You are on page 1of 6

Generator Specification

(Diesel - 480V Available)

Generator Model:
Engine Model:
Alternator:

TC1650
Cummins KTA50-G9
Stamford PI734B
Three Phase

Power Factor:
Cos = 0.8

Prime Power
PRP
kW
kVA
1200
1500

Standby Power
LTP
kVA
kW
1650
1320

60Hz
1800 r.p.m
Rating
Voltage (V)
480/277

Scope of Supply:
High efficient water cooled diesel engine
Brushless alternators (Class H, with AVR.)
Heavy duty rubber anti-vibration mountings
24V starter batteries and connecting cables
Engine-drive battery charging alternator
Container type generator sets
Auto start Digital Control Panel
Radiator with cap and drain point
Fully guarded engine driven fan
Circuit Breaker
Fuel tank for 6-8 hours running
Operation & Maintenance Manual & Diagrams
Factory Testing Report

Emissions Certification:

Rated Current
(Amp)
1804,27
We reserves the right to change the specifications
without notice and without any obligation or liability
whatsoever.

Warranty:
The goods manufactured Tang Power are under
warranty against defects in materials and workmanship
for a period of 12 months or 1000 hours whichever
come first from the date of delivery to the end user
(except the damageable spare parts of genset caused by
incorrect man-made operation), and that the
aforementioned warranty for the same token is back up
by the engine & alternator manufactures and their
global distributors.
Silent Type Genset: 12000*2400*2400mm/10000kg
Dimension need to be confirmed before
shipment,canopy design are subject to change
without notice.

Generator Specification
(Diesel - 480V Available)

Generator Model:
TC1650
Engine Model:
Cummins KTA50-G9
Alternator:
Stamford PI734B
(1) Engine Specification
General Performance
Manufacture

CCEC Cummins

Engine Model
Engine Type
Engine Speed
Base Output Power
Standby Power
Governor Type

KTA50-G9
4 Cycle, 60 Vee, 16 Cylinder
1800 r.p.m
1384kW/1855hp
1656kW/2220hp
Electronic

Coolant Capacity - Engine Only


Standard Thermostat (Modulating) Range
Maximum Top Tank Temperature
- Standby Power
- Prime Power

Air Intake Way


Displacement
Cylinder Bore * Stroke
NO. of Cylinders

Turbocharged & Low Temp. Aftercooled


50.3L
159mm 159mm
16

Electrical System Voltage:


Battery:
Connecting Cables:

Compression Ratio

13.9:1

Thermal

Engine Idle Speed


Piston Speed
Intake Air Flow

725-775 r/min
9.5 m/s
2075 Litres/sec.

Radiated Heat to Ambient


Heat Rejection to Coolant
Heat Rejection to Exhaust

Cooling System
140 Litres
82 - 93
104
100

Electric System
24V
Maintenance-free
Auailable
170-200kkW
620-715kW
910-1040kW

Generator Specification
(Diesel - 480V Available)

Generator Model:
Engine Model:
Alternator:
Exhaust System

TC1650
Cummins KTA50-G9
Stamford PI734B

Exhaust Gas Flow

5025 Litres/sec.

(2) Alternator Specification

Exhaust Gas Temperature


Maximum Back Pressure

470 - 515
51mm Hg

Manufacture / Brand:

STAMFORD

635mm H2O
381mm H2O

Model
AVR Model
Winding Leads
Phase
Power Factor

PI734B
MX321
6
3 Phase
Cos = 0.8

Oil Pan CapacityHigh-Low

178-148 Litres

Winding pitch - Code


Drip Proof

2/3 - (N 6)
IP 23

Maximum Oil Temperature


Maximum Oil Consumption

121
N/A

Prime Output Power

Fuel System

Standby Output Power


Direct Injection Cummins PT Insulation class
Voltage regulation
392 Litres/hour
Total harmonic TGH / THC
330 Litres/hour
Wave form : NEMA = TIF - (*)
257 Litres/hour
Wave form : I.E.C. = THF - (*)
180Litres/hour
Altitude
Only Base Frame

1352kW/1690kVA
1448kW/1810kVA
H
0,5 %
<3,5%
< 50
<2%
1000 m

Air Intake System


Recommended intake piping size
Maximum Intake Air Restriction
- Dirty Element
- Clean Element

N/A

Lubrication System

Type Of Injection:
Fuel consumption:
1- At 100% Standby power
2- At 100% Prime power
3- At 75% Prime power
4- At 50% Prime power
Fuel Tank Capacity:

(A) Informations:

General Data - 60HZ/1800r.p.m

Prime Power:
Available continuously at variable load
in lieu of commercially purchased
power for an unlimited number of
hours per year in accordance with
ISO8528-1, and an overload of 10%
permitted for one hour in every
twelve hours of operation in
accordance with ISO 3046-1.

(B) Informations:
Standby Power:
Emergency Standby Power in variable
load applications in accordance with
ISO8528-1 in the event of a utility
power failure. No overload available
for this service as relevant alternators
are peak continuous rated at 27.

Generator Specification
(Diesel - 480V Available)

Generator Model:
Engine Model:
Alternator:

TC1650
Cummins KTA50-G9
Stamford PI734B

Control Systems
Synchronising Panel:
ModelComAp IC-NT MINT
* Compact gen-set controller for gensets operating
in multiple island and/or parallel to mains mode
(together with MainsCompact NT)
*Cooperation of up to 32 gen-sets
* Simple paralleling (easy wiring, installation and
configuration
Key features:
*Generator measurements: V, A, kW, kVAr (3
phase, true RMS), Hz, including energy counters
*Bus measurements: V (3 phase, true RMS), Hz
*Generator and Engine protections (incl. Vector
Shift)
*Automatic synchronizing and load control (via
speed governor or ECU)
*AVR control (Volt and PF control)
*Digital active and reactive load sharing
*Advanced power management function
o Load Dependent Start/Stop
o Load Demand Swap
o Running Hours Equalization
*Wide range of communication interfaces RS232,
RS485, USB, Modbus, GSM/Analog modem,
GPRS, Ethernet
*Support of electronic controlled engines (J1939,
Modbus)
*Event based history with capacity for nearby 200
records.

3 Pole MCCB upto 1250A as


Standard (4 Pole or ACB above
1250A as optional)
The generators are supplied
together with a circuit breaker that
permits a thermal protection
against overloads and magnetic
protection against short-circuit.

Generator Specification
(Diesel - 480V Available)

Generator Model:
Engine Model:
Alternator:

TC1650
Cummins KTA50-G9
Stamford PI734B

Mains supervison controller: MainsCompact NT MC-NT)

*Mains controller for multiple systems equipped


with InteliCompact NT MINT gen-set controllers
*Mains monitoring and protection
*Synchronizing of the gen-set group to the mains

Standard Enclosure / Canopy / Container


(Sound-attenuated & Weather Protective)

Common Type Canopy (for Gensets 800kva)

Containerized Canopy (for Gensets 750kva)

Extremely Rugged & Highly Corrosion ResistantConstruction

Robust Container Design

Body made from 2.0mm sheet steel components with powder coating
Base Frame & 4-12 hours built-in fuel tank integrated into the skid-mount base (TBC)
Excellent design and craftmanship
Zinc alloy with black powder coated or Bright polished stainless steel hinges tested
and proven to withstand corrosive conditions.
Compact structure and longer service life

20ft 40ft (HC also available) ISO footprint


Container made from steel components with durable paint system
Full bunded steel floor and steel louvres
Rugged surface - excellent corrosion & rust protection
Long service life

Easy Commissioning and Maintenance

Excellent Access for Maintenance

Quick fix electrical power connections


1ph and 3ph easy accessible electric sockets as optional
Side doors allowing 180opening rotation
Radiator fill access through cover in canopy roof.
Lube oil drain and radiator drain

Separate & Standing control cabinet at one side


Walk around interior with access doors
Fully bounded steel floor
Anti-explosive light bulb

Generator Specification
(Diesel - 480V Available)

Generator Model:
Engine Model:
Alternator:

TC1650
Cummins KTA50-G9
Stamford PI734B

Security and Safety

Security and Safety

Earth leakage protection


40-50mm non-inflammable sponge inside
Control panel viewing window in a lockable access door
Emergency stop button mounted on canopy exterior
Fuel fill and battery can only be reached via lockable door
Exhaust silencing system enclosed for operator safety
Excellent cooling system to avoid high water temp.,
Reliable operation under harshest conditions
Ambient temp.upto 40-52 and altitudes up to 1000M

Control panel viewing window in a lockable access door


Emergency stop button mounted on canopy exterior
Fuel fill and battery can only be reached via lockable door
Fire extinguisher
Fuel fill and battery can only be reached via lockable door
Exhaust silencing system enclosed for operator safety
Excellent cooling system to avoid high water temp.,
Reliable operation under harshest conditions
Ambient temp.upto 40-52 and altitudes up to 1000M

Transportability

Transportability

Lifting points on baseframe


4L engine drive genset, single hook on top prepared, to be confirmed.
4L engine drive genset, hook as optional, to be confirmed.

ISO shipping dimensioned container


CSC Certificate
Lifting capability

Quiet (Reduce Sound and Vibration)

Quiet (Reduce Sound and Vibration)

Noice Level:
73-80dBA at 1m & 65-72dBA at 7m (Small capacity genset)
77-88dBA at 1m & 67-78dBA at 7m (Middle and big capacity genset)

Noice Level:
85-88dBA at 1m

You might also like