Professional Documents
Culture Documents
Summary
There are basically 3 coupler configurations
2 CTs, overlap
2 CTs, differential
Single CT
The REB500 has for each configuration an appropriate solution. Details are written in chapter 3.
Table underneath shows the solutions available in REB500 for handling Busbar Faults between TieBreaker and the related CT.
CT Configuration
Cost
Clearing Time
Zones Lost
2 CTs,overlap
Fast
2 CTs,differential
Slow
1, selective
Single CT
Slow
2. Conclusion
The REB500 can handle all types of Tie-Breaker configurations. In order to achieve the optimal
settings, it is recommended to check the datasheet of the Tie_Breaker involved.
As indicated in
Minimum treclaim for a circuit-breaker operating time (tCB) of 40 ms
treclaim > tCB + tv + tmargin = 40 ms + 19 ms + 20 ms > 79 ms.
This can be achieved by setting the related parameter Recovery time (bus-tie breaker) in the REB500 parameter
setting.
Telefon:
+41 (0)58 585 77 44
Telefax:
+41 (0)58 585 55 77
http://www.abb.ch
3. Coupler configurations
3.1 Coupler with 2 CTs, overlapping zones
ZONE 1
ZONE 2
CT2
CT3
CB1
CT1
CB4
CT4
1. The above diagram shows two CTs across the Bus-Section breaker (CT2 & CT3). In conventional
bus bar schemes zone 1 (between CT1 & CT2) would include in its protection zone CT3 and for
zone 2 (between CT1 & CT3) would include CT2 in its protection zone. Since both bays are
connected to the busbar with the sectionaliser and if the bus-section breaker is closed, the
following happens:
All bays in zone 1 and 2 will trip without a time delay since they are all connected to the BusSection i.e. the breaker is closed at the time of the fault.
2. If the bus-section breaker is open at the time when the fault occurs, only zone 1 will trip. This is
because the coupler breaker is open and the associated coupler measurements are blocked after
the reclaim time of the related breaker.
Summarized
Advantage
Disadvantage
In the following solution, the circuit breaker is connected to both Bay Units and a virtual bussection zone between the coupler CTs is configured.
ZONE 1
BUS-SECTION ZONE
CT2
ZONE 2
CT3
CB1
CT1
CB4
CT4
Note: The software will image two coupler CBs out of the one coupler CB.
This brings the following advantage as we can define now an additional protected zone, indicated in
green.
1. In case the breaker is closed, this protection zone (green) will trip in case of a fault between the two
CTs. Now in order to guarantee that the arcing has ceased, the measurement of the related CT2 is
taken out of the measurement, after the reclaim time has expired. After that zone1 will see a fault
and clear the fault. This reclaim time can be selected in the REB500 setting tool.
2. In case the breaker is open, both CT measurements CT2 and CT3 are already taken out of the
BBP measurement and a fault between Breaker and CT is cleared immediately selective
Advantage
Disadvantage
In case of a fault between closed Breaker and CTs, fault clearance Fault can
only be cleared after the breaker opened, and it is guaranteed that the arcing
has ceased
Two Bay Units are required
ZONE 2
CT3
CB1
CT1
CB4
CT4
1. In case the breaker is closed, and fault is located between CT and Breaker, zone 2 will trip
immediately. Now in order to guarantee that the arcing has ceased, the measurement of the related
CT3 is taken out of the measurement, after the reclaim time has expired. After that zone1 will see a
fault and clear the fault. This reclaim time can be selected in the REB500 setting tool.
2. In case the breaker is open, both CT measurements CT3 and CT1 are taken out of the BBP
measurement and a fault between Breaker and CT is cleared immediately selective
Advantage
Disadvantage