LOWER GROUND FLOOR

BASIS OF DESIGN
1.
2.
3.

5.
6.
7.
8.
9.
10.

Area to be air-conditioned
Total Area
Internal Load
Occupancy ( Persons )
Light (watt / sq.ft.)
Equipment Load ( KW)
Design conditions
Outside Summer / Monsoon
Inside Summer / Monsoon
Humidity
Air Change/hr
Dehumidified CFM
AC Load as per cfm
AC- Installed
Additional AC Required
Electric Power requirements

S.N.

LOCATION

LGF

AC AREA
CONSIDERED
SQ.FT ( SQM)

4500 (418)

:
:

Medicine store
4500 sq. ft (418.2 SQM)

:
:
:

08
1.5
1.0

:
:
:
:
:
:
:
:
:

42.3 /35 C
25.4 C 1.1C
65% 5
01
12600 cfm
31.5 TR
20.5TR
1x11.0TR Ducted Unit (4400 CFM)
45.5 KW (3 Phase, 415 V 10% )

IN-SIDE TEMP- C
REQUIRED

25.4 C 1C

AC CAPACITY
REQUIRED TR

32.0 TR

INSTALLED AC
CAPACITY -TR

ADDITIONAL
CAP. REQDTR

20.5 TR

11.0TR

****************

UPPER GROUND FLOOR

BASIS OF DESIGN
1.
2.
3.

5.
6.
7.
8.
9.
10.

S.N.

Area to be air-conditioned
Total Area
Internal Load
Occupancy ( Persons )
Light (watt / sq.ft.)
Equipment Load ( KW)
Design conditions
Outside Summer / Monsoon
Inside Summer / Monsoon
Humidity
Air Change/hr
Dehumidified CFM
AC Load as per cfm
AC- Installed
Additional AC Required
Electric Power requirements

LOCATION

AC AREA
CONSIDERED
SQ.FT ( SQM)

:
:

Medicine store
3200 sq. ft (297.3 SQM)

:
:
:

08
1.5
1.0

:
:
:
:
:
:
:
:
:

42.3 /35 C
25.4 C 1.1C
65% 5
01
10800 cfm
27.0 TR
21.5TR
1x 5.5TR Ducted Unit (2200 CFM)
37.5 KW (3 Phase, 415 V 10% )

IN-SIDE TEMP- C
REQUIRED

AC CAPACITY
REQUIRED TR

INSTALLED AC
CAPACITY -TR

ADDITIONAL
CAP. REQDTR

UGF

3200 (297)

25.4 C 1C

27.0 TR

21.5 TR

5.5TR

****************

FIRST FLOOR

BASIS OF DESIGN
1.
2.
3.

5.
6.
7.
8.
9.
10.

Area to be air-conditioned
Total Area
Internal Load
Occupancy ( Persons )
Light (watt / sq.ft.)
Equipment Load ( KW)
Design conditions
Outside Summer / Monsoon
Inside Summer / Monsoon
Humidity
Air Change/hr
Dehumidified CFM
AC Load as per cfm
AC- Installed
Additional AC Required
Electric Power requirements

:
:

Medicine store
2852 sq. ft (265.0 SQM)

:
:
:

10
1.5
1.0

:
:
:
:
:
:
:
:
:

42.3 /35 C
25.4 C 1.1C
65% 5
01
9200 CFM
27.0 TR
14.5TR
1x 8.5TR Ducted Unit (3400 CFM)
30.5 KW (3 Phase, 415 V 10% )

S.N.

LOCATION

FF

AC AREA
CONSIDERED
SQ.FT ( SQM)

2852 (265)

IN-SIDE TEMP- C
REQUIRED

25.4 C 1C

AC CAPACITY
REQUIRED TR

23.0 TR

INSTALLED AC
CAPACITY -TR

ADDITIONAL
CAP. REQDTR

14.5 TR

8.5TR

****************

REAR BUILDING - UPPER GROUND FLOOR


BLUE- R BIG HALL

BASIS OF DESIGN
1.
2.
3.

5.
6.
7.

Area to be air-conditioned
Total Area
Internal Load
Occupancy ( Persons )
Light (watt / sq.ft.)
Equipment Load ( KW)
Design conditions
Outside Summer / Monsoon
Inside Summer / Monsoon
Humidity
Air Change/hr
Dehumidified CFM
AC Load as per cfm

:
:

Medicine store
4000 sq. ft (371.7 SQM)

:
:
:

10
1.5
1.0

:
:
:
:
:
:

42.3 /35 C
25.4 C 1.1C
65% 5
01
13600 CFM
31.0 TR

8.
9.

AC- Installed
Air-Conditioning Cap(TR)Reqd.

:
:

10.

Electric Power requirements

SN

LOCATION

AC AREA
CONSIDERED
SQ.FT ( SQM)

IN-SIDE TEMP- C
REQUIRED

BLUE-R
BIG- HALL

4000 (371.7)

25.4 C 1C

0.0 TR ( NIL )
3x 8.5TR Ducted Unit(10200 CFM)
1x 5.5TR Ducted Unit (2200 CFM)
37.5 KW (3 Phase, 415 V 10% )
AC CAPACITY
REQUIRED TR

INSTALLED AC
CAPACITY -TR

31.0 TR

NIL

****************

REAR BUILDING - UPPER GROUND FLOOR


BLUE- R SMALL HALL

BASIS OF DESIGN
1.
2.
3.

5.
6.
7.
8.

Area to be air-conditioned
Total Area
Internal Load
Occupancy ( Persons )
Light (watt / sq.ft.)
Equipment Load ( KW)

:
:

Medicine store
1350 sq. ft (125.5 SQM)

:
:
:

05
1.5
1.0

Design conditions
Outside Summer / Monsoon :
Inside Summer / Monsoon :
Humidity
:

42.3 /35 C
25.4 C 1.1C
65% 5

Air Change/hr
Dehumidified CFM
AC Load as per cfm
AC- Installed

01
4400 CFM
11.0 TR
0.0 TR ( NIL )

:
:
:
:

CAPACITY
REQD- TR

3 X 8.5TR
1 X 5.5 TR

9.
10.

SN

Air-Conditioning Cap(TR)Reqd.
Electric Power requirements

LOCATION

BLUE-R
SMALL HALL

:
:

AC AREA
CONSIDERED
SQ.FT ( SQM)

IN-SIDE TEMP- C
REQUIRED

1350 (125.5)

25.4 C 1C

2x 5.5TR Ducted Unit(4400 CFM)


15.0 KW (3 Phase, 415 V 10% )

AC CAPACITY
REQUIRED TR

11.0 TR

INSTALLED AC
CAPACITY -TR

CAPACITY
REQD- TR

NIL

2 X 5.5 TR

****************

AIR-CONDITIONING & ELECTRICAL LOAD ASSESSMENT


MEDICINES STORE
LUCKNOW
AIR-CONDITIONING & ELECTRICAL LOAD ASSESSMENT
RANBAXY LABORATORIES LIMITED
MEDICINE STORES
LUCKNOW.
LOCATION

LOWER GROUND FLOOR

AC

AC

AC

DUCTED

DUCTED

DUCTED

DUCTED

DUCTED

DUCTED

LIGHT

1.5TR

2.0TR

1.0TR

AC 3TR

AC 5TR

7.5TR

11.0TR

8.5TR

5.5TR

LOAD

SPLIT

WRAC

WRAC

UNIT

UNIT

UNIT

UNIT

UNIT

UNIT

UPPER GROUND FLOOR

FIRST FLOOR

COMMON FLOOR AREA

MARKETING OFFICE

2
1
1

1.5

2
4

REAR UGF BLUE-R (BIGHALL)

REAR GF.BLUE-R (SMALLHALL)

TOTAL EQUIPMENT

1.5

0.5

12.5

INPUT (KW)

2.2

2.8

1.5

4.5

7.5

10

15

10

7.5

EQUIPT. LOAD (KW)

17.6

22.4

1.5

13.5

37.5

20

15

40

30

12.5

SANCTIONED LOAD-I

KW

75

SANCTIONED LOAD-II

KW

75

COMULATIVE SANCTIONED

KW

150

INSTALLED LOAD

KW

218.0

RUN.LOAD- 70% DIVERSITY

KW

152.6

KVA

180

CAPTIVE POWER REQD.


ADDL. D.G. SET PROPOSED

SUMMARY
AIR-CONDITIONING & ELECTRICAL LOAD
ASSESSMENT & REQUIREMENT
S.N.

ASSESSMENT CHECK
POINT

LOWER
GF

UPPER
GF

FIRST
FLOOR

COMMON
FLOOR
AREA

1X 11.0TR

1X 5.5 TR

1 X 8.5TR

MARKETING
OFFICE

REARHALL
UPPER GF
BLUE-R-I

REAR-HALL
G. FLOOR
BLUE-R-II

AIR-CONDITIONING REQUIREMENT
1.
2.

Additional AC requirement
Total additional AC Capacity
Required. - TR

3 X 8.5 TR
1 X 5.5TR

2 X 5.5TR

NIL

37.5 KW

15.0 KW

24.5 KW

1.5 KW

0.5 KW

67 TR

ELECTRICAL POWER REQUIREMENT


3.
4.
5.
6.
7.
8.
9.
10.

Additional Electrical Load


Required for AC KW
Total additional Load
Required. - KW
Existing Electrical
Equipment Load KW
Total Existing Equipment
Load- KW
Total projected Installed
Load - KW
Actual Load requirement with
70% diversity
Total Sanction Load KW
Connection -1 75 KW
Connection -2 75 KW
Additional Electrical
Load requirement -KW

15.0 KW

7.5 KW

10.0 KW

NIL
85.0 KW

38.7 KW

35.4 KW

21.8 KW

10.6 KW
133.0 KW
218.0 KW
152.60 KW
150.0 KW

( 152.6 KW 150 KW ) = 2.6 KW


The requirement of additional power is almost nil, however additional 7 to 10% Electrical energy can be
saved / spares by considering the energy saving steps like;
1. Additional wall and under deck insulation in proposed AC area of Blue-R stores
2. By maintaining power factor between 0.95 0.98 Leg.

CAPTIVE POWER REQUIREMENT


11.

Captive Power Requirement


as per projected Electrical

200 KVA ( 160 KW )

12.
13.

Load of total Area including


Marketing KVA (KW )
Existing Stand by D.G. set
Capacity KVA (KW)
Additional Captive Power
Requirement KVA (KW)

30 KVA ( 24 KW)
180 KVA ( 144 KW)

ELECTRICAL PANEL REQUIREMENT


14.
15.

NOTE

Existing Electrical
Distribution Panel
Add. Electrical Distribution
Panel requirement.

The existing running electrical distribution panel is not suitable to withstand and distribute additional load as
the same is very old (more than 12 years) and repaired/modified many time as per need.
A new Electrical Panel complete with necessary feeders as per proposed new distribution is required.
The Air-conditioning requirement projected above is additional to the existing rental ducted Air-conditioning
Units of total 30TR ( 3 x5.0 TR + 2 x 7.5TR ) installed on LGF, UGF & FF.