You are on page 1of 15

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
1 of 15

Specification for Capacitor bank

B02

17-Mar-14

Issued for Design

S.Garjani

S.Garjani

A.bodaghi

B01

07-Jun-14

Issued for Comment

T.Rostami

S.Garjani

A.bodaghi

Rev.

Date

Description

Prepared

Checked

Approved
SAZ. POI :

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

IFC1

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
2 of 15

TABULATION OF REVISED PAGES


SHEET
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50

REVISIONS
01 02 03 04 05 06 07
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

SHEET

REVISIONS
01 02 03 04 05 06 07

51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
3 of 15

1. GENERAL ................................................................................................................. 4
2. Applicable Documents .............................................................................................. 4
3. Definitions ................................................................................................................. 4
4. Overview ................................................................................................................... 4
5. General Requirements .............................................................................................. 4
6. Applicable codes and standards ............................................................................... 5
7. Abbreviations ............................................................................................................ 5
8. General ..................................................................................................................... 6
9. Application ................................................................................................................ 6
10.

Construction Requirements ................................................................................... 8

11.

Auxiliary Circuits .................................................................................................. 10

12.

Interfaces with Power Distribution Control System - PDCS ................................. 11

13.

Miscellaneous ...................................................................................................... 11

14.

Inspection and Testing ......................................................................................... 12

15.

Shipping, handling And Storage .......................................................................... 14

16.

Guarantee ............................................................................................................ 15

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
4 of 15

1. GENERAL
1.1

Scope

This job specification shall be used to support the engineering, manufacturing and supplying
of Capacitor bank for the south YARAN Project.

2. Applicable Documents
Document references which shall be used in conjunction with this general specification are
listed below, but shall not be limited to the below documents;
SYME-ELBASC-ENEL-SPMC-0002
Specification For LV Switchgear and MCC
SYME-ELBASC-ENEL-SPMC-0001
Specification For MV Switchgear and MCC
SYME-ELBASC-ENEL-SPEL-0004
Specification For PDCS
SYME-ELBASC-ENEL-CIDE-0001
Electrical Design Criteria
Material and equipment standard for power
IPS-M-EL-181(2)
factor improvement capacitor
In the event of any conflict between this specification and engineering documents, this
specification shall take precedence.

3. Definitions
OWNER
CLIENT
CONSULTING ENGINEER
PROJECT
LOCATION
APPROVED

: NIOC
: Petroleum Engineering and development Co.(PEDEC)
: SAZEH Consultants
: South Yaran oil Field Development (Basic Engineering)
: Khuzestan Province-120Km west of AHWAZ
: Approved by Client

4. Overview
4.1

Introduction

South Yaran oil field is located in Khuzestan province 120KM west of Ahwaz with 20Km
length and 2.5Km width at south part of Yaran oil field.
24 No wells considered at this area consisting of 14 No Sarvak wells, 8 No Fahlian &
Gadvan wells and 2 No appraisal wells for sarvak and fahlian&Gadvan layers with total
estimated output between 50,000 to 60,000 STB/Day.
Flow of wells is transferred to the 2 phase separation unit (Cluster) for separation of gas
from liquids and dehydrating of gas.
The dehydrated gas is transferred to NGL 3200 and the liquids are transferred to Karoon
production plant for further processing.

5. General Requirements
5.1

Language

All documents, drawings and submittals shall be in English.


This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

5.2

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
5 of 15

Climate data
Max absolute temperature
Min temperature
Max & Min Wind speed
Storm wind speed
Soil temperature
Maximum sun temperature
Rain fall volume
Barometric pressure
Maximum & Minimum Humidity

50 oC
0 oC
9.6 & 6.2 m/s
68 m/s
40 oC (1m under finish grade)
85 oC
170-250mm/y
736 mmHg
74% & 41%

6. Applicable codes and standards


The following standards shall be added to the standard list of clause 2:
IEC 60044 Instrument transformers
IEC 60050-191 International Electrotechnical Vocabulary, Dependability and quality of
service
IEC 60068 Environmental testing
IEC 60073 Basic and safety principles for man-machine interface, marking and
identification. Coding principles for indicators and actuators.
IEC 60255 Electrical relays
IEC 60265 High voltage switches
IEC 60282 High voltage fuses
IEC 60364 Low-voltage electrical installations
IEC 60445 Basic and safety principles for man-machine interface, marking and
identification -Identification of equipment terminals and of terminations of certain designated
conductors, including general rules for an alphanumeric system
IEC 60446 Basic and safety principles for man-machine interface, marking and
identification of conductors by color or numerals.
IEC 60470 High-voltage alternating current contactors and contactor-based motor-starters
IEC 60529 Degrees of protection provided by enclosures (IP Code)
IEC 60549 High-voltage fuses for the external protection of shunt power capacitors
IEC 60644 Specification for high voltage fuse-links for motor circuit applications.
IEC 60688 Electrical measuring transducers for converting ac electrical quantities to
analogue or digital signals
IEC 60694 Common specifications for high-voltage switchgear and control-gear standards
IEC 60871 Shunt capacitors for a.c. power systems having a rated voltage above 1000V
IEC 61000 Electromagnetic compatibility (EMC)
IEC 62271 High-voltage switchgear and control-gear
BS 381C
Specification for colours for identification, coding and special purposes
The design shall be performed based on the requirements detailed in this specification.

7. Abbreviations
DCS

Distributed Control System


This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
6 of 15

ELCB
Earth Leakage Circuit Breaker
IRP
Interposing Relay Panels
HV
High Voltage
MV
Medium Voltage
LV
Low Voltage
PDCS Power Distribution Control System
MCC Motor Control Centre

8. General
8.1

Electrical Service Conditions

Equipment shall be supplied in accordance with the single line diagrams and data sheets. All
equipment shall be rated for continuous operation at full load service. The rating (voltage,
current, frequency, fault current, etc.) shall be as stated on the single line diagrams/data
sheets. Short time current rating as well as making and breaking capacity shall be certified
by a recognised independent testing authority.
Equipment shall be suitable for operation, without deteriorating effect, with variations of
voltage and frequency as follows:
High voltage supply 10%
50 Hz frequency
2%
Transient voltage depressions down to 80% of rated voltage shall not affect performance of
the equipment.
8.2

Environmental Data

Capacitor banks shall be installed in air-conditioned electrical room in a non-hazardous


atmosphere.
All equipment shall be capable of continuous operation at site condition without deleterious
effect.
8.3

Extent of Supply

Extent of supply shall consist of the design, production of material, fabrication, manufacture,
drawings and data, assembly, painting, testing and all sub-supplier co-ordination.
All instructions for assembly, disassembly maintenance, placing in service, operation, etc.,
shall also be furnished.

9. Application
9.1 Each capacitor bank assembly shall consist of a metal-clad, free floor standing, vertical,
front access, dead-front steel structures, containing power buses, a ground bus, power
circuit breakers/fuses/contactors, capacitor banks with built-in fuses, series reactor, auxiliary
control devices, instrument transformers (CTs/VTs), relays, meters, meter switches, control
switches, indicating lights and other necessary components.
The enclosure, buses, fused contactors, secondary wiring, cable terminations, instrument
transformers and transducers shall be in accordance with relevant clauses of Specification

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
7 of 15

for LV Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0002) & Specification for MV


Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0001)
9.2 Capacitor banks shall be connected to distribution switchgear or motor control centers
by means of suitable switching devices..
9.3 The switching devices shall be approved for such duty and shall be rated for 1.5 times of
rated current of the capacitor banks. They shall be able to withstand transient inrush
currents of up to 100 times of rated current of the capacitor banks. The switching devices
shall be equipped with suitable over current protections.
9.4 Connecting cables between the switching device and the capacitor bank shall have a
continuous current rating of 1.5 times the nominal current rating of the capacitor bank.
9.5 In case of installing two medium voltage capacitor banks in parallel, the inrush current of
the capacitor bank in parallel with the energized one shall be investigated and current
limiting reactors shall be used when necessary (refer to Annex D of IEC 60871-1 for Inrush
Transient Current).
9.6 Automatically controlled capacitor bank which regulates reactive power shall be adopted
as per Project Data Sheet and Single Line Diagram, in order to keep the power factor at
target level. Automatically controlled scheme can be adopted when the capacitor kVAR is
more than 15% of the size of upstream transformer in kVA. In such case a power factor
controller can be included to connect or disconnect capacitors as required. The number of
steps for connecting capacitors shall be approved by Company.
9.7 The power factor controller includes power factor sensor (or regulator) together with
appropriate contactors and protective devices.
9.8 Three phase medium and high voltage capacitor banks can be connected Delta, Star or
Double star. The supplier shall indicate connection mode in data sheet.
9.9 Medium and high voltage capacitor banks of 1000 kVAR and above shall be connected
as Double star. Double star capacitor banks shall be equipped with unbalance protection
monitoring the current flowing between the two neutrals of the star connections.
9.10 When a network or a transformer supplies power to device which generates harmonics
such as variable speed drives or big battery chargers, UPSs, etc. the capacitor voltage shall
be increased and detuning reactors shall be connected in series with the capacitor bank.
9.11 When the harmonic generating load is less than 20% of the total load, the voltage of
the power factor correction capacitors shall be increased by at least 10%. In case where
more than 20% of the total load is harmonic generating, detuning reactors shall additionally
be supplied with the capacitor bank.
9.12 The detuning reactors shall be sized so that the resonance frequency of the detuned
capacitor bank shall be at the frequency of the 5th harmonic.
9.13 When reactor is used in series with capacitor bank as detuning reactor or current
limiting reactor, the kVAR rating of the capacitor at 50 Hz shall be increase so that the KVAR
This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
8 of 15

of the combined capacitor plus reactor shall be equal to the required kVAR indicated in data
sheet. More over the voltage rating of the capacitor shall be increased proportional to reactor
voltage.

10. Construction Requirements


10.1

Enclosure

10.1.1 The capacitor bank shall be metal enclosed self-supporting, free standing, floor
mounted made of sheet steel, containing power buses, ground bus, circuit breakers, fuses,
contactors, capacitor units, reactors, auxiliary control devices, instrument transformers,
relays, meters, switches, indicating lights and other necessary components.
10.1.2. The enclosure, buses, fused contactors, Circuit breaker, secondary wiring, cable
terminations, instrument transformers and transducers shall be in accordance with relevant
clauses of Specification For LV Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0002)
& Specification For MV Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0001).
10.1.3 The enclosure shall be suitably subdivided into separate compartments, such as
power entrance compartment, capacitor compartment and when required switching
compartment. The internal partitions shall be metallic and shall be earthed.
The capacitor compartment shall be properly ventilated. When forced ventilation is required,
thermostatically controlled fans shall be supplied.
10.1.4 Doors of the enclosures shall be equipped with proper danger and warning sign.
10.2

Capacitor Units

10.2.1 Low voltage capacitors shall be of the self-healing type and shall comply with the
requirements of IEC 60831 and may be of either three phases or single phase construction
Medium voltage and high voltage capacitors shall comply with the requirements of IEC
60871.
10.2.2 Capacitor units may consist of one or more capacitor elements. The electrodes and
dielectric materials of the capacitor elements shall be indicated in data sheet.
10.2.3 Each capacitor unit shall be enclosed in a sealed case. The case of medium voltage
and high voltage capacitor unit shall be welded steel.
10.2.4 The insulating medium of low voltage capacitor units shall be according to IEC
recommendation and shall be indicated in data sheet. Dry type air insulated capacitor is
acceptable for low voltage application. The insulating medium shall be suitable for the
maximum ambient temperature or room temperature indicated in data sheet.
10.2.5. The leads of each capacitor unit shall be brought out through sealed connectors or
bushings made of high quality resin or porcelain. The complete assembly shall be a sealed
unit.
10.2.6 Medium and high voltage capacitor units shall be oil filled. The units shall not contain
polychlorinated biphenyl (PCB). The supplier shall indicate the insulating medium of the
capacitor units in data sheet.
This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
9 of 15

10.2.7 Suitable means shall be provided on the metal case of each capacitor unit for
connecting the metal case to ground.
10.2.8 The leads of each capacitor unit shall be brought out through sealed connectors or
bushings made of high quality resin or porcelain. The complete assembly shall be a sealed
unit.
10.2.9 The insulating medium of low voltage capacitor units shall be according to IEC
recommendation and shall be indicated in data sheet. Dry type air insulated capacitor is
acceptable for low voltage application. The insulating medium shall be suitable for the
maximum ambient temperature or room temperature indicated in data sheet.
10.3

Internal Fuses

10.3.1 Internal fuses shall be provided to effectively remove a capacitor unit from the circuit
in case of capacitor unit failure. Operation of a capacitor fuse shall be indicated by a suitable
visible means.
10.3.2 For low voltage capacitor units, internal over pressure disconnectors can be
supplied instead of fuses
10.3.3 Internal fuses shall comply with IEC 60871-4.
10.4

Discharge Resistor

10.4.1 Low voltage capacitor unit shall be provided with a discharge resistor to discharge the
stored energy of the capacitor and reduce the voltage of the unit from the peak voltage (2
times the rated voltage) to 75 volt or less in 3 minutes after disconnection. The method of
connection of the resistors to capacitor units shall be according to IEC 60831-1 with a K
factor of 1.
10.4.2 Medium voltage and high voltage capacitor unit shall be provided with a discharge
resistor to discharge the stored energy of the capacitor and reduce the voltage from the
peak voltage (2 times the rated voltage) to 75 volt or less in 10 minutes after disconnection.
10.4.3 There shall be no fuse, switch or any other disconnecting device between the
capacitor unit and the discharge resistors.
10.4.4 The resistance of the discharge resistors shall be calculated according to the
formulas given in IEC 60871-1. The supplier shall indicate in data sheet, the size of
discharge resistors in ohm.
10.4.5 In order to meet the requirements of paragraph 10.4 additional discharge resistors or
reactors may be installed at the capacitor contactors or at the power supply switching device
located in the station switch room. Such scheme shall be approved by Company.
10.4.6 The supplier of the capacitor bank may propose, as an option, the application of
discharge reactors instead of discharge resistors for each capacitor unit.

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

10.5

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
10 of 15

Grounding (Earthing) Switch

10.5.1 On the capacitor enclosure, a load break switch shall be provided for grounding
(earthing) capacitors. The operating handle of this grounding switch shall be outside the
enclosure. The grounding switch shall be closed after the elapse of the times specified in
paragraph 10.4
10.5.2 For medium voltage and high voltage capacitor banks, a grounding switch safety
relay shall be included when necessary to prohibit the operation of the grounding switch
before the elapse of the above mentioned time.
10.5.3 The grounding switch, when in closed or ground position shall short circuit and
ground the capacitor leads and discharge the remaining energy left on the capacitors. This
switch shall be key interlocked with the power supply switching device located in the station
switch room.
10.5.4 It shall not be possible to close the grounding switch before opening the power
supply switching device and the power supply switching device may only be closed after the
grounding switch is opened.
10.6

Safety Requirement

10.6.1 Safety interlocks shall be provided between the power supply switching device
located in the station switch room and the grounding switch specified in clause 10.5
10.6.2 The power supply switching device shall be opened and locked in open position
before operating the handle of the grounding switch.
10.6.3 The grounding switch shall be closed and locked in grounding position before
opening the door of the capacitor compartments.
10.6.4 The interlock system and the type and location of the grounding switch shall be
approved by Company.
10.6.5 The purchaser will provide the interlock elements in the form of electrical interlock
and/or key interlock.
10.7

Marking

10.7.1 The information outlined in IEC 60871-1 shall be marked on each capacitor unit
either directly or on a rating plate attached to each unit.
10.7.2 Each capacitor bank shall have a rating plate. At lease the information outlined in
IEC 60871-1 shall be engraved or indelibly marked on such rating plate.

11. Auxiliary Circuits


Auxiliary voltages shall be as follows:
Contactors
: 110V DC (external supply)
Switchboard anti-condensation heaters and lighting : 230V AC (external supply)

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
11 of 15

Auxiliary supplies shall be distributed throughout the switchboard by means of standard


conductors.
Control voltage shall be 110V dc. The control circuit including protection relays, controller,
trip and close coils and auxiliary relays shall be capable to work on a voltage range of
88VDC to 126.5VDC. The control power source shall be supplied by the Purchaser.
Close and trip circuits for each breaker shall be separately protected by miniature circuit
breakers.
Auxiliary supplies (closing, tripping, control, indication, heaters, etc) shall be in accordance
with the datasheet, and shall have under voltage alarms in each incoming supply and sub
fuses or MCBs for each circuit breaker Circuit breaker/contactor closing, tripping, control
and indication power and contactor protection shall be supplied by feeders from suitably,
rated external DC supply units, for which supplier shall specify load requirements.
Suppliers shall specify auxiliary load requirements.

12. Interfaces with Power Distribution Control System - PDCS


The following shall be hardwired from the PDCS RTU to the capacitor bank switchboard.
Further details can be found on the data sheet and PDCS I/O List
- General fault (lockout relay)
- Metering information (from dedicated transducers)
The Power Distribution System I/O list provides a guide to the signals to be made available
from the switchboard.

13. Miscellaneous
13.1

Earthing

An earthing bus bar shall be provided along the full length of the capacitor cubicle structure
with the provision for the earth cable connections at each end. Earthing bus bars shall be
made of hard drawn copper.
Earthing facilities shall be provided as per relevant clauses of Specification For LV
Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0002) & Specification For MV
Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0001).
13.2

Anti-Condensation Heating

Enclosures shall be equipped with anti-condensation heaters of sufficient capacity to prevent


the formation of condensation within the enclosure under service conditions.
Anti- condensation heaters shall be installed at the bottom of each vertical section and shall
be individually protected by ELCB 30mA. Heaters shall be controlled by hygrostats. A
dedicated feeder breaker shall be provided with alarm contacts.
Space heaters shall be 230V, 50Hz, single phase and shall be supplied from an external
source by PURCHASER.
13.3

Special Tools and Accessories

Special tools and accessories shall be proved as per relevant clauses of Specification For
LV Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0002) & Specification For MV
Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0001).

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

13.4

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
12 of 15

Painting and Fastener Protection

Unless otherwise indicated in data sheet, switchgear shall be painted light grey, BS 381C,
No. 361 (IPS-E-TP-100).
The complete interior surface of the enclosure shall have a find coat of moisture and fungus
resistant vanishes.
All fasteners, bolts, etc., shall be protected against oxidation by a coating appropriate to the
type of metal.
VENDOR shall supply paint, matching each color used, for filed touch-up after installation
of equipment. Two spray cans of each color shall be supplied per assembly.

14. Inspection and Testing


14.1

General

All equipment covered by this specification shall be subjected to inspection and testing
witnessed by the COMPANY at the works during manufacture. In certain cases these
activities may extend to sub-suppliers.
Inspection and testing shall be in accordance with IEC standards.
The equipment under this specification shall be factory tested. Certified copies of test reports
and certificates shall be submitted to the Purchaser.
14.2

Routine Tests

Routine test shall be performed according to the requirements of IEC 60871-1 and the
relevant IEC publications referred to therein.
Capacitance and output
Capacitor losses
Voltage test between terminals
A.C. Voltage test between terminals and container, dry test
Tests between terminals and earth for capacitor banks
Self-healing test, only for self-healing metabolized power capacitors
Oil leakage test, relevant test shall be performed to prove tightness of all oil filled
compartments.
All the other applicable tests mentioned in Specification For LV Switchgear and MCC
(SYME-ELBASC-ENEL-SPMC-0002) & Specification For MV Switchgear and MCC
(SYME-ELBASC-ENEL-SPMC-0001).
14.3

Type Tests

Type tests shall be performed on selected capacitors according to the recommendations of


IEC 60871-1. The results of such tests on identical equipment are acceptable.
Type test in accordance with referenced standards shall have been carried out on suppliers
similar equipment and the type test certificate shall be provided with the proposal.
Capacitor losses
Thermal stability test
A.C. Voltage test between terminals and container, dry test
Impulse voltage test between terminals and container for capacitor
intended for exposed installations
Discharge test
This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

14.4

SHEET NO. : REV. :


B02
13 of 15

Ionization test

Other Tests

In addition each capacitor bank shall be subject to any such tests on site as are required to
prove compliance with the specification independently of any tests which may have already
been carried out at the manufacturers works.
These tests shall normally include:
Measurement of the capacitance of each capacitor equipment
Measurement of the out of balance signal and adjustment of fuse failure
detecting equipment
An examination of the voltage wave form without and with the capacitor
banks connected.
All the other applicable tests mentioned in Specification For LV
Switchgear
and
MCC
(SYME-ELBASC-ENEL-SPMC-0002)
&
Specification For MV Switchgear and MCC (SYME-ELBASC-ENELSPMC-0001).
14.5

Field Tests

Field tests shall be carried out before power capacitor banks are energised and/ or placed in
service and shall include but limited to:
Insulation check
Primary injection and adjustment of all protective devices
Interlock and inter-trip function
Earthing device interlock preventing closing of earthing device while
capacitor is energized
Phase rotation
PDCS interface functions
Check of earthing circuits (effective and continuous connection).
Interconnection and cabling check between cubicles
Power frequency dielectric withstand
Full functional check of each unit
Resistance test measurements across all busbar connections, circuit
breakers and incomer/outgoing copper-work
Voltage transformer ratio and phasing checks
Current transformer ratio and polarity checks
Verification of current transformer magnetization curves for main incomer
and feeder protection current transformers.
Secondary injection tests for all protection relays to prove time/current
characteristics (minimum of 3 points)
Injection of all feeder earth leakage relays
Primary injection of all indicating instruments
Mechanical operation of all circuit breakers and contactors
Visual examination (appearance, paintwork, finish, welding, sheet metal,
lifting rings, assembly bolt tightness, busbar tightness, conformity of
torque tightness for main connections, wiring and internal cabling
This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
14 of 15

appearance, lining up of measurement instruments, handling devices,


remote-control and signalling, indicator devices and name plate).
Size checks (terminals, busbars and wires, leakage path and isolation
distance, fixation axis, overall sizes, materials).

15. Shipping, handling And Storage


15.1

General

Capacitor bank assemblies shall be handled according to relevant clauses of Specification For
LV Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0002) & Specification For MV
Switchgear and MCC (SYME-ELBASC-ENEL-SPMC-0001).
15.2

Engineering Data Requirements

The vendor shall supply the necessary information with the quotation to enable evaluation of the
submitted proposal.
documents/drawings are not acceptable unless they are revised to show the equipment
proposed.
The documents to be supplied with the quotation shall at least include the following:
a) Completed enquiry data sheet/s
b) Summary of exceptions/deviations to this standard specification.
c) Brochures and catalogues containing description of typical capacitor banks.
d) Preliminary dimensional drawings
e) Type of packaging and approximate shipping weights.
The documents which shall be supplied at ordering stage, shall at least include the following:
a) Updated and completed enquiry data sheet/s.
b) Drawings showing main dimensions and arrangement of components.
c) Wiring diagrams of all accessories, or devices.
d) List of components or accessories, showing complete reordering information for all
replaceable parts.
e) Installation, operation and maintenance instruction/s.
f) Recommended spare parts list for two years of operation.
g) Test reports and/ or certificates for routine tests, type tests and special tests.

15.3

SHIPMENT

15.3.1 The supplier of the equipment under this specification is the sole responsible for
packaging and preparation for shipment.
15.3.2 The packaging and preparation for shipment shall be adequate to avoid mechanical
15.3.3 Each shipping package shall be provided with permanently attached identification tag
containing necessary information together with the capacitor identification number indicated in
data sheet .
15.3.4 Shipping documents with exact description of equipment for custom release shall be
supplied, with the equipment.

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.

PROJECT:

SOUTH YARAN OIL FIELD


DEVELOPMENT PROJECT
DOCUMENT TITLE
DOCUMENT NO

:
:

Specification for Capacitor bank


SYME-ELBASC-ENEL-SPEL-0003-B02

SHEET NO. : REV. :


B02
15 of 15

16. Guarantee
16.1 The supplier of the equipment under this specification shall guarantee the equipment and
shall replace any damaged equipment/parts resulting from poor workmanship and/or faulty
design.
16.2 The supplier shall replace any equipment/part failed under the following condition:
- Failure under startup and commissioning tests performed according to IEC recommendations.
- Failure under normal usage for a period of 12 months, not exceeding 18 months from the date
of dispatch from the manufacturers works.

This document is the property of OWNER. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited.