, 420, 430

Note: (1); V0 is measured directly in the form of the system residual voltage.
(2); V0 is calculated from the three measured phase voltages.

The low voltage settings which may be applied make the ZOV element susceptible to any 3rd
harmonic component which may be superimposed on the input signal. Therefore, a 3rd harmonic
filter is provided to suppress such superimposed components.
For the earth fault detection, following two methods are in general use.
Measuring the zero sequence voltage produced by VT residual connection (broken-delta
connection) as shown in Figure 2.2.9.
Measuring the residual voltage across the earthing transformers as shown in Figure 2.2.10.
A

GRD140
V0

Figure 2.2.9
A

Earth Fault Detection on Unearthed System

V0

GRD140

Resistor

Figure 2.2.10

Earth Fault Detection on Generator

Two independent elements ZOV1 and ZOV2 are provided. The ZOV1 element is programmable
for definite time delayed or inverse time delayed (IDMT) operation, and the ZOV2 element for

67

6 F 2 S 0 7 5 8
definite time delayed operation only.
The inverse time characteristic is defined by equation (3).

t = TMS

V 0 Vs 1

(3)

where:
t = operating time for constant voltage V0 (seconds),
V0 = Zero sequence voltage (V),
Vs = Zero sequence overvoltage setting (V),
TMS = time multiplier setting.
The IDMT characteristic is illustrated in Figure 2.2.11.

ZOV Overvoltage
Inverse Time Curves
1000.000

Operating Time (secs)

100.000

10.000

1.000
TMS = 10
TMS = 5

TMS = 2

0.100
TMS = 1

0.010
0

10

15

20

Applied Voltage (x Vs)

Figure 2.2.11

IDMT Characteristic of ZOV

68

6 F 2 S 0 7 5 8
Definite time reset
A definite time reset characteristic is applied to the ZOV1 element when the inverse time delay is
used. Its operation is identical to that for the phase overvoltage protection.
Scheme Logic
Figure 2.2.12 shows the scheme logic of the zero-phase sequence overvoltage protection. Two
zero-phase sequence overvoltage elements ZOV1 and ZOV2 with independent thresholds output
trip signals ZOV1 TRIP and ZOV2 TRIP through delayed pick-up timers TZOV1 and TZOV2.
The tripping can be disabled by the scheme switches [ZOV1EN] and [ZOV2EN] or binary input
signals ZOV1 BLOCK and ZOV2 BLOCK.
Further, this protection can be blocked when VT failure (VTF) is detected.
TZOV1

ZOV1

&
"DT"

[ZOV1EN]

&

0.00 - 300.00s

ZOV1 TRIP

&
"IDMT"

ZOV1 BLOCK

&

NON VTF
[VTF ZV1-BLK]
+

"OFF"
TZOV2

ZOV2

&

&

[ZOV2EN]
+

ZOV2 ALARM

0.00 - 300.00s

"ON"

ZOV2 BLOCK
[VTF ZV2-BLK]
+

&
1

"OFF"

Figure 2.2.12

Zero Sequence Overvoltage Protection

Setting
The table below shows the setting elements necessary for the zero sequence overvoltage
protection and their setting ranges.
Element

Range

Step

Default

Remarks

ZOV1

1.0 - 130.0 V

0.1V

20.0 V

ZOV1 threshold setting (V0) for tripping.

ZOV2

1.0 - 130.0 V

0.1V

40.0 V

ZOV2 threshold setting (V0) for alarming.

TZOV1P

0.05 100.00

0.01

1.00

ZOV1 time multiplier setting. Required if [ZOV1EN]=IDMT.

TZOV1D

0.00 300.00 s

0.01 s

1.00 s

ZOV1 definite time setting. Required if [ZOV1EN]=DT.

TZOV1R

0.0 300.0 s

0.1 s

0.0 s

ZOV1 definite time delayed reset.

TZOV2

0.00 300.00 s

0.01 s

1.00 s

ZOV2 definite time setting

[ZOV1EN]

Off / DT/IDMT

DT

ZOV1 Enable

[VTF ZV1BLK]

Off / On

Off

ZOV1 VTF block

[ZOV2EN]

Off / On

Off

ZOV2 Enable

[VTF ZV2BLK]

Off / On

Off

ZOV2 VTF block

69

6 F 2 S 0 7 5 8
Negative Phase Sequence Overvoltage Protection
The negative phase sequence overvoltage protection is used to detect voltage unbalance
conditions such as reverse-phase rotation, unbalanced voltage supply etc.
The NOV protection is applied to protect three-phase motors from the damage which may be
caused by the voltage unbalance. Unbalanced voltage supply to motors due to a phase loss can
lead to increases in the negative sequence voltage.
The NOV protection is also applied to prevent the starting of the motor in the wrong direction, if
the phase sequence is reversed.
Two independent elements NOV1 and NOV2 are provided. The NOV1 element is programmable
for definite time delayed or inverse time delayed (IDMT) operation, and the NOV2 element for
definite time delayed operation only.
The inverse time characteristic is defined by equation (4).

t = TMS

V 2 Vs 1

(4)

where:
t = operating time for constant voltage V2 (seconds),
V2 = Negative sequence voltage (V),
Vs = Negative sequence overvoltage setting (V),
TMS = time multiplier setting.
The IDMT characteristic is illustrated in Figure 2.2.13.

NOV Overvoltage
Inverse Time Curves
1000.000

100.000

Operating Time (secs)

2.2.4

10.000

1.000

TMS = 10
TMS = 5
TMS = 2

0.100
TMS = 1

0.010
0

10

15

20

Applied Voltage (x Vs)

Figure 2.2.13

IDMT Characteristic of NOV

70

6 F 2 S 0 7 5 8
Definite time reset
A definite time reset characteristic is applied to the NOV1 element when the inverse time delay is
used. Its operation is identical to that for the phase overvoltage protection.
Scheme Logic
Figure 2.2.14 shows the scheme logic of the negative sequence overvoltage protection. Two
negative sequence overvoltage elements NOV1 and NOV2 with independent thresholds output
trip signals NOV1 TRIP and NOV2 TRIP through delayed pick-up timers TNOV1 and TNOV2.
The tripping can be disabled by the scheme switches [NOV1EN] and [NOV2EN] or binary input
signals NOV1 BLOCK and NOV2 BLOCK.
Further, this protection can be blocked when VT failure (VTF) is detected.
TNOV1

NOV1

&

[NOV1EN]

"DT"

&

0.00 - 300.00s

NOV1 TRIP

&
"IDMT"

NOV1 BLOCK

&

NON VTF
[VTF NV1-BLK]
+

"OFF"
TNOV2

NOV2

&

&

[NOV2EN]
+

NOV2 ALARM

0.00 - 300.00s

"ON"

NOV2 BLOCK

[VTF NV2-BLK]
+

&
1

"OFF"

Figure 2.2.14

Negative Sequence Overvoltage Protection

Setting
The table below shows the setting elements necessary for the negative sequence overvoltage
protection and their setting ranges.
The delay time setting TNOV1 and TNOV2 is added to the inherent delay of the measuring
elements NOV1 and NOV2. The minimum operating time of the NOV elements is around 200ms.
Element

Range

Step

Default

Remarks

NOV1

1.0 - 130.0 V

0.1V

20.0 V

NOV1 threshold setting for tripping.

NOV2

1.0 - 130.0 V

0.1V

40.0 V

NOV2 threshold setting for alarming.

TNOV1P

0.05 100.00

0.01

1.00

NOV1 time multiplier setting. Required if [NOV1EN]=IDMT.

TNOV1D

0.00 300.00 s

0.01 s

1.00 s

NOV1 definite time setting. Required if [NOV1EN]=DT.

TNOV1R

0.0 300.0 s

0.1 s

0.0 s

NOV1 definite time delayed reset.

TNOV2

0.00 300.00 s

0.01 s

1.00 s

NOV2 definite time setting

[NOV1EN]

Off / DT/IDMT

Off

NOV1 Enable

[NOV2EN]

Off / On

Off

NOV2 Enable

71

6 F 2 S 0 7 5 8

2.3

Frequency Protection
For a four-stage frequency protection, GRD140 incorporates dedicated frequency measuring
elements and scheme logic for each stage. Each stage is programmable for underfrequency or
overfrequency protection.
Underfrequency protection is provided to maintain the balance between the power generation
capability and the loads. It is also used to maintain the frequency within the normal range by load
shedding.
Overfrequency protection is typically applied to protect synchronous machines from possible damage
due to overfrequency conditions.

A-phase to B-phase voltage is used to detect frequency.


Frequency element
Underfrequency element UF operates when the power system frequency falls under the setting
value.
Overfrequency element OF operates when the power system frequency rises over the setting
value.
These elements measure the frequency and check for underfrequency or overfrequency every 5
ms. They operate when the underfrequency or overfrequency condition is detected 16 consecutive
times.
Both UF and OF elements output is invalidated by undervoltage block element (FVBLK)
operation during undervoltage condition.
Figure 2.3.1 shows characteristics of UF and OF elements.
Hz

OF

OF setting
UF setting

UF

0
FVBLK setting

Figure 2.3.1

Underfrequency and Overfrequency Element

Scheme Logic
Figure 2.3.2 shows the scheme logic of frequency protection in stage 1. The frequency element
FRQ1 can output a trip command under the condition that the system voltage is higher than the
setting of the undervoltage element FVBLK (FVBLK=1). The FRQ1 element is programmable for
underfrequency or overfrequency operation by the scheme switch [FRQ1EN].
The tripping can be disabled by the scheme switches [FRQ1EN].
The stage 2 (FRQ2) to stage 4 (FRQ4) are the same logic of FRQ1

72

6 F 2 S 0 7 5 8
TFRQ1

FRQ1

OF

&

&

&
FRQ2

TFRQ2

OF

&

&

TFRQ3

OF

&

&

FRQ4

TFRQ4

t
&

&

&

FRQ4 TRIP

0.00 - 300.00s

UF

FRQ3 TRIP

0.00 - 300.00s

&
OF

&

UF

FRQ2 TRIP

0.00 - 300.00s

&
FRQ3

&

UF

FRQ1 TRIP

0.00 - 300.00s

UF

&

&
FVBLK
[FRQ1EN]
+
[FRQ2EN]
+
[FRQ3EN]
+
[FRQ4EN]
+

1
"OF"
"UF"

"OF"
"UF"

"OF"
"UF"

"OF"
"UF"

FRQ1 BLOCK

FRQ2 BLOCK

FRQ3 BLOCK

FRQ4 BLOCK

Figure 2.3.2

Scheme Logic of Frequency Protection

Setting
The setting elements necessary for the frequency protection and their setting ranges are shown in
the table below.
Element
FRQ1
TFRQ1
FRQ2
TFRQ2
FRQ3
TFRQ3
FRQ4
TFRQ4
FVBLK
FRQ1EN
FRQ2EN
FRQ3EN
FRQ4EN

Range
-10.00 +10.00 Hz
0.00 300.00 s
-10.00 +10.00 Hz
0.00 300.00 s
-10.00 +10.00 Hz
0.00 300.00 s
-10.00 +10.00 Hz
0.00 300.00 s
40.0 100.0 V
Off / OF / UF
Off / OF / UF
Off / OF / UF
Off / OF / UF

Step
0.01 Hz
0.01 s
0.01 Hz
0.01 s
0.01 Hz
0.01 s
0.01 Hz
0.01 s
0.1 V

Default
-1.00 Hz
1.00 s
-1.00 Hz
1.00 s
-1.00 Hz
1.00 s
-1.00 Hz
1.00 s
40.0 V
Off
Off
Off
Off

73

Remarks
FRQ1 frequency element setting
Timer setting of FRQ1
FRQ2 frequency element setting
Timer setting of FRQ2
FRQ3 frequency element setting
Timer setting of FRQ3
FRQ4 frequency element setting
Timer setting of FRQ4
UV block setting
FRQ1 Enable
FRQ2 Enable
FRQ3 Enable
FRQ4 Enable

6 F 2 S 0 7 5 8

2.4

Trip and Alarm Signal Output


GRD140 provides various trip and alarm signal outputs such as three-phase and single-phase trip
and alarm of each protection. Figures 2.4.1 and 2.4.2 show gathered trip and alarm signals of each
protection.
GRD140 provides 8 auxiliary relays for binary outputs as described in Section 3.2.7 of the
auxiliary relays can be assigned to any protection outputs.
After the trip signal disappears by clearing the fault, the reset time of the tripping output relay can
be programmed. The setting is respective for each output relay.
When the relay is latched, it can be reset with the RESET key on the relay front panel or a binary
input. This resetting resets all the output relays collectively.
In the tripping output relay, it must be checked that the tripping circuit is opened with a circuit
breaker auxiliary contact prior to the tripping output relay resetting, in order to prevent the
tripping output relay from directly interrupting the circuit breaker tripping coil current.
OC1 TRIP
OC2 TRIP
OC3 TRIP

EF1 TRIP
EF2 TRIP
EF3 TRIP

GEN. TRIP

GEN. ALARM

SEF1-S1 TRIP
SEF2 TRIP

SEF3 TRIP
NOC1 TRIP
UC1 TRIP
THM TRIP

BCD TRIP
OV1 TRIP
UV1 TRIP

ZOV1 TRIP
NOV1 TRIP
OC4 ALARM
EF4 ALARM
SEF4 ALARM
NOC2 ALARM
UC2 ALARM
THM ALARM

OV2 ALARM
UV2 ALARM

ZOV2 ALARM
NOV2 ALARM
FRQ1 TRIP
FRQ2 TRIP

FRQ3 TRIP
FRQ4 TRIP

Figure 2.4.1 Three-phase Output

74

FRQ. TRIP

6 F 2 S 0 7 5 8

OC1-A TRIP
OC2-A TRIP

OC3-A TRIP

GEN. TRIP-A

GEN. TRIP-B

GEN. TRIP-C

UC1-A TRIP
OV1-A TRIP

UV1-A TRIP
OC1-B TRIP
OC2-B TRIP

OC3-B TRIP
UC1-B TRIP
OV1-B TRIP
UV1-B TRIP
OC1-C TRIP
OC2-C TRIP

OC3-C TRIP
UC1-C TRIP
OV1-C TRIP
UV1-C TRIP
EF1 TRIP
EF2 TRIP

GEN. TRIP-N

EF3 TRIP
SEF1-S1 TRIP
SEF2 TRIP

SEF3 TRIP
ZOV1 TRIP
OC4-A ALARM

UC2-A ALARM
OV2-A ALARM

GEN. ALARM-A

GEN. ALARM-B

GEN. ALARM-C

UV2-A ALARM
OC4-B ALARM

UC2-B ALARM
OV2-B ALARM

UV2-B ALARM
OC4-C ALARM

UC2-C ALARM
OV2-C ALARM

UV2-C ALARM
EF4 ALARM
SEF4 ALARM

GEN. ALARM-N

ZOV2 ALARM

Figure 2.4.2

Single-phase Output

75

6 F 2 S 0 7 5 8

2.5

Autoreclose
The GRD140 provides a multi-shot (five shots) autoreclosing scheme applied for one-circuit
breaker:
Three phase autoreclosing scheme for all shots
Autoreclosing counter
The autoreclosing (ARC) can be initialized by OC1 to OC4, EF1 to EF4, SEF1-S1 to SEF4 trip
signals or external trip signals via binary inputs, as determined by scheme switches [-INIT].
Trip signals are selected to be used or not used for ARC, by setting [-INIT] to On or NA
respectively. If a trip signal is used to block ARC, then [-INIT] is set to BLK. ARC can also
be blocked by binary input signal ARC BLOCK.
Three-phase autoreclosing is provided for all shots, regardless of whether the fault is single-phase
or multi-phase. Autoreclosing can be programmed to provide any number of shots, from one to
five. In each case, if the first shot fails, then all subsequent shots apply three-phase tripping and
reclosing.
To disable autoreclosing, scheme switch [ARCEN] is set to "Off".

2.5.1

Scheme Logic
Figure 2.5.1 shows the simplified scheme logic for the autoreclose. Autoreclose becomes ready
when the circuit breaker is closed and ready for autoreclose (CB READY=1), the on-delay timer
TRDY is picked up, and the [ARCEN] is set to "ON". TRDY is used to determine the reclaim time.
If the autoreclose is ready, then reclosing is activated by ARC INIT. ARC INIT is programmed
from tripping commands of the various protections by scheme switches [-INIT]. Further, the
external tripping command signal EXT TRIP-APH, EXT TRIP-BPH, EXT TRIP-CPH or EXT
TRIP-3PH can also activate the autoreclose via binary inputs.
Once autoreclose is activated, it is maintained by a flip-flop circuit until one reclosing cycle is
completed.
Multi-shot autoreclose
Regardless of the tripping mode, three-phase reclose is performed. If the [ARCEN] is set to "On",
the dead time counter TD1 for three-phase reclosing is started. After the dead time has elapsed,
reclosing command ARC-SHOT is initiated.
Multi-shot autoreclose can be executed up to four times after the first-shot autoreclose fails. The
multi-shot mode, one to five shots, is set with the scheme switch [ARC-NUM].
During multi-shot reclosing, the dead time counter TD2 for the second shot is activated if the first
shot autoreclose is performed, but tripping occurs again. Second shot autoreclose is performed
after the period of time set on TD2 has elapsed. At this time, outputs of the step counter are: SP1 =
1, SP2 = 0, SP3 = 0, SP4 = 0 and SP5 = 0.
Autoreclose is completed at this step if the two shots mode is selected for the multi-shot mode. In
this case, tripping following a "reclose-onto-a-fault" becomes the final trip (ARC FT = 1).
If three shot mode is selected for the multi-shot mode, autoreclose is further retried after the above
tripping occurs. At this time, the T1S3 is started. The third shot autoreclose is performed after the
period of time set on the TD3 has elapsed. At this time, outputs of the step counter are: SP1 = 0,
SP2 = 1, SP3 = 0, SP4 = 0 and SP5 = 0.
The three shot mode of autoreclose is then completed, and tripping following a
"reclose-onto-a-fault" becomes the final trip (ARC FT = 1).

76

6 F 2 S 0 7 5 8
When four or five shot autoreclose is selected, autoreclose is further retried once again for tripping
that occurs after "reclose-onto-a-fault". This functions in the same manner as the three shot
autoreclose.
If a fault occurs under the following conditions, the final trip is performed and autoreclose is
blocked.
Reclosing block signal is applied.
During the reclaim time
In the OC, EF and SE protections, each tripping is selected by setting [OC-TP], [EF-TP]
or [SE-TP] to any one of Inst(instantaneous trip), Set(delayed trip by T and [M1]
setting) or Off(blocked). (See Section 2.3.)
STEP COUNTER
SP0
1 CLK SP1
SP2
SP3
SP4
SP5

Coordination
TRDY
t
0

ARC READY

0.0-600.0s

[ARCEN]
+
"ON"

&

S
F/F
R

&

&
SP1

ARC INIT (Trip command)

S
F/F
R

SP2

S
F/F
R

TRSET
t
0
CB CLOSE
TARCP
t
0

&

0.01-300.00s

SP4

0.1-600.0s

S
F/F
R

0.01-300.00s

TD3
t
0 ARC-SHOT3
0.01-300.00s

TD4
t
0 ARC-SHOT4
0.01-300.00s

ARC-SHOT4
&

SP5

ARC-SHOT
0.01-10.00s

ARC-SHOT3

&

0.01-300.00s

TRCOV
0
t

S
F/F
R

&

TD2
t
0 ARC-SHOT2

ARC-SHOT2
&

SP3

TW

1
1

ARC-SUCCESS
ARC-FT

0.01-300.00s

ARC-SHOT1
&

EXT TRIP

TD1
t
0 ARC-SHOT1

SHOT NUM1
SHOT NUM2
SHOT NUM3
SHOT NUM4
SHOT NUM5
SHOT NUM6

S
F/F
R

TD5
t
0 ARC-SHOT5
0.01-300.00s

ARC-SHOT5

&

MANUAL CLOSE

Figure 2.5.1 Autoreclose Scheme Logic

2.5.2

Sequence Coordination
When two or more relays protect the same feeder their sequences (trip shot number) must be
coordinated. Considering the diagram as shown in Figure 2.5.2, relays A and B protect the same
feeder and both are programmed for 2 instantaneous and 2 IDMT trips. Both relays A and B see
the permanent fault at Fault F, and relays operate with instantaneous protection for 1st trip (at
SHOT NUM1) and 2nd trip (at SHOT NUM2).
3rd trip (at SHOT NUM3) is delayed, and the relays have different IDMT settings, so that relay B
only operates. Relay A does not trip and autoreclose, and judges the autoreclose succeeded. It
reclaims and returns to the beginning of its autoreclose cycle (= SHOT NUM1). Next, though the
relay B will attempt the delayed 4th trip (at SHOT NUM4), then mal-instantaneous trip will be
done by the relay A. In this case, the sequence co-ordination function is applied and the trip shot
number is coordinated as shown in Figure 2.5.3. The trip shot number is coordinated by the
operation of OC, EF or SEF element. The sensitivity (OC, EF or SEF) and the scheme switch
([COORD-OC], [COORD-EF] or [COORD-SE]) are set (See Section 2.5.3).

77

6 F 2 S 0 7 5 8
A

A:GRD140

B:GRD140

Figure 2.5.2

Fault F

Relay Location

Co-ordination disabled:
1st trip 2nd trip
(Inst)
(Inst)

No trip & judged ARC succeed


1st trip (Inst): mal-operate

Relay A

1st trip 2nd trip 3rd trip


(Inst)
(Inst)
(IDMT)

No trip

Relay B

Co-ordination enabled:

1st trip 2nd trip


(Inst)
(Inst)

No trip

No trip

Relay A

1st trip 2nd trip 3rd trip


(IDMT)
(Inst)
(Inst)

4th trip
(IDMT)

Relay B

Figure 2.5.3

Sequence Coordination Function

78

6 F 2 S 0 7 5 8
2.5.3

Setting
The setting elements necessary for the autoreclose and their setting ranges are shown in the table
below.

Element
ARC
TRDY
TD1
TD2
TD3
TD4
TD5
TW
TSUC
TRCOV
TARCP
TRSET
[ARCEN]
[ARC-NUM]
[OC1-INIT]
[OC1-TP1]
[OC1-TP2]
[OC1-TP3]
[OC1-TP4]
[OC1-TP5]
[OC1-TP6]
[OC2-INIT]
[OC2-TP1]
[OC2-TP2]
[OC2-TP3]
[OC2-TP4]
[OC2-TP5]
[OC2-TP6]
[OC3-INIT]
[OC3-TP1]
[OC3-TP2]
[OC3-TP3]
[OC3-TP4]
[OC3-TP5]
[OC3-TP6]
[OC4-INIT]
[OC4-TP1]
[OC4-TP2]
[OC4-TP3]
[OC4-TP4]
[OC4-TP5]
[OC4-TP6]
[EF1-INIT]
[EF1-TP1]
[EF1-TP2]
[EF1-TP3]

Range

Step

Default

Remarks

0.0 600.0 s
0.01 300.00 s
0.01 300.00 s
0.01 300.00 s
0.01 300.00 s
0.01 300.00 s
0.01 10.00 s
0.1 600.0 s
0.1 600.0 s
0.1 600.0 s
0.01 300.00 s
Off/On
S1/S2/S3/S4/S5
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET

0.1 s
0.01 s
0.01 s
0.01 s
0.01 s
0.01 s
0.01 s
0.1 s
0.1 s
0.1 s
0.01 s

60.0 s
10.00 s
10.00 s
10.00 s
10.00 s
10.00 s
2.00 s
3.0 s
10.0 s
10.0 s
3.00 s
On
S1
A1
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET

Reclaim time
1st shot dead time for Stage 1
2nd shot dead time for Stage 1
3rd shot dead time for Stage 1
4th shot dead time for Stage 1
5th shot dead time for Stage 1
Output pulse time
Autoreclose succeed judgement time
Autoreclose recovery time after final trip
Autoreclose pause time after manually closing
Autoreclose reset time
Autoreclose enable
Autoreclosing shot number
Autoreclose initiation by OC1
OC1 trip mode of 1st trip
OC1 trip mode of 2nd trip
OC1 trip mode of 3rd trip
OC1 trip mode of 4th trip
OC1 trip mode of 5th trip
OC1 trip mode of 6th trip
Autoreclose initiation by OC2
OC2 trip mode of 1st trip
OC2 trip mode of 2nd trip
OC2 trip mode of 3rd trip
OC2 trip mode of 4th trip
OC2 trip mode of 5th trip
OC2 trip mode of 6th trip
Autoreclose initiation by OC3
OC3 trip mode of 1st trip
OC3 trip mode of 2nd trip
OC3 trip mode of 3rd trip
OC3 trip mode of 4th trip
OC3 trip mode of 5th trip
OC3 trip mode of 6th trip
Autoreclose initiation by OC4
OC4 trip mode of 1st trip
OC4 trip mode of 2nd trip
OC4 trip mode of 3rd trip
OC4 trip mode of 4th trip
OC4 trip mode of 5th trip
OC4 trip mode of 6th trip
Autoreclose initiation by EF1
EF1 trip mode of 1st trip
EF1 trip mode of 2nd trip
EF1 trip mode of 3rd trip

79

6 F 2 S 0 7 5 8
Element
[EF1-TP4]
[EF1-TP5]
[EF1-TP6]
[EF2-INIT]
[EF2-TP1]
[EF2-TP2]
[EF2-TP3]
[EF2-TP4]
[EF2-TP5]
[EF2-TP6]
[EF3-INIT]
[EF3-TP1]
[EF3-TP2]
[EF3-TP3]
[EF3-TP4]
[EF3-TP5]
[EF3-TP6]
[EF4-INIT]
[EF4-TP1]
[EF4-TP2]
[EF4-TP3]
[EF4-TP4]
[EF4-TP5]
[EF4-TP6]
[SE1-INIT]
[SE1-TP1]
[SE1-TP2]
[SE1-TP3]
[SE1-TP4]
[SE1-TP5]
[SE1-TP6]
[SE2-INIT]
[SE2-TP1]
[SE2-TP2]
[SE2-TP3]
[SE2-TP4]
[SE2-TP5]
[SE2-TP6]
[SE3-INIT]
[SE3-TP1]
[SE3-TP2]
[SE3-TP3]
[SE3-TP4]
[SE3-TP5]
[SE3-TP6]
[SE4-INIT]
[SE4-TP1]
[SE4-TP2]
[SE4-TP3]
[SE4-TP4]
[SE4-TP5]

Range
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
NA/A1/A2/BLK
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET
OFF/INST/SET

Step

Default
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET

80

Remarks
EF1 trip mode of 4th trip
EF1 trip mode of 5th trip
EF1 trip mode of 6th trip
Autoreclose initiation by EF2
EF2 trip mode of 1st trip
EF2 trip mode of 2nd trip
EF2 trip mode of 3rd trip
EF2 trip mode of 4th trip
EF2 trip mode of 5th trip
EF2 trip mode of 6th trip
Autoreclose initiation by EF3
EF3 trip mode of 1st trip
EF3 trip mode of 2nd trip
EF3 trip mode of 3rd trip
EF3 trip mode of 4th trip
EF3 trip mode of 5th trip
EF3 trip mode of 6th trip
Autoreclose initiation by EF4
EF4 trip mode of 1st trip
EF4 trip mode of 2nd trip
EF4 trip mode of 3rd trip
EF4 trip mode of 4th trip
EF4 trip mode of 5th trip
EF4 trip mode of 6th trip
Autoreclose initiation by SE1
SE1 trip mode of 1st trip
SE1 trip mode of 2nd trip
SE1 trip mode of 3rd trip
SE1 trip mode of 4th trip
SE1 trip mode of 5th trip
SE1 trip mode of 6th trip
Autoreclose initiation by SE2
SE2 trip mode of 1st trip
SE2 trip mode of 2nd trip
SE2 trip mode of 3rd trip
SE2 trip mode of 4th trip
SE2 trip mode of 5th trip
SE2 trip mode of 6th trip
Autoreclose initiation by SE3
SE3 trip mode of 1st trip
SE3 trip mode of 2nd trip
SE3 trip mode of 3rd trip
SE3 trip mode of 4th trip
SE3 trip mode of 5th trip
SE3 trip mode of 6th trip
Autoreclose initiation by SE4
SE4 trip mode of 1st trip
SE4 trip mode of 2nd trip
SE4 trip mode of 3rd trip
SE4 trip mode of 4th trip
SE4 trip mode of 5th trip

6 F 2 S 0 7 5 8
Element
[SE4-TP6]
[EXT-INIT]
[COORD-OC]
[COORD-EF]
[COORD-SE]
OC
EF

SEF

Range
OFF/INST/SET
NA/A1/A2/BLK
Off/On
Off/On
Off/On
0.1 250.0 A
(0.02 50.00 A) (*)
0.1 250.0 A
(0.02 50.00 A) (*)
0.1 40.0 A
(0.02 8.00 A)
0.01 1.00 A
(0.002 0.200 A) (*)
0.002 0.200 A

Step

0.1 A
(0.01 A)
0.1 A
(0.01 A)
0.1 A
(0.01 A)
0.01 A
(0.001 A)
0.001 A

Default
SET
NA
Off
Off
Off
5.0 A
(1.00 A)
1.5 A
(0.30 A)
1.5 A
(0.30 A)
0.05 A
(0.010 A)
0.010 A

Remarks
SE4 trip mode of 6th trip
Autoreclose initiation by external trip command
OC relay for Co-ordination
EF relay for Co-ordination
SE relay for Co-ordination
OC for co-ordination
EF for co-ordination for Models 110, 400 and 420
EF for co-ordination for Model 430
SEF for co-ordination

SEF for co-ordination for Model


GRD140-420A-3-
(*) Current values shown in the parenthesis are in the case of a 1 A rating. Other current values are in
the case of a 5 A rating.

To determine the dead time, it is essential to find an optimal value while taking factors,
de-ionization time and power system stability, into consideration which normally contradict each
other.
Normally, a longer de-ionization time is required as for a higher line voltage or larger fault current.
For three-phase autoreclose, the dead time is generally 15 to 30 cycles.

81

6 F 2 S 0 7 5 8

3. Technical Description
3.1

Hardware Description
3.1.1

Outline of Hardware Modules


The case outline of GRD140 is shown in Appendix F.
The hardware structure of GRD140 is shown in Figure 3.1.1.
The GRD140 relay unit consists of the following hardware modules. These modules are fixed in a
frame and cannot be taken off individually. The human machine interface module is provided with
the front panel.
Power module (POWD)
Signal processing module (SPMD)
Human machine interface module (HMI)
The hardware block diagram of GRD140 is shown in Figure 3.1.2.

SPMD

POWD
HMI
IN SERVICE VIEW
TRIP
ALARM

RESET

Handle for relay


withdrawal

0V

CAN
CEL ENTER
END

Figure 3.1.1 Hardware Structure without Case

82

6 F 2 S 0 7 5 8

DC
supply
Binary
input

AC input
I, V

POWD

SPMD

DC/DC
Converter
Photo-coupler
5 or 8

CT 4
(Max)
VT x 4
(Max)

Analogue
filter

Multiplexer

A/D
converter

Auxiliary relay
8

MPU

RAM

ROM

RS485
Transceiver
1 or 2

Binary output
(Trip
command etc.)
Relay
setting and
monitoring
system
or
IEC60870-5
-103

Human machine
Interface (HMI)
Liquid crystal display
16 characters 2 lines
LEDs
Local
personal
computer

RS232C
I/F

Operation keys
Monitoring
jacks

Figure 3.1.2 Hardware Block Diagram

POWD Module
The POWD module insulates between the internal and external circuits through an auxiliary
transformer and transforms the magnitude of AC input signals to suit the electronic circuits. The
AC input signals may be one to three phase currents and a residual current depending on the relay
model.
This module incorporates max. 4 auxiliary CTs and max. 4 VTs, DC/DC converter and 5 or 8
photo-coupler circuits for binary input signals.
The available input voltage ratings of the DC/DC converter are, 48V, 110V/125V or 220/250V.
The normal range of input voltage is 20% to +20%.
SPMD Module
The SPMD module consists of analogue filter, multiplexer, analogue to digital (A/D) converter,
main processing unit (MPU), random access memory (RAM) and read only memory (ROM) and
executes all kinds of processing such as protection, measurement, recording and display.
The analogue filter performs low-pass filtering for the corresponding current signals.
The A/D converter has a resolution of 12 bits and samples input signals at sampling frequencies of
2400 Hz (at 50 Hz) and 2880 Hz (at 60 Hz).
The MPU implements more than 240 MIPS and uses a RISC (Reduced Instruction Set Computer)
type 32-bit microprocessors.

83

6 F 2 S 0 7 5 8
The SPMD module also incorporates 8 auxiliary relays (BO1-BO7 and FAIL) for binary output
signals and an RS485 transceiver.
BO1 to BO6 are user configurable output signals and have one normally open and one normally
closed contact. BO7 is also a user-configurable output signal and has one normally open contact.
The auxiliary relay FAIL has one normally open and one normally closed contacts, and operates
when a relay failure or abnormality in the DC circuit is detected.
The RS485 transceiver is used for the link with the relay setting and monitoring (RSM) system or
IEC60870-5-103 communication. The external signal is isolated from the relays internal circuits.
Human Machine Interface (HMI) Module
The operator can access the GRD140 via the human machine interface (HMI) module. As shown
in Figure 3.1.3, the HMI panel has a liquid crystal display (LCD), light emitting diodes (LED),
view and reset keys, operation keys, monitoring jacks and an RS232C connector on the front
panel.
The LCD consists of 16 columns by 2 rows with a back-light and displays recording, status and
setting data.
There are a total of 6 LED indicators and their signal labels and LED colors are defined as follows:
Label

Color

Remarks

IN SERVICE

Green

Lit when the relay is in service and flickered when the relay is in Test menu.

TRIP

Red

Lit when a trip command is issued.

ALARM

Red

Lit when a failure is detected.

(LED1)

Yellow

(LED2)

Yellow

(LED3)

Yellow

LED1, LED2 and LED3 are user-configurable. Each is driven via a logic gate which can be
programmed for OR gate or AND gate operation. Further, each LED has a programmable reset
characteristic, settable for instantaneous drop-off, or for latching operation. A configurable LED
can be programmed to indicate the OR combination of a maximum of 4 elements, the individual
statuses of which can be viewed on the LCD screen as Virtual LEDs. For the setting, see Section
4.2.6.10. For the operation, see Section 4.2.1.
The TRIP LED and an operated LED if latching operation is selected, must be reset by user, either
by pressing the RESET key, by energising a binary input which has been programmed for
Remote Reset operation, or by a communications command. Other LEDs operate as long as a
signal is present. The RESET key is ineffective for these LEDs. Further, the TRIP LED is
controlled with the scheme switch [AOLED] whether it is lit or not by an output of alarm element
such as OC4 ALARM, EF4 ALARM, SEF4 ALARM, NOC2 ALARM, UC2 ALARM, THM
ALARM, OV2 ALARM, UV2 ALARM, ZOV2 ALARM, and NOV2 ALARM.
The VIEW key starts the LCD indication and switches between windows. The RESET key
clears the LCD indication and turns off the LCD back-light.
The operation keys are used to display the record, status and setting data on the LCD, input the
settings or change the settings.
The monitoring jacks and two pairs of LEDs, A and B, on top of the jacks can be used while the
test mode is selected in the LCD window. Signals can be displayed on LED A or LED B by
selecting the signal to be observed from the "Signal List" and setting it in the window and the

84

6 F 2 S 0 7 5 8
signals can be transmitted to an oscilloscope via the monitoring jacks. (For the "Signal List", see
Appendix C.)
The RS232C connector is a 9-way D-type connector for serial RS232C connection. This
connector is used for connection with a local personal computer.
Screw for cover

Liquid crystal
display
IN SERVICE

VIEW

TRIP
ALARM

Light emitting
diodes (LED)

RESET

Operation keys
Light emitting
diodes (LED)
Monitoring Jacks

RS232C connector

0V CAN
CEL ENTER
END

Screw for handle

To a local PC
Screw for cover

Figure 3.1.3 Front Panel

85

6 F 2 S 0 7 5 8

3.2

Input and Output Signals


3.2.1

AC Input Signals
Table 3.2.1 shows the AC input signals necessary for the GRD140 model and their respective
input terminal numbers. Model 400, 430 and 420 depend on their scheme switch [APPL-CT] or
[APPL-VT] setting.
Table 3.2.1 AC Input Signals
[APPL-CT] setting

Term. No.
TB1
1-2
TB1
3-4
TB1
5-6
TB1
7-8

TB2
A1-B2
TB2
B1-B2
TB2
A2-B2
TB2
A3-B3

[APPL-VT] setting

3P or Model 430

2P

1P or Model 110

3PN

3PV

2PP

Model 110

A phase current Ia

A phase
current Ia

---

---

---

---

Residual
voltage Ve

B phase current Ib

C phase
current Ic

---

---

---

---

---

C phase current Ic

Residual
current Ie

Residual current Ie

---

---

---

---

Zero sequence
current Ise(*)

---

---

---

---

Zero
Residual current Ie
sequence
or
current Ise(*)
Zero sequence
current Ise(*)
---

---

---

A phase
voltage Va

A phase
voltage Va

A-B phase
voltage

---

---

---

---

B phase
voltage Vb

B phase
voltage Vb

C-B phase
voltage

---

---

---

---

C phase
voltage Vc

C phase
voltage Vc

---

---

---

---

---

---

Residual
voltage Ve

Residual
voltage Ve

---

(*): Ise required for SEF elements for model 420. In the model 420 and [APPL-CT]=3P, the residual
current is calculated by Ia , Ib and Ic.
In the models 110 and 430, [APPL-CT] setting is not available.

3.2.2

Binary Input, Output Signals


The GRD140 provides eight programmable binary input circuits. Each binary input circuit is
programmable, and provided with the function of Logic level inversion and Function selection.

Logic level inversion

The binary input circuit of the GRD140 is provided with a logic level inversion function and a
pick-up and drop-off delay timer function as shown in Figure 3.2.1. Each input circuit has a binary
switch BISNS which can be used to select either normal or inverted operation. This allows the
inputs to be driven either by normally open or normally closed contacts. Where the driving contact
meets the contact conditions then the BISNS can be set to Norm (normal). If not, then Inv
(inverted) should be selected. The pick-up and drop-off delay times can be set 0.0 to 300.00s
respectively.
Logic level inversion function, and pick-up and drop-off delay timer settings are as follow:
Element

Contents

Range

BI1SNS - BI8SNS

Binary switch

Norm/ Inv

BI1PUD - BI8PUD

Delayed pick-up timer

0.00 - 300.00s

86

Step

Default
Norm

0.01s

0.00

6 F 2 S 0 7 5 8
BI1DOD - BI8DOD

Delayed drop-off timer

0.00 - 300.00s

0.01s

0.00

The operating voltage of binary input signal is typical 74V DC at 110V/125V DC rating and 138V
DC at 220/250V DC. The minimum operating voltage is 70V DC at 110/125V DC rating and
125V DC at 220/250V DC.
GRD140

(+) ()
BI1

BI1PUD

BI1DOD

[BI1SNS]
BI1 command

BI1

"Norm"
"Inv"

BI2

BI2PUD

BI2DOD

[BI2SNS]
BI2 command

BI2

"Norm"
"Inv"
BI8PUD

BI8

BI8DOD
0

[BI8SNS]
BI8 command

BI8

"Norm"
"Inv"

0V

Figure 3.2.1 Logic Level Inversion

Function selection

The input signals BI1 COMMAND to BI5 COMMAND or to BI8 COMMAND are used for the
functions listed in Table 3.2.2. Each input signal can be allocated for one or some of those
functions by setting. For the setting, refer to Section 4.2.6.8.
The Table also shows the signal name corresponding to each function used in the scheme logic and
LCD indication and driving contact condition required for each function.
[OC1BLK]

BI1 COMMAND

"ON"
[OC2BLK]
"ON"
[OC3BLK]
"ON"

[Alarm4]

OC1 BLOCK

OC2 BLOCK

OC3 BLOCK

Alarm 4

"ON"

Figure 3.2.2

Function Scheme Logic

The logic of BI2 COMMAND to BI8 COMMAND are the same as that of BI1 COMMAND as

87

6 F 2 S 0 7 5 8
shown in Figure 3.2.2.
Table 3.2.2 Function of Binary Input Signals
Functions

Signal Names (*1)

Driving Contact Condition

Change active setting Group 1

SET.GROUP1

Closed to change the setting to Group 1

Change active setting Group 2

SET.GROUP2

Closed to change the setting to Group 2

Change active setting Group 3

SET.GROUP3

Closed to change the setting to Group 3

Change active setting Group 4

SET.GROUP4

Closed to change the setting to Group 4

OC1 protection block

OC1 BLOCK / OC1BLK

Closed to block OC1

OC2 protection block

OC2 BLOCK / OC2BLK

Closed to block OC2

OC3 protection block

OC3 BLOCK / OC3BLK

Closed to block OC3

OC4 protection block

OC4 BLOCK / OC4BLK

Closed to block OC4

EF1 protection block

EF1 BLOCK / EF1BLK

Closed to block EF1

EF2 protection block

EF2 BLOCK / EF2BLK

Closed to block EF2

EF3 protection block

EF3 BLOCK / EF3BLK

Closed to block EF3

EF4 protection block

EF4 BLOCK / EF4BLK

Closed to block EF4

EF1 protection permission

EF1 PERMIT

Closed to permit EF1

EF2 protection permission

EF2 PERMIT

Closed to permit EF2

EF3 protection permission

EF3 PERMIT

Closed to permit EF3

EF4 protection permission

EF4 PERMIT

Closed to permit EF4

SEF1 protection block

SEF1 BLOCK / SEF1BLK

Closed to block SEF1

SEF2 protection block

SEF2 BLOCK / SEF2BLK

Closed to block SEF2

SEF3 protection block

SEF3 BLOCK / SEF3BLK

Closed to block SEF3

SEF4 protection block

SEF4 BLOCK / SEF4BLK

Closed to block SEF4

UC1 protection block

UC1 BLOCK / UC1BLK

Closed to block UC1

UC2 protection block

UC2 BLOCK / UC1BLK

Closed to block UC2

THM protection block

THM BLOCK / THMBLK

Closed to block THM

THMA protection block

THMA BLOCK / THMABLK

Closed to block THMA

NOC1 protection block

NOC1 BLOCK / NC1BLK

Closed to block NOC1

NOC2 protection block

NOC2 BLOCK / NC1BLK

Closed to block NOC2

BCD protection block

BCD BLOCK / BCDBLK

Closed to block BCD

CBF protection block

CBF BLOCK / CBFBLK

Closed to block CBF

OV1 protection block

OV1 BLOCK / OV1BLK

Closed to block OV1

OV2 protection block

OV2 BLOCK / OV2BLK

Closed to block OV2

UV1 protection block

UV1 BLOCK / OV1BLK

Closed to block UV1

UV2 protection block

UV2 BLOCK / OV2BLK

Closed to block UV2

ZOV1 protection block

ZOV1 BLOCK / ZOV1BLK

Closed to block ZOV1

ZOV2 protection block

ZOV2 BLOCK / ZOV2BLK

Closed to block ZOV2

NOV1 protection block

NOV1 BLOCK / NOV1BLK

Closed to block NOV1

NOV2 protection block

NOV2 BLOCK / NOV2BLK

Closed to block NOV2

FRQ1 protection block

FRQ1 BLOCK / FRQ1BLK

Closed to block FRQ1

FRQ2 protection block

FRQ2 BLOCK / FRQ1BLK

Closed to block FRQ2

FRQ3 protection block

FRQ3 BLOCK / FRQ1BLK

Closed to block FRQ3

FRQ4 protection block

FRQ4 BLOCK / FRQ1BLK

Closed to block FRQ4

88

6 F 2 S 0 7 5 8
Functions

Signal Names (*1)

Driving Contact Condition

Autoreclose (ARC) scheme block

ARC BLOCK / ARCBLK

Closed to block ARC

ARC ready

ARC READY / ARCRDY

Closed when CB is closed and gas pressure is


sufficient.

ARC initiation

ARC INIT / ARCINI

Closed to initiate ARC

Manual close

MANUAL CLOSE / MNLCLS

Closed to close CB manually.

ARC not applied

ARC N/A / ARCNA

Closed not to apply ARC scheme

CTF function block

CTF BLOCK / CTFBLK

Closed to block CTF function

External CTF

EXT CTF / CTFEXT

Closed to block a protection

VTF function block

VTF BLOCK / VTFBLK

Closed to block VTF function

External VTF

EXT VTF / VTFEXT

Closed to block a protection

Trip circuit supervision

TC FAIL / TCFALM

Trip circuit failure alarm

State transition for cold load


protection, trip supervision and CB
monitoring

CB CONT OPN / CBOPN

CB normally open contact

CB monitoring

CB CONT CLS / CBCLS

CB normally closed contact.

Breaker failure protection initiate

EXT TRIP-3PH / EXT3PH

External trip - 3 phase.

Breaker failure protection initiate

EXT TRIP-APH / EXTAPH

External trip - A phase.

Breaker failure protection initiate

EXT TRIP-BPH / EXTBPH

External trip - B phase

Breaker failure protection initiate

EXT TRIP-CPH / EXTCPH

External trip - C phase

Indication remote reset

REMOTE RESET / RMTRST

Closed to reset TRIP LED indication and latch of


binary output relays

Synchronise clock

SYNC CLOCK / SYNCLK

Synchronise clock

Disturbance record store

STORE RECORD / STORCD

Closed to store the record

Alarm 1

Alarm 1 / Alarm1

Closed to display Alarm 1 text.

Alarm 2

Alarm 2 / Alarm2

Closed to display Alarm 2 text.

Alarm 3

Alarm 3 / Alarm3

Closed to display Alarm 3 text.

Alarm 4

Alarm 4 / Alarm4

Closed to display Alarm 4 text.

(*1) : Signal names are those used in the scheme logic / LCD indication.

The binary input signals can be programmed to switch between four settings groups.
Element

Contents

Range

BI1SGS BI8SGS

Setting group selection

OFF / 1 / 2 / 3 / 4

Step

Default
OFF

Four alarm messages can be set. The user can define a text message within 16 characters for each
alarm. The messages are valid for any of the input signals BI1 to BI8 by setting. Then when inputs
associated with that alarm are raised, the defined text is displayed on the LCD.

89

6 F 2 S 0 7 5 8
3.2.3

Binary Output Signals


The number of binary output signals and their output terminals are as shown in Appendix G. All
outputs, except the relay failure signal, can be configured.
The signals shown in the signal list in Appendix B can be assigned to the output relays BO1 to
BO7 individually or in arbitrary combinations. Signals can be combined using either an AND
circuit or OR circuit with 4 gates each as shown in Figure 3.2.3. The output circuit can be
configured according to the setting menu. Appendix H shows the factory default settings.
Further, each BO has a programmable reset characteristic, settable for instantaneous drop-off
Inst, for delayed drop-off Dl, for dwell operation Dw or for latching operation Latch by
the scheme switch [RESET]. The time of the delayed drop-off Dl or dwell operation Dw can
be set by TBO. When Dw selected, the BO outputs for the TBO set time if the input signal does
not continue on the TBO set time. If the input signal continues more, the BO output is continuous
for the input signal time.
The relay failure contact closes when a relay defect or abnormality in the DC power supply circuit
is detected.

Signal List
&
Appendix B

Auxiliary relay

4 GATES
&

or
1

1
TBO

4 GATES
&

&

"Inst"
"Dw"

[RESET]

0.00 10.00s

"Dl"

&

"Lat"

S
F/F
R

Reset button
1

REMOTE RESET

Figure 3.2.3 Configurable Output

Settings

The setting elements necessary for binary output relays and their setting ranges are as follows:
Element
[RESET]

Range
Inst / Dl / Dw /Latch

Step

Default
See Appendix C

TBO

0.00 10.00s

0.01s

See Appendix C

90

Remarks
Output relay reset time. Instantaneous,
delayed, dwell or latched.

6 F 2 S 0 7 5 8

3.3

Automatic Supervision
3.3.1

Basic Concept of Supervision


Though the protection system is in a non-operating state under normal conditions, it waits for a
power system fault to occur at any time, and must operate for the fault without fail. Therefore, the
automatic supervision function, which checks the health of the protection system during normal
operation, plays an important role. The GRD140 implements an automatic supervision function,
based on the following concepts:
The supervising function should not affect the protection performance.
Perform supervision with no omissions wherever possible.
When a failure occurs, it is recorded as Alarm record, the user should be able to easily identify
the location of the failure.

3.3.2

Relay Monitoring
The relay is supervised by the following functions.
AC input imbalance monitoring

The AC current input is monitored to check that the following equation is satisfied and the health
of the AC input circuit is verified.
CT circuit current monitoring for [APPL-CT] = 3P setting

Max(|Ia|, |Ib|, |Ic|) 4 Min(|Ia|, |Ib|, |Ic|) k0


where,
Max(|Ia|, |Ib|, |Ic|) = Maximum amplitude among Ia, Ib and Ic
Min(|Ia|, |Ib|, |Ic|) = Minimum amplitude among Ia, Ib and Ic
k0 = 20% of rated current
Zero sequence voltage monitoring for [APPL-VT]= 3PN setting

|Va + Vb + Vc| / 3 6.35 (V)


Negative sequence voltage monitoring for [APPL-VT]= 3PN and 3PV setting

|Va + a2Vb + aVc| / 3 6.35 (V)


where, a = Phase shifter of 120, a2 = Phase shifter of 240
The CT circuit current monitoring allows high sensitivity detection of failures that have occurred
in the AC input circuit. This monitoring can be disabled by the scheme switch [CTSVEN].
The zero sequence monitoring and negative sequence monitoring allow high sensitivity detection
of failures that have occurred in the AC input circuits. These monitoring can be disabled by the
scheme switches [V0SVEN] and [V2SVEN] respectively.
The negative sequence voltage monitoring allows high sensitivity detection of failures in the
voltage input circuit, and it is effective for detection particularly when cables have been connected
with the incorrect phase sequence.
A/D accuracy checking

An analog reference voltage is input to a prescribed channel in the analog-to-digital (A/D)


converter, and it is checked that the data after A/D conversion is within a prescribed range, and

91

6 F 2 S 0 7 5 8
that the A/D conversion characteristics are correct.
Memory monitoring

Memory is monitored as follows, depending on the type of memory, and checks are done to verify
that memory circuits are healthy:
Random access memory monitoring:
Writes/reads prescribed data and checks the storage function.
Program memory monitoring: Checks the checksum value of the written data.
Setting value monitoring:

Checks discrepancies between the setting values stored in


duplicate.

Watchdog Timer

A hardware timer that is cleared periodically by the software is provided, which checks that the
software is running normally.
DC Supply Monitoring

The secondary voltage level of the built-in DC/DC converter is monitored, and is checked to see
that the DC voltage is within a prescribed range.

3.3.3

CT Failure Supervision
This function is available for [APPL-CT] = 3P setting only.
Figure 3.3.1 shows the scheme logic of the CT failure supervision (CTFS). If the residual
overcurrent element EFF(EFCF) operates and the residual overvoltage element ZOVF(ZOVCF)
does not operate, CT failure (CTF) is detected. When the CTFS detects a CTF, it can alarm and
block various protections as EF, NOC and UC protections etc.
The CTF signal is reset 100 ms after the CT failure condition has reset. When the CTF continues
for 10s or more, Err: CTF is displayed in LCD message.
Further, the CT failure is detected when the binary input signal (external CTF) is received.
This function can be enabled or disabled by the scheme switch [CTFEN] and has a programmable
reset characteristic. For latching operation, set to ON, and for automatic reset after recovery, set
to OPT-ON.

EFF

&

ZOVF

&
&

&

0.015s

0.1s

1
"OPT-ON"

CB CLOSE
A.M.F. ON
CTF BLOCK

CB NON BLK

1
0.2s

EXT CTF

Figure 3.3.1

CT Failure Supervision

92

CTF

[CTFEN] "ON"

&

10s

CTF ALM

6 F 2 S 0 7 5 8
3.3.4

VT Failure Supervision
This function is available for [APPL-VT] = 3PN and 3PV settings.
When a fault occurs in the secondary circuit of the voltage transformer (VT), the voltage
dependent measuring elements may operate incorrectly. GRD140 incorporates a VT failure
supervision function (VTFS) as a measure against such incorrect operation. When the VTFS
detects a VT failure, it can alarm and block the following voltage dependent protections by a
binary input.
Directional overcurrent protection
Directional earth fault protection
Directional sensitive earth fault protection
Directional negative overcurrent protection
Undervoltage protection
Zero phase sequence overvoltage protection
Negative phase sequence overvoltage protection

A binary input signal (external VTF) to indicate a miniature circuit breaker trip in the VT circuits
is also available for the VTFS.
Scheme logic

Figure 3.3.2 shows the scheme logic for the VTFS. VT failure is detected by the following two
schemes.
VTF1: The residual overcurrent element EFF(EFVF) does not operate (EFF=0), the residual
overvoltage element ZOVF(ZOVVF) operates (ZOVF=1) and the phase current
change detection element OCDF(OCDVF) does not operate (OCDF=0).
VTF2: The phase undervoltage element UVF(UVVF) operates (UVF=1) when the three
phases of the circuit breaker are closed (CB CLOSE=1) and the phase current change
detection element OCDF(OCDVF) does not operate (OCDF=0).
In order to prevent detection of false VT failures due to unequal pole closing of the circuit breaker,
the VTFS is blocked for 200 ms after line energization.
The VTF signal is reset 100 ms after the VT failure condition has reset. When the VTF continues
for 10s or more, Err: VTF1 or Err: VTF2 is displayed in LCD message.
Further, the VT failure is detected when the binary input signal (external VTF) is received.
This function can be enabled or disabled by the scheme switch [VTF1EN] or [VTF2EN] and has a
programmable reset characteristic. For latching operation, set to ON, and for automatic reset
after the recover, set to OPT-ON.

93

6 F 2 S 0 7 5 8
t

A
UVF

OCDF B

&

t
0

&

VTF1

&

NON VTF1

0.1s

&
1

VTF

NON VTF

&

"OPT-ON"

0.015s

S
F/F
R

0.1s

"ON"

VTF1 ALM

10s

[VTF1EN]

VTF2 ALM

CB CLOSE
10s

ZOVF

&
1

EFF

&

&

0.015s

[VTF2EN]

VTF2

&

NON VTF2

0.1s

&

"ON"

"OPT-ON"

CB NON BLK
A.M.F. ON
VTF BLOCK

EXT VTF

Figure 3.3.2

3.3.5

VT Failure Supervision

Trip Circuit Supervision


The circuit breaker tripping control circuit can be monitored by a binary input. Figure 3.3.3 shows
a typical scheme. When the trip circuit is complete, a small current flows through the binary input
and the trip circuit. Then logic signal of the binary input circuit BI is "1".
If the trip supply is lost or if a connection becomes an open circuit, then the binary input resets and
the BI output is "0". A trip circuit fail alarm TCSV is output when the BI output is "0".
If the trip circuit failure is detected, then ALARM LED is lit and Err: TC is displayed in LCD
message.
The monitoring is enabled by setting the scheme switch [TCSPEN] to "ON" or "OPT-ON". When
"OPT-ON" is selected, the monitoring is enabled only while CB is closed.
(+)

Trip circuit supervision


BI

Trip
output

1
CB CLOSE
[TCSPEN]

"OPT-ON"

&

&
0.4s
1

"ON"

CB trip coil

Figure 3.3.3

Trip Circuit Supervision Scheme Logic

94

TCSV

6 F 2 S 0 7 5 8
3.3.6

Circuit Breaker Monitoring


The relay provides the following circuit breaker monitoring functions.

Circuit Breaker State Monitoring

Circuit breaker state monitoring is provided for checking the health of circuit breaker (CB). If two
binary inputs are programmed to the functions CB OPEN and CB CLOSED, then the CB state
monitoring function becomes active. In normal circumstances these inputs are in opposite states.
Figure 3.3.4 shows the scheme logic. If both show the same state during five seconds, then a CB
state alarm CBSV operates and Err:CB and CB err are displayed in LCD message and event
record message respectively.
The monitoring can be enabled or disabled by setting the scheme switch [CBSMEN].
CB CONT OPN

=1

(BI command)

&

CBSV

5.0s

CB CONT CLS
(BI command)
[CBSMEN]

"ON"

Figure 3.3.4 CB State Monitoring Scheme Logic

Normally open and normally closed contacts of the CB are connected to binary inputs BIm and
BIn respectively, and functions of BIm and BIn are set to CBOPN=ON and CBCLS=ON.
(Refer to Section 4.2.6.8.)
Circuit Breaker Condition Monitoring

Periodic maintenance of CB is required for checking of the trip circuit, the operation mechanism
and the interrupting capability. Generally, maintenance is based on a time interval or a number of
fault current interruptions.
The following CB condition monitoring functions are provided to determine the time for
maintenance of CB:
Trip is counted for maintenance of the trip circuit and CB operation mechanism. The trip
counter increments the number of tripping operations performed. An alarm is issued and
informs user of time for maintenance when the count exceeds a user-defined setting TCALM.
The trip count alarm can be enabled or disabled by setting the scheme switch [TCAEN].
Sum of the broken current quantity Iy is counted for monitoring the interrupting capability of
CB. The Iy counter increments the value of current to the power y, recorded at the time of
issue of the tripping signal, on a phase by phase basis. For oil circuit breakers, the dielectric
withstand of the oil generally decreases as a function of I2t, and maintenance such as oil
changes, etc., may be required. I is the fault current broken by CB. t is the arcing time
within the interrupter tank and it cannot be determined accurately. Therefore, y is normally
set to 2 to monitor the broken current squared. For other circuit breaker types, especially those
for HV systems, y may be set lower, typically 1.0. An alarm is issued when the count for any
phase exceeds a user-defined setting IyALM. This feature is not available in GRD140-110.
The Iy count alarm can be enabled or disabled by setting the scheme switch [IyAEN].
Operating time monitoring is provided for CB mechanism maintenance. It checks CB
operating time and the need for mechanism maintenance is informed if the CB operation is
slow. The operating time monitor records the time between issuing the tripping signal and the
phase currents falling to zero. An alarm is issued when the operating time for any phase

95

6 F 2 S 0 7 5 8
exceeds a user-defined setting OPTALM. The operating time is set in relation to the specified
interrupting time of the CB. The operating time alarm can be enabled or disabled by setting the
scheme switch [OPTAEN].
The maintenance program should comply with the switchgear manufacturers instructions.
The CB condition monitoring functions are triggered each time a trip is issued, and they can also
be triggered by an external device via binary input EXT TRIP3PH (EXT3PH) or EXT TRIPPH
(EXTPH) as shown in Figure 3.3.5. (Refer to Section 4.2.6.8.)
(+) ()

External trip
three-phase

GRD140
BIa

External trip
A-phase
BIb

Figure 3.3.5

3.3.7

Binary input setting


BIa command

[EXT3PH]
"ON"

BIb command

[EXTAPH]
"ON"

EXT3PH

EXTAPH

Binary Input Setting for CB Condition Monitoring

Failure Alarms
When a failure is detected by the automatic supervision, it is followed with an LCD message, LED
indication, external alarm and event recording. Table 3.3.1 summarizes the supervision items and
alarms.
The LCD messages are shown on the "Auto-supervision" screen, which is displayed automatically
when a failure is detected or displayed by pressing the VIEW key. The event record messages
are shown on the "Event record" screen by opening the "Record" sub-menu.

The alarms are retained until the failure is recovered.


The alarms can be disabled collectively by setting the scheme switch [AMF] to "OFF". The AC
input imbalance monitoring alarms can be disabled collectively by setting the scheme switches
[CTSVEN], [V0SVEN] and [V2SVEN] to "OFF". The setting is used to block unnecessary alarms
during commissioning, test or maintenance.
When the Watchdog Timer detects that the software is not running normally, LCD display and
event recording of the failure may not function normally.

96

6 F 2 S 0 7 5 8

Table 3.3.1 Supervision Items and Alarms


Supervision Item

LED
"IN
SERVICE"

LED
"ALARM"

Err:CT, Err:V0,
Err:V2 (1)

On/Off (2)

On

(4)

CT err, V0 err, V2 err,


Relay fail or Relay fail-A (2)

A/D accuracy check

Err:A/D

Off

On

(4)

Relay fail

Memory monitoring

Err:SUM, Err:RAM,
Err:BRAM, Err:EEP

Off

On

(4)

Relay fail

----

Off

On

(4)

----

DC supply monitoring

Err:DC

Off

(3)

Off

Relay fail-A

Trip circuit supervision

Err:TC

On

On

Off

TC err, Relay fail-A

CB state monitoring

Err:CB

On

On

Off

CB err, Relay fail-A

ALM:TP COUNT

On

On

Off

TP COUNT ALM,
Relay fail-A

ALM: OP time

On

On

Off

OP time ALM, Relay fail-A

Iy count alarm

ALM:IY

On

On

Off

IY-A ALM, IY-B ALM or


IY-C ALM, Relay fail-A

CT failure supervision

Err:CTF

On

On

Off

CTF err, Relay fail-A

VT failure supervision

Err:VTF1, Err:VTF2

On

On

Off

VTF1 err, VTF2 err,


Relay fail-A

AC input
monitoring

imbalance

LCD Message

Watchdog Timer

External
alarm

Alarm record Message

CB condition monitoring
Trip count alarm
Operating time alarm

(1): Diverse messages are provided as expressed with "Err:---" in the table in Section 6.7.2.
(2): The LED is on when the scheme switch [CTSVEN], [V0SVEN] or [V2SVEN] is set to "ALM"
and off when set to "ALM & BLK" (refer to Section 3.3.6). The message "Relay fail-A" is
recorded when the scheme switch [SVCNT] is set to "ALM".
(3): Whether the LED is lit or not depends on the degree of the voltage drop.
(4): The binary output relay "FAIL" operates.

The relationship between the LCD message and the location of the failure is shown in Table 6.7.1
in Section 6.7.2.

3.3.8

Trip Blocking
When a failure is detected by the following supervision items, the trip function is blocked as long
as the failure exists, and is restored when the failure is removed.
A/D accuracy check
Memory monitoring
Watchdog Timer

When a fault is detected by the AC input imbalance monitoring, the scheme switches [CTSVEN],
[V0SVEN] and [V2SVEN] setting can be used to determine if both tripping is blocked and an
alarm is output, or if only an alarm is output.

97

6 F 2 S 0 7 5 8
3.3.9

Setting
The setting element necessary for the automatic supervision and its setting range are shown in the
table below.
Element
CTF supervision
EFF

Range

Step

Default

Remarks

0.1 - 25.0 A
( 0.02 - 5.00 A
5.0 130.0 V

0.1 A
0.01 A
0.1 V

1.0 A
0.20 A) (*)
20.0 V

Residual overcurrent threshold setting

0.1 V

51.0 V

Undervoltage threshold setting


Phase current change detection

[CTFEN]
[VTF1EN]
[VTF2EN]
[CTSVEN]
[V0SVEN]
[V2SVEN]
[TCSPEN]
[CBSMEN]

5.0 130.0 V
0.5 A (Fixed)
( 0.1 A (Fixed) )
Off/On/OPT-On
Off/On/OPT-On
Off/On/OPT-On
Off/ALM&BLK/ALM
Off/ALM&BLK/ALM
Off/ALM&BLK/ALM
Off/On/OPT-On
Off/On

Off
Off
Off
ALM
ALM
ALM
Off
Off

CTF supervision
VTF1 supervision
VTF2 supervision
AC input imbalance monitoring (current)
AC input imbalance monitoring (Vo)
AC input imbalance monitoring (V2)
Trip circuit supervision
CB condition supervision

[TCAEN]

OFF/ON

OFF

Trip count alarm

[IyAEN]

OFF/ON

OFF

Iy count alarm

[OPTAEN]

OFF/ON

OFF

Operate time alarm

TCALM

1 - 10000

10000

Trip count alarm threshold setting

IyALM

10 10000 E6

E6

10000

Iy alarm threshold setting

YVALUE

1.0 2.0

0.1

2.0

y value setting

OPTALM

100 5000 ms

10 ms

1000 ms

Operate time alarm threshold setting

ZOVF
VTF supervision
UVF
OCDF

Residual overvoltage threshold setting

(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.

When setting the ZOVF and EFF, the maximum detection sensitivity of each element should be
set with a margin of 15 to 20% taking account of variations in the system voltage, the asymmetry
of the primary system and CT and VT error.

98

6 F 2 S 0 7 5 8

3.4

Recording Function
The GRD140 is provided with the following recording functions:
Fault recording
Event recording
Disturbance recording
Counters
These records are displayed on the LCD of the relay front panel or on the local or remote PC.

3.4.1

Fault Recording
Fault recording is started by a tripping command of the GRD140 and the following items are
recorded for one fault:
Date and time
Trip mode
Operating phase
Fault location
Relevant events
Power system quantities
Up to the 8 most-recent faults are stored as fault records. If a new fault occurs when 8 faults have
been stored, the record of the oldest fault is deleted and the record of the latest fault is then stored.
Date and time occurrence

This is the time at which a tripping command has been initiated.


The time resolution is 1 ms using the relay internal clock.
Trip mode

This shows the protection scheme such as OC1, EF1, UV1 etc. that output the tripping command.
Operating phase

This is the phase to which a tripping command is output.


Fault location

The distance to the fault point calculated by the fault locator is recorded.
The distance is expressed in km and as a percentage (%) of the line length.
Relevant events

Such events as autoreclose, re-tripping following the reclose-on-to-a fault or autoreclose are
recorded with time-tags.
Power system quantities

The following power system quantities in pre-faults and post-faults are recorded.
-

Magnitude and phase angle of phase voltage (Va, Vb, Vc)

Magnitude and phase angle of phase-to-phase voltage (Vab, Vbc, Vca)

Magnitude and phase angle of symmetrical component voltage (V1, V2, V0)

Magnitude and phase angle of zero sequence voltage which is measured directly in the form of

99

6 F 2 S 0 7 5 8
the system residual voltage (Ve)
-

Magnitude and phase angle of phase current (Ia, Ib, Ic)

Magnitude and phase angle of symmetrical component current (I1, I2, I0)

Magnitude and phase angle of zero sequence current from residual circuit (Ie)

Magnitude and phase angle of zero sequence current from core balance CT (Ise) for model 110
and 420 series

Percentage of thermal capacity (THM%) only recorded at post-fault

Frequency (f)

The displayed power system quantities depend on [APPL-CT] and [APPL-VT] setting for models
400, 430 and 420 as shown in Table 3.4.1.
Table 3.4.1 Displayed Power System Quantities
Power system quantities

[APPL-CT]

[APPL-VT]

3P

2P

1P

3PN

3PV

2PP

Phase voltage

Va, Vb, Vc

Va, Vb, Vc

Phase-to-phase voltage

Vab, Vbc, Vca(*3)

Residual voltage

Ve

Ve

Symmetrical component
voltage

V1, V2, V0

Phase current

Ia, Ib, Ic

Ia, Ic

Zero sequence current from


residual circuit

Ie (*1) or
Ise(*2)

Ie (*1) or
Ie, Ise(*2)

Ie (*1) or
Ie, Ise(*2)

Symmetrical component
current

I1, I2, I0

Percentage of thermal
capacity

THM

THM

Note: (*1) marked for Model 400 and 430. In Model 430, [APPL-CT]=3P is fixed.
(*2) marked for Model 420.
(*3) In these phase names, Vab, Vbc and Vca are expressed as Va, Vb and Vc. Vca is
calculated value from Vab and Vbc.

3.4.2

Event Recording
The events shown in Appendix D are recorded with the 1 ms resolution time-tag when the status
changes. For BI1 to BI8 command, the user can select the recording items and their status change
mode to initiate recording as below.
One of the following four modes is selectable.
Modes

Setting

Not to record the event.

To record the event when the status changes to "operate".

To record the event when the status changes to "reset".

To record the event when the status changes both to "operate" and "reset".

100

6 F 2 S 0 7 5 8
For the setting, see the Section 4.2.6.5. The default setting is "B"
Up to 480 records can be stored. If an additional event occurs when 480 records have been stored,
the oldest event record is deleted and the latest event record is then stored.

3.4.3

Disturbance Recording
Disturbance recording is started when the overcurrent, overvoltage or undervoltage starter
element operates or a tripping command is initiated. The records include maximum 8 analogue
signals as shown in Table 3.4.2, 32 binary signals and the dates and times at which recording
started. Any binary signal shown in Appendix C can be assigned by the binary signal setting of
disturbance record.
Table 3.4.2 Analog Signals for Disturbance Recording
Model

Model 110

Model 400

Model 420

Model 430

I0

Ie(I0), Ise(I0)

--

Ia, Ic, Ie(I0)

Ia, Ic, Ie(I0), Ise(I0)

--

APPL CT = 3P

Ia, Ib, Ic, Ie(I0)

Ia, Ib, Ic, Ise(I0)

Ia, Ib, Ic, Ie

APPL VT = 3PN

Va, Vb, Vc

Va, Vb, Vc

Va, Vb, Vc

Va, Vb, Vc, Ve(V0)

Va, Vb, Vc, Ve(V0)

Va, Vb, Vc, Ve(V0)

Vab, Vbc, Vca, Ve (*)

Vab, Vbc, Vca, Ve (*)

Vab, Vbc, Vca, Ve (*)

APPL setting
APPL CT = 1P
CT

VT

APPL CT = 2P

APPL VT = 3PV

Ie(I0), Ise(I0)

Ve(V0)

APPL VT = 2PP

Note: (*) In these phase names, Vab, Vbc and Vca are expressed as Va, Vb and Vc. Vca is
calculated value from Vab and Vbc.

The LCD display only shows the dates and times of disturbance records stored. Details can be
displayed on a PC. For how to obtain disturbance records on the PC, see the PC software
instruction manual.
The pre-fault recording time is fixed at 0.3s and post-fault recording time can be set between 0.1
and 3.0s.
The number of records stored depends on the post-fault recording time. The approximate
relationship between the post-fault recording time and the number of records stored is shown in
Table 3.4.3.
Note: If the recording time setting is changed, the records stored so far are deleted.
Table 3.4.3 Post Fault Recording Time and Number of Disturbance Records Stored
Recording time

0.1s

0.5s

1.0s

1.5s

2.0s

2.5s

3.0s

50Hz

40

23

14

10

60Hz

38

19

11

101

6 F 2 S 0 7 5 8

Settings

The elements necessary for initiating a disturbance recording and their setting ranges are shown in
the table below.
Element

Range

Step

Default

Remarks

OC

0.1-250.0 A

0.1 A

10.0 A

Overcurrent detection

(0.02-50.00 A

0.01 A

2.00 A) (*)

0.1-125.0 A

0.1 A

3.0 A

(0.02-25.00 A

0.01 A

0.60A)

0.01-1.00 A

0.01 A

1.00 A

(0.002-0.200 A

0.001 A

0.200 A)

0.5-10.0 A

0.1 A

2.0 A

(0.10-2.00 A

0.01 A

0.40 A)

OV

10.0-200.0 V

0.1 V

120.0 V

Overvoltage detection

UV

1.0-130.0 V

0.1 V

60.0 V

Undervoltage detection

ZOV

1.0-130.0 V

0.1 V

20.0 V

Zero sequence overvoltage detection

NOV

1.0-130.0 V

0.1 V

20.0 V

Negative sequence overvoltage detection

EF
SEF
NC

Earth fault detection


Sensitive earth fault detection
Negative sequence overcurrent detection

(*) Current values shown in the parentheses are for the case of a 1A rating. Other current values are
for the case of a 5A rating.

Starting the disturbance recording by a tripping command or the starter element listed above is
enabled or disabled by setting the following scheme switches.
Element

Range

[Trip]

Step

Default

Remarks

OFF/ON

ON

Start by tripping command

[BI]

OFF/ON

ON

Start by Binary Input signal

[OC]

OFF/ON

ON

Start by OC operation

[EF]

OFF/ON

ON

Start by EF operation

[SEF]

OFF/ON

ON

Start by SEF operation

[NC]

OFF/ON

ON

Start by NC operation

[OV]

OFF/ON

ON

Start by OV operation

[UV]

OFF/ON

ON

Start by UV operation

[ZOV]

OFF/ON

ON

Start by ZOV operation

[NOV]

OFF/ON

ON

Start by NOV operation

102

6 F 2 S 0 7 5 8

3.5

Metering Function
The GRD140 measures current and demand values of phase currents, phase and phase-to-phase
voltages, residual current, residual voltage, symmetrical component currents and voltages,
frequency, power factor, active and reactive power, and apparent power. The measurement data
shown below is displayed on the LCD of the relay front panel or on the local or remote PC.
Current
The following quantities are measured and updated every second.
-

Magnitude and phase angle of phase current (Ia, Ib, Ic)

Magnitude and phase angle of zero sequence current from residual circuit (Ie)

Magnitude and phase angle of zero sequence current from core balance CT (Ise) for model 110
and 420 series

Magnitude of positive and negative sequence currents (I1, I2)

The ratio of negative to positive sequence current (I2/I1)

Magnitude and phase angle of phase voltage (Va, Vb, Vc)

Magnitude and phase angle of phase-to-phase voltage (Vab, Vbc, Vca)

Magnitude and phase angle of zero sequence voltage which is measured directly in the form of
the system residual voltage (Ve)

Magnitude and phase angle of symmetrical component voltage (V1, V2, V0)

Active power (P)

Reactive power (Q)

Apparent power (S)

Power factor (PF)

Active energy (Wh)

Reactive energy (varh)

Frequency (f)

Percentage of thermal capacity (THM%)

Direction of each current (Ia, Ib, Ic, Ie, Ise, I2)

Demand
-

Maximum and minimum of phase voltage (Va, Vb, Vc: max, min)

Maximum and minimum of zero sequence voltage (V0: max, min)

Maximum and minimum of zero sequence voltage which is measured directly in the form of
the system residual voltage (Ve: max, min)

Maximum of phase current (Ia, Ib, Ic: max.)

Maximum of zero sequence current from residual circuit (Ie: max)

Maximum of zero sequence current from core balance CT (Ise: max) for model 110 and 420 series

Maximum of negative sequence current (I2: max.)

Maximum of the ratio of negative to positive sequence current (I2/I1(I21): max)

103

6 F 2 S 0 7 5 8
-

Maximum of active power (P: max.)

Maximum of reactive power (Q: max.)

Maximum of apparent power (S: max.)

Maximum and minimum of frequency (f: max, min)

The above system quantities are displayed in values on the primary side or on the secondary side
as determined by a setting. To display accurate values, it is necessary to set the CT ratio as well.
For the setting method, see "Setting the metering" in 4.2.6.6 and "Setting the parameter" in 4.2.6.7.
In the case of the maximum and minimum values display above, the measured quantity is averaged
over a rolling 15 minute time window, and the maximum and minimum recorded average values
are shown on the display screen.
The displayed quantities depend on [APPL-CT] and [APPL-VT] setting as shown in Table 3.5.1.
Input current and voltage greater than 0.01In(rated current) and 0.06V at the secondary side are
required for the measurement.
The zero sequence current Ie in 3P setting of the model 420 is calculated from the three phase
input currents and the calculated Ie (I0) is displayed. The Ie displayed in other settings and models
is the current fed from CT.
Phase angles above are expressed taking the positive sequence voltage as a reference phase angle,
where leading phase angles are expressed as positive, (+).
The signing of active and reactive power flow direction can be set positive for either power
sending or power receiving. The signing of reactive power can be also set positive for either
lagging phase or leading phase.
Table 3.5.1
Model

Displayed Quantity Depends on APPL setting

110

430

400

420

400, 420, 430

--

APPL-CT

APPL-CT

APPL-CT

APPL-VT

APPL
setting

--

1P

2P

3P

1P

2P

3P

3PN

3PV

2PP

--

--

--

--

--

--

Ib

--

--

--

--

--

--

--

--

Ic

--

--

--

--

--

--

Ie (Io)

--

--

--

Ise

--

--

--

--

--

--

--

I1

--

--

--

--

--

--

--

--

I2

--

--

--

--

--

--

--

--

I2/I1

--

--

--

--

--

--

--

--

Va

--

--

--

--

--

--

--

--

0 (*)

Vb

--

--

--

--

--

--

--

--

0 (*)

Vc

--

--

--

--

--

--

--

--

0 (*)

Vab

--

--

--

--

--

--

--

--

Vbc

--

--

--

--

--

--

--

--

Vca

--

--

--

--

--

--

--

--

Ve

--

--

--

--

--

--

--

--

V1

--

--

--

--

--

--

--

--

V2

--

--

--

--

--

--

--

--

V0

--

--

--

--

--

--

--

--

0 (*)

Quantity
Ia

104

6 F 2 S 0 7 5 8
Model

110

430

400

420

400, 420, 430

--

APPL-CT

APPL-CT

APPL-CT

APPL-VT

APPL
setting

--

1P

2P

3P

1P

2P

3P

3PN

3PV

2PP

--

--

--

--

--

--

--

--

--

PF

--

--

--

Wh

--

--

--

--

varh

--

--

--

--

--

--

--

--

--

--

--

--

THM

--

--

--

--

--

--

--

--

Quantity
P

Note: (*) These quantities are indicated as 0 at all times.

105

6 F 2 S 0 7 5 8

3.6

Fault locator
3.6.1

Application
The fault locator incorporated in the GRD140 measures the distance to fault on the protected line
using local voltages and currents. The measurement result is expressed as a percentage (%) of the
line length and the distance (km) and is displayed on the LCD on the relay front panel. It is also
output to a local PC or RSM (relay setting and monitoring) system.
To measure the distance to fault, the fault locator requires minimum 3 cycles as fault duration
time.
In distance to fault calculations, the change in the current before and after the fault has occurred is
used as a reference current, alleviating influences of the load current and arc voltage. As a result,
the location error is a maximum of 2.5 km for faults at a distance of up to 100 km, and a
maximum of 2.5% for faults at a distance between 100 km and 250 km.
The fault locator is available for [APPL-CT]= "3P" and [APPL-VT]= "3PN" or "3PV" setting.
The fault locator cannot correctly measure the distance to fault during a power swing.

3.6.2

Distance to Fault Calculation


The distance to fault x1 is calculated from equation (1) and (2) using the voltage and current of the
fault phase and a current change before and after the fault occurrence. The current change before
and after the fault occurrence represented by I" and I" is used as the reference current. The
impedance imbalance compensation factor is used to maintain high measuring accuracy even
when the impedance of each phase has great variations.
Distance calculation for phase fault (in the case of BC-phase fault)

Im(Vbc I") L
x 1 = {I (R I I") + R (X I I")} K
m 1 bc
e 1 bc
bc

(1)

where,
Vbc = fault voltage between faulted phases = Vb Vc
Ibc = fault current between faulted phases = Ib Ic
I" = change of fault current before and after fault occurrence = (Ib-Ic) (ILb-ILc)
ILb, ILc = load current
R1 = resistance component of line positive sequence impedance
X1 = reactance component of line positive sequence impedance
Kbc = impedance imbalance compensation factor
Im( ) = imaginary part in parentheses
Re( ) = real part in parentheses
L = line length (km)

106

6 F 2 S 0 7 5 8
Distance calculation for earth fault (in the case of A-phase earth fault)
x1=

Im(Va I") L

{Im(R1 I I" + R0 I0S I") + Re(X1 I I" + X0 I0S I")} Ka

(2)

where,
Va = fault voltage
I = fault current = (2Ia Ib Ic)/3
I" = change of fault current before and after fault occurrence
=

2Ia Ib Ic 2ILa ILb ILc

3
3

Ia, Ib, Ic = fault current


ILa, ILb, ILc = load current
I0s = zero sequence current
R1 = resistance component of line positive sequence impedance
X1 = reactance component of line positive sequence impedance
R0 = resistance component of line zero sequence impedance
X0 = reactance component of line zero sequence impedance
Ka = impedance imbalance compensation factor
Im( ) = imaginary part in parentheses
Re( ) = real part in parentheses
L = line length (km)
Equations (1) and (2) are general expressions when lines are treated as having lumped constants
and these expressions are sufficient for lines within 100 km. For lines exceeding 100 km,
influences of the distributed capacitance must be considered. For this fault locator, the following
equation is used irrespective of line length to find the compensated distance x2 with respect to
distance x1 which was obtained in equation (1) or (2).
x1
x2 = x1 k2 3

(3)

where,
k = propagation constant of the protected line = 0.001km-1 (fixed)

3.6.3

Starting Calculation
Calculation of the fault location is initiated by the operation of OC element. It is initiated only
when the direction of fault is forward (FWD).

3.6.4

Displaying Location
The measurement result is stored in the "Fault record" and displayed on the LCD of the relay front
panel or on the local or remote PC. For displaying on the LCD, see Section 4.2.3.1.

107

6 F 2 S 0 7 5 8
3.6.5

Setting
The setting items necessary for the fault location and their setting ranges are shown in the table
below. The reactance and resistance values are input in expressions on the secondary side.
When there are great variations in the impedance of each phase, equation (4) is used to find the
positive sequence impedance, zero sequence impedance and zero sequence mutual impedance,
while equation (5) is used to find imbalance compensation factors Kab to Ka.
When variations in impedance of each phase can be ignored, the imbalance compensation factor is
set to 100%.
Z1 = {(Zaa + Zbb + Zcc) (Zab + Zbc + Zca)}/3
Z0 = {(Zaa + Zbb + Zcc) + 2(Zab + Zbc + Zca)}/3

(4)

Kab = {(Zaa + Zbb)/2 Zab}/Z1


Kbc = {(Zbb + Zcc)/2 Zbc}/Z1
Kca = {(Zcc + Zaa)/2 Zca}/Z1

(5)

Ka = {Zaa (Zab + Zca)/2}/Z1


Kb = {Zbb (Zbc + Zab)/2}/Z1
Kc = {Zcc (Zca + Zab)/2}/Z1

Item

Range

Step

Default

R1

0.0 - 199.99

0.01

0.20

(0.0 - 999.9

0.1

1.0) (*)

0.0 - 199.99

0.01

2.00

(0.0 - 999.9

0.1

10.0)

0.0 - 999.99

0.01

0.70

(0.0 - 999.9

0.1

3.5)

0.0 - 199.99

0.01

6.80

(0.0 - 999.9

0.1

34.0)

Kab

80 - 120%

1%

100%

Kbc

80 - 120%

1%

100%

Kca

80 - 120%

1%

100%

Ka

80 - 120%

1%

100%

Kb

80 - 120%

1%

100%

Kc

80 - 120%

1%

100%

Line

0 - 399.9 km

0.1 km

50.0km

X1
R0
X0

Remarks

(*) Ohmic values shown in the parentheses are in the case of 1 A rating. Other ohmic values are
in the case of 5A rating.

108

6 F 2 S 0 7 5 8

4. User Interface
4.1

Outline of User Interface


The user can access the relay from the front or rear panel.
Local communication with the relay is also possible using a personal computer (PC) via an
RS232C port. Furthermore, remote communication is also possible using RSM (Relay Setting and
Monitoring) or IEC60870-5-103 communication via RS485 port.
This section describes the front panel configuration and the basic configuration of the menu tree of
the local human machine communication ports and HMI (Human Machine Interface).

4.1.1

Front Panel
As shown in Figure 3.1.3, the front panel is provided with a liquid crystal display (LCD), light
emitting diodes (LED), operation keys, and RS-232C connector.
LCD

The LCD screen, provided with a 2-line, 16-character display and back-light, provides the user
with information such as records, statuses and settings. The LCD screen is normally unlit, but
pressing the VIEW key will display the digest screen and pressing any key other than VIEW
and RESET will display the menu screen.
These screens are turned off by pressing the RESET key or END key. If any display is left for 5
minutes or longer without operation, the back-light will go off.
LED

There are 6 LED displays. The signal labels and LED colors are defined as follows:
Label

Color

Remarks

IN SERVICE

Green

Lit when the relay is in service and flickered when the relay is in Test menu.

TRIP
ALARM
(LED1)
(LED2)
(LED3)

Red
Red
Yellow
Yellow
Yellow

Lit when a trip command is issued.


Lit when a failure is detected.

LED1, LED2 and LED3 are configurable. For the setting, see Section 4.2.6.10.
The TRIP LED lights up once the relay is operating and remains lit even after the trip command
goes off. The TRIP LED can be turned off by pressing the RESET key. Other LEDs are lit as
long as a signal is present and the RESET key is invalid while the signal is being maintained.

109

6 F 2 S 0 7 5 8

Operation keys

The operation keys are used to display records, status, and set values on the LCD, as well as to
input or change set values. The function of each operation key is as follows:
c

: Used to move between lines displayed on a screen and to enter numerical


values and text strings.

d CANCEL :

Used to cancel entries and return to the upper screen.

e END :

Used to end the entering operation, return to the upper screen or turn off the
display.

f ENTER :

Used to store or establish entries.

VIEW and RESET keys

Pressing VIEW key displays digest screens such as "Metering", "Latest fault",
"Auto-supervision", "Alarm display" and "Indication".
Pressing RESET key turns off the display.
Monitoring jacks

The two monitoring jacks A and B and their respective LEDs can be used when the test mode is
selected on the LCD screen. By selecting the signal to be observed from the "Signal List" and
setting it on the screen, the signal can be displayed on LED A or LED B, or transmitted to an
oscilloscope via a monitoring jack.
RS232C connector

The RS232C connector is a 9-way D-type connector for serial RS232C connection with a local
personal computer.

110

6 F 2 S 0 7 5 8
4.1.2

Communication Ports
The following two interfaces are mounted as communication ports:

RS232C port

RS485 port or optional fibre optic port

RS232C port

This connector is a standard 9-way D-type connector for serial port RS232C transmission and is
mounted on the front panel. By connecting a personal computer to this connector, setting
operation and display functions can be performed.
RS485 port or optional fibre optic port

RS485 and optional fibre optic ports are screw terminals and ST connector, and mounted on the
back of the relay.
The RS485 port is used for the RSM (Remote Setting and Monitoring system) via the protocol
converter G1PR2 and IEC60870-5-103 communication via BCU/RTU (Bay Control Unit /
Remote Terminal Unit) or Modbus to connect between relays and to construct a network
communication system. (See Figure 4.4.1 in Section 4.4.)
One or two RS485 ports (COM1 and COM2) is provided on the rear of the relay as shown in
Figure 4.1.1. In the relay provided with two RS485 ports, COM1 is used for the RSM or
IEC60870-5-103 or Modbus communication, and COM2 used for IEC60870-5-103 or Modbus
communication. When the COM1 is used for IEC60870-5-103 or Modbus communication, the
COM2 cannot be used for IEC60870-5-103 or modbus communication.
The fibre optic port is used for IEC60870-5-103 communications.
RS485
connection
terminal

RS485
connection
terminal
COM2

TB3

TB1

TB2

COM1

TB4

TB3

TB1

TB2

Rear view
(a) One port

Rear view
(b) Two RS485 ports
Figure 4.1.1 Location of RS485 Port

111

OPT1
TX
TB1

RX
TB3

TB2

Fibre Optic
(ST)

Rear view
(C) Fibre optic port

6 F 2 S 0 7 5 8

4.2

Operation of the User Interface


The user can access such functions as recording, measurement, relay setting and testing with the
LCD display and operation keys.

4.2.1

LCD and LED Displays


Displays during normal operation

When the GRD140 is operating normally, the green "IN SERVICE" LED is lit and the LCD is off.
Press the VIEW key when the LCD is off to display the digest screens which are "Indication",
"Metering1", "Metering2", "Metering3", "Metering4", "Metering5", "Latest fault",
"Auto-supervision" and "Alarm Display" screens in turn. "Latest fault", "Auto-supervision" and
"Alarm Display" screens are displayed only when there is some data. The following are the digest
screens and can be displayed without entering the menu screens.
Indication
I N D 1 [ 0 0 0 0
I N D 2 [ 0 0 0 1

0 0 0 0 ]
0 0 0 0 ]

Metering 1
I a

. k A

Not available for model 110 and APPL=1P


setting in models 400 and 420.

I b

. k A

Not available for model 110, and APPL=1P and 2P


settings in models 400 and 420.

I c

. k A

Not available for model 110 and APPL=1P


setting in models 400 and 420.

I e

. k A

Metering 2

Metering 3

Metering 4

Metering 5
I s e

. k A

Not available for models 400 and 430.

V a n

. k V
.

Available for APPL=3PN and 3PV settings in


models 400, 430 and 420.

V b n

. k V
.

Available for APPL=3PN and 3PV settings in


models 400, 430 and 420.

V c n

. k V
.

Available for APPL=3PN and 3PV settings in


models 400, 430 and 420.

V e

. k V
.

Metering 6

Metering 7

Metering 8

Metering 9

112

6 F 2 S 0 7 5 8
Metering 10
V 0

. k V
.

V 1

. k V
.

Not available for model 110.

V 2

. k V
.

Not available for model 110

Metering 11

Metering 12

Metering 13
. H z

ff

To clear the latched indications (LEDs, LCD screen of Latest fault), press RESET key for 3
seconds or more.
For any display, the back-light is automatically turned off after five minutes.
Indication

This screen shows the status of elements assigned as a virtual LED.


I N D 1 [ 0 0 0 0
I N D 2 [ 0 0 0 1

0 0 0 0 ]
0 0 0 0 ]

Status of element,
Elements depend on user setting. 1: Operate, 0: Not operate (Reset)
Displays in tripping

Latest fault
P h a s e
O C 1

A B C E

: Faulted phases. Not displayed for model 110


: Tripping element

If a fault occurs and a tripping command is output when the LCD is off, the red "TRIP" LED and
other configurable LED if signals assigned to trigger by tripping
Press the VIEW key to scroll the LCD screen to read the rest of messages.
Press the RESET key to turn off the LEDs and LCD display.
Notes:
1) When configurable LEDs (LED1 through LED3) are assigned to latch signals by trigger of
tripping, press the RESET key more than 3s until the LCD screens relight. Confirm turning off
the configurable LEDs. Refer to Table 4.2.1 Step 1.
2) Then, press the RESET key again on the "Latest fault" screen in short period, confirm turning
off the "TRIP" LED. Refer to Table 4.2.1 Step 2.
3) When only the "TRIP" LED is go off by pressing the RESET key in short period, press the

RESET key again to reset remained LEDs in the manner 1) on the "Latest fault" screen or other
digest screens. LED1 through LED3 will remain lit in case the assigned signals are still active
state.

113

6 F 2 S 0 7 5 8

Table 4.2.1 Turning off latch LED operation


LED lighting status
Operation
Step 1

"TRIP" LED

Press the RESET key more than 3s on


the "Latest fault" screen
continue to lit

Step 2

Configurable LED
(LED1 LED3)

turn off

Then, press the RESET key in short


period on the "Latest fault" screen
turn off

When any of the menu screens is displayed, the VIEW and RESET keys do not function.
To return from menu screen to the digest "Latest fault" screen, do the following:
Return to the top screen of the menu by repeatedly pressing the END key.
Press the END key to turn off the LCD.
Press the VIEW key to display the digest "Latest fault" screen.

Auto-supervision
E r r : R OM , A / D

If the automatic supervision function detects a failure while the LCD is off, the
"Auto-supervision" screen is displayed automatically, showing the location of the failure, and the
"ALARM" LED lights.
Press the VIEW key to display other digest screens in turn including the "Metering" and "Latest
fault" screens.
Press the RESET key to turn off the LEDs and LCD display. However, if the failure continues,
the "ALARM" LED remains lit.
After recovery from a failure, the "ALARM" LED and "Auto-supervision" display turn off
automatically.
If a failure is detected while any of the screens is displayed, the current screen remains displayed
and the "ALARM" LED lights.
Notes:
1) When configurable LEDs (LED1 through LED3) are assigned to latch signals by issuing an
alarm, press the RESET key more than 3s until all LEDs reset except "IN SERVICE" LED.
2) When configurable LED is still lit by pressing RESET key in short period, press RESET key
again to reset remained LED in the above manner.
3) LED1 through LED3 will remain lit in case the assigned signals are still active state.

While any of the menu screens is displayed, the VIEW and RESET keys do not function. To

114

6 F 2 S 0 7 5 8
return to the digest "Auto-supervision" screen, do the following:
Return to the top screen of the menu by repeatedly pressing the END key.
Press the END key to turn off the LCD.
Press the VIEW key to display the digest screen.
Alarm Display

Alarm Display (ALM1 to ALM4)



: A L M 1

The four alarm screens can be provided, and their text messages are defined by user. (For setting,
see Section 4.2.6.8) These alarms are raised by associated binary inputs.
Press the VIEW key to display other digest screens in turn including the "Metering" and "Latest
fault" screens.
To clear the Alarm Display, press RESET key. The clearing is available after displaying up to
ALM4.

4.2.2

Relay Menu
Figure 4.2.1 shows the menu hierarchy in the GRD140. The menu has five sub-menus, "Record",
"Status", "Set. (view)", "Set. (change)", and "Test". For details of the menu hierarchy, see
Appendix E.

115

6 F 2 S 0 7 5 8
Menu

Record

F. record
E. record
D. record
Counter

Status

Metering
Binary I/O
Relay element
Time sync.
Clock adjust.
LCD contrast

Set. (view)

Version
Description
Comms
Record
Status
Protection
Binary I/P
Binary O/P
LED

Set. (change)

Password
Description
Comms
Record
Status
Protection
Binary I/P
Binary O/P
LED

Test

Switch
Binary O/P

Figure 4.2.1 Relay Menu

116

6 F 2 S 0 7 5 8
Record

In the "Record" menu, the fault records event records, disturbance records and counts such as trip
count.
Status

The "Status" menu displays the power system quantities, binary input and output status, relay
measuring element status, signal source for time synchronisation (BI, RSM or IEC60870-5-103),
clock adjustment and LCD contrast.
Set. (view)

The "Set. (view)" menu displays the relay version, description, relay address and baud rate in
RSM or IEC60870-5-103 communication, the current settings of record, status, protection, binary
inputs, configurable binary outputs and configurable LEDs.
Set. (change)

The "Set. (change)" menu is used to change the settings of password, description, relay address
and baud rate in RSM, IEC60870-5-103 or Modbus communication, record, status, protection,
binary inputs, configurable binary outputs and configurable LEDs.
Since this is an important menu and is used to change settings related to relay tripping, it has
password security protection.
Test

The "Test" menu is used to set testing switches and to forcibly operate binary output relays.
When the LCD is off, press any key other than the VIEW and RESET keys to display the top
"MENU" screen and then proceed to the relay menus.

R
S
S
S
T

e
t
e
e
e

M
c
a
t
t
s

E N U
o r d
t u s
.
( v i e w )
.
( c h a n g e )
t

To display the "MENU" screen when the digest screen is displayed, press the RESET key to turn
off the LCD, then press any key other than the VIEW and RESET keys.
Press the END key when the top screen is displayed to turn off the LCD.
An example of the sub-menu screen is shown below. The top line shows the hierarchical layer.
The last item is not displayed for all the screens. " " or " " displayed on the far right shows that
lower or upper lines exist.
To move the cursor downward or upward for setting or for viewing other lines not displayed on the
and
keys.
window, use the
/ 5
T r i p
s w
S c h e m e
P r o t . e l e m e n t

To return to the higher screen or move from the right side screen to the left side screen in Appendix

117

6 F 2 S 0 7 5 8
E, press the END key.
The CANCEL key can also be used to return to the higher screen but it must be used carefully
because it may cancel entries made so far.
To move between screens of the same hierarchical depth, first return to the higher screen and then
move to the lower screen.

4.2.3

Displaying Records
The sub-menu of "Record" is used to display fault records, event records, disturbance records and
counts such as trip count, Iy count and reclose count.

4.2.3.1 Displaying Fault Records

To display fault records, do the following:


Open the top "MENU" screen by pressing any keys other than the VIEW and RESET keys.
Select "Record" to display the "Record" sub-menu.
/

1
F
E
D
C

.
.
.
o

R
r
r
r
u

e
e
e
e
n

c
c
c
c
t

o
o
o
o
e

r
r
r
r
r

d
d
d
d

Select "F. record" to display the "F. record" screen.


/ 2
F . r e c o r d
D i s p l a y
C l e a r

Select "Display" to display the dates and times of fault records stored in the relay from the top
in new-to-old sequence.
/ 3

F . r e c o r d

# 1

1
1
2
1
0
1
2
0

# 2
# 3
# 4

6
8
0
5
4
1
8
7

/
:
/
:
/
:
/
:

J
1
M
2
F
5
J
3

u
3
a
9
e
4
a
0

l
:
y
:
b
:
n
:

/
5
/
2
/
5
/
1

2
7
2
2
2
3
2
8

0
.
0
.
0
.
0
.

0
0
0
1
0
2
0
4

1
3
1
0
1
9
1
1

1
1
9
2

Move the cursor to the fault record line to be displayed using the
ENTER key to display the details of the fault record.

118

and

keys and press the

6 F 2 S 0 7 5 8
/
0
1
O
P

P
I

4
1
8
C
h

r
a

/
:
1
a

I b
I c
I e
I s e
I 1
I 2
I 2 /
V a n
V b n
V c n
V e
V a b
V b c
V c a
V 0
V 1
V 2
f
F a u
I a
I b
I c
I e
I s e
I 1
I 2

F . r e c o r d
# 1
J a n / 2 0 0 2
1 3 : 5 7 . 0 3 1
Trip element

s e
A
. k m
f a u l

I 1

l t
v

B
(
t

C

v
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
l u
.
.
.
.
.
.
.
.

.
.
.
.

Not available for model 110.

%
l
k

)
u e s
A

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.

Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.

H
s
k

Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

Not available for model 110.

A
A

Not available for models 400 and 430.

Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.

Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.
Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.

V
V

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110 and APPL=1P setting in models 400 and 420.

Not available for model 110 and APPL=1P and 2P settings in models 400 and 420.

Not available for model 110 and APPL=1P setting in models 400 and 420.

A
A

Not available for models 400 and 430.

Not available for model 110 and APPL=1P and 2P settings in models 400 and 420.

Not available for model 110 and APPL=1P and 2P settings in models 400 and 420.

119

6 F 2 S 0 7 5 8

I 2 / I 1
.
T H M

V a n
.

V b n
.

V c n
.

V e
.

V a b
.

V b c
.

V c a
.

V 0
.

V 1
.

V 2
.

f
.
0 1 / J a n / 2 0
1 8 : 1 3 : 5 8 .
A R C - S 1
0 1 / J a n / 2 0
1 8 : 1 3 : 5 9 .
O C 1
0 1 / J a n / 2 0
1 8 : 1 4 : 0 0 .
A R C - S 2
0 1 / J a n / 2 0
1 8 : 1 4 : 0 1 .
O C 1 , A R C - F

0
0

2
3

Not available for model 110 and APPL=1P and 2P settings in models 400 and 420.

%
k

Not available for model 110.

Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

V
V

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

Not available for model 110.

0 2
0 3 1
0 2
0 3 1
0 2
0 3 1
T

The lines which are not displayed in the window can be displayed by pressing the

and

keys.

To clear all the fault records, do the following:


Open the "Record" sub-menu.
Select "F. record" to display the "F. record" screen.
Select "Clear" to display the following confirmation screen.
C l e a r
E N D = Y

r e c o r d s ?
C A N C E L = N

Press the END (= Y) key to clear all the fault records stored in non-volatile memory.

If all fault records have been cleared, the "Latest fault" screen of the digest screens is not
displayed.
Note: When changing the units (kA/A) of primary side current with RSM100, press the "Units"
button which is indicated in the primary side screen.

120

6 F 2 S 0 7 5 8
4.2.3.2 Displaying Event Records

To display event records, do the following:


Open the top "MENU" screen by pressing any keys other than the VIEW and RESET keys.
Select "Record" to display the "Record" sub-menu.
Select "E. record" to display the "E. record" screen.
/ 2
E . r e c o r d
D
i
s p l a y

C l e a r

Select "Display" to display the events with date from the top in new-to-old sequence.
/ 3
2
O
2
O

1
C
1
C

E . r e c o r d
/
1
/
1

S
S
-

e p / 2 0 0 2
A
t r i p
e p / 2 0 0 2
A

The time is displayed by pressing the


/ 3
1
O
1
O

Press the

3
C
3
C

4
O
4
O

8 0
n
7 9
n

key.

E . r e c o r d
:
1
:
1

2
2
-

2 : 4 5 . 2 1 1
A
t r i p
O n
2 : 4 5 . 1 0 9
A
O n

key to return the screen with date.

The lines which are not displayed in the window can be displayed by pressing the

and

keys.

To clear all the event records, do the following:


Open the "Record" sub-menu.
Select "E. record" to display the "E. record" screen.
Select "Clear" to display the following confirmation screen.
C l e a r
E N D = Y

r e c o r d s ?
C A N C E L = N

Press the END (= Y) key to clear all the event records stored in non-volatile memory.
4.2.3.3 Displaying Disturbance Records

Details of disturbance records can be displayed on the PC screen only (*); the LCD displays only
the recorded date and time for all disturbances stored in the relay. They are displayed in the
following sequence.
(*) For the display on the PC screen, refer to RSM100 manual.
Open the top "MENU" screen by pressing any keys other than the VIEW and RESET keys.
Select "Record" to display the "Record" sub-menu.
Select "D. record" to display the "D. record" screen.

121

6 F 2 S 0 7 5 8
/ 2
D . r e c o r d
D i s p l a y
C l e a r

Select "Display" to display the date and time of the disturbance records from the top in
new-to-old sequence.
/ 3

D . r e c o r d

# 1

1
1
2
1
0
1
2
0

# 2
# 3
# 4

6
8
0
5
4
1
8
7

/
:
/
:
/
:
/
:

J
1
M
2
F
5
J
3

u
3
a
9
e
4
a
0

l
:
y
:
b
:
n
:

/
5
/
2
/
5
/
1

2
7
2
2
2
3
2
8

0
.
0
.
0
.
0
.

0
4
0
3
0
4
0
8

1
0
1
8
1
4
1
7

1
8
4
6

The lines which are not displayed in the window can be displayed by pressing the

and

keys.

To clear all the disturbance records, do the following:


Open the "Record" sub-menu.
Select "D. record" to display the "D. record" screen.
Select "Clear" to display the following confirmation screen.
C l e a r
E N D = Y

r e c o r d s ?
C A N C E L = N

Press the END (= Y) key to clear all the disturbance records stored in non-volatile memory.
4.2.3.4 Displaying Counter
Open the top "MENU" screen by pressing any keys other than the VIEW and RESET keys.
Select "Record" to display the "Record" sub-menu.
Select "Counter" to display the "Counter" screen.
/ 2
C o u n t e r
D i s p l a y
T r i p s
C l e a r
T r i p s
A
(*)
C l e a r
T r i p s
B
(*)
C l e a r
T r i p s
C
(*)
C l e a r
C l e a r
I ^ y A
C l e a r
I ^ y B
C l e a r
I ^ y C
A R C s
C l e a r
(*) Note: These settings are only available when single phase External Trip BI functions
are used. In this case, the main "Clear Trips" option is not available.

Select "Display" to display the counts stored in the relay.


/
T
T
T

3
C o u n t e r
r i p s

r i p s A

r i p s B

122

(*)
(*)

6 F 2 S 0 7 5 8
T r i p s C
(*)

I ^ y A
E 6
I ^ y B
E 6
I ^ y C
E 6
A R C s

Note (*): These settings are only available when single phase External Trip BI functions
are used. In this case, the main "Trips" option is not available.

The lines which are not displayed in the window can be displayed by pressing the

and

keys.

To clear each count, do the following:


Open the "Record" sub-menu.
Select "Counter" to display the "Counter" screen.
Select "Clear Trips" to display the following confirmation screen.
C l e a r
E N D = Y

T r i p s ?
C A N C E L = N

Select "Clear Trips A" to display the following confirmation screen.


C l e a r
E N D = Y

T r i p s
A ?
C A N C E L = N

Select "Clear Trips B" to display the following confirmation screen.


C l e a r
E N D = Y

T r i p s
B ?
C A N C E L = N

Select "Clear Trips C" to display the following confirmation screen.


C l e a r
E N D = Y

T r i p s
C ?
C A N C E L = N

Select "Clear I^yA" to display the following confirmation screen.


C l e a r
E N D = Y

I ^ y A ?
C A N C E L = N

Select "Clear I^yB" to display the following confirmation screen.


C l e a r
E N D = Y

I ^ y B ?
C A N C E L = N

Select "Clear I^yC" to display the following confirmation screen.


C l e a r
E N D = Y

I ^ y C ?
C A N C E L = N

Select "Clear ARCs" to display the following confirmation screen.


C l e a r
E N D = Y

A R C s ?
C A N C E L = N

Press the END (= Y) key to clear the count stored in non-volatile memory.

4.2.4

Displaying the Status


From the sub-menu of "Status", the following status condition can be displayed on the LCD:
Metering data of the protected line, apparatus, etc.

123

6 F 2 S 0 7 5 8
Status of binary inputs and outputs
Status of measuring elements output
Status of time synchronisation source
Status of clock adjustment
Status of LCD contrast
The data are updated every second.
4.2.4.1 Displaying Metering Data

To display metering data on the LCD, do the following:


Select "Status" on the top "MENU" screen to display the "Status" screen.
/

1
M
B
R
T
C
L

e
i
e
i
l
C

S
t
n
l
m
o
D

t
e
a
a
e
c

a t u s
r i n g
r y
I /
y
e l e
s y n
k
a d j
c o n t r

O
m
c
u
a

e n t
.
s t .
s t

Select "Metering" to display the "Metering" screen.


/

2
M e
C u r r
D e m a
D i r e

t
e
n
c

e r i n g
n t
d
t i o n

Select "Current" to display the current power system quantities on the "Metering" screen.
/ 3
I a
I b
I c
I e
I s e
I 1
I 2
I 2 /
T H M
V a n
V b n
V c n
V e
V a b

C u r r e

I 1

t
.

.
.
.

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.

Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.

k A

k A

Not available for models 400 and 430.


Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.
Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.
Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.

%
k V

k V

k V

k V

k V

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.
Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.
Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.
Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

Not available for model 110.

124

6 F 2 S 0 7 5 8

V b c
V c a
V 0
V 1
V 2
f
P F
P
Q
S
Wh +
Wh
v a h
v a h

.
. k V
Not available for model 110.
.
. k V
Not available for model 110.
.
. k V
Not available for model 110.
.
. k V
Not available for model 110.
.
. k V
Not available for model 110.
.
. H z
Not available for model 110.

Not available for model 110. Total 3 phase power factor.
k
W
-

Not available for model 110. Total 3 phase active power.
-
k v a r
Not available for model 110. Total 3 phase reactive power.
-
k V A
Not available for model 110. Total 3 phase apparent power.

Not available for model 110. Figure over times (999). (*)
k Wh

Not available for model 110. Figure over times (999). (*)
k Wh
+

Not available for model 110. Figure over times (999). (*)
k v a h

Not available for model 110. Figure over times (999). (*)
k v a h
Note: The unit depends on the setting value of Display-Wh.
(*) This value indicates the times counted over the 6 figures (999999). When the power energy
(kWh or kvah) exceeds 999999, this value is counted up.

If the primary side unit (A) is required, select 2(=Pri-A) on the "Metering" screen. See Section
4.2.6.6.
Note: When changing the units (kA/A) of primary side current with RSM100, press the "Units"
button which is indicated in the primary side screen.

Select "Demand" to display the current demand on the "Metering" screen.


/
I
I
I
I
I
I
I
P
Q
S
V
V
V
V
V
V
V
V
V
V
f

3
a
b
c
e
s
2
2
m
m
m
a
a
b
b
c
c
e
e
0
0
m

D
a
a
a
a
m
a
m
x
x
x
m
m
m
m
m
m
m
m
m a
m i
a x
m
m
m
m
e
m
1
a
a
a
n
n
n
n
n
n

e m
x
x
x
x
a x
x
a x
a x
i n
a x
i n
a x
i n
a x
i n
x
n

a n

.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.

k
k
k
k
k
k

A
A
A
A
A
A

Not available for model 110.


Not available for model 110.
Not available for model 110.
Not available for models 400 and 430.
Not available for model 110.
Not available for model 110.

k
k
k

W
v
V
k
k
k
k
k
k
k
k
k
k
H

Not available for model 110.

a
A
V
V
V
V
V
V
V
V
V
V
z

Not available for model 110.


Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.

Not available for model 110.

125

6 F 2 S 0 7 5 8
f m i n

. H z

Not available for model 110.

To clear all max data, do the following:


Press the RESET key on any max demand screen (primary or secondary) to display the
following confirmation screen.
C l e a r
E N D = Y

m a x ?
C A N C E L = N

Press the END (= Y) key to clear all max data stored in non-volatile memory.
Select "Direction" to display the direction of a current on the "Metering" screen.

The direction of each current is displayed when the directional characteristic is selected as
follows:
Ia, Ib, Ic: [OC-DIR]= "FWD" or "REV" setting
Ie: [EF-DIR]= "FWD" or "REV" setting
Ise: [SE-DIR]= "FWD" or "REV" setting
I2: [NC-DIR]= "FWD" or "REV" setting
/
I
I
I
I
I
I

3
D i r e c t i o n
a
F o r w a r
b
R e v e r s
c
F o r w a r
e
F o r w a r
s e
F o r w a r
2
_ _ _ _ _ _

d
e
d
d
d
_

Not available for model 110.


Not available for model 110.
Not available for model 110.
Not available for model 400 and 430.
Not available for model 110.

4.2.4.2 Displaying the Status of Binary Inputs and Outputs

To display the binary input and output status, do the following:


Select "Status" on the top "MENU" screen to display the "Status" screen.
Select "Binary I/O" to display the binary input and output status.
/ 2
I P
O P

B i n a r y
I / O
0 0 0 0 ]
[ 0 0 0 0
0 0 0 0 ]
[ 0 0 0 0

The display format is shown below.


[

Input (IP)

BI1

BI2

BI3

BI4

BI5

BI6

BI7

BI8

Output (OP)

BO1

BO2

BO3

BO4

BO5

BO6

BO7

FAIL

Line 1 shows the binary input status. BI1 to BI8 correspond to each binary input signal. The
models 400, 430 and 420 are available for BI1 to BI5. For the binary input signal, see Appendix H.
The status is expressed with logical level "1" or "0" at the photo-coupler output circuit.
Line 2 shows the binary output status. All binary outputs BO1 to BO7 are configurable. The status
of these outputs is expressed with logical level "1" or "0" at the input circuit of the output relay
driver. That is, the output relay is energised when the status is "1".
To display all the lines, press the

and

keys.

126

6 F 2 S 0 7 5 8
4.2.4.3 Displaying the Status of Measuring Elements

To display the status of measuring elements on the LCD, do the following:


Select "Status" on the top "MENU" screen to display the "Status" screen.
Select 3 "Ry element" to display the status of the relay elements.
/
A
B
C
E
S
N
A
B
C
T
B
C
C
A
B
C
A
B
C
Z
N
F

2
O
O
O
F 1
E 1
C
U
U
U
H M
C
B F
o l
O
O
O
U
U
U
O V
O V
R Q

R
C
C
C
C
C
C
A
d
V
V
V
V
V
V
1
1
1

y
e l e m
1 - 4 [ 0 0
1 - 4 [ 0 0
1 - 4 [ 0 0
4
[ 0 0
4
[ 0 0
[ 0 0
1 - 2 [ 0 0
1 - 2 [ 0 0
1 - 2 [ 0 0
[ 0 0
[ 0
B C
[ 0 0
L d [ 0 0
1 - 2 [ 0 0
1 - 2 [ 0 0
1 - 2 [ 0 0
1 - 2 [ 0 0
1 - 2 [ 0 0
1 - 2 [ 0 0
- 2
[ 0 0
- 2
[ 0 0
- 4
[ 0 0

e
0
0
0
0
0

n t
0
0
0
0
0

0
0 0

0 0

]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]

The displayed elements depend on relay model. (See Table 1.1.1 in Section 1.)
The operation status of phase and residual overcurrent elements are shown as below.
[

A OC1-4

OC1

OC2

OC3

OC4

A phase OC elements

B OC1-4

OC1

OC2

OC3

OC4

B phase OC elements

C OC1-4

OC1

OC2

OC3

OC4

C phase OC elements

EF1-4

EF1

EF2

EF3

EF4

SE1-4

SE1

SE2

SE3

SE4

NC

NC1

NC2

A UC1-2

UC1

UC2

A phase UC elements

B UC1-2

UC1

UC2

B phase UC elements

C UC1-2
THM
BC
CBFABC
Cold Ld
A OV1-2
B OV1-2
C OV1-2

UC1
Alarm
BC
A
0
OV1
OV1
OV1

UC2
Trip
B
1
OV2
OV2
OV2

C
2
-

3
-

C phase UC elements

127

Cold Load state


A phase OV elements
B phase OV elements
C phase OV elements

6 F 2 S 0 7 5 8
A UV1-2
B UV1-2
C UV1-2
ZOV1-2
NOV1-2
FRQ1-4

UV1 UV2
UV1 UV2
UV1 UV2
ZOV1 ZOV2
NOV1 NOV2
FRQ1 FRQ2 FRQ3

FRQ4

A phase UV elements
B phase UV elements
C phase UV elements

The status of each element is expressed with logical level "1" or "0". Status "1" means the element
is in operation.
4.2.4.4 Displaying the Status of the Time Synchronisation Source

The internal clock of the GRD140 can be synchronised with external clocks such as the binary
input signal clock (BI), RSM (relay setting and monitoring system) clock or IEC60870-5-103
(IEC) or Modbus (MOD). To display on the LCD whether these clocks are active (=Act.) or
inactive (=Inact.) and which clock the relay is synchronised with, do the following:
Select "Status" on the top "MENU" screen to display the "Status" screen.
Select "Time sync." to display the status of time synchronisation sources.
/ 2
B I
R S
I E
M O

T i m e
s y n
:
A c t .
M :
I n a c
C :
I n a c
D
I n a c

c .
t .
t .
t .

The asterisk on the far left shows that the internal clock is synchronised with the marked source
clock. If the marked source clock is inactive, the internal clock runs locally.
Note: If the Binary input signal has not been detected for one hour or more after the last detection, the
status becomes "inactive".

For details of the setting time synchronisation, see Section 4.2.6.6.


4.2.4.5 Clock Adjustment

To adjust the clock when the internal clock is running locally, do the following:
Select "Status" on the top "MENU" screen to display the "Status" screen.
Select "Clock adjust." to display the setting screen.
/ 2
M i
H o
D a
M o
Y e

1 2 / N o v / 2 0 0 1
2 2 : 5 6 : 1 9
[ L ]
n u t e
5 6
_
u r
2 2
y
1 2
n t h
1 1
a r
2 0 0 1

Clock runs with L=Local, B=BI, R=RSM, I=IEC, M=Modbus

Line 1 and 2 show the current date and time. The time can be adjusted only when the clock is
running locally. When [BI], [RSM], [IEC] or [MOD] is active, the adjustment is invalid.
Enter a numerical value for each item and press the ENTER key. For details to enter a

128

6 F 2 S 0 7 5 8
numerical value, see 4.2.6.1.
Press the END key to adjust the internal clock to the set hours without fractions and return to
the previous screen.

If a date which does not exist in the calendar is set and END is pressed, "**** Error ****" is
displayed on the top line and the adjustment is discarded. Return to the normal screen by pressing
the CANCEL key and adjust again.
4.2.4.6 LCD Contrast

To adjust the contrast of LCD screen, do the following:


Select "Status" on the top "MENU" screen to display the "Status" screen.
Select "LCD contrast" to display the setting screen.
/ 2

L C D

c o n t r a s t

Press the or key to adjust the contrast. The characters on the screen become thin by
pressing the key and deep by pressing the key.

4.2.5

Viewing the Settings


The sub-menu "Set. (view)" is used to view the settings made using the sub-menu "Set. (change)".
The following items are displayed:
Relay version
Description
Relay address and baud rate in the RSM (relay setting and monitoring system) or
IEC60870-5-103 or Modbus communication
Record setting
Status setting
Protection setting
Binary input setting
Binary output setting
LED setting
Enter an item on the LCD to display each item as described in the previous sections.

4.2.5.1 Relay Version

To view the relay version, do the following.


Press the "Set.(view)" on the main menu.
/

1
V
D
C
R
S
P
B

e
e
o
e
t
r
i

S
r
s
m
c
a
o
n

e
s
c
m
o
t
t
a

t
i
r
s
r
u
e
r

. ( v i e w )
o n
i p t i o n
d
s
c t i o n
y
I / P

129

6 F 2 S 0 7 5 8
B i n a r y
L E D

O / P

Press the "Version" on the "Set.(view)" menu.


/ 2
V e r s i o n
t y p e
R e l a y
N o .
S e r i a l
S o f t w a r e

Select "Relay type" to display the relay type form and model number.
G R D 1 4 0 - 1 1 0 A - 1 1
- 1 1

Select "Serial number" to display the relay manufacturing number.


Select "Software" to display the relay software type form and version.
G S 1 D P 1 - 0 4 -

4.2.5.2 Settings

The "Description", "Comms", "Record", "Status", "Protection", "Binary I/P", "Binary O/P" and
"LED" screens display the current settings input using the "Set. (change)" sub-menu.

4.2.6

Changing the Settings


The "Set. (change)" sub-menu is used to make or change settings for the following items:
Password
Description
Relay address and baud rate in the RSM, IEC60870-5-103 or Modbus communication
Recording setting
Status setting
Protection setting
Binary input setting
Binary output setting
LED setting
All of the above settings except the password can be seen using the "Set. (view)" sub-menu.

CAUTION
Care should be taken when modifying settings for "active group",
Modification of settings :
"scheme switch" and "protection element" in the "Protection" menu. Dependencies exist between
the settings in the various menus, with settings in one menu becoming active (or inactive)
depending on the selection made in another menu. Therefore, it is recommended that all necessary
settings changes be made while the circuit breaker tripping circuit is disconnected.
Alternatively, if it is necessary to make settings changes with the tripping circuit active, then it is
recommended to enter the new settings into a different settings group, and then change the "active
group" setting, thus ensuring that all new settings become valid simultaneously.

130

6 F 2 S 0 7 5 8
4.2.6.1 Setting Method

There are three setting methods as follows:


- To enter a selected item
- To enter a text string
- To enter numerical values
To enter a selected item

If a screen as shown below is displayed, perform setting as follows.


The cursor can be moved to upper or lower lines within the screen by pressing the
If setting (change) is not required, skip the line with the
and
keys.
/

1
P
D
C
R
S
P
B
B
L

a
e
o
e
t
r
i
i
E

S
s
s
m
c
a
o
n
n
D

e
s
c
m
o
t
t
a
a

t
w
r
s
r
u
e
r
r

and

keys.

. ( c h a n g e)
o r d
i p t i o n
d
s
c t i o n
y
I / P
y
O / P

Move the cursor to a setting item.


Press the ENTER key.
To enter a text string

Texts strings are entered under "Plant name" or "Description" screen.


/ 2
D e s c r i p t i o n
n a m e
P l a n t
D e s c r i p t i o n

To select a character, use keys , , and to move blinking cursor down, up, left and right.
"" and "" on each of lines 4, 8 and 10 indicate a space and backspace, respectively. A
maximum of 22 characters can be entered.
_
A
H
O
V
a
h
o
v
0
7
(
}
>

B
I
P
W
b
i
p
w
1
8
)

!
:

C
J
Q
X
c
j
q
x
2
9
[
/

D
K
R
Y
d
k
r
y
3
]
+
#
,

E
L
S
Z
e
l
s
z
4

F G
M N
T U

f g
m n
t u

5 6

@_ {
< =
$ %&
. `

Set the cursor position in the bracket by selecting "" or "" and pressing the ENTER key.

131

6 F 2 S 0 7 5 8
Move the blinking cursor to a selecting character.
Press the ENTER key to enter the blinking character at the cursor position in the brackets.
Press the END key to confirm the entry and return to the upper screen.

To correct the entered character, do either of the following:


Discard the character by selecting "" and pressing the ENTER key and enter the new
character.
Discard the whole entry by pressing the CANCEL key and restart the entry from the first.
To enter numerical values

When the screen shown below is displayed, perform setting as follows:


The number to the left of the cursor shows the current setting or default setting set at shipment. The
cursor can be moved to upper or lower lines within the screen by pressing the
and
keys. If
setting (change) is not required, skip the line with the
and
keys.
/ 4

T i m e / s t a r t e r

T i m
2
O C
2
E F
0
S E F
0
N C
0
O V
1 2
U V
6
Z O V
2
N O V
2

e
. 0

s
_
A

. 0 0
A
. 6 0
A
. 2 0 0
A
. 4 0
V
0 . 0
V
0 . 0
V
0 . 0
V
0 . 0

Move the cursor to a setting line.


Press the
key.

or

key to set a desired value. The value is up or down by pressing the

or

Press the ENTER key to enter the value.


After completing the setting on the screen, press the END key to return to the upper screen.

To correct the entered numerical value, do the following.


If it is before pressing the ENTER key, press the CANCEL key and enter the new
numerical value.
If it is after pressing the ENTER key, move the cursor to the correcting line by pressing the
and
keys and enter the new numerical value.
Note: If the CANCEL key is pressed after any entry is confirmed by pressing the ENTER key, all

132

6 F 2 S 0 7 5 8
the entries made so far on the screen concerned are canceled and screen returns to the upper
one.

To complete the setting

Enter after making entries on each setting screen by pressing the ENTER key, the new settings
are not yet used for operation, though stored in the memory. To validate the new settings, take the
following steps.
Press the END key to return to the upper screen. Repeat this until the confirmation screen
shown below is displayed. The confirmation screen is displayed just before returning to the
"Set. (change)" sub-menu.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

When the screen is displayed, press the ENTER key to start operation using the new settings,

or press the CANCEL key to correct or cancel entries. In the latter case, the screen turns back
to the setting screen to enable re-entries. Press the CANCEL key to cancel entries made so far
and to turn to the "Set. (change)" sub-menu.
4.2.6.2

Password

For the sake of security of setting changes, password protection can be set as follows:
Select "Set. (change)" on the main "MENU" screen to display the "Setting change" screen.
Select "Password" to display the "Password" screen.
Enter a 4-digit number within the brackets after "Input" and press the ENTER key.
I n p u t
[ _
1 2 3 4 5 6 7 8 9 0

For confirmation, enter the same 4-digit number in the brackets after "Retype".
R e t y p e
[ _
1 2 3 4 5 6 7 8 9 0

Press the END key to display the confirmation screen. If the retyped number is different from
that first entered, the following message is displayed on the bottom of the "Password" screen
before returning to the upper screen.

"Unmatch passwd!"
Re-entry is then requested.
Password trap

After the password has been set, the password must be entered in order to enter the setting change
screens.
If "Set. (change)" is entered on the top "MENU" screen, the password trap screen "Password" is
displayed. If the password is not entered correctly, it is not possible to move to the "Setting
(change)" sub-menu screens.
P a s s w o r d
[ _
1 2 3 4 5 6 7 8 9 0

133

6 F 2 S 0 7 5 8
Canceling or changing the password

To cancel the password protection, enter "0000" in the two brackets on the "Password" screen. The
"Set. (change)" screen is then displayed without having to enter a password.
The password can be changed by entering a new 4-digit number on the "Password" screen in the
same way as the first password setting.
If you forget the password

Press CANCEL and RESET keys together for one second on the top "MENU" screen. The
screen goes off, and the password protection of the GRD140 is canceled. Set the password again.
4.2.6.3 Plant Name

To enter the plant name and other data, do the following. These data are attached to records.
Select "Set. (change)" on the main "MENU" screen to display the " Set. (change)" screen.
Select "Description" to display the "Description" screen.
/ 2
D e s c r i p t i o n
n a m e
P l a n t
D e s c r i p t i o n

To enter the plant name, select "Plant name" on the "Description" screen.
To enter special items, select "Description" on the "Description" screen.
_
A
H
O
V
a
h
o
v
0
7
(
}
>

B
I
P
W
b
i
p
w
1
8
)

!
:

C
J
Q
X
c
j
q
x
2
9
[
/

D
K
R
Y
d
k
r
y
3
]
+
#
,

E
L
S
Z
e
l
s
z
4

F G
M N
T U

f g
m n
t u

5 6

@_ {
< =
$ %&
. `

Enter the text string.


4.2.6.4 Communication

If the relay is linked with RSM (relay setting and monitoring system) or IEC60870-5-103
communication, the relay address must be set. Do this as follows:
Select "Set. (change)" on the main "MENU" screen to display the "Set. (change)" screen.
Select "Comms" to display the "Comms" screen.
/ 2
C o m m s
.
A d d r . / P a r a m .
S w i t c h

Select "Addr./Param." on the "Comms" screen to enter the relay address number.

134

6 F 2 S 0 7 5 8
/ 3

A d d r . / P a r a m

H D L C
1

2
M O D B U S
1
I E C B 1
0
:
:
I E C B 4
0
I E C G T
1
I E C A T
1
I E C B T
1
I E C C T
1
I E C E 1
0
:
:
I E C E 8
0
I E C I 1
0
:
:
I E C I 8
0

I E C
_
1

4
1
1
1
1
0

0
0

Enter the relay address number on "HDLC" line for RSM or "IEC" line for IEC60870-5-103 or
"MODBUS" line for Modbus and press the ENTER key.

CAUTION

Do not overlap the relay address number.

Settings for IEC60870-5-103 communication


The lines "IECB1" to "IECB4" are used for auxiliary inputs of IEC103 events INF27 to INF30
in Appendix M. Assign signals to the columns "IECB1" to "IECB4" by entering the number
corresponding to each signal referring to Appendix C.
The lines "IECGT" to "IECCT" are used for fault indications of IEC103 events INF68 to
INF71 in Appendix M. Assign signals to the columns "IECGT" to "IECCT" by entering the BO
numbers (1 to 7) corresponding to the binary output settings.
The lines "IECE1" to "IECE8" are used to assign the signals for user customization. Assign
signals to the columns "IECE1" to "IECE8" by entering the number corresponding to each
signal referring to Appendix C.
Note: Assign "0" to the column when this function is not used.

The lines "IECI1" to "IECI8" are used to assign the above signals of "IECE1" to "IECE8" to
each INF number. Enter the INF number to the columns "IECI1" to "IECI8".
Select "Switch" on the "Comms" screen to select the protocol and transmission speed (baud

135

6 F 2 S 0 7 5 8
rate), etc., of the RSM, IEC60870-5-103 and Modbus.
/ 3

S w i t c h

P
H
2
9
I
9
M
9
I
N
I
1
I
1
I
1
I
1
I
P
I
N

t
C
C
/
B
/
B
/
B
m
N
/
N
/
N
/
N
/
F
m
G
Y

r
D
3
.
E
.
O
.
E
o
E
.
E
.
E
.
E
.
E
r
E
o

o
L
2
6
C
6
D
6
C
r
C
2
C
2
C
2
C
2
C
i
C
/
:
:
I E C
N o /

o c o l
0
_
/ I E C / M O D
0
1 9 . 2 / 5 7 . 6
R
1
1 9 . 2
R
1 9 . 2
L K
0
a l / B l o c k e d
F I
0
2 . 4
F V
0
2 . 4
F P
1
2 . 4
F f
0
2 . 4
L
0
/ S e c o n d / k m
I 1
0
e s

G I 8
Y e s

Select the number and press the ENTER key.


<Protocol>

This setting is for changing the protocol (HDLC, IEC or MOD) of the channel 1 (COM1 port). In
the model with two channels (COM1 and COM2 ports), this setting for COM1 should be
HDLC.
When the remote RSM system applied, select 0(=HDLC). When the IEC60870-5-103 applied,
select 1(=IEC103). When the Modbus applied, select 2(=Modbus).

CAUTION

When changing the setting to the HDLC during the IEC103 operation, the
IEC103 command INF18 in Appendix M is canceled. The output of IEC103
command INF18 can be observed by assigning their signal numbers to LEDs or
binary output relays (see Sections 4.2.6.9 and 4.2.6.10).
Do not change the <Protocol> setting via Modbus communication.

<232C>

This line is to select the RS-232C baud rate when the RSM system applied.
Note: The default setting of the 232C is 9.6kbps. The 57.6kbps setting, if possible, is recommended to
serve user for comfortable operation. The setting of RSM100 is also set to the same baud rate.

<IECBR>

This line is to select the baud rate when the IEC60870-5-103 system applied.

136

6 F 2 S 0 7 5 8
<MODBR>

This line is to select the baud rate when the Modbus applied.
<IECBLK>

Enter 1(=Blocked) to block the monitor direction in the IEC60870-5-103 communication.


<IECNFI , IECNFV, IECNFP, IECNFf>

These lines are to select the normalized factor (1.2 or 2.4) of the current measurand.
IECNFI:

Current

IECNFV:

Voltage

IECNFP:

Active power, Reactive power

IECNFf:

Frequency

<IECFL >

This line is to select the measurement result of the fault locator which is expressed as the primary
side value or the secondary side value of power system impedance, or the distance (km).
<IECGI1 - 8 >

These lines are to use the GI (General Interrogation) or not for user customized signals. If use the
GI, enter 1(=Yes).
4.2.6.5 Setting the Recording

To set the recording function as described in Section 4.2.3, do the following:


Select "Set. (change)" on the main "MENU" screen to display the "Set. (change)" screen.
Select "Record" to display the "Record " screen.
/

2
F
E
D
C

.
.
.
o

R
r
r
r
u

e
e
e
e
n

c
c
c
c
t

o
o
o
o
e

r
r
r
r
r

d
d
d
d

Setting the fault recording


Select "F. record" to display the "F. record" screen.
/ 3

F . r e c o r d

F a u l t
L o c .
O f f / O n

Enter 1 to enable the fault locator. If to disable the fault locator, enter 0.
Setting the event recording
Select "E. record" to display the "E. record" screen.
/ 3

E . r e c o r d

B I 1
c o m m .
N / O / R / B
B I 2
c o m m .

137

3
3

6 F 2 S 0 7 5 8
N
B
N
B
N
B
N

/
I
/
I
/
I
/

O
3
O
4
O
5
O

/ R
c
/ R
c
/ R
c
/ R

/
o
/
o
/
o
/

B
m m .
B
m m .
B
m m .
B

3
3
3

Enter 0(=None) or 1(=Operate) or 2(=Reset) or 3(=Both) for BI command trigger setting and
press the ENTER key.
Setting the disturbance recording
Select "D. record" to display the "D. record" screen.
/

3
D .
T i m e
S c h e
B i n a

r
/
m
r

e c o r d
s t a r t e r
e
s w
y
s i g .

Select "Time/starter" to display the "Time/starter" screen.


/ 4

T i m e / s t a r t e r

T i m
2
O C
2
E F
0
S E F
0
N C
0
O V
1 2
U V
6
Z O V
2
N O V
2

e
. 0

s
_
A

. 0 0
A
. 6 0
A
. 2 0 0
A
. 4 0
V
0 . 0
V
0 . 0
V
0 . 0
V
0 . 0

Enter the recording time and starter element settings.

To set each starter to use or not to use, do the following:


Select "Scheme sw" on the "D. record" screen to display the "Scheme sw" screen.
/ 4
T
O
B
O
O
O
E
O
S

r
f
I
f
C
f
F
f
E

S c h e m e

s w

i p
f / O n

1
1

f / O n
1
f / O n
1
f / O n
F

138

6 F 2 S 0 7 5 8
O
N
O
O
O
U
O
Z
O
N
O

f
C
f
V
f
V
f
O
f
O
f

f / O n
1
f / O n
1
f / O n
1
f / O n
V
f / O n
V
f / O n

1
1

Enter 1 to use as a starter. If not to be used as a starter, enter 0.

To set each signal number to record binary signals, do the following:


Select "Binary sig." on the "D. record" screen to display the "Binary sig." screen.
/ 4

B i n a r y

S I G 1
1 0 1
S I G 2
1 0 2

s i g .

S I G 3 2
1 3 3

Enter the signal number to record binary signals in Appendix C.


Setting the counter
Select "Counter" to display the "Counter" screen.
/ 3
C o u n t e r
s w
S c h e m e
A l a r m s e t

To set each counter to use or not to use, do the following:


Select "Scheme sw" on the "Counter" screen to display the "Scheme sw" screen.
/ 4
T
O
C
O
T
O

O
O
O

C
f
B
f
C
f
I
f
P
f

S c h e m e
S
f
S
f
A
f
y
f
T
f

P
/
M
/
E
/
A
/
A
/

E
O
E
O
N
O
E
O
E
O

s w

N
0
_
n / O p t - O n
N
0
n
0
n
N
0
n
N
0
n

Enter 1 to use as a counter. If not to be used as a counter, enter 0.

To set threshold setting, do the following:


Select "Alarm set" on the "Counter" screen to display the "Alarm set" screen.
/ 4

A l a r m

s e t

139

6 F 2 S 0 7 5 8
T C
1
I
1
Y V

A
0
y
0
A

L
0
A
0
L
2
O P T A
1 0

M
0
L
0
U
.
L
0

0
M
0
E
0
M
0

_
E 6

m s

Enter the threshold settings.


4.2.6.6 Status

To set the status display described in Section 4.2.4, do the following:


Select "Status" on the "Set. (change)" sub-menu to display the "Status" screen.
/ 2
S t a t u s
M e t e r i n g
s y n c .
T i m e

Setting the metering


Select "Metering" to display the "Metering" screen.
/ 3
M e t e r i n g
s w
S c h e me
V a l u e

Not available for model 110.

Select "Scheme sw" to display the "Scheme sw" screen.


/ 4
D
P
D
k
P
S
C
L

i
r
i
W
o
e
u
a

S c h e m e
s
i
s
h
w
n
r
g

p
/
p
/
e
d
r
/

l
S
l
M
r
/
e
L

s w

a
e
a
W

y
1
_
c / P r i - A
y - Wh
0
h
0
R e c e i v e
n t
0
e a d

Enter 0 or 1 or 2 for Display.

Enter 0(=Pri) to display the primary side current in kilo-amperes(kA).


Enter 1(=Sec) to display the secondary side current.
Enter 2(=Pri-A) to display the primary side current in amperes(A).
Enter 0(=kWh) or 1(=MWh) for Display-Wh.
Enter 0(=Send) or 1(=Receive) for Power, and 0(=Lag) or 1(=Lead) for Current, and press the
ENTER key.
Note: Power and Current setting

140

6 F 2 S 0 7 5 8
Active Power Display
Power setting=1(Send)

Power setting=2(Receive)

V
I

Reactive Power Display


Current setting=1(Lag)

Current setting=2(Lead)

V
I

Select "Value" to display the "Value" screen for compensating or modifying the value for
Wh+, Wh, vah+ and vah.
Enter the value for Wh+, Wh, vah+ and vah.
Note: Number of figure less than the unit (kWh or MWh) is rounded down.
(Example) If actual power energy is 123,456kW and the unit is MW, the displayed value is
123MW.
If the value 78 is input to compensate the power energy value, the displayed value is
78MW. The actual power energy is 78, 000kW but it is not 78,456kW.
/ 4

V a l u e

Wh +

k Wh

C o u n t - Wh +


Wh
k Wh

C o u n t - Wh


v a h +
k v a h

C o u n t - v a h +


v a h
k v a h

C o u n t - v a h


Note: The unit depends on the setting value of Display-Wh.

CAUTION: Caution: If sending to a relay by Send all on RSM100 to change a certain setting

value, a power energy value (Wh+, Wh, Vah+, Vah) may change into a value
different from a current value.
Particularly, take notice in case a setting value is loaded from a file and is sent
to a relay.
If the power energy values continue on the values before a setting change, in case of the
setting change in operation, the values before the setting change should be memorized
and the power energy values should be changed by the compensation function of power
energy values after the setting change.

141

6 F 2 S 0 7 5 8
Enter the value for Count-Wh+, -Wh, -vah+ and -vah to the times counted over the 6 figures
(999999) and press the ENTER key.
Setting the time synchronisation

The calendar clock can run locally or be synchronised with the binary input signal, RSM clock, or
by an IEC60870-5-103 or Modbus. This is selected by setting as follows.
Select "Time sync." to display the "Time sync" screen.
/ 3

T i m e

s y n c .

T i m e
s y n c .
0
_
O f / B I / R S M / I E C / M

Enter 0, 1, 2, 3 or 4 and press the ENTER key.

Enter 0(=of) not to be synchronised with any external signals.


Enter 1(=BI) to be synchronised with the binary input signal.
Enter 2(=RSM) to be synchronised with the RSM clock.
Enter 3(=IEC) to be synchronised with IEC60870-5-103.
Enter 4(=M) to be synchronised with Modbus.
Note: When selecting BI, RSM, IEC or Modbus, check that they are active on the "Status" screen in
"Status" sub-menu.
If BI is selected, the BI command trigger setting should be None because event records will
become full soon. (See Section 4.2.6.5.)
If it is set to an inactive BI, RSM, IEC or Modbus, the calendar clock runs locally.

4.2.6.7 Protection

The GRD140 can have 4 setting groups for protection in order to accommodate changes in the
operation of the power system, one setting group is assigned active. To set the protection, do the
following:
Select "Protection" on the "Set. (change)" screen to display the "Protection" screen.
/

2
P r o t e
C h a n g e
C h a n g e
C o p y
g p

c t i o n
a c t . g p .
s e t .
.

Changing the active group


Select "Change act. gp." to display the "Change act. gp." screen.
/ 3

C h a n g e
a c t .
g p .
A c t i v e
g p .
1
_

Enter the group number and press the ENTER key.


Changing the settings

Almost all the setting items have default values that are set when the product is shipped. For the
default values, see Appendix H. To change the settings, do the following:
Select "Change set." to display the "Act gp.= *" screen.

142

6 F 2 S 0 7 5 8
/

3
C
G
G
G
G

o
r
r
r
r

A
m
o
o
o
o

c
m
u
u
u
u

t
o
p
p
p
p

g p . =
n
1
2
3
4

Changing the Common settings


Select "Common" to set the current and voltage input state and input imbalance monitoring for
GRD140-400, 430 and -420 and press the ENTER key.
/ 4

C o m m o n

A P P L C T
1
_
O f f / 3 P / 2 P / 1 P
A P P L V T
1
O f f / 3 P N / 3 P V / 2 P P
O p t i m e
0
N o r m a l / F a s t
C T F E N
0
O f f / O n / O P T - O n
V T F 1 E N
0
O f f / O n / O P T - O n
V T F 2 E N
0
O f f / O n / O P T - O n
C T S V E N
2
O f f / A L M & B L K / A L M
V 0 S V E N
2
O f f / A L M & B L K / A L M
V 2 S V E N
2
O f f / A L M & B L K / A L M
A O L E D
1
O f f / O n
Note: In Model 430, [APPL-CT]=3P is fixed.

<APPLCT>
Enter 0(=Off: not used), 1(=3P: 3 phase), 2(=2P: 2 phase) or 3(=1P: 1 pole) to set the current
input state and press the ENTER key.
<APPLVT>
Enter 0(=Off: not used), 1(=3PN: three phase-to-neutral voltage input), 2(=3PV: three
phase-to-neutral voltage and zero sequence voltage input) or 3(=2PP: two phase voltage input)
and press the ENTER key.

CAUTION: Do not change the APPL setting under service condition of the relay.
<Optime>
Enter 0(=Normal : Transient free operation), 1(=Fast : High speed operation) to set the
operating time and press the ENTER key.
Note: If Fast selected, all OC and EF elements operate at high-speed ( approximately 20ms).

<CTFEN, VTF1EN, VTF2EN>

To set CT failure function and VT failure function enable, do the following.

143

6 F 2 S 0 7 5 8
Enter 0(=Off) or 1(=On) or 2(=OPT-On) by pressing the
key.

or

key and press the ENTER

< CTSVEN, V0SVEN, V2SVEN>

To set AC input imbalance supervision enable, do the following.


Enter 0(=Off) or 1(=ALM&BLK) or 2(=ALM) by pressing the
ENTER key.

or

key and press the

<AOLED>

This switch is used to control the TRIP LED lighting when an alarm element outputs.
Enter 1 (=On) to light the TRIP LED when an alarm element outputs, and press the
ENTER key. If not, enter 0 (=Off) and press the ENTER key.
Changing the Group settings
Select the "Group" on the "Act gp.= *" screen to change the settings and press the ENTER
key.
/

4
G r o u p
P a r a m e t e r
T r i p
A R C

Setting the parameter

Enter the line name, the CT/VT ratio and the fault locator as follows:
Select "Parameter" on the "Group " screen to display the "Parameter" screen.
/

5
P a r a m e
L i n e
n a m
C T / V T
r a
F a u l t L o c

t e r
e
t i o
a t o r

Select "Line name" to display the "Line name" screen.


Enter the line name as a text string and press the EN D key.
Select "CT/VT ratio" to display the "CT/VT ratio" screen.
/ 6

C T / V T

O C C
4
E F C
4
S E F
4
P V T
1
R V T
1

T
0
T
0
C
0

r a t i o

0
T
0

0 0
0 0

Note: The "CT ratio" screen depends on the APPL setting.


In Model 420, the settings of OCCT and EFCT are set to the same value.

Enter the CT/VT ratio and press the ENTER key.

144

6 F 2 S 0 7 5 8
CAUTION: If the CT/VT ratio is changed, power energy values (Wh+, Wh, Vah+, Vah,

Count-) on the "Metering" screen will be also changed because the power energy
values are calculated from the CT/VT ratio. If the power energy values continue on
the values before the CT/VT change, in case of the CT/VT change in operation, the
values before the CT/VT change should be memorized and the power energy values
should be changed by the compensation function of power energy values after
changing the CT/VT. (See section 4.2.6.6.)

Select "Fault Locator" to display the "Fault Locator" screen.


/ 6
X 1

F a u l t
1 0 . 0

L o c .
O H M

X 0

O H M
3 4 . 0

R 1

O H M
1 . 0

R 0

O H M
3 . 5

K a b

%
1 0 0

K b c

%
1 0 0

K c a

%
1 0 0

K a

%
1 0 0

K b

%
1 0 0

K c

1 0 0
L I N E
5 0 . 0

k m

Enter the setting value and press the ENTER key.


Setting the trip function

To set the scheme switches and protection elements, do the following.


Select "Trip" on the "Group " screen to display the "Trip" screen.
/ 5
T r i p
s w
S c h e m e
e l e m e n t
P r o t .

Setting the scheme switch


Select "Scheme sw" on the "Trip" screen to display the "Scheme sw" screen.
/

6
A
O
E
S
N
M
C
O
U

p
C
F
E
O
i
o
V
V

S c h e m e
s w
p l i c a t i o n

F
C
s c
l d

L o a d

145

6 F 2 S 0 7 5 8
Z O V
N O V
F R Q

Setting the application

To set the application setting, do the following.


Select "Application" on the " Scheme sw" screen to display the "Application" screen.
/ 7
M
D
M
D
M
D

O
/
E
/
S
/

A p p l i c a t i o n
C
I
F
I
E
I

1
1
_
E C / I E E E / U S / C
1
1
E C / I E E E / U S / C
1
1
E C / I E E E / U S / C

<MOC1>, <MEF1>, <MSE1>

To set the OC1, EF1 and SEF1 time delay characteristic type, do the following.
Enter 0(=D: DT) or 1(=IEC) or 2(=IEEE) or 3(=US) or 4(=C: CON) and press the ENTER
key.
Setting the OC protection

The settings for the OC protection are as follows:


Select "OC" on the "Scheme sw" screen to display the "OC" screen.
/ 7
O
O
O
F
M
N
M
M
M
C
O
D
V
O
O
O
O
F
V
O
O
O
O
F
V
O
O

C
f
C
W
O
I
O
I
O
O
C
E
T
f
C
f
C
W
T
f
C
f
C
W
T
f
C

O C
1
f
1
D
C
/
C
/
C
2
1
F
F
f
2
f
2
D
F
f
3
f
3
D
F
f
4

E
/
/
1
V
1
V
1
/
R
/
/
E
/
/
/
E
/
/
/
E

N
O
D
R
C
I
C
I
C
C

1
n
I
E
/
/
O

R
V
I
E
I
E
U
8

/
E
I
E
I
S

0
N O N
C
0
/ L T I
E E
0

This setting is displayed if [MOC1] is 1(=IEC).

This setting is displayed if [MOC1] is 3(=US).

0
D
O
O
N
O
D
R
O
O
N
O
D
R
O
O
N

E P
C 1 B L K
n

0
n
I R
0
E V / N O N
C 2 B L K
0
n
0
n
I R
0
E V / N O N
C 3 B L K
0
n
0

146

This setting is displayed if [MOC1] is 2(=IEEE).

6 F 2 S 0 7 5 8
O
O
F
V
O
O
3

f
C
W
T
f
C
P

f
4
D
F
f
T
O

/
/
/
P
R

O
D
R
O
O

n
I R
0
E V / N O N
C 4 B L K
0
n
0
/ 2 O U T O F 3

<OCEN>
Enter 1(=On) to enable the OC and press the ENTER key. If disabling the OC, enter

0(=Off) and press the ENTER key.


<OC-DIR>

To set the OC directional characteristic, do the following.


Enter 0(=FWD) or 1(=REV) or 2(=NON) and press the ENTER key.
<MOC1C>

To set the OC1 Inverse Curve Type, do the following.


If [MOC1] is 1(=IEC), enter 0(=NI) or 1(=VI) or 2(=EI) or 3(=LTI) and press the ENTER
key.
If [MOC1] is 2(=IEEE), enter 0(=MI) or 1(=VI) or 2(=EI) and press the ENTER key.
If [MOC1] is 3(=US), enter 0(=CO2) or 1(=CO8) and press the ENTER key.
<OC1R>

To set the Reset Characteristic, do the following.


If [MOC1] is 2(=IEEE) or 3(=US), enter 0(=DEF) or 1(=DEP) and press the ENTER key.
<VTF-OCBLK>

To set the VTF block enable of OC, do the following.


Enter 1(=On) to enable "Trip block" by the VTF function and press the ENTER key. If

disabling it, enter 0(=Off) and press the ENTER key.


<OCTP>

To set the trip mode, do the following.


Enter 0(=3POR) or 1(=2OUTOF3) and press the ENTER key. If the 2OUTOF3 selected,
the trip signal is not issued when only one phase element operates.
After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Scheme sw" screen.

147

6 F 2 S 0 7 5 8
Setting the EF protection

The settings for the EF protection are as follows:


Select the "EF" on the "Scheme sw" screen to display the "EF" screen.
/ 7
E
O
E
F
M
N
M
M
M
C
E
D
C
O
V
O
E
O
E
F
C
O
V
O
E
O
E
F
C
O
V
O
E
O
E
F
C
O
V
O
C
O

F
f
F
W
E
I
E
I
E
O
F
E
T
f
T
f
F
f
F
W
T
f
T
f
F
f
F
W
T
f
T
f
F
f
F
W
T
f
T
f
U
f

E F
1
f
1
D
F
/
F
/
F
2
1
F
F
f
F
f
2
f
2
D
F
f
F
f
3
f
3
D
F
f
F
f
4
f
4
D
F
f
F
f
R
f

E
/
/
1
V
1
V
1
/
R
/
/
/
E
/
/
/
/
E
/
/
/
/
E
/
/
/
/
R
/

N
O
D
R
C
I
C
I
C
C

1
n
I
E
/
/
O

/
R
V
I
E
I
E
U
8

P O P
/
E
I
E
I
S

0
N O N
C
0
/ L T I
E E
0

This setting is displayed if [MEF1] is 1(=IEC).

This setting is displayed if [MEF1] is 3(=US).

This setting is displayed if [MEF1] is 2(=IEEE).

0
D
E
O
E
O
N
O
D
R
E
O
E
O
N
O
D
R
E
O
E
O
N
O
D
R
E
O
E
O
E
1

E P
F 1 B L K
n
F 1 B L K
n
n
I
E
F
n
F
n
n
I
E
F
n
F
n

0
0

0
/ P O P
R
0
V / N O N
2 B L K
0
2 B L K

0
/ P O P
R
0
V / N O N
3 B L K
0
3 B L K

0
0

n
I
E
F
n
F
n
V
/

R
0
V / N O N
4 B L K
0
4 B L K

0
0

2 / 3 / 4

<EFEN>
Enter 1(=On) to use an earth fault protection or enter 2(=POP) to use the directional earth fault
command protection (POP scheme), and press the ENTER key. If disabling the EF, enter

0(=Off) and press the ENTER key.

148

6 F 2 S 0 7 5 8
<EF-DIR>

To set the EF directional characteristic, do the following.


Enter 0(=FWD) or 1(=REV) or 2(=NON) and press the ENTER key.
<MEF1C>

To set the EF1 Inverse Curve Type, do the following.


If [MEF1] is 1(=IEC), enter 0(=NI) or 1(=VI) or 2(=EI) or 3(=LTI) and press the ENTER
key.
If [MEF1] is 2(=IEEE), enter 0(=MI) or 1(=VI) or 2(=EI) and press the ENTER key.
If [MEF1] is 3(=US), enter 0(=CO2) or 1(=CO8) and press the ENTER key.
<EF1R>

To set the Reset Characteristic, do the following.


If [MEF1] is 2(=IEEE) or 3(=US), enter 0(=DEF) or 1(=DEP) and press the ENTER key.
<CTF-EFBLK>, <VTF-EFBLK>

To set the CTF block and VTF block enable of EF, do the following.
Enter 1(=On) to enable "Trip block" by the CTF function and VTF function, and press the
ENTER key. If disabling them, enter 0(=Off) and press the ENTER key.
<CURREV>

To set which stage is used for current reverse detection in the command protection, do the
following.
Enter 1(=EF1), 2(=EF2), 3(EF3) or 4(=EF4) and press the ENTER key. If disabling them,

enter 0(=Off) and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Scheme sw" screen.
Setting the SEF protection

The settings for the SEF protection are as follows:


Select "SEF" on the "Scheme sw" screen to display the "SEF" screen.
/ 7
S
O
S
F
M
N
M

E
f
E
W
S
I
S

S E F
1
f
1
D
E
/
E

E
/
/
1
V
1

N
O
D
R
C
I
C

1
n
I
E
/
-

R
V
I
E
I

/
E
I
E

0
N O N
C
0
/ L T I
E E
0

149

This setting is displayed if [MSE1] is 1(=IEC).


This setting is displayed if [MSE1] is 2(=IEEE).

6 F 2 S 0 7 5 8
M
M
C
S
D
S
O
V
O
S
O
S
F
V
O
S
O
S
F
V
O
S
O
S
F
V
O
R
O

I
S
O
E
E
E
f
T
f
E
f
E
W
T
f
E
f
E
W
T
f
E
f
E
W
T
f
P
f

/
E
2
1
F
1
f
F
f
2
f
2
D
F
f
3
f
3
D
F
f
4
f
4
D
F
f
E
f

V
1
/
R
/
S
/
/
E
/
/
/
E
/
/
/
E
/
/
/
N
/

I / E I
C - U S
C O 8

This setting is displayed if [MSE1] is 3(=US).

0
D
2
O
S
O
N
O
D
R
S
O
N
O
D
R
S
O
N
O
D
R
S
O

E P
0
n
E 1 B L K
n

0
n
I R
0
E V / N O N
E 2 B L K
0
n
0
n
I R
0
E V / N O N
E 3 B L K
0
n
0
n
I R
0
E V / N O N
E 4 B L K
0
n

O n

<SEEN>
Enter 1(=On) to enable the SEF and press the ENTER key. If disabling the SEF, enter

0(=Off) and press the ENTER key.


<MSE1C>

To set the SEF1 Inverse Curve Type, do the following.


If [MSE1] is 1(=IEC), enter 0(=NI) or 1(=VI) or 2(=EI) or 3(=LTI) and press the ENTER
key.
If [MSE1] is 2(=IEEE), enter 0(=MI) or 1(=VI) or 2(=EI) and press the ENTER key.
If [MSE1] is 3(=US), enter 0(=CO2) or 1(=CO8) and press the ENTER key.
<SE1R>

To set the Reset Characteristic, do the following.


If [MSE1] is 2(=IEEE) or 3(=US), enter 0(=DEF) or 1(=DEP) and press the ENTER key.
<SE1S2>

To set the Stage 2 Timer Enable, do the following.


Enter 1(=On) to enable the SE1S2 and press the ENTER key. If disabling the SE1S2, enter

0(=Off) and press the ENTER key.

150

6 F 2 S 0 7 5 8
<VTF-SEBLK>

To set the VTF block enable of SE, do the following.


Enter 1(=On) to enable "Trip block" by the VTF function and press the ENTER key. If

disabling it, enter 0(=Off) and press the ENTER key.


<RPEN>

To set the residual power block enable of SE, do the following.


Enter 1(=On) to enable "Trip block" by the residual power block function and press the
ENTER key. If disabling it, enter 0(=Off) and press the ENTER key.
After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Scheme sw" screen.
Setting the NOC protection

The settings for the NOC protection are as follows:


Select the "NOC" on the "Scheme sw" screen to display the "NOC" screen.
/ 7
N
O
N
F
C
O
V
O
N
O
N
F
C
O
V
O

C
f
C
W
T
f
T
f
C
f
C
W
T
f
T
f

N O C
1
f
1
D
F
f
F
f
2
f
2
D
F
f
F
f

E
/
/
/
/
E
/
/
/
/

N
O
D
R
N
O
N
O
N
O
D
R
N
O
N
O

1
n
I
E
C
n
C
n

R
0
V / N O N
1 B L K
0
1 B L K

0
0

n
I
E
C
n
C
n

R
0
V / N O N
2 B L K
0
2 B L K

<NCEN>
Enter 1(=On) to enable the NC and press the ENTER key. If disabling the NC, enter

0(=Off) and press the ENTER key.


<NC-DIR>

To set the NC directional characteristic, do the following.


Enter 0(=FWD) or 1(=REV) or 2(=NON) and press the ENTER key.

151

6 F 2 S 0 7 5 8
<CTF-NCBLK>, <VTF-NCBLK>

To set the CTF block and VTF block enable of NC, do the following.
Enter 1(=On) to enable "Trip block" by the CTF function and VTF function, and press the
ENTER key. If disabling them, enter 0(=Off) and press the ENTER key.
After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Scheme sw" screen.
Setting the Misc. protection

The settings for the miscellaneous protection are as follows:


Select "Misc." on the "Scheme sw" screen to display the "Misc." screen.
/ 7
U
O
C
O
U
O
C
O
T
O
T
O
B
O
B
O
R
O

C
f
T
f
C
f
T
f
H
f
H
f
C
f
T
f
T
f

M i s c .
1
f
F
f
2
f
F
f
M
f
M
f
D
f
C
f
C
f

E
/
/
E
/
/
E
/
A
/
E
/

N
O
U
O
N
O
U
O
N
O
E
O
N
O

0
n
C 1 B L K
n

0
0

n
C 2 B L K
n

0
0

n
N
n

0
0

n
0

/ O n
0
/ D I R / O C

<UCEN>
Enter 1(=On) to enable the UC and press the ENTER key. If disabling the UC, enter

0(=Off) and press the ENTER key.


<CTF-UCBLK>

To set the CTF block enable of UC, do the following.


Enter 1(=On) to enable "Trip block" by the CTF function, and press the ENTER key. If

disabling it, enter 0(=Off) and press the ENTER key.


<THMEN>
Enter 1(=On) to enable the Thermal OL and press the ENTER key. If disabling the Thermal

OL, enter 0(=Off) and press the ENTER key.

152

6 F 2 S 0 7 5 8
<THMAEN>
Enter 1(=On) to enable the Thermal Alarm and press the ENTER key. If disabling the

Thermal Alarm, enter 0(=Off) and press the ENTER key.


<BCDEN>
Enter 1(=On) to enable the Broken Conductor and press the ENTER key. If disabling the

Broken Conductor, enter 0(=Off) and press the ENTER key.


<BTC>
Enter 1(=On) to set the Back-trip control and press the ENTER key. If not setting the

Back-trip control, enter 0(=Off) and press the ENTER key.


<RTC>

To set the Re-trip control, do the following.


Enter 0(=Off) or 1(=Direct) or 2(=OC controlled) and press the ENTER key.
Setting the Cold Load protection

The settings for the Cold Load protection are as follows:


Select "Misc." on the "Scheme sw" screen to display the "Misc." screen.
/ 7
C
O
C
O

L
f
L
f

C o l d
E
f
D
f

L o a d

N
/ O n
O E N
/ O n

<CLEN>

To set the Cold load function enable, do the following.


Enter 1(=On) to enable the Cold Load function and press the ENTER key. If disabling the

Cold Load, enter 0(=Off) and press the ENTER key.


<CLDOEN>
Enter 1(=On) to enable the Cold Load drop-off and press the ENTER key. If disabling the

Cold Load drop-off, enter 0(=Off) and press the ENTER key.
After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Scheme sw" screen.
Setting the OV protection

The settings for the OV protection are as follows:


Select "OV" on the "Scheme sw" screen to display the "OV" screen.

153

6 F 2 S 0 7 5 8
/ 7
O
O
O
O

V
f
V
f

O V
1
f
2
f

E
/
E
/

N
0
D T / I D M T
N
0
O n

<OV1EN>

To set the OV1 delay type, do the following.


Enter 1 (=DT) or 2 (=IDMT) and press the ENTER key. If disabling the OV1, enter 0 (=Off)

and press the ENTER key.


<OV2EN>
Enter 1 (=On) to enable the OV2 and press the ENTER key. If disabling the OV2, enter 0

(=Off) and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
Setting the UV protection

The settings for the UV protection are as follows:


Select "UV" on the "Scheme sw" screen to display the "UV" screen.
/ 7
U
O
V
O
U
O
V
O
V
O

V
f
T
f
V
f
B
f
T
f

U V
1
f
F
f
2
f
L
f
F
f

E
/
/
E
/
K
/
/

N
D
U
O
N
O
E
O
U
O

1
T / I D M T
V 1 B L K
0
n
0
n
N
0
n
V 2 B L K
0
n

<UV1EN>

To set the UV1 delay type, do the following.


Enter 1 (=DT) or 2 (=IDMT) and press the ENTER key. If disabling the UV1, enter 0 (=Off)

and press the ENTER key.


<UV2EN>
Enter 1 (=On) to enable the UV2 and press the ENTER key. If disabling the UV2, enter 0

(=Off) and press the ENTER key.

154

6 F 2 S 0 7 5 8
<VBLKEN>
Enter 1 (=On) to enable the UV blocking and press the ENTER key. If disabling the UV

blocking, enter 0 (=Off) and press the ENTER key.


<VTF-UVBLK>

To set the VTF block enable of UV, do the following.


Enter 1(=On) to enable "Trip block" by the VTF function and press the ENTER key. If

disabling it, enter 0(=Off) and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
Setting the ZOV protection

The settings for the ZOV protection are as follows:


Select "ZOV" on the "Scheme sw" screen to display the "ZOV" screen.
/ 7
Z
O
V
O
Z
O
V
O

O
f
T
f
O
f
T
f

Z O V
V
f
F
f
V
f
F
f

1
/
/
2
/
/

E
D
Z
O
E
O
Z
O

N
1
T / I D M T
V 1 B L K
0
n
N
0
n
V 2 B L K
0
n

<ZOV1EN>

To set the ZOV1 delay type, do the following.


Enter 1(=DT) or 2(=IDMT) and press the ENTER key. If disabling the ZOV1, enter 0(=Off)

and press the ENTER key.


< ZOV2EN >
Enter 1(=On) to enable the ZOV2 and press the ENTER key. If disabling the ZOV2, enter

0(=Off) and press the ENTER key.


<VTF-ZVBLK>

To set the VTF block enable of ZOV, do the following.


Enter 1(=On) to enable "Trip block" by the VTF function and press the ENTER key. If

disabling it, enter 0(=Off) and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e

s e t t i n g s ?

155

6 F 2 S 0 7 5 8
E N T E R = Y

C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
Setting the NOV protection

The settings for the NOV protection are as follows:


Select "NOV" on the "Scheme sw" screen to display the "NOV" screen.
/ 7
N
O
V
O
N
O
V
O

O
f
T
f
O
f
T
f

N O V
V
f
F
f
V
f
F
f

1
/
/
2
/
/

E
D
N
O
E
O
N
O

N
1
T / I D M T
V 1 B L K
0
n
N
0
n
V 2 B L K
0
n

<NOV1EN>

To set the NOV1 delay type, do the following.


Enter 1(=DT) or 2(=IDMT) and press the ENTER key. If disabling the NOV1, enter 0(=Off)

and press the ENTER key.


< NOV2EN >
Enter 1(=On) to enable the NOV2 and press the ENTER key. If disabling the NOV2, enter

0(=Off) and press the ENTER key.


<VTF-NVBLK>

To set the VTF block enable of NOV, do the following.


Enter 1(=On) to enable "Trip block" by the VTF function and press the ENTER key. If

disabling it, enter 0(=Off) and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Scheme sw" screen.
Setting the FRQ protection

The settings for the FRQ (over/under frequency) protection are as follows:
Select "FRQ" on the "Scheme sw" screen to display the "FRQ" screen.
/ 7
F
O
F
O

R
f
R
f

F R Q
Q
f
Q
f

1
/
2
/

E
O
E
O

N
F / U F
N
F / U F

156

0
0

6 F 2 S 0 7 5 8
F
O
F
O

R
f
R
f

Q
f
Q
f

3
/
4
/

E
O
E
O

N
F / U F
N
F / U F

0
0

<FRQEN>

To set the FRQ scheme enable, do the following.


Enter 1(=OF, overfrequency) or 2(=UF, underfrequency) and press the ENTER key. If

disabling the FRQ, enter 0(=Off) and press the ENTER key.
Setting the protection elements

To set the protection elements, do the following.


Select "Prot. element" on the "Trip" screen to display the "Prot. element" screen.
/

6
O
E
S
N
M
C
O
U
Z
N
F
C

P r o t . e l e m e n t
C
F
E
O
i
o
V
V
O
O
R
T

F
C
s c
l d

L o a d

V
V
Q
F / V T F

Setting the OC elements


Select "OC" on the "Prot. element" screen to display the "OC" screen.
/ 7

O C

O C
4 5
O C 1
1
T O C
1 .
T O C
1
T O C
0
T O C
1 .
O C 2
5
T O C
0
O C 3
1 0
T O C
0
O C 4
2 0

_
A

.
1
0
1
.
1
.
1
0

0 0
M
0 0
s
0 0
R
0
R M
0 0

A
. 0 0
2
. 0 0

s
A

. 0 0
3
. 0 0

s
A

. 0 0

157

Directional characteristic setting

6 F 2 S 0 7 5 8
T O C
0
O C 1
0 .
O C 1
0
O C 1
0 .
O C 1
0 .
O C 1
0

4
.
0
.
0
0
.

s
0
k
0

0
C
0
k
0

0
OC1 User configurable IDMT curve setting
0
ditto
0
ditto
0
r
0

ditto
ditto

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Prot. element" screen.
Setting the EF elements
Select "EF" on the "Prot. element" screen to display the "EF" screen.
/ 7
E F

E F

4 5

Directional characteristic setting

V0 threshold setting for directional characteristic

E F V
3 . 0
E F 1
0
T E F
1 .
T E F
1
T E F
T
E
T
E
T
E
T
T
E
E

.
1
0
1
.
1
0
E F 1
1 . 0
F 2
3 .
E F 2
1 .
F 3
5 .
E F 3
0 .
F 4
1 0 .
E F 4
0 .
R E B
0 .
F 1 0 . 0
F 1 -

A
3 0
M
0 0

_
s

0
R
.
R
0

0
s
0
M
0
A

0 0
s
0 0
A
0 0
s
0 0
A
0 0
s
0 0
K
1 0
k
0 0

Delay time of current reverse detection


EF1 User configurable IDMT curve setting
ditto

158

6 F 2 S 0 7 5 8

E F
0
E F
0
E F

0
1
.
1
.
1
0

.
0
0
.

0
C
0
k
0

0
ditto
0
r
0

ditto
ditto

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Prot. element" screen.
Setting the SEF elements
Select "SEF" on the "Prot. element" screen to display the "SEF" screen.
/ 7
S E

S E F

+ 9 0

S E V

Directional characteristic setting

V0 threshold setting for directional characteristic

3 . 0
S E
0
T S
1
T S

1
.
E
.
E
1
T S E
T S E
1 .
T S 1
0
S E 2
0 .
T S E
1
S E 3
0 .
T S E
0
S E 4
0 .
T S E
0
S E 1
0 .
S E 1
0
S E 1
0 .
S E 1
0 .

A
0
1
0
1
.
1
0
1
0
S
.

1 0
M
0 0
s
0
R
.
R
0
2
0

0
s
0
M
0
s
0
A

0 1 0
2
. 0 0

s
A

0 1 0
3
. 0 0

s
A

0
4
.
0
.
0
0

10
s
0
k
0

0
C
0
k
0

0
SE1 User configurable IDMT curve setting
0
ditto
0
ditto
0
r
0

ditto

159

6 F 2 S 0 7 5 8
S E 1 -
0 . 0 0

ditto

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Prot. element" screen.
Setting the NOC elements
Select "EF" on the "Prot. element" screen to display the "EF" screen.
/ 7
N C

N O C

4 5

Directional characteristic setting

V0 threshold setting for directional characteristic

N C V
3 . 0
N C 1
0
T N C
1
T N C

.
1
.
1
0
T N C 1
1 . 0
N C 2
0 .
T N C 2
0 .

2 0
s
0
R
.
R
0

0
s
0
M
0
A

4 0
s
0 0

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Prot. element" screen.
Setting the Misc. protection elements
Select "Misc." on the "Prot. element" screen to display the "Misc." screen.

/ 7
U C 1
0
T U C
1
U C 2
0
T U C
1

M i s c .
A
. 4 0
1
. 0 0

_
s
A

. 2 0
2
. 0 0

160

6 F 2 S 0 7 5 8
T H M
1
T H M
0
T T H
1
T H M

A
.
I
.
M
0
A

0 0
P
0 0

A
m i n

. 0
%
8 0

B C D
0
T B C
0
C B F
0
T B T
0
T R T
1

. 2 0
D
. 0 0

s
A

. 5 0
C
. 5 0
C
. 0 0

s
s

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Prot. element" screen.
Setting the Cold Load protection elements
Select "Cold Load" on the "Prot. element" screen to display the "Cold Load" screen.
/ 7
O C 1
2
O C 2
1 0
O C 3
2 0
O C 4
4 0
E F 1
2
E F 2
1 0
E F 3
2 0
E F 4
4 0
S E 1
0 .
S E 2
0 .
S E 3
0 .
S E 4
0 .
N C 1

C o l d

l o a d
A

. 0 0

_
A

. 0 0
A
. 0 0
A
. 0 0
A
. 0 0
A
. 0 0
A
. 0 0
A
. 0 0
A
0 2 0
A
0 2 0
A
0 2 0
A
0 2 0
A

161

6 F 2 S 0 7 5 8
0
N C 2
0
B C D
0
T C L
1
T C L
1
I C L
0
T C L
0

. 8 0
A
. 4 0
.
E
0
R
0
D
.
D
.

4 0
s
0
s
0
O
5 0
O
0 0

A
s

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Prot. element" screen.
Setting the OV elements
Select "OV" on the "Prot. element" screen to display the "OV" screen.
/ 7

O V

O V 1
1 2 0 .
T O V 1 M
1 . 0
T O V 1
0 . 0
T O V 1 R
0 .
O V 1 D P
9
O V 2
1 4 0 .
T O V 2
0 . 0
O V 2 D P
9

V
0

OV1 Threshold setting.

0
s
0
0
R
5

OV1 Definite time reset delay.

OV1 DO/PU ratio

OV2 Threshold setting.

OV2 Definite time setting.

OV2 DO/PU ratio

0
0
R
5

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
Setting the UV elements
Select "UV" on the "Prot. element" screen to display the "UV" screen.
/ 7

U V

162

6 F 2 S 0 7 5 8

U V 1
6
T U V
1
T U V
0
T U V
U V 2
4
T U V
0
V B L
1

V
0
1
.
1
.
1
0

. 0
M
0 0

UV1 Threshold setting.

_
s

0 0
R
. 0

0 . 0
2
. 0 0
K
0 . 0

UV1 Definite time reset delay.

UV2 Threshold setting.

UV2 Definite time setting.

UV Blocking threshold

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
Setting the ZOV elements
Select "ZOV" on the "Prot. element" screen to display the "ZOV" screen.
/ 7

Z O V

Z O V
2
T Z O
1
T Z O
0
T Z O

1
0
V
.
V
.
V
0
2
0
V
.

Z O V
4
T Z O
0

V
.
1
0
1
0
1
.

0
M
0

ZOV1 Threshold setting.

_
s

0
R
0

. 0
2
0 0

ZOV1 Definite time reset delay.

ZOV2 Threshold setting.

ZOV2 Definite time setting.

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
Setting the NOV protection elements
Select "NOV" on the "Prot. element" screen to display the "NOV" screen.
/ 7

N O V

163

6 F 2 S 0 7 5 8
N O V
2
T N O
1
T N O
0
T N O
N O V
4
T N O
0

1
0
V
.
V
.
V
0
2
0
V
.

V
.
1
0
1
0
1
.

0
M
0

NOV1 Threshold setting.

_
s

0
R
0

. 0
2
0 0

NOV1 Definite time reset delay.

NOV2 Threshold setting.

NOV2 Definite time setting.

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
Setting the FRQ elements
Select "FRQ" on the "Prot. element" screen to display the "FRQ" screen.
/ 7

F R Q

F R Q 1
1 . 0
T F R Q 1
1 . 0
F R Q 2
1 . 0
T F R Q 2
1 . 0
F R Q 3
1 . 0
T F R Q 3
1 . 0
F R Q 4
1 . 0
T F R Q 4
1 . 0
F V B L K
4 0 .

H z
0

0
H z
0
0
H z
0
0
H z
0

0
V

UV Blocking threshold

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (= Y) key to change settings and return to the "Prot. element" screen.
Setting the CTF/VTF elements
Select "CTF/VTF" on the "Prot. element" screen to display the "CTF/VTF" screen.

164

6 F 2 S 0 7 5 8
/ 7

C T F / V T F

E F F
0
Z O V
2
U V F
5

A
. 2 0
F
0 . 0

_
V
V

1 . 0

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "Prot. element" screen.
Setting the autoreclose function

To set the autoreclose function, do the following.


Select "ARC" on the "Group " screen to display the "ARC" screen.
/ 5
A R C
S c h e m e
T i m e r s

s w

Setting the scheme switch


Select "Scheme sw" on the "ARC" screen to display the "Scheme sw" screen.
/

6
G
O
E
S
E

S c h e m e
e n e r a l
C
F
E F
X T

s w

<General>
Select "General" on the "Scheme sw" screen to set the autoreclose mode.
/ 7
A
O
A
S
C
O
C
O
C
O

R
f
R
1
O
f
O
f
O
f

G e n e r a l
C
f
C
/
O
f
O
f
O
f

E
/
S
R
/
R
/
R
/

N
O
N
2
D
O
D
O
D
O

0
n
U
/
n
n
n

M
0
S 3 / S 4 / S 5
O C
0
E F

S E

Enter 1(=On) or 0(=Off) to enable or to disable the autoreclose.


Enter 0 or 1 or 2 or 3 or 4 to set the number of shot.

Enter 0 (= S1) to perform single-shot autoreclosing.

165

6 F 2 S 0 7 5 8
Enter 1 (= S2) to perform two-shot autoreclosing..
Enter 2 (= S3) to perform three-shot autoreclosing.
Enter 3 (= S4) to perform four-shot autoreclosing.
Enter 4 (= S5) to perform five-shot autoreclosing.
Enter 1(=On) or 0(=Off) to enable or to disable the co-ordination for "COOD-OC",
"COOD-EF" and "COOD-SE" and press the ENTER key.
<OC>, <EF>, <SEF>
Select "OC" on the "Scheme sw" screen to set the autoreclose initiation and trip mode of OC
protection.
/ 7
O
N
O
O
O
O
O
O
O
O
O
O
O
O

C
A
C
f
C
f
C
f
C
f
C
f
C
f

O
O
O
O
O
O
O
O
O
O
O
O
O

C
C
f
C
f
C
f
C
f
C
f
C
f

O C
1
/
1
f
1
f
1
f
1
f
1
f
1
f
:
:
4
4
f
4
f
4
f
4
f
4
f
4
f

O
T
/
T
/
T
/
T
/
T
/
T
/

I
n
P
I
P
I
P
I
P
I
P
I
P
I

N
/
1
n
2
n
3
n
4
n
5
n
6
n

I T
0
B l o c k
0
s t / S e t
0
s t / S e t
0
s t / S e t
0
s t / S e t
0
s t / S e t
0
s t / S e t

T
/
T
/
T
/
T
/
T
/
T
/

I
P
I
P
I
P
I
P
I
P
I
P
I

N
1
n
2
n
3
n
4
n
5
n
6
n

I T
s t / S e
s t / S e
s t / S e
s t / S e
s t / S e
s t / S e

0
0
t
0
t
0
t
0
t
0
t
0
t

Enter 1(=INIT) or 2(=Block) to initiate or to block the autoreclose by the OC1 trip in
"OC1-INIT". To neither initiate nor block it, enter 0(=NA).
Enter 1(=Inst) or 2(=Set) to set the OC1 first trip to Instantaneous trip or Set time delay trip
in the "OC1-TP1". To not use the OC1 trip, enter 0(=Off).
Note: OC1-TP2 to OC1-TP6 show the OC1 second trip to OC1 sixth trip.

For OC2 to OC4, the settings are same as OC1. After changing settings, press the ENTER key.
The setting method for EF and SEF is same as that of OC above.

166

6 F 2 S 0 7 5 8
<EXT>
Select "EXT" on the "Scheme sw" screen to set the external initiation of the autoreclose.
/ 7

E X T

E X T - I N I T
0
N A / O n / B l o c k

Enter 1(=INIT) or 2(=Block) to initiate or to block the autoreclose by the external trip. To
neither initiate nor block it, enter 0(=NA).
Setting the timers
Select "Timers" on the "Group " screen to set timer setting and the threshold setting of OC, EF
and SEF for co-ordination.
/ 6

T i m e r s

T R D
6
T D 1
1 0
T D 2
1 0
T D 3
1 0
T D 4
1 0
T D 5
1 0
T W
2
T S U
3
T R C
1 0
T A R
1 0
T R S
3
O C
1
E F
0
S E
0 .

Y
0 . 0

s
_
s

. 0 0
s
. 0 0
s
. 0 0
s
. 0 0
s
. 0 0
s
.
C
.
O
.
C
.
E
.

0 0
s
0
V
0
P
0
T
0

0
s
0
s
0
s
0
A

. 0 0
A
. 3 0
A
0 1 0

Enter the numerical value and press the ENTER key.


After setting, press the END key to display the following confirmation screen.
C h a n g e
s e t t i n g s ?
E N T E R = Y
C A N C E L = N

Press the ENTER (=Y) key to change settings and return to the "ARC" screen.

167

6 F 2 S 0 7 5 8
Setting group copy

To copy the settings of one group and overwrite them to another group, do the following:
Select "Copy gp." on the "Protection" screen to display the "Copy A to B" screen.
/ 3

C o p y

t o

A
B

Enter the group number to be copied in line A and press the ENTER key.
Enter the group number to be overwritten by the copy in line B and press the ENTER key.
4.2.6.8 Binary Input

The logic level of binary input signals can be inverted by setting before entering the scheme logic.
Inversion is used when the input contact cannot meet the requirements described in Table 3.2.2.
Select "Binary I/P" on the "Set. (change)" sub-menu to display the "Binary I/P" screen.
/
.
.
.
.
.
.
.
.
.
.
.
.

2
B
B
B
B
B
B
B
B
A
A
A
A

I
I
I
I
I
I
I
I
l
l
l
l

B
1
2
3
4
5
6
7
8
a
a
a
a

i n a r y

r
r
r
r

m
m
m
m

1
2
3
4

T
T
T
T

I / P

e
e
e
e

x
x
x
x

t
t
t
t

Selection of Binary Input


Select the input number (BI number) on the "Binary I/P" screen.
Setting Alarm Text

If the BI selected is used for an alarm, alarm message can be set.


Select the Alarm text and press the ENTER key to display the text input screen.
_
A
H
O
V
a
h
o
v
0
7
(
}
>

B
I
P
W
b
i
p
w
1
8
)

!
:

168

C
J
Q
X
c
j
q
x
2
9
[
/

D
K
R
Y
d
k
r
y
3
]
+
#
,

E
L
S
Z
e
l
s
z
4

F G
M N
T U

f g
m n
t u

5 6

@_ {
< =
$ %&
. `

6 F 2 S 0 7 5 8
Enter the characters (up to 22 characters) according to the text setting method.

After setting, press the ENTER key to display the "BI" screen.
/ 3
B I
T i m e r s
F u n c t i o n s

Setting timers
Select "Timers" on the "BI" screen to display the "Timers" screen.
/ 4

T i m e r s

B I 1
0
B I 1
0

P
.
D
.

U
0
O
0

D
0
D
0

Pick-up delay setting

Drop-off delay setting

Enter the numerical value and press the ENTER key.


After setting, press the END key to return to the "BI" screen.
Setting Functions
Select "Functions" on the "BI" screen to display the "Functions" screen.
/ 4
B
N
B
O
O
O
O
O
O
O
O
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O
E
O

I
o
I
f
C
f
C
f
C
f
C
f
F
f
F
f
F
f
F
f
F
f
F
f
F
f
F
f

F u n c t i o n s
1
r
1
f
1
f
2
f
3
f
4
f
1
f
2
f
3
f
4
f
1
f
2
f
3
f
4
f

S
m
S
/
B
/
B
/
B
/
B
/
B
/
B
/
B
/
B
/
P
/
P
/
P
/
P
/

N
/
G
1
L
O
L
O
L
O
L
O
L
O
L
O
L
O
L
O
E
O
E
O
E
O
E
O

S
1
I n v
S
0
/ 2 / 3 / 4
K
0
n
K
0
n
K
0
n
K
0
n
K
0
n
K
0
n
K
0
n
K
0
n
R
0
n
R
0
n
R
0
n
R
0
n

169

6 F 2 S 0 7 5 8
S
O
S
O
S
O
S
O
N
O
N
O
U
O
U
O
C
O
T
O
T
O
B
O
O
O
O
O
U
O
U
O
Z
O
Z
O
N
O
N
O
F
O
F
O
F
O
F
O
A
O
A
O
A
O

E
f
E
f
E
f
E
f
C
f
C
f
C
f
C
f
B
f
H
f
H
f
C
f
V
f
V
f
V
f
V
f
O
f
O
f
O
f
O
f
R
f
R
f
R
f
R
f
R
f
R
f
R
f

1
f
2
f
3
f
4
f
1
f
2
f
1
f
2
f
F
f
M
f
M
f
D
f
1
f
2
f
1
f
2
f
V
f
V
f
V
f
V
f
Q
f
Q
f
Q
f
Q
f
C
f
C
f
C
f

B
/
B
/
B
/
B
/
B
/
B
/
B
/
B
/
B
/
B
/
A
/
B
/
B
/
B
/
B
/
B
/
1
/
2
/
1
/
2
/
1
/
2
/
3
/
4
/
B
/
R
/
I
/

L
O
L
O
L
O
L
O
L
O
L
O
L
O
L
O
L
O
L
O
B
O
L
O
L
O
L
O
L
O
L
O
B
O
B
O
B
O
B
O
B
O
B
O
B
O
B
O
L
O
D
O
N
O

K
n
K
n
K
n
K
n
K
n
K
n
K
n
K
n
K
n
K
n
L
n
K
n
K
n
K
n
K
n
K
n
L
n
L
n
L
n
L
n
L
n
L
n
L
n
L
n
K
n
Y
n
I
n

0
0
0
0
0
0
0
0
0
0
K

0
0
0
0
0
0

0
0
0
0

170

6 F 2 S 0 7 5 8
M
O
A
O
C
O
V
O
C
O
V
O
E
O
E
O
E
O
E
O
T
O
C
O
C
O
R
O
S
O
S
O
A
O
A
O
A
O
A
O

N
f
R
f
T
f
T
f
T
f
T
f
X
f
X
f
X
f
X
f
C
f
B
f
B
f
M
f
Y
f
T
f
l
f
l
f
l
f
l
f

L
f
C
f
F
f
F
f
F
f
F
f
T
f
T
f
T
f
T
f
F
f
O
f
C
f
T
f
N
f
O
f
a
f
a
f
a
f
a
f

C
/
N
/
B
/
B
/
E
/
E
/
A
/
B
/
C
/
3
/
A
/
P
/
L
/
R
/
C
/
R
/
r
/
r
/
r
/
r
/

L
O
A
O
L
O
L
O
X
O
X
O
P
O
P
O
P
O
P
O
L
O
N
O
S
O
S
O
L
O
C
O
m
O
m
O
m
O
m
O

S
n

0
0

n
K
n
K
n
T
n
T
n
H
n
H
n
H
n
H
n
M
n

0
0
0
0
0
0
0
0
0
0

n
0
n
T
n
K
n
D
n
1
n
2
n
3
n
4
n

0
0
0
0
0
0
0

<BI1SNS>

To set the Binary Input 1 Sense, do the following.


Enter 0(=Normal) or 1(=Inverted) and press the ENTER key.
<BI1SGS>

To set the Binary Input 1 Settings Group Select, do the following.


Enter 0(=Off) or 1(=1) or 2(=2) or 3(=3) or 4(=4) and press the ENTER key.
<Others>
Enter 1(=On) to set the function and press the ENTER key. If not setting the function, enter

171

6 F 2 S 0 7 5 8
0(=Off) and press the ENTER key.
After setting, press the END key to return to the "BI" screen.
4.2.6.9

Binary Output

All the binary outputs of the GRD140 except the relay failure signal are user-configurable. It is
possible to assign one signal or up to four ANDing or ORing signals to one output relay. Available
signals are listed in Appendix C.
It is also possible to attach Instantaneous or delayed or latched reset timing to these signals.
Appendix H shows the factory default settings.

CAUTION
When having changed the binary output settings, release the latch state on a digest screen by
pressing the RESET key for more than 3 seconds.
To configure the binary output signals, do the following:
Selection of output relay

Select "Binary O/P" on the "Set. (change)" screen to display the "Binary O/P" screen.
/

2
B
B
B
B
B
B
B

O
O
O
O
O
O
O

B i n a r y
1
2
3
4
5
6
7

O / P

Note: The setting is required for all the binary outputs. If any of the binary outputs are not used, enter
0 to logic gates #1 to #4 in assigning signals.

Select the output relay number (BO number) and press the ENTER key to display the "BO"
screen.
/ 3
B O
L o g i c / R e s e t
F u n c t i o n s

Setting the logic gate type and timer


Select "Logic/Reset" to display the "Logic/Reset" screen.
/ 4
L
O
R
I

o
R
e
n

L o g i c / R e s e t
g
/
s
s

i
A
e
/

c
0
_
N D
t
0
D l / D w / L a t

Enter 0(=OR) or 1(=AND) to use an OR gate or AND gate and press the ENTER key.
Enter 0(=Instantaneous) or 1(=Delayed) or 2(=Dwell) or 3(=Latched) to select the reset timing
and press the ENTER key.

172

6 F 2 S 0 7 5 8
Press the END key to return to the "BO" screen.
Note: To release the latch state, push the [RESET] key for more than 3 seconds.

Assigning signals
Select "Functions" on the "BO" screen to display the "Functions" screen.
/ 4

F u n c t i o n s

I n

# 1
2 1
# 2
1 1
# 3
2 4
# 4
0

I n
I n
I n

T B O
0 . 2 0

Assign signals to gates (In #1 to #4) by entering the number corresponding to each signal
referring to Appendix C. Do not assign the signal numbers 471 to 477 (signal names: "BO1
OP" to "BO7 OP"). And set the delay time of timer TBO.
Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s).

Repeat this process for the outputs to be configured.


4.2.6.10 LEDs

Three LEDs of the GRD140 are user-configurable. A configurable LED can be programmed to
indicate the OR combination of a maximum of 4 elements, the individual statuses of which can be
viewed on the LED screen as Virtual LEDs. The signals listed in Appendix C can be assigned to
each LED as follows.

CAUTION
When having changed the LED settings, must release the latch state on a digest screen by
pressing the RESET key for more than 3 seconds.
Selection of LEDs
Select "LED" on the "Set. (change)" screen to display the "LED" screen.
/ 2
L E D
L E D
V i r t u a l

L E D

Selection of real LEDs


Select "LED" on the "/2 LED" screen to display the "/3 LED" screen.
/

3
L E D
L E D 1
L E D 2
L E D 3

Select the LED number and press the ENTER key to display the "LED" screen.

173

6 F 2 S 0 7 5 8
/ 4
L E D
L
o
g i c / R e s e t

F u n c t i o n s

Setting the logic gate type and reset tipe


Select "Logic/Reset" to display the "Logic/Reset" screen.
/ 5
L
O
R
I

o
R
e
n

L o g i c / R e s e t
g
/
s
s

i
A
e
t

c
N D
t
/ L a t c h

Enter 0(=OR) or 1(=AND) to use an OR gate or AND gate and press the ENTER key.
Enter 0(=Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER key.
Press the END key to return to the "LED" screen.
Note: To release the latch state, refer to Section 4.2.1.

Assigning signals
Select "Functions" on the "LED" screen to display the "Functions" screen.
/ 5

F u n c t i o n s

I n

# 1
2 1
# 2
1 1
# 3
2 4
# 4
0

I n
I n
I n

Assign signals to gates (In #1 to #4) by entering the number corresponding to each signal
referring to Appendix C.
Note: If signals are not assigned to all the gates #1 to #4, enter 0 for the unassigned gate(s).

Press the END key to return to the "LED" screen.

Repeat this process for the outputs to be configured.


Selection of virtual LEDs
Select "Virtual LED" on the "/2 LED" screen to display the "Virtual LED" screen.
/ 3
V i r t u a l
I N D 1
I N D 2

L E D

Select the IND number and press the ENTER key to display the "IND" screen.
/ 4
I N D
R e s e t
F u n c t i o n s

174

6 F 2 S 0 7 5 8
Setting the reset timing
Select "Reset" to display the "Reset" screen.
/ 5

R e s e t

R e s e t
I n s t / L a t c h

Enter 0(=Instantaneous) or 1(=Latched) to select the reset timing and press the ENTER key.
Press the END key to return to the "IND" screen.
Note: To release the latch state, push the [RESET] key for more than 3 seconds.

Assigning signals
Select "Functions" on the "IND" screen to display the "Functions" screen.
/ 5

F u n c t i o n s

B I T 1
5 1

B I T 2
5 4
B I T 8
7 8

Assign signals to bits (1 to 8) by entering the number corresponding to each signal referring to
Appendix C.
Note: If signals are not assigned to all the bits 1 to 8, enter 0 for the unassigned bit(s).

Press the END key to return to the "IND" screen.

Repeat this process for the outputs to be configured.

4.2.7

Testing
The sub-menu "Test" provides such functions as disabling the automatic monitoring function and
forced operation of binary outputs.
Note: When operating the "Test" menu, the "IN SERVICE" LED is flickering. But if an alarm occurs
during the test, the flickering stops. The "IN SERVICE" LED flickers only in a lighting state.

4.2.7.1 Scheme Switch

The automatic monitor function (A.M.F.) can be disabled by setting the switch [A.M.F] to "OFF".
Disabling the A.M.F. inhibits trip blocking even in the event of a failure in the items being
monitored by this function. It also prevents failures from being displayed on the "ALARM" LED
and LCD described in Section 4.2.1. No events related to A.M.F. are recorded, either.
Disabling A.M.F. is useful for blocking the output of unnecessary alarms during testing.
Select "Test" on the top "MENU" screen to display the "Test" screen.
/

1
T e
S w i t
B i n a
L o g i

s t
c h
r y
O / P
c
c i r c u i t

175

6 F 2 S 0 7 5 8
Select "Switch" to display the "Switch" screen.
/ 2
A
O
U
O
C
O
T
O
S
O
I
O

.
f
V
f
L
f
H
f
H
f
E
f

S w i t c h
M
f
T
f
P
f
M
f
O
f
C
f

.
/
S
/
T
/
R
/
T
/
T
/

F
O
T
O
S
S
S
O
N
S
S
O

.
n

0
n
T
0 / S 3
T
n
U M
1 - S 6
T
n

0
0
0
0

Enter 0(=Off) to disable the A.M.F. and press the ENTER key.
Enter 1(=On) to disable the UV block when testing UV elements and press the ENTER key.
Enter 0(=Off) or 1(=State0) or 2(=State3) to set forcibly the test condition of the Cold Load
Protection (CLPTST) and press the ENTER key.
Enter 1(=On) to set the reset delay time of the thermal overload element to instantaneous reset
for testing (THMRST) and press the ENTER key.
Enter 0(=Off) or 1(=S1) or 2(=S2) or 3(=S3) or 4(=S4) or 5(=S5) to set shot number
(SHOTNUM) for autoreclose test and press the ENTER key.
Enter 1(=On) for IECTST to transmit test mode to the control system by IEC60870-5-103
communication when testing the local relay, and press the ENTER key.
Press the END key to return to the "Test" screen.
4.2.7.2 Binary Output Relay

It is possible to forcibly operate all binary output relays for checking connections with the external
devices. Forced operation can be performed on one or more binary outputs at a time.
Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. Then the LCD
displays the name of the output relay.
/ 2
B
D
B
D
B
D
B
D
B
D
B
D
B

O
i
O
i
O
i
O
i
O
i
O
i
O

B i n a r y
1
s
2
s
3
s
4
s
5
s
6
s
7

O / P

0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0

176

_
l e
l e
l e
l e
l e
l e

6 F 2 S 0 7 5 8
D i s a b l e / E n a b l e

Enter 1(=Enable) and press the ENTER key to operate the output relays forcibly.
After completing the entries, press the END key. Then the LCD displays the screen shown
below.
O p e r a t e ?
E N T E R = Y
C A N C E L = N

Keep pressing the ENTER key to operate the assigned output relays.
Release pressing the ENTER key to reset the operation.
Press the CANCEL key to return to the upper "Binary O/P" screen.
4.2.7.3 Logic Circuit

It is possible to observe the binary signal level on the signals listed in Appendix C with monitoring
jacks A and B.
Select "Logic circuit" on the "Test" screen to display the "Logic circuit" screen.
/ 2

L o g i c
c i r c u i t
T e r m A
1
_
T e r m B
4 8
_

Enter a signal number to be observed at monitoring jack A and press the ENTER key.
Enter the other signal number to be observed at monitoring jack B and press the ENTER key.

After completing the setting, the signals can be observed by the binary logic level at monitoring
jacks A and B or by the LEDs above the jacks.
On screens other than the above screen, observation with the monitoring jacks is disabled.

177

6 F 2 S 0 7 5 8

4.3

Personal Computer Interface


The relay can be operated from a personal computer using an RS232C port on the front panel.
On the personal computer, the following analysis and display of the fault currents are available in
addition to the items available on the LCD screen.
Display of current and voltage waveforms:

Oscillograph display

Symmetrical component analysis:

On arbitrary time span

Harmonic analysis:

On arbitrary time span

Frequency analysis:

On arbitrary time span

For the details, see the separate instruction manual "PC INTERFACE RSM100".

4.4

Relay Setting and Monitoring System


The Relay Setting and Monitoring (RSM) system is a system that retrieves and analyses the data
on power system quantities, fault and event records and views or changes settings in individual
relays via a telecommunication network using a remote PC.
Figure 4.4.1 shows the typical configuration of the RSM system via a protocol converter G1PR2.
The relays are connected through twisted pair cables, and the maximum 256 relays can be
connected since the G1PR2 can provide up to 8 ports. The total length of twisted pair wires should
not exceed 1200 m. Relays are mutually connected using an RS485 port on the relay rear panel and
connected to a PC RS232C port via G1PR2. Terminal resistor (150 ohms) is connected the last
relay. The transmission rate used is 64 kbits/s.

Twisted paired
cable

Figure 4.4.1 Relay Setting and Monitoring System

178

6 F 2 S 0 7 5 8

4.5

IEC 60870-5-103 Interface


The GRD140 supports the IEC60870-5-103 communication protocol. This protocol is mainly
used when the relay communicates with a control system and is used to transfer the following
measurand and status data from the relay to the control system. (For details, see Appendix M.)
Measurand data: current, voltage, active power, reactive power, frequency
Status data:

events, fault indications, etc.

The protocol can be used through the RS485 port on the relay rear panel.
The relay supports two baud-rates 9.6kbps and 19.2kbps, and supports two normalizing factors 1.2
and 2.4 for measurand. These are selected by setting. See Section 4.2.6.4.
The data transfer from the relay can be blocked by the setting.
For the settings, see the Section 4.2.6.

4.6

Modbus Interface
The GRD140 supports the Modbus communication protocol. This protocol is mainly used when
the relay communicates with a control system and is used to transfer the following measurement
and status data from the relay to the control system. (For details, see Appendix N.)
Measurement data:

current, voltage, active power, reactive power, frequency

Status data:

events, fault indications, counters, etc.

Setting data
Time setting / synchronization

The protocol can be used via the RS-485 port on the relay rear panel.
The relay supports two baud-rates 9.6kbps and 19.2kbps. These are selected by setting. See
Section 4.2.6.4.

4.7

Clock Function
The clock function (Calendar clock) is used for time-tagging for the following purposes:
Event records
Disturbance records
Fault records

The calendar clock can run locally or be synchronised with the external clock such as the binary
time standard input signal, RSM clock or IEC60870-5-103 or Modbus. This can be selected by
setting.
The clock synchronise function synchronises the relay internal clock to the binary input signal
by the following method. Since the BI signal is an ON or OFF signal which cannot express
year-month-day and hour-minute-second etc, synchronising is achieved by setting the number of
milliseconds to zero. This method will give accurate timing if the synchronising BI signal is input
every second.
Synchronisation is triggered by an OFF to ON (rising edge) transition of the BI signal. When
the trigger is detected, the millisecond value of the internal clock is checked, and if the value is
between 0~500ms then it is rounded down. If it is between 500~999ms then it is rounded up (ie the
number of seconds is incremented).

179

6 F 2 S 0 7 5 8

n sec

(n+1) sec
500ms
corrected to (n+1) sec
corrected to n sec

When the relays are connected with the RSM system as shown in Figure 4.4.1 and selected "RSM"
in the time synchronisation setting, the calendar clock of each relay is synchronised with the RSM
clock. If the RSM clock is synchronised with the external time standard, then all the relay clocks
are synchronised with the external time standard.

180

6 F 2 S 0 7 5 8

5. Installation
5.1

Receipt of Relays
When relays are received, carry out the acceptance inspection immediately. In particular, check
for damage during transportation, and if any is found, contact the vendor.
Always store the relays in a clean, dry environment.

5.2

Relay Mounting
A flush mounting relay is included. Appendix F shows the case outline.
For details of relay withdrawal and insertion, see Section 6.7.3.

5.3

Electrostatic Discharge
CAUTION
Do not take out the relay unit outside the relay case since electronic components on the modules
are very sensitive to electrostatic discharge. If it is absolutely essential to take the modules out of
the case, do not touch the electronic components and terminals with your bare hands.
Additionally, always put the module in a conductive anti-static bag when storing it.

5.4

Handling Precautions
A person's normal movements can easily generate electrostatic potentials of several thousand
volts. Discharge of these voltages into semiconductor devices when handling electronic circuits
can cause serious damage. This damage often may not be immediately apparent, but the reliability
of the circuit will have been reduced.
The electronic circuits are completely safe from electrostatic discharge when housed in the case.
Do not expose them to risk of damage by withdrawing the relay unit unnecessarily.
The relay unit incorporates the highest practical protection for its semiconductor devices.
However, if it becomes necessary to withdraw the relay unit, precautions should be taken to
preserve the high reliability and long life for which the equipment has been designed and
manufactured.

CAUTION
Before removing the relay unit, ensure that you are at the same electrostatic potential as the
equipment by touching the case.
Use the handle to draw out the relay unit. Avoid touching the electronic components,
printed circuit board or connectors.
Do not pass the relay unit to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
Place the relay unit on an anti-static surface, or on a conducting surface which is at the same
potential as yourself.
Do not place the relay unit in polystyrene trays.

181

6 F 2 S 0 7 5 8
It is strongly recommended that detailed investigations on electronic circuitry should be carried
out in a Special Handling Area such as described in the aforementioned IEC 60747.

5.5

External Connections
External connections for each relay model are shown in Appendix G.

182

6 F 2 S 0 7 5 8

6. Commissioning and Maintenance


6.1

Outline of Commissioning Tests


The GRD140 is fully numerical and the hardware is continuously monitored.
Commissioning tests can be kept to a minimum and need only include hardware tests and the
conjunctive tests. The function tests are at the users discretion.
In these tests, user interfaces on the front panel of the relay or local PC can be fully applied.
Test personnel must be familiar with general relay testing practices and safety precautions to avoid
personal injuries or equipment damage.
Hardware tests

These tests are performed for the following hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by monitoring which circuits
function when the DC power is supplied.
User interfaces
Binary input circuits and output circuits
AC input circuits
Function tests

These tests are performed for the following functions that are fully software-based.
Measuring elements
Metering and recording
Conjunctive tests

The tests are performed after the relay is connected with the primary equipment and other external
equipment.
The following tests are included:
On load test: phase sequence check and polarity check
Tripping circuit test
Reclosing circuit test

183

6 F 2 S 0 7 5 8

6.2

Cautions
6.2.1

Safety Precautions
CAUTION
The relay rack is provided with an earthing terminal.
Before starting the work, always make sure the relay rack is earthed.
When connecting the cable to the back of the relay, firmly fix it to the terminal block and attach
the cover provided on top of it.
Before checking the interior of the relay, be sure to turn off the power.

Failure to observe any of the precautions above may cause electric shock or malfunction.

6.2.2

Cautions on Tests
CAUTION
While the power is on, do not drawout/insert the relay unit.
Before turning on the power, check the following:
- Make sure the polarity and voltage of the power supply are correct.
- Make sure the CT circuit is not open.
- Make sure the VT circuit is not short-circuited.
Be careful that the relay is not damaged due to an overcurrent or overvoltage.
If settings are changed for testing, remember to reset them to the original settings.

Failure to observe any of the precautions above may cause damage or malfunction of the relay.

184

6 F 2 S 0 7 5 8

6.3

Preparations
Test equipment

The following test equipment is required for the commissioning tests.


1 Single-phase current source
1 Three-phase current source
1 Single-phase voltage source
1 Three-phase voltage source
1 DC power supply
3 Phase angle meter
3 AC ammeter
3 AC voltmeter
1 Time counter, precision timer
1 PC (not essential)
Relay settings

Before starting the tests, it must be specified whether the tests will use the users settings or the
default settings.
For the default settings, see the Appendix H Relay Setting Sheet.
Visual inspection

After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected. Contact the vendor.
Relay ratings

Check that the items described on the nameplate on the front of the relay conform to the users
specification. The items are: relay type and model, AC current and frequency ratings, and
auxiliary DC supply voltage rating.
Local PC

When using a local PC, connect it with the relay via the RS232C port on the front of the relay.
RSM100 software is required to run the PC.
For the details, see the separate volume "PC INTERFACE RSM100".

185

6 F 2 S 0 7 5 8

6.4

Hardware Tests
The tests can be performed without external wiring, but a DC power supply and AC current and
voltage sources are required.

6.4.1

User Interfaces
This test ensures that the LCD, LEDs and keys function correctly.

LCD display
Apply the rated DC voltage and check that the LCD is off.
Note: If there is a failure, the LCD will display the "Err: " screen when the DC voltage is applied.

Press the RESET key for one second or more and check that black dots appear on the whole
screen.
LED display
Apply the rated DC voltage and check that the "IN SERVICE" LED is lit in green.
Press the RESET key for one second or more and check that remaining five LEDs are lit in
red or yellow. (Programmable LEDs are yellow.)
VIEW and RESET keys
Press the VIEW key when the LCD is off and check that the "Virtual LED" and "Metering"
screens are sequentially displayed on the LCD.
Press the RESET key and check that the LCD turns off.
Other operation keys
Press any key when the LCD is off and check that the LCD displays the "MENU" screen. Press
the END key to turn off the LCD.
Repeat this for all keys.

6.4.2

Binary Input Circuit


The testing circuit is shown in Figure 6.4.1.

186

6 F 2 S 0 7 5 8
GRD140
TB2

- A1
- B1

- A8
DC
power
supply

- B8
TB2 -A9

- B9

BI6
BI7
BI8
BI1
BI2
BI3
BI4
BI5

E
Note: Models 400 and 420 are not provided with BI6 to BI8.

Figure 6.4.1 Testing Binary Input Circuit

Display the "Binary I/O" screen from the "Status" sub-menu.


/ 2
I P
O P

B i n a r y
I / O
0
0
0
0
0
0 0 0 ]
[
0 0 0 0 ]
[ 0 0 0 0

Apply the rated DC voltage to terminal A1-B1, A2-B2, ..., A8-B8 of terminal block TB2.
Check that the status display corresponding to the input signal (IP) changes from 0 to 1. (For
details of the binary input status display, see Section 4.2.4.2.)
Note: Models 400, 430 and 420 are not provided with BI6 to BI8.

The user will be able to perform this test for one terminal to another or for all the terminals at once.

6.4.3

Binary Output Circuit


This test can be performed by using the "Test" sub-menu and forcibly operating the relay drivers
and output relays. Operation of the output contacts is monitored at the output terminal. The output
contact and corresponding terminal number are shown in Appendix G.
Select "Binary O/P" on the "Test" screen to display the "Binary O/P" screen. The LCD displays
the name of the output relay.
/ 2
B
D
B
D
B
D
B
D
B
D
B
D
B
D

O
i
O
i
O
i
O
i
O
i
O
i
O
i

B i n a r y
1
s
2
s
3
s
4
s
5
s
6
s
7
s

O / P

0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b

187

_
l e
l e
l e
l e
l e
l e
l e

6 F 2 S 0 7 5 8
Enter 1 and press the ENTER key.
After completing the entries, press the END key. The LCD will display the screen shown
below. If 1 is entered for all the output relays, the following forcible operation can be
performed collectively.
O p e r a t e ?
E N T E R = Y
C A N C E L = N

Keep pressing the ENTER key to operate the output relays forcibly.
Check that the output contacts operate at the terminal.
Stop pressing the ENTER key to reset the operation

6.4.4

AC Input Circuits
This test can be performed by applying known values of voltage and current to the AC input
circuits and verifying that the values applied coincide with the values displayed on the LCD
screen.
The testing circuits are shown in Figures 6.4.2 and 6.4.3. A three-phase voltage source and a
single-phase current source are required.
GRD140-110
V

Single-phase
voltage
source

TB1

-1
V
-2

TB1 -5

Single-phase
current
source

-6
-7
-8

DC
power
supply

TB2 -A9

-B9
E

Figure 6.4.2 Testing AC Input Circuit for Model 110

188

Ie

Ise

6 F 2 S 0 7 5 8
GRD140-400 or -420
V

Three-phase
voltage
a
source
b

V
TB 2

-A1

Va

-B1

Vb

-A2

Vc

-B2
-A3

TB1 -1

Single-phase
current
source

-B3

-2
-3
-4
-5
-6

VR

Ia

Ib

Ic

-7
-8

DC
power
supply

TB2 -A9

-B9

Ie or I
se

Figure 6.4.3 Testing AC Input Circuit for Models 400, 430 and 420

Check that the metering data is set to be expressed as secondary values on the "Metering switch"
screen.

"Settings" sub-menu "Status" screen "Metering switch" screen


If the setting is Display Value = Primary, change the setting in the "Metering switch".
Remember to reset it to the initial setting after the test is finished.
Open the "Metering" screen in the "Status" sub-menu.

"Status" sub-menu "Metering" screen


Apply AC rated voltages and currents and check that the displayed values are within 5% of the
input values.

189

6 F 2 S 0 7 5 8

6.5

Function Test
CAUTION
The function test may cause the output relays to operate including the tripping output relays.
Therefore, the test must be performed with tripping circuits disconnected.

6.5.1

Measuring Element
Measuring element characteristics are realized by software, so it is possible to verify the overall
characteristics by checking representative points.
Operation of the element under test is observed by the binary output signal at monitoring jacks A
or B or by the LED indications above the jacks. In any case, the signal number corresponding to
each element output must be set on the "Logic circuit" screen of the "Test" sub-menu.
/ 2

L o g i c
c i r c u i t
T e r m A
1
_
T e r m B
4 8
_

When a signal number is entered for the Term A line, the signal is observed at monitoring jack A
and when entered for the Term B line, it is observed at monitoring jack B.
Note:

The voltage level at the monitoring jacks is +5V for logic level "1" and less than 0.1V for
logic level "0".

CAUTION

Use test equipment with more than 1 k of internal impedance when observing the output
signal at the monitoring jacks.
Do not apply an external voltage to the monitoring jacks.
Do not leave the A or B terminal shorted to 0V terminal for a long time.

In case of a three-phase element, it is sufficient to test for a representative phase. The A-phase
element is selected hereafter. Further, the [APPL-CT] and [APPL-VT] settings are selected 3P
and 3PV.
Note: Operating time test of measuring relay elements at monitoring jack A or B is not
including the operation of binary output. Whole the operating time test, if required,
should be measured at a binary output relay.

190

6 F 2 S 0 7 5 8
6.5.1.1

Overcurrent and undercurrent element OC1 to OC4, UC1, UC2 and CBF and Earth fault
element EF1 to EF4 and SEF1 to SEF4

The overcurrent element is checked on the operating current value and operating time for IDMT
curve.
Operating current check

Figure 6.5.1 shows a testing circuit. The operating current value is checked by increasing or
decreasing the magnitude of the current applied.
GRD140
+
Single-phase
current
source

TB1 -(*)

-(*)

Monitoring
jack
DC
power
supply

TB2 -A9

-B9

A
0V

DC
voltmeter

+
0V
(): Connect the terminal number corresponding to the testing element. Refer to Table 3.2.1.

Figure 6.5.1 Operating Current Value Test

The output signal of testing element is assigned to the monitoring jack A.


The output signal numbers of the elements are as follows:
Element

Signal No.

Element

Signal No.

Element

Signal No.

Element

Signal No.

OC1-A

101

EF1

131

SEF1

141

UC1-A

161

OC2-A

107

EF2

133

SEF2

143

UC2-A

164

OC3-A

113

EF3

135

SEF3

145

CBF-A

173

OC4-A

116

EF4

136

SEF4

146

Enter the signal number to observe the operation at the LED as shown in Section 6.5.1 and
press the ENTER key.
Set the scheme switches [-DIR] to NON.
Apply a test current and change the magnitude of the current applied and measure the value
at which the element operates.
Check that the measured value is within 5% of the setting value.

191

6 F 2 S 0 7 5 8
Operating time check for IDMT curve

The testing circuit is shown in Figure 6.5.2.


GRD140
A

Single-phase
current
source

TB1 ()
- ()

Monitoring
jack
DC
power
supply

TB2 -A9

-B9

A
0V

E
Start
Time
counter
Stop
OV
(): Connect the terminal number corresponding to the testing element. Refer to Table 3.2.1.

Figure 6.5.2 Testing IDMT

One of the inverse time characteristics can be set, and the output signal numbers of the IDMT
elements are as follows:
Element

Signal No.

OC1-A

101

EF1

131

SEF1

141

Fix the time characteristic to test by setting the scheme switch MOC1, MEF1 or MSE1 on the
"OC", "EF" or "SEF" screen.
Example: "Settings" sub-menu "Protection" screen "Group" screen "OC" screen
The test procedure is as follows:

Enter the signal number to observe the operating time at the monitoring jack A as shown in
Section 6.5.1.

Apply a test current and measure the operating time. The magnitude of the test current should
be between 1.2 Is to 20 Is, where Is is the current setting.

Calculate the theoretical operating time using the characteristic equations shown in Section
2.1.1. Check that the measured operating time is within IEC 60255-3 class 5.

192

6 F 2 S 0 7 5 8
6.5.1.2

Directional characteristic test

The directional characteristic is checked as follows:


OC element for Models 400, 430 and 420

The test circuit is shown in Figure 6.5.3.


GRD140-400 and -420

TB2 -A1

Va

-B1

Vb

-A2

Vc

-B2

a
Three-phase
voltage
b
source

Monitoring
jack

Single-phase
current
source

DC
power
supply

TB1 -1

A
0V

Ia

-2

TB2 -A9

-B9
(E)

DC
voltmeter

Figure 6.5.3 Testing OC Element

OC elements and their output signal number are shown in Section 6.5.1.1.
The following shows the case when testing OC1.
Select "Logic circuit" on the Test screen to display the "Logic circuit" screen.
Enter the signal number to be observed at monitoring jack as shown in Section 6.5.1.
Set the scheme switch [OC1-DIR] to FWD.
Apply three-phase rated voltage and single-phase test current IT (= Ia).
Set IT to lag Vbc by OC characteristic angle OC . (The default setting of OC is -45.)
Changing the magnitude of IT while retaining the phase angle with the voltages, and measure
the current at which the element operates. Check that the measured current magnitude is within
5% of the current setting.
EF element

The test circuit is shown in Figure 6.5.4.

193

6 F 2 S 0 7 5 8
GRD140

TB1 or TB2

-(*)
Residual voltage

Single-phase
voltage
source

-(*)
Monitoring
jack

Single-phase
current
source

DC
power
supply

TB1 -(*)

Ie or Ise

A
0V

-(*)

TB2 -A9

-B9
E

DC
voltmeter
Note: Connect the terminal number of residual voltage input and residual current
input or zero sequence current input for SEF as shown in Table 3.2.1.

Figure 6.5.4

Testing EF and SEF Elements

EF elements and their output signal number are shown in Section 6.5.1.1.
The following shows the case when testing EF1.
Select Logic circuit on the Test menu screen to display the Logic circuit screen.
Enter the signal number to be observed at monitoring jack A as shown in Section 6.5.1.
Set the scheme switch [EF1-DIR] to FWD.
Apply the rated voltage VT (= V0) and single-phase test current IT.
Set IT to lag V0 by EF characteristic angle EF . (The default setting of EF is -45.)
Changing the magnitude of IT while retaining the phase angle with the voltages, and measure
the current at which the element operates. Check that the measured current magnitude is within
5% of the current setting.
SEF element

The test circuit is shown in Figure 6.5.4.


SEF elements and their output signal number are shown in Section 6.5.1.1.
The following shows the case when testing SEF1.
Select Logic circuit on the Test menu screen to display the Logic circuit screen.
Enter the signal number to be observed at monitoring jack A as shown in Section 6.5.1.
Set the scheme switch [SE1-DIR] to FWD.
Apply the rated voltage VT (= V0) and single-phase test current IT (= Ise).
Set IT to lag V0 by SEF characteristic angle SE . (The default setting of SE is 0.)
Changing the magnitude of IT while retaining the phase angle with the voltages, and measure
the current at which the element operates. Check that the measured current magnitude is within
5% of the current setting.

194

6 F 2 S 0 7 5 8
6.5.1.3

Thermal overload element THM-A and THM-T

The testing circuit is same as the circuit shown in Figure 6.5.2.


The output signal of testing element is assigned to the monitoring jack A.
The output signal numbers of the elements are as follows:
Element

Signal No.

THM-A

167

THM-T

168

To test easily the thermal overload element, the scheme switch [THMRST] in the "Switch" screen
on the "Test" menu is used.
Set the scheme switch [THMRST] to "ON".
Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Apply a test current and measure the operating time. The magnitude of the test current
should be between 1.2 Is to 10 Is, where Is is the current setting.

CAUTION
After the setting of a test current, apply the test current after checking that the THM% has
become 0 on the "Metering" screen.
Calculate the theoretical operating time using the characteristic equations shown in Section
2.1.5. Check that the measured operating time is within 5%.
6.5.1.4

Negative sequence overcurrent element NOC1 and NOC2

The testing circuit is shown in Figure 6.5.5.


The output signal of testing element is assigned to the monitoring jack A.
The output signal numbers of the elements are as follows:
Element

Signal No.

NOC1

169

NOC2

171

Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Apply the three-phase balance current and the operating current value is checked by
increasing the magnitude of the current applied.

Check that the measured value is within 5% of the setting value.

195

6 F 2 S 0 7 5 8
GRD140
Ia

TB1 -1

-2

Three-phase
Current
source

Ib

-3

-4
Ic

-5

-6

DC
power
supply

TB2 -A9

-B9

Monitoring
jack

A
0V

E
DC
voltmeter

+
0V

Figure 6.5.5 Testing NOC elements

Directional characteristic test of NOC element

The test circuit is shown in Figure 6.5.6.


GRD140

Va

TB2 -A1

Vb

Three-phase
voltage
source

-B1

Vc

-A2
-B2
Monitoring
jack

Ia

TB1 -1

-3

A
0V

-2

Three-phase
Current
source

Ib
Ic

-4
-5

-6

DC
power
supply

TB2 -A9

-B9
E

DC
voltmeter

Figure 6.5.6 Testing Directional Characteristic of NOC Element

The following shows the case when testing NOC1.


Select "Logic circuit" on the Test screen to display the "Logic circuit" screen.
Enter the signal number to be observed at monitoring jack as shown in Section 6.5.1.

196

6 F 2 S 0 7 5 8
Set the scheme switch [NC1-DIR] to FWD.
Apply three-phase balance voltage (=30V) and three-phase balance current.
Set Ia to lag Va by NOC characteristic angle NC . (The default setting of NC is -45.)

Changing the magnitude of three-phase balance current while retaining the phase angle with
the voltages, and measure the current Ia at which the element operates. Check that the
measured current magnitude is within 5% of the current setting.

6.5.1.5

Broken conductor detection element BCD

The testing circuit is shown in Figure 6.5.7.


GRD140
Ia
Three-phase
Current
source

TB1 -1

-2
Ib

-3

-4
Ic

-5

-6
Monitoring
jack

DC
power
supply

TB2 -A9

-B9

A
0V

E
DC
voltmeter

+
0V

Figure 6.5.7 Testing BCD element

The output signal of testing element is assigned to the monitoring jack A.


The output signal numbers of the elements are as follows:
Element
BCD

Signal No.
172

Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Apply the three-phase balance current at 10% of the rated current and interrupt a phase
current.

Then, check the BCD element operates.


6.5.1.6

Cold load protection

The testing circuit is same as the circuit shown in Figure 6.5.1.


To check the cold load protection function, the scheme switch [CLPTST] in the "Switch" screen
on the "Test" menu is used. Test the item of OC1 shown in Section 6.5.1.1.
Set the scheme switch [CLPTST] to "S0".

Check that the OC1 operates at the setting value of normal setting group.
Next, set the scheme switch [CLPTST] to "S3".

197

6 F 2 S 0 7 5 8
Check that the OC1 operates at the setting value of cold load setting group [CLSG].
6.5.1.7

Overvoltage and undervoltage elements

The testing circuit is shown in Figure 6.5.8.


GRD140
+

Variable-

TB2

Voltage source

DC
power
supply

-(*)
-(*)

TB2 -A9

-B9

Monitoring
jack

A
0V

E
DC
voltmeter

+
0V
(): Connect the terminal number corresponding to the testing element. Refer to Table 3.2.1.

Figure 6.5.8 Operating Value Test Circuit

The output signal of testing element is assigned to the monitoring jack A.


Overvoltage and undervoltage elements and their output signal number are listed below.
Element

Signal No.

OV1-A
OV2-A
UV1-A
UV2-A
ZOV1
ZOV2

191
197
201
207
211
213

Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Operating value test of OV1, OV2, ZOV1, ZOV2
Apply a rated voltage as shown in Figure 6.5.8.
Increase the voltage and measure the value at which the element operates. Check that the
measured value is within 5% of the setting.
Operating value test of UV1, UV2
Apply a rated voltage and frequency as shown Figure 6.5.8.
Decrease the voltage and measure the value at which the element operates. Check that the
measured value is within 5% of the setting.
Operating time check of OV1, UV1, ZOV1 IDMT curves
Change the voltage from the rated voltage to the test voltage quickly and measure the
operating time.
Calculate the theoretical operating time using the characteristic equations shown in Section
2.2.1 and 2.2.2. Check the measured operating time.

198

6 F 2 S 0 7 5 8
6.5.1.8

Negative sequence overvoltage element NOV1 and NOV2

The testing circuit is shown in Figure 6.5.9.


GRD140
Va
Three-phase
Voltage
source

TB2 -A1

Vb

-B1

Vc
VN

-A2
-B2
Monitoring
jack

DC
power
supply

TB2 -A9

-B9

A
0V

DC
voltmeter

+
0V

Figure 6.5.9 Testing NOV elements

The output signal of testing element is assigned to the monitoring jack A.


The output signal numbers of the elements are as follows:
Element

Signal No.

NOV1

214

NOV2

216

Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Apply the three-phase balance voltage and the operating voltage value is checked by
increasing the magnitude of the voltage applied.

Check that the measured value is within 5% of the setting value.


Operating time check of NOV1 IDMT curve
Change the voltage from the rated voltage to the test voltage quickly and measure the
operating time.
Calculate the theoretical operating time using the characteristic equations shown in Section
2.2.4. Check the measured operating time.

199

6 F 2 S 0 7 5 8
6.5.1.9

Frequency Elements

The testing circuit is shown in Figure 6.5.10.


GRD140
+
VariableFrequency /

Voltage source

DC
power
supply

TB2

-A1
-B2

TB2 -A9

-B9

Monitoring
jack

A
0V

DC
voltmeter

Figure 6.5.10 Operating Value Test Circuit

The output signal of testing element is assigned to the monitoring jack A.


Frequency elements and their output signal number are listed below.
Element

Signal No.

FRQ1
FRQ2
FRQ3
FRQ4
FRQBLK

218
219
220
221
222

Overfrequency or underfrequency elements FRQ1 to FRQ4


Enter the signal number to observe the operation at the monitoring jack A as shown in
Section 6.5.1.
Apply a rated voltage and frequency as shown in Figure 6.5.10.

In case of overfrequency characteristic,


Increase the frequency and measure the value at which the element operates. Check that the
measured value is within 0.005Hz of the setting.

In case of underfrequency characteristics,


Decrease the frequency and measure the value at which the element operates. Check that
the measured value is within 0.005Hz of the setting.
Undervoltage block test, FRQBLK
Apply a rated voltage and change the magnitude of frequency to operate an element.
Keep the frequency that the element is operating, and change the magnitude of the voltage
applied from the rated voltage to less than FRQBLK setting voltage. And then, check that
the element resets.

200

6 F 2 S 0 7 5 8
6.5.2

Protection Scheme
In the protection scheme tests, a dynamic test set is required to simulate power system pre-fault,
fault and post-fault conditions.
Tripping is observed with the tripping command output relays after a simulated fault occurs.
Circuit Breaker failure tripping
Set the scheme switch [BTC] to "ON" and [RTC] to "DIR" or "OC".
Apply a fault, retain it and input an external trip signal. Check that the retrip output relays
operate after the time setting of the TRTC and the adjacent breaker tripping output relay
operates after the time setting of the TBTC.

6.5.3

Metering and Recording


The metering function can be checked while testing the AC input circuit. See Section 6.4.4.
Fault recording can be checked while testing the protection schemes. Open the "Fault record"
screen and check that the descriptions are correct for the fault concerned.
Recording events are listed in Appendix D. There are internal events and external events by binary
input commands. Event recording on the external event can be checked by changing the status of
binary input command signals. Change the status in the same way as the binary input circuit test
(see Section 6.4.2) and check that the description displayed on the "Event record" screen is
correct. Some of the internal events can be checked in the protection scheme tests.
Disturbance recording can be checked while testing the protection schemes. The LCD display
only shows the date and time when a disturbance is recorded. Open the "Disturbance record"
screen and check that the descriptions are correct.
Details can be displayed on the PC. Check that the descriptions on the PC are correct. For details
on how to obtain disturbance records on the PC, see the RSM100 Manual.

201

6 F 2 S 0 7 5 8

6.6

Conjunctive Tests
6.6.1

On Load Test
To check the polarity of the current and voltage transformers, check the load current, system
voltage and their phase angle with the metering displays on the LCD screen.
Open the "Auto-supervision" screen check that no message appears.
Open the following "Metering" screen from the "Status" sub-menu to check the above. (See
Section 4.2.4.1.)

/ 3
I a
I b
I c
I e
I s e
I 1
I 2
I 2 /
T H M
V a n
V b n
V c n
V e
V a b
V b c
V c a
V 0
V 1
V 2
f
P F
P
Q
S
Wh +
Wh

C u r r e

I 1

- .
-
-
-

t
.

.
.
.

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.

Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.

k A

k A

Not available for models 400 and 430.


Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.
Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.
Not available for model 110 and APPL-CT=1P and 2P settings in models 400 and 420.

%
k V

k V

k V

k V

k V

k V

k V

k V

k V

k V

H z

Not available for model 110 and APPL-CT=1P setting in models 400 and 420.
Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.
Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.
Not available for model 110 and APPL-VT=3P and 2P settings in model 4xx.

Not available for model 110.


Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110.
Not available for model 110. Total 3 phase power factor.

k W
k v a r
k V A

Not available for model 110. Total 3 phase active power.


Not available for model 110. Total 3 phase reactive power.
Not available for model 110. Total 3 phase apparent power.
Not available for model 110. Figure over times (999).

k Wh
Not available for model 110. Figure over times (999).

k Wh

202

6 F 2 S 0 7 5 8
v a h +
v a h

k v a h

k v a h

Not available for model 110. Figure over times (999).


Not available for model 110. Figure over times (999).

Note: The magnitude of current can be set in values on the primary side or on the secondary side by
the setting. (The default setting is the secondary side.)

Directional check of Directional phase overcurrent element

The rightness of the polarity of directional phase overcurrent element is verified if current and
voltage values and their phase angle are all right in above metering check. Further, it can be also
checked as follows:
Select Direction on the Metering screen to display Direction screen, and then the
direction of current is displayed. (See Section 4.2.4.1.) Check the direction of current is
correct.
Note: Not available for models 110 and APPL-CT=1P and 2P settings in models 400, 420 and 430.

Directional check of Directional earth fault element

The rightness of the polarity of directional earth fault element is verified if current and voltage
values and their phase angle are all right in above metering check. Further, if required, it can be
also checked as follows:
Check the operation of this element by simulating the unbalanced condition of three phase
voltages and currents.
Note: Not available for APPL-CT=1P and 2P settings in models 400, 420 and 430.

CAUTION: Must block the tripping circuit while checking by simulating the unbalanced
condition. After checking, must return the connections to their original state.

6.6.2

Tripping and Reclosing Circuit Test


The tripping circuit including the circuit breaker is checked by forcibly operating the output relay
and monitoring the circuit breaker to confirm that it is tripped. Forcible operation of the output
relay is performed on the "Binary O/P " screen of the "Test" sub-menu as described in Section
6.4.3.
Tripping circuit
Set the breaker to be closed.
Select "Binary O/P" on the "Test" sub-menu screen to display the "Binary O/P" screen.
/ 2
B
D
B
D
B
D
B
D
B
D
B

O
i
O
i
O
i
O
i
O
i
O

B i n a r y
1
s
2
s
3
s
4
s
5
s
6

O / P

0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0
a b l e / E n a b
0

203

_
l e
l e
l e
l e
l e

6 F 2 S 0 7 5 8
D i s a b l e / E n a b l e
B O 7
0
D i s a b l e / E n a b l e

BO1 to BO7 are output relays with one normally open contact.
Enter 1 for BO1 and press the ENTER key.
Press the END key. Then the LCD displays the screen shown below.
O p e r a t e ?
E N T E R = Y
C A N C E L = N

Keep pressing the ENTER key to operate the output relay BO1 and check that the A-phase
breaker is tripped.
Stop pressing the ENTER key to reset the operation.
Repeat the above for BO2 to BO7.
Reclosing circuit
Ensure that the circuit breaker is open.
Select "Binary O/P" on the "Test" sub-menu screen to display the "Binary O/P" screen.
Select the BO number which is an autoreclose command output relay with one normally open
contact.
Note: The autoreclose command is assigned to any of the output relays by the user setting

Operate the BO by the same manner as above.

204

6 F 2 S 0 7 5 8

6.7

Maintenance
6.7.1

Regular Testing
The relay is almost completely self-supervised. The circuits that can not be supervised are binary
input and output circuits and human interfaces.
Therefore, regular testing is minimised to checking the unsupervised circuits. The test procedures
are the same as described in Sections 6.4.1, 6.4.2 and 6.4.3.

6.7.2

Failure Tracing and Repair


Failures will be detected by automatic supervision or regular testing.
When a failure is detected by supervision, a remote alarm is issued with the binary output relay of
FAIL and the failure is indicated on the front panel with LED indicators or LCD display. It is also
recorded in the event record.
Failures detected by supervision are traced by checking the "Err: " screen on the LCD. Table 6.7.1
shows LCD messages and failure locations.
The locations marked with (1) have a higher probability than locations marked with (2).
Table 6.7.1 LCD Message and Failure Location
Message

Failure location
Relay Unit

AC cable

Err: SUM

(Flash memory)

Err: RAM

(SRAM)

Err: BRAM

(Backup RAM)

Err: EEP

(EEPROM)

Err: A/D

(A/D converter)

Err: DC

(DC power supply circuit)

Err: TC

(Tripping circuit)(1)

Err: CT, Err: V0, Err: V2

(AC input circuit)(1)

Err: CB

(Circuit breaker)(1)

Err: CTF

(AC input circuit)(2)

(1)

Err: VTF1, Err: VTF2

(AC input circuit)(2)

(1)

CB or cable

(2)
(2)
(2)

( ): Probable failure location in the relay unit including its peripheral circuits.
If no message is shown on the LCD, this means that the failure location is either in the DC power
supply circuit or in the microprocessors. If the "ALARM" LED is off, the failure is in the DC
power supply circuit. If the LED is lit, the failure is in the microprocessors. Replace the relay unit
in both cases after checking if the correct DC voltage is applied to the relay.
If a failure is detected by automatic supervision or regular testing, replace the failed relay unit.
Note: When a failure or an abnormality is detected during the regular test, confirm the following
first:
- Test circuit connections are correct.
- Modules are securely inserted in position.
- Correct DC power voltage is applied.

205

6 F 2 S 0 7 5 8
- Correct AC inputs are applied.
- Test procedures comply with those stated in the manual.

6.7.3

Replacing Failed Relay Unit


If the failure is identified to be in the relay unit and the user has a spare relay unit, the user can
recover the protection by replacing the failed relay unit.
Repair at the site should be limited to relay unit replacement. Maintenance at the component level
is not recommended.
Check that the replacement relay unit has an identical Model Number and relay version (software
type form) as the removed relay.
The Model Number is indicated on the front of the relay. For the relay version, see Section 4.2.5.1.
Replacing the relay unit

CAUTION

After replacing the relay unit, check the settings.

The procedure of relay withdrawal and insertion is as follows:


Switch off the DC power supply.

WARNING Hazardous voltage may remain in the DC circuit just after switching off the
DC power supply. It takes about 30 seconds for the voltage to discharge.

Disconnect the trip outputs.


Short-circuit all AC current inputs. Open all AC voltage inputs.
Unscrew the relay front cover.
Unscrew the binding screw on the handle.
To remove the relay unit from its case, pull up the handle and pull the handle towards you. (See
Figure 6.7.1.)
Insert the (spare) relay unit in the reverse procedure.

CAUTION

To avoid risk of damage:


Keep the handle up when inserting the relay unit into the case.
Do not catch the handle when carrying the relay unit.
Check that the relay unit and its case have the identical Model Number
when inserting the relay unit.

206

6 F 2 S 0 7 5 8

IN SERVICE VIEW
TRIP
ALARM

IN SERVICE VIEW
TRIP
ALARM

RESET

RESET

0V CAN ENTER
CEL

END

0V CAN ENTER
CEL

END

Handle

Pull up handle

Bind screw

Figure 6.7.1 Handle of Relay Unit

6.7.4

Resumption of Service
After replacing the failed relay unit or repairing failed external circuits, take the following
procedures to restore the relay to the service.
Switch on the DC power supply and confirm that the "IN SERVICE" green LED is lit and the
"ALARM" red LED is not lit.
Supply the AC inputs and reconnect the trip outputs.

6.7.5

Storage
The spare relay should be stored in a dry and clean room. Based on IEC Standard 60255-6 the
storage temperature should be 25C to +70C, but the temperature of 0C to +40C is
recommended for long-term storage.

207

6 F 2 S 0 7 5 8

7. Putting Relay into Service


The following procedure must be adhered to when putting the relay into service after finishing the
commissioning tests or maintenance tests.
Check that all the external connections are correct.
Check the settings of all measuring elements, timers, scheme switches, recordings and clock
are correct.

In particular, when settings are changed temporarily for testing, be sure to restore them.
Clear any unnecessary records on faults, alarms, events, disturbances and counters which are
recorded during the tests.
Press the VIEW key and check that no failure message is displayed on the "Alarm view"
screen.
Check that the green "IN SERVICE" LED is lit and no other LEDs are lit on the front panel.

208

6 F 2 S 0 7 5 8

Appendix A
Programmable Reset Characteristics
and Implementation of Thermal Model
to IEC60255-8

209

6 F 2 S 0 7 5 8

Programmable Reset Characteristics


The overcurrent stages for phase and earth faults, OC1 and EF1, each have a programmable reset
feature. Resetting may be instantaneous, definite time delayed, or, in the case of IEEE/US curves,
inverse time delayed.
Instantaneous resetting is normally applied in multi-shot auto-reclosing schemes, to ensure correct
grading between relays at various points in the scheme. On the other hand, the inverse reset
characteristic is particularly useful to provide correct co-ordination with an upstream induction disc type
overcurrent relay.
The definite time delayed reset characteristic may be used to provide faster clearance of intermittent
(pecking or flashing) fault conditions. An example of where such phenomena may be experienced is
in plastic insulated cables, where the fault energy melts the cable insulation and temporarily
extinguishes the fault, after which the insulation again breaks down and the process repeats.
An inverse time overcurrent protection with instantaneous resetting cannot detect this condition until the
fault becomes permanent, thereby allowing a succession of such breakdowns to occur, with associated
damage to plant and danger to personnel. If a definite time reset delay of, for example, 60 seconds is
applied, on the other hand, the inverse time element does not reset immediately after each successive
fault occurrence. Instead, with each new fault inception, it continues to integrate from the point reached
during the previous breakdown, and therefore operates before the condition becomes permanent. Figure
A-1 illustrates this theory.
Intermittent
Fault Condition
TRIP LEVEL

Inverse Time Relay


with Instantaneous
Reset
RX
RX

Inverse Time Relay


with Definite Time
Reset
Delayed Reset

Figure A-1

210

6 F 2 S 0 7 5 8

Implementation of Thermal Model to IEC60255-8


Heating by overload current and cooling by dissipation of an electrical system follow exponential time
constants. The thermal characteristics of the electrical system can be shown by equation (1).
=

t
I2
1 e 100%
2

I AOL

(1)

where:
= thermal state of the system as a percentage of allowable thermal capacity,
I = applied load current,
IAOL = allowable overload current of the system,
= thermal time constant of the system.
The thermal stateis expressed as a percentage of the thermal capacity of the protected system, where
0% represents the cold state and 100% represents the thermal limit, that is the point at which no further
temperature rise can be safely tolerated and the system should be disconnected. The thermal limit for
any given electrical plant is fixed by the thermal setting IAOL. The relay gives a trip output when =
100%.
If current I is applied to a cold system, then will rise exponentially from 0% to (I2/IAOL2 100%), with time
constant , as in Figure A-2. If = 100%, then the allowable thermal capacity of the system has been reached.

(%)
100%
I2

I AOL

100%
2

= I I 2 1 e
AOL

100 %

t (s)
Figure A-2

A thermal overload protection relay can be designed to model this function, giving tripping times
according to the IEC60255-8 Hot and Cold curves.

I2
t =Ln 2 2
I I AOL

(1)

Cold curve

I2 I 2
t =Ln 2 2P
I I AOL

(2)

Hot curve

where:

211

6 F 2 S 0 7 5 8
IP = prior load current.

In fact, the cold curve is simply a special case of the hot curve where prior load current IP = 0, catering
for the situation where a cold system is switched on to an immediate overload.
Figure A-3 shows a typical thermal profile for a system which initially carries normal load current, and
is then subjected to an overload condition until a trip results, before finally cooling to ambient
temperature.

(%)

Overload Current
Condition

Trip at 100%

100%

Normal Load
Current Condition

Cooling Curve

t (s)

Figure A-3

212

6 F 2 S 0 7 5 8

Appendix B
Directional Earth Fault Protection and
Power System Earthing

213

6 F 2 S 0 7 5 8

Directional Earth Fault Protection and Power System Earthing


Power systems may be solidly earthed, impedance earthed or unearthed (insulated). Depending
on the method used, faults to earth have widely differing characteristics, and so methods of earth
fault protection differ greatly between the various types of system.

1. Solidly earthed systems


In a solidly earthed system the neutral points of the power transformers are connected directly to
earth, for the purposes of reducing overvoltages and facilitating fault detection. The
disadvantage of solid earthing is that fault currents can be very high, and must be disconnected
quickly.
Since the impedance of the source is normally very low, fault current varies greatly in
magnitude depending on the location of the fault. Selective isolation of a faulty section is
therefore possible via time/current graded earth fault overcurrent protection. Fault current is
detected by measuring the system residual current.
On an interconnected system, where fault current can flow in either direction, then directional
earth fault relays are applied. The fault causes a residual voltage to be generated, and this can be
used for directional polarization. Residual current and voltage can be measured as shown in
Figure B-1.
Residual current IR is equal in magnitude and direction to the fault current. It typically lags the
faulted phase voltage by a considerable angle due to the reactance of the source. Directional
control is achieved by polarising against the system residual voltage, which may be found either
by summating the phase voltages, or it may be extracted from the open delta connected
secondary (or tertiary) winding of a five limb VT, as shown in the diagram.
A directional earth fault relay protecting a solidly earthed system is normally connected to
measure VR inverted. If GRD140 is applied to derive residual voltage from the phase voltages
then the inversion of VR is performed internally.
F

51N

67
V an

Prefault
V cn

Ia
n

IR

V an

Post-fault

Earth
n
V bn

V cn

V bn
VR

Figure B-1 Directional Earth Fault Protection for Solidly Earthed Systems

214

6 F 2 S 0 7 5 8
The relay characteristic angle setting is applied to compensate for lag of the fault current.
Generally accepted angle settings are -45 for solidly earthed distribution systems and -60 for
transmission systems.
Due to system imbalances and measuring tolerances, small levels of residual voltage can be
present during normal operating conditions. Therefore, GRD140 provides a voltage threshold
which must be exceeded before the directional protection will operate. Although this threshold is
user programmable, most applications will be satisfied by the default setting of 3V.

2. Unearthed (insulated) systems


An insulated system has no intentional connection to earth, although all systems are in fact
earthed by natural capacitive coupling. Fault current is very low, being made up of capacitive
charging currents, thus limiting damage to plant. However, high steady-state and transient
overvoltages are produced, and selective isolation of faults is difficult.
An earth fault on an ungrounded system causes a voltage shift between the neutral point and
earth, and the fault can be detected by measuring this shift. So called neutral voltage
displacement protection is commonly applied but, unfortunately, the shift in voltage is
essentially the same throughout the system and so this method cannot selectively isolate a
faulted section.
The method of directional earth fault protection described previously for solidly earthed systems
cannot be used in the case of insulated systems because of the absence of real fault current.
However, an alternative method can be applied, using GRD140 directional sensitive earth fault
protection. The relay must be connected using a core balance CT, to measure the flow of
capacitive charging currents, which become unbalanced in the event of a fault.
A phase to earth fault effectively short circuits that phases capacitance to earth for the whole
system, thus creating an unbalance in the charging currents for all feeders connected to the
system. The resulting fault current is made up of the sum of the combined residual charging
currents for both the faulty and healthy feeders.

215

6 F 2 S 0 7 5 8

A
B
C

51N

51N

F
IF
IU2

IU1

-VR

IU3+....
Healthy
feeder

V an

Faulty
feeder

Earth (e)
IR1
Ib

n
V cn

IU2(=IR2)
Ic

IU1

IU1

IF=IU1+IU2+IU3+...
V bn

V an

V cn

n
V bn

Figure B-2 Residual Current Flow in an Unearthed System

It can be shown that the residual current measured in the faulty feeder is 180 out of phase with
that in the healthy feeder, as illustrated in Figure B-2 This fact can be used to apply a GRD140
directional sensitive earth fault relay. The polarising voltage used for directional earth fault
relays is normally -VR (the residual voltage inverted), and it can be seen that the residual current
(IR1) for the faulty feeder leads this voltage by 90. For the healthy feeders the residual current
lags the voltage by 90. Therefore, the GRD140 sensitive earth fault protection should be
applied with a characteristic angle of +90 so as to provide discriminatory protection.
The residual current in the faulted phase is equal to three times the per phase charging current,
and the sensitive earth fault element should be set well below this value to ensure operation
(30% of this value is typical).

3. Impedance earthing
In between the two extremes of solidly earthed and unearthed systems there are a variety of
compromise solutions, which normally involve connecting the system neutrals to earth via a
resistance or reactance.
3a. Resistance earthing
In the case of resistance earthed systems, GRD140 directional earth fault relays can normally be
applied in a similar manner to that for solidly earthed systems, with the exceptions that current
settings will be lower and the characteristic angle setting will probably be different. In the event
of a fault, it is the resistance in the neutral which predominates in the source impedance, and so
the residual current lags its polarising voltage by a much smaller angle. Characteristic angle

216

6 F 2 S 0 7 5 8
settings of -15 or 0 are common.
3b. Reactance earthing
Reactance earthed systems are also common in many countries. A special case of this method is
known as Petersen coil, or resonant, earthing. The inductance in the neutral is chosen to cancel
the total capacitance of the system so that no current flows into an earth fault.
Directional sensitive earth fault protection can again be applied by detecting the unbalance in
charging currents. It can be shown that the residual current distribution for healthy and faulty
feeders is as illustrated in Figure B-3.
In the case of the healthy feeder, the residual current lags the polarising voltage (-VR) by more
than 90, while for the faulty feeder, the angle is less than 90. GRD140 directional sensitive
earth fault protection can be applied, with a 0 characteristic angle. Note that the SEF boundary
of directional operation should be set to 90. The residual current for the healthy feeder then
falls in the restraint zone, while for the faulty feeder it lies in the operate zone, thus providing
selective isolation of the fault.
-V R

-V R

Healthy
feeder

Faulty
feeder

Earth (e)

V an

V an

IR1

Operate Zone
n
V cn

V bn

Restraint Zone
IR2
V cn

n
V bn

Figure B-3 Residual Current Flow in a Resonant Earthed System

3c. Reactance Earthing and Residual Power Control


GRD140 can provide an additional restraint on operation by the (optional) residual power
control feature. The active component of residual power can be calculated as follows:

(PR ) = I R V R cos
where is the phase angle between the residual current (IR) and the polarising voltage (-VR).
It is clear from Figure B-3 that this value will be positive when measured at the faulty feeder and
negative anywhere else. GRD140 directional sensitive earth fault protection can be applied with
a power threshold such that operation is permitted when residual power exceeds the setting and
is in the operate direction.

217

6 F 2 S 0 7 5 8

218

6 F 2 S 0 7 5 8

Appendix C
Signal List

219

6 F 2 S 0 7 5 8
No.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80

Signal Name
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8

COMMAND
COMMAND
COMMAND
COMMAND
COMMAND
COMMAND
COMMAND
COMMAND

SET.GROUP1
SET.GROUP2
SET.GROUP3
SET.GROUP4
OC1 BLOCK
OC2 BLOCK
OC3 BLOCK
OC4 BLOCK
EF1 BLOCK
EF2 BLOCK
EF3 BLOCK
EF4 BLOCK
EF1 PERMIT
EF2 PERMIT
EF3 PERMIT
EF4 PERMIT
SEF1 BLOCK
SEF2 BLOCK
SEF3 BLOCK
SEF4 BLOCK
UC1 BLOCK
UC2 BLOCK
THM BLOCK
THMA BLOCK
NOC1 BLOCK
NOC2 BLOCK
BCD BLOCK
CBF BLOCK
OV1 BLOCK
OV2 BLOCK
UV1 BLOCK
UV2 BLOCK
ZOV1 BLOCK
ZOV2 BLOCK
NOV1 BLOCK
NOV2 BLOCK
FRQ1 BLOCK
FRQ2 BLOCK
FRQ3 BLOCK
FRQ4 BLOCK
ARC BLOCK
ARC READY
ARC INIT
MANUAL CLOSE
ARC N/A
CTF BLOCK
EXT CTF
VTF BLOCK
EXT VTF
TC FAIL
CB CONT OPN
CB CONT CLS
EXT TRIP-3PH
EXT TRIP-APH
EXT TRIP-BPH
EXT TRIP-CPH
REMOTE RESET
SYNC CLOCK
STORE RECORD
ALARM1

Contents
Not in use
Binary input signal
Binary input signal
Binary input signal
Binary input signal
Binary input signal
Binary input signal
Binary input signal
Binary input signal

of BI1
of BI2
of BI3
of BI4
of BI5
of BI6
of BI7
of BI8

BI command of change active setting group1


BI command of change active setting group2
BI command of change active setting group3
BI command of change active setting group4
BI command of OC1 protection scheme block
BI command of OC2 protection scheme block
BI command of OC3 protection scheme block
BI command of OC4 protection scheme block
BI command of EF1 protection scheme block
BI command of EF2 protection scheme block
BI command of EF3 protection scheme block
BI command of EF4 protection scheme block
BI command of EF1 protection scheme permission
BI command of EF2 protection scheme permission
BI command of EF3 protection scheme permission
BI command of EF4 protection scheme permission
BI command of SEF1 protection scheme block
BI command of SEF2 protection scheme block
BI command of SEF3 protection scheme block
BI command of SEF4 protection scheme block
BI command of UC1 protection scheme block
BI command of UC2 protection scheme block
BI command of Thermal overload protection scheme block
BI command of Thermal overload alarm scheme block
BI command of NOC1 protection scheme block
BI command of NOC2 protection scheme block
BI command of Broken Conductor protection scheme block
BI command of CBF protection scheme block
BI command of OV1 protection scheme block
BI command of OV2 protection scheme block
BI command of UV1 protection scheme block
BI command of UV2 protection scheme block
BI command of ZOV1 protection scheme block
BI command of ZOV2 protection scheme block
BI command of NOV1 protection scheme block
BI command of NOV2 protection scheme block
BI command of FRQ1 protection scheme block
BI command of FRQ2 protection scheme block
BI command of FRQ3 protection scheme block
BI command of FRQ4 protection scheme block
BI command of ARC scheme block
BI command of ARC ready
BI command of ARC initiation
BI command of Manual close
BI command of ARC not applied
BI command of CTF blocking
BI command of External CTF
BI command of VTF blocking
BI command of External VTF
BI command of Trip circuit Fail Alarm
BI command of CB N/O contact
BI command of CB N/C contact
BI command of External trip (3 Phase)
BI command of External trip (A Phase)
BI command of External trip (B Phase)
BI command of External trip (C Phase)
BI command of Remote reset
BI command of Synchronise Clock
BI command of Store Disturbance Record
BI command of Alarm1

220

6 F 2 S 0 7 5 8
No.
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160

Signal Name
ALARM2
ALARM3
ALARM4

Contents
BI command of Alarm2
BI command of Alarm3
BI command of Alarm4

OC1-A
OC1-B
OC1-C
OC1-A INST
OC1-B INST
OC1-C INST
OC2-A
OC2-B
OC2-C

OC1-A relay element output


OC1-B relay element output
OC1-C relay element output
OC1-A relay element start
OC1-B relay element start
OC1-C relay element start
OC2-A relay element output
OC2-B relay element output
OC2-C relay element output

OC3-A
OC3-B
OC3-C
OC4-A
OC4-B
OC4-C
OC1-A HS
OC1-B HS
OC1-C HS
OC1 INST

OC3-A relay element output


OC3-B relay element output
OC3-C relay element output
OC4-A relay element output
OC4-B relay element output
OC4-C relay element output
High speed output of OC1-A relay
High speed output of OC1-B relay
High speed output of OC1-C relay
OC1 relay element start (OR Logic of No. 104, 105 and 106)

EF1
EF1 INST
EF2

EF1 relay element output


EF1 relay element start
EF2 relay element output

EF3
EF4
CUR-REV DET.
EF1 HS

EF3 relay element output


EF4 relay element output
Current reversal detection.
High speed output of EF1 relay

SEF1
SEF1 INST
SEF2

SEF1 relay element output


SEF1 relay element start
SEF2 relay element output

SEF3
SEF4
SEF1 HS
RPF
RPR

SEF3 relay element output


SEF4 relay element output
High speed output of SEF1 relay
Residual power forward element
Residual power reverse element

221

6 F 2 S 0 7 5 8
No.
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240

Signal Name
UC1-A
UC1-B
UC1-C
UC2-A
UC2-B
UC2-C
THM-A
THM-T
NOC1

Contents
UC1-A relay element output
UC1-B relay element output
UC1-C relay element output
UC2-A relay element output
UC2-B relay element output
UC2-C relay element output
THERMAL Alarm relay element output
THERMAL Trip relay element output
NOC1 relay element output

NOC2
BCD
CBF-A
CBF-B
CBF-C
ICLDO-A
ICLDO-B
ICLDO-C
OC-A DIST
OC-B DIST
OC-C DIST
EF DIST
SEF DIST
NOC DIST

NOC2 relay element output


BCD relay element output
CBF-A relay element output
CBF-B relay element output
CBF-C relay element output
ICLDO-A relay (OC relay) element output used in "CLP scheme"
ICLDO-B relay (OC relay) element output used in "CLP scheme"
ICLDO-C relay (OC relay) element output used in "CLP scheme"
OC-A relay for disturbance record
OC-B relay for disturbance record
OC-C relay for disturbance record
EF relay for disturbance record
SEF relay for disturbance record
NOC relay for disturbance record

OV1-A
OV1-B
OV1-C
OV1-A INST
OV1-B INST
OV1-C INST
OV2-A
OV2-B
OV2-C

OV1-1 relay element output


OV1-2 relay element output
OV1-3 relay element output
OV1-1 relay element start
OV1-2 relay element start
OV1-3 relay element start
OV2-1 relay element output
OV2-2 relay element output
OV2-3 relay element output

UV1-A
UV1-B
UV1-C
UV1-A INST
UV1-B INST
UV1-C INST
UV2-A
UV2-B
UV2-C

UV1-1 relay element output


UV1-2 relay element output
UV1-3 relay element output
UV1-1 relay element start
UV1-2 relay element start
UV1-3 relay element start
UV2-1 relay element output
UV2-2 relay element output
UV2-3 relay element output

ZOV1
ZOV1 INST
ZOV2
NOV1
NOV1 INST
NOV2
UVBLK
FRQ1
FRQ2
FRQ3
FRQ4
FRQBLK

ZOV1 relay element ouput


ZOV1 relay element start
ZOV2 relay element ouput
NOV1 relay element ouput
NOV1 relay element start
NOV2 relay element ouput
UV blocked element operating
FRQ1 relay element ouput
FRQ2 relay element ouput
FRQ3 relay element ouput
FRQ4 relay element ouput
FRQ blocked element operating

EFCF
ZOVCF
UVVF-A
UVVF-B
UVVF-C
UVVF-OR
OCDVF-A
OCDVF-B
OCDVF-C
OCDVF-OR

EF element for CTF detection


ZOV element for CTF detection
UV-A element for VTF detection
UV-B element for VTF detection
UV-C element for VTF detection
UV-OR element for VTF detection
OCD-A element for VTF detection
OCD-B element for VTF detection
OCD-C element for VTF detection
OCD-OR element for VTF detection

222

6 F 2 S 0 7 5 8
No.
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320

Signal Name
ZOVVF
EFVF
OC COORD-A
OC COORD-B
OC COORD-C
EF COORD
SEF COORD
ZOV DIST
NOV DIST
OV-A DIST
OV-B DIST
OV-C DIST
UV-A DIST
UV-B DIST
UV-C DIST

Contents
ZOV element for VTF detection
EF element for VTF detection
OC-A coordination element
OC-B coordination element
OC-C coordination element
EF coordination element
SEF coordination element
ZOV relay for disturbance record
NOV relay for disturbance record
OV-A relay for disturbance record
OV-B relay for disturbance record
OV-C relay for disturbance record
UV-A relay for disturbance record
UV-B relay for disturbance record
UV-C relay for disturbance record
(NOT USED, reserved for disturbance record)

OC1 TRIP
OC1-A TRIP
OC1-B TRIP
OC1-C TRIP
OC2 TRIP
OC2-A TRIP
OC2-B TRIP
OC2-C TRIP
OC3 TRIP
OC3-A TRIP
OC3-B TRIP
OC3-C TRIP
OC4 ALARM
OC4-A ALARM
OC4-B ALARM
OC4-C ALARM

OC1 trip command


OC1 trip command (A Phase)
OC1 trip command (B Phase)
OC1 trip command (C Phase)
OC2 trip command
OC2 trip command (A Phase)
OC2 trip command (B Phase)
OC2 trip command (C Phase)
OC3 trip command
OC3 trip command (A Phase)
OC3 trip command (B Phase)
OC3 trip command (C Phase)
OC4 alarm command
OC4 alarm command (A Phase)
OC4 alarm command (B Phase)
OC4 alarm command (C Phase)

EF1 TRIP
EF2 TRIP
EF3 TRIP
EF4 ALARM
EF1 CARRIER
EF2 CARRIER
EF3 CARRIER
EF4 CARRIER

EF1
EF2
EF3
EF4
EF1
EF2
EF3
EF4

SEF1-S1 TRIP
SEF1-S2 TRIP
SEF2 TRIP
SEF3 TRIP
SEF4 ALARM

SEF1 Stage1 trip command


SEF1 Stage2 trip command
SEF2 trip command
SEF3 trip command
SEF4 alarm command

UC1 TRIP
UC1-A TRIP
UC1-B TRIP
UC1-C TRIP
UC2 ALARM
UC2-A ALARM
UC2-B ALARM
UC2-C ALARM
THM ALARM
THM TRIP
NOC1 TRIP
NOC2 ALARM
BCD TRIP
CBF RETRIP
CBF RETRIP-A
CBF RETRIP-B
CBF RETRIP-C
CBF TRIP
CBF TRIP-A
CBF TRIP-B

UC1 trip command


UC1 trip command (A Phase)
UC1 trip command (B Phase)
UC1 trip command (C Phase)
UC2 alarm command
UC2 alarm command (A Phase)
UC2 alarm command (B Phase)
UC2 alarm command (C Phase)
Thermal alarm command
Thermal trip command
NOC1 trip command
NOC2 alarm command
BCD trip command
CBF retrip command
CBF retrip command(A Phase)
CBF retrip command(B Phase)
CBF retrip command(C Phase)
CBF back trip command
CBF back trip command(A Phase)
CBF back trip command(B Phase)

trip command
trip command
trip command
alarm command
carrier command
carrier command
carrier command
carrier command

223

6 F 2 S 0 7 5 8
No.
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400

Signal Name
CBF TRIP-C

Contents
CBF back trip command(C Phase)

OV1 TRIP
OV1-A TRIP
OV1-B TRIP
OV1-C TRIP
OV2 ALARM
OV2-A ALARM
OV2-B ALARM
OV2-C ALARM

OV1 trip command


OV1 trip command(A Phase)
OV1 trip command(B Phase)
OV1 trip command(C Phase)
OV2 alarm command
OV2 alarm command(A Phase)
OV2 alarm command(B Phase)
OV2 alarm command(C Phase)

UV1 TRIP
UV1-A TRIP
UV1-B TRIP
UV1-C TRIP
UV2 ALARM
UV2-A ALARM
UV2-B ALARM
UV2-C ALARM

UV1 trip command


UV1 trip command(A Phase)
UV1 trip command(B Phase)
UV1 trip command(C Phase)
UV2 alarm command
UV2 alarm command(A Phase)
UV2 alarm command(B Phase)
UV2 alarm command(C Phase)

ZOV1 TRIP
ZOV2 ALARM
NOV1 TRIP
NOV2 ALARM
FRQ TRIP
FRQ1 TRIP
FRQ2 TRIP
FRQ3 TRIP
FRQ4 TRIP

ZOV1 trip command


ZOV2 alarm command
NOV1 trip command
NOV2 alarm command
FRQ trip command
FRQ1 trip command
FRQ2 trip command
FRQ3 trip command
FRQ4 trip command

GEN.TRIP
GEN.TRIP-A
GEN.TRIP-B
GEN.TRIP-C
GEN.TRIP-N
CLP STATE0
CLP STATE1
CLP STATE2
CLP STATE3
GEN.ALARM
GEN.ALARM-A
GEN.ALARM-B
GEN.ALARM-C
GEN.ALARM-N
CTF
VTF
VTF1
VTF2

General trip command


General trip command (A Phase)
General trip command (B Phase)
General trip command (C Phase)
General trip command (N Phase)
Cold Load Protection State
Cold Load Protection State
Cold Load Protection State
Cold Load Protection State
General alarm command
General alarm command (A Phase)
General alarm command (B Phase)
General alarm command (C Phase)
General alarm command (N Phase)
CT failure detection
VT failure detection
VT failure detection 1
VT failure detection 2

224

6 F 2 S 0 7 5 8
No.
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480

Signal Name
ARC READY T
ARC IN-PROG
ARC SHOT
ARC SHOT1
ARC SHOT2
ARC SHOT3
ARC SHOT4
ARC SHOT5
ARC FT
ARC SUCCESS
ARC COORD

Contents
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing
Auto-Reclosing

A.M.F.OFF
RELAY FAIL
RELAY FAIL-A
TCSV
CBSV
TC ALARM
SGM I^y ALM
OT ALARM
CT ERR
V0 ERR
V2 ERR
CTF ALARM
VTF1 ALARM
VTF2 ALARM

Automatic monitoring function off


Relay failure & trip blocked alarm
Relay failure alarm (Trip not blocked)
Trip circuit supervision failure
Circuit breaker status monitoring failure
Trip counter alarm
IY alarm
Operate time alarm
CT circuit supervison
VT circuit supervison(V0)
VT circuit supervison(V2)
CT failure detection
VT failure detection 1
VT failure detection 2

F.RECORD CLR
E.RECORD CLR
D.RECORD CLR
TP COUNT CLR
I^y COUNT CLR
AR COUNT CLR
DEMAND CLR
IND.RESET
DATA LOST
SYS.CHANGE
RLY.CHANGE
GRP.CHANGE

Fault record cleared


Event record cleared
Disturbance record cleared
Trip counter cleared
SGM_I^y counter cleared
ARC Counter CLR
Demand cleared
Indication reset
Data lost
System setting changed
Relay setting changed
Group setting changed

BO1 OP
BO2 OP
BO3 OP
BO4 OP
BO5 OP
BO6 OP
BO7 OP

Binary output 1
Binary output 2
Binary output 3
Binary output 4
Binary output 5
Binary output 6
Binary output 7

ready condition
in-progress conditon
shot
shot of number1
shot of number2
shot of number3
shot of number4
shot of number5
failed (Final trip)
succeed
coordination

225

6 F 2 S 0 7 5 8

No.
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500

Signal Name

Contents

LCD IND.
LCD IND1.
LCD IND2.
TESTING
ARC.COM.ON

LCD indication(Virtual LED) command


LCD indication1(Virtual LED) command
LCD indication2(Virtual LED) command
Test LED ON
Auto-recloser command ON

PROT.COM.ON
IECTST
IECBLK

Protection command ON
IEC60870-5-103 test mode
IEC60870-5-103 monitor direction blocked

226

6 F 2 S 0 7 5 8

Appendix D
Event Record Items

227

6 F 2 S 0 7 5 8
Event Record Items
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70

LCD indication
GEN.trip
GEN.alarm
OC1 trip
OC2 trip
OC3 trip
OC4 alarm
EF1 trip
EF2 trip
EF3 trip
EF4 alarm
SEF1-S1 trip
SEF1-S2 trip
SEF2 trip
SEF3 trip
SEF4 alarm
NOC1 trip
NOC2 alarm
UC1 trip
UC2 alarm
THM alarm
THM trip
BCD trip
CBF retrip
CBF trip
OV1 trip
OV2 alarm
UV1 trip
UV2 alarm
ZOV1 trip
ZOV2 alarm
NOV1 trip
NOV2 alarm
FRQ1 trip
FRQ2 trip
FRQ3 trip
FRQ4 trip
ARC READY T
ARC SHOT
ARC IN-PROG
OC1-A
OC1-B
OC1-C
OC2-A
OC2-B
OC2-C
OC3-A
OC3-B
OC3-C
OC4-A
OC4-B
OC4-C
EF1
EF2
EF3
EF4
SEF1
SEF2
SEF3
SEF4
NOC1
NOC2
UC1-A
UC1-B
UC1-C
UC2-A
UC2-B
UC2-C
THM-A
THM
BCD

Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On

Contents
General trip command
General trip command
OC1 trip command
OC2 trip command
OC3 trip command
OC4 alarm command
EF1 trip command
EF2 trip command
EF3 trip command
EF4 alarm command
SEF1 Stage1 trip command
SEF1 Stage2 trip command
SEF2 trip command
SEF3 trip command
SEF4 alarm command
NOC1 trip command
NOC2 alarm command
UC1 trip
UC2 alarm
Thermal alarm command
Thermal trip command
BCD trip command
CBF retrip command
CBF back trip command
OV1 trip command
OV3 alarm command
UV1 trip command
UV3 alarm command
ZOV1 trip command
ZOV2 alarm command
NOV1 trip command
NOV2 alarm command
FRQ1 trip command
FRQ2 trip command
FRQ3 trip command
FRQ4 trip command
Auto-Reclosing ready
Auto-Reclosing shot of number
Auto-Reclosing in progress
OC1-A relay element operating
OC1-B relay element operating
OC1-C relay element operating
OC2-A relay element operating
OC2-B relay element operating
OC2-C relay element operating
OC3-A relay element operating
OC3-B relay element operating
OC3-C relay element operating
OC4-A relay element operating
OC4-B relay element operating
OC4-C relay element operating
EF1 relay element operating
EF2 relay element operating
EF3 relay element operating
EF4 relay element operating
SEF1 relay element operating
SEF2 relay element operating
SEF3 relay element operating
SEF4 relay element operating
NOC1 relay element operating
NOC2 relay element operating
UC1-A relay element operating
UC1-B relay element operating
UC1-C relay element operating
UC2-A relay element operating
UC2-B relay element operating
UC2-C relay element operating
Thermal-Alarm operating
Thermal operating
BCD relay element operating

228

6 F 2 S 0 7 5 8
No.
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140

LCD indication
CLP STATE0
CLP STATE1
CLP STATE2
CLP STATE3
RPF
RPR
OV1-A
OV1-B
OV1-C
OV2-A
OV2-B
OV2-C
UV1-A
UV1-B
UV1-C
UV2-A
UV2-B
UV2-C
UVBLK
ZOV1
ZOV2
NOV1
NOV2
FRQ1
FRQ2
FRQ3
FRQ4
FRQBLK
BI1 command
BI2 command
BI3 command
BI4 command
BI5 command
BI6 command
BI7 command
BI8 command
SET.group1
SET.group2
SET.group3
SET.group4
OC1 block
OC2 block
OC3 block
OC4 block
EF1 block
EF2 block
EF3 block
EF4 block
EF1 permit
EF2 permit
EF3 permit
EF4 permit
SEF1 block
SEF2 block
SEF3 block
SEF4 block
NOC1 block
NOC2 block
UC1 block
UC2 block
THM block
THMA block
CBF block
BCD block
OV1 block
OV2 block
UV1 block
UV2 block
ZOV1 block
ZOV2 block

Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On

Contents
Cold Load Protection State
ditto
ditto
ditto
Residual power forward
Residual Power reverse
OV1-1 relay element operating
OV1-2 relay element operating
OV1-3 relay element operating
OV2-1 relay element operating
OV2-2 relay element operating
OV2-3 relay element operating
UV1-1 relay element operating
UV1-2 relay element operating
UV1-3 relay element operating
UV2-1 relay element operating
UV2-2 relay element operating
UV2-3 relay element operating
UV blocking element operationg
ZOV1 relay element operating
ZOV2 relay element operating
NOC1 relay element operating
NOC2 relay element operating
FRQ1 relay element operating
FRQ2 relay element operating
FRQ3 relay element operating
FRQ4 relay element operating
FRQ blockig element operating
Binary input signal of BI1
Binary input signal of BI2
Binary input signal of BI3
Binary input signal of BI4
Binary input signal of BI5
Binary input signal of BI6
Binary input signal of BI7
Binary input signal of BI8
BI command of change active setting group1
BI command of change active setting group2
BI command of change active setting group3
BI command of change active setting group4
BI command of OC1 protection scheme block
BI command of OC2 protection scheme block
BI command of OC3 protection scheme block
BI command of OC4 protection scheme block
BI command of EF1 protection scheme block
BI command of EF2 protection scheme block
BI command of EF3 protection scheme block
BI command of EF4 protection scheme block
BI command of EF1 protection scheme permission
BI command of EF2 protection scheme permission
BI command of EF3 protection scheme permission
BI command of EF4 protection scheme permission
BI command of SEF1 protection scheme block
BI command of SEF2 protection scheme block
BI command of SEF3 protection scheme block
BI command of SEF4 protection scheme block
BI command of NOC1 protection scheme block
BI command of NOC2 protection scheme block
BI command of UC1 protection scheme block
BI command of UC2 protection scheme block
BI command of Thermal overload protection scheme block
BI command of Thermal overload alarm scheme block
BI command of CBF protection scheme block
BI command of Broken Conductor protection scheme block
BI command of OV1 protection scheme block
BI command of OV2 protection scheme block
BI command of UV1 protection scheme block
BI command of UV2 protection scheme block
BI command of ZOV1 protection scheme block
BI command of ZOV2 protection scheme block

229

6 F 2 S 0 7 5 8
No.
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205

LCD indication
NOV1 block
NOV2 block
FRQ1 block
FRQ2 block
FRQ3 block
FRQ4 block
ARC block
ARC ready
ARC INIT
ARC N/A
Manual CLS
EXT trip-3PH
EXT trip-APH
EXT trip-BPH
EXT trip-CPH
EXT CTF
CTF block
EXT VTF
VTF block
TC fail
CB CONT OPN
CB CONT CLS
Remote reset
Store record
Alarm1
Alarm2
Alarm3
Alarm4
CTF
VTF1
VTF2
Relay fail
Relay fail-A
TC err
CB err
CT err
TP COUNT ALM
V0 err
V2 err
I^yA ALM
I^yA ALM
I^yA ALM
OP time ALM
ARC SHOT1
ARC SHOT2
ARC SHOT3
ARC SHOT4
ARC SHOT5
ARC FT
ARC SUCCESS
ARC RESET
ARC CRD RST
ARC COORD
F.record CLR
E.record CLR
D.record CLR
TP COUNT CLR
I^y CLR
AR COUNT CLR
Demand CLR
IND.reset
Data lost
Sys.change
Rly.change
Grp.change

Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On
On

Contents
BI command of NOV1 protection scheme block
BI command of NOV2 protection scheme block
BI command of FRQ1 protection scheme block
BI command of FRQ2 protection scheme block
BI command of FRQ3 protection scheme block
BI command of FRQ4 protection scheme block
BI command of ARC block
BI command of ARC ready
BI command of ARC initiation
BI command of ARC no action
BI command of ARC initiation
BI command of External trip (3 Phase)
BI command of External trip (A Phase)
BI command of External trip (B Phase)
BI command of External trip (C Phase)
BI command of External CTF
BI command of CTF scheme block
BI command of External VTF
BI command of VTF scheme block
BI command of Trip circuit Fail Alarm
BI command of CB N/O contact
BI command of CB N/C contact
BI command of Remote reset
BI command of Store Disturbance Record
BI command of Alarm1
BI command of Alarm2
BI command of Alarm3
BI command of Alarm4
CTF detection
VTF1 detection
VTF2 detection
Relay failure & trip blocked alarm
Relay failure alarm (Trip not blocked)
Trip circiut supervision failure
Circuit breaker status monitoring failure
CT circuit supervision failure
Trip counter alarm
VT surpervision V0 error
VT supervision V2 error
IY A-phase alarm
IY B-phase alarm
IY C-phase alarm
Operate time alarm
Auto-Reclosing shot of number1
Auto-Reclosing shot of number2
Auto-Reclosing shot of number3
Auto-Reclosing shot of number4
Auto-Reclosing shot of number5
Auto-Reclosing failed (Final trip)
Auto-Reclosing succeed
Auto-Reclosing reset
Auto-Reclosing coordination reset
Auto-Reclosing coordination
Clear Fault records
Clear Event records
Clear Disturbance records
Clear Trip counter
Clear IY counter
Clear Autoreclose counter
Clear demand
Reset the indication of Trip mode,Alarm etc
Record and time date lost bye DC power supply off for a long time
Setting change command
ditto
ditto

230

6 F 2 S 0 7 5 8

Appendix E
Details of Relay Menu and
LCD & Button Operation

231

6 F 2 S 0 7 5 8

MENU
xRecord
xStatus
xSet. (view)
xSet. (change)
xTest
/1 Record
xF. record
xE. record
xD. record
xCounter
/2 F.record
xDisplay

/3 F.record

xClear

#1 16/Jul/2002
18:13:57.031

Refer to Section
4.2.3.1.

Clear records?
END=Y CANCEL=N
/2 E.record
xDisplay

/3 E.record

xClear

16/Jul/2002 480
OC1-A trip On

Refer to Section
4.2.3.2.

Clear records?
END=Y CANCEL=N
/2 D.record
xDisplay

/3 D.record

xClear

#1 16/Jul/2002
18:13:57.401

Refer to Section
4.2.3.3.

Clear records?
END=Y CANCEL=N

a-1 b-1

232

/4 F.record #1
16/Jul/2002

6 F 2 S 0 7 5 8
a-1 b-1

/2 Counter
xDisplay

/3 Counter
Trips *****

xClear
xClear
xClear
xClear
xClear
xClear
xClear
xClear

TripsA *****
TripsB *****
TripsC *****
I^yA ******E6
I^yB ******E6
I^yC ******E6
ARCs ******

Trips
Trips A
Trips B
Trips C
I^yA
I^yB
I^yC
ARCs

Refer to Section
4.2.3.4.

Clear Trips?
END=Y CANCEL=N
Clear Trips A?
END=Y CANCEL=N
Clear Trips B?
END=Y CANCEL=N
Clear Trips C?
END=Y CANCEL=N
Clear I^yA?
END=Y CANCEL=N
Clear I^yB?
END=Y CANCEL=N
Clear I^yC?
END=Y CANCEL=N
Clear ARCs?
END=Y CANCEL=N

a-1

233

6 F 2 S 0 7 5 8
a-1

/1 Status
xMetering

/2 Metering
xCurrent

xBinary I/O
xRelay element
xTime sync.
xClock adjust.
xLCD contrast

xDemand
xDirection
/2 Binary I/O
IP [0000 0000]

Refer to Section 4.2.4.

/2 Ry element
A OC1-4[0000 ]
/2 Time sync.
*BI: Act.
/2 12/Nov/2002
22:56:19
/2 LCD contrast
/1 Set. (view)
xVersion
xDescription
xComms
xRecord
xStatus
xProtection
xBinary I/P
xBinary O/P
xLED
/2 Version
xRelay type
xSerial No.
xSoftware
/2 Description
xPlant name

Refer to Section 4.2.5

GRD140-110A-11
-11

GS1DP1-04-*

xDescription
/2 Comms
xAddr./Param.
xSwitch

/3 Addr./Param.
HDLC
1
/3 Switch

a-1, b-1

234

/3 Current
la
**.** kA
/3 Demand
lamax
**.** kA
/3 Direction
la
Forward

6 F 2 S 0 7 5 8
a-1 b-1

/2 Record
xF.record
xE.record
xD.record
xCounter

/3 F.record
Fault Loc.
Off/On

/3 E.record
xBI1 comm.
N/O/R/B
:
:
/3 D.record
xTime/starter
xScheme sw
xBinary sig.
/3 Counter
xScheme sw
xAlarm set
/2 Status
xMetering
xTime sync.

/3 Metering

/3 Time sync.

/2 Act. gp. =*
xCommon
xGroup1
xGroup2
xGroup3
xGroup4
/3 Common

/3 Group1
xParameter
xTrip
xARC
a-1 b-1 c-1 d-1

235

3
/4 Time/starter
Time
2.0s
/4 Scheme sw

/4 Binary sig.
SIG1

/4 Scheme sw

/4 Alarm set
TCALM 10000

6 F 2 S 0 7 5 8
a-1 b-1 c-1 d-1

/4 Parameter
xLine name
xCT/VT ratio
xFault Locator

/5 CT/VT ratio
OCCT
400
/5 Fault Loc.
X1
10.0 OHM
/6 Application

/4 Trip
xScheme sw

/6 OC

xProt.element
/5 Scheme sw
xApplication
xOC
xEF
xSEF
xNOC
xMisc.
xCold Load
xOV
xUV
xZOV
xNOV
xFRQ

/6 EF

/6 SEF

/6 NOC

/6 Misc.

/6 Cold Load

/6 OV

/6 UV

/6 ZOV

/6 NOV

/6 FRQ
a-1

b-1

C-1

d-1

e-1

236

6 F 2 S 0 7 5 8
a-1

b-1

c-1

d-1 e-1

/5 Prot.element
xOC
xEF
xSEF
xNOC
xMisc.
xCold Load
xOV
xUV
xZOV
xNOV
xFRQ
xCTF/VTF

/6 OC
OC

45

/6 EF
EF

45

/6 SEF
SE

+90

/6 NOC
NC

45

/6 Misc.
UC1
0.40A
/6 Cold Load
OC1
2.00A

/4 ARC
xScheme sw

/6 OV
OV1

120.0V

/6 UV
UV1

60.0V

/6 ZOV
ZOV1

20.0V

/6 NOV
NOV1

20.0V

/6 FRQ
FRQ1

1.00Hz

/6 CTF/VTF
EFF
0.20A

xTimers
/5 Scheme SW
xGeneral

/6 General

xOC
xEF
xSEF
xEXT

/6 OC
/6 EF

/5 Timers
TRDY
60.0s

/6 SEF
/6 EXT

a-1

b-1

C-1

237

6 F 2 S 0 7 5 8
a-1

b-1

c-1

/3 Group2
xParameter
/3 Group4
xParameter
/2 Binary I/P
xBI1

/3 BI1
xTimers

xBI2
xBI3
xBI4
xBI5
xBI6
xBI7
xBI8
xAlarm1
xAlarm2
xAlarm3
xAlarm4

xFunctions

/4 Timers
BI1PUD
0.00s
/4 Functions

/3 BI8
xTimers
xFunctions
Text
Text
Text
Text

Alarm Text

/2 Binary O/P
BO1 AND, D
1, 10, 29, 0
BO7 OR , L
1, 2, 3, 4
TBO1
0.20s
TBO7

0.20s

/2 LED
xLED

/3 LED

xVirtual LED
/3 Virtual LED
xIND1

/4 LED1
BIT1

I,O

/4 LED2
BIT1

I,O

xIND2

a-1 b-1

238

6 F 2 S 0 7 5 8
a-1

/1 Set.(change)
xPassword
xDescription
xComms
xRecord
xStatus
xProtection
xBinary I/P
xBinary O/P
xLED

: Password trap

Password [_ ]
1234567890
: Confirmation trap

Input
[_ ]
1234567890

Change settings?
ENTER=Y CANCEL=N

Retype
[_ ]
1234567890

Refer to Section 4.2.6.2.

/2 Description
xPlant name
xDescription
Refer to Section
4.2.6.3.

/2 Comms
xAddr./Param.
xSwitch

_
ABCDEFG
_
ABCDEFG
/3 Addr./Param.

/3 Switch

Refer to Section
4.2.6.4.

/2 Record
xF.record
xE.record
xD.record
xCounter
Refer to Section
4.2.6.5.

/3 F.record

/3 E.record
xBI1 comm.
N/O/R/B
:

3 _

/3 D.record
xTime/starter
xScheme sw
xBinary sig.
/3 Counter
xScheme sw
xAlarm set
a-1 b-2

239

/4 Time/starter

/4 Scheme sw

/4 Binary sig.

/4 Scheme sw

/4 Alarm set

6 F 2 S 0 7 5 8
a-1 b-2

/3 Metering

/2 Status
xMetering
xTime sync.

/3 Time sync.

Refer to Section
4.2.6.6.

/2 Protection
xChange act. gp.
xChange set.
xCopy gp.

Refer to Section
4.2.6.7.

/3 Change act.
gp.
/3 Act gp.=1
xCommon
xGroup1
xGroup2
xGroup3
xGroup4
/4 Common

/4 Group1
xParameter
xTrip
xARC
/5 Parameter
xLine name
xCT/VT ratio
xFault Locator

_
ABCDEFG
/6 CT/VT ratio

/6 Fault Loc.
X1
OHM

a-1 b-2

c-2 d-2 e-2

240

6 F 2 S 0 7 5 8
a-1 b-2 c-2 d-2

e-2

/5 Trip
xScheme sw
xProt.element
/6 Scheme sw
xApplication
xOC
xEF
xSEF
xNOC
xMisc.
xCold Load
xOV
xUV
xZOV
xNOV
xFRQ

/7 Application

/7 OC

/7 EF

/7 SEF

/7 NOC

/7 Misc.

/7 Cold Load

/7 OV

/7 UV

/7 ZOV

/7 NOV

/7 FRQ

a-1, b-2 c-2 d-2 e-2 f-2

241

6 F 2 S 0 7 5 8
a-1 b-2 c-2 d-2

e-2 f-2

/7 OC
/6 Prot.element
xOC
xEF
xSEF
xNOC
xMisc.
xCold Load
xOV
xUV
xZOV
xNOV
xFRQ
xCTF/VTF

/7 EF
/7 SEF
/7 NOC
/7 Misc.
/7 Cold Load
/7 OV
/7 UV
/7 ZOV
/7 NOV
/7 FRQ

/5 ARC
xScheme sw

/7 CTF/VTF

xTimers
/6 Scheme SW
xGeneral

/7 General

xOC
xEF
xSEF
xEXT

/7 OC
/7 EF

/6 Timers

/7 SEF
/7 EXT

a-1, b-2 c-2 e-2

242

6 F 2 S 0 7 5 8
a-1 b-2 c-2

d-2

/4 Group2
xParameter
/4 Group4
xParameter
/3 Copy A to B
A
_
B

/2 Binary I/P
xBI1

/3 BI1
xTimers

xBI2
xBI3
xBI4
xBI5
xBI6
xBI7
xBI8
xAlarm1
xAlarm2
xAlarm3
xAlarm4

xFunctions

/4 Timers

/4 Functions

/3 BI8
xTimers
xFunctions
Text
Text
Text
Text

ABCDEFG
Alarm Text

Refer to Section 4.2.6.8.

/2 Binary O/P
xBO1

/3 BO1
xLogic/Reset
xFunctions

xBO7
Refer to Section
4.2.6.9.

/2 LED
xLED
xVirtual LED
/3 LED
xLED1

xFunctions
Refer to Section
4.2.6.10.

/4 LED1
xLogic/Reset

xLED3
/4 LED3
xLogic/Reset
c-3

/4 Functions

/3 BO7
xLogic/Reset

xFunctions

a-1

/4 Logic/Reset

xFunctions

243

/5 Logic/Reset

/5 Functions

6 F 2 S 0 7 5 8
a-1

c-3

/3 Virtual LED
xIND1

/4 IND1
xReset

xIND2

xFunctions

/5 Reset

/5 Functions

/4 IND2
xReset
xFunctions
/1 Test
xSwitch

/2 Switch

xBinary O/P
xLogic circuit

A.M.F.
Off/On
UVTST
Off/On
CLPTST
Off/S0/S3
THMRST
Off/On
CLPTST
Off/S1-S6
IECTST
Off/On

Refer to Section 4.2.7.

1 _
0
0
0
0
0

/2 Binary O/P
BO1
0 _
Disable/Enable
FAIL
0
Disable/Enable
/2 Logic
circuit
TermA
1
TermB
48

_
_

244

Operate?
ENTER=Y CANCEL=N

6 F 2 S 0 7 5 8
LCD AND BUTTON OPERATION INSTRUCTION

MANUAL
MODE
1. PRESS ARROW KEY TO MOVE TO EACH DISPLAYED
ITEMS

NORMAL
(DISPLAY OFF)

VIEW

PRESS ANY
BUTTON
EXCEPT FOR
"VIEW" AND
"RESET"

2. PRESS "END" KEY TO BACK TO PREVIOUS SCREEN

1=RECORD
MENU
( DISPLAY ON )

1=FAULT RECORD
2=EVENT RECORD
3=DISTURBANCE RECORD

METERING 1
( DISPLAY ON )

4=COUNTER

2=STATUS
VIEW

RESET

1=METERING
2=BINARY INPUT&OUPUT

METERING 13
( DISPLAY ON )

VIEW

AUTOMODE 1

3=RELAY ELELMENT

TRIP OUTPUT
ISSUED !

5=CLOCK ADJUSTMENT

4=TIME SYNC SOURCE

RESET

TRIP
( LED ON )

3=SETTING
(VIEW)
1=RELAY VERSION

LATEST FAULT *
( DISPLAY ON )

2=DESCRIPTION

AUTOMODE 2

3=COMMUNICATION
4=RECORD

RELAY
FAILED !
VIEW

5=STATUS

RESET

ALARM
( LED ON )

6=PROTECTION
7=BINARY INPUT
8=BINARY OUTPUT

AUTO SUPERVISON *
( DISPLAY ON )

9=LED
*. "LATEST FAULT" AND "AUTO
SUPERVISION" SCREEN IS
DISPLAYED ONLY IF DATA
IS STORED

VIEW

RESET

4=SETTING
(CHANGE)

Same as SETTING (VIEW) menu

5=TEST
1=SWITCH
2=BINARY OUTPUT

245

6 F 2 S 0 7 5 8

246

6 F 2 S 0 7 5 8

Appendix F
Case Outline

247

6 F 2 S 0 7 5 8

R ESET

25 8

IN SER VIC E VIEW


TRIP
ALARM

0V CAN

CEL ENTER
END

15.6

104

185.2

32

Side view

Front view

4 holes-5.5

4 holes-4.5
TB4

OPT1
TX
TB1

TB3

TB1

TB2

RX
TB3

Rear view for


Fibre optic Model

Rear view for


Dual RS485 Model
TB4
A1
B1

TB3

A1

A1

2
4
6
8

TB2

B1

Terminal

Application

TB3: A1 A3

RS485 I/F (CH1) for RSM

TB4

RS485 I/F (CH2) for IEC 60870-5-103

OPT1

Fibre optic for IEC 60870-5-103

B1
TB1,TB2,TB3: Screw terminal (M3.5 Ring)
TB4: Screw terminal for Dual RS485 Model only

A10

OPT1: ST connector for Fibre optic Model only

B10
A18

102

Panel cut-out

A3
B3

TB1

1
3
5
7

56

B18

Terminal block

Case Outline

248

24 9

239

TB2

6 F 2 S 0 7 5 8

Appendix G
Typical External Connection

249

6 F 2 S 0 7 5 8
GRD140 - 110
A

Core balance
CT

Ie
Ise

TB11
2

BO2

A7
B7
A6
B6

BO3

B8
A8
A9
B9

Ve

B10
A11
B11

BO4

BI6

COMMAND

BI7

COMMAND

BI8

COMMAND

BI1

COMMAND

BI2

COMMAND

BI3

COMMAND

BI4

COMMAND

TB2A1
B1
A2
B2
A3
B3
A4
B4
A5
B5
A6
B6
A7
B7
A8
B8

COMMAND

GENERAL TRIP
GENERAL TRIP
GENERAL TRIP
EF1 TRIP
EF1 TRIP
SEF1-S1 TRIP
ZOV1 TRIP

A10

FRAME EARTH

(P)

BO1
BO2
BO3
BO4
BO5
BO6
BO7

A4
A5
B5

BO1

TB15
6
7
8

FRAME EARTH

BI5

OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)

TB3B4

CT

A13
BI6

B13
A12
B12

BO5

BI7

A14
BI8

B14
A15
B15

BO6

BI1

A16

BI2

BO7

B16

FAIL

A17
A18
B18

BI3
B17

BI4
BI5

(N)
OPT1
RELAY FAIL.

(+)

TB2- A9
B9

(-)

+5Vdc

COM1-A

0V

COM1-B

DC-DC

A10

COM1-0V

B10

()

CASE EARTH

TB3-A2
B2

COM2-A
COM2-B
COM2-0V

B1

RS485 I/F for RSM, IEC60870-5-103 or Modbus

()

TB4-A2
B2
A1
B1
A3

()This connection is connected by short bar before shipment.

250

()

A3

B3

Typical External Connection

()

A1

B3

FRAME EARTH
E

Fibre optic I/F for IEC60870-5-103


(Fibre optic model only: option)

DD FAIL.
DC
SUPPLY

TX
RX

RS485 I/F for IEC60870-5-103 or Modbus


(Two ports model only)

6 F 2 S 0 7 5 8
GRD140 - 400

TB11
2
3
4
5
6
7
8

CT

Ia

Ic
Ie

B7
A6
B6

BO2

FRAME EARTH

Vb

A2
B2

A10

Vc

A3
B3

B10
A11
B11

BO4

Ve

A13
B13
A12
B12

BO5
FRAME EARTH
(P)
BI1

COMMAND

BI2

COMMAND

BI3

COMMAND

BI4

COMMAND

BI5

COMMAND

TB2A4
B4
A5
B5
A6
B6
A7
B7
A8
B8

A14
B14
A15
B15

BO6

BI1
BI2

A16
BO7

BI3

B16

BI4

B17
A17
A18
B18

FAIL

BI5

(N)

OPT1
RELAY FAIL.

(+)

TB2- A9
B9

(-)

+5Vdc

COM1-A

0V

COM1-B

DC-DC

A10

COM1-0V

B10

()

Fibre optic I/F for IEC60870-5-103


(Fibre optic model only: option)

CASE EARTH

TB3-A2
B2

COM2-A
COM2-B
COM2-0V

()

A1
B1

()
()

TB4-A2
B2
A1
B1
A3
B3

()This connection is connected by short bar before shipment.

APPL-CT = 3P, APPL-VT = 3PV Setting


Typical External Connection

251

RS485 I/F for RSM, IEC60870-5-103 or Modbus

A3
B3

FRAME EARTH
E

TX
RX

DD FAIL.
DC
SUPPLY

GENERAL TRIP
GENERAL TRIP
GENERAL TRIP
OC1 TRIP
EF1 TRIP
UV1 TRIP
ZOV1 TRIP

B8
A8
A9
B9

BO3

Va

B1

BO1
BO2
BO3
BO4
BO5
BO6
BO7

A4
A5
B5
A7

BO1

Ib

TB2A1

OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)

TB3B4

RS485 I/F for IEC60870-5-103 or Modbus


(Two ports model only)

6 F 2 S 0 7 5 8

GRD140 - 420

TB11
2
3
4
5
6
7
8

CT

Core balance
CT

Ia

Ic
Ise

B7
A6
B6

BO2

FRAME EARTH

Vb

A2
B2

A10

Vc

A3
B3

B10
A11
B11

BO4

A13

Ve

B13
A12
B12

BO5
FRAME EARTH
(P)
BI1

COMMAND

BI2

COMMAND

BI3

COMMAND

BI4

COMMAND

BI5

COMMAND

TB2A4
B4
A5
B5
A6
B6
A7
B7
A8
B8

A14
B14
A15
B15

BO6

BI1
BI2

A16
BO7

BI3

B16

BI4

B17
A17
A18
B18

FAIL

BI5

(N)

OPT1
RELAY FAIL.

(+)

TB2- A9
B9

(-)

+5Vdc

COM1-A

0V

COM1-B

DC-DC

A10

COM1-0V

B10

()

Fibre optic I/F for IEC60870-5-103


(Fibre optic model only: option)

CASE EARTH

TB3-A2
B2

COM2-A
COM2-B
COM2-0V

()

A1
B1

()
()

TB4-A2
B2
A1
B1
A3
B3

()This connection is connected by short bar before shipment.

APPL-CT = 3P, APPL-VT = 3PV Setting


Typical External Connection

252

RS485 I/F for RSM, IEC60870-5-103 or Modbus

A3
B3

FRAME EARTH
E

TX
RX

DD FAIL.
DC
SUPPLY

GENERAL TRIP
GENERAL TRIP
OC1 TRIP
EF1 TRIP
SEF1-S1 TRIP
UV1 TRIP
ZOV1 TRIP

B8
A8
A9
B9

BO3

Va

B1

BO1
BO2
BO3
BO4
BO5
BO6
BO7

A4
A5
B5
A7

BO1

Ib

TB2A1

OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)

TB3B4

RS485 I/F for IEC60870-5-103 or Modbus


(Two ports model only)

6 F 2 S 0 7 5 8

GRD140 - 430

TB11
2
3
4
5
6
7
8

CT

Core balance
CT

Ia

Ic
Ie

B7
A6
B6

BO2

FRAME EARTH

Vb

A2
B2

Vc

A3
B3

Ve

A10
B10
A11
B11

BO4

A13
B13
A12
B12

BO5
FRAME EARTH
(P)
BI1

COMMAND

BI2

COMMAND

BI3

COMMAND

BI4

COMMAND

BI5

COMMAND

TB2A4
B4
A5
B5
A6
B6
A7
B7
A8
B8

A14
B14
A15
B15

BO6

BI1
BI2

A16
BO7

BI3

B16

BI4

B17
A17
A18
B18

FAIL

BI5

(N)

OPT1
RELAY FAIL.

(+)

TB2- A9
B9

(-)

+5Vdc

COM1-A

0V

COM1-B

DC-DC

A10

COM1-0V

B10

()

Fibre optic I/F for IEC60870-5-103


(Fibre optic model only: option)

CASE EARTH

TB3-A2
B2

COM2-A
COM2-B
COM2-0V

()

A1
B1

()
()

TB4-A2
B2
A1
B1
A3
B3

()This connection is connected by short bar before shipment.

APPL-VT = 3PV Setting


Typical External Connection

253

RS485 I/F for RSM, IEC60870-5-103 or Modbus

A3
B3

FRAME EARTH
E

TX
RX

DD FAIL.
DC
SUPPLY

GENERAL TRIP
GENERAL TRIP
OC1 TRIP
EF1 TRIP
SEF1-S1 TRIP
UV1 TRIP
ZOV1 TRIP

B8
A8
A9
B9

BO3

Va

B1

BO1
BO2
BO3
BO4
BO5
BO6
BO7

A4
A5
B5
A7

BO1

Ib

TB2A1

OUTPUT CONTACTS
SIGNAL LIST (DEFAULT)

TB3B4

RS485 I/F for IEC60870-5-103 or Modbus


(Two ports model only)

6 F 2 S 0 7 5 8
CT connection
Bus

Bus
TB1 -1
TB1 -2

TB1 -1

Ia

TB1 -2

TB1 -3
TB1 -4

Ib

TB1 -4

Ic

TB1 -6

Ic

TB1 -7

TB1 -7
TB1 -8

Ib

TB1 -5

TB1 -5
TB1 -6

Ia

TB1 -3

Ie(Io)

[APPL-CT] = 3P Setting for Model 400

TB1 -8

Ise(Io)

[APPL-CT] = 3P Setting for Model 420

Bus

Bus

TB1 -1

TB1 -1
TB1 -2

Ia

TB1 -2

TB1 -4

Ic

TB1 -4

Ic

TB1 -5

TB1 -5
TB1 -6

Ia

TB1 -3

TB1 -3

Ie(Io)

TB1 -6

TB1 -7

TB1 -7

TB1 -8

TB1 -8

[APPL-CT] = 2P Setting for Model 400

Bus

Ie(Io)
Ise(Io)

[APPL-CT] = 2P Setting for Model 420

Bus
TB1 -1

TB1 -1

TB1 -2

TB1 -2

TB1 -3

TB1 -3

TB1 -4

TB1 -4

TB1 -5

TB1 -5

TB1 -6

Ie(Io)

TB1 -6

TB1 -7

TB1 -7

TB1 -8

TB1 -8

[APPL-CT] = 1P Setting for Model 400

Bus
TB1 -1
TB1 -2

Ia

TB1 -3
TB1 -4

Ib

TB1 -5
TB1 -6

Ic

TB1 -7
TB1 -8

Ie(Io)

For Model 430

254

Ie(Io)
Ise(Io)

[APPL-CT] = 1P Setting for Model 420

6 F 2 S 0 7 5 8
VT connection
Bus

Bus
TB2A1

TB2-A1

Va
TB2-B1

Va
TB2-B1

Vb
TB2-A2
TB2-B2

Vb
TB2-A2

Vc

TB2-B2

TB2-A3

TB2-A3

TB2-B3

TB2-B3

[APPL-VT] = 3PN Setting for Model 400,420 or 430

Bus
TB2-A1

Vab
TB2-B1

Vcb
TB2-A2
TB2-B2
TB2-A3
TB2-B3

Ve

[APPL-VT] = 2PP Setting for Model 400, 430 or 430

255

Vc
Ve(Vo)

[APPL-VT] = 3PV Setting for Model 400,420 or 430

6 F 2 S 0 7 5 8

256

6 F 2 S 0 7 5 8

Appendix H
Relay Setting Sheet
1. Relay Identification
2. Line parameter
3. Binary output setting
4. Relay setting
5. Disturbance record signal setting
6. LED setting

257

6 F 2 S 0 7 5 8

1. Relay Identification

Date:

Relay type

Serial Number

Frequency

AC current

AC voltage

DC supply voltage

Password
Active setting group

2. Line parameter
CT ratio

OC:

EF:

VT ratio

PVT:

RVT:

SEF:

3. Binary output setting


Model 110
BO

Logic

Setting range
Reset

BO1 OR / AND

Ins/Dl/Dw /Lat

Timer
BO2 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO3 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO4 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO5 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO6 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO7 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer

0.00 -

Default Setting
110
Logic BOTD
Functions
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
281
EF1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
281
EF1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
291
SEF1-S1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
351
ZOV1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20

Setting

Functions
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00

258

Logic BOTD

Functions
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4

6 F 2 S 0 7 5 8
Model 400
BO

Logic

Setting range
Reset

BO1 OR / AND

Ins/Dl/Dw /Lat

Timer
BO2 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO3 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO4 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO5 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO6 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO7 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer

0.00 -

Default Setting
400
Logic BOTD
Functions
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
261
OC1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
281
EF1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
341
UV1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
351
ZOV1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20

Setting

Functions
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00

Logic BOTD

Functions
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4

Model 420
BO

Logic

Setting range
Reset

BO1 OR / AND

Ins/Dl/Dw /Lat

Timer
BO2 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO3 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO4 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO5 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO6 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer
BO7 OR / AND

0.00 Ins/Dl/Dw /Lat

Timer

0.00 -

Default Setting
420
Logic BOTD
Functions
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
371
GEN.TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
261
OC1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
281
EF1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
291
SEF1-S1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
341
UV1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20
0-500 OR
Del
In #1
351
ZOV1 TRIP
0-500
In #2
0
0-500
In #3
0
0-500
In #4
0
0.20

Setting

Functions
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00
In #1
In #2
In #3
In #4
10.00

259

Logic BOTD

Functions
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4

6 F 2 S 0 7 5 8
4. Relay setting: (Setting 1)
No.
comm
1 19,968

Name
6

5A rating

Contents
Units

AG/

Active gp.

--

Active group

Common

APPL-CT
APPL-VT
CTFEN
VTF1EN
VTF2EN

Off / 3P / 2P / 1P
Off / 3PN / 3PV / 2PP
Off / On / OPT-On
Off / On / OPT-On
Off / On / OPT-On

------

7 19,975

CTSVEN

Off / ALM&BLK / ALM

--

8 19,976
9 19,977

V0SVEN
V2SVEN

Off / ALM&BLK / ALM


Off / ALM&BLK / ALM

---

AOLED

Off - On

--

MOC1
MEF1
MSE1
OC1EN

DT/ IEC/ IEEE/ US/ CON


DT/ IEC/ IEEE/ US/ CON
DT/ IEC/ IEEE/ US/ CON
Off / On

-----

Application setting of CT
Application setting of VT
CTF Enable
VTF1 Enable
VTF2 Enable
AC input imbalance Super Visor
Enable
ditto
ditto
TRIP LED lighting control at alarm
output
OC1 Delay Type (if OC1EN=On)
EF1 Delay Type (if EF1EN=On)
SEF1 Delay Type (if SE1EN=On)
OC1 Enable
OC1 Directional Characteristic (if
OC1EN=On)
OC1 IEC Inverse Curve Type (if
MOC1=IEC)
OC1 IEEE Inverse Curve Type (if
MOC1=IEEE)
OC1 US Inverse Curve Type (if
MOC1=US)
OC1 Reset Characteristic (if
MOCI=IEEE,orUS)
VTF block enable
OC2 Enable
OC2 Directional Characteristic (if
OC2EN=On)
VTF block enable
OC3 Enable
OC3 Directional Characteristic (if
OC3EN=On)
VTF block enable
OC4 Enable
OC4 Directional Characteristic (if
OC4EN=On)
VTF block enable
OC trip mode (if OC1 or 2 or 3 or
3EN=On)
EF1 Enable

19,969
19,970
19,972
19,973
19,974

Range
1A rating
1- 4

2
3
4
5
6

modbus address
Active group
2
3
4

10 19,978
11
12
13
14

16,385
16,387
16,389
16,393

16,641
16,643
16,645
16,649

16,897
16,899
16,901
16,905

17,153
17,155
17,157
17,161

15

16,394

16,650

16,906

17,162

OC1-DIR

FWD / REV /NON

--

16

16,395

16,651

16,907

17,163

MOC1C-IEC

NI / VI / EI / LTI

--

17

16,396

16,652

16,908

17,164

MOC1C-IEEE

MI / VI / EI

--

18

16,397

16,653

16,909

17,165

MOC1C-US

CO2 / CO8

--

19

16,398

16,654

16,910

17,166

OC1R

DEF / DEP

--

20
21

16,399
16,400

16,655
16,656

16,911
16,912

17,167
17,168

VTF-OC1BLK
OC2EN

Off / On
Off / On

---

22

16,401

16,657

16,913

17,169

OC2-DIR

FWD / REV /NON

--

23
24

16,406
16,407

16,662
16,663

16,918
16,919

17,174
17,175

VTF-OC2BLK
OC3EN

Off / On
Off / On

---

25

16,408

16,664

16,920

17,176

OC3-DIR

FWD / REV /NON

--

26
27

16,409
16,410

16,665
16,666

16,921
16,922

17,177
17,178

VTF-OC3BLK
OC4EN

Off / On
Off / On

---

28

16,411

16,667

16,923

17,179

OC4-DIR

FWD / REV /NON

--

29

16,412

16,668

16,924

17,180

VTF-OC4BLK

Off / On

--

30

16,413

16,669

16,925

17,181

OCTP

3POR / 2OUTOF3

--

31

16,414

16,670

16,926

17,182

32

16,415

16,671

16,927

17,183

33

16,416

16,672

16,928

34

16,417

16,673

16,929

35

16,418

16,674

36

16,419

37
38
39

16,420
16,421
16,422

40
41
42
43
44
45
46
47

OC

EF

EF1EN

Off / On / POP

--

EF1-DIR

FWD / REV /NON

--

17,184

MEF1C-IEC

NI / VI / EI / LTI

--

17,185

MEF1C-IEEE

MI / VI / EI

--

16,930

17,186

MEF1C-US

CO2 / CO8

--

16,675

16,931

17,187

EF1R

DEF / DEP

--

16,676
16,677
16,678

16,932
16,933
16,934

17,188
17,189
17,190

CTF-EF1BLK
VTF-EF1BLK
EF2EN

Off / On
Off / On
Off / On / POP

----

16,423

16,679

16,935

17,191

EF2-DIR

FWD / REV /NON

--

16,428
16,429
16,430

16,684
16,685
16,686

16,940
16,941
16,942

17,196
17,197
17,198

CTF-EF2BLK
VTF-EF2BLK
EF3EN

Off / On
Off / On
Off / On / POP

----

16,431

16,687

16,943

17,199

EF3-DIR

FWD / REV /NON

--

16,432
16,433
16,434

16,688
16,689
16,690

16,944
16,945
16,946

17,200
17,201
17,202

CTF-EF3BLK
VTF-EF3BLK
EF4EN

Off / On
Off / On
Off / On / POP

----

48

16,435

16,691

16,947

17,203

EF4-DIR

FWD / REV /NON

--

49
50
51

16,436
16,437
16,438

16,692
16,693
16,694

16,948
16,949
16,950

17,204
17,205
17,206

CTF-EF4BLK
VTF-EF4BLK
CURREV

Off / On
Off / On
Off / 1 / 2 / 3 / 4

----

52

16,439

16,695

16,951

17,207

SE1EN

Off / On

--

53

16,440

16,696

16,952

17,208

SE1-DIR

FWD / REV /NON

--

54

16,441

16,697

16,953

17,209

MSE1C-IEC

NI / VI / EI / LTI

--

SEF

55

16,442

16,698

16,954

17,210

MSE1C-IEEE

MI / VI / EI

--

56

16,443

16,699

16,955

17,211

MSE1C-US

CO2 / CO8

--

57

16,444

16,700

16,956

17,212

SE1R

DEF / DEP

--

58

16,445

16,701

16,957

17,213

SE1S2

Off / On

--

59
60

16,446
16,447

16,702
16,703

16,958
16,959

17,214
17,215

VTF-SE1BLK
SE2EN

Off / On
Off / On

---

61

16,448

16,704

16,960

17,216

SE2-DIR

FWD / REV /NON

--

62

16,453

16,709

16,965

17,221

VTF-SE2BLK

Off / On

--

260

EF1 Directional Characteristic (if


EF1EN=On)
EF1 IEC Inverse Curve Type (if
MEF1=IEC)
EF1 IEEE Inverse Curve Type (if
MEF1=IEEE)
EF1 US Inverse Curve Type (if
MEF1=US)
EF1 Reset Characteristic. (if
MEFI=IEEE,orUS)
CTF block enable
VTF block enable
EF2 Enable
EF2 Directional Characteristic (if
EF2EN=On)
CTF block enable
VTF block enable
EF3 Enable
EF3 Directional Characteristic (if
EF3EN=On)
CTF block enable
VTF block enable
EF4 Enable
EF4 Directional Characteristic (if
EF4EN=On)
CTF block enable
VTF block enable
Current reverse detection
SEF1 Enable
SEF1 Directional Characteristic (if
SE1EN=On)
SEF1 IEC Inverse Curve Type (if
MSE1=IEC)
SEF1 IEEE Inverse Curve Type (if
MSE1=IEEE)
SEF1 US Inverse Curve Type (if
MSE1=US)
SEF1 Reset Characteristic. (if
MSEI=IEEE,orUS)
SEF1 Stage 2 Timer Enable (if
SE1EN=0m)
VTF block enable
SEF2 Enable
SEF2 Directional Characteristic (if
SE2EN=On)
VTF block enable

Default Setting of Relay Series(5A rating / 1A rating)


110
400
430
420
1
------

3P

-3PV
Off
Off
Off

--

ALM

---

ALM
ALM

3P

On
--

DT
DT
--

DT
--

DT
On

--

FWD

--

NI

--

MI

--

CO2

--

DEF

---

Off
Off

--

FWD

---

Off
Off

--

FWD

---

Off
Off

--

FWD

--

Off

--

3POR
On
FWD
NI
MI
CO2
DEF

---

Off
Off
Off
FWD

---

Off
Off
Off
FWD

---

Off
Off
Off
FWD

---

Off
Off
Off

On

--

On

FWD

--

FWD

NI

--

NI

MI

--

MI

CO2

--

CO2

DEF

--

DEF

--

Off

--

Off
Off

--

FWD

Off
-Off
FWD
--

Off

User
Setting

6 F 2 S 0 7 5 8

No.
comm

modbus address
Active group
1
2
3
4

Name
5

Range
5A rating

Contents
Units

1A rating

63

16,454 16,710 16,966 17,222

SE3EN

Off / On

--

64

16,455 16,711 16,967 17,223

SE3-DIR

FWD / REV /NON

--

65
66

16,456 16,712 16,968 17,224


16,457 16,713 16,969 17,225

VTF-SE3BLK
SE4EN

Off / On
Off / On

---

67

16,458 16,714 16,970 17,226

SE4-DIR

FWD / REV /NON

--

68
69
70

16,459 16,715 16,971 17,227


16,460 16,716 16,972 17,228
16,461 16,717 16,973 17,229

VTF-SE4BLK
RPEN
NC1EN

Off / On
Off / On
Off / On

----

71

16,462 16,718 16,974 17,230

NC1-DIR

FWD / REV /NON

--

72
73
74

16,467 16,723 16,979 17,235


16,468 16,724 16,980 17,236
16,469 16,725 16,981 17,237

CTF-NC1BLK
VTF-NC1BLK
NC2EN

Off / On
Off / On
Off / On

----

75

16,470 16,726 16,982 17,238

NC2-DIR

FWD / REV /NON

--

76
77
78
79
80
81
82
83
84
85
86

16,471
16,472
16,473
16,474
16,475
16,476
16,477
16,478
16,479
16,480
16,481

Off / On
Off / On
Off / On
Off / On
Off / On
Off / On
Off / On
Off / On
Off / On
Off / On
Off / DIR / OC

------------

88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109

16,483
16,484
16,485
16,486
16,487
16,488
16,490
16,489
16,491
16,492
16,493
16,494
16,495
16,496
16,497
16,498
16,499
16,500
16,501
16,502
16,503
16,504

17,251
17,252
17,253
17,254
17,255
17,256
17,258
17,257
17,259
17,260
17,261
17,262
17,263
17,264
17,265
17,266
17,267
17,268
17,269
17,270
17,271
17,272

CTF-NC2BLK
VTF-NC2BLK
UC
UC1EN
CTF-UC1BLK
UC2EN
CTF-UC2BLK
Thermal
THMEN
THMAEN
BCD
BCDEN
CBF
BTC
RTC
Cold
CLEN
Load
Load
CLDOEN
OV
OV1EN
OV2EN
UV
UV1EN
VTF-UV1BLK
UV2EN
VTF-UV2BLK
VBLKEN
ZOV
ZOV1EN
VTF-ZV1BLK
ZOV2EN
VTF-ZV2BLK
NOV
NOV1EN
VTF-NV1BLK
NOV2EN
VTF-NV2BLK
FRQ
FRQ1EN
FRQ2EN
FRQ3EN
FRQ4EN
ARC
ARCEN
ARC-NUM

110

16,505 16,761 17,017 17,273

108

16,506 16,762 17,018 17,274

107

16,507 16,763 17,019 17,275

COORD-SE

108

16,508 16,764 17,020 17,276

OC1-INIT

109

16,509 16,765 17,021 17,277

OC1-TP1

Off / Inst / Set

--

110

16,510 16,766 17,022 17,278

OC1-TP2

Off / Inst / Set

--

111

16,511 16,767 17,023 17,279

OC1-TP3

Off / Inst / Set

--

112

16,512 16,768 17,024 17,280

OC1-TP4

Off / Inst / Set

--

113

16,513 16,769 17,025 17,281

OC1-TP5

Off / Inst / Set

--

114

16,514 16,770 17,026 17,282

OC1-TP6

Off / Inst / Set

--

87

16,727
16,728
16,729
16,730
16,731
16,732
16,733
16,734
16,735
16,736
16,737

16,983
16,984
16,985
16,986
16,987
16,988
16,989
16,990
16,991
16,992
16,993

17,239
17,240
17,241
17,242
17,243
17,244
17,245
17,246
17,247
17,248
17,249

NOC

16,482 16,738 16,994 17,250


16,739
16,740
16,741
16,742
16,743
16,744
16,746
16,745
16,747
16,748
16,749
16,750
16,751
16,752
16,753
16,754
16,755
16,756
16,757
16,758
16,759
16,760

16,995
16,996
16,997
16,998
16,999
17,000
17,002
17,001
17,003
17,004
17,005
17,006
17,007
17,008
17,009
17,010
17,011
17,012
17,013
17,014
17,015
17,016

Default Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

SEF3 Enable
SEF3 Directional Characteristic (if
SE3EN=On)
VTF block enable
SEF4 Enable
SEF4 Directional Characteristic (if
SE4EN=On)
VTF block enable
Residual Power block Enable.
NOC1 Enable
NOC1 Directional Characteristic (if
NC1EN=On)
CTF block enable
VTF block enable
NOC2 Enable
NOC2 Directional Characteristic (if
NC2EN=On)
CTF block enable
VTF block enable
UC1 Enable
CTF block enable
UC2 Enable
CTF block enable
Thermal OL Enable
Thermal Alarm Enable
Broken Conductor Enable
Back-trip control
Re-trip control

Off

--

Off

FWD

--

FWD

--

Off
Off

--

FWD

--

Off
Off

-Off
FWD
-Off
--

Off

--

FWD

----

Off
Off
Off

--

FWD

------------

Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off

Off / On

--

Cold Load Protection Enable

--

Off

Off / On
Off / DT / IDMT
Off / On
Off / DT / IDMT
Off / On
Off / On
Off / On
Off / On
Off / DT / IDMT
Off / On
Off / On
Off / On
Off / DT / IDMT
Off / On
Off / On
Off / On
Off / OF / UF
Off / OF / UF
Off / OF / UF
Off / OF / UF
Off / On
S1 / S2 / S3 / S4 / S5

-----------------------

Cold Load drop-off Enable


OV1 Enable
OV2 Enable
UV1 Enable
VTF block enable
UV2 Enable
VTF block enable
UV Block Enable
ZOV1 Enable
VTF block enable
ZOV2 Enable
VTF block enable
NOV1 Enable
VTF block enable
NOV2 Enable
VTF block enable
FRQ1 Enable
FRQ2 Enable
FRQ3 Enable
FRQ4 Enable
Autoreclosing Enable.
Reclosing shot max. number

---------

Off
Off
Off
DT
Off
Off
Off
Off

COORD-OC

Off / On

--

OC relay for Co-ordination Enable

--

COORD-EF

Off / On

--

EF relay for Co-ordination Enable

Off / On

--

SEF relay for Co-ordination Enable

NA / On / Block

--

115

16,515 16,771 17,027 17,283

OC2-INIT

NA / On / Block

--

116

16,516 16,772 17,028 17,284

OC2-TP1

Off / Inst / Set

--

117

16,517 16,773 17,029 17,285

OC2-TP2

Off / Inst / Set

--

118

16,518 16,774 17,030 17,286

OC2-TP3

Off / Inst / Set

--

119

16,519 16,775 17,031 17,287

OC2-TP4

Off / Inst / Set

--

120

16,520 16,776 17,032 17,288

OC2-TP5

Off / Inst / Set

--

121

16,521 16,777 17,033 17,289

OC2-TP6

Off / Inst / Set

--

122

16,522 16,778 17,034 17,290

OC3-INIT

NA / On / Block

--

261

Autoreclosing initiation by OC1


enable
OC1 trip mode of 1st trip (if
OC1EN=On)
OC1 trip mode of 2nd trip (if
OC1EN=On)
OC1 trip mode of 3rd trip (if
OC1EN=On)
OC1 trip mode of 4th trip (if
OC1EN=On)
OC1 trip mode of 5th trip (if
OC1EN=On)
OC1 trip mode of 6th trip (if
OC1EN=On)
Autoreclosing initiation by OC2
enable
OC2 trip mode of 1st trip (if
OC2EN=On)
OC2 trip mode of 2nd trip (if
OC2EN=On)
OC2 trip mode of 3rd trip (if
OC2EN=On)
OC2 trip mode of 4th trip (if
OC2EN=On)
OC2 trip mode of 5th trip (if
OC2EN=On)
OC2 trip mode of 6th trip (if
OC2EN=On)
Autoreclosing initiation by OC3
enable

DT
--

Off
Off

----------

Off
Off
Off
Off
Off
Off
Off
Off
Off
On
S1
Off
Off

Off

--

Off

--

NA

--

SET

--

SET

--

SET

--

SET

--

SET

--

SET

--

NA

--

SET

--

SET

--

SET

--

SET

--

SET

--

SET

--

NA

User
Setting

6 F 2 S 0 7 5 8

No.
comm

modbus address
Active group
2
3
4

Name
5

Range
5A rating

Contents
Units

Default Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

1A rating

123

16,523

16,779

17,035

17,291

OC3-TP1

Off / Inst / Set

--

124

16,524

16,780

17,036

17,292

OC3-TP2

Off / Inst / Set

--

125

16,525

16,781

17,037

17,293

OC3-TP3

Off / Inst / Set

--

126

16,526

16,782

17,038

17,294

OC3-TP4

Off / Inst / Set

--

127

16,527

16,783

17,039

17,295

OC3-TP5

Off / Inst / Set

--

128

16,528

16,784

17,040

17,296

OC3-TP6

Off / Inst / Set

--

129

16,529

16,785

17,041

17,297

OC4-INIT

NA / On / Block

--

130

16,530

16,786

17,042

17,298

OC4-TP1

Off / Inst / Set

--

131

16,531

16,787

17,043

17,299

OC4-TP2

Off / Inst / Set

--

132

16,532

16,788

17,044

17,300

OC4-TP3

Off / Inst / Set

--

133

16,533

16,789

17,045

17,301

OC4-TP4

Off / Inst / Set

--

134

16,534

16,790

17,046

17,302

OC4-TP5

Off / Inst / Set

--

135

16,535

16,791

17,047

17,303

OC4-TP6

Off / Inst / Set

--

136

16,536

16,792

17,048

17,304

EF1-INIT

NA / On / Block

--

137

16,537

16,793

17,049

17,305

EF1-TP1

Off / Inst / Set

--

138

16,538

16,794

17,050

17,306

EF1-TP2

Off / Inst / Set

--

139

16,539

16,795

17,051

17,307

EF1-TP3

Off / Inst / Set

--

140

16,540

16,796

17,052

17,308

EF1-TP4

Off / Inst / Set

--

141

16,541

16,797

17,053

17,309

EF1-TP5

Off / Inst / Set

--

142

16,542

16,798

17,054

17,310

EF1-TP6

Off / Inst / Set

--

143

16,543

16,799

17,055

17,311

EF2-INIT

NA / On / Block

--

144

16,544

16,800

17,056

17,312

EF2-TP1

Off / Inst / Set

--

145

16,545

16,801

17,057

17,313

EF2-TP2

Off / Inst / Set

--

146

16,546

16,802

17,058

17,314

EF2-TP3

Off / Inst / Set

--

147

16,547

16,803

17,059

17,315

EF2-TP4

Off / Inst / Set

--

148

16,548

16,804

17,060

17,316

EF2-TP5

Off / Inst / Set

--

149

16,549

16,805

17,061

17,317

EF2-TP6

Off / Inst / Set

--

150

16,550

16,806

17,062

17,318

EF3-INIT

NA / On / Block

--

151

16,551

16,807

17,063

17,319

EF3-TP1

Off / Inst / Set

--

152

16,552

16,808

17,064

17,320

EF3-TP2

Off / Inst / Set

--

153

16,553

16,809

17,065

17,321

EF3-TP3

Off / Inst / Set

--

154

16,554

16,810

17,066

17,322

EF3-TP4

Off / Inst / Set

--

155

16,555

16,811

17,067

17,323

EF3-TP5

Off / Inst / Set

--

156

16,556

16,812

17,068

17,324

EF3-TP6

Off / Inst / Set

--

157

16,557

16,813

17,069

17,325

EF4-INIT

NA / On / Block

--

158

16,558

16,814

17,070

17,326

EF4-TP1

Off / Inst / Set

--

159

16,559

16,815

17,071

17,327

EF4-TP2

Off / Inst / Set

--

160

16,560

16,816

17,072

17,328

EF4-TP3

Off / Inst / Set

--

161

16,561

16,817

17,073

17,329

EF4-TP4

Off / Inst / Set

--

162

16,562

16,818

17,074

17,330

EF4-TP5

Off / Inst / Set

--

163

16,563

16,819

17,075

17,331

EF4-TP6

Off / Inst / Set

--

164

16,564

16,820

17,076

17,332

SE1-INIT

NA / On / Block

--

165

16,565

16,821

17,077

17,333

SE1-TP1

Off / Inst / Set

--

166

16,566

16,822

17,078

17,334

SE1-TP2

Off / Inst / Set

--

262

OC3 trip mode of 1st trip (if


OC3EN=On)
OC3 trip mode of 2nd trip (if
OC3EN=On)
OC3 trip mode of 3rd trip (if
OC3EN=On)
OC3 trip mode of 4th trip (if
OC3EN=On)
OC3 trip mode of 5th trip (if
OC3EN=On)
OC3 trip mode of 6th trip (if
OC3EN=On)
Autoreclosing initiation by OC4
enable
OC4 trip mode of 1st trip (if
OC4EN=On)
OC4 trip mode of 2nd trip (if
OC4EN=On)
OC4 trip mode of 3rd trip (if
OC4EN=On)
OC4 trip mode of 4th trip (if
OC4EN=On)
OC4 trip mode of 5th trip (if
OC4EN=On)
OC4 trip mode of 6th trip (if
OC4EN=On)
Autoreclosing initiation by EF1
enable
EF1 trip mode of 1st trip (if
EF1EN=On)
EF1 trip mode of 2nd trip (if
EF1EN=On)
EF1 trip mode of 3rd trip (if
EF1EN=On)
EF1 trip mode of 4th trip (if
EF1EN=On)
EF1 trip mode of 5th trip (if
EF1EN=On)
EF1 trip mode of 6th trip (if
EF1EN=On)
Autoreclosing initiation by EF2
enable
EF2 trip mode of 1st trip (if
EF2EN=On)
EF2 trip mode of 2nd trip (if
EF2EN=On)
EF2 trip mode of 3rd trip (if
EF2EN=On)
EF2 trip mode of 4th trip (if
EF2EN=On)
EF2 trip mode of 5th trip (if
EF2EN=On)
EF2 trip mode of 6th trip (if
EF2EN=On)
Autoreclosing initiation by EF3
enable
EF3 trip mode of 1st trip (if
EF3EN=On)
EF3 trip mode of 2nd trip (if
EF3EN=On)
EF3 trip mode of 3rd trip (if
EF3EN=On)
EF3 trip mode of 4th trip (if
EF3EN=On)
EF3 trip mode of 5th trip (if
EF3EN=On)
EF3 trip mode of 6th trip (if
EF1EN=On)
Autoreclosing initiation by EF4
enable
EF4 trip mode of 1st trip (if
EF4EN=On)
EF4 trip mode of 2nd trip (if
EF4EN=On)
EF4 trip mode of 3rd trip (if
EF4EN=On)
EF4 trip mode of 4th trip (if
EF4EN=On)
EF4 trip mode of 5th trip (if
EF4EN=On)
EF4 trip mode of 6th trip (if
EF1EN=On)
Autoreclosing initiation by SEF1
enable
SEF1 trip mode of 1st trip (if
SE1EN=On)
SEF1 trip mode of 2nd trip (if
SE1EN=On)

--

SET

--

SET

--

SET

--

SET

--

SET

--

SET

--

NA

--

SET

--

SET

--

SET

--

SET

--

SET

--

SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET
NA
SET
SET
SET
SET
SET
SET

NA

--

NA

SET

--

SET

SET

--

SET

User
Setting

6 F 2 S 0 7 5 8

No.
comm

modbus address
Active group
2
3
4

Name
5

5A rating

16,567

16,823

17,079

17,335

SE1-TP3

Off / Inst / Set

168

16,568

16,824

17,080

17,336

SE1-TP4

Off / Inst / Set

169

16,569

16,825

17,081

17,337

SE1-TP5

Off / Inst / Set

170

16,570

16,826

17,082

17,338

SE1-TP6

Off / Inst / Set

171

16,571

16,827

17,083

17,339

SE2-INIT

NA / On / Block

172

16,572

16,828

17,084

17,340

SE2-TP1

Off / Inst / Set

173

16,573

16,829

17,085

17,341

SE2-TP2

Off / Inst / Set

174

16,574

16,830

17,086

17,342

SE2-TP3

Off / Inst / Set

175

16,575

16,831

17,087

17,343

SE2-TP4

Off / Inst / Set

176

16,576

16,832

17,088

17,344

SE2-TP5

Off / Inst / Set

177

16,577

16,833

17,089

17,345

SE2-TP6

Off / Inst / Set

178

16,578

16,834

17,090

17,346

SE3-INIT

NA / On / Block

179

16,579

16,835

17,091

17,347

SE3-TP1

Off / Inst / Set

180

16,580

16,836

17,092

17,348

SE3-TP2

Off / Inst / Set

181

16,581

16,837

17,093

17,349

SE3-TP3

Off / Inst / Set

182

16,582

16,838

17,094

17,350

SE3-TP4

Off / Inst / Set

183

16,583

16,839

17,095

17,351

SE3-TP5

Off / Inst / Set

184

16,584

16,840

17,096

17,352

SE3-TP6

Off / Inst / Set

185

16,585

16,841

17,097

17,353

SE4-INIT

NA / On / Block

186

16,586

16,842

17,098

17,354

SE4-TP1

Off / Inst / Set

187

16,587

16,843

17,099

17,355

SE4-TP2

Off / Inst / Set

188

16,588

16,844

17,100

17,356

SE4-TP3

Off / Inst / Set

189

16,589

16,845

17,101

17,357

SE4-TP4

Off / Inst / Set

190

16,590

16,846

17,102

17,358

SE4-TP5

Off / Inst / Set

191

16,591

16,847

17,103

17,359

SE4-TP6

Off / Inst / Set

192

16,592

16,848

17,104

17,360

EXT-INIT

NA / On / Block

193

17,840

18,020

18,200

18,380

UVF

5.0 - 130.0

194

17,839

18,019

18,199

18,379

VTF

ZOVF

CTF

OCDF

0.5(Fixed)

0.1(Fixed)

5.0 - 130.0

EFF

0. - 25.0

0.02 - 5.00

196

17,838

18,018

18,198

18,378

197

17,712

17,892

18,072

18,252

198

17,713

17,893

18,073

18,253

OC1

199

17,408

17,484

17,560

17,636

TOC1

0.00 - 300.00

200

17,714

17,894

18,074

18,254

TOC1M

0.010 - 1.500

201

17,715

17,895

18,075

18,255

TOC1R

0.0 - 300.0

202

17,716

17,896

18,076

18,256

TOC1RM

0.010 - 1.500

OC

OC

-95 - 95
0.1 - 25.0

0.1 - 25.0

Units

Default Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

1A rating

167

195

Contents

Range

0.02 - 5.00

203

17,717

17,897

18,077

18,257

OC2

204

17,409

17,485

17,561

17,637

TOC2

0.00 - 300.00

0.02 - 5.00

205

17,721

17,901

18,081

18,261

OC3

0.1 - 250.0 0.02 - 50.00

206

17,410

17,486

17,562

17,638

TOC3

0.00 - 300.00

207

17,722

17,902

18,082

18,262

OC4

0.1 - 250.0 0.02 - 50.00

208

17,411

17,487

17,563

17,639

TOC4

0.00 - 300.00

SEF1 trip mode of 3rd trip (if


SE1EN=On)
SEF1 trip mode of 4th trip (if
-SE1EN=On)
SEF1 trip mode of 5th trip (if
-SE1EN=On)
SEF1 trip mode of 6th trip (if
-SE1EN=On)
Autoreclosing initiation by SEF2
-enable
SEF2 trip mode of 1st trip (if
-SE2EN=On)
SEF2 trip mode of 2nd trip (if
-SE2EN=On)
SEF2 trip mode of 3rd trip (if
-SE2EN=On)
SEF2 trip mode of 4th trip (if
-SE2EN=On)
SEF2 trip mode of 5th trip (if
-SE2EN=On)
SEF2 trip mode of 6th trip (if
-SE2EN=On)
Autoreclosing initiation by SEF3
-enable
SEF3 trip mode of 1st trip (if
-SE3EN=On)
SEF3 trip mode of 2nd trip (if
-SE3EN=On)
SEF3 trip mode of 3rd trip (if
-SE3EN=On)
SEF3 trip mode of 4th trip (if
-SE3EN=On)
SEF3 trip mode of 5th trip (if
-SE3EN=On)
SEF3 trip mode of 6th trip (if
-SE3EN=On)
Autoreclosing initiation by SEF4
-enable
SEF4 trip mode of 1st trip (if
-SE4EN=On)
SEF4 trip mode of 2nd trip (if
-SE4EN=On)
SEF4 trip mode of 3rd trip (if
-SE4EN=On)
SEF4 trip mode of 4th trip (if
-SE4EN=On)
SEF4 trip mode of 5th trip (if
-SE4EN=On)
SEF4 trip mode of 6th trip (if
-SE4EN=On)
Autoreclosing initiation by External
-Trip Command enable
UV(Ph-G) Threshold setting for
V
VTF scheme.
ZOV Threshold setting for
V
CTF/VTF scheme.
OCD Threshold setting for
A
CTF/VTF scheme.
EF Threshold setting for CTF/VTF
A
scheme.
OC Characteristic Angle (if OC1 or
Degree
2 or 3 or 4EN=On)
OC1 Threshold setting (if
A
OC1EN=On)
OC1 Definite time setting (if
s
MOC1=DT)
OC1 Time multiplier setting (if
-MOC1=IEC,IEEE,US)
OC1 Definite time reset delay (if
s
OC1R =DEF)
OC1 Dependent time reset time
-multiplier (if OC1R=DEP)
OC2 Threshold setting (if
A
OC2EN=On)
OC2 Definite time setting (if
s
MOC2=DT)
OC3 Threshold setting (if
A
OC3EN=On)
OC3 Definite time setting (if
s
OC3EN=On)
OC4 Threshold setting (if
A
OC4EN=On)
OC4 Definite time setting (if
s
OC4EN=On)

263

--

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

NA

--

NA

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

NA

--

NA

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

NA

--

NA

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

SET

--

SET

NA
--

51.0

--

20.0

--

--

--

1.0 / 0.20

--

-45

--

5.0 / 1.00

--

1.00

--

1.000

--

0.0

--

1.000

--

25.0 / 5.00

--

1.00

--

50.0 / 10.00

--

1.00

--

100.0 / 20.00

--

1.00

User
Setting

6 F 2 S 0 7 5 8

No.
comm

modbus address
Active group
2
3
4

Name
5

5A rating

209

17,723

17,903

18,083

18,263

OC1-k

210
211
212
213

17,724
17,725
17,726
17,727

17,904
17,905
17,906
17,907

18,084
18,085
18,086
18,087

18,264
18,265
18,266
18,267

OC1-
OC1-C
OC1-kr
OC1-

214

17,733

17,913

18,093

18,273

215

17,734

17,914

18,094

18,274

EFV

216

17,735

17,915

18,095

18,275

EF1

217

17,412

17,488

17,564

17,640

TEF1

218

17,736

17,916

18,096

18,276

TEF1M

219

17,737

17,917

18,097

18,277

TEF1R

220

17,738

17,918

18,098

18,278

TEF1RM

221

17,739

17,919

18,099

18,279

EF2

222

17,413

17,489

17,565

17,641

TEF2

223

17,743

17,923

18,103

18,283

EF3

EF

EF

224

17,414

17,490

17,566

17,642

TEF3

225

17,744

17,924

18,104

18,284

EF4

17,491

17,567

17,643

TEF4

17,568

17,644

TREBK

18,105

18,285

EF1-k

Contents

Range

Units

Default Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

1A rating

Configurable IDMT Curve setting of


OC1.
0.00 - 5.00
-ditto
0.000 - 5.000
-ditto
0.000 - 30.000
-ditto
0.00 - 5.00
-ditto
EF Characteristic Angle (if EF1 or 2
-95 - 95
Degree
or 3 or 4EN=On)
EF ZPS voltage level (if EF1 or 2 or
0.5 - 100.0
V
3 or 4EN=On)
EF1 Threshold setting (if
0.1 - 25.0 0.02 - 5.00
A
EF1EN=On)
EF1 EFinite time setting. (if
s
0.00 - 300.00
MEF1=DT)
EF1 Time multiplier setting (if
0.010 - 1.500
-MEF1=IEC,IEEE,US)
EF1 EFinite time reset delay. (if
0.0 - 300.0
s
EF1R =DEF)
EF1 Dependent time reset time
-0.010 - 1.500
multiplier. (if EF1R=DEP)
EF2 Threshold setting (if
0.1 - 25.0 0.02 - 5.00
A
EF2EN=On)
EF2 EFinite time setting. (if
s
0.00 - 300.00
MEF2=DT)
EF3 Threshold setting (if
0.1 - 250.0 0.02 - 50.00
A
EF3EN=On)
0.1 - 40.0 0.02 - 8.00
EF3 EFinite time setting. (if
0.00 - 300.00
s
EF3EN=On)
EF4 Threshold setting (if
0.1 - 250.0 0.02 - 50.00
A
EF4EN=On)
0.1 - 40.0 0.02 - 8.00
EF4 EFinite time setting. (if
0.00 - 300.00
s
EF4EN=On)
0.00 - 10.00
s
Current reverse blocking time
0.000 - 30.000

--

--

0.000

-----

0.00
0.000
0.000
0.00
-45
3.0
1.50 / 0.30
1.00
1.000
0.0
1.000
15.0 / 3.00

5.00 / 1.00

25.0 / 5.00

--

25.0 / 5.00

--

15.0 / 3.00

--

1.00
50.0 / 10.00

--

50.0 / 10.00

--

30.0 / 6.00

--

226

17,415

227

17,416

17,492

228

17,745

17,925

229

17,746

17,926

18,106

18,286

EF1-

0.00 - 5.00

--

Configurable IDMT Curve setting of


EF1.
ditto

230
231

17,747
17,748

17,927
17,928

18,107
18,108

18,287
18,288

EF1-C
EF1-kr

0.000 - 5.000
0.000 - 30.000

---

ditto
ditto

0.000
0.000

232

17,749

17,929

18,109

18,289

EF1-

0.00 - 5.00

--

17,755

17,935

18,115

18,295

SE

-95 - 95

Degree

234

17,756

17,936

18,116

18,296

SEV

0.5 - 100.0

235

17,757

17,937

18,117

18,297

SE1

0.01 - 1.00 0.002-0.200

ditto
SEF Characteristic Angle (if DEF1
0
or 2 or 3 or 4EN=On)
SEF ZPS voltage level (if DEF1 or 2
3.0
or 3 or 4EN=On)
SEF1 Threshold setting (if
0.05/0.010
SE1EN=On)

0.00

233

0.002-0.200

SEF

0.000 - 30.000

--

--

236

17,417

17,493

17,569

17,645

TSE1

0.00 - 300.00

237

17,758

17,938

18,118

18,298

TSE1M

0.010 - 1.500

--

238

17,759

17,939

18,119

18,299

TSE1R

0.0 - 300.0

239

17,760

17,940

18,120

18,300

TSE1RM

0.010 - 1.500

--

240

17,418

17,494

17,570

17,646

TS1S2

0.00 - 300.00

241

17,761

17,941

18,121

18,301

SE2

0.01 - 1.00 0.002-0.200

0.002 - 0.200

--

242

17,419

17,495

17,571

17,647

TSE2

0.00 - 300.00

243

17,765

17,945

18,125

18,305

SE3

0.01 - 1.00 0.002 - 0.200

0.002-0.200

--

244

17,420

17,496

17,572

17,648

TSE3

0.00 - 300.00

245

17,766

17,946

18,126

18,306

SE4

0.01 - 1.00 0.002-0.200

0.002-0.200

--

246

17,421

17,497

17,573

17,649

TSE4

0.00 - 300.00

247

17,767

17,947

18,127

18,307

RP

0.00-100.00 0.00-20.00

264

1.00
0.10
0.000
0.00

SEF1 Threshold setting (if


SE1EN=On) (5A SEF: Low Level )
SEF1 Definite time setting. (if
MSE1=DT)
SEF1 Time multiplier setting (if
MSE1=IEC,IEEE,US)
SEF1 Definite time reset delay. (if
SE1R =DEF)
SEF1 Dependent time reset time
multiplier. (if SE1R=DEP)
SEF1 Stage 2 definite timer
settings. (if SE1EN=0n and
SE1S2=On)
SEF2 Threshold setting (if
SE2EN=On)

--

3.0

--

0.05/0.010
0.010

--

1.00

1.000

--

1.000

0.0

--

0.0

1.000

--

1.000

1.00

--

1.00

0.05/0.010

--

0.05/0.010

--

0.010

1.00

--

1.00

0.05/0.010

--

0.05/0.010

--

0.010

1.00

--

1.00

0.05/0.010

--

0.05/0.010

SEF4 Threshold setting (if


SE4EN=On) (5A SEF: Low Level )
SEF4 Definite time setting (if
SE4EN=On)
Residual Power Threshold. (5A
SEF: Low Level )

1.00

SEF3 Threshold setting (if


SE3EN=On) (5A SEF: Low Level )
SEF3 Definite time setting (if
SE3EN=On)
SEF4 Threshold setting (if
SE4EN=On)

--

--

SEF2 Threshold setting (if


SE2EN=On) (5A SEF: Low Level )
SEF2 Definite time setting (if
MSE2=DT)
SEF3 Threshold setting (if
SE3EN=On)

15.0 / 3.00

1.00

--

0.010

1.00

--

1.00

0.00 / 0.00

--

0.00 / 0.00

User
Setting

6 F 2 S 0 7 5 8

No.
comm

modbus address
Active group
2
3
4

Name
5

Contents

Range
5A rating

Units

1A rating

248

17,768

17,948

18,128

18,308

SE1-k

0.000 - 30.000

249
250
251
252

17,769
17,770
17,771
17,772

17,949
17,950
17,951
17,952

18,129
18,130
18,131
18,132

18,309
18,310
18,311
18,312

SE1-
SE1-C
SE1-kr
SE1-

0.00 - 5.00
0.000 - 5.000
0.000 - 30.000
0.00 - 5.00

253

17,778

17,958

18,138

18,318

NC

-95 - 95

254

17,779

17,959

18,139

18,319

NCV

255

17,780

17,960

18,140

18,320

NC1

256

17,422

17,498

17,574

17,650

TNC1

257

17,784

17,964

18,144

18,324

NC2

258

17,423

17,499

17,575

17,651

TNC2

259

17,790

17,970

18,150

18,330

260

17,424

17,500

17,576

17,652

TUC1

261

17,791

17,971

18,151

18,331

UC2

262

17,425

17,501

17,577

17,653

NOC

UC

UC1

TUC2
Thermal

0.5 - 25.0
0.5 - 10.0

0.10 - 2.00

0.00 - 300.00
0.5 - 10.0

0.10 - 2.00

0.00 - 300.00
0.5 - 10.0

0.10 - 2.00

0.00 - 300.00
0.5 - 10.0

0.10 - 2.00

0.00 - 300.00

263

17,792

17,972

18,152

18,332

THM

2.0 - 10.0

0.40 - 2.00

264

17,793

17,973

18,153

18,333

THMIP

0.0 - 5.0

0.00 - 1.00

265

17,794

17,974

18,154

18,334

TTHM

266

17,795

17,975

18,155

18,335

267

17,796

17,976

18,156

18,336

268

17,426

17,502

17,578

17,654

269

17,797

17,977

18,157

18,337

270
271

17,427
17,428

17,503
17,504

17,579
17,580

17,655
17,656

272

17,798

17,978

18,158

18,338

BCD

CBF

Cold
Load

Configurable IDMT Curve setting of


SEF1.
-- ditto
-- ditto
-- ditto
-- ditto
NOC Characteristic Angle (if NC1
Degree
or 2 or 3 or 4EN=On)
NOC NPS voltage level (if NC1 or 2
V
or 3 or 4EN=On)
NOC1 Threshold setting (if
A
NC1EN=On)
NOC1 Definite time setting (if
s
MNC1=DT)
NOC2 Threshold setting (if
A
NC2EN=On)
NOC2 Definite time setting (if
s
NC2EN=On)
UC1 Threshold setting (if
A
UC1EN=On)
UC1 Definite time setting (if
s
UC1EN=On)
UC2 Threshold setting (if
A
UC2EN=On)
UC2 Definite time setting (if
s
UC2EN=On)
Thermal overload setting (if
A
OLTEN=On)
--

0.5 - 500.0

min

THMA

50 - 99

BCD

0.10 - 1.00

--

TBCD

0.00 - 300.00

CBF
TBTC
TRTC
OC1

0.5 - 10.0

Default Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

0.10 - 2.00

0.00 - 300.00
0.00 - 300.00

A
s
s

0.1 - 25.0

0.02 - 5.00

Pre Current value (if OLTEN=On)


Thermal Time Constant (if
OLTEN=On)
Thermal alarm setting (if OLTEN
=On & ALTEN=On)
Broken Conductor Threshold setting
(if BCDEN=On)
Broken Conductor Definite time
setting. (if BCDEN=On)
CBF Threshold setting (if
CBFEN=On)
Back trip Definite time setting
Re-trip Definite time setting
OC1 Threshold setting in CLP
mode.
OC2 Threshold setting in CLP
mode.
OC3 Threshold setting in CLP
mode.
OC4 Threshold setting in CLP
mode.

0.000

--

0.000

0.00
0.000
0.000
0.00

-----

0.00
0.000
0.000
0.00

--

-45

--

3.0

--

2.0 / 0.40

--

1.00

--

1.0 / 0.20

--

1.00

--

1.0 / 0.20

--

1.00

--

2.0 / 0.40

--

1.00

--

5.0 / 1.00

--

0.0 / 0.00

--

10.0

--

80

--

0.20

--

1.00

--

2.5 / 0.50

---

0.50
0.40

--

10.0 / 2.00

273

17,799

17,979

18,159

18,339

OC2

0.1 - 25.0

0.02 - 5.00

274

17,800

17,980

18,160

18,340

OC3

0.1 - 250.0 0.02 - 50.00

275

17,801

17,981

18,161

18,341

OC4

0.1 - 250.0 0.02 - 50.00

276

17,802

17,982

18,162

18,342

EF1

0.1 - 25.0

0.02 - 5.00

EF1 Threshold setting in CLP mode.

--

277

17,803

17,983

18,163

18,343

EF2

0.1 - 25.0

0.02 - 5.00

EF2 Threshold setting in CLP mode.

--

25.0 / 5.00

15.0 / 3.00

25.0 / 5.00

278

17,804

17,984

18,164

18,344

EF3

0.1 - 250.0 0.02 - 50.00

EF3 Threshold setting in CLP mode.

--

100.0/20.00

--

100.0/20.00

--

--

25.0 / 5.00

--

--

200.0/40.00

--

200.0/40.00

--

--

40.0 / 8.00

--

0.02 - 8.00

EF3 Threshold setting in CLP mode


for Model 430

0.1 - 250.0 0.02 - 50.00

EF4 Threshold setting in CLP mode.

0.1 - 40.0

0.1 - 40.0
279

280

17,805

17,806

17,985

17,986

18,165

18,166

18,345

18,346

EF4

SE1

281

17,807

17,987

18,167

18,347

SE2

282

17,808

17,988

18,168

18,348

SE3

0.02 - 8.00

0.01 - 1.00 0.002-0.200

0.002-0.200

--

0.01 - 1.00 0.002-0.200

0.002-0.200

--

0.01 - 1.00 0.002-0.200

0.002-0.200

--

283

17,809

17,989

18,169

18,349

SE4

0.01 - 1.00 0.002-0.200


0.002-0.200

--

284

17,810

17,990

18,170

18,350

NC1

0.5 - 10.0

0.10 - 2.00

285

17,811

17,991

18,171

18,351

NC2

0.5 - 10.0

0.10 - 2.00

286

17,812

17,992

18,172

18,352

BCD

0.0 - 1.00

--

287

17,429

17,505

17,581

17,657

TCLE

0 - 10000

288

17,430

17,506

17,582

17,658

TCLR

0 - 10000

265

EF4 Threshold setting in CLP mode


for Model 430
SEF1 Threshold setting in CLP
mode.
SEF1 Threshold setting in CLP
mode. (5A SEF: Low Level )
SEF2 Threshold setting in CLP
mode.
SEF2 Threshold setting in CLP
mode. (5A SEF: Low Level )
SEF3 Threshold setting in CLP
mode.
SEF3 Threshold setting in CLP
mode. (5A SEF: Low Level )
SEF4 Threshold setting in CLP
mode.
SEF4 Threshold setting in CLP
mode. (5A SEF: Low Level )
NOC1 Threshold setting in CLP
mode.
NOC2 Threshold setting in CLP
mode.
Broken Conductor Threshold setting
in CLP mode.
Cold load enable timer. (if
CLEN=On)
Cold load reset timer (if CLEN=On)

--

25.0 / 5.00

--

100.0 / 20.00

--

200.0 / 40.00
10.0 / 2.00

---

0.10/0.020
--

0.0020

---

0.10/0.020
--

0.0020

---

0.10/0.020
--

0.0020

---

0.10/0.020
--

0.0020

--

4.0 / 0.80

--

2.0 / 0.40

--

0.40

--

100

--

100

User
Setting

6 F 2 S 0 7 5 8

No.
comm

modbus address
Active group
1
2
3
4

289

17,813 17,993 18,173 18,353

290

17,431 17,507 17,583 17,659

291

17,814 17,994 18,174 18,354

292

Name
5

8
ICLDO

Range
5A rating

1A rating

0.5 - 10.0

0.10 - 2.00

Contents
Units

TCLDO

0.00 - 100.00

OV1

10.0 - 200.0

17,432 17,508 17,584 17,660

TOV1

0.00 - 300.00

293

17,815 17,995 18,175 18,355

TOV1M

0.05 - 100.00

--

294
295
296
297
298
299

17,816
17,817
17,818
17,433
17,819
17,820

TOV1R
OV1DPR
OV2
TOV2
OV2DPR
UV1

0.0 - 300.0
10 - 98
10.0 - 200.0
0.00 - 300.00
10 - 98
5.0 - 130.0

s
%
V
s
%
V

300

17,434 17,510 17,586 17,662

TUV1

0.00 - 300.00

301

17,821 18,001 18,181 18,361

TUV1M

0.05 - 100.00

--

302
303
304
305
306

17,822
17,823
17,435
17,824
17,825

TUV1R
UV2
TUV2
VBLK
ZOV1

0.0 - 300.0
5.0 - 130.0
0.00 - 300.00
5.0 - 20.0
1.0 - 130.0

s
V
s
V
V

307

17,436 17,512 17,588 17,664

TZOV1

0.00 - 300.00

17,996
17,997
17,998
17,509
17,999
18,000

18,002
18,003
17,511
18,004
18,005

18,176
18,177
18,178
17,585
18,179
18,180

18,182
18,183
17,587
18,184
18,185

18,356
18,357
18,358
17,661
18,359
18,360

18,362
18,363
17,663
18,364
18,365

OV

UV

ZOV

Cold load drop-out threshold setting.


(if CLDOEN=On)
Cold load drop-out timer (if
CLDOEN=1)
OV1 Threshold setting.
OV1 Definite time setting. Display if
[OV1EN] = 1.
OV1 Time multiplier setting. Display
if [OV1EN] = 2.
OV1 Definite time reset delay.
OV1 DO/PU ratio
OV2 Threshold setting.
OV2 Definite time setting.
OV2 DO/PU ratio
UV1 Threshold setting.
UV1 Definite time setting. Display if
[UV1EN] = 1.
UV1 Time multiplier setting. Display
if [UV1EN] = 2.
UV1 Definite time reset delay.
UV2 Threshold setting.
UV2 Definite time setting.
UV Blocking threshold
ZOV1 Threshold setting.
ZOV1 Definite time setting. Display
if [ZOV1EN] = 1.
ZOV1 Time multiplier setting.
Display if [ZOV1EN] = 2.
ZOV1 Definite time reset delay.
ZOV2 Threshold setting.
ZOV2 Definite time setting.
NOV1 Threshold setting.
NOV1 Definite time setting. Display
if [MNOV1] = 0.
NOV1 Time multiplier setting.
Display if [MNOV1] = 1.
NOV1 Definite time reset delay.
NOV2 Threshold setting.
NOV2 Definite time setting.
FRQ1 Threshold setting.
FRQ1 Definite time setting.
FRQ2 Threshold setting.
FRQ2 Definite time setting.
FRQ3 Threshold setting.
FRQ3 Definite time setting.
FRQ4 Threshold setting.
FRQ4 Definite time setting.
UV Blocking threshold
Reclaim timer
1st shot Dead timer of Stage1
2nd shot Dead timer of Stage1
3rd shot Dead timer of Stage1
4th shot Dead timer of Stage1
5th shot Dead timer of Stage1
Out put pulse timer
Autoreclosing Pause Time after
manually close
Autoreclosing Recovery time after
Final Trip
Autoreclosing Pause Time after
manually close

308

17,826 18,006 18,186 18,366

TZOV1M

0.05 - 100.00

--

309
310
311
312

17,827
17,828
17,437
17,829

TZOV1R
ZOV2
TZOV2
NOV1

0.0 - 300.0
1.0 - 130.0
0.00 - 300.00
1.0 - 130.0

s
V
s
V

313

17,438 17,514 17,590 17,666

TNOV1

0.00 - 300.00

314

17,830 18,010 18,190 18,370

TNOV1M

0.05 - 100.00

--

315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333

17,831
17,832
17,439
17,833
17,440
17,834
17,441
17,835
17,442
17,836
17,443
17,837
17,444
17,445
17,447
17,449
17,451
17,453
17,455

TNOV1R
NOV2
TNOV2
FRQ1
TFRQ1
FRQ2
TFRQ2
FRQ3
TFRQ3
FRQ4
TFRQ4
FVBLK
TRDY
TD1
TD2
TD3
TD4
TD5
TW

0.0 - 300.0
1.0 - 130.0
0.00 - 300.00
-10.00 - +10.00
0.00 - 300.00
-10.00 - +10.00
0.00 - 300.00
-10.00 - +10.00
0.00 - 300.00
-10.00 - +10.00
0.00 - 300.00
40.0 - 100.0
0.0 - 600.0
0.01 - 300.00
0.01 - 300.00
0.01 - 300.00
0.01 - 300.00
0.01 - 300.00
0.01 - 10.00

s
V
s
Hz
s
Hz
s
Hz
s
Hz
s
V
s
s
s
s
s
s
s

334

17,456 17,532 17,608 17,684

TSUC

0.0 - 600.0

335

17,457 17,533 17,609 17,685

TRCOV

0.1 - 600.0

336

17,458 17,534 17,610 17,686

TARCP

0.1 - 600.0

337

17,459 17,535 17,611 17,687

TRSET

0.01 - 300.00

ARC reset time in CB closing mode.

338
339

17,841 18,021 18,201 18,381


17,842 18,022 18,202 18,382

OC
EF

340

17,843 18,023 18,203 18,383

SE

0.1 - 250.0 0.02 - 50.00


0.1 - 250.0 0.02 - 50.00
0.1 - 40.0 0.02 - 8.00
0.01 - 1.00 0.002-0.200

A
A
A
A

For Co-ordination
ditto
ditto (Model 430)
ditto

341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356

18,454
18,455
18,456
18,457
18,458
18,459
18,460
18,461
18,462
18,463
18,464
18,448
18,449
18,451
18,452
18,453

357

18,432 18,496 18,560 18,624

18,007
18,008
17,513
18,009

18,011
18,012
17,515
18,013
17,516
18,014
17,517
18,015
17,518
18,016
17,519
18,017
17,520
17,521
17,523
17,525
17,527
17,529
17,531

18,518
18,519
18,520
18,521
18,522
18,523
18,524
18,525
18,526
18,527
18,528
18,512
18,513
18,515
18,516
18,517

18,187
18,188
17,589
18,189

18,191
18,192
17,591
18,193
17,592
18,194
17,593
18,195
17,594
18,196
17,595
18,197
17,596
17,597
17,599
17,601
17,603
17,605
17,607

18,582
18,583
18,584
18,585
18,586
18,587
18,588
18,589
18,590
18,591
18,592
18,576
18,577
18,579
18,580
18,581

18,367
18,368
17,665
18,369

18,371
18,372
17,667
18,373
17,668
18,374
17,669
18,375
17,670
18,376
17,671
18,377
17,672
17,673
17,675
17,677
17,679
17,681
17,683

18,646
18,647
18,648
18,649
18,650
18,651
18,652
18,653
18,654
18,655
18,656
18,640
18,641
18,643
18,644
18,645

NOV

FRQ

ARC

FL

Parameters

System

X1
X0
R1
R0
Kab
Kbc
Kca
Ka
Kb
Kc
LINE
OCCT
EFCT
SEFCT
PVT
RVT

0.002-0.200
-0.00-199.99 0.0-999.9
0.00-199.99 0.0-999.9
0.00-199.99 0.0-999.9
0.00-199.99 0.0-999.9
80 - 120
80 - 120
80 - 120
80 - 120
80 - 120
80 - 120
0.0 - 399.9
1-20000
1-20000
1-20000
1-20000
1 - 20000

A
OHM
OHM
OHM
OHM
%
%
%
%
%
%
km
--

--

ditto (5A SEF: Low Level )


ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
Phase CT ratio
Residual CT ratio
SEF CT ratio
Phase VT ratio
Residual VT ratio

Line name

Specified by user

--

Line name

266

Default Setting of Relay Series(5A rating / 1A rating)


110
400
430
420
--

2.5 / 0.50

--

0.00

--

120.0

--

1.00

--

1.00

-------

0.0
95
140.0
1.00
95
60.0

--

1.00

--

1.00

-----

0.0
40.0
1.00
10.0
20.0
1.00
1.00
0.0
40.0
1.00

--

20.0

--

1.00

--

1.00

-------------

0.0
40.0
1.00
-1.00
1.00
-1.00
1.00
-1.00
1.00
-1.00
1.00
40.0
60.0
10.00
10.00
10.00
10.00
10.00
2.00
3.00
10.0
10.0
3.00

--0.05/0.010
-------------400
--

5.0 / 1.00
1.5 / 0.30
-1.5 / 0.30
--2.00 / 10.0
6.80 / 34.0
0.20 / 1.0
0.70 / 3.5
100
100
100
100
100
100
50.0
400
400
-100
100
Specified by user

-0.05/0.010
0.0010

400

User
Setting

6 F 2 S 0 7 5 8
(Setting 2)
Modbus address
No.
1
2

Range

Name
comm

5A rating
Plant name
Description

Contents
Units

Def ault Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

1A rating

19,264
19,280

Notes

---

Plant name
Description

19,437

Records

TCAEN

19,435

TCSPEN

19,436

CBSMEN

Of f / On

--

6
7
8
9
10

19,438
19,439
19,440
19,441
19,442

IyAEN
OPTAEN
TCALM
IyALM
YVALUE

Of f / On
Of f / On
1 - 10000
10 - 10000
1.0 - 2.0

---E6
--

Of f / On

--

Of f / On / Opt-On

--

Trip CounterAlarm Enable


Of f
Trip Circuit Supervision
Of f
Enable
CB condition super visor
Of f
enable
I^y Alarm Enable
Of f
Operate Time Alarm Enable
Of f
Trip Count Alarm Threshold
10000
I^y Alarm
10000
Y value
2.0
Operate Time Alarm
1000
Threshold
Fault Locator Enable
Of f
Record time
2.0
OC
-10.0 / 2.00
EF
3.0 / 0.60
-3.0 / 0.60
EF f or Model 430
-3.0 / 0.60
-SEF
1.00 / 0.200
-1.00 / 0.200
SEF (5A SEF:Low Level)
-0.200
NOC
-2.0 / 0.40
OV
-120.0
UV
-60.0
ZOV
20.0
NOV
-20.0
Disturbance trigger Trip
On
Disturbance trigger BI
On
Disturbance trigger OC
-On
Disturbance trigger EF
On
Disturbance trigger SEF
On
-On
Disturbance trigger NC
-On
Disturbance trigger OV
-On
Disturbance trigger UV
-On
Disturbance trigger ZOV
On
Disturbance trigger NOV
-On
Disturbance record binary
(Ref er to the "GRD140(Disturbance)" sheet.)
signal #1
Disturbance record binary
ditto
signal #2
Disturbance record binary
ditto
signal #3
Disturbance record binary
ditto
signal #4
Disturbance record binary
ditto
signal #5
Disturbance record binary
ditto
signal #6
Disturbance record binary
ditto
signal #7
Disturbance record binary
ditto
signal #8
Disturbance record binary
ditto
signal #9
Disturbance record binary
ditto
signal #10
Disturbance record binary
ditto
signal #11
Disturbance record binary
ditto
signal #12
Disturbance record binary
ditto
signal #13
Disturbance record binary
ditto
signal #14
Disturbance record binary
ditto
signal #15
Disturbance record binary
ditto
signal #16
Disturbance record binary
ditto
signal #17
Disturbance record binary
ditto
signal #18
Disturbance record binary
ditto
signal #19
Disturbance record binary
ditto
signal #20
Disturbance record binary
ditto
signal #21
Disturbance record binary
ditto
signal #22
Disturbance record binary
ditto
signal #23
Disturbance record binary
ditto
signal #24
Disturbance record binary
ditto
signal #25
Disturbance record binary
ditto
signal #26
Disturbance record binary
ditto
signal #27

11

19,443

OPTALM

100 - 5000

ms

12
13
14
15

19,460
19,392
19,393
19,394

Fault locator
Time
OC
EF

16

19,395

SEF

17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

19,396
19,452
19,453
19,454
19,455
19,397
19,398
19,399
19,400
19,401
19,402
19,456
19,457
19,458
19,459

NC
OV
UV
ZOV
NOV
Trip
BI
OC
EF
SEF
NC
OV
UV
ZOV
NOV

Of f / On
0.1 - 3.0
0.1 - 250.0
0.02 - 50.00
0.1 - 250.0
0.02 - 50.00
0.1 - 40.0
0.02 - 8.00
0.01 - 1.00
0.002-0.200
0.002-0.200
-0.5 - 10.0
0.10 - 2.00
10.0 - 200.0
1.0 - 130.0
1.0 - 130.0
1.0 - 130.0
Of f / On
Of f / On
Of f / On
Of f / On
Of f / On
Of f / On
Of f / On
Of f / On
Of f / On
Of f / On

-s
A
A
A
A
A
A
V
V
V
V
-----------

32

19,403

SIG1

0 - 500

--

33

19,404

SIG2

0 - 500

--

34

19,405

SIG3

0 - 500

--

35

19,406

SIG4

0 - 500

--

36

19,407

SIG5

0 - 500

--

37

19,408

SIG6

0 - 500

--

38

19,409

SIG7

0 - 500

--

39

19,410

SIG8

0 - 500

--

40

19,411

SIG9

0 - 500

--

41

19,412

SIG10

0 - 500

--

42

19,413

SIG11

0 - 500

--

43

19,414

SIG12

0 - 500

--

44

19,415

SIG13

0 - 500

--

45

19,416

SIG14

0 - 500

--

46

19,417

SIG15

0 - 500

--

47

19,418

SIG16

0 - 500

--

48

19,419

SIG17

0 - 500

--

49

19,420

SIG18

0 - 500

--

50

19,421

SIG19

0 - 500

--

51

19,422

SIG20

0 - 500

--

52

19,423

SIG21

0 - 500

--

53

19,424

SIG22

0 - 500

--

54

19,425

SIG23

0 - 500

--

55

19,426

SIG24

0 - 500

--

56

19,427

SIG25

0 - 500

--

57

19,428

SIG26

0 - 500

--

58

19,429

SIG27

0 - 500

--

267

no-name
no-data

User
Setting

6 F 2 S 0 7 5 8
Modbus address
No.

Range

Name
comm

5A rating

Contents
Units

1A rating

59 19,430

SIG28

0 - 500

--

60 19,431

SIG29

0 - 500

--

61 19,432

SIG30

0 - 500

--

62 19,433

SIG31

0 - 500

--

63 19,434

SIG32

0 - 500

--

1-32
0 - 254
1-247
0 - 500
0 - 500
0 - 500
0 - 500
0-7
0-7
0-7
0-7
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 255
0 - 255
0 - 255
0 - 255
0 - 255
0 - 255
0 - 255
0 - 255
HDLC/IEC/MOD
9.6/19.2/57.6
9.6/19.2
9.6/19.2
Normal/Blocked
1.2/2.4
1.2/2.4
1.2/2.4
1.2/2.4
Prim./Second/km
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
No/Yes
None/Operate/Reset/Both
None/Operate/Reset/Both
None/Operate/Reset/Both
None/Operate/Reset/Both
None/Operate/Reset/Both
None/Operate/Reset/Both
None/Operate/Reset/Both
None/Operate/Reset/Both

64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116

19,712
19,713
19,756
19,728
19,729
19,730
19,731
19,732
19,733
19,734
19,735
19,736
19,737
19,738
19,739
19,740
19,741
19,742
19,743
19,744
19,745
19,746
19,747
19,748
19,749
19,750
19,751
19,714
19,715
19,716
19,755
19,717
19,718
19,719
19,720
19,721
19,754
19,722
19,723
19,724
19,725
19,726
19,727
19,752
19,753
19,444
19,445
19,446
19,447
19,448
19,449
19,450
19,451

HDLC
IEC
MODBUS
IECB1
IECB2
IECB3
IECB4
IECGT
IECAT
IECBT
IECCT
IECE1
IECE2
IECE3
IECE4
IECE5
IECE6
IECE7
IECE8
IECI1
IECI2
IECI3
IECI4
IECI5
IECI6
IECI7
IECI8
Protocol
232C
IECBR
MODBR
IECBLK
IECNFI
IECNFV
IECNFP
IECNFf
IECFL
IECGI1
IECGI2
IECGI3
IECGI4
IECGI5
IECGI6
IECGI7
IECGI8
BI1 comm.
BI2 comm.
BI3 comm.
BI4 comm.
BI5 comm.
BI6 comm.
BI7 comm.
BI8 comm.

117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136

20,648
20,678
20,708
20,738
20,096
20,097
20,159
20,160
20,222
20,223
20,285
20,286
20,348
20,349
20,411
20,412
20,474
20,475
20,537
20,538

Alarm1 Text
Alarm2 Text
Alarm3 Text
Alarm4 Text
BI1PUD
BI1DOD
BI2PUD
BI2DOD
BI3PUD
BI3DOD
BI4PUD
BI4DOD
BI5PUD
BI5DOD
BI6PUD
BI6DOD
BI7PUD
BI7DOD
BI8PUD
BI8DOD

137

20,098 20,161 20,224 20,287 20,350 20,413 20,476 20,539

BI1SNS

138

20,099 20,162 20,225 20,288 20,351 20,414 20,477 20,540

BI1SGS

Def ault Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

Disturbance record binary


signal #28
Disturbance record binary
signal #29
Disturbance record binary
signal #30
Disturbance record binary
signal #31
Disturbance record binary
signal #32
Address for RSM100
Address for IEC103
Address for Modbus
IEC user specif ied signal 1
IEC user specif ied signal 2
IEC user specif ied signal 3
IEC user specif ied signal 4
IEC Trip A phase
IEC Trip B phase
IEC Trip C phase
IEC General Trip
IEC user event 1
IEC user event 2
IEC user event 3
IEC user event 4
IEC user event 5
IEC user event 6
IEC user event 7
IEC user event 8
IEC user INF 1
IEC user INF 2
IEC user INF 3
IEC user INF 4
IEC user INF 5
IEC user INF 6
IEC user INF 7
IEC user INF 8
Switch for communications
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
ditto
IEC event type setting 1
IEC event type setting 2
IEC event type setting 3
IEC event type setting 4
IEC event type setting 5
IEC event type setting 6
IEC event type setting 7
IEC event type setting 8
BI 1 command trigger
BI 2 command trigger
BI 3 command trigger
BI 4 command trigger
BI 5 command trigger
BI 6 command trigger
BI 7 command trigger
BI 8 command trigger

ditto
ditto
ditto
ditto
ditto

Both(3)
Both(3)
Both(3)

Specified by user
Alarm1 Text
Specified by user
Alarm2 Text
Specified by user
Alarm3 Text
Specified by user
Alarm4 Text
0.00 - 300.00
s Binary Input 1 Pick-up
0.00 - 300.00
s Binary Input 1 Drop-off
0.00 - 300.00
s Binary Input 2 Pick-up
0.00 - 300.00
s Binary Input 2 Drop-off
0.00 - 300.00
s Binary Input 3 Pick-up
0.00 - 300.00
s Binary Input 3 Drop-off
0.00 - 300.00
s Binary Input 4 Pick-up
0.00 - 300.00
s Binary Input 4 Drop-off
0.00 - 300.00
s Binary Input 5 Pick-up
0.00 - 300.00
s Binary Input 5 Drop-off
0.00 - 300.00
s Binary Input 6 Pick-up
0.00
0.00 - 300.00
s Binary Input 6 Drop-off
0.00
0.00 - 300.00
s Binary Input 7 Pick-up
0.00
0.00 - 300.00
s Binary Input 7 Drop-off
0.00
0.00 - 300.00
s Binary Input 8 Pick-up
0.00
0.00 - 300.00
s Binary Input 8 Drop-off
0.00
Repeat Following Switches f rom Binary Input 2 to Binary Input 8.
Norm/Inv
Binary Input 1 Sense
Binary Input 1 Settings
Off/1/2/3/4
Group Select

268

1
2
1
1
2
3
4
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
HDLC(0)
9.6(0)
19.2(1)
19.2(1)
Normal(0)
2.4(1)
1.2(0)
2.4(1)
1.2(0)
Prim.(0)
No(0)
No(0)
No(0)
No(0)
No(0)
No(0)
No(0)
No(0)
Both(3)
Both(3)
Both(3)
Both(3)
Both(3)
--(Both(3))
--(Both(3))
--(Both(3))
ALARM 1
ALARM 2
ALARM 3
ALARM 4
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
--(0.00)
--(0.00)
--(0.00)
--(0.00)
--(0.00)
--(0.00)
Normal
Off

User
Setting

6 F 2 S 0 7 5 8
Modbus address
No.

Range

Name
comm

139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161

20,100
20,101
20,102
20,103
20,104
20,105
20,106
20,107
20,108
20,109
20,110
20,111
20,112
20,113
20,114
20,115
20,116
20,117
20,118
20,119
20,120
20,121
20,122

20,163
20,164
20,165
20,166
20,167
20,168
20,169
20,170
20,171
20,172
20,173
20,174
20,175
20,176
20,177
20,178
20,179
20,180
20,181
20,182
20,183
20,184
20,185

20,226
20,227
20,228
20,229
20,230
20,231
20,232
20,233
20,234
20,235
20,236
20,237
20,238
20,239
20,240
20,241
20,242
20,243
20,244
20,245
20,246
20,247
20,248

20,289
20,290
20,291
20,292
20,293
20,294
20,295
20,296
20,297
20,298
20,299
20,300
20,301
20,302
20,303
20,304
20,305
20,306
20,307
20,308
20,309
20,310
20,311

20,352
20,353
20,354
20,355
20,356
20,357
20,358
20,359
20,360
20,361
20,362
20,363
20,364
20,365
20,366
20,367
20,368
20,369
20,370
20,371
20,372
20,373
20,374

20,415
20,416
20,417
20,418
20,419
20,420
20,421
20,422
20,423
20,424
20,425
20,426
20,427
20,428
20,429
20,430
20,431
20,432
20,433
20,434
20,435
20,436
20,437

20,478
20,479
20,480
20,481
20,482
20,483
20,484
20,485
20,486
20,487
20,488
20,489
20,490
20,491
20,492
20,493
20,494
20,495
20,496
20,497
20,498
20,499
20,500

20,541
20,542
20,543
20,544
20,545
20,546
20,547
20,548
20,549
20,550
20,551
20,552
20,553
20,554
20,555
20,556
20,557
20,558
20,559
20,560
20,561
20,562
20,563

OC1BLK
OC2BLK
OC3BLK
OC4BLK
EF1BLK
EF2BLK
EF3BLK
EF4BLK
EF1PER
EF2PER
EF3PER
EF4PER
SE1BLK
SE2BLK
SE3BLK
SE4BLK
NC1BLK
NC2BLK
UC1BLK
UC2BLK
CBFBLK
THMBLK
THMABLK

Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On

162

20,123 20,186 20,249 20,312 20,375 20,438 20,501 20,564

BCDBLK

Off /On

163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197

20,124
20,125
20,126
20,127
20,128
20,129
20,130
20,131
20,132
20,133
20,134
20,135
20,136
20,137
20,138
20,139
20,140
20,141
20,142
20,143
20,144
20,145
20,146
20,147
20,148
20,149
20,150
20,151
20,152
20,153
20,154
20,155
20,156
20,157
20,158

20,187
20,188
20,189
20,190
20,191
20,192
20,193
20,194
20,195
20,196
20,197
20,198
20,199
20,200
20,201
20,202
20,203
20,204
20,205
20,206
20,207
20,208
20,209
20,210
20,211
20,212
20,213
20,214
20,215
20,216
20,217
20,218
20,219
20,220
20,221

20,250
20,251
20,252
20,253
20,254
20,255
20,256
20,257
20,258
20,259
20,260
20,261
20,262
20,263
20,264
20,265
20,266
20,267
20,268
20,269
20,270
20,271
20,272
20,273
20,274
20,275
20,276
20,277
20,278
20,279
20,280
20,281
20,282
20,283
20,284

OV1BLK
OV2BLK
UV1BLK
UV2BLK
ZOV1BLK
ZOV2BLK
NOV1BLK
NOV2BLK
FRQ1BLK
FRQ2BLK
FRQ3BLK
FRQ4BLK
ARCBLK
ARCRDY
ARCINI
MNLCLS
ARCNA
CTFBLK
VTFBLK
CTFEXT
VTFEXT
EXTAPH
EXTBPH
EXTCPH
EXT3PH
TCFALM
CBOPN
CBCLS
RMTRST
SYNCLK
STORCD
Alarm1
Alarm2
Alarm3
Alarm4

Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On
Off /On

198
199
200
201
202
203

22,176
22,177
22,144
22,145
22,146
22,147

22,178
22,179
22,148
22,149
22,150
22,151

22,180
22,181
22,152
22,153
22,154
22,155

Logic
Reset
In #1
In #2
In #3
In #4

OR/AND
Inst/Latch
0 - 500
0 - 500
0 - 500
0 - 500

204
205
206
207
208
209
210
211
212
213
214

22,224
22,192
22,193
22,194
22,195
22,196
22,197
22,198
22,199

22,225
22,200
22,201
22,202
22,203
22,204
22,205
22,206
22,207

Reset
BIT1
BIT2
BIT3
BIT4
BIT5
BIT6
BIT7
BIT8
Term A
Term B

Inst/Latch
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500
0 - 500

20,313
20,314
20,315
20,316
20,317
20,318
20,319
20,320
20,321
20,322
20,323
20,324
20,325
20,326
20,327
20,328
20,329
20,330
20,331
20,332
20,333
20,334
20,335
20,336
20,337
20,338
20,339
20,340
20,341
20,342
20,343
20,344
20,345
20,346
20,347

20,376
20,377
20,378
20,379
20,380
20,381
20,382
20,383
20,384
20,385
20,386
20,387
20,388
20,389
20,390
20,391
20,392
20,393
20,394
20,395
20,396
20,397
20,398
20,399
20,400
20,401
20,402
20,403
20,404
20,405
20,406
20,407
20,408
20,409
20,410

20,439
20,440
20,441
20,442
20,443
20,444
20,445
20,446
20,447
20,448
20,449
20,450
20,451
20,452
20,453
20,454
20,455
20,456
20,457
20,458
20,459
20,460
20,461
20,462
20,463
20,464
20,465
20,466
20,467
20,468
20,469
20,470
20,471
20,472
20,473

20,502
20,503
20,504
20,505
20,506
20,507
20,508
20,509
20,510
20,511
20,512
20,513
20,514
20,515
20,516
20,517
20,518
20,519
20,520
20,521
20,522
20,523
20,524
20,525
20,526
20,527
20,528
20,529
20,530
20,531
20,532
20,533
20,534
20,535
20,536

20,565
20,566
20,567
20,568
20,569
20,570
20,571
20,572
20,573
20,574
20,575
20,576
20,577
20,578
20,579
20,580
20,581
20,582
20,583
20,584
20,585
20,586
20,587
20,588
20,589
20,590
20,591
20,592
20,593
20,594
20,595
20,596
20,597
20,598
20,599

5A rating

Contents
Units

Def ault Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

1A rating

269

OC1 Block
--(Off )
OC2 Block
--(Off )
OC3 Block
--(Off )
OC4 Block
--(Off )
EF1 Block
EF2 Block
EF3 Block
EF4 Block
EF1 Permission
EF2 Permission
EF3 Permission
EF4 Permission
SEF1 Block
Off
SEF2 Block
Off
SEF3 Block
Off
SEF4 Block
Off
NC1 Block
--(Off )
NC2 Block
--(Off )
Undercurrent 1 Block
--(Off )
Undercurrent 2 Block
--(Off )
CBF Block
--(Off )
Thermal Protection Block
--(Off )
Thermal Alarm Block
--(Off )
Broken Conductor
--(Off )
Protection Block
OV1 Block
--(Off )
OV2 Block
--(Off )
UV1 Block
--(Off )
UV2 Block
--(Off )
ZOV1 Block
ZOV2 Block
NOV1 Block
--(Off )
NOV2 Block
--(Off )
FRQ1 Block
--(Off )
FRQ2 Block
--(Off )
FRQ3 Block
--(Off )
FRQ4 Block
--(Off )
Autoreclose Block
Autoreclose Ready
Autoreclose Initiation
Manual Close
Autoreclose Not Applicated
CTF Block
--(Off )
VTF Block
--(Off )
External CTF
--(Off )
External VTF
--(Off )
External Trip - Aphase
External Trip - Bphase
External Trip - Cphase
External Trip - 3phase
Trip Circuit Fail Alarm
Circuit Breaker Open
Circuit Breaker Close
Remote Reset
Synchronize clock
Store Disturbance Record
Alarm screen 1.
Alarm screen 2.
Alarm screen 3.
Alarm screen 4.
Repeat Following Switches from LED 2 to LED3.
LED1 Logic Gate Type
LED1 Reset operation
LED Functions
ditto
ditto
ditto
Repeat Following Switches for IND2.
IND1 Reset operation
Virtual LED
ditto
ditto
ditto
ditto
ditto
ditto
ditto
Logic circuit Functions
ditto

Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
--(Off)
--(Off)
--(Off)
--(Off)

Of f
Of f
Of f
Of f
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off

Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
OR
Inst
0
0
0
0
Inst
0
0
0
0
0
0
0
0
0
0

User
Setting

6 F 2 S 0 7 5 8
Modbus address
No.

Name
comm

215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231

19,840
19,845
19,841
19,843
19,844

Range
5A rating

Status

Display
Display-Wh
Time sync.
Power
Current
Count-Wh+
Wh+
Wh+
Count-WhWhWhCount-v ah+
vah+
vah+
Count-vahvahvah-

Contents
Units

Def ault Setting of Relay Series(5A rating / 1A rating)


110
400
430
420

1A rating

Pri / Sec / Pri-A


kWh/ MWh
Of / BI / RSM / IEC / M
Send / Receive
Lag / Lead
0 - 999
0 - 999999
0 - 999
0 - 999999
0 - 999
0 - 999999
0 - 999
0 - 999999

------

metering
Unit of Wh/vah
time sy nc source

Wh+ Counter
kWh Wh+ (lower word)
or Wh+ (upper word)
Wh- Counter
kWh Wh- (lower word)
or Wh- (upper word)
vah+ Counter
kvah varh+ (lower word)
or varh+ (upper word)
vah- Counter
kvah varh- (lower word)
or varh- (upper word)

Pri
--

kWh
Of
Send
Lead

--

--

--

--

--

--

--

--

Repeat Following Switches f or BO2-BO7


232
233
234
235
236
237
238

22,312
22,313
22,272
22,273
22,274
22,275
22,276

22,314
22,315
22,277
22,278
22,279
22,280
22,281

22,316
22,317
22,282
22,283
22,284
22,285
22,286

22,318
22,319
22,287
22,288
22,289
22,290
22,291

22,320
22,321
22,292
22,293
22,294
22,295
22,296

22,322
22,323
22,297
22,298
22,299
22,300
22,301

22,324
22,325
22,302
22,303
22,304
22,305
22,306

Binary
Output

Logic
Reset
In #1
In #2
In #3
In #4
TBO

OR/AND
INS/DL/DW/LAT
0 - 500
0 - 500
0 - 500
0 - 500
0.00 - 10.00

270

BO logic
BO time delay
BO signal.
ditto
ditto
ditto
BO delay timer

See BO setting sheet


ditto
ditto
ditto
ditto
ditto
ditto

User
Setting

6 F 2 S 0 7 5 8
5. Disturbance record setting
Name

Range

SIG1
SIG2
SIG3
SIG4
SIG5
SIG6
SIG7
SIG8
SIG9
SIG10
SIG11
SIG12
SIG13
SIG14
SIG15
SIG16
SIG17
SIG18
SIG19
SIG20
SIG21
SIG22
SIG23
SIG24
SIG25
SIG26
SIG27
SIG28
SIG29
SIG30
SIG31

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500
- 500

Unit

NO.
131
281
141
291
211
351
0
0
0
0
0
0
0
0
0
371
401
61
403
0
0
0
0
0
0
0
0
0
0
0
0

110
Signal name
EF1
EF1 TRIP
SEF1
SEF1-S1 TRIP
ZOV1
ZOV1 TRIP

GEN.TRIP
ARC READY T
ARC BLOCK
ARC SHOT

NO.
101
102
103
261
131
281
201
202
203
341
211
351
0
0
0
371
401
61
403
0
0
0
0
0
0
0
0
0
0
0
0

Default
400
Signal name
OC1-A
OC1-B
OC1-C
OC1 TRIP
EF1
EF1 TRIP
UV1-A
UV1-B
UV1-C
UV1 TRIP
ZOV1
ZOV1 TRIP

GEN.TRIP
ARC READY T
ARC BLOCK
ARC SHOT

setting
NO.
101
102
103
261
131
281
141
291
201
202
203
341
211
351
0
371
401
61
403
0
0
0
0
0
0
0
0
0
0
0
0

420
Signal name
OC1-A
OC1-B
OC1-C
OC1 TRIP
EF1
EF1 TRIP
SEF1
SEF1-S1 TRIP
UV1-A
UV1-B
UV1-C
UV1 TRIP
ZOV1
ZOV1 TRIP
GEN.TRIP
ARC READY T
ARC BLOCK
ARC SHOT

NO.
101
102
103
261
131
281
201
202
203
341
211
351
0
0
0
371
401
61
403
0
0
0
0
0
0
0
0
0
0
0
0

430
Signal name
OC1-A
OC1-B
OC1-C
OC1 TRIP
EF1
EF1 TRIP
UV1-A
UV1-B
UV1-C
UV1 TRIP
ZOV1
ZOV1 TRIP

GEN.TRIP
ARC READY T
ARC BLOCK
ARC SHOT

6. LED setting
LED1 - LED3 setting
LED
LED1

Logic
OR / AND

Setting range
Reset
Inst/Latch

LED2

OR / AND

Inst/Latch

LED3

OR / AND

Inst/Latch

Default Setting
Functions
Logic Reset
Functions
In #1 0-500 OR
Inst
In #1
0
In #2 0-500
In #2
0
In #3 0-500
In #3
0
In #4 0-500
In #4
0
In #1 0-500 OR
Inst
In #1
0
In #2 0-500
In #2
0
In #3 0-500
In #3
0
In #4 0-500
In #4
0
In #1 0-500 OR
Inst
In #1
0
In #2 0-500
In #2
0
In #3 0-500
In #3
0
In #4 0-500
In #4
0

Logic Reset

Setting
Functions
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4
In #1
In #2
In #3
In #4

User setting of Virtual LED


Setting range
LED

Reset

Default setting

Setting

Functions

Reset

Functions

IND1 Inst / Latch

0 - 500

Inst

BIT1 - BIT8 : 0

IND2 Inst / Latch

0 - 500

Inst

BIT1 - BIT8 : 0

BIT1

BIT2

271

BIT3

BIT4

BIT5

BIT6

BIT7

BIT8

Setting

6 F 2 S 0 7 5 8

272

6 F 2 S 0 7 5 8

Appendix I
Commissioning Test Sheet (sample)
1. Relay identification
2. Preliminary check
3. Hardware check
4. Function test
5. Protection scheme test
6. Metering and recording check
7. Conjunctive test

273

6 F 2 S 0 7 5 8
1.

Relay identification

Type

Serial number

Model

System frequency

Station

Date

Circuit

Engineer

Protection scheme

Witness

Active settings group number


2.

Preliminary check

Ratings
CT shorting contacts
DC power supply
Power up
Wiring
Relay inoperative
alarm contact
Calendar and clock
3.

Hardware check

3.1 User interface check


3.2 Binary input/binary output circuit check
Binary input circuit
Binary output circuit
3.3 AC input circuit

274

6 F 2 S 0 7 5 8
4.

Function test

4.1 Overcurrent elements test


(1) Operating value test
Element

Current setting

Measured current

Element

OC1-A

UC1-A

OC2-A

UC2-A

OC3-A

THM-A

OC4-A

THM-T

EF1

NOC1

EF2

NOC2

EF3

CBF-A

Current setting

Measured current

EF4
SEF1
SEF2
SEF3
SEF4

(2) Operating time test (IDMT)


Element

Curve setting

Multiplier setting

Changed current

Measured time

OC1-A

Current setting
Current setting
Current setting

EF1

Current setting
Current setting
Current setting

SEF1

Current setting
Current setting
Current setting

(3) Directional operate characteristic test


Element

Current setting

Measured current

Element

OC1-A

SEF1

OC2-A

SEF2

OC3-A

SEF3

OC4-A

SEF4

EF1

NOC1

EF2

NOC2

EF3
EF4

275

Current setting

Measured current

6 F 2 S 0 7 5 8
4.2 Overvoltage and undervoltage elements test
(1) Operating value test
Element

Voltage
setting

Measured
voltage

Element

OV1

ZOV1

OV2

ZOV2

UV1

NOV1

UV2

NOV2

Voltage
setting

Measured
voltage

(2) Operating time test (IDMT)


Element

Voltage setting

Multiplier setting

Changed voltage

OV1

Voltage setting
Voltage setting
Voltage setting

UV1

Voltage setting
Voltage setting
Voltage setting

ZOV1

Voltage setting
Voltage setting
Voltage setting

NOV1

Voltage setting
Voltage setting
Voltage setting

Measured time

4.3 BCD element check


4.4 Cold load function check
4.5 Frequency elements test
Element

Frequency setting

FRQ1
FRQ2
FRQ3
FRQ4

5.

Protection scheme test

6.

Metering and recording check

7.

Conjunctive test
Scheme

Results

On load check
Tripping circuit
Reclosing circuit

276

Measured frequency

6 F 2 S 0 7 5 8

Appendix J
Return Repair Form

277

6 F 2 S 0 7 5 8

RETURN / REPAIR FORM


Please fill in this form and return it to Toshiba Corporation with the GRD140 to be repaired.

Type:

Model:

GRD140

(Example: Type:

GRD140

Model:

400A

Product No.:
Serial No.:
Date:
1.

Reason for returning the relay


mal-function
does not operate
increased error
investigation
others

2.

Fault records, event records or disturbance records stored in the relay and relay settings are
very helpful information to investigate the incident.
Please provide relevant information regarding the incident on floppy disk, or fill in the
attached fault record sheet and relay setting sheet.

278

6 F 2 S 0 7 5 8
Fault Record
Date/Month/Year
/
:

Time

/
:

(Example: 04/ Jul./ 2002

15:09:58.442)

Faulty phase:
Prefault values
Ia:
Ib :
Ic:
Ie:
Ise:
I1 :
I2 :
I2 / I1 :

Fault values
Ia:
Ib :
Ic:
Ie:
Ise:
I1 :
I2 :
I2 / I1 :
THM:

A
A
A
A
A
A
A

Van :
Vbn :
Vcn :
Ve:
Vab:
Vbc:
Vca:
V0:
V1:
V2:
f:

V
V
V
V
V
V
V
V
V
V
Hz

A
A
A
A
A
A
A

Van :
Vbn :
Vcn :
Ve:
Vab:
Vbc:
Vca:
V0:
V1:
V2:
f:

V
V
V
V
V
V
V
V
V
V
Hz

279

6 F 2 S 0 7 5 8
3.

What was the message on the LCD display at the time of the incident?

4.

Describe the details of the incident:

5.

Date incident occurred


Day/Month/Year:

(Example: 10/July/2002)
6.

Give any comments about the GRD140, including the documents:

Customer
Name:
Company Name:
Address:

Telephone No.:
Facsimile No.:
Signature:

280

6 F 2 S 0 7 5 8

Appendix K
Technical Data

281

6 F 2 S 0 7 5 8

TECHNICAL DATA
Ratings
AC current In:

1A or 5A

AC voltage Vn:

100V to 120 V

Frequency:

50Hz or 60Hz

DC auxiliary supply:

110/125Vdc (Operative range: 88 - 150Vdc)


220/250Vdc (Operative range: 176 - 300Vdc)
48/54/60Vdc (Operative range: 38.4 - 72Vdc)
24/30Vdc (Operative range: 19.2 - 36Vdc)

Superimposed AC ripple on DC supply:

maximum 12%

DC supply interruption:

maximum 50ms at 110V

Binary input circuit DC voltage:

110/125Vdc
220/250Vdc
48/54/60Vdc
24/30Vdc

Overload Ratings
AC current inputs:

4 times rated current continuous


100 times rated current for 1 second

AC voltage inputs:

2 times rated voltage continuous

Burden
AC phase current inputs:

0.1VA (1A rating)


0.2VA (5A rating)

AC earth current inputs:

0.3VA (1A rating)


0.4VA (5A rating)

AC sensitive earth inputs:

0.3VA (1A rating)


0.4VA (5A rating)

AC voltage inputs:

0.1VA (at rated voltage)

DC power supply:

10W (quiescent)
15W (maximum)

Binary input circuit:

0.5W per input at 110Vdc

Current Transformer Requirements


Phase Inputs

Typically 5P20 with rated burden according to load.

Standard Earth Inputs:

Core balance CT or residual connection of phase CTs.

Sensitive Earth Inputs:

Core balance CT.

Directional Phase Overcurrent Protection


P/F 1st Overcurrent threshold:

OFF, 0.02 5.00A in 0.01A steps (1A rating)


OFF, 0.1 25.0A in 0.1A steps (5A rating)

Delay type:

DTL, IEC NI, IEC VI, IEC EI, UK LTI, IEEE MI,
IEEE VI, IEEE EI, US CO8 I, US CO2 STI

IDMTL Time Multiplier Setting TMS:

0.010 1.500 in 0.001 steps

DTL delay:

0.00 300.00s in 0.01s steps

Reset Type:

Definite Time or Dependent Time

Reset Definite Delay:

0.0 300.0s in 0.1s steps

Reset Time Multiplier Setting RTMS:

0.010 1.500 in 0.001 steps

P/F 2nd Overcurrent threshold:

OFF, 0.02 5.00A in 0.01A steps (1A rating)


OFF, 0.1 25.0A in 0.1A steps (5A rating)

P/F 3rd, 4th Overcurrent thresholds:

OFF, 0.02 50.00A in 0.01A steps (1A rating)


OFF, 0.1 250.0A in 0.1A steps (5A rating)

DTL delay:

0.00 300.00s in 0.01s steps

P/F Characteristic Angle:

95 to +95 in 1 steps

282

6 F 2 S 0 7 5 8
Directional Earth Fault Protection
E/F 1st Overcurrent threshold:

OFF, 0.02 5.00A in 0.01A steps (1A rating)


OFF, 0.1 25.0A in 0.1A steps (5A rating)

Delay type:

DTL, IEC NI, IEC VI, IEC EI, UK LTI, IEEE MI,
IEEE VI, IEEE EI, US CO8 I, US CO2 STI

IDMTL Time Multiplier Setting TMS:

0.010 1.500 in 0.001 steps

DTL delay:

0.00 300.00s in 0.01s steps

Reset Type:

Definite Time or Dependent Time

Reset Definite Delay:

0.0 300.0s in 0.1s steps

Reset Time Multiplier Setting RTMS:

0.010 1.500 in 0.001 steps

E/F 2nd threshold:

OFF, 0.02 5.00A in 0.01A steps (1A rating)


OFF, 0.1 25.0A in 0.1A steps (5A rating)

E/F 3rd, 4th thresholds:

OFF, 0.02 50.00A in 0.01A steps (1A rating)


OFF, 0.1 250.0A in 0.1A steps (5A rating)

E/F 3rd, 4th thresholds only for Model 430:

OFF, 0.02 8.00A in 0.01A steps (1A rating)


OFF, 0.1 40.0A in 0.1A steps (5A rating)

DTL delay:

0.00 300.00s in 0.01s steps

E/F Characteristic angle:

95 to +95 in 1 steps

E/F directional voltage threshold:

0.5 100.0V in 0.1V steps

Directional Sensitive Earth Fault Protection


SEF 1st Overcurrent threshold:

OFF, 0.002 0.200A in 0.001A steps (1A rating)


OFF, 0.01 1.00A in 0.01A steps (5A rating)
OFF, 0.002 0.200A in 0.001A steps (5A SEF: Low Level)

Delay Type:

DTL, IEC NI, IEC VI, IEC EI, UK LTI, IEEE MI,
IEEE VI, IEEE EI, US CO8 I, US CO2 STI

IDMTL Time Multiplier Setting TMS:

0.010 1.500 in 0.001 steps

DTL delay:

0.00 300.00s in 0.01s steps

Reset Type:

Definite Time or Dependent Time

Reset Definite Delay:

0.0 300.0s in 0.1s steps

Reset Time Multiplier Setting RTMS:

0.010 1.500 in 0.001 steps

DTL delay (back-up timer):

0.00 300.00s in 0.01s steps

SEF 2nd, 3rd, 4th threshold:

OFF, 0.002 0.200A in 0.001A steps (1A rating)


OFF, 0.01 1.00A in 0.01A steps (5A rating)

DTL delay:

0.00 300.00s in 0.01s steps

SEF Characteristic angle:

95 to +95 in 1 steps

SEF Boundary of operation:

87.5, 90

SEF directional voltage threshold:

0.5 100.0V in 0.1V steps

Residual power threshold:

OFF, 0.00 20.00W in 0.01W steps (1A primary)


OFF, 0.0 100.0W in 0.1W steps (5A primary)

Phase Undercurrent Protection


Undercurrent 1st, 2nd threshold:

OFF, 0.10 2.00A in 0.01A steps (1A rating)


OFF, 0.5 10.0A in 0.1A steps (5A rating)

DTL Delay:

0.00 300.00s in 0.01s steps

Thermal Overload Protection


I = k.IFLC (Thermal setting):
Previous load current (IP)

OFF, 0.40 2.00A in 0.01A steps (1A rating)


OFF, 2.0 10.0A in 0.1A steps (5A rating)
0.00 1.00A in 0.01A steps (1A rating)
0.0 5.0A in 0.1A steps (5A rating)

Time constant ():

0.5 500.0mins in 0.1min steps

Thermal alarm:

OFF, 50% to 99% in 1% steps

283

6 F 2 S 0 7 5 8

Directional Negative Phase Sequence Overcurrent Protection (NOC)


NOC 1st, 2nd threshold:

OFF, 0.10 2.00A in 0.01A steps (1A rating)


OFF, 0.5 10.0A in 0.1A steps (5A rating)

DTL delay:

0.00 300.00s in 0.01s steps

NOC Characteristic angle:

95 to +95 in 1 steps

NOC Directional voltage threshold

0.5 25.0V in 0.1V steps

Overvoltage Protection
1st, 2nd Overvoltage thresholds:

OFF, 10.0 200.0V in 0.1V steps

Delay type (1st threshold only):

DTL, IDMTL

IDMTL Time Multiplier Setting TMS:

0.05 100.00 in 0.01 steps

DTL delay:

0.00 300.00s in 0.01s steps

DO/PU ratio

10 98% in 1% steps

Reset Delay (1st threshold only):

0.0 300.0s in 0.1s steps

Undervoltage Protection
1st, 2nd Undervoltage thresholds:

OFF, 5.0 130.0V in 0.1V steps

Delay type (1st threshold only):

DTL, IDMTL

IDMTL Time Multiplier Setting TMS:

0.05 100.00 in 0.01 steps

DTL delay:

0.00 300.00s in 0.01s steps


st

Reset Delay (1 threshold only):

0.0 300.0s in 0.1s steps

Undervoltage Block

5.0 20.0Vin 0.1V steps

Zero Phase Sequence Overvoltage Protection (ZOV)


1st, 2nd ZOV Overvoltage thresholds:

OFF, 1.0 130.0V in 0.1V steps

Delay type (1st threshold only):

DTL, IDMTL

IDMTL Time Multiplier Setting TMS:

0.05 100.00 in 0.01 steps

DTL delay:

0.00 300.00s in 0.01s steps


st

Reset Delay (1 threshold only):

0.0 300.0s in 0.1s steps

Negative Phase Sequence Overvoltage Protection (NOV)


1st, 2nd NOV Overvoltage thresholds:

OFF, 1.0 130.0V in 0.1V steps

Delay type (1st threshold only):

DTL, IDMTL

IDMTL Time Multiplier Setting TMS:

0.05 100.00 in 0.01 steps

DTL delay:

0.00 300.00s in 0.01s steps


st

Reset Delay (1 threshold only):

0.0 300.0s in 0.1s steps

Under/Over Frequency Protection


1st - 4th under/overfrequency threshold

(Fnom 10.00Hz) (Fnom + 10.00Hz) in 0.01Hz steps


Fnom: nominal frequency

DTL delay:

0.00 300.00s in 0.01s steps

Frequency UV Block

40.0 100.0V in 0.1V steps

Broken Conductor Protection


Broken conductor threshold (I2/I1):

OFF, 0.10 1.00 in 0.01 steps

DTL delay:

0.00 300.00s in 0.01s steps

CBF Protection
CBF threshold:

OFF, 0.10 2.00A in 0.01A steps (1A rating)


OFF, 0.5 10.0A in 0.1A steps (5A rating)

CBF stage 1 (Backup trip) DTL:

0.00 300.00s in 0.01s steps

CBF stage 2 (Re-trip) DTL:

0.00 300.00s in 0.01s steps

284

6 F 2 S 0 7 5 8

Autoreclose
ARC Reclaim Time

0.0 600.0s in 0.1s steps

Close Pulse Width

0.01 10.00s

Lock-out Recovery Time

OFF, 0.1 600.0s in 0.1s steps

Sequences

1 5 Shots to Lock-out, each trip programmable for inst or


Delayed operation

Dead Times(programmable for each shot)

0.01 300.00s in 0.01s steps

in 0.01s steps

Accuracy
Overcurrent Pick-ups:

100% of setting 5%

Overcurrent PU/DO ratio:

100%

Undercurrent Pick-up:

100% of setting 5%

Undercurrent PU/DO ratio:

100%

Overvoltage Pick-ups:
Undervoltage Pick-ups:

100% of setting 5%
100% of setting 5%

Inverse Time Delays:

5% or 30ms (1.5 to 30 times setting)

Definite Time Delays:

1% or 10ms

Transient Overreach for instantaneous elements:

<5% for X/R = 100.

Front Communication port - local PC (RS232)


Connection:

Point to point

Cable type:

Multi-core (straight)

Cable length:

15m (max.)

Connector:

RS232C 9-way D-type female

Rear Communication port - remote PC (RS485)


Connection:

Multidrop (max. 32 relays)

Cable type:

Twisted pair

Cable length:

1200m (max.)

Connector:

Screw terminals

Isolation:

1kVac for 1 min.

Transmission rate:

64kpbs for RSM system


9.6, 19.2kbps for IEC60870-5-103

Rear Communication port - remote PC (Fibre Optic for IEC60870-5-103: option)


Cable type:

50/125 or 62.5/125m fibre

Cable length:

1000m (max.)

Connector:

ST

Transmission rate:

9.6, 19.2kbps for IEC60870-5-103

Time synchronization port


IRIG Time Code
Input impedance
Input voltage range
Connection

IRIG-B122
4k-ohm
4Vp-p to 10Vp-p
Screw type

Binary Inputs
Operating voltage

Typical 74Vdc(min. 70Vdc) for 110V/125Vdc rating


Typical 138Vdc(min. 125Vdc) for 220V/250Vdc rating
Typical 31Vdc(min. 28Vdc) for 48V/54V/60Vdc rating
Typical 15Vdc(min. 13Vdc) for 24/30Vdc rating

285

6 F 2 S 0 7 5 8

Binary Outputs
Number
Ratings:

Durability:

8
Make and carry: 4A continuously
Make and carry: 20A, 220Vdc for 0.5s (L/R5ms)
Break: 0.1A, 220Vdc (L/R=40ms) or 0.2A, 110Vdc (L/R=40ms)
Loaded contact: 10000 operations
Unloaded contact: 100000 operations

Mechanical design
Weight

4.5kg

Case colour

Munsell No. 10YR8/1

Installation

Flush mounting

286

6 F 2 S 0 7 5 8

ENVIRONMENTAL PERFORMANCE
Test

Standards

Details

Atmospheric Environment
Temperature

IEC60068-2-1/2

Operating range: -10C to +55C.


Storage / Transit: -25C to +70C.

Humidity

IEC60068-2-3

56 days at 40C and 93% relative humidity.

Enclosure Protection

IEC60529

IP51

Mechanical Environment
Vibration

IEC60255-21-1

Response - Class 1
Endurance - Class 1

Shock and Bump

IEC60255-21-2

Shock Response Class 1


Shock Withstand Class 1
Bump Class 1

Seismic

IEC60255-21-3

Class 1

Dielectric Withstand

IEC60255-5

2kVrms for 1 minute between all terminals and earth.


2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.

High Voltage Impulse

IEC60255-5

Three positive and three negative impulses of


5kV(peak), 1.2/50s, 0.5J between all terminals and
between all terminals and earth.

Electrical Environment

Electromagnetic Environment
High Frequency
Disturbance / Damped
Oscillatory Wave

IEC60255-22-1 Class 3,
IEC61000-4-12 / EN61000-4-12

1MHz 2.5kV applied to all ports in common mode.


1MHz 1.0kV applied to all ports in differential mode.

Electrostatic
Discharge

IEC60255-22-2 Class 3,
IEC61000-4-2 / EN61000-4-2

6kV contact discharge, 8kV air discharge.

Radiated RF
Electromagnetic
Disturbance

IEC60255-22-3 Class 3,
IEC61000-4-3 / EN61000-4-3

Field strength 10V/m for frequency sweeps of 80MHz to


1GHz and 1.7GHz to 2.2GHz. Additional spot tests at
80, 160, 450, 900 and 1890MHz.

Fast Transient
Disturbance

IEC60255-22-4, IEC61000-4-4 /
EN61000-4-4

4kV, 2.5kHz, 5/50ns applied to all inputs.

Surge Immunity

IEC60255-22-5,
IEC61000-4-5 / EN61000-4-5

1.2/50s surge in common/differential modes:


HV ports: 4kV/2kV (peak)
PSU and I/O ports: 2kV/1kV (peak)
RS485 port: 1kV/0.5kV (peak)

Conducted RF
Electromagnetic
Disturbance

IEC60255-22-6 Class 3,
IEC61000-4-6 / EN61000-4-6

10Vrms applied over frequency range 150kHz to


100MHz. Additional spot tests at 27 and 68MHz.

Power Frequency
Disturbance

IEC60255-22-7, IEC61000-4-16
/ EN61000-4-16

300V 50Hz for 10s applied to ports in common mode.


150V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.

Conducted and
Radiated Emissions

IEC60255-25,
EN55022 Class A,
IEC61000-6-4 / EN61000-6-4

Conducted emissions:
0.15 to 0.50MHz: <79dB (peak) or <66dB (mean)
0.50 to 30MHz: <73dB (peak) or <60dB (mean)
Radiated emissions (at 30m):
30 to 230MHz: <30dB
230 to 1000MHz: <37dB

287

6 F 2 S 0 7 5 8

288

6 F 2 S 0 7 5 8

Appendix L
Symbols Used in Scheme Logic

289

6 F 2 S 0 7 5 8
Symbols used in the scheme logic and their meanings are as follows:
Signal names
Marked with

: Measuring element output signal

Marked with

: Binary signal input from or output to the external equipment

Marked with [

Marked with "

"

Unmarked

Scheme switch

Scheme switch position

: Internal scheme logic signal

AND gates
A

A
B

&

Output

A
&

Output

Output

1
0

Output

Other cases

A
B

Other cases

&

Output

Output

Other cases

OR gates
A
B

Output

Output

Other cases

A
B

Output

Output

Other cases

A
B

Output

Output

Other cases

290

6 F 2 S 0 7 5 8
Signal inversion
A

Output

Output

Timer
t

Delayed pick-up timer with fixed setting

XXX:

Set time

XXX
0

Delayed drop-off timer with fixed setting

XXX:

Set time

XXX
t

Delayed pick-up timer with variable setting

XXX - YYY: Setting range


XXX - YYY
0

Delayed drop-off timer with variable setting

XXX - YYY: Setting range


XXX - YYY

One-shot timer
A

Output

Output

XXX - YYY

XXX - YYY: Setting range


Flip-flop
S
S
F/F

Output

Output

No change

Switch

Output

ON

Scheme switch
A

Output
ON

Other cases

Output
ON

291

Switch

Output

ON

OFF

6 F 2 S 0 7 5 8

292

6 F 2 S 0 7 5 8

Appendix M
IEC60870-5-103: Interoperability

293

6 F 2 S 0 7 5 8
IEC60870-5-103: Interoperability
1. Physical Layer
1.1 Electrical interface: EIA RS-485
Number of loads, 32 for one protection equipment
1.2 Optical interface
Glass fibre (option)
ST type connector (option)
1.3 Transmission speed
User setting: 9600 or 19200 bit/s
2. Application Layer
COMMON ADDRESS of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)
3. IEC60870-5-103 Interface
3.1 Spontaneous events
The events created by the relay will be sent using Function type (FUN) / Information numbers
(INF) to the IEC60870-5-103 master station. 8 wide-use events are provided.
3.2 General interrogation
The GI request can be used to read the status of the relay, the Function types and Information
numbers that will be returned during the GI cycle are shown in the table below.
3.3 Cyclic measurements
The relay will produce measured values using Type ID=3 and 9 on a cyclical basis, this can be
read from the relay using a Class 2 poll. The rate at which the relay produces new measured
values is 2 seconds.
It should be noted that the measurands transmitted by the relay are sent as a proportion of either
1.2 or 2.4 times the rated value of the analog value. Either 1.2 or 2.4 can be selected by the
IECNF setting.
3.4 Commands
A list of the supported commands is contained in the table below. The relay will respond to
other commands with an ASDU 1, with a cause of transmission (COT) of negative
acknowledgement of a command.
3.5 Test mode
In test mode, both spontaneous messages and polled measured values, intended for processing in
the control system, are designated by means of the CAUSE OF TRANSMISSION test mode.
This means that CAUSE OF TRANSMISSION = 7 test mode is used for messages normally
transmitted with COT=1 (spontaneous) or COT=2 (cyclic).
For details, refer to the standard IEC60870-5-103.

294

6 F 2 S 0 7 5 8
3.6 Blocking of monitor direction
If the blocking of the monitor direction is activated in the protection equipment, all indications
and measurands are no longer transmitted.
For details, refer to the standard IEC60870-5-103.
4. List of Information

295

6 F 2 S 0 7 5 8
List of Information
INF

Description

Contents

GI

Type
ID

COT

FUN

Standard Information numbers in monitor direction


System Function
0

End of General Interrogation

Transmission completion of GI items.

--

10

255

Time Synchronization

Time Synchronization ACK.

--

255

Reset FCB

Reset FCB(toggle bit) ACK

--

219

Reset CU

Reset CU ACK

--

219

Start/Restart

Relay start/restart

--

219

Pow er On

Relay pow er on.

Not supported

Status Indications
16

Auto-recloser active

If it is possible to use auto-recloser, this item is set active, if


impossible, inactive.

17

Teleprotection active

If protection using telecommunication is available, this item is set to


active. If not, set to inactive.

18

Protection active

If the protection is available, this item is set to active. If not, set to


inactive.

GI

1, 7, 9, 12,
20, 21

219

19

LED reset

Reset of latched LEDs

--

1, 7, 11, 12,
20, 21

219

20

Monitor direction blocked

Block the 103 transmission from a relay to control system. IECBLK:


"Blocked" setting.

GI

9, 11

219

21

Test mode

Transmission of testmode situation froma relay to control system.


IECTST: "ON" setting.

GI

9, 11

219

22

Local parameter Setting

When a setting change has done at the local, the event is sent to
control system.

23

Characteristic1

Setting group 1 active

GI

1, 7, 9, 11,
12, 20, 21

219

Not supported

Not supported
GI

1, 7, 9, 11,
12, 20, 21

219
219

24

Characteristic2

Setting group 2 active

GI

1, 7, 9, 11,
12, 20, 21

25

Characteristic3

Setting group 3 active

GI

1, 7, 9, 11,
12, 20, 21

219

26

Characteristic4

Setting group 4 active

GI

1, 7, 9, 11,
12, 20, 21

219

27

Auxiliary input1

User specified signal 1 (Signal specified by IECB1: ON) (*1)

GI

1, 7, 9

219

28

Auxiliary input2

User specified signal 2 (Signal specified by IECB2: ON) (*1)

GI

1, 7, 9

219

29

Auxiliary input3

User specified signal 3 (Signal specified by IECB3: ON) (*1)

GI

1, 7, 9

219

30

Auxiliary input4

User specified signal 4 (Signal specified by IECB4: ON) (*1)

GI

1, 7, 9

219

Supervision Indications
32

Measurand supervision I

Zero sequence current supervision

GI

1, 7, 9

219

33

Measurand supervision V

Zero sequence voltage supervision

GI

1, 7, 9

219

35

Phase sequence supervision

Negative sequence voltage supevision

GI

1, 7, 9

219

36

Trip circuit supervision

Output circuit supervision

GI

1, 7, 9

219

37

I>>backup operation

Not supported

38

VT fuse failure

VT failure

39

Teleprotection disturbed

CF(Communication system Fail) supervision

GI

1, 7, 9

219

46

Group w arning

Only alarming

GI

1, 7, 9

219

47

Group alarm

Trip blocking and alarming

GI

1, 7, 9

219

Not supported

Earth Fault Indications


48

Earth Fault L1

A phase earth fault (*2)

GI

1, 7, 9

219

49

Earth Fault L2

B phase earth fault (*2)

GI

1, 7, 9

219

50

Earth Fault L3

C phase earth fault (*2)

GI

1, 7, 9

219

51

Earth Fault Fw d

Earth fault forw ard (*2) (*3)

GI

1, 7, 9

219

52

Earth Fault Rev

Earth fault reverse (*2) (*3)

GI

1, 7, 9

219

296

6 F 2 S 0 7 5 8

INF

Description

Contents

GI

Type
ID

COT

FUN

219

Fault Indications
64

Start/pick-up L1

A phase, A-B phase or C-A phase element pick-up

GI

1, 7, 9

65

Start/pick-up L2

B phase, A-B phase or B-C phase element pick-up

GI

1, 7, 9

219

66

Start/pick-up L3

C phase, B-C phase or C-A phase element pick-up

GI

1, 7, 9

219
219

67

Start/pick-up N

Earth fault element pick-up

GI

1, 7, 9

68

General trip

BO status specified by IECGT: ON (*1)

--

1, 7

219

69

Trip L1

BO status specified by IECAT: ON (*1)

--

1, 7

219

70

Trip L2

BO status specified by IECBT: ON (*1)

--

1, 7

219

71

Trip L3

BO status specified by IECCT: ON (*1)

--

1, 7

219

72

Trip I>>(back-up)

Back up trip

73

Fault location X In ohms

Fault location (prim. [ohm] / second. [ohm] / km selectable by IECFL)

--

1, 7

Not supported
219

74

Fault forw ard/line

Forw ard fault (*2) (for OC, EF, SEF)

--

1, 7

219

75

Fault reverse/Busbar

Reverse fault (*2) (for OC, EF, SEF)

--

1, 7

219

76

Teleprotection Signal transmitted Carrier signal sending

Not supported

77

Teleprotection Signal received

Not supported

Carrier signal receiving

78

Zone1

Zone 1 trip

Not supported

79

Zone2

Zone 2 trip

Not supported

80

Zone3

Zone 3 trip

Not supported

81

Zone4

Zone 4 trip

Not supported

82

Zone5

Zone 5 trip

Not supported

83

Zone6

Zone 6 trip

Not supported

84

General Start/Pick-up

Any elements pick-up

GI

1, 7, 9

219

85

Breaker Failure

CBF trip or CBF retrip

--

1, 7

219

86

Trip measuring system L1

Not supported

87

Trip measuring system L2

Not supported

88

Trip measuring system L3

Not supported

89

Trip measuring system E

90

Trip I>

Inverse time OC trip (OC1 trip)

--

1, 7

219

91

Trip I>>

Definite time OC trip (OR logic of OC1 to OC3 trip)

--

1, 7

219

92

Trip IN>

Inverse time earth fault OC trip (OR logic of EF1 and SEF1 trip)

--

1, 7

219

93

Trip IN>>

Definite time earth fault OC trip (OR logic of EF1 to EF3 and SEF1 to
SEF3 trip)

--

1, 7

219

CB close command output

--

1, 7

219

--

1, 7

219

GI

1, 7, 9

219

Not supported

Autoreclose indications
128

CB 'ON' by Autoreclose

129

CB 'ON' by long-time
Autoreclose

130

Autoreclose Blocked

Autoreclose block

Note (*1): Not available if the setting is "0".


(*2): Not available when neither EF nor SEF element is used.
(*3): Not available when directional operate characteristic is not used.

297

6 F 2 S 0 7 5 8

INF

Description

Contents

GI

Type
ID

COT

FUN

IECI1 User specified 1

Signal specified by IECE1: ON (*1)

IECG1
(yes/no)

1, 7

219

IECI2 User specified 2

Signal specified by IECE2: ON (*1)

IECG2
(yes/no)

1, 7

219

IECI3 User specified 3

Signal specified by IECE3: ON (*1)

IECG3
(yes/no)

1, 7

219

IECI4 User specified 4

Signal specified by IECE4: ON (*1)

IECG4
(yes/no)

1, 7

219

IECI5 User specified 5

Signal specified by IECE5: ON (*1)

IECG5
(yes/no)

1, 7

219

IECI6 User specified 6

Signal specified by IECE6: ON (*1)

IECG6
(yes/no)

1, 7

219

IECI7 User specified 7

Signal specified by IECE7: ON (*1)

IECG7
(yes/no)

1, 7

219

IECI8 User specified 8

Signal specified by IECE8: ON (*1)

IECG8
(yes/no)

1, 7

219

Measurands(*4)
144

Measurand I

Ib meaurand

--

3.1

2, 7

219

145

Measurand I,V

Ib, Vab measurand

--

3.2

2, 7

219

146

Measurand I,V,P,Q

Ib, Vab, P, Q measurand

--

3.3

2, 7

219

147

Measurand IN,VEN

Ie, Ve measurand

--

3.4

2, 7

219

148

Measurand IL1,2,3, VL1,2,3,


P,Q,f (*5)

Ia, Ib, Ic, Va, Vb, Vc, P, Q, f measurand

--

2, 7

219

Generic Function
240

Read Headings

Not supported

241

Read attributes of all entries of


a group

Not supported

243

Read directory of entry

Not supported

244

Real attribute of entry

Not supported

245

End of GGI

Not supported

249

Write entry w ith confirm

Not supported

250

Write entry w ith execute

Not supported

251

Write entry aborted

Not supported

Note (4): depends on relay model as follows:

110
400
420
430

Type ID=3.1
(INF=144)
IL2
0
Ib
Ib
Ib

110
400
420
430

Type ID=9
(INF=148)
IL1
0
Ia
Ia
Ia

Model
Model
Model
Model
Model

Model
Model
Model
Model
Model

Type ID=3.2
Type ID=3.3
Type ID=3.4
(INF=145)
(INF=146)
(INF=147)
IL2
VL1-VL2
IL2
VL1-VL2 3-phase P 3-phase Q
IN
0
0
0
0
0
0
Ie
Ib
Vab
Ib
Vab
P
Q
Ie
Ib
Vab
Ib
Vab
P
Q
Ie
Ib
Vab
Ib
Vab
P
Q
Ie

IL2
0
Ib
Ib
Ib

IL3
0
Ic
Ic
Ic

VL1
0
Van
Van
Van

Above values are normalized by IECNF.

298

VL2
0
Vbn
Vbn
Vbn

VL3
0
Vcn
Vcn
Vcn

3-phase P 3-phase Q
0
0
P
Q
P
Q
P
Q

VEN
Ve
Ve
Ve
Ve

f
0
f
f
f

6 F 2 S 0 7 5 8
Note (*5):
(a). Transmission format for Type ID=9(INF=148)
Item

Oct.

Value

Start

68H

Length

8 + 2 * number of mesurands = 34

Length

8 + 2 * number of mesurands = 34

Start

Control field

Address

Type identification (Type ID)

Variable structure qualifier

Cause of transmission (COT)

10

Common address of ASDU

11

Function type (FUN)

216

12

Information number (INF)

148

68H
08H+ACD+DFC
1-254
9
0EH
2
1-254

13, 14

Measurand Ia

15, 16

Measurand Ib

17, 18

Measurand Ic

19, 20

Measurand Van

21, 22

Measurand Vbn

23, 24

Measurand Vcn

25, 26

Measurand P

27, 28

Measurand Q

29, 30

Measurand f

31, 32

Unit of power energy (kWh=0, MWh=1)

33, 34

Lower 3 figures of + active power energy (Wh+)

0 - 999

35, 36

Higher 3 figures of + active power energy (Wh+)

0 - 999

37, 38

Figure over times of + active power energy (Wh+)

0 - 999

39, 40

Lower 3 figures of active power energy (Wh+)

0 - 999

41, 42

Higher 3 figures of active power energy (Wh+)

0 - 999

43, 44

Figure over times of active power energy (Wh+)

0 - 999

45, 46

Lower 3 figures of + reactive power energy (Wh+)

0 - 999

47, 48

Higher 3 figures of + reactive power energy (Wh+)

0 - 999

49,50

Figure over times of + reactive power energy (Wh+)

0 - 999

51,52

Lower 3 figures of reactive power energy (Wh+)

0 - 999

53,54

Higher 3 figures of reactive power energy (Wh+)

0 - 999

55,56

Figure over times of reactive power energy (Wh+)

0 - 999

57

Checksum

58

End

Value of Display-Wh setting

16H

(*) Power energy is indicated in 6 figures.

299

6 F 2 S 0 7 5 8
(b). Detail of Measurand (example)
Measured data (12bit)

Signe

(0)

Blank
(0)

IV

OV

Flag

Flag

(0)

(0)

In case the rated voltage Va=63.5V is applied, for example, the theoretical value of MEA is
3413[DEC]=1101 0101 0101[BIN] and is stored as shown in the Figure above. The 19th octet of Type
ID=9 becomes 1010 1000[BIN]=A8[HEX] or the 20th octet of it become 0110 1010[BIN]=6A[HEX].

(c). Transmission image for the measured value of power energy


Wh
Limit

0 reset

999999[kW or MW]

wh2
wh1

wh3
0 t1 t1 t1 t1

Counter=0

Counter=1

t1: periodical cycle transmission (synchronization with polling cycle)


Limit: Wh upper limit value 999999[kW or MW]
() kW or MW depends on the value of Display-Wh setting.
In case the measured value is 12,345,678 kWh and the Display-Wh setting is 0(=kWh), for example, the
transmission data from the relay is as follows:
31, 32

Unit of power energy: (kWh=0, MWh=1)

33, 34

Lower 3 figures of + active power energy (Wh+)

678

35, 36

Higher 3 figures of + active power energy (Wh+)

345

37, 38

Figure over times of + active power energy (Wh+)

12

300

6 F 2 S 0 7 5 8

INF

Description

Contents

COM

Type
ID

COT

FUN

Selection of standard information numbers in control direction


System functions
0

Initiation of general interrogation

--

255

Time synchronization

--

255

219

General commands
16

Auto-recloser on/off

ON/OFF

20

20

17

Teleprotection on/off

ON/OFF

20

20

219

18

Protection on/off

(*5)

ON/OFF

20

20

219

19

LED reset

Reset indication of latched LEDs.

ON

20

20

219

23

Activate characteristic 1

Setting Group 1

ON

20

20

219

24

Activate characteristic 2

Setting Group 2

ON

20

20

219

25

Activate characteristic 3

Setting Group 3

ON

20

20

219

26

Activate characteristic 4

Setting Group 4

ON

20

20

219

Generic functions
Read headings of all defined
240
groups

Not supported

241

Read values or attributes of all


entries of one group

Not supported

243

Read directory of a single entry

Not supported

244

Read values or attributes of a


single entry

Not supported

245

General Interrogation of generic


data

Not supported

248

Write entry

Not supported

249

Write entry w ith confirmation

Not supported

250

Write entry w ith execution

Not supported

251

Write entry abort

Not supported

Note (5): While the relay receives the "Protection off" command, "IN SERVICE LED" is off.

Description

Contents

GRD140
supported

Comment

Basic application functions


Test mode

Yes

Blocking of monitor direction

Yes

Disturbance data

No

Generic services

No

Private data

Yes

Miscellaneous
Max. MVAL = rated
value times

Measurand
Current L1

Ia

1,2 or 2,4

IECNFI setting

Current L2

Ib

1,2 or 2,4

IECNFI setting

Current L3

Ic

1,2 or 2,4

IECNFI setting

Voltage L1-E

Va

1,2 or 2,4

IECNFV setting

Voltage L2-E

Vb

1,2 or 2,4

IECNFV setting

Voltage L3-E

Vc

1,2 or 2,4

IECNFV setting

Active power P

1,2 or 2,4

IECNFP setting
IECNFP setting

Reactive power Q

1,2 or 2,4

Frequency f

1,2 or 2,4

IECNFf setting

Voltage L1 - L2

Vab

1,2 or 2,4

IECNFV setting

301

6 F 2 S 0 7 5 8
[Legend]
GI: General Interrogation
Type ID: Type Identification (refer to IEC60870-5-103 section 7.2.1)
1 : time-tagged message
2 : time-tagged message with relative time
3 : measurands I
4 : time-tagged measurands with relative time
5 : identification
6 : time synchronization
8 : general interrogation termination
9 : measurands II
10: generic data
11: generic identification
20: general command
23: list of recorded disturbances
26: ready for transmission for disturbance data
27: ready for transmission of a channel
28: ready for transmission of tags
29: transmission of tags
30: transmission of disturbance values
31: end of transmission
COT: Cause of Transmission (refer to IEC60870-5-103 section 7.2.3)
1: spontaneous
2: cyclic
3: reset frame count bit (FCB)
4: reset communication unit (CU)
5: start / restart
6: power on
7: test mode
8: time synchronization
9: general interrogation
10: termination of general interrogation
11: local operation
12: remote operation
20: positive acknowledgement of command
21: negative acknowledgement of command
31: transmission of disturbance data
40: positive acknowledgement of generic write command
41: negative acknowledgement of generic write command
42: valid data response to generic read command
43: invalid data response to generic read command
44: generic write confirmation

302

6 F 2 S 0 7 5 8

Appendix N
Modbus: Interoperability

303

6 F 2 S 0 7 5 8
Modbus: Interoperability
1. Physical and Data Link Layer
- RS485(EIA/TIA-485) 2-wire interface
- RTU mode only
- Coding System:
8bit binary (1 start bit, 8 data bits, 1 parity bit, 1 stop bit)
Even parity
- Address setting range: 1-247
- Baud rate setting range: 9600 or 19200

2. Application Layer
(1) Modbus response format
FC
01
02
03
04
05
06
07
08
16
17
43

Description
Read Coils
Read Discrete Inputs
Read Holding Registers
Read Input Register
Write Single Coil
Write Single Register
Read Exception status
Diagnostic
Write Multiple Registers
Report Slave ID
Read device Identification (SC:14)

Supplementary explanation
Returns remote control enable flag
Returns BIs or LED lamp status, etc.
Returns value of analog inputs
Remote command and Time synchronization
Need to specify record number
Returns relay and CB status
Current time setting, etc.
Returns device ID
Returns device information

For FC=01, 02, 03, 04, 05, 06 and 16, the response format is the same as described in "MODBUS
Application Protocol Specification V1.1b".
For other FCs, the response format is as following:
07 Read Exception status
Response Data
Output Data (1byte)
bit Description
0 IN SERVICE (LED)
1 TRIP (LED)
2 ALARM (LED)
3 Prog. LED1 (LED)
4 Prog. LED2 (LED)
5 Prog. LED3 (LED)
6 Relay fail output (BO)
7 <Reserved>

304

6 F 2 S 0 7 5 8

08 Diagnostic
Response Data
SC
Response Data Field
00
Echo Request Data (2Bytes)
01
<not supported>
02
Diagnostic Register Contents (2Bytes)
bit0 IN SERVICE (LED)
bit1 TRIP (LED)
bit2 ALARM (LED)
bit3 Prog. LED1 (LED)
bit4 Prog. LED2 (LED)
bit5 Prog. LED3 (LED)
bit6 <Reserved>
bit7 <Reserved>
bit8 3-phase current balance alarm
bit9 CB contact status alarm
bit10 CB operation number alarm
bit11 CB operating time alarm
bit12 Iy monitoring alarm
bit13 Trip circuit supervision alarm
bit14 <Reserved>
bit15 <Reserved>
03<not supported>
17 Report Slave ID
Response Data
Byte Count (1byte)
Slave ID (17bytes)
GRD140-400A-22-11 (for example)
Run Indicator Status (1byte)
43 Read Device Identification (SC:14)
Response Data
Param OID
01
00
TOSHIBA
01
GRD140-400 (for example)
02
A
02
03
<Non>
04
GRD140
05
400A-22-11 (for example)
DIRECTIONAL
06
OVRRCURRENT PROTECTION
RELAY
07<Reserved>
03
80
<SPACE>
81
GS1DM1-04-L (for example)
04

<not supported>

305

Description
Return Query Data
Return Diagnostic Register

18bytes
Relay type and model ID
ASCII
0x00=out of service, 0xFF=in service

Basic device identification


Vendor Name
Product Code
Major Minor Revision
Regular device identification
Vendor URL
Product Name
Model Name
User Application Name
Reserved
Extended device identification
Software version
One specific identification
object

6 F 2 S 0 7 5 8
(2) Modbus address map
address hex

function

Contents

512

200

1,5

Control
Control start

1026
1027
1028

402
403
404

4608
4609
4610

5108

1200
1201
1202

13F4

7680
7681

7711

1E00
1E01

1E1F

8192
8193
8194
8195
8196
8197
8198
8199
8200
8201
8202
8203

2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
200A
200B

4
4
4
4
4
4
4
4
4
4
4
4

8204

200C

8205
8206
8207
8208
8209
8210
8211
8212
8213
8214
8215
8216
8217
8218
8219
8220
8221
8222
8223

200D
200E
200F
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
201A
201B
201C
201D
201E
201F

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

1,2
1,2
1,2

1,2

Unit

LSB

0.001IN

5 Reset lached LED


5 Time trigger
5 Reset Trip LED
Signal List
signal list#0
signal list#1
signal list#2

signal list#500
Alias (bit)
2 alias coil #1
2 alias coil #2

2 alias coil #32


Metering
Ia
(Phase)
Ib
(Phase)
Ic
(Phase)
Ie
(Phase)
Ise
(Phase)
I0
(Phase)
I1
(Phase)
I2
(Phase)

[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]

degree
A

0.01
0.001IN

degree
A
degree
A

0.01
0.001IN
0.01
430A:0.0025IN
Others:0.001

[Low]
[Hi]
degree
0.01
[Low]
[Hi]
A
0.00025IN
[Low]
[Hi]
degree
0.01
[Low]
[Hi]
A
0.001IN
[Low]
[Hi]
degree
0.01
[Low]
[Hi]
A
0.001IN
[Low]
[Hi]
degree
0.01
[Low]
[Hi]
A
0.001IN
[Low]
[Hi]
degree
0.01
[Low]
IN: rated current (See address 49153.)

306

6 F 2 S 0 7 5 8
address hex

function

Contents

8224
8225
8226
8227
8228
8229
8230
8231
8232
8233
8234
8235
8236
8237
8238
8239
8240
8241
8242
8243
8244
8245
8246
8247
8248
8249
8250
8251
8252
8253
8254
8255
8256
8257
8258
8259
8260
8261
8262
8263
8264
8265
8266
8267
8268
8269
8270
8271
8272
8273
8274
8275
8276
8277
8278
8279
8280
8281
8282
8283

2020
2021
2022
2023
2024
2025
2026
2027
2028
2029
202A
202B
202C
202D
202E
202F
2030
2031
2032
2033
2034
2035
2036
2037
2038
2039
203A
203B
203C
203D
203E
203F
2040
2041
2042
2043
2044
2045
2046
2047
2048
2049
204A
204B
204C
204D
204E
204F
2050
2051
2052
2053
2054
2055
2056
2057
2058
2059
205A
205B

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

Va

8284

205C

Iemax

8285

205D

(Phase)
Vb
(Phase)
Vc
(Phase)
Ve
(Phase)
Vab
(Phase)
Vbc
(Phase)
Vca
(Phase)
V0
(Phase)
V1
(Phase)
V2
(Phase)
I2/I1
THM
f
PF
P
Q
S
Iamax
Ibmax
Icmax

Unit

LSB

[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

0.06

degree

0.01

[Hi]
[Low]

307

0.001

0.01
0.01
0.001
1
1
1

0.001IN

0.001IN

0.001IN

430A:0.0025IN
Others:0.001

6 F 2 S 0 7 5 8
address hex

function

Contents

8286
8287
8288
8289
8290
8291
8292
8293
8294
8295
8296
8297
8298
8299
8300
8301
8302
8303
8304
8305
8306
8307
8308
8309
8310
8311
8312
8313
8314
8315
8316
8317
8318
8319
8320
8321
8334
8335
8336
8337
8338
8339
8340
8341
8342
8343
8344
8345
8346
8347
8348
8349

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16

Isemax

205E
205F
2060
2061
2062
2063
2064
2065
2066
2067
2068
2069
206A
206B
206C
206D
206E
206F
2070
2071
2072
2073
2074
2075
2076
2077
2078
2079
207A
207B
207C
207D
207E
207F
2080
2081
208E
208F
2090
2091
2092
2093
2094
2095
2096
2097
2098
2099
209A
209B
209C
209D

I2max
I2/I1 max
Pmax
Qmax
Smax
Vamax
Vamin
Vbmax
Vbmin
Vcmax
Vcmin
Vemax
Vemin
V0max
V0min
fmax
fmin
No use
Count-Wh+
Wh+
No use
Count-WhWhNo use
Count-vah+
vah+
No use
Count-vah1
vah-

[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]

308

Unit

LSB

0.0025IN

0.001IN

0.001
1
1
1
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.06
0.01
0.01

0.1

0.1

0.1

0.1

6 F 2 S 0 7 5 8
address hex

function

Contents

Unit

LSB

bit

9216
9217

2400
2401

4
4

0
1
Binary input/output BI6 to 8 are not provided with Model 4xxA.
BI
BI1
BI2
BI3
BO
BO1
BO2
BO3

9472
9473
9474
9475
9476
9477
9478
9479
9480
9481

2500
2501
2502
2503
2504
2505
2506
2507
2508
2509

4
4
4
4
4
4
4
4
4
4

Ry element
OC
EF,SEF,NOC,CBF
OV
UV
ZOV,NOV
FRQ
BCD
Cold ld
UC,THM
Direction

9728
9729
9730

2600
2601
2602

4
4
4

LED
LED
VLED1
VLED2

function

Contents

address hex

MRY01
MRY02
MRY05
MRY06
MRY07
MRY10
MRY02E
MSTATE
MRY04
wp-

OC1-A
EF1
OV1-A
UV1-A
ZOV1
FRQ1

OC1-B
EF2
OV1-B
UV1-B
ZOV2
FRQ2

3
BI4
BO4

OC1-C
EF3
OV1-C
UV1-C

EF4

FRQ3

FRQ4

Cold Ld0 Cold Ld1 Cold Ld2 Cold Ld3


UC1-A
UC1-B
UC1-C
Forward(Ia)Forward(Ib)Forward(Ic)Forward(Ie)
In service Trip
Alarm
Prog.LED1
IND1 bit1 IND1 bit2 IND1 bit3 IND1 bit4
IND2 bit1 IND2 bit2 IND2 bit3 IND2 bit4

Unit

LSB

9216
9217

2400
2401

4
4

4
Binary input/output BI6 to 8 are not provided with Model 4xxA.
BI
BI5
BI6
BO
BO5
BO6

9472
9473
9474
9475
9476
9477
9478
9479
9480
9481

2500
2501
2502
2503
2504
2505
2506
2507
2508
2509

4
4
4
4
4
4
4
4
4
4

Ry element
OC
EF,SEF,NOC,CBF
OV
UV
ZOV,NOV
FRQ
BCD
Cold ld
UC,THM
Direction

9728
9729
9730

2600
2601
2602

4
4
4

LED
LED
VLED1
VLED2

function

Contents

address hex

MRY01
MRY02
MRY05
MRY06
MRY07
MRY10
MRY02E
MSTATE
MRY04
wp-

OC2-A
SEF1
OV2-A
UV2-A
NOV1

6
BI7
BO7

7
BI8
Fail BO

OC2-B
SEF2
OV2-B
UV2-B
NOV2

OC2-C
SEF3
OV2-C
UV2-C

UC2-A
UC2-B
Forward(Ise)

UC2-C

SEF4

Forward(I2

Prog.LED2 Prog.LED3
IND1 bit5 IND1 bit6 IND1 bit7 IND1 bit8
IND2 bit5 IND2 bit6 IND2 bit7 IND2 bit8

Unit

LSB

9216
9217

2400
2401

4
4

8
9
Binary input/output BI6 to 8 are not provided with Model 4xxA.
BI
BO

9472
9473
9474
9475
9476
9477
9478
9479
9480
9481

2500
2501
2502
2503
2504
2505
2506
2507
2508
2509

4
4
4
4
4
4
4
4
4
4

Ry element
OC
EF,SEF,NOC,CBF
OV
UV
ZOV,NOV
FRQ
BCD
Cold ld
UC,THM
Direction

9728
9729
9730

2600
2601
2602

4
4
4

LED
LED
VLED1
VLED2

MRY01
MRY02
MRY05
MRY06
MRY07
MRY10
MRY02E
MSTATE
MRY04
wp-

OC3-A
NOC1

OC3-B
NOC2

10

11

OC3-C

Reverse(Ia)Reverse(Ib)Reverse(Ic)Reverse(Ie)

309

6 F 2 S 0 7 5 8
address hex

function

Contents

Unit

LSB

9216
9217

2400
2401

4
4

12
13
Binary input/output BI6 to 8 are not provided with Model 4xxA.
BI
BO

9472
9473
9474
9475
9476
9477
9478
9479
9480
9481

2500
2501
2502
2503
2504
2505
2506
2507
2508
2509

4
4
4
4
4
4
4
4
4
4

Ry element
OC
EF,SEF,NOC,CBF
OV
UV
ZOV,NOV
FRQ
BCD
Cold ld
UC,THM
Direction

9728
9729
9730

2600
2601
2602

4
4
4

LED
LED
VLED1
VLED2

MRY01
MRY02
MRY05
MRY06
MRY07
MRY10
MRY02E
MSTATE
MRY04
wp-

address hex

function

Contents

10240
10241
10242
10243
10244
10245
10246
10247
10248
10249
10250
10251
10252
10253
10254
10255
10256
10257
10258
10259
10260
10261
10262
10263
10264
10265
10266
10267
10268
10269
10270
10271
10272
10273
10274
10275
10276
10277
10278
10279
10280
10281

4
3,4,6,16
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

Distrubance records
records count
set No (R/W) 1
No.X
millseconds
hours/minutes
months/days
year
No.X+1
millseconds
hours/minutes
months/days
year
No.X+2
millseconds
hours/minutes
months/days
year
No.X+3
millseconds
hours/minutes
months/days
year
No.X+4
millseconds
hours/minutes
months/days
year
No.X+5
millseconds
hours/minutes
months/days
year
No.X+6
millseconds
hours/minutes
months/days
year
No.X+7
millseconds
hours/minutes
months/days
year

2800
2801
2802
2803
2804
2805
2806
2807
2808
2809
280A
280B
280C
280D
280E
280F
2810
2811
2812
2813
2814
2815
2816
2817
2818
2819
281A
281B
281C
281D
281E
281F
2820
2821
2822
2823
2824
2825
2826
2827
2828
2829

OC4-A
CBF-A

OC4-B
CBF-B

14

15

OC4-C
CBF-C

BCD
THM-T
THM-A
Reverse(Ise)

Unit

LSB

Reverse(I2)

bit

Higher 8bit hour Lower 8bit minutes


Higher 8bit months Lower 8bit days
Higher 8bit 00H
Lower 8bit year

310

6 F 2 S 0 7 5 8
address hex

function

Contents

10282
10283
10284
10285
10286
10287
10288
10289
10290
10291
10292
10293
10294
10295
10296
10297
10298
10299
10300
10301
10302
10303
10304
10305
10306
10307
10308
10309
10310
10311
10312
10313
10314
10315
10316
10317
10318
10319
10320
10321
10322
10323
10324
10325
10326
10327
10328
10329
10330
10331
10332
10333
10334
10335
10336
10337
10338
10339
10340
10341

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

No.X+8
millseconds
hours/minutes
months/days
year
No.X+9
millseconds
hours/minutes
months/days
year
No.X+10
millseconds
hours/minutes
months/days
year
No.X+11
millseconds
hours/minutes
months/days
year
No.X+12
millseconds
hours/minutes
months/days
year
No.X+13
millseconds
hours/minutes
months/days
year
No.X+14
millseconds
hours/minutes
months/days
year
No.X+15
millseconds
hours/minutes
months/days
year
No.X+16
millseconds
hours/minutes
months/days
year
No.X+17
millseconds
hours/minutes
months/days
year
No.X+18
millseconds
hours/minutes
months/days
year
No.X+19
millseconds
hours/minutes
months/days
year

282A
282B
282C
282D
282E
282F
2830
2831
2832
2833
2834
2835
2836
2837
2838
2839
283A
283B
283C
283D
283E
283F
2840
2841
2842
2843
2844
2845
2846
2847
2848
2849
284A
284B
284C
284D
284E
284F
2850
2851
2852
2853
2854
2855
2856
2857
2858
2859
285A
285B
285C
285D
285E
285F
2860
2861
2862
2863
2864
2865

Unit

LSB

311

bit

6 F 2 S 0 7 5 8
address hex

function

Contents

10496
10497
10498
10499
10500
10501
10502
10503
10504
10505
10506
10507
10508
10509
10510
10511
10512
10513
10514
10515
10634
10635

3,4,6,16
3,4,6,16
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

disturbance records number


start page(1)
max page
millseconds
hours/minutes
months/days
year
sample
bytes/sample
pre trigger
sampling rate
dummy1
dummy2
dummy3
dummy4
dummy5
Page number
page size
data #1
data #2
data #121
data #122

function

Contents

4
3,4,6,16
4
4
4
4
4
4
4
4
4
4
4
4

Fault records
records count
No.
millseconds
hours/minutes
months/days
year
(Reserved)
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Trip phase
FL error status
FL value

km

0.1

function

Contents

Unit

LSB

4
3,4,6,16
4
4
4
4
4
4
4
4
4
4
4
4

Fault records
records count
No.
millseconds
hours/minutes
months/days
year
(Reserved)
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Trip phase
FL error status
FL value

2900
2901
2902
2903
2904
2905
2906
2907
2908
2909
290A
290B
290C
290D
290E
290F
2910
2911
2912
2913
298A
298B

address hex

Unit

LSB

Unit

LSB

bit

bit
0

12288
12289
12290
12291
12292
12293
12294
12295
12296
12297
12298
12299
12300
12301

3000
3001
3002
3003
3004
3005
3006
3007
3008
3009
300A
300B
300C
300D

address hex

fault_val.h
fault_val.h

OC1
UC2
FRQ1

OC2
THM-A
FRQ2

OC3
THM
FRQ3

A
OFF

4
12288
12289
12290
12291
12292
12293
12294
12295
12296
12297
12298
12299
12300
12301

3000
3001
3002
3003
3004
3005
3006
3007
3008
3009
300A
300B
300C
300D

fault_val.h
fault_val.h

km

0.1

312

EF1
CBF-RE
EXTTP

OC4
BCD
FRQ4

EF2
CBF

EF3
OV1

LLO

BFL

EF4
OV2

6 F 2 S 0 7 5 8
address hex

function

Contents

Unit

LSB

4
3,4,6,16
4
4
4
4
4
4
4
4
4
4
4
4

Fault records
records count
No.
millseconds
hours/minutes
months/days
year
(Reserved)
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Trip phase
FL error status
FL value

km

0.1

function

Contents

Unit

LSB

4
3,4,6,16
4
4
4
4
4
4
4
4
4
4
4
4

Fault records
records count
No.
millseconds
hours/minutes
months/days
year
(Reserved)
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Trip phase
FL error status
FL value

8
12288
12289
12290
12291
12292
12293
12294
12295
12296
12297
12298
12299
12300
12301

3000
3001
3002
3003
3004
3005
3006
3007
3008
3009
300A
300B
300C
300D

address hex

fault_val.h

SEF1-1
UV1

SEF1-2
UV2

3000
3001
3002
3003
3004
3005
3006
3007
3008
3009
300A
300B
300C
300D

SEF2
ZOV1

11

SEF3
ZOV2

fault_val.h

12
12288
12289
12290
12291
12292
12293
12294
12295
12296
12297
12298
12299
12300
12301

10

fault_val.h

SEF4
NOV1

13

NOC1
NOV2

14

NOC2

15

UC1

fault_val.h
ARC-FT
km

0.1

313

6 F 2 S 0 7 5 8
address hex

function

12302
12303
12304
12305
12306
12307
12308
12309
12310
12311
12312
12313

300E
300F
3010
3011
3012
3013
3014
3015
3016
3017
3018
3019

4
4
4
4
4
4
4
4
4
4
4
4

12314

301A

12315
12316
12317
12318
12319
12320
12321
12322
12323
12324
12325
12326
12327
12328
12329
12330
12331
12332
12333
12334
12335
12336
12337
12338
12339
12340
12341
12342
12343
12344
12345
12346
12347
12348
12349
12350
12351
12352

301B
301C
301D
301E
301F
3020
3021
3022
3023
3024
3025
3026
3027
3028
3029
302A
302B
302C
302D
302E
302F
3030
3031
3032
3033
3034
3035
3036
3037
3038
3039
303A
303B
303C
303D
303E
303F
3040

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

Contents
Prefault value
Ia
(Phase)
No use
Ib
(Phase)
No use
Ic

[Hi]
[Low]

Unit

LSB

0.001IN
0.01

[Hi]
[Low]

0.01
[Hi]
[Low]

(Phase)
No use
Ie

0.001IN

0.001IN
0.01

[Hi]

430A:0.0025IN
Others:0.001IN

[Low]
(Phase)
No use
Ise
(Phase)
No use
I0(use)
(Phase)
No use
I1
(Phase)
No use
I2
(Phase)
No use
I2/I1
No use
No use
THM(no use)
No use
No use
Va
(Phase)
No use
Vb
(Phase)
No use
Vc

0.01
[Hi]
[Low]

0.00025IN
0.01

[Hi]
[Low]

[Hi]
[Low]

0.001IN
0.01

[Hi]
[Low]

0.001IN
0.01

[Hi]
[Low]

0.001

[Hi]
[Low]

0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

(Phase)

0.06
0.01

314

6 F 2 S 0 7 5 8
address hex

function

Contents

12353
12354
12355
12356
12357
12358
12359
12360
12361
12362
12363
12364
12365
12366
12367
12368
12369
12370
12371
12372
12373
12374
12375
12376
12377
12378
12379
12380
12381
12382
12383
12384
12385
12386
12387
12388
12389
12390
12391
12392
12393
12394
12395
12396
12397
12398
12399
12400
12401

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

No use
Ve

3041
3042
3043
3044
3045
3046
3047
3048
3049
304A
304B
304C
304D
304E
304F
3050
3051
3052
3053
3054
3055
3056
3057
3058
3059
305A
305B
305C
305D
305E
305F
3060
3061
3062
3063
3064
3065
3066
3067
3068
3069
306A
306B
306C
306D
306E
306F
3070
3071

(Phase)
No use
Vab
(Phase)
No use
Vbc
(Phase)
No use
Vca
(Phase)
No use
V0
(Phase)
No use
V1
(Phase)
No use
V2
(Phase)
No use
f
No use
No use
PF(no use)
No use
No use
P(no use
No use
No use
Q(no use
No use
No use
S(no use

Unit

[Hi]
[Low]

LSB

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]

No use
No use

315

0.01

6 F 2 S 0 7 5 8
address hex

function

12430
12431
12432
12433
12434
12435
12436
12437
12438
12439
12440
12441

308E
308F
3090
3091
3092
3093
3094
3095
3096
3097
3098
3099

4
4
4
4
4
4
4
4
4
4
4
4

12442

309A

12443
12444
12445
12446
12447
12448
12449
12450
12451
12452
12453
12454
12455
12456
12457
12458
12459
12460
12461
12462
12463
12464
12465
12466
12467
12468
12469
12470
12471
12472
12473
12474
12475
12476
12477
12478
12479
12480
12481
12482
12483
12484
12485
12486
12487
12488
12489
12490
12491
12492
12493
12494
12495
12496
12497

309B
309C
309D
309E
309F
30A0
30A1
30A2
30A3
30A4
30A5
30A6
30A7
30A8
30A9
30AA
30AB
30AC
30AD
30AE
30AF
30B0
30B1
30B2
30B3
30B4
30B5
30B6
30B7
30B8
30B9
30BA
30BB
30BC
30BD
30BE
30BF
30C0
30C1
30C2
30C3
30C4
30C5
30C6
30C7
30C8
30C9
30CA
30CB
30CC
30CD
30CE
30CF
30D0
30D1

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

Contents
During fault value
Ia
(Phase)
No use
Ib
(Phase)
No use
Ic

[Hi]
[Low]

Unit

LSB

0.001IN
0.01

[Hi]
[Low]

0.01
[Hi]
[Low]

(Phase)
No use
Ie

0.001IN

0.001IN
0.01

[Hi]

430A:0.0025IN
Others:0.001IN

[Low]
(Phase)
No use
Ise
(Phase)
No use
I0(no use)
(Phase)
No use
I1
(Phase)
No use
I2
(Phase)
No use
I2/I1
No use
No use
THM
No use
No use
Va
(Phase)
No use
Vb
(Phase)
No use
Vc
(Phase)
No use
Ve
(Phase)
No use
Vab
(Phase)
No use
Vbc
(Phase)
No use
Vca

0.01
[Hi]
[Low]

0.00025IN
0.01

[Hi]
[Low]

[Hi]
[Low]

0.001IN
0.01

[Hi]
[Low]

0.001IN
0.01

[Hi]
[Low]

0.001

[Hi]
[Low]

0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

(Phase)
No use

0.06
0.01

316

6 F 2 S 0 7 5 8
address hex

function

Contents

12498
12499
12500
12501
12502
12503
12504
12505
12506
12507
12508
12509
12510
12511
12512
12513
12514
12515
12516
12517
12518
12519
12520
12521
12522
12523
12524
12525
12526
12527
12528
12529

30D2
30D3
30D4
30D5
30D6
30D7
30D8
30D9
30DA
30DB
30DC
30DD
30DE
30DF
30E0
30E1
30E2
30E3
30E4
30E5
30E6
30E7
30E8
30E9
30EA
30EB
30EC
30ED
30EE
30EF
30F0
30F1

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

V0

address

hex

function

Contents

(Phase)
No use
V1
(Phase)
No use
V2
(Phase)
No use
f
No use
No use
PF(no use)
No use
No use
P(no use
No use
No use
Q(no use
No use
No use
S(no use

Unit
[Hi]
[Low]

LSB
0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.06
0.01

[Hi]
[Low]

0.01

[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]

No use
No use

Unit

LSB

bit
0

12558
12559
12560
12561
12562
12563
12564
12565
12566
12567
12568
12569
12570
12581
12592
12603
12614
12625
12636
12647
12658
12669
12680
12691
12702
12713
12724

310E
310F
3110
3111
3112
3113
3114
3115
3116
3117
3118
3119

4
4
4
4
4
4
4
4
4
4
4

Autoreclose
Number of record(Max16)
millseconds
hours/minutes
months/days
year
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Fault phase
autoreclose mode(Low)
autoreclose mode(High)

Autoreclose#2 inf.
Autoreclose#3 inf.
Autoreclose#4 inf.
Autoreclose#5 inf.
Autoreclose#6 inf.
Autoreclose#7 inf.
Autoreclose#8 inf.
Autoreclose#9 inf.
Autoreclose#10 inf.
Autoreclose#11 inf.
Autoreclose#12 inf.
Autoreclose#13 inf.
Autoreclose#14 inf.
Autoreclose#15 inf.
Autoreclose#16 inf.

fault_val.h

317

fault_val.h

OC1
UC2
FRQ1

OC2
THM-A
FRQ2

OC3
THM
FRQ3

OC4
BCD
FRQ4

fault_val.h

A
ARC-S5

B
ARC-S4

C
ARC-S3

ARC-S2

6 F 2 S 0 7 5 8
address

hex

function

Contents

Unit

LSB
4

12558
12559
12560
12561
12562
12563
12564
12565
12566
12567
12568
12569

310E
310F
3110
3111
3112
3113
3114
3115
3116
3117
3118
3119

4
4
4
4
4
4
4
4
4
4
4

hex

function

12570
12581
12592
12603
12614
12625
12636
12647
12658
12669
12680
12691
12702
12713
12724

address

Autoreclose
Number of record(Max16)
millseconds
hours/minutes
months/days
year
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Fault phase
autoreclose mode(Low)
autoreclose mode(High)

Autoreclose#2 inf.
Autoreclose#3 inf.
Autoreclose#4 inf.
Autoreclose#5 inf.
Autoreclose#6 inf.
Autoreclose#7 inf.
Autoreclose#8 inf.
Autoreclose#9 inf.
Autoreclose#10 inf.
Autoreclose#11 inf.
Autoreclose#12 inf.
Autoreclose#13 inf.
Autoreclose#14 inf.
Autoreclose#15 inf.
Autoreclose#16 inf.

fault_val.h

Contents

EF2
CBF

fault_val.h

fault_val.h

ARC-S1

ARC-SUC ARC-RST ARC-CO

Unit

LSB

12558
12559
12560
12561
12562
12563
12564
12565
12566
12567
12568
12569
12570
12581
12592
12603
12614
12625
12636
12647
12658
12669
12680
12691
12702
12713
12724

310E
310F
3110
3111
3112
3113
3114
3115
3116
3117
3118
3119

4
4
4
4
4
4
4
4
4
4
4

fault_val.h

SEF1-1
UV1

SEF1-2
UV2

fault_val.h

fault_val.h

318

EF3
OV1

EF1
CBF-RE
EXTTP

8
Autoreclose
Number of record(Max16)
millseconds
hours/minutes
months/days
year
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Fault phase
autoreclose mode(Low)
autoreclose mode(High)

Autoreclose#2 inf.
Autoreclose#3 inf.
Autoreclose#4 inf.
Autoreclose#5 inf.
Autoreclose#6 inf.
Autoreclose#7 inf.
Autoreclose#8 inf.
Autoreclose#9 inf.
Autoreclose#10 inf.
Autoreclose#11 inf.
Autoreclose#12 inf.
Autoreclose#13 inf.
Autoreclose#14 inf.
Autoreclose#15 inf.
Autoreclose#16 inf.

ARC-CORST

EF4
OV2

10

SEF2
ZOV1

11

SEF3
ZOV2

6 F 2 S 0 7 5 8
address hex

function

Contents

Unit

LSB
12

12558
12559
12560
12561
12562
12563
12564
12565
12566
12567
12568
12569

310E
310F
3110
3111
3112
3113
3114
3115
3116
3117
3118
3119

4
4
4
4
4
4
4
4
4
4
4

12570
12581
12592
12603
12614
12625
12636
12647
12658
12669
12680
12691
12702
12713
12724

address hex

Autoreclose
Number of record(Max16)
millseconds
hours/minutes
months/days
year
Trip mode1(Low)
Trip mode1(High)
Trip mode2(Low)
Trip mode2(High)
Fault phase
autoreclose mode(Low)
autoreclose mode(High)

Autoreclose#2 inf.
Autoreclose#3 inf.
Autoreclose#4 inf.
Autoreclose#5 inf.
Autoreclose#6 inf.
Autoreclose#7 inf.
Autoreclose#8 inf.
Autoreclose#9 inf.
Autoreclose#10 inf.
Autoreclose#11 inf.
Autoreclose#12 inf.
Autoreclose#13 inf.
Autoreclose#14 inf.
Autoreclose#15 inf.
Autoreclose#16 inf.

function

Contents

4
3,4,6,16
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

Event Records
records count
set No. (R/W)
No.X
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+1
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+2
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+3
millseconds
hours/minutes
months/days
year
Event ID
Action

fault_val.h SEF4
NOV1
fault_val.h

13

NOC1
NOV2

3400
3401
3402
3403
3404
3405
3406
3407
3408
3409
340A
340B
340C
340D
340E
340F
3410
3411
3412
3413
3414
3415
3416
3417
3418
3419
341A
341B
341C
341D

NOC2

15

UC1
ARC-FT

fault_val.h

Unit

LSB

bit
0

13312
13313
13314
13315
13316
13317
13318
13319
13320
13321
13322
13323
13324
13325
13326
13327
13328
13329
13330
13331
13332
13333
13334
13335
13336
13337
13338
13339
13340
13341

14

On

319

Off

6 F 2 S 0 7 5 8
address hex

function

Contents

13342
13343
13344
13345
13346
13347
13348
13349
13350
13351
13352
13353
13354
13355
13356
13357
13358
13359
13360
13361
13362
13363
13364
13365
13366
13367
13368
13369
13370
13371
13372
13373
13374
13375
13376
13377
13378
13379
13380
13381
13382
13383

341E
341F
3420
3421
3422
3423
3424
3425
3426
3427
3428
3429
342A
342B
342C
342D
342E
342F
3430
3431
3432
3433
3434
3435
3436
3437
3438
3439
343A
343B
343C
343D
343E
343F
3440
3441
3442
3443
3444
3445
3446
3447

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

No.X+4
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+5
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+6
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+7
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+8
millseconds
hours/minutes
months/days
year
Event ID
Action
No.X+9
millseconds
hours/minutes
months/days
year
Event ID
Action

14336
14337
14338
14339

3800
3801
3802
3803

3,4,16
3,4,16
3,4,16
3,4,16

set time
millseconds
hours/minutes
months/days
(non)/year

14352
14353
14354
14355
14356
14357
14358
14359
14360
14361
14362
14363
14364
14365
14366
14367

3810
3811
3812
3813
3814
3815
3816
3817
3818
3819
381A
381B
381C
381D
381E
381F

3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16
3,4,16

Unit

LSB

bit
0

Trip counter
Trip counter
Trip-A
Trip-B
Trip-C
I A
I B
I C
ARCs

[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]
[Hi]
[Low]

320

6 F 2 S 0 7 5 8
address hex

function

Contents
Alias (word)
alias #1
alias #2

alias #32

Unit

LSB

bit
0

15360
15361

15391

3C00
3C01

3C1F

3,4
3,4

3,4

15872
15873

3E00
3E01

15903
15904
15905

3E1F
3E20
3E21

15935

3E3F

3,4,6,16
3,4,6,16
3,4,6,16
3,4,6,16
3,4,6,16
3,4,6,16
3,4,6,16
3,4,6,16

16000
16001

3E80
3E81

6,16
6,16

Password
Passwordfor starting to set "00"
Password (continued)
"00"

16128
16129

3F00
3F01

3,4,6,16
3,4

Setting
Setting flag
Setting error adr

16384

4000

3,4,6,16

Setting data(ref. setting table)

49152
49153

C000
C001

4
4

System information
System frequency
Rated current

49162
49163
49164
49165
49166

C00A
C00B
C00C
C00D
C00E

4
4
4
4
4

OC CT ratio
EF CT ratio
SEF CT ratio
PVT ratio
RVT ratio

alias set data(coil) #1


alias set data(coil) #2
alias set data(coil) #32
alias set data(register) #1
alias set data(register) #2
alias set data(register) #32

1=setting start 2=setting write

Hz
A

1
1
1
1
1
1
1

321

6 F 2 S 0 7 5 8

322

6 F 2 S 0 7 5 8

Appendix O
Inverse Time Characteristics

323

6 F 2 S 0 7 5 8

IEC/UK Inverse Curves (NI)


(Time Multiplier TMS = 0.1 - 1.5)

100

IEC/UK Inverse Curves (VI)


(Time Multiplier TMS = 0.1 - 1.5)

100

10

Operating Time (s)

Operating Time (s)

10
TMS
1.5
1.

TMS
1.5

1.0
0.5

0.5

0.2

0.1

0.2

0.1

0.1

0.01

0.1
1

10
Current (Multiple of Setting)

100

Normal Inverse

10
Current (Multiple of Setting)
Very Inverse

324

100

6 F 2 S 0 7 5 8

IEC/UK Inverse Curves (EI)


(Time Multiplier TMS = 0.1 - 1.5)
1000

100

UK Inverse Curves (LTI)


(Time Multiplier TMS = 0.1 - 1.5)

10

100

Operating Time (s)

Operating Time (s)

1000

1
TMS
1.5
1.0

0.1

TMS
1.5

10

1.0
0.5

0.5

0.2

0.1

0.2
0.1

0.1

0.01
1

10
Current (Multiple of Setting)

100

Extremely Inverse

10
Current (Multiple of Setting)

Long Time Inverse

325

100

6 F 2 S 0 7 5 8

IEEE Inverse Curves (MI)


(Time Multiplier TMS = 0.1 - 1.5)

IEEE Inverse Curves (VI)


(Time Multiplier TMS = 0.1 - 1.5)

10

10

Operating Time (s)

100

Operating Time (s)

100

TMS
1.5

1.0
0.5

TM
1

1.5
1.0
0.5

0.2
0.2

0.1

0.1
0.1

0.1

0.01

0.01
1

10
Current (Multiple of Setting)

100

Moderately Inverse

10
Current (Multiple of Setting)

Very Inverse

326

100

6 F 2 S 0 7 5 8

IEEE Inverse Curves (EI)


(Time Multiplier TMS = 0.1 - 1.5)

100

Operating Time (s)

10

1
TMS
1.5
1.0

0.1
0.5

0.2
0.1
0.01
1

10
Current (Multiple of Setting)

100

Extremely Inverse

327

6 F 2 S 0 7 5 8

US Inverse Curves (CO8)


(Time Multiplier TMS = 0.1 - 1.5)

US Inverse Curves (CO2)


(Time Multiplier TMS = 0.1 - 1.5)

10

100

10
1
Operating Time (s)

Operating Time (s)

TMS

1
TMS

1.5
1.0

0.5

1.5
0.1

1.0
0.1

0.2

0.5

0.1
0.2
0.1
0.01

0.01
1

10
Current (Multiple of Setting)

100

CO8 Inverse

10
Current (Multiple of Setting)

CO2 Short Time Inverse

328

100

6 F 2 S 0 7 5 8

Appendix P
Ordering

329

6 F 2 S 0 7 5 8

Ordering
Directional Overcurrent Relay

GRD140

Type:
Directional Overcurrent Relay
Model:
-Model 110: Directional earth fault and directional sensitive
earth fault

GRD140

-Model 400: Directional 3 phase + earth fault()


Aux. CT of the relay for Core balance CT is same as
phase CTs.
-Model 420: Directional 3 phase + earth + sensitive earth
-Model 430: Directional 3 phase + earth fault()
Aux. CT of the relay for Core balance CT is independent of
phase CTs.
CT Rating:
1A
5A
5A (SEF-L) () Only for Model 420
Frequency:
50Hz
60Hz
DC auxiliary supply rating:
110V/125V
220V/250V
48V/54V/60V
24V/30V
Rear communication port:
RS485
Dual RS485
RS485 + Fibre optic
LED label
Standard
Option: User configurable LED label

110
400

420
430

1
2
3
1
2
1
2
3
4
1
3
9
None
J

330

6 F 2 S 0 7 5 8

Version-up Records
Version
No.

Date

Revised Section

0.0
0.1

Mar. 25, 2004


Apr. 23, 2004

-2.1.2
2.1.3
2.1.8
2.3
2.5, 2.5.1
3.3
4.2.6.7
6.4.2
Appendices

0.2

Aug. 19, 2004

0.3

Sep. 01, 2005

0.4

Apr. 17, 2007

0.5

Jul. 24, 2007

0.6

Jul. 31, 2009

0.7

Dec. 02, 2009

3.2.2
Appendices
2.1.1.1
2.1.3.4
2.1.6
2.1.7
3.3.6
3.3.7
4.2.6.8
Appendices
2.1.6
2.3
4.1.1
4.2.1
4.2.3.1, 4.2.4.1
4.2.6.6, 4.2.6.10
4.4
Appendices
2.2.3
3.3.9
6.6.1
Appendices
2.1.3.1
2.1.3.2
2.1.3.4
2.1.5
2.5.1
2.5.3
3.5.1
4.1.2
4.2.7.1
Appendices
2.2.1, 2.2.2
3.2.1
3.4.1
3.5.1
4.2.6.7
Appendices

Contents
First issue
Modified the description of sections 2.1.2.1 and 2.1.2.2.
Modified the description of sections 2.1.3.1 to 2.1.3.6, and Figure 2.1.16.
Modified the description.
Modified the description.
Modified the description.
Modified the descriptions of sections 3.3.3 and 3.3.4.
Modified the description.
Modified the Figure 6.4.1.
Modified the Appendix C (No. 122 added.), Appendix G (GRD140-110 and
CT connection modified.) and Appendix H (Setting sheet modified.).
Modified the description.
Modified the Appendix K and M.
Modified the configurable curve setting range. (k and kr corrected.)
Modified the description of setting table.
Modified the description.
Modified the description.
Modified the description.
Modified Table 3.3.1.
Modified the description.
Modified Appendix M.
Added Figure 2.1.42.
Modified the description.
Modified the description.
Modified the description and added Table 4.2.1.
Added Note.
Modified the description.
Modified the description.
Modified Appendix E, H and O.
Modified the description.
Modified the description of setting table.
Added the description of Directional check.
Modified Appendix H.
Modified the description and Figure 2.1.16.
Modified the description and Figure 2.1.20.
Modified the description and Figure 2.1.27.
Modified the description of Note and Figure 2.1.40.
Modified the description and Figure 2.5.1.
Modified the setting range table.
Modified Table 3.5.1.
Modified the description and Figure 4.1.1.
Modified the description.
Modified Appendix F, G and O.
Added note.
Modified Table 3.2.1.
Modified Table 3.4.1.
Modified Table 3.5.1.
Modified the description.
Modified Appendix G, H and K.

331

6 F 2 S 0 7 5 8
Version
No.
0.8

0.9

Date
Aug. 31, 2010

Dec. 7, 2010

Revised Section
Precaution
2.1.1.1
2.1.3.3, 2.1.3.4
2.5.2
3.5
3.6.3
4.2.3.4, 4.2.4.1,
4.2.6.6, 4.2.6.7
6.6.1
Appendices
1
2.1.3.3, 2.1.3.4, 2.2.3
2.5.3
3.1.1, 3.2.1, 3.4.1
3.4.3
3.5
4.1.2
4.2.1, 4.2.2
4.2.3.1 to 4.2.4.5
4.2.5, 4.2.6
4.2.6.4, 4.2.6.6,
4.2.6.7
4.6
6.4.2, 6.5.1.2
6.6.1
Appendices

Contents
Modified the description.
Modified the description and Table 2.1.1.
Modified the setting range table.
Modified the description.
Modified the description and Table 3.5.1.
Modified the description.
Modified the description.
Modified the description.
Modified Appendix K and O
Modified the description and Table 1.1.1.
Modified the setting range table.
Modified the description.
Modified Table 3.4.2.
Modified Table 3.5.1.
Modified the description.(Modbus)
Modified the description.
Modified the description and sample screens.
Modified the description.
Modified the description and sample screens.
Added 4.6 Modbus Interface.
Modified the description.
Modified a sample of screen.
Modified Appendix H, K, M and P. Added Appendix N.

332