REF 610
REF 610
1MRS 755574
Issued: 16.02.2005
Status: edited from 1MRS755431 (B)
Version: A/31.03.2005
Data subject to change without notice
Features
Disturbance recorder
- recording time up to 80 seconds
- triggering by one or several internal or
digital input signals
- records four analog channels and up to
eight user-selectable digital channels
- adjustable sampling rate
Non-volatile memory for
- up to 100 event codes with time stamp
- setting values
- disturbance recorder data
- recorded data of the five last events with
time stamp
- number of AR shots and pickups/trips
for protection elements
- target messages and LEDs showing the
status at the moment of power failure
HMI with an alphanumeric LCD and
manoeuvring buttons
- eight programmable LEDs
Multi-language support
Demand values
REF 610
1MRS 755574
Application
REF 610 is a versatile multifunction protection relay mainly designed for protection of
incoming and outgoing feeders in MV distribution substations. REF 610 can also be used
as back-up protection for motors, transformers and generators, in industrial as well as in
utility applications.
The large number of integrated protection
functions, including three-element overcurrent protection, two-element, non-directional
ground-fault protection as well as thermal
Design
REF 610 is based on a microprocessor environment. A self-supervision system continuously monitors the operation of the relay.
The HMI includes a Liquid Crystal Display
(LCD) which makes the local use of the relay
safe and easy.
Local control of the relay via serial communication can be carried out with a computer
connected to the front communication port.
Remote control can be carried out via the rear
connector connected to the control and monitoring system through the serial communication bus.
protection, makes REF 610 a complete protection against overcurrent and ground faults.
The optional arc protection for detection of
arc situations in air insulated metal-clad
switchgears and the auto-reclose function for
automatic clearing of overhead line faults
increase the range of applications further.
The large number of digital inputs and output
contacts allows a wide range of applications.
Auxiliary voltage
REF 610
1MRS 755574
Technical data
Protection functions
Element 51P
Element 50P-1
Element 50P-2
Operation accuracy
0.3...0.5 x In (CT)
0.5...5.0 x In (CT)
5.0...35.0 x In (CT)
1)
2)
55 ms
30 ms
30 ms
0.05...300 s
0.04...300 s
0.04...300 s
50 ms 2)
30 ms
0.05...2.50 s
50 ms
50 ms
30 ms
30 ms
0.96
0.96
0.96
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
0.05...1.00
RI-type inverse
0.05...1.00
Extremely inverse
Very inverse
Moderately inverse
1...15
2% of the set
2% of the set
2% of the set
operate time or 25 operate time or 25 operate time or 25
ms
ms
ms
5
7% of the
calculated operate
time
7% of the
calculated operate
time
5% of the set
pickup value or
0.05% In
3% of the set
pickup value
3% of the set
pickup value
3% of the set
pickup value
3% of the set
pickup value
3% of the set
pickup value
At IDMT (mode) characteristic, the relay allows settings above 2.5 x In for element 51P, but regards any
setting >2.5 x In (CT) as equal to 2.5x In (CT).
Resetting time of the trip signal.
5
REF 610
1MRS 755574
Element 51N
1.0...40% In (CT)1)
60 ms
40 ms
0.05...300 s
0.04...300 s
Operation accuracy
1.0...10.0% In (CT)
10.0...100% In (CT)
100...400% In (CT)
1)
2)
Element 50N
Extremely inverse
Very inverse
Normal inverse
Long-time inverse
0.05...1.00
RI-type inverse
0.05...1.00
Extremely inverse
Very inverse
Moderately
inverse
1...15
50 ms 2)
30 ms
0.05...2.50 s
50 ms
0.96
0.96
2% of the set
operate time or
25 ms
5
2% of the set
operate time or
25 ms
30 ms
7% of the
calculated operate
time
7% of the
calculated operate
time
5% of the set
pickup value or
0.05% In
5% of the set
pickup value or
0.05% In
3% of the set
pickup value
3% of the set
pickup value
3% of the set
pickup value
At IDMT (mode) characteristic, the relay allows settings above 0.4 x In (CT) for element 51N,
but regards any setting >0.4 x In (CT) as equal to 0.4 x In (CT).
Resetting time of the trip signal.
REF 610
1MRS 755574
Value
0.30...1.50 x In (CT)
50...100%
100%
Time constant,
1...200 min
Table 4: Element 46
Feature
Value
10...100%
100 ms
1...300 s
70 ms
0.90
2% of the set
operate time or 25
ms
Operation accuracy
10...100%
3% of the set
pickup value and 1
unit
Value
Element ARC
Set current limit
Arc 50P
0.5...35.0 x In (CT)
Arc 50N
5.0...400% In (CT)
Operate time
< 15 ms 1)
30 ms
7% of the set pickup
value
Resetting time
Operation accuracy
L>
Activation time of L>
Resetting time
1)
< 15 ms
20 ms
REF 610
1MRS 755574
ArcSensitREF610_a
Fig. 6
Value
Number of shots
CB Closing time
pickup delay of element 51P
pickuppickup delay of element 51N
Reset time
Cutout time
Open time of shot 1
Open time of shot 2
Open time of shot 3
Operate time accuracy
0...3
0.1...10 s
0...300 s
0...300 s
3...300 s
0.1...300 s
0.1...300 s
0.1...300 s
0.1...300 s
2% of the set time and
25 ms
Table 8: CBFP
Feature
Value
0.10...60.0 s
0.08/0.04 x In (CT)
REF 610
1MRS 755574
Technical data
Table 9: Dimensions
Width
Height
Depth
case 149.3 mm
~3.5 kg
~1.8 kg
164
160
177 (4U)
149.3
180.1
Fig. 1
30.8
Dimensions_a
177
85...110% of Ur (ac)
80...120% of Ur (dc)
80...120% of Ur (dc
<9 W/13 W
<350 ms
+100C (~212 F)
Fuse type
T2A/250 V
Rated frequency
Rated current, In
0.2 A
1.5 A
4A
20 A
for 1 s
20 A
100 A
500 A
for 10 s
5A
25 A
100 A
1A
5A
50 A
250 A
1250 A
<750 m
<100 m
<20 m
9
REF 610
1MRS 755574
0...50 x In
0...8 x In
Rated voltage
DI1...DI2 REF610xxxHxxx
110/125/220/250 V dc
DI1...DI2 REF610xxxLxxx
24/48/60/110/125/220/250 V dc
110/125/220/250 V dc
24/48/60/110/125/220/250 V dc
Current drain
2...18 mA
Power consumption/input
<0.9 W
Table 14: Non-trip output SO1 and optional SO4 and SO5
Rated voltage
250 V ac/dc
Continuous carry
5A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V dc
1 A/0.25 A/0.15 A
5 A/3 A/1 A for series connection of
SO4 and SO5
100 mA at 24 V ac/dc
Table 15: Non-trip output SO2, optional SO3 and IRF output
Rated voltage
250 V ac/dc
Continuous carry
5A
10 A
15 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V dc
1 A/0.25 A/0.15 A
100 mA at 24 V ac/dc
10
Rated voltage
250 V ac
Continuous carry
5A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at 48/110/220 V dc (PO1 with both
contacts connected in series)
5 A/3 A/1 A
100 mA at 24 V ac/dc
TCS
Control voltage range
20...265 V ac/dc
~1.5 mA
20 V ac/dc (15...20 V)
REF 610
1MRS 755574
Table 17: Lens sensor and optic fibre for arc protection
Normal service temperature range
-40oC...+100oC (~-40...~212F)
+140oC (~284F)
100 mm (~4)
IP 54 (NEMA 35)
-10...+55C (~-14...~131F)
-40...+70C (~-40...~158F)
-40...+85C according to
IEC 60068-2-48
Differential mode
1.0 kV
8 kV
15 kV
2.5 kV
Radiated, amplitude-modulated
Radiated, pulse-modulated
4 kV
2 kV
I/O ports
2 kV, line-to-ground
1 kV, line-to-line
11
REF 610
1MRS 755574
Radiated RF-emission
CE approval
Mechanical tests
Vibration tests (sinusoidal)
12
X5.1
Light sensor 1
Light sensor 2
X5.2
8 1
2 3
4 5
Fig. 2
18
19
16
17
20
8
10
6
7
1
2
3
4
5
18
19
16
17
20
8
10
6
7
1
2
3
4
5
8
10
6
7
1
2
3
4
5
15
15
15
18
19
16
17
20
14
14
14
13
13
13
12
12
12
11
SGB4
11
11
DI3
2
SGB3
DI4
4
SGB5
DI5
6
Optional
X3.1
X4.1
52a
DI1
DI2
SGB2
3
4
5
7
1
2
8
10
6
18
19
16
17
20
15
14
13
12
11
3
4
5
7
1
2
8
10
6
18
19
16
17
20
15
14
13
12
11
SGB1
23 24
52b
21 22
51P
SGF1...SGF5
SGL1...SGL8
IRF
Alarm
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
Pickup
Trip
Warning
IRF
3 4 5
Trip
Trip lockout
External Trip
Open CB Command
Close CB Command
CB Reclosing Failed
Shot Due
Definite Trip Alarm
AR Lockout
Indications cleared
Output contacts unlatched
Memorized values cleared
Setting group selection
Time sync
External Triggering
CB FAIL
External Triggering
Reset
External trip
Trip lockout
CB Position Open
CB Position Closed
AR Disable
CB Close Disable
External AR Initiation
79
External Arc
Arc 51P/51N
49
Blocking
46
Blocking
50N
Blocking
51N
50P-2
Blocking
50P-1
Blocking
(dc/ac)
Self-supervision
(dc/ac)
Uaux
SO1
SO2
PO3
15
16
17
19
20
18
21
23
22
13
14
15
16
17
19
20
18
21
23
22
13
14
11
12
15
16
17
19
20
18
21
23
22
13
14
11
12
9
10
9
10
9
10
11
12
7
8
5
6
3
4
1
2
SGR3
12 13
7
8
5
6
3
4
1
2
SGR4
9 10 11
7
8
5
6
3
4
1
2
SGR5
6 7 8
52
cs
c
15
16
17
19
20
18
21
23
22
13
14
11
12
9
10
7
8
5
6
3
4
1
2
SGR2
14 15
PO2
CLOSE
52b
PO1
15
16
17
19
20
18
21
23
22
13
14
11
12
9
10
7
8
5
6
3
4
1
2
SGR1
16 17 18 19
16 17 18
SO5
cs
T
15
16
17
19
20
18
21
23
22
13
14
11
12
9
10
7
8
5
6
3
4
1
2
SGR8
Optional
52
TC
52A
SO4
SO3
15
16
17
19
20
18
21
23
22
13
14
11
12
9
10
7
8
5
6
3
4
1
2
SGR6
22 23 24 X3.1
ConnDiagr1REF610_ANSI_a
15
16
17
19
20
18
21
23
22
13
14
11
12
9
10
7
8
5
6
3
4
1
2
SGR7
19 20 21
Connection diagram
Optional
X2.1
L1
L2
L3
REF 610
Example connection
13
REF 610
1MRS 755574
Ordering
Quantity
REF610B55HCNP XX
Language set:
Power supply:
Ground-fault current
input:
Phase-current inputs:
OrdInfo1REF610_ANSI_b
Revision
Fig. 3
HMI language set numbers, and corresponding terminology and languages included, are
described in Table 15:
Table 23: HMI language codes
Language set number
Terminology
Languages
11
ANSI
Power supply:
Ground-fault current
input:
Phase-current inputs:
Revision
Fig. 4
14
OrdInfo2REF610_ANSI_b
REF610B55HSNS
REF 610
1MRS 755574
Order number
References
25o)
1MRS050696
1MRS050831
1MRS050697
1MRS050695
1MRS050694
1MRS050783
1MRS061208
1MRS061207
1MRS120534-1.5
3 m 3%
1MRS120534-3.0
5 m 3%
1MRS120534-5.0
1MRS050698
Available manuals:
Item
Order number
1MRS 755535
1MRS 755539
Installation Manual
The following tool versions are needed to support the new functions and features of REF
610 release B:
CAP 501 Relay Setting Tool
15
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa, FINLAND
Tel +358 10 22 11
Fax +358 10 224 1094
www.abb.com/substationautomation