mov78452_epce02-20a Page 1

24-FEB-03

EPCE02-20A

HRV
Heat Recovery Ventilation

FA

VAM - FA series

Combined
Air Conditioning
and Ventilation
for Energy Efficiency
and Comfort

Cyan Magenta Yellow Black

mov78452_epce02-20a Page 2

T a b l e
o f
C O N T E N T S

Cyan Magenta Yellow Black

24-FEB-03

mov78452_epce02-20a Page 3

24-FEB-03

I NTRODUCTION

p4

F E AT U R E S O F DA I K I N H RV
First-class compactness in the industry
First-class energy conservation in the industry
Simple design and construction
Cleanliness

p6
p6
p7
p8
p8

C O N T R O L S YST E M S
p9
Centralised control of air conditioning and ventilation
p9
Various control systems according to applications and conditions p 12

page

Cyan Magenta Yellow Black

MODE L LI N E-U P

p 14

DIMENSIONS

p 16

S P E C I F I C AT I O N S

p 18

AC C E S S O R I E S
Installation of accessories
List of accessories
PC board adapter for heater control kit
Direct expansion coil unit

p 19
p 19
p 19
p 20
p 21

mov78452_epce02-20a Page 4

24-FEB-03

Introduction
Daikin's HRV (Heat Recovery Ventilation) recovers heat energy lost
through ventilation and holds down room temperature changes
caused by ventilation, thereby maintaining a comfortable and clean
environment. This also curbs the load on the air conditioning system
and conserves energy.

The HRV creates


a high-quality
environment by
interlocking
with the
air conditioner

In addition, the HRV is interlocked to Daikin's VRV system,


Sky Air and other air conditioning systems and automatically
switches over ventilation mode,further increasing the effects of
energy conservation. HRV operation has been centralised on
the air conditioner remote control allowing total control over
air conditioning and ventilation with a simple configuration.

VAM-FA Series Released !


9 MODELS TO CHOOSE FROM !
First-class compactness in the industry
Has been achieved by employing a newly developed High
Efficiency Paper (HEP) element, and using an optimized fan
and airflow passage design.
First-class energy conservation in
the industry
A total of 28% reduction of air conditioning load has been
achieved through a combined use of total heat exchange
mode, linked operation with an air conditioner, and
pre-heat/pre-cool control.
Standard operation down to -15C
The new operation mode is activated when outdoor
temperature goes down to -10C or below, preventing
freezing or condensation in the unit. Standard models can
now be used in cold climate regions.
page

Cyan Magenta Yellow Black

mov78452_epce02-20a Page 5

24-FEB-03

DAIKIN INDOOR UNIT

Operating mode signal


Filter cleaning signal
LCD remote control
for indoor unit
BRC1C517

Failure detection signal

HRV UNIT

ON/OFF signal
Cooling/Heating mode signal
Set temperature signal
Ventilation signal
Humidifier ON/OFF signal

page

Cyan Magenta Yellow Black

mov78452_epce02-20a Page 6

24-FEB-03

F e a t u r e s o f D a i k i n H RV
VA M - FA s e r i e s

First-class
compactness in
the industry

First-class compactness in the industry, yet incorporating the same


performance and functions, 9 models of the VAM-FA series have
been released.

30%

Over 30% size reduction

Installation under the floor of a small building

The use of the specially developed High Efficiency Paper (HEP)


element and optimized design of the fan and airflow passages,
has enabled first-class compactness in the industry while
maintaining some 28% reduction of air conditioning load as
before. The height of the main unit has been reduced by up to
40mm and easily fits in limited spaces, such as in ceilings.

348mm

Installation under a beam

The VAM1000FA5VE is 348mm high and can be installed in narrow


ceiling voids.

Installation in an irregular space

Specially developed HEP element


The heat exchange element uses a High Efficiency Paper (HEP)
that has superior moisture-absorption and humidifying properties
and doubles the current efficiency of moisture-absorption. This
heat exchange unit speedily recovers heat contained in latent heat
(vapor) and its volume has been reduced about 25% while
maintaining the same heat recovery efficiency.
This element employs a material with superior flame-resistant
properties and is treated with an anti-molding agent.

page

Cyan Magenta Yellow Black

mov78452_epce02-20a Page 7

24-FEB-03

Auto-ventilation mode changeover switching

First-class energy
conservation in
the industry

Automatically switches the ventilation mode (Total Heat Exchange


Mode/Bypass Mode) according to the operating status of the air
conditioner.

TOTAL HEAT EXCHANGE MODE (cooling operation in summer/heating operation in winter)


Air exhaust fan

Room temperature sensor

Heat exchange element

Return air

Exhaust
air

Outdoor
air intake

Supply air
Outdoor air temperature sensor

Air Conditioning
Load Reduced by
28% on Average
(maximum 40%)

Air supply fan

BYPASS MODE (Intermediate season)


Heat exchange element
Air exhaust fan

1 20% by operating in total

Return air

Exhaust
air

heat exchange mode (in


comparison with normal
ventilation fans)

Air supply fan

Outdoor
air intake

2 Another approximately 6%

Supply air*
Intermediate season
Outdoor air temperature sensor

gained by auto-ventilation
mode changeover switching

Indoor air
temperature sensor

* The air cannot be supplied at


the same temperature as the outdoor
air because it is partly heat exchanged.

3 Yet another approximately


2% by pre-cool, pre-heat
control

Pre-cool, Pre-heat control


Reduces air conditioning load by not running the HRV while air is
still clean soon after the air conditioner is turned ON.

Note
The values mentioned above may vary according to
weather and other environmental conditions at
the location of the units installation.

page

Cyan Magenta Yellow Black

mov78452_epce02-20a Page 8

24-FEB-03

F e a t u r e s o f D a i k i n H RV
VA M - FA s e r i e s

Simple design
and construction

The unit can be installed upside down in accordance with


the conditions of the location.

Switch box
Access door

With only one 450mm square inspection aperture, maintenance and


heat exchange element replacement can be performed with ease.

Maintenance cover

Supply rich mode:

Raising the air supply maintains proper room pressure


to prevent back-flow of toilet/kitchen odours or
moisture inflow.

Portion of fresh-up
operation

HRV

Normal
ventilation fan

Exhaust rich mode:

Raising exhaust air decreases room pressure to prevent


the leaking of odours or floating bacteria into other
rooms.

Air exhaust

HRV

Floor area

Air supply

Air exhaust

Cleanliness

Fresh-up Operation

Air supply

Portion of
exhaust
operation

The user can select between


two fresh-up modes using the
remote control.

eg. Office

eg. Hospital

Prevents dust from


falling with directly
mounted ducts
A sign is displayed
on the remote control
when the air filter
needs cleaning

page

Cyan Magenta Yellow Black

Sick room

OFF

Dust

Blowing mode

No dust is blown out

With Competitors' Products

With HRV

When conventional total heat exchange units, which


are independently operated using a dedicated remote
control, are directly connected by a duct, there is a
possibility of dust falling from the air filter of the
indoor unit when the air conditioner is OFF.

When the HRV is operating independently,


the fan in a interlocked indoor unit continues
turning, so dust does not fall from the air filter.

mov78452_epce02-20a Page 9

24-FEB-03

Control
systems
The operation of the air conditioner using its remote control is
interlocked to the operation of the HRV, greatly simplifying overall
system operation. In addition, installation work associated with
the HRV remote control is not necessary because operations for
air conditioning and ventilation are completely centralised on
the air conditioner remote control.
Also, the use of such a centralised remote control allows the user
to choose a wide range of control systems that integrate air
conditioning and ventilation. Furthermore, by using a variety of
centralised control equipment, the user can build a large, highgrade centralised control system.

Centralised
control of air
conditioning
and ventilation

Operations and control with the air


conditioner remote control - BRC1C517

page

Cyan Magenta Yellow Black

Simultaneous ON/OFF of the HRV and air conditioner

Fan speed and ventilation mode can be altered by a simple push


on the button. After a few seconds, the HRV display will return
to the standard display showing the settings of the indoor unit

Independent operation of the HRV

Self-diagnosis functions

Filter sign display and reset

Timer settings (simultaneous control with air conditioner)

Pre-cool, pre-heat control settings (initial setting)

Fresh-up mode switching (Selectable: supply rich mode, exhaust


rich mode; Initial setting)

mov78452_epce02-20a Page 10

24-FEB-03

Control
systems

A variety of control
systems can be
controlled using
only the air conditioner
remote control

Group Control
One air conditioner remote
control simultaneously controls
up to 16 air conditioners and
1 HRV unit.

Air Conditioner

Up to 16 units
HRV
Air conditioner
remote control

Control via 2 remote controls


Allows control of air conditioner
and HRV units from two places
by connecting two air
conditioner remote controls.
(Group control possible)

Up to 500m

Air Conditioner
Group control
possible
HRV
Up to 500m
Air conditioner remote control (No.2)
Air conditioner remote control (No.1)

Long-distance remote control


Operation control from afar,
i.e., a distant control room, is
possible thanks to wiring of up
to 500m. (Group control and
control via 2 remote controls
possible)

Air Conditioner
Group control
possible
HRV
Up to 500m
Air conditioner remote control
Control via 2 remote controls

Control with 2 remote controls


(for HRV and air conditioner)
System with dual use of the
HRV remote control and air
conditioner remote control can
be achieved. Changes in initial
setting functions are always
possible.
(Group control possible)

page

Cyan Magenta Yellow Black

Air Conditioner
Group control
possible
HRV
Up to 500 m
Air conditioner remote control
HRV remote control

10

mov78452_epce02-20a Page 11

24-FEB-03

Centralised control
systems
By combining the centralised
control systems (available as
accessory) below, the user can
achieve a wide range of
comprehensive centralised
control systems for air
conditioning and ventilation.

DCS302B51

Centralised remote control

One unit can operate and monitor up to 64 groups (128 units) of


HRV and air conditioner units individually or in batch.
Allows the user to divide connected HRV or air conditioner units
into zones (up to 64) and control any or all of them.
Two units of this control can be linked, thereby allowing
centralised control of up to 128 groups (128 units).
Centralised control from two places is possible using two units of
this control.

DCS301B51

Unified ON/OFF control

One unit can turn ON/OFF up to 16 groups (128 units) of HRV


and air conditioner units individually or in a batch.
Lamps display operation and failure status of the connected HRV
and air conditioner units.
Up to 8 units can be linked to allow centralised control of up to
128 units.

DST301B51

Schedule timer

One unit can control the operation of up to 128 HRV and air
conditioner units on a weekly schedule.
Can set two ON/OFF operations per day for a period of one week.

Number of units that can be connected per system


Centralised remote control
Unified ON/OFF control
Schedule timer

page

Cyan Magenta Yellow Black

11

2 units
8 units
1 unit

mov78452_epce02-20a Page 12

24-FEB-03

Control
systems

Major HRV control systems

System
characteristics

INDEPENDENT
OPERATION
SIMULTANEOUS
OPERATION OF
MULTIPLE UNITS
STANDARD SYSTEM

HRV

Operation is possible using


2 HRV remote controls.
Multiple HRV units can be
simultaneously controlled in
batch.

Indoor unit

HRV remote control does not


have to be used.

HRV

Up to 16 VRV indoor units or


HRV units can be connected
and controlled in batch, with
interlocked operation of
HRVs and air conditioners by
using the air conditioner
remote control.

Air conditioner
remote control

Group 1

Indoor
unit

Air conditioner
remote control

Group 1

Indoor
unit

Air conditioner
remote control

HRV

page

12

HRV
remote
control

Main
remote control

Group 2

Indoor
unit

When one of the multiple


groups operates, HRVs are
interlocked and operate
simultaneously.

Air conditioner
remote control

Group 2

Air
conditioner
remote
control

Can control interlocked


operation of multiple groups
of VRV or Sky Air indoor
units.

Indoor
unit

Air conditioner
remote control

Wiring adapter
for electrical
appendices

Cyan Magenta Yellow Black

HRV
remote
control

HRV
remote control

Main
remote control

Necessary
accessories

Independent operation of
HRV is possible.

HRV

HRV

MULTIPLE GROUPS INTERLOCKED


OPERATION SYSTEM

AIR CONDITIONING INTERLOCKED CONTROL


VRV, SKY AIR SYSTEM

INDEPENDENT OPERATION SYSTEM

System construction

HRV

Air
conditioner
remote
control

mov78452_epce02-20a Page 13

24-FEB-03

Image of group
control system

Various control systems


according to applications
and conditions

BATCH/INDIVIDUAL CONTROL SYTEM

ON/OFF
control
HRV
Indoor
unit

Indoor
unit

HRV LCD
remote
control

Air conditioner
remote control

HRV
Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

HRV

Air conditioner
remote control
Indoor
unit

Indoor
unit

HRV

COMBINATION
WITH OTHER
TYPES OF
AIR CONDITIONERS

Cyan Magenta Yellow Black

HRV

Can connect to
multiple HRV units

Air conditioner
remote control

No-voltage a-contact signal


HRV
Adapter

Air conditioner
Air conditioner
remote control

page

13

Combined system
Independent
system

System
characteristics

Necessary
accessories

Up to 128 VRV, Sky Air and


HRV units can be centrally
controlled over a centralised
line (Special adapter is
required to connect the Sky
Air to the centralised line.)
HRV remote control can set
the individual operation of
each HRV unit.
Control system can be
expanded depending on its
purposes by combining a
variety of centralised control
equipment.

Unified ON/OFF
control, air
conditioner
remote control.
When necessary,
centralised remote
control, schedule
timer, HRV remote
control, and Sky Air
connection adapter

Centralised remote control


has setting and monitoring
functions equivalent to those
of a remote control and can
centrally control up to
128 VRV, Sky Air and HRV
units. (Special adapter is
required to connect the Sky
Air to the centralised line.)
Control is possible in three
different patterns:
individual/batch/zone.
Can independently operate
multiple HRV units.
System without air conditioner
and HRV remote controls can
be constructed.
Control system can be
expanded depending on its
purposes by combining a
variety of central control
equipment.

Unified ON/OFF
control, air
conditioner
remote control.
When necessary,
centralised remote
control, schedule
timer, HRV remote
control, and Sky Air
connection adapter

Simultaneous operation of
HRVs and air conditioners is
possible using the air
conditioner remote control.
Use of the HRV remote
control enables to change
settings or operate HRVs
independently.

Connection adapter
(No-voltage
a-contact signal)

HRV LCD
remote
control

Air conditioner
remote control

Centralised remote
control

ZONE CONTROL SYSTEM

AIR CONDITIONING INTERLOCKED CENTRALISED CONTROL SYSTEM

System construction

Combined
individual system

Connecting line
can be extended
up to 50m

mov78452_epce02-20a Page 14

24-FEB-03

M
Model
Line-up

VAM150FA7VE
50Hz, 220-240V
60Hz, 220V
Exchange efficiency
90 (%)

VAM150FAVE

Tem
pera
ture

exc

80

han
ge
effic
ienc
y

Ent
halp
ye
xch
ang
e
Ent
halp
ye
xch
ang

ee
ffic

Ultra-High

200

70

effic
ien
cy (h

eati
n

20m
60

g)

ien
cy
(co
olin
g)

VAM250FA7VE

15m

External static pressure (Pa)

High

50Hz, 220-240V
60Hz, 220V

150

Exchange efficiency

10m

90 (%)
100

VAM250FAVE

Tempe
rature
exchan
ge effic
iency
Enthal
py ex
chang
e effic
iency
(heatin
g)
Enthal
py exch
ange
efficie
ncy (c
ooling)

5m
50

100
Pipe
length

Low

0
50

100

150

200
250
Air flow rate (m3/h)

250

80

70

60

Ultra-High
200
External static pressure (Pa)

150
Pipe
length

High

150
40m
30m

100

50

20m

Low

10m
0
50

100

150

200

250

300
350
Air flow rate (m3/h)

VAM350FA7VE
50Hz, 220-240V
60Hz, 220V
Exchange efficiency

VAM350FAVE
Tem
pera

Enth

300

Ent
halp
y

alpy

exch
a

exc
han
ge

250

External static pressure (Pa)

ture

exch

nge

ang e

80
effic
ie

effic
ienc
y (h

effic
ienc
y

nc y

eatin
g)

70
30m
60

(coo
ling
)

Ultra-High

200

90 (%)
40m

VAM500FA7VE

50
20m

50Hz, 220-240V
60Hz, 220V

High

150

Exchange efficiency
400
100

90 (%)

10m

VAM500FAVE

150
Pipe
length

50
Low

Temp
eratu
re exch

350

Enth
a

icien

Enth

150

200

250
300
Air flow rate (m3/h)

250
External static pressure (Pa)

100

80

efficie
ncy

hang
e eff

300
0
50

ange

lpy e
xc

alpy
e

xcha
n

ge e

fficie

70
cy (h
eating)

ncy
(co

Ultra-High
200

60
oling

High

200
Pipe
length
50m

150

40m

100

30m
20m

Low
50

10m
0
100

page

Cyan Magenta Yellow Black

14

200

300

400

500

600
700
Air flow rate (m3/h)

mov78452_epce02-20a Page 15

24-FEB-03

VAM650FA5VE
50Hz, 220-240V
60Hz, 220V
Exchange efficiency
550

90 (%)
VAM650FAVE

Tempe
rature

500

Entha

450

Enth
a

exchan

lpy ex
chang

lpy e
xc

400

hang
e

ge effic

e effic
iency
(h

efficie
ncy (c

80

iency

70
eating)

60

oolin
g)

External static pressure (Pa)

350

VAM800FA5VE

50

Ultra-High

60m
300

High
50m
250
40m

200

30m

150

50Hz, 220-240V
60Hz, 220V

Low

Exchange efficiency

20m

100

90 (%)
VAM800FA(5)VE
Temp
eratu

400

hang
ee

100

fficie
ncy
Enth
alpy
exch
ange
Enth
effic
alpy
ienc
exch
y (hea
ang
ting)
e eff
icien
cy (c
oolin
g)
Ultra-High

500

External static pressure (Pa)

re exc

10m

50
80

200

300

400

500

600

700

800
900
Air flow rate (m3/h)

70

60

High
300

50

200

100m

VAM1000FA5VE

80m
Low

60m

100

50Hz, 220-240V
60Hz, 220V

40m

Exchange efficiency
90 (%)

20m
0
200

400

600

800

1000
Air flow rate (m3/h)

250
Pipe
length

VAM1000FA5VE
Tempe
rature
exchan
ge effic
iency
Enth
alpy
exch
ang e
effic
iency
(heatin
Enth
g)
alpy
exch
ang e
effic
iency
(coo
ling)

500

VAM1500FA5VE

400
External static pressure (Pa)

Enth

External static pressure (Pa)

Enth

alpy

60

100m
80m

200

60m

High

40m

Low

20m
0

VAM1500FA5VE
Tem
p

500

70

Exchange efficiency
90 (%)

700

600

80

Ultra-High

300

100

50Hz, 220-240V
60Hz, 220V

200
Pipe
length

400

600

800

1000

1200
3

eratu

alpy

exch

400

200

re ex

exch
a

a ng e

chan
g

ng e

Air flow rate (m /h)

80
e eff

icien

cy

effic
iency
(heatin
g

effic
iency
(c

250
Pipe
length

70
)

60
oolin

g)

50

300
Ultra-High

VAM2000FA5VE

200

High
100

50Hz, 220-240V
60Hz, 220V

Low

Exchange efficiency
90 (%)

0
500

1000

1500

2000

VAM2000FA5VE

2500

Air flow rate (m3/h)

Tempe
Entha

External static pressure (Pa)

500

Enth

alpy

rature

exch

ang e

80

exchan
ge effic
iency

lpy e
xcha
ng

e eff

effic

400

iciency
(h

iency

(coo

70

eating)
60

ling)

Ultra-High
50

300

200

High
100
Low

0
500

1000

1500

2000

2500

Air flow rate (m3/h)

page

Cyan Magenta Yellow Black

15

mov78452_epce02-20a Page 16

24-FEB-03

Dimensions

VAM150~500FA7VE
VAM650~1000FA5VE

Maintenance space for the heat


exchange element, air filters and fans
Maintenance cover

Supply air fan


Switch box

20

Fresh air
from outdoors
(Outdoor air)
OA

Supply
air to
room SA

EA
Exhaust
air to outdoors

67

150~250

600 or more

A
B

Celling hook
4-14x40 oval hole

Inspection
hole
450

20

RA
Return
air from
room

Damper plate
M

Exhaust air fan

Maintenance cover
J

K
L

Remark:
Be sure to provide the inspection
hole (450x450mm) to inspect
air filters, exchange elements and fans.

DIMENSIONS

VAM150FA7VE

Switch box

269 149 104 509 288 560 718

VAM250FA7VE
VAM350FA7VE

285 161 112 800 416 850 758

VAM500FA7VE
VAM650FA5VE
VAM800FA5VE

348 204 140

VAM1000FA5VE

852 421 902


1,140 568 1,190

page

Cyan Magenta Yellow Black

16

Heat exchange element

Air filters

H
145
132
132
84

J
760

89

97

120 124 164

146 200
812

137
912

121 263 153

197
196 250

988

246

263 146

264 157
379 189

mov78452_epce02-20a Page 17

24-FEB-03

VAM1500~2000FA5VE

Maintenance space for the heat exchange


element, air filters and fans
Maintenance cover

Switch box

EA
Exhaust air
to outdoors

380

140

Fresh air
from
outdoors
(Outdoor air)
OA

20

325

RA
Return air
from room

A
B

E
1186

Supply air
to room
SA

380
C

95

20

710
383

Celling hook
4-14x40 oval hole

Inspection
hole
450

200~300

600 or more

Supply air fan


(2 pieces)

912

Damper plate

Exhaust air fan


(2 pieces)
254

988

DIMENSIONS

VAM1500FA5VE

852 421 199 222 898

VAM2000FA5VE

1,140 568 315 253 1,186

page

Cyan Magenta Yellow Black

17

14.5

Remark:
Be sure to provide the
inspection hole (450x450mm)
to inspect air filters, exchange
elements and fans.

Air filters
Switch box

130

621

254

621
395
350
330

130

16.5

Maintenance cover
(Heat
exchange
element)

mov78452_epce02-20a Page 18

24-FEB-03

Specifications

Models
Temperature exchange efficiency (%)

Enthalpy exchange
efficiency (%)

for heating

for cooling

Power Supply
Sound pressure
level dB(A)

VAM-FA7VE
250
350

150

Heat exchange
mode
Bypass mode

External static
pressure (Pa)

74
74
79
64
64
69
58
58
64

72
72
77
64
64
68
58
58
62

27-28.5
26-27.5
20.5-21.5
27-28.5
26.5-27.5
20.5-21.5

28-29
26-27
21-22
28-29
27-28
21-22

mm
kg

ultra-high

kW
mm

page

Cyan Magenta Yellow Black

18

150
150
110
69
39
20

250
250
155
64
39
20
0.030 x 2

100

650

800

74
74
74
74
74
74
77
77
76
62
63
65
62
63
65
67
66
67
58
58
60
58
58
60
63
63
62
1 ~, 220~240V, 50Hz
32-34
33-34.5
34.5-35.5
36-37
31.5-33
31.5-33
33-34
34.5-36
23.5-26
24.5-26.5
27-28
31-32
32-34
33.5-34.5
34.5-35.5
36-37
31-32.5
32.5-33.5
34-35
34.5-36
24.5-26.5
25.5-27.5
27-28.5
31-33
galvanised steel plate
self-extinguishable urethane foam
285 x 812 x 800
348 x 988 x 852

24

high
low
ultra-high
high
low

Motor Output
Connection Duct Diameter
Unit ambient condition

75
75
80
65
65
70
61
61
67

269 x 760 x 509

VAM-FA

Casing
Insulation Material
Dimensions
HxWxD
Weight
Heat Exchange System
Heat Exchange Element Material
Air Filter
Fan
Type
Air Flow
Rate (m3/h)

ultra-high
high
low
ultra-high
high
low
ultra-high
high
low
VE
ultra-high
high
low
ultra-high
high
low

500

150

VAM-FA5VE
1000
1500

2000

75
75
76.5
66
66
68
61
61
63

75
75
78
66
66
68
61
61
64

75
75
78
66
66
70
61
61
66

36-37
35-36
31-32
36-37
35.5-36
31-32

39.5-41.5
38-39
34-36
40.5-41.5
38-39
33.5-36

40-42.5
38-41
35-37
40-42.5
38-41
35-37

348x988x1,140 710x1,498x852 710x1,498x1,140


33
48
61
132
158
air to air cross flow total heat (sensible heat + latent heat) exchange
specially processed nonflammable paper
multidirectional fibrous fleeces
sirroco fan
350
500
650
800
1,000
1,500
2,000
350
500
650
800
1,000
1,500
2,000
230
350
500
670
870
1,200
1,400
98
98
93
137
157
137
137
70
54
39
98
98
98
78
25
25
25
49
78
49
59
0.090 x 2
0.140 x 2
0.230 x 2
0.230 x 4
200
250
350
-15C ~ +50CDB, 80% RH or less

Notes: Air flow rate can be changed over to Low mode or High mode.
Sound pressure level is measured at 1.5m below the center of the body.
Sound pressure level is measured in an anechoic chamber.
Sound pressure levels generally become greater than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound pressure level at the air discharge port is about 8dB higher than the unit's sound level.
Even when the outdoor temperature is below -15C, the system is operable down to -20C with the pre-heater installed at the outdoor air intake side.

mov78452_epce02-20a Page 19

24-FEB-03

Accessories
Air suction/discharge grille (accessory)

Installation of
accessories

Flexible duct
(Accessory)
High efficiency filter
(Accessory)

RA
SA

Round hood
(Field supply)

Branch duct
(Field supply)
Silencer ( Accessory)

SA

Duct
(Field supply)
Thermal insulation material
(Field supply)

EA

OA

List of
accessories

HRV remote control

VAM-FA7VE
250
350

Model
Item

150

PC Board Adapter

Controlling device

HRV remote control


CentralIsed control
system

Centralised remote control


Unified ON/OFF control
Schedule timer
Wiring adapter for electrical appendices
For humidifier
Installation box for adapter PCB
For heater control kit
For wiring
VRV indoor unit
reference
Installation box for adapter PCB*

FXYCP
KRP1B61*
KRP1B96 *2, 3
Notes:

page

Cyan Magenta Yellow Black

19

FXK
KRP1B61

Centralised remote control

500

650

Unified ON/OFF control

800

VAM-FA5VE
1000
1500

BRC301B61
DCS302B51
DCS301B51
DST301B51
KRP2A61
KRP50-2
KRP50-2A90 (mounted electric component assembly of HRV)
BRP4A50
FXYFP
FXYSP
FXH
FXYAP/FXA
FXL
KRP1B59*
KRP1B61
KRP1B3
KRP1D98*4

KRP1B93*3

*1 Installation box is necessary for each adapter marked with *.


*2 Up to 2 adapters can be fixed per installation box.
*3 Only 1 installation box can be installed per indoor unit.
*4 Up to 2 installation boxes can be installed per indoor unit.

Schedule timer

FXN
KRP1B61

2000

FXM

mov78452_epce02-20a Page 20

24-FEB-03

Silencer

VAM-FA7VE
250
350

Model
Additional function

Item
Silencer

150
reference
nominal pipe (mm)
white
nominal pipe (mm)

Air suction/discharge grille


(Noise suppression type)

Air suction /
Discharge grille
High efficiency filter
Replacement for high efficiency filter
Flexible duct (1m)
Flexible duct (2m)
Duct adapter
reference
nominal pipe (mm)
Direct expansion
reference
coil unit
discharge adapter

K-DGL100A
100
YAFM323F15
YAFF323F15
K-FDS101C
K-FDS102C

K-DGL150A
150
YAFM323F25
YAFM323F35
YAFF323F25
YAFF323F35
K-FDS151C
K-FDS152C

500

Flexible duct
(Noise suppression type)

650

KDDM24A50
200
K-DGL200A
200
YAFM323F50
YAFF323F50
K-FDS201C
K-FDS202C

BHDM50AJVE
KDAJ25K36

800

VAM-FA5VE
1000
1500

KDDM24A100

YAFM323F65
YAFF323F65

BHDM80AJVE
KDAJ25K56

Duct adapter

2000

KDDM24A100X2
250
K-DGL250A
250
YAFM323F100 YAFM323F65X2 YAFM323F100X2
YAFF323F100 YAFF323F65X2 YAFF323F100X2
K-FDS251C
K-FDS252C
YDFA25A1
250
BHDM100AJVE

PC board adapter for heater control kit


(BRP4A50)
When the installation of an electric heater is required in a cold
region, this adapter with an internal timer function eliminates
the complicated timer connecting work that was necessary with
conventional heaters.

INDOOR

RA

OUTDOOR

EA
HRV

SA

BRP4A50
Temperature thermostat. (field supply)
(OFF when the temperature is at or more than 5C)

Heater
control kit
(field supply)

OA
Temperature thermostat
(field supply)
(ON when the temperature
is at or below -10C)

Power supply (field supply)


Relay box

Notes when installing


Examine fully an installation place and specification for using the electric heater based on the standard and regulations of each country.
Supply the electric heater and safety production devices such as a relay and a thermostat, etc of which qualities satisfy the standard and
regulation of each country at site.
Use a non-inflammable connecting duct to the electric heater. Be sure to allow 2m or more between the electric heater and HRV for safety.
For the HRV units, use a different power supply from that of the electric heater and install a circuit breaker for each of them.

page

Cyan Magenta Yellow Black

20

mov78452_epce02-20a Page 21

24-FEB-03

Direct expansion coil unit (BHDM50~100AJVE)


for R-407C system
The direct expansion coil functions to heat or cool the supply air out
from HRV to make the outlet air temperature nearer to the room
temperature for maintaining the comfort.

OUTDOOR

INDOOR

RA

EA
HRV

SA

BHDM

OA

Connection with
VRV system
HRV remote
control

Air conditioner
remote control

Notes:
Be sure to interlock HRV and BHDM in the same group by using an air conditioner remote control.
All system operations other than air flow rate switching can be controlled using the air conditioner remote control. To switch the air flow rate,
please use the HRV remote control.

Specifications :
direct expansion coil unit
BHDM-AJVE

50

Capacity index
Power supply
Cooling capacity *1
Heating capacity *2

25

Casing/colour
Dimensions
Air flow rate range
Weight
Piping
connection

Flare
connection

HxWxD

liquid
gas
drain

kW
kW

2.8 (3.0*)
3.2 (3.2*)

mm
m3/h

300 x 550 x 800


330~600
24

kg
mm
mm
mm

80
40
1 ~, 220~240V / 220V, 50Hz/60Hz
4.5 (4.8*)
5.0 (5.0*)
galvanised steel plate
300 x 700 x 800
480~780
25
6.4
12.7
VP25 (external diameter 32, internal diameter 25)
R-407C

Refrigerant *3

100
50
5.6 (6.1*)
6.3 (6.3*)

540~930
9.5
15.9

Notes
*1. Nominal cooling capacities are based on:
indoor temperature: 27CDB, 19CWB outdoor temperature: 35CDB equivalent refrigeratn piping: 5m (horizontal)
*2. Nominal heating capacities are based on: indoor temperature: 20CDB outdoor temperature: 7CDB, 6CWB equivalent refrigerant piping: 5m (horizontal)
Cooling and Heating capacities marked with * are in case of connecting HRV unit.
Cooling capacities are based on:
Indoor temperature: 27CDB, 50RH% Outdoor temperature: 35CDB, 60RH% Equivalent ref. piping: 5m (horizontal)
HRV performance :
Temperature exchange efficiency: 74% Enthalpy exchange efficiency: 58%
Heating capacities are based on:
Indoor temperature: 20CDB, 40RH% Outdoor temperature: 7CDB, 70RH% Equivalent ref. piping: 5m (horizontal)
HRV performance :
Temperature exchange efficiency: 74% Enthalpy exchange efficiency: 62%
*3. R-22 compatible models can be manufactured on request

page

Cyan Magenta Yellow Black

21

mov78452_epce02-20a Page 22

24-FEB-03

DIMENSIONS: direct expansion coil unit


suspension position
A

suspension position 630

9
150

9
10

27

YVIEW
145

67

150
200

135

300
245
215
150

5
Y

G
H

4-M8~10

65

How to connect wirings:


Loosen the screw and open the bottom
plate, open the switch box lid.

800
440
315

135 120

60
50

25

suspension
C

2X65=130

4-screw

bottom plate

57

E
F

service space

1.

2.

3.
4.

DIMENSIONS

A
600

BHDM80AJVE

750

BHDM100AJVE

page

4
300 or more
required installation space

11

BHDM50AJVE

ZVIEW

46

300 or more

XVIEW

Cyan Magenta Yellow Black

45

22

B
4x65=
260
6x65=
390

5.
6.
7.
8.

Power wiring port


Drain hole: VP5 (O.D. 32, I.D. 25)
Discharge flange
Suction flange
(BHDM50,80AJVE: 200, BHDM100AJVE: 250)
9.
Switch box
10. Inspection hole (450x450)
11. Bottom plate

Liquid pipe connection


(BHDM50,80AJVE: 6.4 flare connection)
(BHDM100AJVE: 9.5 flare connection)
Gas pipe connection
(BHDM50,80AJVE: 12.7 flare connection)
(BHDM100AJVE: 15.9 flare connection)
Drain pipe connection:
VP25 (O.D. 32, I.D. 25)
Interunit wiring port

550

310

700

460

E
2x150=
300
3x150=
450

F
335
485

197

89

137

89

246 263

mov78452_epce02-20a Page 23

Cyan Magenta Yellow Black

24-FEB-03

mov78452_epce02-20a Page 24

24-FEB-03

Daikin Europe N.V. is approved by LRQA for


its Quality Management System in accordance
with the ISO9001 standard.
ISO9001 pertains to quality assurance regarding
design, development, manufacturing as well as
to services related to the product.

Daikin units comply with the European regulations


that guarantee the safety of the product.

ISO14001 assures an effective environmental


management system in order to help protect
human health and the environment from the
potential impact of our activities, products and
services and to assist in maintaining and
improving the quality of the environment.

VRV products are not within the scope of


the Eurovent certification programme

Daikin products are distributed by:

Zandvoordestraat 300
B-8400 Oostende, Belgium
Internet: http://www.daikineurope.com

Cyan Magenta Yellow Black

EPCE02-02A / 700 / 02/03 La Movida


Printed on non-chlorinated paper / Printed in Belgium

Specifications are subject to change without


prior notice